UCM-316 User`s Manual
Contents
1. UCM 316 User s Manual 1 0 gt advanticsys j Page 5 2 Setting up connection to the device In order to configure the controller user must connect its PC to the device by using any of the following interfaces 1 USB port 2 ETHERNET interface 3 Through a GPRS connection only accessible after configuring GPRS APN user and password inside the controller Figure 2 UCM 316 connection interfaces NOTE Not all the models support above interfaces Check your ordering code first 2 1 USB connection Steps to be followed Connect an USB cable class B to the correspondent port Open UCM 136 Configuration Tool Set up Connection Parameters frame o Select ModBus RTU option under Connection type o Configure Bode and Parity parameters default values are 19200 none o Select COM port number assigned by your PC to the USB port o Click on Get all to establish connection with controller f UCM 316 configurator Analog inputs Analog outputs Discrete inputs Discrete outputs Communication Archives Time parameters Start Other parameters Get all Save configuration Open configuration Write configuration Get all at connection Connection parameters Connection type Modbus RTU Float number format EMI M2 C M2M3EMI C M3M2MIE C MI EM3M2 Modbus Last restart information Number of controller 85227 Set Firmware version 1 19
2. 1 Figure 35 Archives tab Storage frequency configuration In case user needs to customize storage blocks signals acquisition must be configured accordingly Memory block used will be defined as User Archive see next step o Goto Archives gt User Archive Configuration o Under this tab user can configure datalogging following his own requirements In the next pages a configuration example is given by setting the following parameters Count of parameters number of registers to be stored Register Specific register to be stored NOTE Timestamp is registered automatically UCM 316 User s Manual advanticsys Figure 36 Archives tab User archive configuration In order to check current data logged in the internal memory go to Archives gt Values gt User archive tab This is only a test feature in order to ensure datalogging is performing correctly 30102015 015 12 01 00 30102015 12 00 00 301102015 11 59 00 301012015 11 58 00 i 301102015 1 11 57 00 301102015 1 11 56 00 3011012015 115500 2 3014012015 1151 00 0 0000Hex 00000 16672 4120Hex 00000 16582 40C6Hex 5243 14 28100015 18 29 00 0 0000 OHex 0 0000 16582 40C6Hex 5243 14 2811042015 18 28 00 0 0000 36672 4120Hex 0 0000 16582 40C6Hex 5243 14 O 0000Hex 00000 166724120
3. 2811042015 182100 Figure 37 Archives tab User archive current values NOTE Internal datalogging memory is organized as a file system accessible through the use of standard Modbus function 20 File register UCM 316 User s Manual 1 0 advanticsys Page 31 10 Time parameters tab This tab enables users to set up time synchronization between UCM 316 Real Time Clock RTC and external time references Several parameters can be configured under this tab Set PC time It synchronizes internal RTC with PC time Figure 38 Time Parameters tab Set PC time Clock synchronization It must be enabled if synchronization between UCM 316 and any Network Time Protocol NTP server is requested This option is particularly accurate since every given period Synchronization period parameter device connects to an NTP server to get current UTC time Also automatic summertime is adjusted Figure 39 Time Parameters tab NTP server configuration UCM 316 User s Manual
4. Time parameters son i Bx Td Moo Dd Figure 6 GPRS connection set up UCM 316 User s Manual 10 gt advanticsys Page 8 2 4 UCM 316 connection diagrams In the following Figure the most typical connection schemes of UCM 316 with PC are shown The Configuration Tool described in this document or any other Modbus complaint software can establish a communication link making use of Modbus RTU and or Modbus TCP protocols Ethernet internet USB R5232 R5485 Controller Internet E s IAS Type TCP IP Ethernet LAN Type TCP IP Figure 7 UCM 316 typical connection diagrams UCM 316 User s Manual advanticsys 1 0 Page 9 3 Start tab 3 1 UCM 316 Basic Information Once user has established communication with UCM 316 basic information such as User identificator Serial number Last restart Firmware version Software version etc is shown in the left frame Analog inputs Analog outputs Discrete inputs Discrete outputs Communication Archives Time parameters Start Figure 8 Start tab UCM 316 basic information UCM 316 User s Manual advanticsys gt 1 0 Page 10 3 2 Configuration files This feature enables user to save and load configuration files so that programming a number of controllers with the same configuration becomes an easy process Steps to be followed are 1 2 3 Set up all the configuration parameters mak
