1. S Escalonamiento 1 1 1 1 1 1 Secuencia lineal Aplicaci n para el filtrado de arm nicos 11 7 troubleshooting code faults possibleorigin____k necessaryactions__ k automation low power factor m wrong voltage connection set LL m check voltage connection setting alarm the controller has connected all steps LL LN 3 target cos p 1s not reached m wrong connection m refer to drawings behind the door m contactors or fuses do not operate m check contactors and fuses m capacitors are not effective m measure current on each capacitor terminals m bank is undersized m think about bank extension m target cos p occasionaly not m alarm can be de activated see page 20 reached CL hunting m C K setting too low m set correct value of C K or use alarm PIE unstable regulation making automatic search function progressive disconnection of all steps contactors hunt m load variations too fast m modify the bank to adapt it to regulation is stopped your site can be restarted by pressing any key or after power cut as abnormal cos m wrong voltage connection set LL m check voltage connection setting alarm ri lower than 0 3 inductive or greater LN LL LN and controller connections than 0 7 capacitive m wrong connection m refer to drawings behind the door m check location of CT AH undervoltage alarm lower than 80 of nominal voltage fast disconnection of all steps until for 1s duration v
2. C K takes between 2 and 8 minutes If for reasons of important load variations the controller cannot find a proper C K value Er appears on display and C K manual setting must be used Examples of C K manual calculation a 400 V network 500 5A CT 10 kvar first step Current in first step 10000 400 V3 14 4 A CT ratio K 500 5 100 C K 14 4 100 0 14 b 600 V network 1500 5 A CT 50 kvar first step Current in first step 50000 600 V3 48 1 A CT ratio K 1500 5 300 C K 48 1 300 0 16 m manual stepping This makes possible manual step connection and disconnection After five minutes the controller comes back to automatic regulation Connection and disconnection order depends on the regulation program selected Connection delay depends on the programmed delay between successive connections of same step Les r glages et tests de mise en service sont effectu s dans le mode installateur lls concernent O le r glage du cos P cible o la recherche automatique ou le r glage manuel du C K o la commande manuelle d enclenchement ou de d clenchement des gradins Le mode installateur est accessible par pression sur la touche pendant 2 s m le r glage du C K La valeur de C K permet de d terminer le seuil de courant r actif a partir duquel le r gulateur enclenche un gradin Elle est gale au rapport entre le courant dans le premier gradin et le ratio primaire secondaire du transformateur de courant Elle
3. alarm and warning codes flashing with cos p and the red l e d Z Der Anzeigemodus beinhaltet 3 Arten von Informationen m Cos P Anzeige X Betreibernetz induktiv Betreibernetz kapazitiv m Schaltstufenanzeige Y Meldung Regler ist im Begriff zuzuschalten 1 Meldung Regler ist im Begriff abzuschalten m Wenn n tig kann der Alarm und Fehlermeldecode Meldung mit cos p und die rote LED angezeigt werden Z und Schaltstufenanzeige visualizaci n cos P Le mode affichage comprend 3 types d information m affichage du cos P X r seau inductif L r seau capacitif m l affichage du nombre de gradins enclench s Y clignote enclenchement imminent clignote d clenchement imminent m e cas ch ant l affichage des codes d alarmes et avertissements en alternance avec le cos p et la d e l rouge Z El men usuario proporciona 3 tipos de informaci n m visualizaci n del cos P X red inductiva red capacitiva m visualizaci n del n mero de escalones conectados Y E parpadea conexi n inminente L parpadea desconexi n inminente m visualizaci n de los c digos de alarmas y avisos alternado con el cos P y LED rojo en el caso de que exista condici n de defecto zZ 4 alarms and warnings alarmes el avertissements Alarm und Fehlermeldungen alarmas y avisos The controller includes 8 alarms and 2 warnings m when an alarm
