1. NETWORK 1275 Danner Dr Tel 330 562 7070 m m m mm TECHNOLOGIES Aurora OH 44202 Fax 330 562 1999 E ws 58 INCORPORATED www networktechinc com ENVIROMUX Series Sensor Installation Manual Or ENVIROMUX T RH TRH M E7 Temperature Humidity sensors ENVIROMUX LDSx y 2 Detection Sensor ENVIROMUX SRN M Siren ENVIROMUX BCN R Beacon i oe ENVIROMUX TDS ENVIROMUX M DCS Tamper Switch Door Contact Switch MANO57 Rev Date 10 15 2015 NTI ENVIROMUX SENSOR INSTALLATION TABLE OF CONTENTS PAO TET 2 Connect Sensors to ener nnns n nna aer inert 2 ENVIROMUX T RH or TRH M E7 ccccccccssececeessceeeeeeeeeceeeeeseeeeceseeeeeeeseaeeeseeseeeeseeceeseeeeessaeeeeeessaeeeeseeeeesaeeeeeas 2 siio cp 4 ROCF SS 4 Connect Sensors to The ENVIROMUX xD Models esses nennen 6 T Qt 6 Temperature Humidity Noise Level and Light Sensors cccccsseeeceeecaeeeeeeeeceeeeeeeecaeeeeeeessaeaeeeeessaaeeeeessaaeeeeeeeaas 6 Contact Sensors REM 7 MEA E t 7 Bieb Iga RITE 9 BEACON SIREN
2. sssssssssisssseseeeeeeenne nennen nennen nnn nissan ntes sena ann 9 Figure 13 Connect visual and audible external indicators seeeeeeeissssssssssssssssseeenn nennen nennen nnne nnne n nennen nnn nnn nnns 10 NTI ENVIROMUX SENSOR INSTALLATION INTRODUCTION Many different sensors can be connected to the ENVIROMUX Series Enterprise Environment Monitoring Systems Series models include ENVIROMUX SEMS 16U ENVIROMUX 16D 5D 2D and ENVIROMUX MINI LXO A complete listing of available sensors and accessories can be found at http www networktechinc com enviro rems html for the ENVIROMUX SEMS 16U http www networktechinc com environment monitor 16d html for the ENVIROMUX 16D http www networktechinc com environment monitor 5d html for the ENVIROMUX 5D http Www networktechinc com environment monitor 2d html for the ENVIROMUX 2D and http Www networktechinc com environment monitoring html for the ENVIROMUX MINI LXO http www networktechinc com environment monitor micro html for the ENVIROMUX MICRO T RHP Manuals for each Environment Monitoring System covering installation and configuration for all features can also be found at these websites This manual is only provided to instruct how to connect the various sensors to these systems CONNECT SENSORS TO ENVIROMUX MINI LXO MICRO T RHP ENVIROMUX T RH or TRH M E7 For measuring temperature and humidity the ENVIROMUX MINI LXO and ENVIROMUX
3. CONMECHOTS OTT 10 Bi 11 TABLE OF FIGURES Figure 1 Connect sensors to 2 Fig re 2 LCiguid detection SENSOR PETRI M 4 Figure 3 Terminal block for dry contact eene nennen nnns nnn nnne nnn nsns snis nnne nnns nnns 5 Figure 4 Sensors connected by cables with RJ45 CONNECHOSS cccccccceeeeececeeeeeeeeeeeeeeeeeseeeeeeeeeeaeeeeeeseaeeeesseeeeeeesseaeeeesesaaeeeesesaeges 6 Figure 5 A portion of the sensor configuration page 6 Figure 8 Contact sensor wired to RJ45 socket ccccccccccsseseeeeeceeecaeeeeeeeeeeeeseeeseeeeeeeseseeseseeeeeessseeeeeeeeeessaeeeeeeeeeessseaaeeeeeeesssaaaseeseeees 7 Figure 9 DIGITAL IN terminal blocks on ENVIROMUX Systems sesssssssssseeseeeenen nennen 7 Figure 10 Basic DIGITAL IN Terminal Connections cccccccccccccsseseeccecececeeeeeeceeeeeeaeseeceeeeesseeeeeeeeeeessaeeneeeeeessseeaaeeeeeeesssaaneeeeeees 8 Figure 11 Secure liquid detection sensor with tape cccccsessecccceesecececeeseeececeeueeeeecseaeeeeeseaaeeeeseeuseceesseaeceesseaaeceessaaeeeessaaeeeeesaaaaes 9 Figure 12 Portion of Water Sensor configuration page
4. Itself or cross conductive Sansa fable surfaces to avoid false triggers up to 1000 feet long Apply tape at ends ENVIROMUX LDS For added flexibility install an ENVIROMUX LDSx y using CATS cable to a port labeled RJ45 Sensors With the ENVIROMUX LDS you can use up to 1000 feet of CAT5 cable 1000 feet of two wire cable plus 1000 feet of sensor cable Apply tape at ends at least 5 8 Sensor exposed Two wire cable up to 1000 feet long RJ45 male To RJ45 Sensors connector port on ENVIROMUX xD Sensor Cable up to 1000 feet long up to 1000 feet long Figure 9 Secure liquid detection sensor with tape To test the ENVIROMUX LD S 1 Configure the sensor Normal Status set to Open Sampling Period set to 5 seconds 2 Submerge at least 1 2 inch of the exposed twisted orange wire not the wrapped end for up to 30 seconds Do NOT use distilled water as water must be conductive 3 Monitor the sensor to see the sensor Value change from Open dry to Closed wet 4 Dry the exposed area of sensor and the sensor Value should change back to Open within 30 seconds Hl Digital Input Settings Description Water Sensor Descriptive name for the digital input Group E cw Select which group the digital input belongs to Normal Status Open Select the normal status for the digital input Refresh Rat
