Home

DAM-E3062 User`s Manual

image

Contents

1. 401043 Analog Output Slope Corresponding current channel I 401044 Analog Output Slope Corresponding voltage channel 1 Reservation 401057 Analog Output Power on Value Corresponding current channel 0 401058 Analog Output Power on Value Corresponding voltage channel 0 401059 Analog Output Power on Value Corresponding current channel I 401060 Analog Output Power on Value Corresponding voltage channel 1 Reservation 401073 Analog Output Current Value Corresponding current channel 0 401074 Analog Output Current Value Corresponding voltage channel 0 401075 Analog Output Current Value Corresponding current channel 1 401076 Analog Output Current Value Corresponding voltage channel 1 Reservation 401089 Analog Output Security Level Corresponding current channel 0 401090 Analog Output Security Level Corresponding voltage channel 0 401091 Analog Output Security Level Corresponding current channel 1 401092 Analog Output Security Level Corresponding voltage channel I Reservation Request Domain Name Byte Value Function Code I byte 0x03 Start Address 2 bytes 0 X 0000 to 0 X FFFF Read Amount 2 bytes I to 125 0X7D Response Domain Name Byte Value Function Code I byte 0x03 Byte Count 1 byte 2n Input Status 2n bytes Exception Domain Name Byte Value Function Code 1 byte 0 X 03 0 X 80 Error Code 1 byte 0X1 or0X2 Example Request Response Domain Name Data hex Domain Name Data hex Function Code 03 Function Code 03 Start A
2. 2 MODULE_VER_ADDR Module Version Information Byte 42byte Content DAM E3012 V6 20 2006 09 01 ID DAME123456 3 NET CONFIG ADDR Network configuration parameter call table 1 for structures
3. Content Setting 2 bytes 0 X 0000 to 0 X FFFF Exception Domain Name Byte Value Function Code 1 byte 0 X 06 0 X 80 Error Code 1 byte 0OXlor0X2 Example IRequest IResponse Domain Name Data hex Domain Name Data hex Function Code 06 Function Code 06 DAM E3062 User s Manual V6 10 Set Address High byte 00 Set Address High byte 00 Set Address Low byte 08 Set Address Low byte 08 Set Content High byte 00 Set Content High byte 00 Set Content Low byte 19 Set Content Low byte 19 Set Multiple Relay Function Code OF Request Domain Name Byte Value Function Code 1 byte 0XOF Start Address Setting 2 bytes 0X 0000 to 0 X FFFF Length Setting 2 bytes 0X 0000 to 0X07B0 Byte count 1 byte n Content Setting n bytes Response Domain Name Byte Value Function Code 1 byte 0X OF Start Address Setting 2 bytes 0 X 0000 to 0 X FFFF Length Setting 2 bytes 0X 0000 to 0X 07B0 Exception Domain Name Byte Value Function Code 1 byte 0 XOF 0 X 80 Error Code 1 byte 0X1 or 0X2 Example IRequest IResponse Domain Name Data hex Domain Name Data hex Function Code OF Function Code OF Set Address High byte 00 Set Address High byte 00 Set Address Low byte 13 Set Address Low byte 13 Set Amount High byte 00 Set Amount High byte 00 Set Amount Low byte 0A Set Amount Low byte 0A Byte count 02 Set Content
4. to 0x270F Read Length 2 byte s ii Data 2n bytes Response Domain Name Byte Value Function Code 1 byte 0X15 Byte Count 1 byte 0x07 to OxF5 Sub Function Code 1 byte 0x06 File Number 2 bytes 0x0000 to OxFFFF Record Number 2 bytes 0x0000 to 0x270F Write Length 2 bytes n Data 2n bytes DAM E3062 User s Manual V6 10 Exception Domain Name Byte Value Function Code 1 byte 0X 15 0X80 Error Code 1 byte OX10r0X2 Example Request Response Domain Name Data hex Domain Name Data hex Function Code 15 Function Code 15 Byte Count 0B Byte Count 0B Sub Function Code 06 Sub Function Code 06 File Number High byte 00 File Number High byte 00 File Number Low byte 04 File Number Low byte 04 Record Number High byte 00 Record Number High byte 00 Record Number Low byte 01 Record Number Low byte 01 Read Length High byte 00 Write Length High byte 00 Read Length Low byte 02 Write Length Low byte 02 Write Data 4 bytes Write Data 4 bytes EEPROM assignment file 0 define MODULE_NET ADDR 0x0000 define MODULE VER ADDR 0x0020 file 1 define NET CONFIG ADDR 0x0000 file 2 to file 7 EEPROM is 8kbyte capacity divide to 8 file blocks every block Ikbyte 1 MODULE NET ADDR Restore to factory defaults network configuration parameter Byte 4 4 4 6 Content IP Address Default Gateway Subnet Mask MAC Address
