Home

1761-UM005 - Rockwell Automation

image

Contents

1. Input Split Point on page 30 Input Assembly Data Explicit Split Point and Slave on page 67 For MicroLogix 1000 controllers use N7 as the destination file type For other controllers see the recommended file number on page 41 Status Byte The first byte bits 0 7 of the first word of I O data is set aside as status information The second byte bits 8 15 of the first word of I O is available for user data The DNI Input Output Image is shown below Word Input Output Image Series A Series B 0 0 Data bits 8 15 Status Byte bits 0 7 1 1 Data Most Significant Byte MSB Data Least Significant Byte LSB 2 2 Data MSB Data LSB 3 3 Data MSB Data LSB Y L L L 14 30 Data MSB Data LSB 1 31 Data MSB Data LSB Input Status to Master Device The Input Status Byte provides the following information Function Output Buffer Overdrive n a Bit Number DNI Configuration Parameters and Programming Notes 51 Output Buffer Overdrive Bit 6 written by the DNI This bit is set 1 when Master Outputs arrive at a rate faster than the DNI can forward the data to the DF1 device When the Buffer Overdrive bit is set the output image is being overwritten before it can be sent to the DF1 device To resolve this limit the data production rate in the scanner until this bit stays clear 0 Output Status to DF1 Device The Output Status Byte provides the followi
2. Heartbeat Multiplier AutobaudEnable Data Rate Load from DNI Save to File Substitute Destination Address g Save to DNI Connected Device MicroLogix1 000 C SLC Other MicroLogix Print to Text File f pre Module Configuration Status Other Modified MDNI Slave Mode Configuration a 140 Data Souce Destination l M File File Word Size Split Number Offset words words Type Input p iN 42 1 Setup Programming and Troubleshooting 61 Using RSNetWorx to Modify Parameters Once a DNI is placed on the network double click to open the EDS file All adjustable parameters that configure the DNI for operation are set up through this configuration utility The illustration below shows the RSNetWorx Device Configuration screen with each DNI configurable parameter Perform this procedure to configure any of the parameters 1 2 Highlight the parameter Click the Modify Parameter button or double click on the parameter For DNI Series A set DNI mode to Standby For DNI Series B set I O Scan Enable to Disable Change the parameter data as needed For DNI Series A set DNI mode to Operational For DNI Series B set I O Scan Enable to Enable For more detailed information click on Help Once a parameter is changed or after all parameters are changed click Download to Device E 1761 NET DNI Series B DeviceNet Interface 27 x General Device Parameters
3. e Cyclic The DNI continuously sends the input image data to the master at a user scanner defined time interval regardless of whether the data has changed Output Image The output image is a configurable array of 16 bit data words The image is configurable from 1 16 data words for DNI Series A 1 32 data words for DNI Series B The actual data that resides in the output image is delivered to the DNI from the master by one of two mechanisms e Polled Where the DeviceNet Master sends a poll request with output data and the DNI responds with its current input data e COS Change Of State Where the DeviceNet Master detects that data has changed within its output image and automatically sends the data to the DNI e Cyclic The DNI continuously receives the output image data from the master at a user scanner defined time interval regardless of whether the data has changed All DNI I O parameters are configured with software such as the DNI Configuration Utility RSNetWorx or DeviceNet Manager and stored as part of the network configuration Configuration software is covered in Setup Programming and Troubleshooting on page 53 Individual settings of the DNI are covered in DNI Configuration Parameters and Programming Notes on page 27 Operation 19 Messaging Services The capabilities of each individual device determine what level of messaging is supported The types of messaging supported are e I O Assembly
4. Allen Bradley DeviceNet Interface Catalog Number 1761 NET DNI User Manual Seeseesee m LH Rockwell Automation d Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls publication SGI 1 1 available from your local Rockwell Automation sales office or online at http literature rockwellautomation com describes some important differences between solid state equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described
5. clearance for DIN rail latch movement during installation and removal Publication 1761 UMO005B EN P October 2006 Mounting Template 118 mm 4 64 in Specifications 87 52 07 mm 2 05 in 7 mm 20 in Y a Zs ch c 27 7 mm Allow 15 mm 0 6 in 1 09 in clearance for DIN rail latch movement during installation and removal Publication 1761 UMO005B EN P October 2006 88 Specifications Publication 1761 UMO005B EN P October 2006 Interface Basics Terms and Abbreviations Glossary The 1761 NET DNI DND is a smart interface that provides DF1 full duplex capable devices a connection to the DeviceNet network To understand how the DNI operates you need to become familiar with certain terms This figure illustrates the relationship between the DF1 Device the DNI function and the DeviceNet network 1761 NET DNI Interface Diagram DNI DeviceNet Configuration os Parameters Input Operating Systems u Image To Master Output Image From Master Messaging ES MicroLogix or other DFI Device The following terms and abbreviations are specific to this product For a complete listing of Allen Bradley terminology refer to Allen Bradley Industrial Automation Glossary publication AG 7 1 Autobaud A feature that allows a communicati
6. e If you are monitoring the heartbeat bit in the controller to determine communications integrity as a general rule multiply the Data Scan Delay by the DF1 Heartbeat plus 1 to determine the preset time value for the heartbeat timer e DF1 Heartbeat determines how many input reads are done between heartbeat checks and toggles step B When the DF1 Heartbeat is set to 2 this occurs on every other read when the DF1 Heartbeat is set to 3 this occurs on every third read See the application example DF1 Heartbeat Bit 7 on page 51 and MicroLogix as I O on the DeviceNet Network on page 69 for more information about using the DF1 Heartbeat Publication 1761 UMO005B EN P October 2006 DNI Configuration Parameters and Programming Notes 45 Data Scan Delay Data Scan Delay Parameter Definition Parameter Parameter Number Description Range Default Type Value Series A Series B 1 0 13 Data Scan 20 3000 ms 50 ms Delay Polling Delay When Data Enable parameter 3 is enabled DNI Series A or I O Scan Enable parameter 12 is enabled DNI Series B the value entered for Data Scan Delay defines the amount of time that the DNI will delay between communications This value does not identify how often communications take place it defines the delay between the completion end of one communication sequence and the beginning of the next me 16i important not to set this value too low Setting Data Scan De
7. COS ML DND is covered in the following section Publication 1761 UMO005B EN P October 2006 74 Application Examples Publication 1761 UMO005B EN P October 2006 DNI COS change of state 1 0 Messaging The ladder logic shown below is an example of how to send input data to the DNI COS input messaging This procedure is recommended because the latency issue associated with polling devices is minimized Polling is a mechanism that is used to acquire data from a device The DNI reading data from a controller at a set interval is an example of a polled relationship The problem with polling is that usually the data does not change so the communications are consumed by reading the same data over and over Another problem is that information cannot be received quicker than the polled rate and depending on when the data changes worst case update can take up to twice the polled rate One solution to this problem is to allow for COS change of state messaging What this allows is for the device MicroLogix for example to send input data to the DNI when it detects new changed data Many also call this type of relationship unsolicited communications This can significantly improve system throughput because the polling interval is eliminated The way the MicroLogix controllers can get input data into the DNI is to message to node address 254 Address 254 is an invalid address on the DeviceNet network When the DNI detects an incomi
8. Cable Selection Guide Publication 1761 UMOOBB EN P October 2006 DeviceNet Network To properly design your DeviceNet network see DeviceNet Media Design Installation Guide publication DNET UMO72 This document provides design guidelines concerning wiring practices connectors grounding and power budgeting This publication is available from your Allen Bradley distributor or from the Internet at www literature rockwell com Port Identification DeviceNet Network TALS Port 1 Replacement Bed connector part no O 1761 RPL 0000 y Te ba 2 A DANGER 7 Use this write on N area to mark the THR DeviceNet node A IS RS 232 Port 2 NY B Address e Port 2 of the DNI is an 8 pin mini DIN RS 232 port that provides connection to DF1 compatible RS 232 devices The table below describes the RS 232 compatible cables RS 232 Devices DNI Connected to Catalog Number Use Cable MicroLogix all series 1761 CBL AMOO Mini DIN to Mini DIN 1761 CBL HM02 45cm 17 7 in 2m 6 5 ft SLC 5 03 SLC 5 04 or 1761 CBL APOO Mini DIN to D Shell SLC 5 05 Channel 0 1761 CBL PM02 45cm 17 7 in 2m 6 5 ft PLC 5 1761 CBL APOO Mini DIN to D Shell 1761 CBL PM02 45cm 17 7 in 2m 6 5 ft Chapter 5 DNI Configuration Parameters and Programming Notes Information About DNI The following changes have been made which affect the EDS file Series B The Standby Operationa
9. EDS 1 0 Default Groups r On Line Upicad tram Geyice Single DownlGad ta device CA Parameter Details Parameter 0001 Input Size 1 word 0002 Input Split Point 1 word 0003 Input Type Integer File 0004 Input Data File 7 0005 Input Word Offset 0 0006 Output Size 1 word 0007 Output Split Point 1 word 0008 Output Type Integer File 0009 Output Data File 7 0010 Output Word Offset 1 0011 DF1 Device MicroLogix1 000 0012 1 0 Scan Enable Disable m ll n E Publication 1761 UM005B EN P October 2006 62 Setup Programming and Troubleshooting Publication 1761 UMO005B EN P October 2006 Using DeviceNet Manager to Modify Parameters Once a DNI is placed on the network double click to open the EDS file All adjustable parameters that configure the DNI for operation are set up through this configuration utility The illustration below shows the DeviceNet Manager Device Configuration screen with each DNI configurable parameter To configure any of the parameters perform this procedure 1 2 Highlight the parameter Click the Modify Parameter button or double click on the parameter For DNI Series A set DNI mode to Standby For DNI Series B set I O Scan Enable to Disable Change the parameter data as needed For DNI Series A set DNI mode to Operational For DNI Series B set I O Scan Enable to Enable For more detailed informatio
10. Hazardous Environment Communication Cables 1761 CBL PM02 Series C or later 761 CBL HM02 Series C or later 1761 1761 CBL AMOO Series C or later 1761 CBL APOQO Series C or later 1761 61 RPL 00 DeviceNet Connector The DNI can be mounted in the vertical or horizontal position There are no spacing requirements except as necessary for DIN rail latch movement See Physical Specifications on page 85 for operating temperature specifications DIN Rail Mounting Follow these steps to mount the DNI on a DIN rail 1 Mount your DIN rail 2 Snap the DIN rail latch into the closed position 3 Hook the top slot over the DIN rail 4 While pressing the unit against the rail snap the unit into position Installation and Wiring 25 Side View DIN Rail Follow these steps to remove the DNI from the DIN rail 1 Place a screwdriver in the DIN rail latch at the bottom of the unit 2 Holding the unit pry downward on the latch until the unit is released from the DIN rail DIN Rail Panel Mounting Follow these steps to mount the DNI on a panel 1 Remove the mounting template from Appendix A of this document 2 Secure the template to the mounting surface 3 Drill holes through the template 4 Remove the mounting template 5 Mount the unit Mounting Template Publication 1761 UM005B EN P October 2006 26 Installation and Wiring Network Port Wiring
11. Input Size Series A 1 16 1 word 2 words Series B 1 32 Not Applicable 2 Input Split Point 1 32 1 word 2 words 5 3 Input Type Bit or Integer File Integer File Integer File 6 4 Input Data File 3 254 7 7 7 5 Input Word Offset 0 254 0 90 8 6 Output Size Series A 1 16 1 word 2 words Series B 1 32 9 8 Output Type Bit or Integer File Integer File Integer File 10 9 Output Data File 3 254 7 7 11 10 Output Word Offset 0 254 1 95 14 11 DF1 Device 0 3 3 MicroLogix 1000 3 MicroLogix 1000 0 Other 1 PLC 2 SLC Other MicroLogix 3 MicroLogix 1000 3 12 DNI Series A Disabled 0 or Enabled Disabled 0 Enabled 1 Data Enable 1 DNI Series B 1 0 Scan Enable Polling Enable 12 13 DF1 Heartbeat Series A 2 10 2 2 Series B 1 10 13 14 Data Scan Delay 20 3000 ms 50 ms 100 ms Polling Delay 2 15 Message Timeout 0 2500 ms 0 ms 0 ms Not Applicable 16 DF1 Substitute Address 0 64 64 Disabled 64 Disabled 15 17 DF1 Autobaud Disabled 0 or Enabled Enabled 1 Enabled 1 1 16 18 DF1 Baud Rate 0 5 Series A 2 9600 n a 0 38 400 Series B 1 19 200 1 19 200 2 9600 3 4800 4 2400 5 1200 1 19 DeviceNet Autobaud Disabled 0 or Enabled Enabled 1 Enabled 1 1 17 Not DNI Mode Standby 0 or Operational 1 Operational 1 Applicable Operational 1 Publication 1761 UMOOBB EN P October 2006 Quick Start 15 7 Click Modified Parameter then OK 8 Save to the conf