4. casos en que no se desee que permanezca el mensaje de alarma ES E sx Te _ weg aj Cc A1 de activated A1 d sactiv e A1 Quittieren A1 desactivada TN E Ce Sa a 9 technical specifications m connection type m connection features m voltage input m frequency m voltage circuit consumption m current input m current circuit consumption m step outputs contacts m alarm output contact m momentary no voltage function m alarms and warnings O line line or line neutral see drawings O insensitive to CT direction O insensitive to phase rotation polarity o 220 240 V 198 264 V 0 380 415 V 342 456 V O 50 60 Hz 1 Hz o 6 VA O for CT 5A class 1 min 0 18 A 00 7 VA O 6 volt free contacts 2 A 400 V ac 2 250 V ac 0 3 110 V de 0 6 60 V dc 2 24 V dc O 1 volt free contact 8 A 400 V ac 8 A 250 V ac 0 3 110 V de 0 6 60 V dc 2 24 V dc O disconnection of all steps after voltage loss greater than 15ms automatic reconnection abnormal cos overcapacitive frequency not detected low load current high load current overcurrent undervoltage overvoltage low power factor hunting pOoOD0o0OD0oDOoOoDOoO m power factor setting m C K setting m regulation programs m step combinations m safety delay between successive connections of same step m processing m acc
5. condition is detected the appropriate alarm code flashes on display a red l e d is switched on and the alarm relay closes Once the fault has cleared the red l e d is switched off the alarm relay opens but display of alarm code is kept till manual reset using key 4 m when a warning condition is detected a warning code is displayed and disappears when the fault has cleared Im Regler sind 8 Alarmmeldungen und 2 Fehlermeldungen integriert m Wird eine Alarmfunktion ausgel st so wird sie auf dem Display und durch eine rote LED angezeigt der Alarmkontakt wird geschlossen Wird die St rung behoben so ffnet sich der Alarmkontakt und die rote LED erlischt die Alarmfunktion im Display muB aber manuel zur ckgesetzt werden durch Tastendruck m Wird eine Fehlfunktion festgestellt so wird sie im Display signalisiert erlischt aber sofort sobald die St rung behoben ist Le r gulateur inclut 8 alarmes et 2 avertissements m orsqu une condition d alarme est d tect e le code d alarme appropri clignote l cran une del rouge s allume et le contact d alarme se ferme Lorsque le d faut dispara t la d e l rouge s teint le contact d alarme s ouvre mais l affichage du code d alarme est maintenu jusqu affranchissement manuel par pression sur la touche 4 m orsqu une condition d avertissement est d tect e seul le code d avertissement est affich jusqu la disparition du d faut El regu
6. gemessen Die Strommessung erfolgt in dem AuBenLeiter der nicht zur Spannungsmessung genutzt wird GemaB AnschluBschema auf Seite 3 m Au enleiter Nulleiter Anschluf Die Spannung wird zwischen dem Au en und Nulleiter gemessen Die Strommessung erfolgt im gleichen Pfad GemaB AnschluBschema auf Seite 3 Achtung Reglerprogrammierung und anschluB mussen konform sein Fur den Reglerbetrieb in Netzen mit abweichenden Spannungsniveaus gegenuber den Standardbemessungs spannungen von 220 240 V bzw 380 415 V werden Anpassungstransformatoren ben tigt Achtung Spezifikation der Anpassungstransformatoren fur den richtigen Netzbetrieb auslegen El regulador funciona correctamente sin tener en cuenta el sentido de rotaci n de fases ni al sentido de conexi n del transformador de intensidad Puede conectarse de dos maneras m conexi n tipo FF La medida de tensi n se realiza entre dos fases La medida de intensidad se realiza en una fase distinta de las dos fases utilizadas anteriormente Ver esquema el ctrico p gina 3 m conexi n tipo FN La medida de tensi n se realiza entre una fase y el neutro La medida de intensidad se realiza en la misma fase Ver esquema el ctrico p gina 3 Importante el tipo de conexi n utilizada debe ser coherente con la programaci n del regulador En una red de tensi n distinta de 220 240 V 380 415 V utilizar un transformador para alimentar las entradas de tensi n del regu
7. input voltage out of specifications voltage input and state of m protection fuses defective protection fuses controller does not disconnect any step C K setting is too high m enter correct C K or use at small load automatic search function m wrong target cos setting m set correct target cos e capacitive display shows that some steps are control circuit defective m check control circuit of connected but connections are not contactors effective m contactors or fuses defective m check contactors and fuses E automatic search of C K does m network is not stable m wait for network stabilisation or El not succeed manually set C K m wrong connection m check connection contactors or fuses defective m check contactors and fuses 13 8 de activating alarms d sactivation des alarmes Quittieren von Fehlermeldungen desactivaci n de las alarmas The drawing on the left gives the procedure 1 to follow to de activate one or several alarms in cases where keeping the alarm code on u display is not desirable Le sch ma de gauche donne la proc dure suivre pour d sactiver une ou plusieurs alarmes dans le cas o le maintien du message d alarme n est pas souhait Zur Reglerreaktivierung mu die jeweilige Fehlerursache gem dem zugeornetem Alarmcode behoben werden En el esquema de la izquierda se indica el procedimiento a seguir para desactivar una o varias alarmas en los