5. via network cable If the wiring and power is ok then the power indicator should be stop flash and keep on The module initialization is completed The indicator flashes according to the transmitted data when the module is working DAM E3062 User s Manual V6 10 DAM E3062 Fig l DAM E3062 Drawing DAM E3062 can be installed in standard DIN rail inside the cabinet it also can be installed by stacking mode Fig 2 DAM E3062 standard DIN installation DAM E3062 User s Manual V6 10 Fig 3 DAM E3062 stack installation Code Configuration Analog Output Range Configuration Code Table Signal Type Range Code 0 20mA 0B mA 4 20mA OC y 0 5V 0D 0 10V OE Analog Output Rate Configuration Code Table Output rate 20mA S Output rate 10V S Code 16Hex Immediate Immediate 00 0 125 0 0625 01 0 25 0 125 02 05 0 25 03 i 0 5 04 gt I 05 4 2 06 8 4 07 16 8 08 39 16 09 64 32 0A 128 64 0B 256 128 OG 512 256 0D 1024 512 0E 2048 1024 OF DAM E3062 User s Manual V6 10 Default Setting If the module s network configuration is wrong or forget the last modified value the module can be reverted to default settings Steps short circuit the INIT and GND when there is no power power on for 3 seconds power off disconnect INIT and GND The module is reverted to the default settings 1 IP Addr
6. DAM E3062 User s Manual 9 Beijing ART Technology Development Co Ltd DAM E3062 User s Manual V6 10 DAM E3062 Module Introduction Features Two Channels Analog Output Output Type V mA Output Range 0 20mA 4 20mA or 0 5V 0 10V 12 bit resolution Precision 0 1 full scale Read back Precision 1 full scale Zero Drift VV VV V WV Voltage Output 30uV C Current Output 0 2uA C Full scale Drift 25ppm C Programmable output conversion slope Isolated Voltage 2000 V VV v Y Current Load Resistance Internal Power 500Q External Power 10509 Support 10 100Mbps Ethernet Provide default web page or custom built web page Support double watchdogs Power Supply unregulated 10 30Vpc Power Consumption 1 4W 24Vpc VV v v WV Easy to operate DAM E3062 utility software can help you to select configuration set the operating parameter for your process control needed Industrial Design DAM E3062 was designed to use in industrial environment It can be installed in standard DIN rail inside the cabinet And it can be powered by unregulated 10 30Vpc to meet the various power supplied source in field It also withstands ambient temperature up to 60 C and resists the effects of vibration and mechanical shock Wiring amp Installation Power supply requirements unregulated 10 Vpc 30 Vpc Vs is a positive and GND is ground The Ethernet interface is connected to a computer switch directly
7. High byte CD Set Content Low byte 01 Set Multiple Holding Registers Function Code 10 Request Domain Name Byte Value Function Code 1 byte 0X10 Start Address Setting 2 bytes 0 X 0000 to 0 X FFFF Length Setting 2 bytes 0 X 0000 to 0 X 07B0 Byte count 1 byte 2n Content Setting 2n bytes DAM E3062 User s Manual V6 10 Response Domain Name Byte Value Function Code 1 byte 0X10 Start Address Setting 2 bytes 0 X 0000 to OK FFFF Length Setting 2 bytes 0X 0000 to 0 X 07B0 Exception Domain Name Byte Value Function Code 1 byte 0X10 0X 80 Error Code 1 byte 0X1lor0X2 Example Request Response Domain Name Data hex Domain Name Data hex Function Code 10 Function Code 10 Set Address High byte 00 Set Address High byte 00 Set Address Low byte 01 Set Address Low byte 01 Set Amount High byte 00 Set Amount High byte 00 Set Amount Low byte 02 Set Amount Low byte 02 Byte count 04 Set Content High byte 00 Set Content Low byte 0A Set Content High byte 01 Set Content Low byte 02 Read File Record Function Code 14 06 Read file record in MODBUS file is considered to be 16 bit array addressing according to address Read file set the start address and read length and change the Start Address and Read Length can traverse the entire file The file does not have a name it has number only You can on
