Renata - I Series User Manual

image

Contents

1. 7 Stay away from fire and extremely hot location 8 Do not stack materials and standing on the top of the unit 9 The unit should not be exposed to corrosive air 10 The normal operating temperature is 0 45 C Page 10 electronics amp controls power systems pvt Itd 4 2 Battery Maintenance 1 2 3 4 The lead acid free SMF battery requires very low maintenance Check the Battery links loose connections Keep the battery terminals clean for every month If the battery you are using is Tubular like the automobile use you should Renata I Series User Manual check the electrolyte every three months Refill with distill water when the electrolyte level is too low 5 Keep the Batteries at cool place 25 C 5 Troubleshooting A LED Indicators Indicator ON 0 Indicator OFF Buzzer CED Indicatorsistatus Buzzer Status Action Mains Bypass Load onLoad onjLoad on Output Mains Batt Inv Over Battery Bypass Inverter ON Fault Low Fault load a z 0 o z x 0 o 0 o Normal With AC power failure 0 0 j 0 i 0 0 0 ie Battery Mode ByPass 0 0 0 0 0 0 Mode With o 0 o o Or ESAS ll a Inverter _ Ref to e is 0 dd 0 0 0 l 0 Beeping fault Fig IV 4 With Overload Ref to 0 0 0 0 0 oY 1 Sp pup Fig IV 3 With After lias every 4 Batter e 0 0 0 0 0 0 0 0 Ulsa el low Trip Battery Supply System Check the 0 0 0 0 0
2. 2 5ms Over load Output Short Circuit Over Temperature Input Low High cut off Battery Low Trip Input Green 2 Bypass On Green 3 Load On Bypass Yellow 4 Load On Inverter Green 5 Output On Green 6 Load On battery Yellow 7 Mains Fault Red Level indicator Battery Level 8 Battery Low Red 9 Inverter Fault Red 10 Overload Output Short Red Load Level Input Voltage On Battery Mains Fail Overload _ Ups Fault Noise Level 1 m Distance Environment Temperature Humidity Physical Size L D H mm Note Specifications are subjected to change without prior notice Page 16 Output Voltage Output Frequency Output Current Capacity Input Frequency Battery Voltage Capacity Beep every 2 Soc Continuous Beep 60dB OC ASC __0 90 Nom condensing _ 630 350 850 1630 350 850 1650 400 1000 650 400 1000 electronics amp controls power systems pvt Itd Renata I Series User Manual Our Contact Information Head Office 29 A 2nd Phase Peenya Industrial Area Bangalore 560 058 India Tel No 91 80 28371974 28379401 Fax No 91 80 28391587 For sales enquiries contact sales eandcpowercom Regional Sales Offices Ahmedabad Bangalore Chandigarh Chennai Cochin Hyderabad Indore Jaipur Kolkata Lucknow Mumbai New Delhi Service Locations e Agra e Guwahati e Meerut e Rajamundry e Ahmedabad e Gwalior Mumbai e Salem e Aura
3. 0 0 0 0 0 Shutdown 1 P MCB Page 11 electronics amp controls power systems pvt ltd B Troubleshooting Guide Renata 1 Series User Manual A Mains ON Indication not ON Is power switch ON Turn ON power switch Is Line Indication ON s the Input Voltage Normal Call for Service Check the AC Input Yes Fig IV 1 Page 12 Y Continue electronics amp controls power systems pvt Itd Renata I Series User Manual B Inverter Indication not ON Turn ON Inverter switch Is Inverter switch is ON Is Inverter indication ON Yes Did Inverter indicators go off in 20 Sec Disconnect the Loads Did Inverter indicators go off in 20 Sec No Call for Continue Service operation Fig IV 2 Page 13 electronics 3 controls power systems pvt Itd Renata I Series User Manual C Load on bypass Indication ON Is Load on N Bypass Indication ON after 20 Sec Turn ON No Inverter switch Is Inverter switch is ON s the Input Disconnect some Voltage ma md Normal uncritical loads Is Fault Indicators ON v Call for Continue Service operation Fig IV 3 Page 14 elect
4. Inspect the input output fuses to be in working order 3 3 2 Controls and LCD Indicators 21 1 2 3 4 8 6 7 5 10 9 sw1 oW3 11 SWZ 15 16 20 Page 8 electronics amp controls power systems pvt ltd Renata I Series User Manual 1 Bypass On Green 8 Battery Low Red 2 Load on Bypass Yellow 9 Inverter Fault Red 3 Mains ON Green 10 Over Load Red 4 Load On Battery Yellow 11 15 Battery Levels LED Indicators 5 Load On Inverter Green 16 20 Load Levels LED Indicators 6 Output ON Green 21 Display 7 Input fault Red Control Switches 1 SW41 Inverter OFF Switch Red Turn OFF the Inverter When press SW1 red for 5 Sec the unit will turn off the inverter and unit transfer from normal operation to Bypass mode 2 SW2 DPM Scroll Blue 3 SW3 Inverter ON Switch Green Turn ON the Inverter When press SW3 Green the unit will turn ON the inverter and unit transfer from Bypass to Normal operation Power Switch Located at the rear panel of the unit controls the input AC power and Input batteries power forthe unit 3 3 3 Power ON Procedure The procedure is very simple Please follow the steps for bellow operations Start Up a Make sure that the power switch is OFF and there is no equipment connected tothe unit b Check for correct input voltage c Power ON the unit and the LINE BYPASS Load ON Bypass and Output indicator will be
