Integration of Monitoring Equipment to a SCADA System
Contents
1. 35 to support most any type of device 31 In addition detailed procedures were created for each step of the integration where possible These templates and procedures have significantly eased the learning curve for new members of the team making them pro ductive much faster REMUS has been shown to be very adaptable and with the in house development and maintenance effort all the problems encountered including scalability have been quickly resolved Working closely with the end users has allowed us to integrate de vices at much faster pace and to the user s satisfaction As REMUS itself has matured so has the integration process The documents and procedures in addition to the tem plates provide a straight forward path to follow with few unknowns Roadblocks and surprises are still encountered but they are limited mostly to the devices themselves The process allows for quick and predictable integration of various types making it possible for technical students who are usually employed for one year to do at least two integrations of different devices thus providing them with a broad experience in the area of SCADA systems and monitoring equipment 36 7 END NOTES A big part of the thesis was the actual integration of Berthold Technologies LB 112 monitoring instrument The documentation the test results and the source code are available on request but for liability and security reasons the requests must go through
2. CERN Technology Transfer Similarly additional details on each step of the integration procedure from analysis to deployment is available on CERN EDMS document sharing system under the REMUS project documents 37 REREFENCES 1 6 10 11 12 13 S Kleiner 2001 Monitoring of Non Radiation Environmental Parameters at CERN Geneva Switzerland CERN ETM WWW page 2014 Referred 03 11 2014 http www etm at Herve Milcent amp Paul Burkimsher amp Wayne Salter 2003 How do I write a Driver Ctrl Managers API Managers and Drivers CERN Referred 03 11 2014 CERN EN Department Knowledge Base The LHCb collaboration WWW page 2014 PVSS Introduction for Newcom ers Referred 03 11 2014 http lhcb online web cern ch lhcb online ecs PVSSIntro htm Ambler Thompson amp Barry N Taylor 2008 NIST Special Publication 811 G Segura Millan amp D Perrin amp L Scibile 2005 RAMSES The LHC Radia tion Monitoring System for the Environment and Safety Geneva Switzerland CERN A Daneels amp W Salter 1999 What is SCADA Geneva Switzeland CERN O Holme et al 2005 The JCOP framework Geneva Switzerland CERN W Mexner et al 2008 Experiences with PVSS II as an overall SCADA system for ANKA Karlsruhe Germany Forschungzentrum Karlsruhe A Di Meglio M Gaillard A Purcell 2014 CERN openlab Whitepaper on Fu ture IT Challenges in Scientific Research Geneva Switzerland CERN P C B
3. changes became more and more complex as each additional variable would cause mul tiple cascading effects Creating a procedure for these changes made it obvious that something had to be done though it was too late for this project It was decided that a more generic driver would be created with the express purpose of simplifying modi fications This lead to the template driver project which has been used in all later in tegrations requiring custom drivers 5 5 Testing and Deployment While internal testing was fast it was difficult to get the users to take time of their schedules to validate the product To emphasize the importance of their involvement we had to offer the test procedure as the final chance to make requests and changes After deployment any and all changes would be released with respect to the release cycle of the entire monitoring system and would not have the same priority as the integration of new devices In the end the product was accepted with little to very few changes necessary and on time 26 32 5 6 Maintenance Later on a problem was found when a new batch of LB 112 devices was delivered to CERN This batch had a different wiring order for the relays used to control the alarm unit On MEVIS setting up relay triggers happened simply by relay number but on REMUS it was assumed that the relays would always be configured in the same order for the horn the interlock and the three different colored lights Unfo
4. and robustness of com munication with these devices adds an additional point of failure and reguires consid eration when designing communication with devices Remus was created from ground up with the purpose of empowering trusted users by letting them add devices and create new views tasks which had previously been left 34 to system administrators Delegating some of the administrative tasks to trusted end users meant that the team could concentrate on the integration of other equipment and in the general improvement of the software However the users lacking understanding of the limitations of the system ended up creating some unexpected views consisting of unforeseen amounts of devices While the event manager is very stable even under extreme stress 11 the increased amount of devices and the rising amount of simulta neous users caused increasingly poorer performance as the callback functions started to get queued up This has required us to frequently revisit the software in an effort to increase performance A few different approaches have been tried including low level comparison and caching in different stages to reduce unnecessary communication and separation of volatile variables to separate function calls These findings will be pre sented at ICALEPCS 2015 The external process of injecting measurements and events to database from temporary files was recycled from the previous SCADA system which foresaw the possible pro