5. removable for easy sensor wire attachment if needed Shielded cable must be used to connect to the DIGITAL IN terminals in order to meet CE emission requirements Connect the drain wire of the shield to the ground terminal of the dry contact in addition to the contact return wire NTI ENVIROMUX SENSOR INSTALLATION CONNECT SENSORS TO THE ENVIROMUX XD MODELS RJ45 Sensors Several sensors for the ENVIROMUX 16D 5D 2D and ENVIROMUX SEMS 16 U Enterprise Environment Monitoring Systems have RJ45 connection ports Some of these sensors include ENVIROMUX STS temperature only ENVIROMUX SHS humidity only ENVIROMUX STHS temperature and humidity ENVIROMUX STHS 99 wide range temperature and humidity ENVIROMUX LDS liquid detection and ENVIROMUX LS light detection In all cases the CAT5 cable between the sensor and the ENVIROMUX can be up to 1000 feet in length Temperature Humidity Noise Level and Light Sensors Note It is very important to locate the temperature and or humidity sensors away from ventilation sources and fans RJ45 SENSORS Connect each sensor to one of the female connectors labeled RJ45 Sensors on the ENVIROMUX Male connectors should snap into place See page 7 for wiring specification and pinout ENVIROMUX STS Temperature Sensor Note Shielded CAT5 cable connector is required between the RJ45 male sensor and the ENVIROMUX connector 4 to maintain CE compliance of the sensor Figure 4 S
6. 57 REV 10 15 2015 11
7. 6D or the plus and ground terminals ENVIROMUX 2D 5D f the sensors require a 12V power source to operate these models include 12V and ground terminals for a power connection Connect each two wire or four wire contact sensor using 16 26 AWG wire Terminals on ENVIROMUX 16D Terminals on ENVIROMUX 5D Terminals on ENVIROMUX 2D T TACH 5 RELAY Fay 1 12V Bay fev af sia 12 I uec n LIUC ea ren C NCNO W H 2 T Figure 7 DIGITAL IN terminal blocks ENVIROMUX Systems FYI The terminal block is removable for easy sensor wire attachment if needed NTI ENVIROMUX SENSOR INSTALLATION Terminal Blocks on ENVIROMUX 16D DIGITAL IN Switch X Only KJ Au du ia aa 1 2 3 4 Connect devices rated 50mA or less to Digital In 1 7 ee Connect devices rated 650mA or less to Digital In 8 gaa aa Wa Switch w 12VDC powered device So Soy Symbol 50mA Max in qi da dd di 650mA Sensor Panic Diaital Button igital In 8 Terminal Blocks on ENVIROMUX 5D Terminal Blocks on ENVIROMUX 2D r DIGITALIN 3 AUX OUTPUT RELAYS 7 DIGITALIN OUTPUT c race 1 2 ALARM 1 TACH REA Y TETE 12V FT NCNO C NNO v Pru cncno NCNO 12V Switch w 12VDC powered device 500mA max i Switch w NM 12VDC powered device 500mA max Figure
8. 8 Basic DIGITAL IN Terminal Connections NTI ENVIROMUX SENSOR INSTALLATION Liquid Detection Sensors Liquid Detection Sensors are available for simple connection to either the Digital In terminals use model ENVIROMUX LD or ENVIROMUX LD LC or the RJ45 Sensor ports use model ENVIROMUX LDS Connect the two wire cable up to 1000 feet long from a liquid detection sensor ENVIROMUX LD shown in Figure 2 upper image to a set of DIGITAL IN contacts For added range up to 1000 more feet use an ENVIROMUX LDS shown in Figure 2 lower image and connect to an RJ45 Sensor port The twisted orange sensing cable should be placed flat on the surface usually the floor where liquid detection is desired If tape is required to hold the sensor in place be sure to only apply tape to the ends exposing as much of the sensor as possible At least 5 8 of the sensor must be exposed for it to function See Figure 2 Terminals on ENVIROMUX 16D DIGITAL IN Tach 2 3 S NOTE The ENVIROMUX LD LC can be connected to the DIGITAL IN SS UU terminals of the ENVIROMUX 16D on units made 5 31 13 or after du Ga ENVIROMUX LD LC is compatible with all ENVIROMUX 5D 2D units ai aa aa Ga du ju ENVIROMUX LD or ENVIROMUX LD LC Two wire cable NOTE When installing the up to 1000 feet long soc least 5 8 ENVIROMUX LD LC it is very important wor exposed to assure the sensing cable does not cross over