12. Menu 3 Select EDS Wizard 4 Select Register an EDS file and follow the prompts RSNetWorx is now set up to recognize and configure the DNI 5 To locate 1761 NET DNI in RSNetWorx file list double click on the following folders Rockwell Automation Allen Bradley Company Publication 1761 UMO005B EN P October 2006 56 Setup Programming and Troubleshooting Publication 1761 UMO005B EN P October 2006 Communications Adapter eNel RSNetWorx for DeviceNet Ele Edt View Network Device Tools Help BEE als mla t e ea amp zs Xs Hardware x E DeviceNet Category AC Drive Barcode Scanner Communication Adapter Dodge EZLINK Enhanced DeviceNet to SCANport General Purpose Discrete 1 0 Generic Device Human Machine Interface Inductive Proximity Switch Limit Switch Photoelectric Sensor Rockwell Automation Unspecified SCANport to DeviceNet Vendor Rockwell Automation Allen Bradley AC Drive Barcode Scanner Communication Adapter E fJ 1747 SDN Scanner Module m A 1756 DNB Scanner Module B B m e DTA A 1761 NET DNI Device Net Interface 1770 KFD RS232 Interface B 1771 5DN 1761 NET DNI Series B DeviceNet Interface Setup Programming and Troubleshooting 57 Setting Up DeviceNet Manager With DeviceNet Manager open install 1761DNI2 EDS for DNI Series A 1761DNI3 EDS for DNI Series B and 1761DNI BMP
13. October 2006 Your configuration software handles all interface issues for connection to a DNI over a DeviceNet network You use exactly the same procedures to connect to a DNI as you do any other DeviceNet product The DNI draws power from the DeviceNet connector When the DNI is connected to a DeviceNet network for the first time the DNI out of box configuration is e Node 63 e Baud Autobaud Commissioning is accomplished with network configuration software such as DNI Configuration Utility RSNetWorx or DeviceNet Manager There are two parameters that need to be set during the commissioning process the Node Address and Baud Rate IMPORTANT If the tool you are using to commission the DNI is connected to the DNI with a point to point connection Example a 1770 KFD connected directly to the DNI without any other devices the commissioning tool must not be set to Autobaud The DNI out of box configuration is set to Autobaud If both devices are set to Autobaud they may hunt and never find each other TIP For DNI Series B you will be able to commission the DNI via the RS 232 port This can be done using the DNI Configuration Software Utility version 2 001 when available For applications that use only DNIs this will eliminate the need for configuration tools such as RSNetWorx and the 1770 KFD Interface You can simply use an RS 232 cable Follow these steps to commission the DNI 1 Connect the DNI to a PC through
14. Overview Publication 1761 UMO005B EN P October 2006 Configure Peer to peer Messaging Chapter 2 Quick Start This chapter can help you to get started using the 1761 NET DNI DeviceNet Interface DND We base the procedures here on the assumption that you have an understanding of MicroLogix products You should understand electronic process control and be able to interpret the ladder logic instructions required to generate the electronic signals that control your application Because this is a start up guide for experienced users this chapter does not contain detailed explanations about the procedures listed It does however reference other chapters in this book where you can get more information If you have any questions or are unfamiliar with the terms used or concepts presented in the procedural steps always read the referenced chapters and other recommended documentation before trying to apply the information Follow these steps to communicate with other controllers connected to DNIs on a DeviceNet network 1 Unpack and mount the DNI 2 Connect the DNI to the DeviceNet network When power is first applied to the DNI it resides at node 63 on the network The DNI out of box configuration is defaulted to Autobaud it synchronizes to the DeviceNet network baud rate 3 Connect a DF1 device to the DNI The DF1 connection automatically enters the Autobaud mode it synchronizes to the attached DF1 device 4 Conn
15. Series B DNI Electronic Data Sheet 1761DNI3 EDS DNI Configuration Software Utility DNIUTIL1 EXE Rev 2 0 or higher DNI Icon for Configuration Software 1761DNI ICO or 1761DNIB BMP Series A DNI Electronic Data Sheet 1761DNI2 EDS DNI Configuration Software Utility DNIUTIL1 EXE DNI Icon for Configuration Software 1761DNI BMP ATTENTION DNI Series A configurations are not compatible with DNI Series B You must manually re enter the Series A parameters into the Series B DNI This step is required because of the enhanced functionality of DNI Series B Publication 1761 UMO005B EN P October 2006 54 Setup Programming and Troubleshooting Publication 1761 UMO005B EN P October 2006 TIP DNI Series A stopped shipping in June of 1999 DNI Series B started shipping in July of 1999 File Descriptions File Description DNI Electronic Data This is a text file that is compatible with A B network configuration Sheet software This file along with the 1761DNI BMP or 1761DNI ICO file must be installed using the EDS import utility built into your network configuration software DNI Icon for This is a bitmap that is used to graphically illustrate the DNI in your Configuration configuration software For RSNetWorx use 1761BMPICO For Software DeviceNet Manager use 1761DNI BMP The DNI Configuration Software Utility includes the DNI icon files DNI Configuration The 1761 NET DNI configur
16. a DeviceNet interface device 1770 KFD 1784 PCD 2 Execute mini who screen to locate the target DNI 3 If DeviceNet Autobaud is disabled enter the DeviceNet baud rate 4 Enter the node address to be configured 5 Apply changes Status is shown in status bar 6 Save changes Setup Programming and Troubleshooting 59 Programming Over the DeviceNet Network IMPORTANT IMPORTANT Configuring the baud rate is needed only when DeviceNet Autobaud is disabled The default out of box setting for DeviceNet Autobaud is enabled The new baud rate takes effect on power cycle or when DNI is reset Use caution when changing the baud rate on an active network The DNI provides the ability to upload download or monitor the ladder logic program of controllers connected to a DNI on the network Computer with DNI Follow these steps to upload download or monitor over the network 1 Connect a commissioned DNI to the RS 232 port on a computer as shown under Local Access to a DeviceNet Network on page 21 2 Set the communications in the configuration software to DF1 full duplex 3 Select the DeviceNet address of the destination DNI You can now upload download monitor over the network The functionality over the network is determined by the destination device If the destination device is a MicroLogix 1000 controller you cannot perform on line editing If the destination device is an SLC 5 03
17. controllers Added note that remote access to a DeviceNet network is 22 available only with RSLogix 5 500 based controllers Publication 1761 UMO005B EN P October 2006 4 Summary of Changes Publication 1761 UMO005B EN P October 2006 Overview Quick Start Operation Installation and Wiring DNI Configuration Parameters and Programming Notes Setup Programming and Troubleshooting Table of Contents Preface About This Publication wu c 1 5 73 Yol d adonde ede thn eon 7 Who Should Use This Publication va s RECTA 7 C ven onS 4 gun ord Rae puc rp ge bet ds a pez tid pea 7 Additional RESOULCES pio coh ise Deu Rp he EU oed de bs ee pes 8 Chapter 1 IO OCMCHOR uo acea ERO UY OR EU EROR aia Ito ha 9 Operating MOdeSSe tus mrs pag kh Gs hee ees E IESSES Be 9 Device Compatibility aoaaa aaa 9 Chapter 2 Configure Peer to peer Messaging 005 11 Configuring Master Slave I O ccce dy ON ea ep ee d 13 Chapter 3 Modes f Usei e a qu n Eee CPC ETE RUP a ee ete s 17 DeyiceNet DIOE oce ub seek dose vet ipit tt ated alte ca doth a tu er E 17 Network Configuration Software 1x Ludo ao ean p ecc ped 18 Messaging Services iesu RR UU DX e vv ERE 19 Programming Over the DeviceNet Network 21 Chapter 4 European Communities EC Directive Compliance 23 Safety Considerations ey ped VR eo ees ee eE SEE 24 Mounting hol Se neh cx UTE dp Sag a 24 Network Port Wiring 40s cet
18. example the light tower The size specified in the DNI s profile register is in bytes The data being sent by the controller is in words In this example N7 0 contains the profile register to be used 241 Location N7 1 contains the data to be sent to the light tower Explicit Messaging DNI Series B Only 83 The message instruction setup screen is shown below EITIETHEREEUET S lol x This Controller r Control Bits Communication Command 500CPU Write Ignore if timed out T0 0 Data Table Address Size in Elements Awaiting Execution EW 2 Channel Error ER 0 Message done DN fo Message Transmitting ST o Message Enabled EN bo Target Device Message Timeout Data Table Address Local Node Addr dec 250 E octal 372 Local Remote e The actual data portion of the controller s write message N7 1 must match the size parameter in the respective profile register In this example e the size of profile register 241 is 1 e the controller s write message has a length of 2 the first word identifies the profile register to be used the second word is the actual data To verify that this is a valid routing profile we see that the data portion of this message is 1 which corresponds to the profile s size of 1 So this example is valid If the sizes do not match the controller s write message will result in an error Publication 1761 UMO0
19. hd a eed dea et UR os 26 Cable Selection Guides Ves nnna Ga EDM Eee REO Ee eS 26 Chapter 5 Information About DNI Series B dad tede d sed 27 EDS Parameters for the DNE esque cem eed ed 28 Programming Notes i o ba oso rs du as e POR e Reg 49 Chapter 6 DNI Software Files lt 9 4 54 4 iHe i BIDEN SS Ne 53 Setting Up Network Configuration Software 55 Commissioning the DNI 4s Rope b TAO A ROK A 58 Programming Over the DeviceNet Network 59 Modifying DNI Parameters sese 60 Troubleshooting v us oS a eiie erat e gom ats odd 62 Fault COH Sos ac en dar dr s am NU EUR c a deed d 64 DNI Series A DeviceNet Class Codes llle 65 DNI Series B DeviceNet Class Codes isses 66 Publication 1761 UMO005B EN P October 2006 Table of Contents 6 Application Examples Explicit Messaging DNI Series B Only Specifications Index Publication 1761 UMO005B EN P October 2006 Chapter 7 MicroLogix as I O on the DeviceNet Network 69 Example DNI Configuration Parameters 70 Example Ladder Logic aua qq dee ede ed OP Ee A 71 Chapter 8 Using DF1 Protocol for Explicit Messages Over a DeviceNet INCUSVOTIG ah aed SX terit e eec E ONS a he Dea 78 Routing Profile Configuration lees 79 Explicit Messaging Ex mples oana naaa 80 Appendix A Physical Specifications uon red dA a SCR Se p CAD 85 DeviceNet Specifications esee s go d e e be Cd 85 DIMENSIONS ch
20. more valid established connections This can be either I O or Messaging Flashing Red Connection I 0 connection s are in the timed out state Time Out Red Critical Link Failure Failed communication device The DNI has detected an error that has rendered it incapable of communicating on the network Bus Off error If the error is Duplicate MAC ID the DNI only communicates via the Group 4 off line connection set Flashing Red Green Communication A specific communication fault recovery Faulted stage or self test Normal condition RS 232 Port LED Indicator The DNI has a green LED next to the RS 232 connector to provide communications activity status The LED is lit whenever data is being transmitted or received When communications are occurring this LED will appear to be flashing The following table defines causes of faults in the DNI MOD LED NET LED Fault Condition DeviceNet Standard Fault Available Recovery Options Solid Red Not Applicable Self Test Failure Module Major Unrecoverable Fault Power Cycle Flash Red Not Applicable Invalid Configuration Module Minor Recoverable Fault Modify Invalid Parameter Parameter Flash Red Not Applicable EEPROM Invalid Module Major Recoverable Fault Re commission the DNI Not Applicable Solid Red Duplicate Node Detected Communication Fault Power Cycle Group 4 Fault Recovery Not Applicable Solid Red Bus Off Error Communication Fault Power Cycle set b
21. on a DeviceNet network RS 232 Port DeviceNet Connection RS 232 DeviceNet DF1 n DNI Module Upload Download E Monitoring E MicroLogix DNI Configuration Controller Publication 1761 UM005B EN P October 2006 22 Operation Remote Access to DeviceNet Modems IMPORTANT Remote access to a DeviceNet network via the DNI is available only with RSLogix 5 500 based controllers such as PLC 5 SLC and MicroLogix If users need to dial into a DeviceNet network and have access to controllers connected to DNIs they can plug a DNI into a modem Now users can dial into the modem and have access to all DNI controllers from a remote site Remote Access to DeviceNet DeviceNet Cable i Modem MicroLogix Controller Publication 1761 UM005B EN P October 2006 European Communities EC Directive Compliance Chapter Installation and Wiring This product has the CE mark and is approved for installation within the European Union and EEA regions It has been designed and tested to meet the following additional directives EMC Directive This product is tested to meet the Council Directive 89 336 EC Electromagnetic Compatibility EMC by applying the following standards in whole or in part documented in a technical construction file e EN 50081 2 EMC Generic Emission Standard Part 2 Industrial Environment e EN 50082 2 EMC Generic Immunit