5. importance of this is magnified at CERN with the extremely short contracts and high employee turnover As the task of device integration is often given to a stu dent creating minute and accurate documentation is especially important 4 8 Testing and validation To ensure the quality of the product a rigorous test procedure is created and followed The tests must be executable with no external programs so that users can perform them provided they have the correct access rights The tests should cover all of the requested functionality ensuring data validity and that alarms faults and events are working correctly It should be noted that slight variation will occur between the values stored on device the driver in the injection files the database and displayed on the faceplates This is due the differences in manner of storage of floating point numbers How each device stores and transmits measurements varies wildly and is out of our control On the drivers the values are stored as 64 bit double precision floating point numbers but when they are sent to the event manager they must be cast to 32 bits as WinCC OA does not support 64 bit floating point numbers Similarly when the measurements are 26 written to the injection files only six significant figures are kept In addition the pro cedure must test for product robustness that is how it will react in case of excessive load networking issues and server crashes While CERN infrast
6. inspired the creation of the REMUS development templates that could facilitate faster de velopment and would provide a gentler learning curve for new members of the team VALVOMOLAITTEEN INTEGRAATIO SCADA JARJESTELMAAN Silvola Riku Pekka Satakunnan ammattikorkeakoulu Tietotekniikan koulutusohjelma Kes kuu 2015 Ohjaaja Petteri Pulkkinen amp Ari Pekka Kainu Sivum r 39 Liitteita 0 Asiasanat SCADA HMI WinCC OA PVSS CERN REMUS T m opinn yte on tehty CERN in HSE SEE Computing osastolle Sen tarkoituksena oli integroida valvomolaite REMUS SCADA j rjestelm n ja ohessa dokumentoida ja formalisoida integraatioprosessi Opinn yte on jaettu nelj n osaan Aluksi k sittelemme projektin l ht kohtia p m r ja projektin arkkitehtuuria Toisessa osassa k sittelemme eri tutkimus menetelmi ja k ymme l pi yleisesti integraatio prosessia ja sen eri vaiheita Nelj s osa on tapaustutkimus s teilyvalvontalaitteen integraatio prosessista Viidenness osassa k ymme l pi projektin esille tuomia ongelmia ja mahdollisia ratkaisuja T m n opinn ytteen tuloksena oli Berthold Technologiesin LB 112 mikro gamma dataloggerin onnistunut integraatio REMUS SCADA j rjestelm n sek lukuisten parannusten tuominen j rjestelm n itseens Integraatio prosessista l ytyi huomattavasti parantamisen varaa Kohdatut ongelmat inspiroivat moninaisten mallipohjien luomisen jotka ovat auttaneet nopeuttamaan kehitys
7. on time and with minimal change reguests The methodologies used were sound and played an essential role in the project s success No surprises were experienced in the final validation phase as the users had been continuously involved with the project Without their involvement the testing and validation phase could have dragged on for much longer as possibly drastic modification would have been postponed until then The users have felt at home in the new SCADA system leading to a sharp decline in the amount of support re guests Prior to the integration it would not be uncommon for the section to receive calls from the users reguesting help in navigating the other systems This can be at tributed to the more intuitive user experience that was achieved by letting the users participate in the design process One major problem encountered was the lack of responsiveness of the devices The lifetime of monitoring eguipment can be up to multiple decades A class of eguipment called ARCON that was designed and created at CERN in the 80 s is still in active use and has been integrated to the previous SCADA systems 6 14 These are not the only legacy systems still in use and most monitoring instruments are still not created with remote control or continuous data acguisition in mind It is common to utilize a legacy industrial bus such as RS232 RS485 or Modbus 12 and then bridge it to Ethernet with a converter 13 This severely limits the speed