8. la puerta E conexi n de entrada corriente tensi n F conexi n de salida escalones G conexi n de salida alarma H placa de caracter sticas I sistema de fijaci n montaje superficie J zona de fijaci n montaje en carril DIN K sistema de fijaci n montaje en carril DIN L gu a Door internal side Face interne de la porte T rinnenseite Cara interna de la puerta low power factor manque de kvar hunting battement abnormal cos o cos q anormal undervoltage tension faible overcapacitive cos p capacitif wrong frequency fr quence overcurrent courant trop fort overvoltage tension trop forte low load current courant faible high load current courant lev zu wenig kvar falta de kvar Reglerstorung C K incorrecto abnormaler cos q cos q anormal Unterspannung tension baja Uberkompensation cos q capacitivo falsche Frequenz frecuencia Uberstrom sobrecarga en TI Uberspannung sobretensi n zu kl MeBstrom intensidad baja zu gr MeBstrom intensidad fuerte connection alarms and warnings raccordement alarmes et avertissements AnschluBschema Alarm und Fehlermeldungen conexionado alarmas y avisos Nota if the interface menu is left more than 5 min in another state the controller will automatically go back to its normal state cos P display N B si le menu est laiss plus de 5 min dans un autre tat le r gulateur revien
9. M Telemecanique 1 description description allgemeine Beschreibung descripci n front view vue face avant end Frontseitenansicht LG vista parte frontal Ss A gs play B keys N D opening of door E current voltage connection inputs F step outputs A G alarm outputs H specification label l mounting bracket for panel mounting installation B J DIN rail mounting installation area K fixing spring for DIN rail mounting installation L screw driver guide legende A Digitale Anzeige B Funktionstasten C Tur D T rentriegelung rear view E Netz und WandleranschluB vue face arri re F Schaltstufenausgange R ckseitenansicht G Fehlermeldekontaktausgang vis H Typenschild l Befestigungskrallen zur T rmontage J Befestigungskrallen f r Hutprofilschienenmontage K Federklemmvorrichtung f r Hutprofilschienenmontage L Schraubendreherf hrung view fom below vue de dessous Ansicht von unten vista inferior l gende A cran B touches de r glage C porte D ouverture de la porte E raccordement d entr e courant tension F raccordement de sortie gradins G raccordement de sortie alarme H plaque de caract ristiques l patte de fixation montage encastr J zone de fixation sur rail DIN K patte de fixation montage rail DIN L guide tournevis leyenda A pantalla B teclas de ajuste C puerta D apertura de
10. Varlogic R6 user manual notice d utilisation Gebrauchsanleitung gu a de utilizaci n K GERIN LA ve SZ Contents Sommaire Inhaltsverzeichnis Indice AZ Z 1 description description allgemeine Beschreibung descripci n 1 2 connection of controller raccordement du r gulateur 2 3 Regleranschlu bedingungen conexi n del regulador 3 cos and connected step display display mode affichage cos F et gradins 4 mode affichage Cos f und Schaltstufenanzeige visualizaci h cos py escalones menu usuario 4 alarms and warnings alarmes et avertissements 5 Alarm und Fehlermeldungen alarmas y avisos 5 commissioning settings commissioning mode r glages de mise en service 6 7 mode installateur Serviceprogrammeinstellungen ajustes de puesta en marcha men instalador 6 programming of controller programming mode param trage du r gulateur 8 11 N mode param trage Reglerprogrammierung programaci n del regulador GER men programador RER 7 troubleshooting p 12 13 d fauts et rem des p 14 15 12 19 Fehlermeldungen und Ursachen S 16 17 defectos y soluciones p 18 19 8 de activating alarms d sactivation des alarmes 20 Quittieren von Fehlermeldungen desactivaci n de las alarmas 9 technical specifications p 21 caract ristiques techniques p 22 21 24 Technische Daten S 23 caracter sticas t cnicas p 24 GROUPE SCHNEIDER E Merlin Gerin M Square D