22. or later or PLC you can edit on line IMPORTANT With a computer connected to a DNI you cannot configure devices on the DeviceNet network You cannot use the DNI as a replacement for a 1770 KFD Publication 1761 UM005B EN P October 2006 60 Setup Programming and Troubleshooting Modifying DNI Parameters Publication 1761 UMO005B EN P October 2006 Computer on DeviceNet Network You must have RSLinx version 2 O or newer to upload download or edit controller programs directly over DeviceNet using a 1770 KFD 1784 PCD 1784 PCID or equal 1 Open RSLinx and select Configure Drivers 2 Select DeviceNet Driver from the list 3 Click Add New 4 Open your configuration software and make sure it recognizes and is configured to use RSLinx DeviceNet driver 5 In the configuration software s communications section select the destination DNI that you want to connect to Use the main configuration to set or change any of the DNI parameters Disable Polling Enable while you are making changes When you are finishing click Save to File and Save to DNI E Allen Bradley Close Cs DNI Configuration Utility Help Configuration Wizard Set to EDS Defaults Load from File r DeviceNet Interface Node Address 2 AutobaudEnable V Explicit Message Timeout 0 2500 Data Rate 500k m m DF1 Full Duplex Interface Polling Delay 20 3000 fsa incr by 10 m incr by IB
23. set up and modify parameters see Setup Programming and Troubleshooting on page 53 DNI Configuration Parameters and Programming Notes 43 DF1 Heartbeat DF1 Heartbeat Parameter Definition Parameter Parameter Number Description Default Type Value Series A Series B 12 13 DF1 Heartbeat Series A 2 10 Series B 1 10 The DF1 data heartbeat is used to detect a valid communications path between the controller and the DNI and also to detect if the connected controller is scanning its ladder logic The heartbeat is enabled when e DNI Series A Data Enable is enabled and DNI Mode is operational e DNI Series B I O Scan Enable is enabled The heartbeat consists of a bit in the first byte byte 0 bit 7 of the data packet that is exchanged with the controller The DNI sets this bit in the output data being sent to the controller The user must move this bit using ladder logic to the corresponding bit position in the input data area where the bit is then read from the controller by the DNI At the heartbeat rate once the DNI sees the bit return in its correct state it toggles the bit to the opposite state and sends it back to the controller this is a round robin process If the bit state does not change it is detected as a communication controller error and reported to the DNI master as a zero length packet Refer to your scanner or master controller documentation to determine how this is detected i
24. with its new DeviceNet messaging capability See page 77 for Explicit Messaging DNI Series B Only Publication 1761 UM005B EN P October 2006 20 Publication 1761 UMO005B EN P October 2006 Operation Programmable Controller Communications Commands PCCC DeviceNet Messaging DF1 peer to peer Allen Bradley controllers with RS 232 ports communicate via PCCC messaging The DNI encapsulates the PCCC messages to allow PCCC messaging to operate over DeviceNet This is an open non proprietary protocol that can be implemented by anyone who needs to exchange information with an Allen Bradley controller The DNI is capable of receiving the DF1 protocol and sending or receiving it over DeviceNet This enables any existing Allen Bradley device that is capable of DF1 communications to an Allen Bradley controller to use the DNI to communicate over DeviceNet For DNI Series A the only stipulation is that the device has to be capable of entering a destination node address For DNI Series B this stipulation has been removed with the addition of the DF1 Substitute Address parameter The DNI uses the DF1 destination node address that is embedded in the DF1 packet to determine where on DeviceNet it needs to send the information This DF1 to DeviceNet capability lets you configure a peer to peer network By programming standard ladder logic message instructions with the destination address the same as the destination DNI when not usi
25. 05B EN P October 2006 84 Explicit Messaging DNI Series B Only Publication 1761 UMO005B EN P October 2006 Physical Specifications DeviceNet Specifications Appendix A Specifications Description Specification 24V dc Power Source Required 11 25V dc Current Draw 200 mA at 24V dc 350 mA at 11V dc 400 mA maximum inrush for 30 ms at 24V dc Internal Isolation 500V dc Ambient Operating Temp 0 C 60 C 432 F 140 F Storage Temperature 40 C 85 C 40 F 175 F Agency Certification UL 1604 C UL C22 2 No 213 Class I Division 2 Groups A B C D CE compliant for all applicable directives ODVA Conformance Version 2 0 Feature Y N Comments Peer to Peer Messaging Y Only to other Controllers DNI s 1 0 Assembly Explicit Y Output sets only when 1 0 connection set is Messaging unowned 1 0 Peer to Peer Messaging N also known as Dynamic 1 0 UCMM Y Configuration Consistency Y Value Deferred Delete Y Faulted Node Recovery Y DeviceNet Auto Baud Y Flash Upgradeable N Baud Rate All 125K 250K 500K Master Scanner N 1 0 Slave Y Bit Strobe N Polling Y COS change of state Y Flat cable TBD Publication 1761 UM005B EN P October 2006 86 Specifications Dimensions 52 07 mm 2 05 in 118 mm 4 64 in y e a Tu 27 7 mm 64 8 mm Allow 15 mm 0 6 in 1 09 in 2 55 in
26. 3 getting started 11 mounting 24 mounting template 87 Publication 1761 UMO005B EN P October 2006 94 Index network port wiring 26 safety considerations 24 setting up network configuration software 53 L LED module status 63 network status 64 RS 232 port 64 master slave I 0 configuration 13 message timeout 46 modes of use 17 DeviceNet 0 17 explicit messaging 17 programming over DeviceNet network 17 mounting DIN rail mounting 24 enclosure 23 mounting template 87 panel mounting 25 0 ODVA 85 operating modes 9 operation 17 output image 18 output size 35 output split point 36 output type 35 output word offset 39 P parameter data enable 41 data scan delay 45 device type 41 DeviceNet autobaud 48 DF1 autobaud 47 DF1 baud rate 48 DF1 heartbeat 43 DF1 substitute address 47 DNI mode 27 49 I O scan enable 41 Publication 1761 UMO005B EN P October 2006 input data file 33 input size 29 input split point 30 input type 33 input word offset 34 message timeout 46 output size 35 output split point 36 output type 38 output word offset 39 polling delay 45 polling enable 41 peer to peer messaging configuration 11 polling delay 45 polling enable 41 product overview description 9 programming notes 49 programming over DeviceNet 21 59 computer on DeviceNet 60 computer with DNI 59 local access 21 remote access 22 routing profile 78 configuration 79 RSNetWorx 55 61 S safety considerat
27. Messaging DNI responds e PCCC encapsulated DeviceNet Messaging peer to peer e Explicit Assembly Messaging DNI initiates DNI Series B Only See Explicit Messaging DNI Series B Only on page 77 for more information 1 0 Assembly Messaging Two conditions must be met to access the I O assemblies e Data Enable DNI Series A or I O Scan Enable DNI Series B must be enabled e The DF1 Device must be servicing the Heartbeat See DF1 Heartbeat on page 43 for information on using the Heartbeat The following sections describe additional conditions based on the DNI Series DNI Series A DNI Series A supports explicit messaging to the master I O assemblies over DeviceNet at a minimal level If the DNI is not owned by a DeviceNet master the DNI responds to explicit messaging gets and accepts explicit messaging sets to the master I O assembly If the DNI is owned by a DeviceNet master it responds to gets but cannot accept sets In either case the data size must be 16 words even if the I O size is smaller See page 65 to address DNI Series A assemblies DNI Series B DNI Series B provides the above described functionality except the data size is equal to the configured I O size Additionally DNI Series B can respond to explicit messages over DeviceNet to its explicit I O assemblies whether it is owned by a DeviceNet master or not See page 66 to address DNI Series B assemblies DNI Series B can also perform get set services
28. NI Heartbeat Bit from DNI Off to On Memory DNI Heartbeat Pulse On Detected N7 95 B3 31 _ B3 31 J OSR C 7 15 14 This rung detects an on to off transition of bit N7 95 7 Bit N7 95 7 is the communication s Heartbeat that is received from the DNI Heartbeat Bit from DNI On to Off Memory DNI Heartbeat Pulse Off Detected N7 95 B3 31 B3 31 it L OSR lt gt 7 13 12 This rung resets the communications watchdog whenever the DNI Heartbeat changes state off to on or on to off DNI Heartbeat Pulse On Detected DNI Communications Watchdog B3 31 T4 39 JE C RES gt 14 DNI Heartbeat Pulse Off Detected B3 31 EE Jj L 12 Timer 39 is the communications watchdog for DNI MicroLogix communications If this timer ever times out the outputs directly controlled by the MicroLogix turn off This timer is constantly being reset by the status of bit N7 95 7 toggle on toggle off Bit N7 95 7 is controlled by communications received from the DNI The amount of time preset the timer should be set to is dependent on the DF1 Heartbeat Data Scan Delay and the baud rate of the RS 232 port Using this logic with a Series D MicroLogix 1000 controller set 14 39 to a preset value of 350 ms If communications are lost with the DNI the MicroLogix 1000 turns off its outputs after 350 ms TON Timer On Delay CEN gt Timer T4 39 Time Base 0 01 CDN 5 Preset 350 Accum 22 TIP Subroutine 6
29. Revision 0x04 STRUCT of Get Major Revision USINT Get 2 Minor Revision USINT Get 1 Status 0x05 WORD Get N A Serial Number 0x06 UDINT Get N A Product Name 0x07 SHORT STRING Get 1761 NET DNI Setup Programming and Troubleshooting Input Assembly Data Explicit Split Point and Slave Class Code 0x04 67 Name Access Instance Data Attribute Inputs Type Value Slave Assembly Get Set Input 100 64h 3 Input Split Point 1 Explicit Assembly Get Set Input 102 66h 3 Explicit word 0 Get Set Input 112 70h 3 Explicit word 1 Get Set Input 113 71h 3 Explicit word 2 Get Set Input 114 72h 3 Explicit word 3 Get Set Input 115 73h 3 Explicit word 4 Get Set Input 116 74h 3 Explicit word 5 Get Set Input 117 75h 3 Explicit word 6 Get Set Input 118 76h 3 Explicit word 7 Get Set Input 119 77h 3 Explicit word 8 Get Set Input 120 78h 3 Explicit word 9 Get Set Input 121 79h 3 Explicit word 10 Get Set Input 122 7Ah 3 Explicit word 11 Get Set Input 123 7Bh 3 Explicit word 12 Get Set Input 124 7Ch 3 Explicit word 13 Get Set Input 125 7Dh 3 Explicit word 14 Get Set Input 126 7Eh 3 Explicit word 15 Get Set Input 121 7Fh 3 Explicit word 16 Get Set Input 128 80h 3 Explicit word 17 Get Set Input 129 81h 3 Explicit word 18 Get Set Input 130 82h 3 Explicit word 19 Get Set Inp
30. The DNI supports data exchange with either bit or integer files SeriesA Series B DNI Configuration Parameters and Programming Notes 39 Output Data File Parameter Parameter Number Description Default Type Value 1 0 0 o 9 Output Data File 3 254 7 This parameter is used to identify the target data file where data will be written within the controller Series A Series B The sizes of compatible data files within Allen Bradley controllers vary based on the DFI device selected Controller Data Files Controller Output Data Files File Sizes MicroLogix 1000 Bit 3 Integer 7 SLC Other MicroLogix Bit 3 10 255 Integer 7 9 255 PLC Bit 3 10 999 Integer 7 9 999 TIP The DNI can access only files 3 254 Output Word Offset Parameter Parameter Number Description Default Type Value 1 0 Output Word Offset 0 254 1 This parameter identifies the starting word within the output file identified by the Output Data File parameter The value entered is the first word of data that is written to the controller attached to the DNI Series A Series B Publication 1761 UMO005B EN P October 2006 40 DNI Configuration Parameters and Programming Notes Publication 1761 UMO005B EN P October 2006 The sizes of compatible data files within Allen Bradley controllers vary based on the DFI device selected Controller Data Files Controller Outp
31. ality of each device determines how it can interact with other devices on the network Many devices can respond only to requests Some devices can be configured to respond but they can also initiate messages to others One example is the PanelView operator interface that has DeviceNet technology built in It can be owned by a master as slave I O and can also get or set data to other devices on the network Publication 1761 UMO005B EN P October 2006 78 Explicit Messaging DNI Series B Only Using DF1 Protocol for Explicit Messages Over a DeviceNet Network Publication 1761 UMO005B EN P October 2006 The Series B DNI also has the ability to exchange data with other DeviceNet devices using explicit messaging provided those devices are capable of interacting The following list provides some of the requirements e If a device is Unconnected Message Manager UCMM capable it should be 100 percent compliant with or without a master being present on the network e If a device is not UCMM capable it will need a master to be present on the network and it should be owned by the master e If a device is not UCMM capable and a master is not present or a master is present but the device is not owned by the master the device will not be compatible with the DNI using explicit messaging The DNI is an intelligent bridge between DF1 full duplex Allen Bradley open protocol and DeviceNet All Allen Bradley controllers that use DF1 pr