8. work could start 5 4 Development During the analysis we had gotten very familiar with the device and subsequently there were very few surprises during the development Some additional idiosyncrasies were found on the communication protocol requiring additional constraints and safeguards to be added 25 To gain more control over the driver state the LB112 integration implemented a sort of a finite state machine 24 This FSM has evolved to the REMUS Finite State Machine mentioned in the prior chapters 31 LB 112 uses serial communication wrapped in TCP IP packages with the encapsula tion being done by a MOXA modem Communication is half duplex with the device requiring about 200 milliseconds delay between messages Message collisions were not of much concern on earlier firmware but later versions exhibited lockdowns re quiring local intervention At CERN these are not always possible While active cer tain areas of the complex can have high levels of radiation rapidly fluctuating mag netic fields or temperatures near absolute zero The control and acquisition loop was redesigned during the development to minimize the chance of collisions on the ex pense of responsiveness In the later phases of the development it became evident that parts of the driver were less than easy to modify Simple addition of a device variable required changes in no less than six places in the driver As the number of variables grew making all these
9. 2 REMUS Integration Technical Specifica tion https edms cern ch document 1276649 Riku Pekka Silvola 2013 On LB112 Commands https edms cern ch document 1276650 A Dorsival amp M Widorski 2013 LB112 REMUS Integration Reception by Users https edms cern ch document 1314681 ETM 2013 PVSS Online Help 28 29 30 31 32 33 34 35 36 39 Riku Pekka Silvola 2013 REMUS LB112 User Manual https edms cern ch document 1303340 Riku Pekka Silvola 2013 Project Definition and User Requirements of LB112 into REMUS https edms cern ch document 1304938 Riku Pekka Silvola 2014 REMUS Finite State Machine https edms cern ch document 1410643 Riku Pekka Silvola 2014 REMUS Template Driver Technical Specification https edms cern ch document 1424954 Thomas Kuhn 1961 The Function of Measurement in Modern Physical Sci ence Chicago The United States of America The University of Chicago Press C Marshall amp G B Rossman 1998 Designing Qualitative Research Thousand Oaks The United States of America SAGE R Diriw chter amp J Valsiner 2006 Qualitative Developmental Research Meth ods in Their Historical and Epistemological Contexts Forum Qualitative So cial Research V Kaptelinin amp B Nardi 1997 Activity Theory Basic Concepts and Applica tions CHI 97 ISO 9241 210 2010 Human centered design for interactive systems ISO
10. Riku Pekka Silvola INTEGRATION OF MONITORING EQUIPMENT TO A SCADA SYSTEM Degree Programme in Information Technologies 2015 samk o Satakunnan ammattikorkeakoulu Satakunta University of Applied Sciences INTEGRATION OF MONITORING EQUIPMENT TO A SCADA SYSTEM Silvola Riku Pekka Satakunnan ammattikorkeakoulu Satakunta University of Applied Sciences Degree Programme in Information Technologies June 2015 Supervisor Petteri Pulkkinen amp Ari Pekka Kainu Number of pages 39 Appendices 0 Keywords SCADA HMI WinCC OA PVSS CERN REMUS This thesis was done for the HSE SEE Computing section of CERN Its purpose was to integrate a radiation monitoring instrument to the REMUS SCADA system document the integration process and create a procedure for further integrations The thesis is divided into four parts The first part details the reasons behind the project and the underlying architecture In the second part we go through some re search methods and document the integration process and its different phases The third part is a case study on the integration of a radiation monitor The fourth part depicts the problems faced during and after the integration and the possible solu tions for them The result of the thesis was a successful integration of the Berthold Technologies LB 112 micro gamma logger and further improvements to the REMUS supervisory system The integration process showed much room for improvement and
11. alibration factor The raw measurements are made with counts per second and the users must apply specific calibration factors to convert from cps to say uSv h These calibration factors depend on the instrument itself and on the type of radiation measured The unit must still be known and supported so that the measured valued can be stored in a meaningful format and to allow further conversion and cal culations 5 3 Driver and UI design Inspiration for the driver design was taken from an older driver created for another device For each monitoring station the driver would create an instance of a monitoring station class and a thread running an infinite control and acquisition loop The moni toring station class would hold measurement data and parameters held in data points and the corresponding values held in the device to detect inconsistencies and to reduce unnecessary data transfer The control and acquisition loop would read measurements and write commands to the device A number of reader classes were created to extract and transform values received from the device Once a message was acquired from the device by the acquisition loop the buffer would be passed to a reader factory The factory would recognize the type of message by matching a part of it to known message types and then returning the ap propriate reader with the message already fed to it The reader would be then used to get the actual values received and to store them i
