Home
LPC2 DO6 User Manual
Contents
1. SMARTEH LIVING SYSTEMS USER MANUAL Longo programmable controller LPC 2 D06 module Version 8 SMARTEH d o o Trg tigrovcev 1 5220 Tolmin Slovenia Tel 386 0 388 44 00 e mail info smarteh si www smarteh si Longo programmable controller LPC 2 D06 module SMARTEH LIVING SYSTEMS Written by SMARTEH d o o Copyright 2005 2012 SMARTEH d o o User Manual Document Version 008 July 1 2012 a Longo programmable controller LPC 2 D06 module SMARTER LIVING SYSTEMS STANDARDS AND PROVISIONS Standards recommendations regulations and provisions of the country in which the devices will operate must be considered while planning and setting up electrical devices Work on 230 VAC network is allowed for authorized personnel only DANGER WARNINGS Devices or modules must be protected from moisture dirt and damage during transport storing and operation WARRANTY CONDITIONS For all modules LONGO LPC 2 if no modifications are performed upon and are correctly connected by authorized personnel in consideration of maximum allowed connecting power we offer warranty for 24 months from date of sale to end buyer In case of claims within warranty time which are based on material malfunctions the producer offers free replacement The method of return of malfunctioned module together with description can be arranged with our authorized representative Warranty does not in
2. Over voltage category II Electrical equipment Class II double insulation Protection class IP 30 NOTE Inductive loads are influencing the relay contacts by shortening their working life period It is recommended to use standard suppression circuits or in worse cases use another type of digital output e g triac 2 This specification is valid only for products with serial number within 564 593 and all greater than 865 For products with different serial No specification are AC 230V 0 5A DC 30V 1A i Longo programmable controller LPC 2 D06 module 5 CHANGES The following table describes all the changes to the document SMARTTEH LIVING SYSTEMS Date V Description 1 7 2012 008 CGP General update and technical data update 11 5 2010 007 Updated warranty permanence 19 12 2009 006 Changed specification for the max switching capability 13 6 2007 005 improved output functioning in heavier conditions noise inductive loads 23 2 2006 004 Added output isolation description Added output protection type description Pollution degree changed to 2 30 6 2005 003 The initial version issues as LPC 2 D06 module UserManual a Longo programmable controller LPC 2 D06 module SMARTER LIVING SYSTEMS 6 NOTES
3. EE E A O E E E AE EE E ne 2 SINS TAHAT ON a E E EE E 3 3 1 Connection SCMEING een a ae en des Dane eue ans 3 3 2 Mounting INS TUCEIONS 5 522 522 aes scene secs senoebseemeccsssessoec 5 D MOULE NA DCUING oarriero EEEE E outer ER EE ENN 7 4 TECHNICAL SPECIFICATIONS Se aan ee mm ee AS 8 CHANGES a ae ese 9 GINO TES a ee 10 3 jii lt Longo programmable controller LPC 2 D06 module SMARTITEH iy LIVING SYSTEMS 1 DESCRIPTION LPC 2 D06 is an eight relay digital output module with make contacts NO It can be used in a wide range of applications but is not suitable to be use with heavy inductive loads reflectors contractors motors etc While using inductive loads it is recommended to use standard suppression circuits or in worse cases use another type of digital output e g triac module like LPC 2 D09 LEDs indicate each relays contacts state If a LED is on the modules connection pins for the correspondent relay are shorted refer to the Table 5 Module is powered from internal BUS NOTE For proper system configuration and data allocation please refer to LPC Composer software help menu a Longo programmable controller LPC 2 D06 module SMARTER LIVING SYSTEMS 2 FEATURES Figure 1 LPC 2 D06 module Table 1 Technical data Eight relay digital output with make contacts NO Flexible output for wide use of operation Standard DIN EN50022 35 rail mounting
4. Label 1 description 1 LPC 2 MC3 is the full product name 2 P N 225MC3040001001 is the part number 225 general code for product family MC3 short product name 04001 sequence code 04 year of code opening 001 derivation code 001 version code reserved for future HW and or SW firmware upgrades 3 D C 16 05 is the date code 16 week and 05 year of production Label 2 description 1 S N MC3 S9 0500000190 is the serial number MC3 short product name S9 user code test procedure e g Smarteh person xxx 0500000190 year and current stack code 05 year last two cyphers 00000190 current stack number previous module would have the stack number 00000189 and the next one 00000191 a Longo programmable controller LPC 2 D06 module SMARTER LIVING SYSTEMS 4 TECHNICAL SPECIFICATIONS Table 6 Technical specifications Power supply from internal BUS Power consumption 2 5 W Output ns tole aa NO Max switching power per channel AC 230 V 3A resistive load DC 48 V 1A 30 V 3A Min permitted load per channel 100 mA at 5 VDC noie screw type connector for stranded wire 0 75 to 2 5mm Dimensions L x W x H 90 x 53 x 60 mm Weight 140 g Ambient temperature Oto 50 C Ambient humidity max 95 no condensation Maximum altitude 2000 m Mounting position vertical Transport and storage temperature 20 to 60 C Pollution degree 2