5. completed click on Set button in order to save changes Communication Ares Tie parameters sun GPRSIGSM race Modbus Set unique MAC 92 7 1 2 411125 04 8 DA 255 72 255 4 J255 20 Figure 20 Ethernet configuration tab UCM 316 User s Manual advanticsys 1 0 Page 19 8 2 Communication gt GPRS As previously described UCM 316 can be configured through a GPRS link In order to do so user must enable GPRS connection as shown below Then click on Set button in order to save changes Figure 21 GPRS Tab Enabling communication Within this tab different services can be configured or checked 1 GPRS connection parameters o APN access point name provided by Internet Service Provider ISP If needed by ISP credentials can also be configured here o Username provided by ISP o Password provided by ISP NOTE After configuration is completed click on Set button in order to save changes UCM 316 User s Manual advanticsys Ana inputs Analog outputs Discrete inputs Discrete outputs Communicton Awe Time parameters san GPRS GSM terface Modbus 00 Code alo Dd jo 255 21255 1255 Dd B 0410232 41255 D4 _ 232 Figure 22 GPRS tab Internet Service Provider access data configuration 2 Connection st
6. UCM 316 User s Manual 1 0 advanticsys 7 23 10 2015 1 0 gt advanticsys Page 2 Document history Date Version Author Remarks 0 Users Manual including new 23 10 2015 1 0 Sara Prior features such as Analog inputs and FTP client configuration UCM 316 User s Manual advanticsys gt 1 0 Page 3 Content DOCUMENT HISTORY 2 CONTENT 3 1 INTRODUCTION 4 2 SETTING UP CONNECTION TO THE DEVICE 5 2 1 USB connection 5 2 2 ETHERNET Connection 6 2 3 GPRS Connection 7 2 4 UCM 316 connection diagrams 8 3 START TAB 9 3 1 UCM 316 Basic Information 9 3 2 Configuration files 10 3 3 Status indicators 11 4 ANALOG INPUTS TAB 12 5 ANALOG OUTPUTS TAB 14 6 DISCRETE OUTPUTS TAB 15 7 DISCRETE INPUTS TAB 17 8 COMMUNICATION TAB 18 8 1 Communication gt Ethernet 18 8 2 Communication gt GPRS 19 8 3 Communication gt Serial Interface 22 8 39 1 Nothing 23 8 3 2 Modbus RTU Server 24 8 33 Modbus RTU Master 25 8 3 4 Router Modbus TCP to Modbus 26 8 4 Communication gt Modbus devices 27 9 ARCHIVES TAB 29 10 TIME PARAMETERS TAB 31 UCM 316 User s Manual advanticsys 1 0 Page 4 1 Introduction This Manual will show you how to configure the UCM 316 datalogger controller by using the UCM 316 configurator software Analog inputs Analog outputs Discrete inputs Discrete outputs Communication Archives Time parameters star Figure 1 UCM 316 Configurator
7. Version ofthis software 1 16 2014 08 29 Figure 3 Time 22311012015 13 03 14 Code 10 Get Restart USB connection set up UCM 316 User s Manual advanticsys gt 1 0 Page 6 2 2 ETHERNET Connection Steps to be followed Connect a RJ45 Ethernet cable to the correspondent port Open UCM 316 Configuration Tool Set up Connection Parameters frame o Select ModBus TCP IP option under Connection type Add controller IP address and TCP port in Host or IP and Port text boxes respectively Select Ethernet option under Connection through o Click on Connect to establish connection with controller O Analog inputs Analog outputs Discrete inputs Discrete outputs Communication Archives Time parameters Start 192 168 1 125 52 4 Figure 4 Ethernet connection set up UCM 316 User s Manual advanticsys 1 0 Page 7 2 3 GPRS Connection Steps to be followed Check GPRS antenna is properly connected to the device zem Figure 5 GPRS antenna connection Open UCM 316 Configuration Tool Set up Connection Parameters frame o Select ModBus TCP IP option under Connection type o Add controller IP address and TCP port in Host or IP and Port text boxes respectively o Click on Connect to establish connection with controller Analog inputs Analog outputs Discrete inputs Discrete outputs Communication Archives
8. ation NOTE Maximum number of requests per each Modbus RTU Client is 50 NOTE There exist 2 Modbus RTU clients In case that both must work together 2 different UARTs must be used one per each Modbus RTU client In Current values window it is possible to check the received information through the Modbus RTU client With this screen it is possible to check the correct performance of Modbus devices GPRSIGSM Serial Modbus dices tanter Configuring Modbus device ent values Modbus RTU Client ent Modbus RTU Client 1 SL Figure 34 Modbus devices tab Current values UCM 316 User s Manual advanticsys 1 0 Page 29 9 Archives tab The UCM 316 has an internal 8MB flash memory In case the device is used as datalogger the following steps must be done o Goto Archives Configuration o Storage parameters frame configure the following Period It defines storage interval Internal memory is organized in different blocks depending on the devices nature which are connected to the UCM 316 lf UCM 316 configurator Analog inputs Analog outputs Discrete inputs Discrete outputs Communication if Archives parameters Configuration eere configuration values Storage parameters Records in archives Period min Delay sec Records User archive 1 0 User archive 562 Clear Set Get Rea 283 Answ 282 0 0 Except