12. ap proach is not recommended 8 Part of REMUS is the Oracle database that holds a record of the structure for each monitoring station type This structure is used when creating new instances of that type Each individual instance of a monitoring station type is then declared on the database to track changes to its configuration and events 21 Injection of data to the database is done either directly from WinCC OA or from in jection files In general events relating to user interactions such as requesting monitor ing station mode and parameterizations have their events along with data injected di rectly to the database Events and measurements acguired from devices can come in bursts or in guick succession exceeding the limitations of what a SCADA system can inject to the database 6 and are written to files These files are then injected to the database with SOL Loader once a minute 20 The approach allows for batch inser tion of data from multiple different sources and provides much better efficiency This method of database injection was created for the previous outsourced SCADA system and was extended for our purposes with only minor modifications 13 2 3 REMUS Finite State Machine The REMUS Finite State Machine FSM is used to track the state of each monitoring station as well as to trigger functions 30 As REMUS can be accessed by multiple users at the same time it was necessary to create a system to track the state of eac
13. ay be useful This specification should document the expected user interface and the experience of using it This includes such things as the colours of status indicators in 18 their various states the format of numbers and dates etc REMUS has a colour coding system for these indicators 15 which should be followed but on certain indicators it can be necessary to deviate from strictly following it if only to reduce ambiguity in the specific case 4 2 Analysis From the user requirements the device s manual and communication document a fea sibility analysis document is made to match the requirements with what is possible In addition to the limitations and functionalities stated in the documents the device must go through a strict analysis Very often the limitations stated on manuals refer to an R amp D environment with a single device and minimal outside elements While the doc umentation of the device and its communication protocol are invaluable in understand ing the functionality and the limitations of the device they should not be trusted blindly These documents very often takes a backseat during development and is only created and updated almost as an afterthought leaving room for outdated and some times downright false information During the analysis every function remotely available must be tested with both valid and invalid data To make this testing faster it can be useful to create a simple program to directl
14. b lems of drivers interfacing with the database directly The first few devices integrated to REMUS produced measurements at a fairly low frequency once every minute or two and for these a single threaded file writer was more than sufficient Later integra tions have included devices generating measurements at much faster rates up to one measurement every 0 1 seconds With a rate as high as this additional bottlenecks will require consideration In addition to the aforementioned limitations of the event man ager the disk I O might not always be able to keep up with the incoming flood of data This development will require additional buffers and possibly monitoring station spe cific file writing threads In any case changes in the file writing scheme are to be expected Integration of LB112 was done with the intent of supporting just that device type and while the specialized code used was fast to write and easy to test later modifications were difficult and subsequently very little code could be recycled to later projects The problems faced nearing the completion of development gave inspiration to the REMUS template project which has helped shorten integration times This can be seen in the evolution of project timelines as a student is now able to integrate two to three devices per year as opposed to being limited to one The templates created range from CONTROL scripts for common panels to a generic driver that can be easily extended
15. by the driver and data is not directly passed to devices Instead all data points are considered internal to the driver and thus the transformations are actually to and from C types These trans formations must be implemented for each type of data received and sent from the driver to the event manager It is possible to have multiple values sub indexed on one address but the number of elements must be same for all data points using the trans formation Should one not declare the amount of sub indexed elements API will try to free the same memory multiple times resulting in undefined behavior Notably this will not crash the driver until the sixth element Every WinCC OA component including the drivers work in full redundancy on REMUS During normal operation the event managers of both servers will keep their data points synchronized and consistent Should one of the servers go down either abruptly or for planned maintenance the other will take over seamlessly continuing from where the first left off Data point updates are not communicated to the redundant driver during normal operation and when a redundancy switch occurs the driver must be notified of the current values The values must be updated on the driver but should 23 not be propagated to the device This is much the same as in the initialization and it is customary to use the initializing FSM state during this process If the REMUS FSM is used great care must be taken t