32. ation utility can be used to configure all Software Utility 1761 NET DNI parameters and also to commission set node number and baud rate of other DeviceNet compatible products for operation on a DeviceNet Network This utility makes configuring a 1761 NET DNI easier through the use of intuitive screens and Wizards Obtaining the Files These files are routinely incorporated into your network configuration software If they are not in your version of configuration software these files are available from a number of sources e Local Allen Bradley distributor e Local Allen Bradley Sales Office e Via the Internet at http www ab com micrologix Setup Programming and Troubleshooting 55 Setting Up Network Configuration Software To configure the DNI you must set up your network configuration software and follow the configuration procedures The initial set up is only performed once After the files have been saved by your network configuration software they are stored on the computer Setting Up DNI Configuration Software Utility No initial set up is required to use the DNI Configuration Software Utility Setting Up RSNetworx With RSNetworx open install 1761DNI2 EDS for DNI Series A 1761DNI3 EDS for DNI Series B and 1761DNLICO using the EDS install utility Gn the Utilities menu of RSNetworx Follow these steps to load both DNI files into RSNetWorx 1 Start RSNetWorx 2 With RSNetWorx open select the View Tools
33. ble of accepting an unsolicited Input Data Message from the DF1 device This capability allows the controller to update the DNI s input data whenever it detects a change in its input data With this capability a user can increase the value of the data scan delay this reduces the amount of communications traffic over the RS 232 DF1 port but still maintains very high I O throughput performance To utilize this feature simply program a message instruction in the controller with a destination address of 254 The DNI accepts the message and when it sees the 254 address which is invalid on DeviceNet it recognizes that the message is input data All data received by message instruction with address 254 is automatically routed to the DNI s input data area See the application example MicroLogix as I O on the DeviceNet Network on page 69 for more information about input messaging Publication 1761 UMO005B EN P October 2006 50 DNI Configuration Parameters and Programming Notes Publication 1761 UMO005B EN P October 2006 Input Messaging Considerations e You cannot write to a specific word in the DNI s input area e The destination offset value in the controller s message instruction is ignored Data always starts at word 0 e The message length must equal the size specified by the Input Size parameter For DNI Series B only both the Master s Slave data and the Explicit Assembly are considered to be input For more information see
34. bled 0 or Enabled 1 Autobaud Enabled 1 The DNI automatically synchronizes to the DeviceNet network that it is attached to 125K 250K or 500K baud To disable this feature set DeviceNet Autobaud to disable 0 When set to disable the DNI uses the DeviceNet baud rate configured during the node commissioning process Therefore when the DeviceNet Autobaud is disabled the baud rate the DNI is set to may be different than the DeviceNet network baud rate ma hen parameter is disabled 0 the baud rate is set using the node commissioning utility in your network configuration software and is not set by the DNI s EDS file IMPORTANT ad cycle the DNI for baud rate changes to take effect Publication 1761 UMO005B EN P October 2006 DNI Configuration Parameters and Programming Notes 49 Programming Notes DNI Mode DNI Mode Parameter Definition Parameter Parameter Number Description Range Default Value Type Device 17 n a DNI Mode Standby 0 or Operational 1 Operational 1 TTTHTUM The DNI Mode parameter only applies to DNI Series A For DNI Series B the operating mode is controlled by the I O Scan Enable parameter Series A Series B This parameter defines the mode of the DNI You must set this mode to Standby 0 when you want to change a number of DNI parameters Once you have made the necessary changes set this value to Operational 1 Input Messaging The DNI is capa
35. ction has N7 10 identified as the data table address so the sensor data will appear in low order byte of N7 10 The message instruction setup screen is shown below gt MSG MG11 0 1 Elements This Controller Control Bits Communication Command 500CPU Read Ignore if timed out T0 0 Data Table Address N7 10 Size in Elements Awaiting Execution EW 2 Channet 0 Error ER 2 Target Device Message done DN 0 Message Timeout Message Transmitting ST 0 Data Table Address Message Enabled EN 0 Local Node Addr dec octal Local Remote Publication 1761 UMO005B EN P October 2006 82 Explicit Messaging DNI Series B Only Publication 1761 UMO005B EN P October 2006 Writing Set Data Example In this example we want to write data to the light tower at node 20 The light tower has specific parameters that are accessible via the DeviceNet network In this example profile register 241 within the DNI node 10 has been configured to set data in the light tower DNI Profile Register 241 e DeviceNet Node 20 e Class 9 e Instance 1 e Attribute 3 e Size 1 byte Node 10 To set DeviceNet data a write message is initiated from the controller to node address 250 The first data word of the write message identifies which profile register to use 240 249 The remaining data words in the message contain the data that is transmitted to the DeviceNet device in this
36. d 47 Applicable Address DF1 15 17 DF1 Autobaud Disabled 0 or Enabled 1 47 Enabled 1 DF1 16 18 DF1 Baud Rate 0 5 Series A 2 9600 48 0 38 400 Series B 1 19 200 1 19 200 2 9600 3 4800 4 2400 5 1200 DeviceNet 1 19 DeviceNet Autobaud Disabled 0 or Enabled 1 48 Enabled 1 Device 17 Not DNI Mode Standby 0 or Operational 1 49 Applicable Operational 1 Input Size Input Size Parameter Definition Parameter Parameter Number Description Range Default Type Series Series B Value A 1 0 4 1 Input Size Series A 1 16 1 Series B 1 32 This parameter identifies the size in words of the data array that is read from the controller attached to the DNI s RS 232 port TTE or DNI Series B you must also configure the Input Split Point See Input Split Point on page 30 The array may contain up to 16 16 bit words of data for DNI Series A 32 words for DNI Series B from a contiguous block within the attached controller Publication 1761 UMO005B EN P October 2006 30 DNI Configuration Parameters and Programming Notes Publication 1761 UMO005B EN P October 2006 The first byte byte 0 of the first word contains the status byte and is not available to the user Input Size Sample Data Array Word Input Image Series A Series B 0 0 Data 8 bits Status 1 1 Data Most Significant Byte Data Least Significant MSB Byt
37. data array is shown below Sample Data Array Word Ouptlmageg gt tst lt i sSOSCS Series A Series B 0 0 Data 8 bits Status 1 1 Data Most Significant Byte Data Least Significant MSB Byte LSB 2 2 Data MSB Data LSB 3 3 Data MSB Data LSB f f f f 14 30 Data MSB Data LSB 15 31 Data MSB Data LSB TIP Byte 1 MSB of word 0 is available for user data TIP For information on the Status Byte byte 0 see the Status Byte section on page 50 Output Split Point Parameter Parameter Number Description Default Type Value Teta The Output Split Point parameter cannot be used with DNI Series A Series A Series B The Output Size within the DNI is configurable from 1 32 words The Output Split Point defines how much data is configured as Master Slave I O and how much data is configured for explicit assembly messaging DNI Configuration Parameters and Programming Notes 37 Organization of Qutput Data The following diagram describes how the Split Point parameter affects the data in the DF1 Device The split point represents the last word of the Master data Words above the split point are Explicit data Output Data Organization DNI Device DF1 Device Hanes Addresses most significant word Explicit Output Explicit Assembly Outputs asesanti word Output Split east significant wor File Point most significant word Size Ma
38. dou quibue Dee ee DUE EU SP n obe eel 86 Glossary Interface BASICS L6G eg mac wif 1 dose Pire Ro ba ee Ge 89 Terms and Abbreviations vdd EO Go P Oe S Rn 89 About This Publication Who Should Use This Publication Conventions Preface This user manual introduces the DeviceNet Interface DND and explains the procedures you need to install configure and commission the interface Use this manual if you are responsible for designing installing programming or troubleshooting control systems that use Allen Bradley controllers on a DeviceNet network You should have a basic understanding of Allen Bradley programmable controllers and DeviceNet technology You should understand programmable controllers and be able to interpret the ladder logic instructions required to control your application If you do not contact your local Allen Bradley representative for information on available training courses before using this product Text that is Identifies Bold Emphasis not used within programming text Italic Software variables and configurable catalog numbers courier Example programming code shown in a monospace font so you can identify each character and space Publication 1761 UMO005B EN P October 2006 8 Preface Additional Resources Resource MicroMentor publication 1761 RM001 Description Information on understanding and applying micro controllers AlC Advanced Interface Converter and DeviceNet I
39. e LSB 2 2 Data MSB Data LSB 3 3 Data MSB Data LSB l l V Y 14 30 Data MSB Data LSB 15 31 Data MSB Data LSB TIP Byte 1 MSB of word 0 is available for user data TIP For information on the Status Byte byte 0 see the Status Byte section on page 50 Input Split Point Input Split Point Parameter Definition Parameter Paremeter Number Description Range Default Type SeriesA Series B ET Value fo v p mes ox T TTTDTUMO The Input Split Point parameter cannot be used with DNI Series A The Input File Size within the DNI is configurable from 1 32 words The Input Split Point defines how much data is configured as Master Slave I O and how much data is configured for explicit assembly messaging DNI Configuration Parameters and Programming Notes 31 Organization of Input Data The following diagram describes how the Split Point parameter affects the data in the DF1 Device The split point represents the last word of the Master data Words above the split point are Explicit data Organization of Input Data DNI Device DF1 Device aight Addresses most significant word Explicit Input AN Assembly nputs PD nput Split least significant word File Point Jo most significant word Size Master Input Master s Assembly Inputs least significant word Lower Addresses Input Split Point Example We need 4 3 5 data 0 5 status words of slave data that the master will own and we need
40. ect to the DNI with your network configuration tool software such as the DNI Configuration Utility RSNetWorx or DeviceNet Manager and set the DNI to the desired node number This is called commissioning the DNI See Commissioning the DNI on page 58 for more details Publication 1761 UMO005B EN P October 2006 12 Quick Start Publication 1761 UMOOBB EN P October 2006 IMPORTANT If your network consists entirely of DNIs no master is present you must disable Autobaud on at least one DNI It is recommended that all DNIs be manually set to a specific baud rate This is to prevent multiple DNIs from hunting for a baud rate at power up 5 To exchange data with other controllers over a DeviceNet network configure a message instruction inside each controller s program See Programming Over the DeviceNet Network on page 21 for more information 6 To send data to a specific controller on the network enter the destination DNI s DeviceNet node address into the destination parameter of a message instruction Think of each DNI Controller pair as one unit To send a message from controller A plugged into DNI number 5 to controller B plugged into DNI number 10 controller A must have a message instruction with a destination node address of 10 See the application example MicroLogix as 1 0 on the DeviceNet Network on page 69 for an example ladder program Quick Start 13 Configuring Master Slave 1 0 You mu
41. een DNI Series A For DNI Series A only the device may be Device in Standby DNI Series B Device Not Scanning in Standby Mode set to operational For DNI Series B 1 0 Scan Polling Enable may need to be set 1 Flashing Red Minor Fault Recoverable fault DNI may need to be commissioned the DNI will not operate when set to the out of box defaults The device needs commissioning due to missing incomplete or incorrect configuration EEPROM may be corrupt re commission the DNI Red Unrecoverable Fault The device has an unrecoverable fault which requires the power to be cycled or the DNI may need to replaced Flashing Red Green Device Self Testing The device is in self test and should occur only at power up or reset Normal condition Publication 1761 UMO005B EN P October 2006 64 Setup Programming and Troubleshooting Fault Conditions Fault Conditions Network Status LED NET LED The network status LED provides information specific to the DeviceNet network Network Status LED LED Condition DNI State Problem Indication Off Not Powered Not DNI is not on line On Line e DNI has not completed the Dup MAC ID test yet e DNI may not be powered Flashing Green On Line Not DNI has passed the Dup MAC ID test is Connected on line but has not established connections to other nodes Green On Line Connected The DNI has one or