9. atus Once GPRS connection is established status will be shown as below eel 1 82 19216825420 Figure 23 GPRS tab Connection status UCM 316 User s Manual gt 1 0 advanticsys Page 21 3 DynDNS account configuration Not supported by all models in order to avoid the need to have a fixed IP address to be able to remotely access the device it is possible to set up a DynDNS account under the DDNS setting Steps to be followed are o Select Enable o Fill in information according to your DynDNS account o Click on Load from file and select dyndns org Register String txt which contains the connection string to be sent to DynDNS servers Cose pas Communicator cies Aon Time parameters Sat Enea cens UARTs vituarntataces Rating Connected Modbus devices Modbus register grouping GET nic update hostname advanticdemo dyndns org amp myip ipaddress Host members dyndns org Authorization Basic authorization User Agent AdvanticSYS MPC333 Conjroller 2 46 Figure 24 GPRS tab DynDNS configuration NOTE After configuration is completed click on Set button in order to save changes NOTE It is recommended to disable GPRS connection if not used UCM 316 User s Manual 1 0 advanticsvs Page 22 8 3 Communication Serial Interface The 1 is in charge of managing the serial communicatio
10. ing use of UCM 316 Configuration Tool Then under Start tab click on Save configuration button A dialog will be shown requesting user to select folder destination Once the file has been stored connect a new controller to the PC and then click on Open configuration and select the file previously stored Then click on Write configuration button to load such configuration into the new controller A restart will be needed so that controller can start using the loaded configuration Repeat from step 3 with all the controllers that need the same configuration Figure 9 Start tab Configuration files management UCM 316 User s Manual advanticsys gt 1 0 11 3 3 Status indicators Several status indicators are shown in the UCM 316 configuration tool in order to inform user about current performance of Modbus communication 1 2 3 4 Req number of Modbus requests performed Answ Number of Modbus answers received Tout number of Modbus requests not answered time outs raised Except number of Modbus errors 192 168 1 125 02 VA Figure 10 Start tab Status indicators UCM 316 User s Manual gt 1 0 advanticsys Page 12 4 Analog Inputs tab The UCM 316 has 6 analog inputs e Ain1 Ain3 Voltage inputs 0 5VDC 0 10 VDC Ain4 Ain6 Current inputs 0 0 20mA 4 20mA Figure 11 Analog inputs connection Go to Analog inputs Configuratio
11. n Enable the analog input Range Select the sensor output range MIN value MAX value Defines the sensor operation range Low alarm limit y High alarm limit In case of Alarms defined it configures the performance limits Current value is the current value read by the sensor and converted according the configured operation range O O 0 9 O k UCM 316 configurator laol Analog inputs e amp alag outputs Discrete inputs Discrete outputs Communication Archives Time parameters Start Configuration esterstion Analog inputs Ain Enabled Range Filter averaging Min value Max value Min resistance duration sec limit Max resistance Current value limit 1 v f Current 0 10 V 4 0 000 1000 000 27 27 4 Voltage Resistor Termistor 2 v C Current 0 10 V 4 0 000 10 000 0 01 4 Voltage Resistor Termistor 3 f Current 0 10 V 4 0 000 10 000 0 01 4 Voltage Resistor Termistor 4 Current 4 20 mA 4 4 000 20000 000 815 49 Voltage Resistor Termistor 5 Current 0 5 mA 4 1 000 0 000 Voltage Resistor Termistor 6 Current 14 1 000 0 000 Voltage Resistor Termistor Set Figure 12 Analog inputs configuration UCM 316 User s Manual advanticsys 1 0 Page 13 Apart from checking the correct Analog inputs performance by using the current values colum
12. n This UART can be configured by using the UCM 316 Config tool NOTE All devices connected to the UART1 in UCM 316 must have the same communication parameters o Bode Transmission rate bauds per second o Parity Communication Parity o Data bits Number of data bits within the communication packet o Stop bits Number of stop bits within the communication packet o Packetization o time One packet time has been reached it is considered that the packet has been properly sent o Symbol Every time a packet symbol is received it is considered that the packet has been properly sent o Length Once the packet byte count has been reached it is considered that the packet has been properly sent o Packet time Transmission duration o Packet symbol Symbol which defines packet ending o Packet byte count Length which defines packet size o Mode Full duplex or half duplex o Destination of DTR bit which defines the Data ready state has been reached It must be configured following peripheral devices connected to UCM 316 UARTs vendor information By default if this information is not available it is recommended to select OFF when send option NOTE After configuration is completed click on Set button in order to save changes Uf UCM 316 configurator zm J inputs Anal Set Get Purpose of UART Modbus RTU Server Nothing re Modbus RTU Server Modbus RTU Master Ro