11. er to drawings on page 3 Warning the connection type used must be in conformity with programming of controller On a network with a volage different to 220 240V or 380 415V use a transformer to connect controller voltage inputs Warning transformer specifications must include a limited phase variation Le r gulateur est insensible au sens de rotation des phases et au sens de raccordement du transformateur de courant Il peut tre raccord de deux mani res m raccordement type PP La mesure de la tension est r alis e entre deux phases La mesure du courant est r alis e sur une phase diff rente des deux phases pr c demment utilis es Voir sch ma lectrique page 3 m raccordement type PN La mesure de la tension est r alis e entre une phase et le neutre La mesure du courant est r alis e partir de la m me phase Voir sch ma lectrique page 3 Attention le type de raccordement utilis doit tre coh rent avec le param trage du r gulateur Sur un r seau de tension autre que 220 240 V ou 380 415 V utiliser un transformateur pour alimenter les entr es tension du r gulateur Attention le transformateur utilis ne doit induire qu un d phasage minimum Keine Funktionsbeeintrachtigungen entstehen dem Regler durch Phasenvertauschung oder falschem WandleranschluB Zwei AnschluBmoglichkeiten sind moglich m AuBenleiter AuBenleiter Anschlu Die Spannung wird zwischen zwei AuBenleitern
12. g das Programm arbeitet nur dann vollig korrekt wenn samiliche programmierten Kondensatoren schaltstufen angeschlossen sind gt Reglerprogramm Type B Cb Regelreihe 1 2 2 2 2 2 Erst ab der zweiten Schaltstufe erfolgt ein Kreisregelverhalten die ersten Schaltgruppe dient als Bezugsschaltstufen Achtung das Programm arbeitet nur dann v llig korrekt wenn s mtliche programmierten Kondensatoren schaltstufen angeschlossen sind Linearprogramm S Regelreihe 1 1 1 1 1 1 Lineares Regelverhalten Das Proramm ist z B f r Filteranlagen gedacht m posibles programas programa normal n Se utiliza para todo tipo de escalonamiento Escalonamientos usuales 1 2 4 4 4 4 1 1 2 2 2 2 Secuencia lineal a partir del tercer escal n los dos primeros son utilizados como escalones de ajuste el regulador empieza siempre por conectar o desconectar el primer escal n luego el segundo programa circular A CA Escalonamiento 1 1 1 1 1 1 Secuencia circular Importante este programa funciona correctamente s lo si el n mero de escalones de la bater a ha sido correctamente programado programa circular B Cb Escalonamiento 1 2 2 2 2 2 Secuencia circular a partir del segundo escal n el primero se utiliza como escal n de ajuste Importante este programa funciona correctamente s lo si el n mero de escalones de la bater a ha sido correctamente programado programa lineal
13. ge reset warning codes affichage cos T tat normal du r gulateur affichage nombre de gradins enclench s mode installateur mode param trage r serv au constructeur de batterie acc s prot g sch mas de raccordement codes d alarmes affranchissement du message d alarme codes d avertissement Anzeige Sch ltstufenanzeige Serviceprogrammeinstellungen Reglerprogrammierung Zugangsschutzfunktion AnschluBschaltbild Alarmcodes Quittieren von Alarmmeldungen Fehlermeldecodes visualizaci n cos estado normal adi regulador visualizaci n n mero de escalones conectados men instalador men programador reservado al constructor de bater a acceso protegido esquemas de conexi n c digos de alarmas eliminaci n de mensajes de alarma O P Q R S T U M N O P Q R S T U M cos N O P Q R S T U M N O P Q R S T U c digos de aviso 2 connection of controller raccordement du r gulateur RegleranschluBbedingungen conexi n del regulador The controller is insensitive to phase rotation and CT polarity Two different connections may be used m LL connection type Voltage is measured between two phases Current is measured from the phase that is not used for voltage connection Refer to drawings on page 3 m LN connection type Voltage is measured between one phase and neutral Current is measured from the same phase Ref
14. gramado 6 programming of controller programming mode param trage du r gulateur mode param trage Reglerprogrammierung Anwender Modus programaci n del regulador men programador voltage LL LN no of steps step program J i i C2 in 118 SEN Er non LL Pass Es fr y O y v gt lle 7 EE EE d ent gt na D a l y D 4 SH SN zl gt zl ON wi al y Y ES Eis IR on O E d n ES ent d O S SC Note nota Bemerkung nota automatic regulation continues regardless of interface operations la r gulation reste op rationnelle pendant les op rations de r glage W hrend der Neuprogrammierung entstehen keine Reglerprogrammunterbrechungen im laufenden Programm la regulaci n permanece operativa durante las operaciones de ajuste initial settings pr reglages initiaux Initialasierung pre ajustes iniciales O gt r Ly delay LL ES AE b le ED I 080 Nota 100s This paragraph is dedicated to bank manufacturers Programming of the controller is done in the programming mode It consits in the definition of the following parameters O number of physical steps in the bank o regulation program O connection type LL or LN o delay The programming mode is entered from the commissioning mode by pressing and 4 simultane