9. J45 connectors on them and instead have terminal blocks These can either be connected to the DIGITAL IN connectors or they can be terminated and plugged into the remaining RJ45 connectors see Figure 6 The illustration uses CAT5 patch cable to make cable connection easy Examples of these sensors include ENVIROMUX IMD motion detector ENVIROMUX IMD CM ceiling mount S motion detector ENVIROMUX VSS vibration sensor ENVIROMUX SDS smoke detection and ENVIROMUX GBS glass break sensor chematic for wiring Contact Sensor to RJ45 Socket ALARM 12VDC TAMPER Note For sensors requiring 5VDC power source substitute the wire connected to pin 4 see below E Hu caeci instead of pin 7 When applying CAT5 cables to contact sensors for plug in to the RJ45 Sensor sockets the following socket to sensor wiring must be followed RJ45 Sensor Socket Pinout wht blue LE d d 12345678 are not used SENSE for 12VDC 3 3 RS485 contact sensors 5 VDC 5 For 5VDC contact sensors substitute pin 4 5VDC for pin 7 12VDC RS485 7 12 VDC View looking into RJ45 Socket TAMPER SWITCH Figure 6 Contact sensor wired to RJ45 socket Digital In Terminals To connect contact sensors without using RJ45 connectors terminal blocks have been provided labeled DIGITAL IN Two wire switch only type sensors can be connected to the plus and minus terminals ENVIROMUX 1
10. MICRO T RHP uses the ENVIROMUX T E7 temperature only ENVIROMUX RH E7 humidity only ENVIROMUX TRH M E7 combination temperature and humidity sensor For high temperature environments ENVIROMUX MINI IND uses the ENVIROMUX T IND E7 High Temperature Sensor 1 Connect either of the temperature humidity sensors to an available port on the ENVIROMUX MINI LXO Plug the RJ45 connector to either of the two ports marked TEMPERATURE HUMIDITY The ENVIROMUX T RH TRH M E7 sensors can be secured anywhere that the temperature and or relative humidity need to be sensed Note The ENVIROMUX TRHM E7 sensor will work with the ENVIROMUX MINI LXO provided firmware version 2 3 or later is installed and with the ENVIROMUX MICRO provided firmware version 1 3 or later is installed 2 Power cycle the ENVIROMUX MINI LXO after the sensor s have been plugged in Note Mounting the sensor in the path of a fan or on a heated surface may affect the accuracy of the sensor s readings Note For best results use the ENVIROMUX T IND E7 with model ENVIROMUX MINI IND RU45 FF SS Front View of ENVIROMUX MINI LXO sonal Supplied EXE REY Extend sensor up to Sa i E aig mm Senso y 500 feet with CATx ENVIROMUX T IND E7 52 LiT cable min 24AWG NOH T TIS e gu aue High Temperature Sensor ser segia eral east using inline coupler 3 For ENVIROMUX MINI IND To extend a sensor cable up to 500 feet long r
11. e 5 Sec The refresh rate at which the digital input view is updated Figure 10 Portion of Water Sensor configuration page 9 NTI ENVIROMUX SENSOR INSTALLATION BEACON and SIREN Connections Terminals have been provided for connection of a beacon ENVIROMUX BCN R L and siren ENVIROMUX SRN M ENVIROMUX BEEP 1 etc to use for visual alerts and audible alerts when configured Devices such as this can be installed in locations best suited to get attention All devices must be installed using 16 26 AWG wire WARNING Terminals on ENVIROMUX 16D Terminals on ENVIROMUX 5D Devices connected Mo qune VI cannot exceed m AUX OUTPUT RELAYS PWR 1 2 ALARM contact Sou 2 C NCNO C NERO S oa 4 ENVIROMUX BCN R Beacon ENVIROMUX SRN M ENVIROMUX BCN R ENVIROMUX SRN M Siren Siren Beacon Terminals on ENVIROMUX 2D mc DIGITAL IN 23 ourPur Terminals on ENVIROMUX MINI LXO ACH RELA pu EI 12V US DIGITAL IN Qi JPNT 12VDC G0 jp moe Siren ENVIROMUX BCN R ENVIROMUX SRN M Beacon 2 1 Siren s ENVIROMUX BCN R Beacon Figure 11 Connect visual and audible external indicators For a complete listing of available sensors and accessories go to the product page for ENVIROMUX Enterprise Environment Monitoring Systems at http wWwww networktechinc com enviro monitor html and at http www networktechinc com enviro m