13. n of the UCM 316 Config tool it is possible to read directly the corresponding modbus registers by using a Modbus function 3 Pp Desmpton 1 A2 aa Dataformat Float Physical value Float 4 4504 4505 4506 4507 4508 4509 4510 4511 Float Recalculated value Floa 4 4522 4513 4514 4515 4516 4517 4518 4519 R Figure 13 Analog inputs UCM 316 s Register list The Physical Values and Recalculated Values registers are real time registers The values are updated each 1 second UCM 316 User s Manual 1 0 gt advanticsys Page 14 5 Analog Outputs tab The UCM 316 presents 2 Channel Analog Output terminals which generate signals in the range between 0 to 10 VDC Both can be used as Dimmer signals Figure 14 Analog outputs connection In order to configure their values go to Analog Output gt Configuration In order to configure the value of the analog output just move the slide bars to the desired value i Jk UCM 316 configurator O x Analog inputs Analog outputs ieesete inputs Discrete outputs Communication Archives Time parameters Start 2 Configuratio tion Channel 1 Channel 1 Channel 2 10 00 Enabled v Range 0 0 5V 0 10V Set value V Measured value V Set Get 6 04 WA V 4 0 6 0 Output voltage V Req 2673 Answ 2654 TOut O Except 2 Figure 15 Analog output configu
14. oller will raised an alarm when one of the following state is reached Open Close Both cases o Enable archiving If enabled events produced by discrete inputs are stored in the datalogging archive o State to archive selects the discrete input state to be stored NOTE After configuration is completed click on Set button in order to save changes x 316 configurator 218 Analog inputs Analog outputs Discrete inputs Discrete outputs Communication Archives Time parameters Start Enabled Current state Debounce time ms 0 0 0 50 Mode 8 Discrete inp Discrete inp Discrete inp Discrete inp Alarm signal Alarm signal Alarm signal Alarm signal Alarm state Open Open Open Close Close f Close f Close Both cases Both cases Both cases Both cases Enable archiving Iv v v v State to archive 8 Open Open Open Open Close Close Close Close Both cases Both cases Both cases Both cases Set Get 260 Answ 186 0 0 74 Figure 19 Discrete inputs tab UCM 316 User s Manual gt 1 0 advanticsys i Page 18 8 Communication tab 8 1 Communication gt Ethernet Ethernet interface parameters can be configured within this tab o MAC number Media Access Control address IP address O Gateway IP o Mask NOTE After configuration is
15. put state 0 Output off 1 Output on g esl 4350 4351 Char fad ene esl as disabled 1 enabmed 4352 4353 Char Figure18 Discrete Outputs UCM 316 s Register list R W R W R W R W R W R W Programmed It is possible to program 2 different working calendars to the discrete outputs in Discrete outouts gt programs of weekly timer and load them to the different discrete outputs UCM 316 User s Manual advanticsys 7 1 0 Analog inputs Analog outputs Discrete Discrete outputs Communicaton Arcnives Tine parameters 17 jo 2000 j EN Figure 18 Discrete outputs programmer UCM 316 User s Manual advanticsys 1 0 Page 17 7 Discrete inputs tab Discrete inputs can be configured within this tab They are shown organized in columns and configuration parameters are shown in rows as follows o Enabled user enable disable discrete inputs to be used In order to save memory it is recommend to only enable inputs in use o Current State Graphical representation of current status open closed o Debounce time only pulses received within one or more Debounce time intervals are registered o Mode o Discrete Input input works as a standard discrete input detecting its current state 1 0 o Alarm signal input is used as an alarm input o Alarm state If Alarm signal option is selected contr