15. ispiel ejemplo ejemplo ejemplo i nota stop C K AUTO rh rep or epee 30s MH i bi El Note nota Bemerkung nota automatic regulation continues regardless of interface operations la r gulation reste op rationnelle pendant les op rations de r glage C K manual Li l ES uN Y Y wr El Es Die e un Wi oa El LI UNSa UNa UNa Pal KERS buet SG DNA DUNA DUDA S a 2 W hrend der Neuprogrammierung entstehen keine Reglerprogrammunterbrechungen im laufenden Programm la regulaci n permanece operativa durante las operaciones de ajuste initial settings pr reglages initiaux Initialasierung pre ajustes iniciales example exemple Beispiel ejemplo esc manual stepping 1 080 l EIS UNS roo Daw 63 Si ES E a a l Dona Commissioning settings and tests are done in the comissioning mode They include O target cos p setting Ra o automatic search or manual setting of C K O manual operation of steps connection disconnection The commissioning mode is entered by pressing for 2 seconds m C K setting The C K value defines the reactive current threshold from which the controller connects one step lt equals value of current in the first step divided by ratio of primary and secondary currents of the main current transformer Hence it does not take account of values of other steps Automatic search of
16. lador Importante el transformador utilizado debe inducir s lo un desfase m nimo 1 control voltage tension auxiliaire Bemessungssteuerspannung tensi n auxiliar TR 5 A class 1 50 60 Hz _380 415 V 4001230 C 1 2 3 er 4 79 10 2 connection drawing LL ex 380 415 V network sch ma de racc PP ex r seau 380 415 V RegleranschluB an LL ca 380 415 V esquema de conexi n FF ejemplo red 380 415 V TR 5 A class 1 50 60 Hz_380 415 V od ANAN O il e connection drawing LN ex 380 415 V network sch ma de racc PN ex r seau 380 415 V RegleranschluB an LN ca 380 415 V esquema de conexi n FN ejemplo red 380 415 V 3 3 COS P and connected step display display mode affichage cos pet gradins mode affichage Cos y escalones conectados menu usuario Example Exemple Beispiel X Ejemplo Y X Example Exemple 7 Beispiel Ejemplo The display mode includes 3 pieces of information m cos display X inductive network L capacitive network m connected step display Y flashes connection is about to occur flashes disconnection is about to occur m when necessary display of
17. lador incluye 8 alarmas y 2 avisos m cuando se detecta una condici n de alarma el c digo de alarma apropiado parpadea en la pantalla el led rojo se enciende y el contacto de alarma se cierra Una vez desaparecido el defecto el led rojo se apaga el contacto de alarma se abre pero la visualizaci n del c digo de alarma permanece hasta la eliminaci n manual presionando sobre la tecla 4 m cuando se detecta una condici n de aviso s lo se visualiza el c digo de aviso hasta la desaparici n del defecto low power factor manque de kvar hunting battement abnormal cos y cos q anormal undervoltage tension faible overcapacitive cos p capacitif wrong frequency fr quence overcurrent courant trop fort overvoltage tension trop forte low load current courant faible high load current courant lev zu wenig kvar falta de kvar Reglerst rung C K incorrecto abnormaler cos q cos q anormal Unterspannung tension baja Uberkompensation cos q capacitivo falsche Frequenz frecuencia berstrom sobrecarga en TI berspannung sobretensi n zu kl MeBstrom intensidad baja zu gr MeBstrom intensidad fuerte 5 commissioning settings commissioning mode r glage de mise en service mode installateur Serviceprogrammeinstellungen ajustes de puesta en marcha menu instalador target cos C K auto example example SE exemple exemple exemple Beispiel 080 Beispiel 080 Be
18. ne tient donc pas compte des valeurs des autres gradins La recherche automatique du C K dure entre 2 et 8 minutes Si pour des raisons de variation de charges excessives la recherche n aboutit pas l cran affiche Er et un r glage manuel est indispensable Exemples de calcul manuel du C K a r seau 400 V TC 500 54 premier gradin 10 kvar Courant dans le premier gradin 10000 400 V3 14 4 A Ratio du TC K 500 5 100 C K 14 4 100 0 14 b r seau 600 V TC 1500 5A premier gradin 50 kvar Courant dans le premier gradin 50000 600 V3 48 1 A Ratio du TC K 1500 5 300 C K 48 1 300 0 16 m a commande manuelle La fonction de commande manuelle permet d enclencher et de d clencher des gradins manuellement Apr s cing minutes le r gulateur retourne en fonctionnement automatique L ordre d enclenchement et de d clenchement est fonction du type de programme param tr Le retard a l enclenchement est fonction de la valeur de temporisation param tr e Serviceprogrammabfragen und Tests k nnen nur in der Serviceprogrammeinstellung durchgef hrt werden Sie beinhalten o Eingabe des Ziel cos E o Automatische oder manuelle C K Einstellung O Manuelle Stufenschaltung Zu und Abschaltung Serviceprogrammabfragen werden durch bet tigen der Taste f r 2 s aktiviert m Eingabe des C K Werts Der C K Wert definiert den Blindstromanteil ab wann eine Kondensatorenstufe zugeschaltet wird Die kleinste Kondnesato