42. er Number Description Default Value Type SeriesA Series B mo p CE This parameter is used to identify the data file to be read within the controller The following table shows the files within Allen Bradley controllers Controller Input Data Files Number Values MicroLogix 1000 Bit 3 Integer 7 SLC Other MicroLogix Bit 3 10 255 Integer 7 9 255 PLC Bit 3 10 999 Integer 7 9 999 TIP The DNI can access only files 3 254 Publication 1761 UMO005B EN P October 2006 34 DNI Configuration Parameters and Programming Notes Publication 1761 UMO005B EN P October 2006 Input Word Offset Parameter Number Description Range SeriesA Series B This parameter identifies the starting word within the input file identified by the parameter Input Data File The value entered is the first word of data that is read from the controller attached to the DNI Parameter Default Value Type The sizes of compatible data files within Allen Bradley controllers vary based on the DFI device selected Compatible Data File Sizes Controller Input Data Files File Size MicroLogix 1000 Bit 32 Words Integer 105 Words SLC Other MicroLogix Bit 255 Words Integer 255 Words PLC Bit 999 Words Integer 999 Words TIP The DNI can only access files 3 through 254 Trotter ia You must have sufficient room in the file that you select Make sure the Input Word Offset plus the Input Size d
43. for DNI Series A 1761DNIB BMP for DNI Series B using the EDS install utility Gn the Utilities menu of DeviceNet Manager Follow these steps to load both DNI files into DeviceNet Manager 1 2 3 Start DeviceNet manager With DeviceNet manager open select the Utilities Menu Select Install EDS Files Locate 1761DNI2 EDS for DNI Series A 1761DNI3 EDS for DNI Series B on your computer Highlight and load electronic data sheet into the software Confirm the prompt to attach a bitmap Locate 1761DNI BMP 1761DNIB BMP for DNI Series B on your computer Highlight and load bitmap into the software DeviceNet manager is now set up to recognize and configure the DNI To locate 1761 NET DNI in DeviceNet managers file list double click on the following folders Communications Adapter Allen Bradley Company a DeviceNet Manager DNI1 PC3 File Edit Project Who Utilities View Windc Generic AC Drive General Purpose Discrete I O Software E Communication Adapter LE Allen Bradley Company Inc 1794 ADN DeviceNet Flex 1 0 Adapter 17944DN DeviceNet Flex 1 0 Adapter 1784 PCD PCMCIA Interface 1747 SDN Scanner Module 1747 SDN Scanner Module 1747 SDN Scanner Module 1747 SDN Scanner Module ET 1761 NET DNI Device Net Interface x Publication 1761 UM005B EN P October 2006 58 Setup Programming and Troubleshooting Commissioning the DNI Publication 1761 UMO005B EN P
44. iguration to the DNI In this configuration the DNI provides two words 32 bits of data The data is scanned read starting at address N7 90 of the attached MicroLogix 1000 controller at 100 msec intervals Data received DeviceNet master output is written to the MicroLogix 1000 controller whenever new changed data is detected by the DNI Two words of data will be written to Integer file 7 starting at word 95 IMPORTANT You must have the following rung programmed into the MicroLogix 1000 controller N7 95 N7 90 lt gt 7 At this point the DNI is configured to be a slave on DeviceNet but it is not part of owned by a DeviceNet master scanner To configure your DeviceNet scanner refer to its manual For the 1747 SDN refer to the SLC 500 DeviceNet Scanner user manual publication 1747 UM655 For the 1771 SDN refer to the PLC 5 DeviceNet Scanner user manual publication 1771 UM118 Publication 1761 UM005B EN P October 2006 16 Quick Start Publication 1761 UMOOBB EN P October 2006 Modes of Use DeviceNet I O Chapter J Operation The DeviceNet Interface has three primary features e DeviceNet I O e Explicit Messaging e Programming over DeviceNet network TITIO ll input and output comments are referenced from the perspective of the DeviceNet Master The DNI is capable of being owned by a master on DeviceNet This functionality on DeviceNet is part of the I O class of service
45. in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations Identifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss IMPORTANT Identifies information that is critical for successful application and understanding of the product Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you identify a hazard avoid a hazard and recognize the consequence ATTENTION FTTISN LVZCn Labels may be on or inside the equipment for example a drive or motor to alert people that dangerous voltage may be present PDT vai Labels may be on or inside the equipment for example a drive or motor to alert people that surfaces may reach dangerous temperatures gt PP PP deed Summary of Changes The information below summarizes the changes to this manual since the last revision Revision bars in the margin identify updated information The following changes are included in this version of the document Change Page Added note that programming over a DeviceNet network is 21 available only with RSLogix 5 500 based
46. ions 24 software DeviceNet Manager 18 57 62 DNI Configuration Utility 18 55 RSNetWorx 18 55 61 specifications 85 DeviceNet 85 dimensions 86 physical 85 split point 27 30 36 standby operational parameter 27 49 start up instructions 11 status input status to master device 50 output status to DF1 device 51 status byte 50 substitute address 47 Index 95 T terms 89 troubleshooting LED indicators 62 U UL 85 W wiring 26 cables 24 Publication 1761 UMO005B EN P October 2006 96 Index Publication 1761 UMO005B EN P October 2006 Index 97 Publication 1761 UMO005B EN P October 2006 98 Index Publication 1761 UMO005B EN P October 2006 Rockwell Automation Rockwell Automation provides technical information on the Web to assist you in using its products At http support rockwellautomation com you can Support find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit http support rockwellautomation com Installation Assistance If you experience a problem with a hardware module within the first 24 h
47. l parameter has been removed from the EDS file The operating mode is now controlled by the I O Scan Enable parameter Three new parameters have been added to the EDS file The parameters are DF1 Substitution Address The DF1 Substitution Address allows any DF1 device such as the MicroView to communicate to A B controllers over the DeviceNet network Input Split Point and Output Split Point The split point parameters are used to define how much data is configured as Master Slave I O and how much data is configured for explicit I O assembly messaging ATTENTION DNI Series A configurations are not compatible with DNI Series B You must manually re enter the Series A parameters into the Series B DNI This step is required because of the enhanced functionality of DNI Series B l TIP DNI Series A stopped shipping in June of 1999 DNI Series B started shipping in July of 1999 Publication 1761 UMO005B EN P October 2006 28 DNI Configuration Parameters and Programming Notes EDS Parameters for the DN The following list shows the available parameters for configuring the DNI Parameter definitions and usage information are provided in the sections following the table EDS Parameters for the DNI IMPORTANT When modifying most DNI parameters you must first disable polling Set the Data Enable parameter to disable for DNI Series A Set the I O Scan Enable parameter to disable for DNI Series B You can enable
48. lave assembly and the explicit assembly If the output size parameter 6 is set to 32 and the split point parameter 7 is the minimum size 1 the remaining words are explicit outputs The example above illustrates the maximum amount of explicit outputs that can be configured For more information about using the split point parameter see Input Split Point on page 30 or Output Split Point on page 36 Q OA get of this instance will return the entire set of Explicit Assembly Data Publication 1761 UMO005B EN P October 2006 MicroLogix as 1 0 on the DeviceNet Network Chapter Application Examples All examples are for illustration and information purposes only Because of the many variables and requirements associated with any particular installation Rockwell Automation cannot assume responsibility or liability for the actual use based on the examples and diagrams MicroLogix controllers are incapable of being true slave I O products But they are capable of behaving like slave I O and more by adding logic user program This example turns a MicroLogix controller into an I O block on the DeviceNet network The MicroLogix input data is sent up to the DeviceNet master as input data and the DeviceNet master output data is sent to the MicroLogix outputs The example logic is a user program that monitors the communications link between the MicroLogix and the DeviceNet master and makes sure it is operational If problems occur with
49. lay too low limits access to the controller from other devices on the network If this value is too low programming terminals other controllers and any other devices attempting to communicate with this controller are unable to due so because the RS 232 port communications link bandwidth is being consumed by the I O scan feature of the DNI mtg To move data from the controller to the DeviceNet master as quickly as possible use the DNI s input messaging feature See input messaging on page 49 See the application example MicroLogix as I O on the DeviceNet Network on page 69 for more information about using the Data Scan Delay Publication 1761 UMO005B EN P October 2006 46 DNI Configuration Parameters and Programming Notes Publication 1761 UMO005B EN P October 2006 Message Timeout Message Timeout Parameter Definition Parameter Description Default Type Value The Message Timeout is the amount of time that a DeviceNet explicit connection is held open after message completion The Message Timeout allows the DNI to hold open a connection with another device over the DeviceNet network On a DeviceNet network a connection means that two devices have established a communications path Each time communications need to occur between devices a connection is established when the communications have completed the connection is released Series B The number of connections that each device can support depends o
50. n click on Help Once a parameter is changed or after all parameters are changed click Save to Device Node Name Node 3 Node Address 3 Vendor Allen Bradley Company Inc Product Name 1761 NET DNI Device Net Interface Description Online Build result Set to Defaults Parameters Modify Parameter Status Default Values Parameter Group Start Monitor All Parameters zl N m Name Value 1 DNet Auto Baud Enable Di Load from File 2 Message Timeout Oms 3 Data Enable Disable Load from Device 4 Input Size 1 word s 5 Input Type Integer File 6 Input Data File Number 7 etos 7 Input Word Offset 0 Sapa 8 Dutput Size 1 word s a het EE 3 Dutput Type Integer File 10 Dutput Data File Number 7 Print to Text File j Setup Programming and Troubleshooting 63 Troubleshooting The DeviceNet Interface has three LED indicators LED Indicators LED Module Status LED Color bicolor red green Network Status LED bicolor red green RS 232 LED green Module Status LED MOD LED The module status LED provides information specific to the DNI Module Status LED LED Condition DNI State Problem Indication Off Not Powered The device may not be powered or firmware unable to run Green DNI Series A Device The device is operating in a normal Operational condition DNI Series B Device Scanning Flashing Gr
51. n the design capabilities of each device The DNI has five connections available for messaging The Message Timeout allows the user to tune how a connection behaves after communications have completed You may want to dedicate a connection to a specific node device to maintain a connection This reduces the amount of time needed to re establish communications with the device It is recommended that this value only be changed from the default if communications with another node is constant When the timeout is set the connection is not released back to the system until the timeout expires Gwhere 0 ms means close immediately after use Toi open connection between devices over DeviceNet does not limit or inhibit communications over the network If two devices maintain a connection other devices continue to communicate DNI Configuration Parameters and Programming Notes 47 DF1 Substitute Address DF1 Substitute Address Parameter Definition Parameter Parameter Number Description Range Default Value Type Series A Series B Messaging n a 16 DF1 Substitute 0 64 64 Disabled Address TTTTUM The DF1 Substitute Address parameter cannot be used with DNI Series A If the device that is connected to the DNI is not capable of selecting a DF1 destination address of 0 63 by entering a value in this parameter the DNI automatically routes all DF1 communications to this address with the following excepti
52. n the master logic This bit should also be monitored by the controller attached to the DNI and if the bit does not change in the output image at the heartbeat rate it can be used within the controller to detect a problem with the DNI DeviceNet Master Publication 1761 UMO005B EN P October 2006 44 DNI Configuration Parameters and Programming Notes DF1 Heartbeat Rotation Example The value entered for the heartbeat determines how often the DNI will rotate the heartbeat bit The table below illustrates the heartbeat rotation with the default setting of two heartbeat checked on every other read DF1 RS 232 Port A D EF A DNI s Read Sequence DNI s Write Sequence NI gets reads data from controller NI checks heartbeat and toggles bit ata Scan Delay period D D DNI sets writes data to controller D D NI gets reads data from controller sim OO Pp Data Scan Delay period IMPORTANT The example above does not represent accurate timing relationships Consider the following with the above list e B is done inside the DNI and is completed extremely fast typically less than a millisecond e D is the only consistent time variable the DNI waits for the amount of time specified by the Data Scan Delay parameter e A C and E are variable the time associated with each is dependent on a number of factors baud rate communication errors retries
