1. DC24 FF pc24 RR aa DC24 DC24 PES Demme ET E DC24 al eae O O O oO O oO O is O 5588 RS485 A RS485 A RS485 A RS485 B o o o RS485 B oo o fT RS485 B o o QL e Q Q Q Q Q amp Q amp Q g Master Panel No 1 Slave Panel No 2 Slave Panel No 31 Slave Panel owo JP1 oma JP1 owe JP1 amo JP1 Swi Swi Swi Swi FOSAS E EA leo 3 BEA Io PEEN 20 FIRE ALARM PANEL Panel address setting Slave panel address must be from 1 to 31 continuously And master address should be set as the total number of slave panels For example if you connect 18 slaves to the master panel the master panel address should be set to 18 And the slave panel address should be set from one to 18 The address setting dip switch SW1 is on the PCB board There are 5 small dip switch on the SW1 switch from right to left each dip switch correspond to binary number of panel address INPUT amp OUTPUT TERMINAL S W A PHOOHVOHHSHS9Sge O O ON ON DP tlle RS485 EOL Jump OFF L123 4 5 Bit4 321 0 Address Setting ow O L O ON is 1 and OFF is 0 for each bit
2. m CEHE EEL a 3 in EREHE m PPMM 29 TeS INSTRUCTION MANUAL AE E E 1 au Smaa 18 SS Srey 2 mmaa 26 TESTAS mmmmal 30 45 P e SS ail 3 7 11 21 The following table would show all address status from 1 to 31 are 4 CAE T 12 5 Eio 19 E 20 23 Ea n p ere 31 maiaa 0 ER 22 FIRE ALARM PANEL RS485 EOL resistor setting For the RS485 communication network two End of Line EOL resistors should be used at both end of RS485 wires The resistor is on the PCB board already you just use jump J1 to select INPUT amp OUTPUT TERMINAL COCCCOCOCOCOOOSOOO O O es JP 1 RS485 EOL Jump Address Setting Cr O E O For the master panel and the last one panel the jump J1 should be set as below BE JP For the other slave panel the jump J1 should be set as below JP1 BE JP 1 INSTRUCTION MANUAL 23 How Master Panel show the Event of Slave Panel When then fire alarm system working all the fire or fault event of slave panel would send to master panel The Master panel would show fire and fault event one bye one When there are no fire alarm events the master would show the fault event If there are fire event the master would not show the fault event Communication Fault Event In the norma
3. 510 200 510 200 Number of Alarm Zones 1 1 1N4007 Sound Output End of Line Diode 1N4007 Max Sound Supply Current in Fire A 1A 24V Fire FaultR elay contacts Load A 2A 24V TA 24V JAI24V 5009 Panel Weight Without Battery kg 5209 Panel Dimensions mm 108 x 143 x40 108 x 143 x40 INSTRUCTION MANUAL 15 Terminal Wiring Diagram Sounders Zone Detectors Auxiliary Signalling Relays FIRE2 FIRE1 FAULT DC24 V POWER INPUT RS485 Communicaiton NO e NO E NO E SO9OSOSOO 16 FIRE ALARM PANEL Sense Zone Wiring Diagrams Find the detector bases you will be using and check to see which end of line device is required either a 5k6 resistor or an active end of line unit The 5k6 resistor should be used if a zone is comprised entirely of call points Sense zone with a 5k6 end of line resistor O0 One js EOL OQ One The color bars on a 5k6 resistor are lt M eg oO Zone O Zone uselb pol pjob The panel is supplied with 5k6 end of line resistors as standard Manual call point can be connected into Zone wiring when the manual call pint switch closed the sense zone wire would be short the panel would alarm when the sense zone circuit is short INSTRUCTION MANUAL 17 Sound Ouptut Wiring Diagram The sound output are wired as in the diagram below A end of line diode must be fitted at the end of
4. Check wiring is as in example diagrams and ensure the end of line monitor is a 5k6 resistor or an active end of line device Sound fault LED flashing buzzer sounding Faults monitored are e Open circuit on the sound output wiring 12 FIRE ALARM PANEL e Short circuit on the sound output wiring e The end of line diode not connected or not connected correctly Head removal not working Check compatible base is being used and is wired correctly Other faults Switch off the power supply and restart the power on Fault Output The fault output marked FAULT on the PCB is a set of volt free changeover contacts When the panel is in fault common C is shorted to normally open NO In normal operation with no faults common C is shorted to normally closed NO INSTRUCTION MANUAL Panel Inside INPUT amp OUTPUT TERMINAL SOUND FIREZ FIRE1 FAULT ZONE2 ZONE1 RS485 24VDC NO C NO C NO C A B ca WOVOVVYYVOVVGOVVVSYVO O ond JP1 RS485 EOL Jump Address Setting SW ON m EJ ER O opr LASAS 13 14 Panel Specifications Master Slave FIRE ALARM PANEL System Voltage V DC DC22 26V DC22 26V Normal Quiescent Current normal status lt S50MA lt 50 mA Detector Voltage V DC 24 24 Firing Resistance Ohms