19. near sequence For harmonic filtering applications m programmes possibles programme normal n Convient pour tout type de gradinage Gradinages courants 1 2 4 4 4 4 ou 1 1 2 2 2 2 S quence lin aire a partir du troisieme gradin les deux premiers gradins tant utilis s comme gradins d ajustement le r gulateur commence toujours par enclencher ou d clencher le premier gradin puis le second programme circulaire A CA Gradinage 1 1 1 1 1 1 S quence circulaire Attention ce programme ne fonctionne correctement que si le nombre de gradins de la batterie a t correctement param tr programme circulaire B Cb Gradinage 1 2 2 2 2 2 S quence circulaire partir du second gradin le premier gradin tant utilis comme gradin d ajustement Attention ce programme ne fonctionne correctement que si le nombre de gradins de la batterie a t correctement param tr programme lin aire S Gradinage 1 1 1 1 1 1 S quence lin aire Application filtrage d harmoniques m Regelprogrammarten n M gliche Regelungsarten Allgemeien Kombinationsarten 1 2 4 4 4 4 oder 1 1 2 2 2 2 Erst ab der dritten Schaltstufe erfolgt ein lineares Regelverhalten die zwei ersten Schaltgruppen dienen als Bezugsschaltstufen der Regler schaltet stets erst die 1 und dann die 2 Schaltstufe zu bzw ab Reglerprogramm Type A CA Regelreihe 1 1 1 1 1 1 Kreisregelverhalten Achtun
20. o ajuste del cos y objetivo H o ajuste SE del C K o ajuste manual del C K o control manual de conexi n o desconexi n de los escalones Se accede al men instalador presionando la tecla durante 2 s m ajuste del C K El valor del C K permite determinar el umbral de intensidad reactiva a partir del cual el regulador conecta un escal n Es igual a la relaci n entre la intensidad del primer escal n y la relaci n primario secundario del transformador de intensidad No tiene en cuenta los valores de otros escalones La b squeda autom tica del C K dura entre 2 y 8 minutos Si por motivos de variaci n de cargas excesivas la b squeda fracasa la pantalla visualiza Er y es necesario un ajuste manual Ejemplos de c lculo manual del C K a red 400 V TI500 5A primer escal n 10 kvar Intensidad en el primer escal n 10000 400 V3 14 4 A Relaci n del TI K 500 5 100 C K 14 4 100 0 14 b red 600 V T11500 5 A primer escal n 50 kvar Intensidad en el primer escal n 50000 600 3 48 1 A Relaci n del TI K 1500 5 300 C K 48 1 300 0 16 control manual de entrada salida de escalones La funci n de control manual permite conectar y desconectar escalones manualmente Transcurridos cinco minutos el regulador vuelve al funcionamiento autom tico La orden de conexi n y desconexi n depende del tipo de programaci n introducida El retardo en la conexi n depende del valor de temporizaci n pro
21. oltage becomes normal again automatic reconnection OC capacitive cos m wrong voltage connection set LL m check voltage connection setting alarm i overcapacitive controller has LN LL LN disconnected all steps m wrong connection m refer to drawings behind the display shows capacitive cos P door m Capacitive network presence of m reduce reactive energy at small fixed capacitors at small load load m alarm can be de activated see page 20 alarm fast disconnection of all steps automatic reconnection nO frequency not detected 7 50 or 60 Hz 1Hz 12 code faults possible origin necessary actions automation D overcurrent m installation overloaded alarm TI greater than 6A for 180 s on CT ECT indere replace CT secondary side IO overvoltage alarm I ILI greater than 120 of nominal voltage for 60 s low load current m small load warning l lower than 0 24A for 2s on CT m defective CT circuit m check CT circuit using an secondary side ammeter IL high load current m CT undersized m replace CT warning I FTI greater than 5 5A for 30s on CT secondary side cos p display is not stable m wrong voltage connection set m check voltage connection setting LL LN LL LN m wrong connection m refer to drawings behind the door m check that CT has been correctly selected secondary 5A display is blank and does not react m wrong connection m check connection of controller to any key m