5. ON The cooling fans will also be running d In about 20 seconds the Bypass Indicator will be OFF while the Inverter will be On indicating every thing is normal Page 9 electronics amp controls LY power systems pvt Itd Renata I Series User Manual e Turn OFF the AC Input and Line and Bypass Indicator will also be OFF and also Load on Battery Input Fault will be ON The Audible alarm will beep in 4 Seconds Interval indicating batteries is in use f Press SW1 button for 5 Seconds inverter will be powered off g Press SW3 Inverter will get ON h Now the unit is ready to use NOTE Please keep the unit running for at least 12 hours so that battery could be fully charged During this period the INVERTER may be turned OFF 3 3 4 Unused for Extend Period I Leave all the switches OFF position if unused for more than 10 days II If Unused for more than 3 Months repeat the start up procedures and let the unit running at least 24 hours to prolong the batteries life III UPS and Battery Maintenance 4 Maintenance 4 1 UPS Maintenance Keep the unit clean and vacuum the ventilation intake periodically Wipe with soft and damp cloth 1 2 3 Check the loose and bad connection monthly 4 Never leave the unit on an uneven surface 5 Position the unit to allow at least 50cm clearance between the surroundings of the unit Keep the ventilation intake open Avoid direct sunlight rain and high humidity 6
6. Renata 1 Series 5K 7 5K 10K 15K 20KVA UPS User Manual C electronics amp controls 19 power systems pvt Itd An ISO 9001 2008 Company electronics amp controls power systems pvt Itd Renata I Series User Manual Contents LT INTO UN Mptadeucvanns 2 2 Theory of Opera sucia 3 2 1 Modes of Oper iesestisicacdccnstensesrviandtadecmsdusanns ts 3 3 Safety ASTUCIA ctra 6 3 1 Preparation and System Setup cece 6 A Gaetan ena meen 6 3 3 Operating INStructiONS oooooccccnnnnnnnnncccccnnncinnnnes 8 4 Matera pa 10 4 1 UPS Mane AiG eso caiste 10 4 2 Battery Maintenance coccccccocionnnconianninarananos 11 drouble SOONG scales 11 Technical SpecificatlOnS o nitrilo 16 electronics amp controls power systems pvt Itd Renata 1 Series User Manual 1 Introduction On Line UPS can supply adjusted stable uninterruptible power to electrical equipments When AC fails Voltage vary voltage surge and noise conditions UPS can keep the load works normally In common operations UPS first feed the power to rectifier for adjust and eliminate the unstable factor then through inverter transfer the DC to pure AC to the Load When UPS detect AC Voltage below the acceptable range of load UPS turn from AC to battery Mode Under this condition battery power through inverter supply and supply stable power to Load When AC turns back to the acceptable range of Load Ups au
7. dard 15A wall outlet will not support the heavy load of the unit b It is safe to connect the unit to the nearest utility panel c Refer Fig for terminal block connections The input power should be connect to the right terminals Note also that UPS output and external batteries also share the same terminal block d Use high quality power wires Page 6 electronics amp controls power systems pvt Itd Renata I Series User Manual e Always turn power off before wiring f Please follow the standard wiring procedures g Check for the correct Polarity h Avoid sharing the same terminals with other equipments i When wiring is done make sure that no wires touches the metal case to prevent short circuit 5kVA 192VDC 11 UPS TERMINAL CONNECTION DETAILS POWER INPUT BATTERY POWER OUTPUT 230VAC 50Hz 192VDC 230VAC 50Hz 7 5 10 15 20KVA 384VDC 31 UPS TERMINAL CONNECTION DETAILS POWER INPUT BATTERY aoe 4159 50Hz 384 DC 230 50Hz Page 7 electronics amp controls LY power systems pvt Itd Renata 1 Series User Manual 3 3 Operating Instructions 3 3 1 Pre testing To ensure proper functioning of the UPS the following step should be followed 1 Double check the site of installation 2 Make sure that the Power switch on the rear panel is OFF 3 Unplug all loads 4 Use a tester to check if the input voltage is at rated level 5 Gently twist the input output wiring and tighten loose ones 6