12. ensors connected by cables with RJ45 connectors Application Note When connecting temperature and humidity sensors to the ENVIROMUX the web interface will identify the sensor accordingly for the type of sensor itis The status bar and configuration page will enter the maximum and minimum range that this type of sensor can operate at if used with the ENVIROMUX not necessarily the operating range of the sensor itself The various temperature and humidity sensor models offered by NTI have varying ranges of performance capabilities as indicated in the table on the next page Be sure to match the sensor installed to the operating range of the environment it will be expected to work in Using a sensor outside of its intended temperature range may result in damage to the sensor Sensor 2 1 Configuration Type Temperature Combo H Sensor Settings Description Sensor 2 1 Descriptive name for the sensor Group 4 Select which group the sensor belongs to Units Deg F Select the units for the sensor This is the range the ENVIROMUX will display not necessarily the range the Min Level 4 0 sensor will work within See Min supported value for the sensor specifications for the sensor being installed for the proper operating Max Level 185 0 environment Max supported value for the sensor Figure 5 A portion of the sensor configuration page 6 NTI ENVIROMUX SENSOR INSTALLATION Contact Sensors Some sensors do not have R
13. equires ENVIROMUX MINI LXO firmware version 2 0 or later 73 RJ45 male connector Mount sensor where high temperature monitoring is needed Up to 500 feet of CATx cable minimum 24AWG Mount sensor where temperature and or humidity monitoring is needed Figure 1 Connect sensors to ENVIROMUX MINI LXO 2 NTI ENVIROMUX SENSOR INSTALLATION TEMPERATURE AND HUMIDITY SENSORS FOR ENVIROMUX MINI LXO AND ENVIROMUX MICRO T RHP SENSOR MODEL OPERATING TEMPERATURE HUMIDITY RANGE ACCURACY RANGE ENVIROMUX T E7 32 to 104 0 to 40 n a 1 35 0 75 C ENVIROMUX RH E 20 to 8096 RH 5 RH 0 90 0 50 C for 4 to 14 F 20 to 10 C 7 ENVIROMUX TRH M E7 4 to 185 F 20 to 85 0 to 90 RH 0 72 0 40 C for 14 to 185 F 10 to 85 5 RH ENVIROMUX T IND E7 32 to 167 0 and 75 2 25 1 25 Sensor Cable The CAT5 connection cable between the ENVIROMUX MINI LXO ENVIROMUX MICRO T RHP and the RJ45 Sensors is terminated with RJ45 connectors and must be wired according to the EIA TIA 568 B industry standard Wiring is as per the table and drawing below RJ45 Sensor Socket Wiring for ENVIROMUX MINI LXO and ENVIROMUX MICRO T RHP Pin Wire Color Pair White Orange White Green White Brown White Blue View Looking into RJ45 Socket NTI ENVIROMUX SENSOR INSTALLATION ENVIROMUX LD Connect the liquid detection sensor ENVIROMUX LD
14. ext section in similar fashion Replace the rag if it becomes too dirty If the rope is still giving you problems after you have cleaned it with isopropyl alcohol or if you think the rope needs a good scrubbing you can clean it with warm soapy water You will have to remove the rope from its installed location It may be helpful to label the sections of the rope or note their locations before you start for an easier re installation 1 Gather Dawn dish soap a large bucket or plastic bin warm water soft bristled scrub brushes and clean rags 2 Add dish soap to the bucket of water approximately 1 cup of detergent to 1 gallon of warm water To determine if the solution is concentrated enough place your finger and thumb in the water and rub them together You should feel a slick slimy residue If you do not feel a residue add more detergent to the water and gently mix to distribute the soap Submerge a section of the in the water Using a scrub brush or rag scrub along all sides of the rope with firm pressure Remove the section of the rope from the soapy solution and rinse it in a bucket of clean fresh water Ensure that there are no oily deposits along the length of the rope If the rope does not appear clean submerge it in water and scrub again repeating steps 3 to 5 6 Hangthe clean rope up to dry Try to point the connectors down so water cannot pool inside the connectors The drying process may take 6 8 hours de