22. ously for 2 seconds m regulation program There are two main types of regulation sequences O the linear sequence O the circular sequence Each of the four possible regulation programs of this controller use one of these two sequences as a main principle See page 10 m delay This is the safety delay between successive connections of same step Warning if a short delay is used capacitors and contactors may be damaged Never use a shorter delay than recommended by the capacitor manufacturer The response time before connection or disconnection is automatically set at one fifth of the above delay with a minimum value of 10s Warning automatic regulation continues regardless of interface operations Ce paragraphe est r serv au constructeur de la batterie de compensation Le param trage du r gulateur est r alis dans le mode param trage Il consiste a d finir les param tres suivants o nombre de gradins physiques de la batterie O programme de r gulation o type de raccordement PP ou PN o temporisation _8 Le mode param trage est accessible partir du mode installateur par pression simultan e sur les touches et 4 pendant 2 s m programme de r gulation Il existe deux principaux types de s quences de r gulation O la s quence lin aire o la s quence circulaire Les quatre programmes de r gulation possibles de ce r gulateur utilisent chacun l une de ces deux s quences comme p
23. renbaustufe ist deshalb eine wichtige Gr e f r den Blindleistungsregler und muB anhand des Ubersetzungsverhaltnisses des Stromwandlers erfast werden Die automatische C K Wertprogrammierung dauert zwischen 2 und 8 Minuten Kann aus irgend einem Grund der C K Wert nicht automatisch eingestellt werden erscheint eine ER Fehlermeldung in der Regleranzeige der C K Wert mu dann manuell eingegeben werden Beispiel einer C K Wert Berechnung a 400 V Netzbemessungsspannung Wandlerverh ltnis 500 5 A kleinste Kondensatorenstufenleistung 10 kvar Kondensatorblindstrom Ic 10000 kvar 400 V V3 14 4 Ar Wandler bersetzungsverh ltnis k 500 A 5 A 100 C K Wert C K 14 4 Ar 100 0 144 Ar b 600 V Netzbemessungsspannung Wandlerverh ltnis 1500 5 A kleinste Kondensatorenstufenleistung 50 kvar Kondensatorblindstrom Ic 50000 kvar 600 V V3 48 1 Ar Wandler bersetzungsverh ltnis k 15004 5A 300 C K Wert C K 48 1 Ar 300 0 16 Ar Manuelle Stufenschaltung Es ist m glich Schaltstufen zu und abzuschalten Werden keine manuelle Schaltvorg nge durchgef hrt schaltet der Regler nach 5 Minuten ins Automatikprogramm zur ck Zu und Abschaltungen h ngen von dem ausgew hlten Reglerprogramm ab Zu und Abschaltzeiten einzelner Schaltstufen sind von der einprogrammierten Verz gerungzeit im Regler abh ngig Los ajustes y tests de puesta en marcha se efect an en el men instalador Se refieren a
24. rincipe de base voir page 10 m temporisation Il s agit du temps de s curit entre connexions successives d un m me gradin Attention la s lection d une valeur faible de temporisation peut endommager condensateurs et contacteurs Ne pas s lectionner une temporisation plus faible que celle recommand e par le constructeur de condensateurs Le temps de r ponse a l enclenchement ou au d clenchement est r gl automatiquement une valeur gale au cinqui me de la valeur de temporisation avec une valeur minimum de 10 s Attention la r gulation est op rationnelle pendant les op rations de r glage Dieser Abschnitt ist f r Kompensationsanlagenbauer bestimmt Die Programmierung des Reglers ist ber den Anwendermodus vorzunehmen Folgende Parameter m ssen definiert werden O Anzahl der physikalisch angeschlossenen Kondensatorenschaltstufen o Regelprogramm o AnschluBart LL oder LN o Schaltzeiten Vom Benutzer Modus springt man in den Anwender Modus indem folgende Tasten f r 2 Sekunden gedr ckt werden gt und 4 m Regelprogramm Zwischen zwei Hauptregelprogrammarten kann gew hlt werden O Standard Regelung linear D Kreisregelung Jede der vier Regelungsarten des Reglers ben tigen eine der zwei Hauptregelprogrammarten s S 10 m Schaltzeit Hier handelt es sich um den Sicherheitsschaltzeitraum den die einzelnen Kondensatorenschaltstufen ben tigen Achtung Zu kleine Schaltzeiten fuhren z
25. t automatiquement l tat normal affichage du cos p Front face of controller door opened Face avant du r gulateur porte ouverte Frontseitenansicht bei ge ffneter T r Cara anterior del regulador con la puerta abierta Q M N i 1 o steps gt G gradins 2 2 Stufen Ell escalones ent target cos D cos cible ziel cos cos deseado C K auto C K auto CIK auto C K auto E In C K manual C K manuel IK Manuell C K manual LL manual stepping commande manuelle Handschaltung conexi n manual no of steps nb de gradins Anzahl der Stufen n de escalones step program programme Schaltprogramm programa voltage LL LN tension PP PN Netzspannung tension FF FN CHEW temporisation Schaltzeit temporizacion interface menu menu d utilisation Funktionsmenu menu de utilizacion Bemerkung Wurden keine neuen Anweisungen innerhalb von 5 Minuten im Funktionsmenu vorgenommen kehrt automatisch das Programm zum Normalstatus zur ck cos P Anzeige Nota si el men permanece durante m s de 5 minutos en otro estado el regulador vuelve autom ticamente al estado normal men usuario visualizaci n del cos p legend l gende Legende leyenda M cos e display normal state of controller N connected step display commissioning mode programming mode restricted to bank manufacturer protected access connection drawings alarm codes alarm messa