5. Longo programmable controller LPC 2 D06 module SMARTERH LIVING SYSTEMS 3 INSTALLATION 3 1 Connection scheme Figure 2 Connection scheme LOAD EE EH LEDS LED8 K2 11 12113 14 Ne OUT6 OUT7 LPC 2 D06 Relay OUT 15 16 es OUT8 OUT2 OUT3 OUT4 Se 3 2S 67 8 EE HN LED1 LED4 U LOAD Table 2 OUT ee Voltage free contacts Make contacts NO o Voltage free contacts Make contacts NO o Voltage free contacts Make contacts NO A Voltage free contacts Make contacts NO ee Voltage free contacts Make contacts NO 1 Wires connected to the module must have cross sectional area at least 0 75 mm Minimum temperature rating of wire insulation must be 85 C ae oF Longo programmable controller LPC 2 D06 module Table 2 OUT SMARTTEH LIVING SYSTEMS OUT6 11 OUT6 12 Voltage free contacts Make contacts NO OUT7 13 OUT7 14 Voltage free contacts Make contacts NO OUT8 15 OUTS 16 Voltage free contacts Make contacts NO Table 3 K1 Internal BUS Data amp DC power supply Connection to I O module Table 4 K2 Internal BUS Data amp DC power supply Connection to I O module Table 5 LED1 LED8 Status Digital output state On Output voltage present between OUT1 1 to OUT1 2 up to Output voltage present between OUT8 15 to OUT8 16 Off Output voltage not present between OUT1 1 to OUT1 2 up t
6. clude damage due to transport or because of unconsidered corresponding regulations of the country where the module is installed This device must be connected properly by the provided connection scheme in this manual Misconnections may result in device damage fire or personal injury Hazardous voltage in the device can cause electric shock and may result in personal injury or death NEVER SERVICE THIS PRODUCT YOURSELF This device must not be installed in the systems critical for life e g medical devices aircrafts etc If the device is used in a manner not specified by the manufacturer the degree of protection provided by the equipment may be impaired ST Waste electrical and electronic equipment WEEE must be collected separately LONGO LPC 2 complies to the following standards e EMC EN 61000 6 2 EN 50082 EN 61000 6 4 EN 50081 e LVD IEC 61131 2 e Vibrations and climatic mechanical EN 60068 2 6 EN 60068 2 27 EN 60068 2 29 Smarteh d o o operates a policy of continuous development Therefore we reserve the right to make changes and improvements to any of the products described in this manual without any prior notice MANUFACTURER SMARTEH d o o Trg tigrovcev 1 5220 Tolmin Slovenia _ Longo programmable controller LPC 2 D06 module SMARTEH Index Longo programmable LIVING SYSTEMS controller LPC 2 D06 module T DESCRIPTION correer irren E E S E E A E E AE OE 1 L FEATURE uana
7. o Output voltage not present between OUT8 15 to OUT8 16 a Longo programmable controller LPC 2 D06 module SMARTER LIVING SYSTEMS 3 2 Mounting instructions Figure 3 Housing dimensions 90 95 e Dimensions in millimeters EXTERNAL SWITCH OR CIRCUIT BREAKER AND EXTERNAL OVERCURRENT PROTECTION The unit is allowed to be connected to installation with over current protection that has nominal value of 16 A or less RECOMMENDATION ON SWITCH OR CIRCUIT BREAKER PROTECTION There should be two poles main switch in the installation in order to switch off the unit The switch should meet the requirements of standard IEC60947 and have a nominal value at least 6 A The switch or circuit breaker should be within easy reach of the operator It should be marked as the disconnecting device for the equipment All connections module attachments and assembling must be done while module is not connected to the main power supply Longo programmable controller LPC 2 D06 module SMARTER LIVING SYSTEMS Mounting instructions 1 Switch OFF main power supply 2 Mount LPC 2 D06 module to the provided place inside an electrical panel DIN EN50022 35 rail mounting 3 Mount other LPC 2 modules if required Mount each module to the DIN rail first then attach modules together through K1 and K2 connec
8. tors 4 Connect digital output wires according to the connection scheme in Figure 2 5 Switch ON main power supply Dismount in reverse order For mounting dismounting modules to from DIN rail a free space of at least one module must be left on the DIN rail NOTE LPC 2 MC3 main control module should be powered separately from other electrical appliance connected to LPC 2 system Signal wires must be installed separately from power and high voltage wires in accordance with general industry electrical installation standard Outputs OUT1 OUT4 on the lower side of module form one group and outputs on the upper side OUT5 OUT8 forms the other Outputs in the same group are basic insulated while outputs from one group to another are double reinforced insulated Mains voltage 230 V and 48 V SELV must not be connected in the same group of outputs It is possible to connect mains voltage in one group and SELV in the other group Figure 4 Minimum clearances 60 mm or more ANANMAN ion Q e of N 00 CR 2 a fe F iS ol la or more The clearances above must be considered before module mounting _ Longo programmable controller LPC 2 D06 module SMARTEH LIVING SYSTEMS 3 3 Module labeling Figure 5 Labels on housing Label 1 MC3 sample Label 2 MC3 sample LPC 2 MC3 P N 225MC304001001 S N MC3 S9 05000001 90 Dic 16 05 C