5. the circuit Motorised fire bells may be used but solenoid bells MUST NOT be connected to the panel Sound in out in out Diode 1N4007 Sound in out in out 18 FIRE ALARM PANEL Auxiliary Signaling Relays and Sound Outputs There are three auxiliary signal relay output and two sound output inside the panel Fire1 Relay Output If any zones fire alarms the Fire1 relay would be activated and output relay contacts C NO Meanwhile the Sound output would be activated Fire2 Relay Output If zone 1 and zone 2 fire alarms together the Evacuate LED flash after 30 seconds delay the LED would light continuously Meanwhile the Fire2 relay would be activated and output relay contacts C NO Fault Relay Output If any fault occurs in the panel the Fault Relay would be activated and output relay signal outputs C NO INSTRUCTION MANUAL 19 Fire Alarm Network One Master Panel could connect 1 to 31 slave panels When the slave panel has alarm or fault event the slave panel would send even to master panel and then master would show the event of slaves one by one RS 485 Communication terminal wiring Mater panel connect all the slave panel with RS485 communication port Each panel RS485 port have two terminals A and B all the terminal A should be connected in one wire and also terminal B should be connected in another wire Also the DC24V power of panels should be connected together
6. Notes 2 Zones Master amp Slave Fire Alarm Control Panel User amp Installation Manual FIRE ALARM CONTROL PANEL FIRE ALARM CONTROL PANEL Master Panel Slave Panel IMPORTANT This manual should be left with the panel after installation We reserve the right to change product specifications without prior notice INSTRUCTION MANUAL 3 Introduction The information provided in this manual covers the Master and Slave fire alarm control panel The panel range is designed to meet the requirements of EN54 Parts 2 amp 4 This product should be installed commissioned and maintained by suitably qualified service personnel with reference to IEE regulations and any statutory requirements General Description The panel 2 zones ranges of fire alarm control panels are microprocessor controlled and are available with 2 sense zones detector zones The panels have 1 alarm sound output zones bell zones a 24V supply energised on fire one set of volt free changeover contacts which operate on fault and two sets of volt free changeover contacts which operate on fire Installation Procedure Before proceeding with the installation please read the section Panel Operation Installation of the panel should be carried out by qualified personnel 4 FIRE ALARM PANEL Using the metal box as a template mark the position of the fixing holes on the wall Drill and plug the wall then screw the panel to the wall Ensure t
7. automatically activate the sound circuits To silence the sound alarms press and hold down the Silence button about 5 seconds Active sound alarm manually Anytime press the Evacuate button the sound output would be activated Active Fire1 amp Fire2 Relay output manually Anytime press and hold down the Evacuate button first and then press and hold down the Silence button and then press Test Reset button then release the Test Reset button then release Silence button at last release the Evacuate button the Evacuate LED would flash and then Fire1 relay and Sound output would be activated after 30 seconds delay the Fire 2 relay would be activated The Evacuate LED would be light steady Pause the Fire2 Relay output delay time INSTRUCTION MANUAL 11 Whenever automatically or manually active the 30 seconds count down delay time press Evacuate button the count down delay time would be paused the Evacuate LED and Silence LED would flash together when press Evacuate button again the Silence LED would not flash the count down delay time would go on continuously Fault Finding RUN LED blinks intermittently This is perfectly normal and indicates that the processor is running an internal memory check Fault LED and sense zone fault LED flashing buzzer sounding Faults monitored are e Open circuit on the sense zone wiring e Detector head removal Check all detectors and call points on the sense zone indicated
8. he digital LED show the PFXX the corresponding zone1 or zone2 fault LED would light For example if zone1 of slave panel 5 has fault zone 2 of master has fault the master would show information as below in cycle FIRE ALARM CONTROL PANEL OC EVACUATE SILENCE TEST RESET Zone of No 5 slave Zone2 of Master 26 FIRE ALARM PANEL Panel System Log All events should be properly recorded in this log book An event should include fire alarms whether real or false faults tests temporary disconnections and the dates of installing or servicing engineer s visits with a brief note of work carried out and outstanding Name and address eae eee cecececcecececeeceeceusceeceecenecaeees Of installation eaeeece ceceaceueceescecaesceeeaeeseeeeeeaes Person responsible seeeeee Date 06 for log book _ __ hha eeeeetttteetetttees Date E ET Date aian EET E ASAE Date aii System installed by ssessssssesssssssrnerrrrrrrrrrrrrrnrerernn and is maintained under contract by 000 INSTRUCTION MANUAL Notes 27