8. e following conditions 1 Over Load 2 Inverter Failure 3 The inverter switch on the front panel isn t pushed to the ON or within the initial 25 seconds after it is pushed to ON 4 The inverter switch is pushed to the OFF Page 4 electronics amp controls power systems pvt Itd Renata 1 Series User Manual Rectifier Inverter Static Switch Filter Input Output Fig 1 3 B External Views Page 5 electronics amp controls power systems pvt Itd Renata 1 Series User Manual 3 Safety Instruction 3 1 A Preparation To achieve ultimate performance of this on Line UPS Please observe the Following Read the User s Manual Follow the Operating Instructions closely Be gentle and careful when moving the unit around 1 2 3 4 Plug into the correct power source 5 Never open the cabinet to avoid electric shock and damaging to the unit 6 Do not apply load which is exceeds the rated capacity Otherwise damage may occur 7 Keep the User s manual handy for quick reference 8 Refer the trouble shooting guide when having problems 9 Keep the unit clean all time 3 1 B System setup 1 Precaution 1 Remove all the wires 2 Handle the unit very carefully and avoid dropping 3 Never leave the unit upside down 3 2 Installation Refer to the following Instructions for system install Input a Never plug the unit into a wall outlet The stan
9. ngabad e Hubli Munnar e Srinagar e Agartala e Hyderabad Mangalore e Tirupati e Bangalore Indore e Mysore e Trichy e Baroda e Jabalpur e Nagpur e Tirunelveli e Bhopal e Jaipur e New Delhi e Trivandrum e Bhubaneshwar Jammu e Ongole e Udaipur e Chandigarh e Kanpur e Palakkad e Vizag e Chennai e Kolkata e Patna e Vijayawada e Cochin e Kottayam e Pondicherry e Varanasi e Coimbatore e Ludhiana e Pune e Calicut e Lucknow e Raipur e Dehradun e Madurai e Ranchi Works A 95 BIS PIPDIC Industrial Area Mettupalayam Pondicherry 605 009 India Tel No 91 413 2277241 Fax No 91 413 4302241 For Service Call our Helpline Tel No 91 80 28397120 28397121 www eandcpower com Page 17
10. ronics amp controls power systems pvt Itd Renata 1 Series User Manual D INVERTER FAULT Indication ON Turn OFF the Inverter Switch Disconnect Loads e Turn ON the Inverter Switch Is Inverter indicators ON Is Fault Indicators ON No Reconnect all Loads and turn ON Y Call for Service Fig IV 4 Page 15 electronics amp controls power systems pvt ltd 6 Technical Specifications 44KW Voltage Voltage Range Phase 230VAC 1160 270V AC 46 to 54Hz Renata I Series User Manual AISVAC 330 470VAC _46 to S4Hz Single Phase 192V Three Phase 384V 32 The lowest discharge Voltage 168V 1 75V cell Charging Voltage 216V 2 25V cell Voltage Frequency Syne mode Free Running mode Power factor Phase Synchronize Rate o ii Crest Factor Waveform Transient Response Harmonic Distortion V Linear Load Non Linear Load Overload Detection Inverter Technology Power Failure Or Recovery Over Load Disappear Bypass Inverter Inverter Bypass a b Transfer Time o Protections LED indicators Status 336V 1 75V cell 432V 2 25V cell BOVI 1 46 SAllz 30Hz 0 5Hz 0 8 Single Phase VHz sec 3 1 At full Load Pure Sine WmSce 2 4 110 125 for 10 Min 150 for 1 Min ine Wave Pulse Width Modulation _ Auto transfer to UPS
11. tomatically adjust power again to the rectifier and inverter Meanwhile UPS charge the Battery During the full courses it has no transfer time from AC to battery backup operating will not be interrupted So we call it true on line UPS Further more when inverter stopped output if UPS fails system will automatically transfer to the bypass AC supplies power directly to load All courses will not power off UPS can supply stable power to electrical machines and carry with the following characters Improve Power quality O Reduce the noise Disturb Compatible with most loads O Output Protection when power off O Perfect battery protection Page 2 electronics amp controls power systems pvt Itd Renata 1 Series User Manual 2 Theory of Operation 2 1 Modes of Operation 1 AC normal mode As shown in Fig 1 1 the AC power supply passes through rectifier inverter static switch filter to the output and chargers the battery by the charger Rectifier Inverter Static Switch Filter Input Fig 1 1 Page 3 electronics amp controls power systems pvt Itd 2 Power Failure Mode Renata 1 Series User Manual As shown in Fig 1 2 the battery supplies the output to Load through the inverter Rectifier Inverter Static Switch Filter k E pe Charger Output Fig 1 1 3 Bypass Mode As Shown in Fig 1 3 the unit will switch to bypass mode under th