16. changed and for initialization purposes The Event manager will periodically call function HWService workProc This should happen every 10ms but the timing is done by a dispatch call which can also suffer from congestion leading to variance of up to multiple seconds 3 During this call the driver has the attention of the Event manager and it is safe to pass data to the event manager with the HWDrvManager toDP function API Driver communication Jata point update i transformation A writeData H H async workProc gt e toDP T U U transformation Illustration 7 API Driver communication 22 HW Object is a WinCC OA API library class holding the data to be passed as well as the information necessary to identify it REMUS makes extensive use of the address property Specified in the device type s data point elements it holds both a numerical identifier for the monitoring station and a textual identifier for the data point For driver wide data points the numerical identifier is left to zero Illustration 8 Simplified HWObject class elements HW Objects pass through transformation before arriving to the driver and after being sent to the event manager A transformation is a custom class used to transform data from hardware format to WinCC OA data point element types and vice versa On REMUS much of the measurement and event analysis is done
17. created func tions These dynamic callbacks aren t as efficient as inline data point functions but allow complex functions to be executed from unsolicited driver messages 4 5 Driver design Each driver must be specified in the REMUS database much in the similar manner as with device types though their definitions are usually much shorter due to having less data points and alarms The drivers communicate between the event manager and the devices This is done by passing HWObjects with derived classes inherited from the WinCC OA API library 21 Changes to the data points with addressing to the driver will arrive as calls to the func tion HWService writeData 23 which must be implemented in the driver to receive them By calling HWDrvManager toDP the driver can pass data to data points 3 It should be noted that while it s possible to write multithreaded drivers the PVSS libraries are not multi thread safe 23 Driver designs must be made with this limita tion in mind In addition there are functions in the WinCC OA library that can be used to query singular data point elements but these are not as efficient or thread safe and are not used in REMUS All data in PVSS passes through the event manager including data between other managers the UI and the drivers Calls to these functions should be restricted to the bare minimum to prevent congestion This means limiting data point updates to only when their values have
18. ctions but some of these will not make sense to be available remotely and for simplicity s sake some expert functions should be restricted to local modification If a function is only used when the device is initially installed it makes little sense to provide a way to change it remotely In addi tion as parameterization should check for data compliancy the ranges of valid param eter values must also be specified Monitoring stations generate measurements at varying frequencies from once every few minutes to every 100 milliseconds 6 and aside from special circumstances such as exceeded alarm thresholds these values can be averaged to save space after they lose their pertinence In addition the everyday usage of the system and devices can generate huge amounts of data especially considering effects of scaling from one de vice to possibly hundreds or thousands of devices Aside from few special events such as alarms most of them lose their value in a matter of years quickly and should not be retained longer than necessary This point can be particularly hard to drive through to the stakeholders but for the long term performance and cost efficiency it is very im portant In addition a separate user interface specification can be created Sometimes it can be sufficient to include the UI drafts in the user requirements specification but should the integration introduce multiple new panels or differ from the norm a separate document m
19. e The database manager mentioned on the above illustrations is a complex but internal manager that handles the application s internal database The database consists of a collection of so called data point elements that hold values and their corresponding metadata such as addressing and connected functions 3 This database should not be confused with the external database used for long term data archival The internal da tabase suffers from severe limitations due to the way it has been implemented Each data point has an associated identifier a running number that is incremented on each data point creation Deleted identifiers are not automatically recycled but manual re use has been necessary in REMUS as the maximum identifier number is fairly limited In any case creation and deletion of data points is not fast and should be avoided REMUS keeps a local copy of some of its database s tables to ensure smooth operation during outages To do this a pool of data points is used and reused and a similar strat egy is advised to avoid unnecessary deletion and creation of data points 2 2 REMUS SCADA system The REMUS software package consists of the base WinCC OA installation with a customized JCOP framework a plethora of panels scripts managers and drivers and an Oracle database 11 ORACLE 5 Archiving Parameters Devices File Servers SQL Loader Measurement Event da Ctrl Manager