15. ini html for the ENVIROMUX MINI LXO Manuals for each product covering installation and configuration for all features can also be found at these websites 10 NTI ENVIROMUX SENSOR INSTALLATION RJ45 Sensor Cable The CAT5 connection cable between the ENVIROMUX and connected external sensors is terminated with RJ45 connectors and must be wired according to the EIA TIA 568 B industry standard Wiring is as per the table and drawing below The sensors that connect to RJ45 Sensor ports ENVIROMUX 16 u xD or the Temperature Humidity ports ENVIROMUX MINI LXO are all designed to use cables wired to this standard Pin Wire Color Pair White Orange 2 White Green Gm 8 View Looking into RJ45 Socket TRADEMARK ENVIROMUX is a registered trademark of Network Technologies Inc in the U S and other countries COPYRIGHT Copyright 2008 2015 by Network Technologies Inc All rights reserved No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means electronic mechanical photocopying recording or otherwise without the prior written consent of Network Technologies Inc 1275 Danner Drive Aurora Ohio 44202 CHANGES The material in this guide is for information only and is subject to change without notice Network Technologies Inc reserves the right to make changes in the product design without reservation and without notification to its users MANO
16. pending on the room conditions 7 When the rope is completely dry reinstall it in its original location NTI ENVIROMUX SENSOR INSTALLATION Contact Sensors Up to five dry contact sensors or liquid detection sensors can be connected to the terminals marked DIGITAL IN Sensors with 16 26 AWG connection wires that operate on 5V at 10mA maximum current may be used A contact resistance of 10kQ or less will be interpreted by the ENVIROMUX MINI LXO as a closed contact Examples of Dry Contact Sensors for the ENVIROMUX MINI LXO NTI Description NTI Description ENVIROMUX EBS Emergency Button ENVIROMUX SDS PA Smoke Detection Sensor Power added ENVIROMUX IMD P Infrared Motion Sensor w power ENVIROMUX TDS Tamper Switch To install the dry contact sensor s A Attach the positive lead to a terminal corresponding to a marking on the ENVIROMUX MINI LXO and the ground lead to the next terminal to the right that will correspond to a 2M marking on the ENVIROMUX MINI LXO Tighten the set screw above each contact Terminal sets are numbered 1 5 OUTPUT B Mount the sensors as desired DIGITAL IN RELAY L 5 PI Device with potential free break make contact relay i e door switch Figure 3 Terminal block for dry contact sensors Note The terminal block is
17. to a set of terminals 1 5 marked DIGITAL IN The twisted orange sensing cable should be placed flat on the surface usually the floor where liquid detection is desired If tape is required to hold the sensor in place be sure to only apply tape to the ends exposing as much of the sensor as possible At least 5 8 of the sensor must be exposed for it to function See Figure 2 Front View of ENVIROMUX MINI LXO OUTPUT ENVIROMUX MINI XO LAY pane amp Humidity ep GD ENVIROMUX Two wire cable up to 1000 feet long Apply tape at ends Do not expose connector to liquids Do not submerge Sensor Cable up to 1000 feet long sensor exposed eid ENVIROMUX LD _ Figure 2 Liquid detection sensor Note The connection between the two wire cable and the sensor cable is not designed for exposure to liquids and cannot be submerged Liquid Detection Rope Maintenance For periodic maintenance you can clean the rope with isopropyl alcohol without completely removing the rope from its installed location 1 Remove the section that you want to clean from its self adhesive clips 2 Soak the alcohol in a dye free rag and proceed to wipe it around the rope squeezing firmly while pulling the rag down the length of the rope Flip the rag every several feet and re saturate the rag with alcohol when needed After cleaning a section of the rope you can replace it and continue to clean the n

Download Pdf Manuals

image

Related Search

Related Contents

Guida per l`utente della stampante/copiatrice Xerox WorkCentre  36880 PKZ UM Mini Vapor Manual multi.indb  CR-555(S)  Manual do produto (PT)  Philips Sonicare DiamondClean HX9333  Oracle Purchasing User's Guide  Managed Switch User Guide  USER`S MANUAL - Security Camera King  ENERGY • CONTROL • SYSTEM - GMC  AKG Acoustics D660S User's Manual  