8. ddress H byte 00 Byte Count 02 Start Address L byte 08 Input Register High 00 Read Amount H byte 00 Input Register Low 0A Read Amount L byte 01 Note 1 The unit of the pulse output level width millisecond DAM E3062 User s Manual V6 10 The unit of the watchdog timer length millisecond Note 2 When power on the highest bit of the watchdog control register is 1 can be done to do determine whether the module is rested or not Read Input Register Function Code 04 Description Read input data Data Description Address Description Note 401073 Analog Output Read back Value Corresponding current channel 0 401074 Analog Output Read back Value Corresponding voltage channel 0 401075 Analog Output Read back Value Corresponding current channel I 401076 Analog Output Read back Value Corresponding voltage channel 1 Reservation Request Domain Name Byte Value Function Code I byte 0X04 Start Address 2 bytes 0 X 0000 to 0 X FFFF Read Amount 2 bytes I to 125 0X 7D Response Domain Name Byte Value Function Code 1 byte 0x04 Byte Count 1 byte 2n Input State 2n bytes Exception Domain Name Byte Value Function Code 1 byte 0X 04 0 X 80 Error Code 1 byte 0X1 or0xX2 Example Request Response Domain Name Data hex Domain Name Data hex Function Code 04 Function Code 04 Start Ad
9. dress H byte 00 Byte Count 02 Start Address L byte 08 Input Register H 9 00 Read Amount H byte 00 Input Register L 9 0A Read Amount L byte 01 Single Relay Setting Function Code 05 Request Domain Name Byte Value Function Code 1 byte 0x05 DAM E3062 User s Manual V6 10 Address Setting 2 bytes 0 X 0000 to 0 X FFFF Content Setting 2 bytes 0x0000 or OxFFOO 0x0000 release relay OxFF00 engage relay Response Domain Name Byte Value Function Code 1 byte 0x05 Address Setting 2 bytes 0x0000 to OxFFFF Content Setting 2 bytes 0x0000 or 0xFF00 Exception Domain Name Byte Value Function Code I byte 0x05 0x80 Error Code I byte Ox1 or 0x2 Example Request Response Domain Name Data hex Domain Name Data hex Function Code 05 Function Code 05 Set Address H byte 00 Set Address H byte 00 Set Address L byte 05 Set Address L byte 05 Set Content H byte FF Set Content H byte FF Set Content L byte 00 Set Content L byte 00 Single Holding Register Setting Function Code 06 MODBUS Request Domain Name Byte Value Function Code I byte 0X 06 Address Setting 2 bytes 0X 0000 to 0 X FFFF Content Setting 2 bytes 0 X 0000 to 0 X FFFF MODBUS Response Domain Name Byte Value Function Code 1 byte 0X06 Address Setting 2 bytes 0X 0000 to 0 X FFFF
10. ess 192 168 2 80 2 Subnet Mask 255 255 255 0 3 Default Gateway 192 168 2 1 4 5 TCP Port 502 HTTP Port 80 Communication Protocol At present Ethernet Distributed Acquisition Modules of our company use MODBUS TCP mode Supported function code includes the following categories 01 READ COIL STATUS 02 READ INPUT STATUS 03 READ HOLDING REGISTERS 04 READ INPUT REGISTERS 05 FORCE SINGLE COIL 06 PRESET SINGLE REGISTER 15 FORCE MULTIPLE COILS 16 FORCE MULTIPLE REGISTERS 20 READ FILE RECORD 21 WRITE FILE RECORD Address Mapping Table Read Holding Register Function Code 03 Note Read the holding register value Data Description 40513 For Watchdog Control Register bit0 0 disabled 1 enabled bitl 0 normal 1 overflow bit2 0 normal lreset 40514 For Watchdog Overflow Register Watchdog Overtime Constant 40515 For Watchdog Reset Register 0x55AA Reservation 401025 Analog Output Range Corresponding current channel 0 401026 Analog Output Range Corresponding voltage channel 0 401027 Analog Output Range Corresponding current channel 1 401028 Analog Output Range Corresponding voltage channel 1 Reservation 401041 Analog Output Slope Corresponding current channel 0 401042 Analog Output Slope Corresponding voltage channel 0 DAM E3062 User s Manual V6 10
11. ly read and write one file at one time Request Domain Name Byte Value Function Code 1 byte 0x14 Byte Count 1 byte 0X07 to 0 XF5 Sub Function Code 1 byte 0X06 File Number 2 byte 0x0000 to OxFFFF Record Number 2 bytes 0x0000 to 0x270F Read Length 2 bytes n Sub Function Code 1 byte 0x06 Response Domain Name Byte Value Function Code 1 byte 0x14 DAM E3062 User s Manual Byte Count 1 byte 0x07 to OxF5 Sub Function Byte Count 1 byte 0x07 to OxF5 Sub Function Code 1 byte 0x06 Data 2n bytes Exception Domain Name Byte Value Function Code 1 byte 0X14 0X 80 Error Code 1 byte 0Xlor0X2 Example Request Response Domain Name Data hex Domain Name Data hex Function Code 14 Function Code 14 Byte Count 07 Byte Count 06 Sub Function Code 06 IRespond Count 05 File Number High byte 00 Sub Function Code 06 File Number Low byte 04 Record Data High byte OD Record Number High byte 00 Record Date Low byte FE Record Number Low byte 01 Record Data High byte 00 Read Length High byte 00 Record Date Low byte 20 Read Length Low byte 02 Write File Record Function Code 15 06 Request Domain Name Byte Value Function Code I byte 0X15 Byte Count 1 byte 0X07 to 0XF5 Sub Function Code 1 byte 0X06 File Number 2 bytes 0x0000 to OxFFFF Record Number 2 bytes 0x0000