26. u Kondensatoren und Schutzproblemen Niemals die werksseitig eingestellte Schaltzeit unterschreiten Die zusatzliche Verz gerungszeit f r das Zu und Abschalten ist automatisch vorgegeben und betr gt 1 5 der minimalen Schaltzeit von 10 sek Achtung w hrend der Neuprogrammierung entstehen keine Reglerprogrammunterbrechungen im laufenden Programm Este apartado est reservado al constructor de la bater a de condensadores La programaci n del regulador se efect a en el men programador Consiste en definir los par metros siguientes o n mero de escalones f sicos de la bater a o programa de regulaci n o tipo de conexi n FF 6 FN o temporizaci n Se accede al men programador desde el men instalador presionando simult neamente las teclas y eq durante 2 s m programa de regulaci n Existen dos tipos principales de secuencias de regulaci n O o la secuencia lineal O lo la secuencia circular Los cuatro posibles programas de regulaci n de este regulador utilizan una de estas dos secuencias como principio de base ver p gina 10 m temporizacion Se trata del tiempo de seguridad entre conexiones sucesivas de un mismo escalon Importante la seleccion de un valor bajo de temporizacion puede danar los condensadores y contactores No se debe seleccionar una temporizacion inferior a la recomendada por los constructores de condensadores El tiempo de respuesta a la conexi n o desconexi n est reg
27. ulado autom ticamente a un valor igual a la quinta parte del valor de temporizaci n con un valor m nimo de 10 s Importante la regulaci n permanece operativa durante las operaciones de ajuste del regulador step combination possible programs gradinage programmes possibles Schaltkombination Regelprogrammarten escalonamiento programas posibles 1 1 1 1 1 1 CA n S 1 1 2 2 2 2 n 1 1 2 3 3 3 n Vee eee Cb n 1 2 3 3 3 3 n 1 2 3 4 4 4 n 1 2 4 4 4 4 n linear sequence S quence lin aire Standard Regelung linear secuencia lineal circular sequence S quence circulaire Kreisregelung secuencia circular 10 m possible programs normal program n Suits all step combinations Common combinations 1 2 4 4 4 4 or 1 1 2 2 2 2 Linear sequence from the third step the first two steps being used as adjustment steps the contoller always first connects or disconnects the first step then the second gt A type circular program CA Step combination 1 1 1 1 1 1 Circular sequence Warning this program will corretly operate only if the total number of steps in the bank is correctly set B type circular program Cb Step combination 1 2 2 2 2 2 Circular sequence from the second step the first step being used as an adjustment step Warning this program will correctly operate only if the total number of steps in the bank is correctly set Stack program S Step combination 1 1 1 1 1 1 Li
28. uracy class m display m user interface m temperature m protection class m enclosure E colour m dimensions m panel cut out m DIN rail mounting m weight m connection m EMC standard O digital 0 80 ind 0 90 cap O automatic search or manual setting digital 0 1 99 O normal circular 2 versions linear 1 2 2 2 2 2 1 2 3 3 3 3 1 2 3 4 4 4 1 2 4 4 4 4 O digital setting 10 s 300 s O digital microprocessor 02037 O 7 segments l e d O 4 keys on front face 3 access levels O working state 0 50 C O in storage 20 60C O DIN rail mounting IP 20 panel mounting IP 40 o UL94 VO class o RAL 7021 O 144 x 144 mm DIN 43700 depth 80 mm o 138 x 138 mm 0 1 mm DIN 43700 O according to EN 50022 O 0 65 kg O using connectors provided with contoller O EN 50082 2 EN 50081 2 Schneider Electric SA As characteristics and dimensions of our products are constantly changing please contact our offices for confirmation Les caract ristiques et encombrements des produits pouvant voluer doivent tre confirm s par nos services Abweichungen zwischen dem gelieferten Ger t und der technischen Dokumentation sind m glich Las caracter sticas y dimensiones de los productos susceptibles de evolucionar deben ser confirmadas por nuestros servicios R alisation AMEG SA 07 1996