9. he panel is free from knockout discs swarf and other debris The back of panel box is as below there are three wiring holes on the back and another three holes on the top of box for cable wiring And there are six diameter 6mm holes on the back of box for screws to fix the box on the wall Diameter 20mm Diameter 6mm 29 5mm rP Q 140mm INSTRUCTION MANUAL 5 Do not remove any end of line resistors from the panel until after the following test is performed With all end of line resistors fitted inside the panel connect the panel DC24V input to an external DC22 to 26V power supply Switch the external DC24V supply on The internal buzzer will sound With the panel DC power supplies connected the panel should be silent and in its normal operating mode the power running lamp above the Test Reset button would flash about 10 seconds without communication about 5 seconds with communication alarms amp buzzer silent lf a fault is indicated refer to the fault finding section before proceeding Switch off the mains supply Remove the 5k6 end of line resistor from sense zone 1 Terminate sense zone 1 circuit wiring in the panel observing correct polarity and fit the end of line resistor at the very end of the circuit Check that all the detectors and call points are correctly wired With sense zone 1 connected and all other end of line resistors fitted inside the panel connect the DC power sup
10. l condition the Master would communicate with Slave panels one by one if one of slave panel is not respond the master panel commands The master would show CF XX XX is the number of slave panel for example if No 7 slave panel has some communication problem the Master panel would show CF 07 as below CF is short abbreviation for Communication Fault 24 FIRE ALARM PANEL Fire alarm Event When master or slave panel alarm the master panel would show all fire alarm events one by one The master panel would show PA XX XX is the address of panel address 00 is for master panel address 01 to 31 is for slave panel When the digital LED show the PA XX the corresponding zone1 or zone2 fire alarm LED would light For example if zone2 of slave panel 16 alarms zone 1 of slave panel 28 alarms the master would show information as below in cycle Any slave panel s alarm event would active the master panel s sound output FIRE ALARM CONTROL PANEL FIRE ALARM CONTROL PANEL ZONE 1 ZONE2 SOUND xlo Ga A A F F F oll PA iB PACE O EVACUATE SILENCE TEST RESET EVACUATE SILENCE TEST RESET Zone2 of No 16 slave Zone of No 28 slave INSTRUCTION MANUAL 25 Fault Event When master or slave panel has fault the master panel would show all fault events one by one The master panel would show PF XX XX is the address of panel address 00 is for master panel address 01 to 31 is for slave panel When t
11. ne1 Alarm LED Zone2 Alarm LED Zone1 Fault LED Zone2 Fault LED Evacuate LED Evacuate Button Slave panel has no 4 digital LED FIRE ALARM PANEL Sound Alarm LED Sound Fault LED Silence LED RUN LED Test Reset Button Silence Button INSTRUCTION MANUAL 9 Panel Operation Normal Status If the panel is in its normal condition the RUN led above the TEST RESET button would flash once every 10 seconds without communication or 5 seconds with communication Performing a lamp test If the panel is in its normal condition pressing the Test Reset button will cause the panel to perform a lamp test In the normal condition press and hold down Test Reset button about 10 seconds the panel would be reset Resetting the panel after a fire or fault is detected To reset the panel after a fire or fault event press the Silence button first and then press the Reset button Resetting the all the panels If any of the panel functions have been activated pressing Silence button first and then press the Reset button will return the panel to its normal condition When the master panel s Reset button pressed master panel and all the slave panels would be reset 10 FIRE ALARM PANEL Silencing the internal buzzer lf a fault or a alarm is detected by the panel the internal buzzer will sound To silence the buzzer press the Silence button Silencing the Sound Alarms If a fire is detected the panel will
12. plies If the panel indicates a fault refer to the fault finding section before proceeding Do not megger cables connected to either the panel or any field devices If no faults are indicated then 6 FIRE ALARM PANEL power down the panel and follow the same procedure with the additional sense zones and then the alarm zones Adding the zones one at a time makes fault finding and commissioning much simpler Make sure that no bare wires come into contact with the panel circuit boards during installation Detector Head Removal The Panel supports head removal The basic principle of head removal is to ensure that all call points will function even if a detector head has been removed Head removal requires either zener clamp bases or schottky diode bases with the appropriate end of line device to be fitted When a detector head is removed the panel will show a fault but the sense zone circuit will remain intact INSTRUCTION MANUAL 7 Control panel fascia In addition to the mandatory controls and indications required by the EN54 2 4 standards Reset Test and Silence Alarm Fault buttons are provided to allow easy operation to the control pane Master Panel Sound Alarm LED Zone1 Alarm LED Sound Fault LED Zone2 Alarm LED Digital LED Zone1 Fault LED Zone2 Fault LED Silence LED RUN LED Evacuate LED Test Reset Button Evacuate Button Silence Button Master panel has 4 digital LED 8 Slave Panel Zo