53. ng DNI Series B address substitution the message is routed across DeviceNet by the DNI The following diagram illustrates the types of messaging Messaging Overview Master Slave 0 Peer to Peer Messaging DeviceNet Network DNI Module Node 1 c cm Running RSLogix 500 and or DeviceNet Manager IBM Compatible LLLIITIT Node 2 Also see Explicit Messaging DNI Series B only on page 80 for DNI Series B Programming Over the DeviceNet Network Operation 21 IMPORTANT Programming over a DeviceNet network via the DNI is available only with RSLogix 5 500 based controllers such as PLC 5 SLC and MicroLogix Local Access to a DeviceNet Network PCCC DF1 messaging allows programming devices to connect to a DeviceNet network and upload download monitor and even edit programs if the controller attached to the destination DNI supports that functionality Rockwell Software RSLogix 500 RSLinx version 2 and higher users can connect directly to the DeviceNet network using a KFD PCD or PCI interface DeviceNet P4 Cable KFD Upload Download Monitoring MicroLogix DNI Configuration Controller You can also use a DNI connected to the computer s RS 232 port to upload download to other controllers connected to DNIs
54. ng information Function Heartbeat Valid Data DeviceNet Node Number Bit Number DeviceNet Node Number Bits 0 5 Whenever the DNI sets writes output data to the DF1 device these six bits contain the DeviceNet address that the DNI is assigned on DeviceNet If the user program needs to know what node number its DNI is configured for program a masked move MVM instruction in the ladder logic to move the node number out of this byte The MVM should have e its destination address located in the controller s integer file e a masked value of 003F e the source address should match the location identified by the Output Word Offset parameter DeviceNet Valid Data Bit 6 The DNI sets this bit 1 to the DF1 device whenever it detects that the DNI s DeviceNet master is on line operational The ladder logic program in the controller should monitor this bit and take any necessary control action DF1 Heartbeat Bit 7 The DNI writes the status of this bit to the controller using the interval set by the DF1 Heartbeat parameter The DNI expects the controller to move the status of bit 7 from the output data area to the input data area The easiest way to accomplish this is by programming an XIC instruction in series with an OTE instruction as shown in the following example Publication 1761 UMO005B EN P October 2006 52 DNI Configuration Parameters and Programming Notes Publication 1761 UMO005B EN P October 2006 E
55. ng message it looks at the destination address and size if it reads 254 for the address and the size is equal to the configured input size it knows the data in the message is input data destined for the DNI For DNI Series B the size includes master and explicit input data The data is then placed into the DNI s input image and is delivered to the DeviceNet master using the polled or COS connection that was configured in the DeviceNet master by the user Application Examples 75 DNI I 0 RSS Ladder 6 COS ML DNI This rung checks to see if the input data has changed from the previous ladder scan If the input data has changed bit B3 31 is set MicroLogix 1000 Inputs Input Data has Changed Flag NEQ B3 31 0000 Not Equal ee Source A 1 0 0 11 341 lt Source B N7 89 341 lt NEQ Not Equal Source A 1 0 1 0 Source B N7 80 0 The Time Out bit TO associated with each message instruction is used to clear the controller s communications buffer and message instruction Setting the TO bit places the controller s communication section in the same condition as when the controller powers up This rung detects if a message instruction is currently being processed and when input data changes the existing message is terminated allowing a new transmission to start It also terminates the message if the message instruction does not complete 14 38 DN MicroLogix to DNI Message Input Data ha
56. nt Explicit Assembly Get Set Output 103 67h 3 Explicit word 0 Get Set Output 144 90h 3 Explicit word 1 Get Set Output 145 91h 3 Explicit word 2 Get Set Output 146 92h 3 Explicit word 3 Get Set Output 147 93h 3 Explicit word 4 Get Set Output 148 94h 3 Explicit word 5 Get Set Output 149 95h 3 Explicit word 6 Get Set Output 150 96h 3 Explicit word 7 Get Set Output 151 97h 3 Explicit word 8 Get Set Output 152 98h 3 Explicit word 9 Get Set Output 153 99h 3 Explicit word 10 Get Set Output 154 9Ah 3 Explicit word 11 Get Set Output 155 9Bh 3 Explicit word 12 Get Set Output 156 9Ch 3 Explicit word 13 Get Set Output 157 9Dh 3 Explicit word 14 Get Set Output 158 9Eh 3 Explicit word 15 Get Set Output 159 9Fh 3 Explicit word 16 Get Set Output 160 AOh 3 Explicit word 17 Get Set Output 161 A1h 3 Explicit word 18 Get Set Output 162 A2h 3 Explicit word 19 Get Set Output 163 A3h 3 Explicit word 20 Get Set Output 164 A4h 3 Explicit word 21 Get Set Output 165 A5h 3 Explicit word 22 Get Set Output 166 A6h 3 Explicit word 23 Get Set Output 167 A7h 3 Explicit word 24 Get Set Output 168 A8h 3 Explicit word 25 Get Set Output 169 A9h 3 Explicit word 26 Get Set Output 170 AAh 3 Explicit word 27 Get Set Output 171 ABh 3 Explicit word 28 Get Set Output 172 ACh 3 Explicit word 29 Get Set Output 173 ADh 3 Explicit word 30 Get Set Output 174 AEh 3 f The split point determines the size of the s
57. nterface Installation Instructions publication 1761 IN002 Mounting instructions for the DeviceNet Interface MicroLogix 1000 Controllers User Manual Information on MicroLogix 1000 Controllers publication 1761 UM003 MicroLogix 1500 Controllers User Manual Information on MicroLogix 1500 Controllers publication 1764 UM001 SLC 500 Modular Hardware Style User Manual Information on SLC Controllers publication 1747 UM011 PLC User Manual publication 1785 UM001 Information on PLC Controllers SLC 500 and MicroLogix 1000 Instruction Set Reference A reference manual that contains status file data and Manual publication 1747 RM001 instruction set information DeviceNet Manager Software User Manual publication 1787 UM053 Information on DeviceNet Manager 1747 DeviceNet Scanner Installation Instructions publication 1747 IN058 1747 DeviceNet Scanner User Manual publication 1747 UM655 Information on 1747 DeviceNet Scanner 1771 DeviceNet Scanner Configuration Manual publication 1771 UM118 Information on 1771 DeviceNet Scanner DeviceNet Cable System Planning and Installation Manual publication DNET UM072 Planning and installing a DeviceNet cable system Allen Bradley Programmable Controller Grounding and Wiring Guidelines publication 1770 IN041 In depth information on grounding and wiring Allen Bradley programmable controllers Allen Bradley Industrial Automation Glossary
58. oes not exceed the boundary of the controller s data file For example a MicroLogix 1000 controller has 32 words in its bit file therefore you could not use a Input Word Offset of 30 and a Input Size of 5 because this exceeds the file size DNI Configuration Parameters and Programming Notes 35 IMPORTANT If you use RSNetWorx or DeviceNet Manager to configure commission the DNI it is up to you to select the correct values for Input Size e Input Split Point DNI Series B only e Input Type e Input Data File e Input Word Offset Only the DNI Configuration Software Utility performs checks on the information entered Output Size Parameter Parameter Number Description Range Default me Series A Series B id Series B 1 0 Output Size Series A 1 16 1 Series B 1 32 TTTIANTUPM or DNI Series B you must also configure the Output Split Point See page 36 This parameter identifies the size in words of the data array that will be written to the controller attached to the DNI s RS 232 port The array may contain up to 16 16 bit words of data for DNI Series A 32 words for DNI Series B from a contiguous block within the attached controller Publication 1761 UMO005B EN P October 2006 36 DNI Configuration Parameters and Programming Notes Publication 1761 UMO005B EN P October 2006 The first byte byte 0 of the first word contains the status byte and is not available to the user A sample of the
59. ompatible with RSLogix 500 programming software The file name is DNI I O RSS and contains two programs DNI MicroLogix Heartbeat Logic DNI I O RSS Ladder 2 Main Program Monitors the communications link for integrity This is considered to be part of the Heartbeat logic associated with the DNI e DNI COS change of state I O Messaging DNI I O RSS Ladder 6 COS ML DNI Moves the Input and Output data inside the controller for correct operation with the DNI Publication 1761 UMO005B EN P October 2006 72 Application Examples Publication 1761 UMO005B EN P October 2006 DNI MicroLogix Heartbeat Logic TIP Rung 9 in this example resets 0 all outputs to off if communications are lost If you prefer your application to have the controller maintain the outputs in their last state remove this rung Or if you want additional logic to control your outputs remove this rung and program the outputs as your application requirements warrant 0000 0001 0002 0003 0004 Application Examples 73 DNI I 0 RSS Ladder 2 Main Program This rung sets status file bit S2 0 8 When this bit is set it allows a program written for a 32 point MicroLogix 1000 controller to run without an I O mismatch error on a 10 16 or 25 point controller Extend 1 0 Configuration 0 This rung detects an off to on transition of bit N7 95 7 Bit N7 95 7 is the communication s Heartbeat that is received from the D
60. ons e Responses to poll requests are sent to the configured address e COS Cyclic I O data messages are sent to the configured device For example when using a MicroView operator interface over DeviceNet DF1 Substitute Address defines the device node number that the MicroView exchanges data with TIP A value of 64 default disables this feature DF1 Autobaud Parameter Parameter Number Description Range Default Value Type Series A SeriesB DF1 15 17 DF1 Autobaud Disabled 0 Enabled 1 or Enabled 1 The DNTs RS 232 baud rate is set up to automatically synchronize to the attached RS 232 device If you want to lock the RS 232 baud rate disable this parameter If this parameter is disabled 0 the DNI s RS 232 port baud rate is set to the value specified by the DF1 Baud Rate parameter Publication 1761 UMO005B EN P October 2006 48 DNI Configuration Parameters and Programming Notes DF1 Baud Rate DF1 Baud Rate Parameter Definition Parameter Parameter Number Description Range Default Value Type SeriesA Series B DF1 16 18 DF1 Baud Rate D Series A 2 9600 38 400 Series B 1 19 200 This parameter defines the baud rate for the RS 232 port when DF1 Autobaud is disabled DeviceNet Autobaud DeviceNet Autobaud Parameter Definition Parameter Parameter Number Description Range Default Value Type Series A Series B DeviceNet DeviceNet Disa
61. ons port to automatically synchronize to the device or network that it is attached to This feature typically minimizes the amount of configuration required and also makes it easier to replace devices Connection Set These methods of communication relate to how data is communicated between master and slave For example a master allocates a slave I O connection set The ownership allows the master to read geO and or write set data to the slave COS Change Of State Communication method that does not send or receive data until a change in data is detected Publication 1761 UMO005B EN P October 2006 90 Glossary Publication 1761 UMO005B EN P October 2006 DeviceNet Master A product capable of owning input output C O on a DeviceNet network DeviceNet Slave A product whose data Cor portion of can be owned by DeviceNet master DF1 Full Duplex DF1 is a standard open point to point communication protocol Virtually all Allen Bradley controllers PLC 3 PLC 5R SLC MicroLogix that support an RS 232 communication port support DF1 Explicit Messaging A DeviceNet message that gets sets device configuration information Heartbeat A mechanism that lets a device set of devices or a connection check for operation or integrity Also known as a watchdog Input Buffer A set of 16 bit words that is available to a master on a DeviceNet network The input buffer in DNI Series A is configurable from 1 16 data wo
62. otocol basically any Allen Bradley controller with an RS 232 port use the historical source destination model to move data The problem with this is that DeviceNet technology uses the newer producer consumer model and is not compatible with the source destination model So to allow controllers that use the source destination model MicroLogix SLC PLC access to devices on the DeviceNet network the DNI can act as an intermediary To act as an intermediary the DNI must allow the historical DF1 message format to be compatible with the newer DeviceNet producer consumer object model This is accomplished by creating a routing profile The routing profile basically takes the DF1 message and converts it to DeviceNet Each routing profile contains the information needed to get or set data to other DeviceNet devices Each routing profile has the following five components e Node the address of the Device on a DeviceNet network e Class the DeviceNet class code e Instance the DeviceNet instance code e Attribute the DeviceNet attribute code e Size the amount of data to be read or written Explicit Messaging DNI Series B Only 79 Routing Profile Configuration The DNI can store up to 10 profiles These profiles can be changed at any time and they are not backed up with a battery If the power to the DeviceNet network is lost the profiles are cleared and must be reloaded This can be done with a subroutine TIP A message ins