16. r configuration is completed click on Set button in order to save changes Figure 31 Virtual interfaces Modbus TCP to Modbus RTU UCM 316 User s Manual gt advanticsys 1 0 Page 27 8 4 Communication gt Modbus devices The UCM 316 can read up to 100 Modbus RTU devices through UARTS as shown in the following figure 5 9 Figure 32 Connecting Modbus RTU devices to the UCM 316 In order to configure Modbus RTU client list follow the next steps Go to Communication Modbus Devices Once the virtual interface has been enabled under Modbus RTU client UART x the list of requests for the Modbus client must be configured For this purpose it must be configured as much lines as Modbus requests required The number of requests can be configured in Amount of requests where O O Address Slave device Modbus Address Function Modbus RTU function Registers coils Register s address to be requested Amount of registers coils number of registers to be read from the register address configured in Register coils MPC Reg index Internal UCM 316 s RAM memory index where data is recorded In case of UCM 316 it starts in the address 52000 index 0 Modbus address 52000 DEC Priority It configures the request management priority UCM 316 User s Manual advanticsys Figure 33 Modbus devices tab Modbus RTU client parameters list configur
17. ration Modbus Register list Figure 16 Analog Outputs UCM 316 s Register list UCM 316 User s Manual advanticsys 1 0 Page 15 6 Discrete Outputs tab The UCM 316 has two discrete relay outputs that can perform in 2 different working modes e Manually It is possible to enable disable the relay status by using the controls that appear in Discrete outputs Configuration lk UCM 316 configurator aj inalog inputs Analog outputs Discrete inputs Discrete outputs lt Archives Time parameters Start Configuration lt fagsams of weekly timer Manual controls Programmed controls D Out 1 D Out2 Enabled Archive Restore after restart Time of impulse msec 1000 1000 Programs of weekly timer Not used Not used Program No 1 Program No 1 Program No 2 Program No 2 sq 79 Answ 78 0 0 Except 1 Figure 17 Discrete Outputs Configuration Also it is possible to manage the state of the relays by using the UCM 316 s register list with Modbus function 3 for reading or 16 for writing Modbus Register list Description 1 Do2 channel use 4300 4301 Char Discrete output state change archive 0 not store 1 gal al el M 4302 4303 Char store reset 1 restore values after reset 4304 4305 Char FE RR 20000 ms 4306 4307 Int16 Discrete out
18. us RTU Master This working mode must be used when the UCM 316 behaves as master in a Modbus RTU network it sends Modbus requests to the slaves connected to the Modbus RTU network Figure 29 Virtual interfaces Modbus RTU server o These requests will be defined under the Modbus devices tab See 5 4 communication gt modbus devices UCM 316 User s Manual gt 1 0 advanticsys Page 26 8 3 4 Router Modbus TCP to Modbus RTU The UCM 316 can also forward Modbus packets from a TCP port to a Modbus HTU client In order to do so Modbus TCP IP server mode must be always enabled as shown in the figure When the device initiating communication sends a request command to the slave device communication will be shut down when this time is reached This routing mode can be done in two ways Destination TCP port This mode enables assignment of a TCP port to each Modbus RTU device as previously configured under Communication gt Virtual interfaces gt Modbus RTU Client tab Figure 30 Virtual interfaces Modbus TCP to Modbus RTU Destination Modbus address Within this mode user can identify Modbus addresses to each Modbus RTU device as previously configured under Communication gt Virtual interfaces gt Modbus RTU Client tab With this configuration Modbus commands can be sent to devices within the network making use of the specific device Modbus address and the UCM 316 IP address and TCP port 502 NOTE Afte
19. uter Modbus to Modbus RTU Figure 25 UARTs Configuration Menu UCM 316 User s Manual 1 0 Page 23 advanticsys The UCM 316 can perform as communication gateway Modbus server client and datalogger simultaneously In order to set up these options different virtual interfaces are needed as shown below k UCM 316 configurator Analog inputs Analog outputs Discrete inputs Discrete outputs Communication Figure 26 Virtual interfaces Menu 8 3 1 Nothing This mode disables UART 1 UCM 316 configurator Analog inputs Analog outputs Discrete inputs Discrete outputs Communication quu Time parameters Start GPRSIGSM Serial bus devices Figure 27 Virtual interfaces Disabled UCM 316 User s Manual advanticsys 1 0 Page 24 8 3 2 Modbus RTU Server This mode is used when the UCM 316 is used as Modbus slave in a network Requests from a Modbus server will be received and answered o Enable Do not enable any Modbus RTU server if not needed o Address Define Modbus address for UCM 316 Modbus master must send requests to the given address NOTE After configuration is completed click on Set button in order to save changes Once the address is added press SET to update the changes and restart the controller Figure 28 Virtual interfaces Modbus RTU server UCM 316 User s Manual gt 1 0 advanticsys Page 25 8 3 3 Modb