63. ours of installation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running United States 1 440 646 3223 Monday Friday 8am 5pm EST Outside United Please contact your local Rockwell Automation representative for any States technical support issues New Product Satisfaction Return Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning it may need to be returned United States Contact your distributor You must provide a Customer Support case number see phone number above to obtain one to your distributor in order to complete the return process Outside United Please contact your local Rockwell Automation representative for States return procedure Allen Bradley CompactLogix ControlLogix PowerFlex Rockwell Automation RSLinx RSLogix MicroLogix Panelview RSNetWorx and TechConnect are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation Vors
64. polling after setting your configuration For information on how to set up and modify parameters see Setup Programming and Troubleshooting on page 53 Parameter Parameter Number Description Range Default Value For More Type Series A Series B Information 1 0 4 1 Input Size Series A 1 16 1 word 29 Series B 1 32 1 0 Not 2 Input Split Point 1 32 1 word 30 Applicable 1 0 5 3 Input Type Bit or Integer File Integer File 33 1 0 6 4 Input Data File 3 254 7 33 1 0 7 5 Input Word Offset 0 254 0 34 1 0 8 6 Output Size Series A 1 16 1 word 35 Series B 1 32 1 0 Not 7 Output Split Point 1 32 1 word 36 Applicable 1 0 9 8 Output Type Bit or Integer File Integer File 38 1 0 10 9 Output Data File 3 254 7 39 1 0 11 10 Output Word Offset 0 254 1 39 1 0 14 11 DF1 Device 0 3 3 MicroLogix 1000 41 0 Other 1 PLC 2 SLC Other MicroLogix 3 MicroLogix 1000 1 0 3 12 DNI Series A Data Disabled 0 or Disabled 0 41 Enable Enabled 1 DNI Series B I O Scan Enable Polling Enable 1 0 12 13 DF1 Heartbeat Series A 2 10 2 43 Series B 1 10 1 0 13 14 Data Scan Delay 20 3000 ms 50 ms 45 Polling Delay Publication 1761 UMO005B EN P October 2006 DNI Configuration Parameters and Programming Notes 29 EDS Parameters for the DNI Messaging 2 15 Message Timeout 0 2500 ms 0 ms 46 Messaging Not 16 DF1 Substitute 0 64 64 Disable
65. publication AG QRO71 A glossary of industrial automation terms and abbreviations Publication 1761 UMO005B EN P October 2006 Chapter 1 Overview Introduction The DeviceNet interface is a standalone DIN rail or panel mounted intelligent DeviceNet to DF1 protocol conversion device that lets existing DF1 devices communicate on a DeviceNet network The DF1 device exchanges I O data with a Master device and originates and receives DF1 encapsulated DeviceNet messages across a DeviceNet network The DNI provides a single DeviceNet connection point and a single RS 232 connection The DeviceNet port is isolated from the DNI digital logic and RS 232 port The primary functions of the DNI are Collect or receive input data from the DF1 device connected on its RS 232 port and forward that data to a connected master on DeviceNet network Monitor output data received from the DeviceNet master and write that data to the DF1 device e Allow DF1 devices to send and receive messages across the DeviceNet network Operating Modes The DNI can be used in either or both of the following modes e Peer to peer e DeviceNet slave Device Compatibility The DNI can be used to interconnect the following devices MicroLogix controllers e DF1 Full Duplex compliant products for example PLC 5 programmable controllers operator interface devices and SLC 5 03 and higher processors Publication 1761 UMO005B EN P October 2006 10
66. rds DNI Series B is configurable from 1 32 The data in the input buffer originates from the device connected to the RS 232 port either by the DNI reading the data or the RS 232 device writing the data to the DND The input buffer terminology is used because the data is input data to the DeviceNet master Messaging A general term that identifies the exchange of data between devices The two major types of DeviceNet messaging are e O DeviceNet master and DeviceNet slave e Peer to peer Between compatible devices without a master s involvement Output Buffer A set of 16 bit data words that is available to a Master on a DeviceNet network The output buffer in DNI Series A is configurable from 1 16 Glossary 91 data words DNI Series B is configurable from 1 32 Output data received from the DeviceNet master is forwarded written to the RS 232 device Peer To peer A type of communication where both devices are equal These devices communicate to each other without a third device to manage the transaction Profile Register The location within the DNI where routing profile configurations are stored PCCC Programmable Controller Communication Commands UCMM Unconnected Message Manager Publication 1761 UMO005B EN P October 2006 92 Glossary Publication 1761 UMO005B EN P October 2006 Numerics 1761 NET DNI agency certification 85 commissioning 58 compliance to EC directives 23 configura
67. s and allows a master device to exclusively manage own another device s a different node number data and resources This type of relationship is functionally the same as a PLC with remote I O A PLC uses the remote I O chassis as distributed inputs and outputs The master slave relationship on DeviceNet is exactly the same except it is being done over DeviceNet The amount of data available between devices that implement I O master slave services is determined by the design of each device and is not a function of DeviceNet The DNI on DeviceNet is capable of handling 32 I O words of data with a DeviceNet I O master for DNI Series A 64 for DNI Series B This is broken up into two data images the input image and the output image Publication 1761 UMO005B EN P October 2006 18 Operation Network Configuration Software Publication 1761 UMO005B EN P October 2006 Input Image The input image is a configurable array of 16 bit data words The image is configurable from 1 16 data words for DNI Series A 1 32 data words for DNI Series B The actual data that resides in the input image is delivered to the DeviceNet master by one of three mechanisms e Polled Where the DeviceNet Master sends a poll request with output data and the DNI responds with its current input data e COS Change of State Where the DNI detects that data has changed within the input image and automatically sends the data to the DeviceNet Master
68. s Changed Flag MicroLogix to DNI Message Timeout N7 82 B3 31 N7 82 0001 it J E lt gt 13 11 8 Retry Message T4 38 n This is the message instruction that writes data to the DNI It is recommended that you use 485CIF as the target device CIF is the most efficient type of communications This message instruction also has a destination address of 254 This value is entered into the Setup Screen area of the message instruction MSG 0002 Read Write Message CEN 5 Read Write Write Target Device 485CIF CDN gt Control Block N7 82 Control Block Length 7 L ER Setup Screen Publication 1761 UM005B EN P October 2006 76 Application Examples Publication 1761 UMO005B EN P October 2006 Chapter 8 Explicit Messaging DNI Series B Only Explicit messaging is the mechanism that is used to move data over the DeviceNet network Every device on the DeviceNet network either initiates or responds to some type of explicit message to either read get or write set data In the network shown below node 5 is a master scanner that owns slave I O data on the DeviceNet network When the master interacts with its slaves either through strobed polled cyclic or COS connections the communications used are specific types of I O messages If the MicroLogix controllers at nodes 10 and 30 want to exchange data they message through the DNIs to each other using explicit messages Node 10 The function
69. st have the DNI s EDS electronic data sheet file and bitmap file or icon loaded into your configuration software See DNI Software Files on page 53 and Setting Up Network Configuration Software on page 55 for more information Follow these steps to configure a DNI connected to a MicroLogix 1000 controller as a slave device to a DeviceNet master 1 2 Unpack and mount the DNI Connect the DNI to the DeviceNet Network When power is first applied to the DNI it resides at node 63 on the network The DNI out of box configuration is defaulted to Autobaud it synchronizes to the DeviceNet network baud rate Connect to the DNI with your network configuration tool software such as DeviceNet Manager or RSNetWorx and set the DNI to the desired node number This is called node commissioning Double click on the DNI icon to open the DNI s EDS For DNI Series A set DNI Mode parameter 17 to Standby mode 0 For DNI Series B set I O Scan Enable parameter 12 to disable 0 default Click Save to Device Publication 1761 UM005B EN P October 2006 14 Quick Start To configure a MicroLogix 1000 controller as a slave device to a DeviceNet master set the parameters as shown in the following table MicroLogix 1000 Controller Parameter Settings Parameter Number Description Range Default Value For this Example Series A Series B ENTER 4 1
70. ster Output Master s Assembly Outputs least significant word Lower Addresses Output Split Point Example We need 4 3 5 data 0 5 status words of slave data that the master will own and we need to configure an additional 15 words so that other DeviceNet products can write data e Output Size 19 e Output Split Point 4 Publication 1761 UMO005B EN P October 2006 38 DNI Configuration Parameters and Programming Notes Publication 1761 UMO005B EN P October 2006 The DNI s output image will consist of DNI s Output Image Word Instance ID 0 Master s Slave Data and Status 0x65 1 Master s Slave Data 2 3 Master s Slave Data Split Point 4 Explicit Output Data 0x90 You can use 5 l 0x91 0x67 to access 6 T 0x92 m configure 3 a 0x93 A 8 M 0x94 assembly 9 U 0x95 10 U 0x96 11 v 0x97 12 4 0x98 13 4 0x99 14 v Ox9A 15 4 0x9B 16 v Ox9C 17 4 0x9D 18 Explicit Output Data Ox9E The minimum value allowed for the Split Point is 1 If the Output Size is 32 maximum the resulting range of explicit output words would be 0x90 to OxAE See Output Assembly Data Explicit Split Point and Slave on page 68 for more information Output Type Parameter Parameter number Description Default Type Value 1 0 8 eol Output Type Bit or Integer File Integer File This parameter is used to identify the type of data to be written to the controller
71. ta To achieve the best communications performance you should use these recommended combinations Recommended Combinations RS 232 Device DF1 Device File Type File Number Value MicroLogix 1000 SLC 5 03 or higher 2 N integer 9g Other MicroLogix MicroLogix 1500 TIP If you do not want to communicate with these specific data files RS 232 port communications throughput will suffer marginally 1 0 Scan Enable Parameter Parameter Number Description Range Default Type Series A Series B Value 1 0 3 12 DNI Series A Disabled 0 or Disabled 0 Data Enable Enabled 1 DNI Series B 1 0 Scan Enable Polling Enable This parameter enables the DNI to scan exchange I O data with DF1 devices If the DNI is being used in an application that does not use this feature disabling this parameter improves the DNI s messaging Publication 1761 UMO005B EN P October 2006 42 DNI Configuration Parameters and Programming Notes Publication 1761 UMO005B EN P October 2006 performance When this parameter is disabled PCCC messaging still operates TTTTUMME Enable this parameter to use explicit messaging to assemblies TTTDTUMM When modifying most DNI parameters you must first disable polling Set the Data Enable parameter to disable for DNI Series A Set the I O Scan Enable parameter to disable for DNI Series B You can enable polling after setting your configuration For information on how to
72. the communications link the MicroLogix controller turns off the outputs If the connection is restored the controller recovers and behaves like an I O block If you would prefer to have the MicroLogix maintain the outputs when a communications fault is detected remove or disable some of the logic in this application review the comments for each rung to determine which logic to remove Or if you prefer to have the controller behave differently on a communications fault simply add the corresponding logic that you require Publication 1761 UMO005B EN P October 2006 70 Application Examples Example DNI Configuration All example ladder logic programs in this section use the following DNI configuration Parameters Parameter Number Description Range Default Value For this Example Series A Series B ENTER 4 1 Input Size Series A 1 16 1 word 4 words Series B 1 32 Not 2 Input Split Point 1 32 1 word 4 words Applicable 5 3 Input Type Bit or Integer File Integer File Integer File 6 4 Input Data File 3 254 7 7 5 Input Word Offset 0 254 0 90 8 6 Output Size Series A 1 16 1 word 4 words Series B 1 32 Not 7 Output Split Point 1 32 1 word 4 words Applicable 9 8 Output Type Bit or Integer File Integer File Integer File 10 9 Output Data File 3 254 7 7 11 10 Output Word Offset 0 254 1 95 14 11 DF1 Device 0 3 3 MicroLogix 1000 3 MicroLogix 1000 0 O
73. ther 1 PLC 2 SLC Other MicroLogix 3 MicroLogix 1000 3 12 DNI Series A 00r 1 Disabled 0 Enabled 1 Data Enable DNI Series B 1 0 Scan Enable Polling Enable 12 13 DF1 Heartbeat Series A 2 10 2 2 Series B 1 10 13 14 Data Scan Delay 20 3000 ms 50 ms 100 ms Polling Delay 2 15 Message Timeout 0 2500 ms 0 ms 0 ms Not 16 DF1 Substitute 0 64 64 Disabled 64 Disabled Applicable Address 15 17 DF1 Autobaud Disabled 0 or Enabled 1 Enabled 1 Enabled 1 Publication 1761 UMO005B EN P October 2006 Application Examples 71 Parameter Number Description Range Default Value For this Example Series A Series B ENTER 16 18 DF1 Baud Rate 0 5 Series A 2 9600 0 38 400 0 38 400 Series B 1 19 200 1 19 200 2 9600 3 4800 4 2400 5 1200 1 19 DeviceNet Autobaud Disabled 0 or Enabled 1 Enabled 1 Enabled 1 17 Not DNI Mode Standby 0 or Operational 1 Operational 1 Applicable Operational 1 Example Ladder Logic The ladder program example is used to monitor the integrity of the communications link with the DNI If something happens and communications are lost cable is cut or removed DNI loses power or faults this logic detects that condition The user can program the controller to respond to a loss of communications if desired The example ladder logic shown below is available for download from http www ab com micrologix The sample is c
74. tion parameters 27 configuration software 53 interface diagram 89 new features 27 port identification 26 specifications 85 A application examples 69 78 autobaud 47 8 B baud rate 8 C cables 24 CE 85 commissioning the DNI 58 configuration parameters 27 28 configuring master slave 1 0 13 configuring peer to peer messaging 11 C UL 85 D data enable 41 data scan delay 45 definitions 89 device compatibility O device type 41 DeviceNet autobaud 8 DeviceNet class codes l 0 assembly data 67 68 identity object 65 66 Series A 65 Series B 66 DeviceNet I O 17 input image 18 output image 18 DeviceNet Manager 57 62 DeviceNet node number 51 Index DeviceNet valid data 51 DF1 autobaud 47 DF1 baud rate 48 DF1 heartbeat 43 DF1 substitute address 27 47 dimensions 86 mounting template 87 DIN rail mounting 24 DNI Configuration Utility 54 55 DNI mode 49 DNI COS 1 0 Messaging 74 DNI MicroLogix heartbeat logic 71 E EDS file 27 28 example explicit messaging 80 MicroLogix as 1 0 on DeviceNet 69 reading get data 80 writing set data 82 explicit messaging 19 77 example 80 I O assembly messaging 19 PCCC encapsulated DeviceNet Messaging 20 using DF1 protocol 78 F fault conditions 64 G getting started 11 H hazardous location operation 24 85 1 0 scan enable 41 input image 18 input messaging 49 input size 29 input split point 30 input word offset 34 installation DNI software files 5
75. tlaan Boulevard du Souverain 36 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1761 UMO005B EN P October 2006 Supersedes Publication 1761 UM005A EN P June 1999 Copyright 2006 Rockwell Automation Inc All rights reserved Printed in the U S A
76. to configure an additional 15 words so that other DeviceNet products can read data Input Size 19 e Input Split Point 4 Publication 1761 UMO005B EN P October 2006 32 DNI Configuration Parameters and Programming Notes The DNI s input image will consist of DNI s Input Image Word Instance ID 0 Master s Slave Data and 0x64 Status 1 Master s Slave Data 2 i 3 Master s Slave Data Split Point 4 Explicit Input Data 0x70 You can use 0x66 3 t 0x71 sis pube 6 4 0x72 explicit assembly 7 4 0x73 8 v 0x74 9 v 0x75 10 v 0x76 11 v 0x77 12 4 0x78 13 4 0x79 14 v Ox7A 15 4 0x7B 16 v 0x C 17 4 0x7D 18 JExplicit Input Data Ox7E The minimum value allowed for the split point is 1 if the Input Size parameter is 32 the maximum the resulting range of explicit input words would be 0x70 to Ox8E See Input Assembly Data Explicit Split Point and Slave on page 67 for more information Publication 1761 UMO005B EN P October 2006 DNI Configuration Parameters and Programming Notes 33 Input Type Parameter Parameter Number Description Range Default s Series A Series B Series B 1 0 Input Type Bit or Integer File Integer File This parameter is used to identify the type of data to be read within the controller The DNI supports data exchange with either bit or integer files Input Data File Parameter Paramet
77. truction returning an error code of OxDOH is an indication that profiles need to be re configured The 10 profiles are stored within the DNI in profile registers To configure a routing profile the user creates a write message in the controller s ladder logic with a destination node address of 240 249 The write message must have a data length of five words Each word corresponds to one of the five components in the routing profile Word Title Function 0 Target Node Node number 0 63 of the target device on a DeviceNet network that communications will be established with 1 Class Class of the target DeviceNet object 2 Instance Instance of the target DeviceNet object 3 Attribute Attribute of the target DeviceNet object that will be read from or written to get set 4 Size Amount of data to be read or written in bytes When the DNI receives a write message with a destination address of 240 249 it stores the five words of data in the corresponding profile register location 240 249 Publication 1761 UMO005B EN P October 2006 80 Explicit Messaging DNI Series B Only Explicit Messaging Examples Publication 1761 UMO005B EN P October 2006 Once the profiles are correctly loaded into the DNI getting data from a DeviceNet device is as simple as reading data from another controller The procedure is illustrated by the following examples Reading Get Data Example For the DeviceNet ne
78. twork shown above we want to read data from the proximity sensor at node 15 The proximity sensor has specific DeviceNet parameters that are accessible via the DeviceNet network In this example profile register 240 within the DNI node 10 has been configured to access specific data within the proximity sensor TIP Devices must be UCMM capable The proximity switch and tower light are not UCMM capable But because they are owned by the 1747 SDN scanner in the SLC chassis the DNI can explicit message to them TIP Any devices parameters should be identified in their respective documents Explicit Messaging DNI Series B Only 81 DNI Profile Register 240 e DeviceNet Node 15 e Class 14 OxOE e Instance 1 e Attribute 1 e Size 1 byte To read data from the proximity sensor a read message is initiated from the controller to node address 240 The DNI receives the node 240 read request and then generates the appropriate DeviceNet explicit message to get read data from the proximity sensor at node 15 TIP The profiles size parameter must match the DeviceNet device In this example the amount of data size being read over DeviceNet Gn bytes is 1 The DNI receives the byte of information from the sensor and replies to the controller read request with a word of data The actual byte of data from the sensor resides in the low order byte of the data word within the controller In this example the read message instru
79. us off attribute of DeviceNet object to 1 Publication 1761 UMO005B EN P October 2006 DNI Series A DeviceNet Class Codes Identity Object Class Code 0x01 Service Name Setup Programming and Troubleshooting 65 Service Code Get Attribute Single OxOE Set Attribute Single 0x10 Reset 0x05 Instance 0x01 Name Attribute Data Access Value Vendor ID 0x01 UINT Get 1 Device Type 0x02 UINT Get 12 Product Code 0x03 UINT Get 2 Revision 0x04 STRUCT of Get Major Revision USINT Get 1 Minor Revision USINT Get 2 Status 0x05 WORD Get N A Serial Number 0x06 UDINT Get N A Product Name 0x07 SHORT STRING Get 1761 NET DNI DNI Mode 0x64 BOOL Get Set Oor1 parameter 17 Slave 1 0 Assembly Data Class Code 0x04 Name Access Instance Data Type Value Attribute Input Assembly Get Set Input 100 64H 3 Output Assembly Get Set Output 101 65H 3 Publication 1761 UMO005B EN P October 2006 66 Setup Programming and Troubleshooting DNI Series B DeviceNet Class Codes Publication 1761 UMO005B EN P October 2006 Identity Object Class Code 0x01 Service Name Service Code Get Attribute Single OxOE Set Attribute Single 0x10 Reset 0x05 Instance 0x01 Name Attribute Data Access Value Vendor ID 0x01 UINT Get 1 Device Type 0x02 UINT Get 12 Product Code 0x03 UINT Get 32
80. ut 131 83h 3 Explicit word 20 Get Set Input 132 84h 3 Explicit word 21 Get Set Input 133 85h 3 Explicit word 22 Get Set Input 134 86h 3 Explicit word 23 Get Set Input 135 87h 3 Explicit word 24 Get Set Input 136 88h 3 Explicit word 25 Get Set Input 137 89h 3 Explicit word 26 Get Set Input 138 8Ah 3 Explicit word 27 Get Set Input 139 8Bh 3 Explicit word 28 Get Set Input 140 8Ch 3 Explicit word 29 Get Set Input 141 8Dh 3 Explicit word 30 Get Set Input 142 8Eh 3 1 The split point determines 1 is set to 32 and the split The example above illustra he size of the slave assembly and the explicit assembly If the input size parameter point parameter 2 is the minimum size 1 the remaining words are explicit inputs es the maximum amount of explicit inputs that can be configured For more information about using the split point parameter see Input Split Point on page 30 or Output Split Point on page 36 2 A get of this instance will return the entire set of Explicit Assembly Data Publication 1761 UMO005B EN P October 2006 68 Setup Programming and Troubleshooting Output Assembly Data Explicit Split Point and Slave Class Code 0x04 Name Access Instance Data Attribute Outputs Type Value Slave Assembly Get Set Output 101 65h 3 Output Split Poi
81. ut Data Files File Sizes Integer 105 Words SLC Other MicroLogix Bit 255 Words Integer 255 Words PLC Bit 999 Words Integer 999 Words TIP The DNI can only access files 0 254 TTTTUMMD You must have sufficient room in the file that you select Make sure the Output Word Offset plus the Output Size does not exceed the boundary of the data file For example a MicroLogix 1000 controller has 32 words in its bit file therefore you could not use a Output Word Offset of 30 and a Output Size of 5 because this exceeds the file size IMPORTANT If you use RSNetWorx or DeviceNet Manager to configure commission the DNI it is up to the user to select the correct values for e Output Size e Output Split Point DNI Series B only e Output Type e Output Data File e Output Word Offset Only the DNI Configuration Software Utility performs checks on the information entered DNI Configuration Parameters and Programming Notes 41 Device Type Device Type Parameter Definition Parameter Parameter Number Description Range Default Type SeriesA Series B Value 1 0 14 11 DF1 Device 0 3 3 MicroLogix 0 Other 1000 1 PLC 2 SLC Other MicroLogix 3 MicroLogix 1000 Select the device connected to the DNI s RS 232 port If you are connecting an Allen Bradley controller as a DeviceNet I O slave device this selection is used by the DNI to determine the type of communication commands used to read and write da
82. xample With the starting output word at N7 95 Output Word Offset and the starting input word at N7 90 Input Word Offset you need to program this rung in the controller s program to move the heartbeat bit N7 95 N7 90 lt gt 7 Your program should also monitor N7 95 7 for activity If activity is lost it represents a problem with the connection to the DNI or the DNI has some type of error or problem See the application example MicroLogix as I O on the DeviceNet Network on page 69 for more information about using the DF1 Heartbeat DNI Software Files Chapter 6 Setup Programming and Troubleshooting To configure the DNI as an I O slave device on a DeviceNet network you may need to obtain two software files These two files provide your network configuration software with the information it needs to interface with the DNI DNI Series A Information RSNetWorx and DeviceNet Manager version 3 0 and higher include the files necessary for DNI Series A DNI Series B Information To configure the Series B DNI you must have the Series B DNI EDS file installed in your DeviceNet configuration software RSNetWorx DeviceNet Network Management software version 2 11 36 or higher includes all Series B DNI files You can also download the new files from http www ab com micrologix The following table shows the old and new file filenames Series B DNI Files 1761 NET DNI File Description File Name
83. y Standard Part 2 Industrial Environment This product is intended for use in an industrial environment Low Voltage Directive This product is tested to meet Council Directive 73 23 EEC Low Voltage by applying the safety requirements of EN 61131 2 Programmable Controllers Part 2 Equipment Requirements and Tests For specific information required by EN 61131 2 see the appropriate sections in this publication as well as the Allen Bradley publication Industrial Automation Wiring and Grounding Guidelines For Noise Immunity publication 1770 4 1 This equipment is classified as open equipment and must be mounted in an enclosure during operation to provide safety protection Publication 1761 UMO005B EN P October 2006 24 Installation and Wiring Safety Considerations Mounting Publication 1761 UMOOBB EN P October 2006 This equipment is suitable for use in Class I Division 2 Groups A B C D or non hazardous locations only ATTENTION A Explosion Hazard Substitution of components may impair suitability for Class I Division 2 Do not replace components unless power has been switched off and the area is known to be non hazardous Do not disconnect connectors unless power has been switched off and the area is known to be non hazardous Use only the following communication cables and replacement connectors in Class I Division 2 Hazardous Locations Environment Classification Class I Division 2

Download Pdf Manuals

image

Related Search

Related Contents

MFP14型,MFP14S型およびMFP14SS型プレッシャー  Epson 811p Projector User Manual  Peinture Anti-Taches    圧センサ  FSG 85 B1 - Lidl Service Website  gaz naturel  Outdoor unit - Single split  Prestar un poco de cuidado al conducir puede significar ¡ahorros en  Builder's Choice HDX164594 Installation Guide : Free Download, Borrow, and Streaming : Internet Archive  

Copyright © All rights reserved.
Failed to retrieve file