20. e finite machine state For example the Initialization 128 state is only allowed if the monitoring station is in either Silent or Off mode and setting the mode to anything else will set the state to 0 or End Conversely setting the mode to Silent or Off will set the state to Ini tialization as that is the only action possible in these modes Further details on the REMUS FSM can be found in the REMUS Finite State Machine document on EDMS 30 and will not be discussed here 14 3 RESEARCH METHODS The research methods used vary from field to field and depend on the questions to be answered The two main methods used in scientific research are quantitative and qual itative research They are based in evidence and are thus part of what is called the empirical research method Though starkly different they are commonly used hand in hand as large amounts of qualitative work is often required for the quantification of phenomena 32 Qualitative method is used in many different fields The aim may vary depending on the person or group utilizing the method but in general it investigates the why and how of phenomena It is often used to define hypotheses as it provides information only on the case studied in contrast to quantitative methods that may find connections in data pertaining to cases not specifically included in the research In scientific re search data is often gathered with observation i
21. ed as a language but it is sufficient for simpler tasks such as manipulating data point element values In combination with the built in drivers they can be used for communicating with equipment but mostly they are restricted to handling user interfaces and running high level background tasks Custom Manager N J Event Manager Driver Device Database Manager Illustration 1 Data flow with custom manager and an inbuilt driver WinCC OA drivers are complex managers that instead of being built with CONTROL scripting language are fully fledged C programs leveraging WinCC OA API 3 Their main purposes are implementing a specific protocol low level filtering data transformation conversion and smoothing 23 On REMUS we have offloaded some other functionality to them including the writing of injection files alarm generation and the data acquisition logic Data between the event manager and the drivers flow directly through API function calls eliminating some overhead 10 pe SS lt En Ge ro JA oi N Ee i A Y P gt Database Event Manager Custom Driver Device saan ee S W el S Illustration 2 Dataflow with custom driver In addition it is possible to build so called API managers which fall in between They are lighter than drivers but still much more complex to write than CONTROL scripts 3 The API managers have not been used in REMUS so far and will not be covered her
22. elements and the alarms related to this device type Certain data points are grouped together under descriptive directories The data points pertaining to the whole device are under directory GLB while the channel specific data points are grouped under CHN where N indicates the channel number starting from one Furthermore these directories have sub directories grouping data points for configuration parameterization and measurements under the directories Configuration Parameters and Measurements respectfully 18 In addition to the data point elements uniquely required by different types of devices certain data points are necessary for the operation of REMUS These included the data points for the monitoring station name and its identifier as well as the names and the identifiers of the channels attached Data points for user name and station id as well as date are necessary to track configuration parameterization and control operations 7 Functions can be bound to data points to do statistical operations on the data held or to dynamically call other functions These statistical functions are limited to internal CONTROL functions and cannot dynamically receive values from other data points The function itself is written inline on the SOL statement as opposed to dynamic func tion callbacks where just the name of the function is defined in the database Dynam ically called functions can be anything from internal functions to user
23. esign A specification of the final user interface is made which must also be validated by the stakeholders Once development has finished a user manual is created to help users navigate the system A test procedure is created to verify that the end product is working as expected This procedure is executed repeat edly first by the developers then by an impartial member of the team until the product passes with no remarks Same procedure is then followed by the users to validate the product for deployment Users may add new test cases as seen necessary and this phase can easily take a couple of months Once the product has been validated it will be deployed to production in the next scheduled production push At all phases of the integration as well as in the maintenance phase it is very important to maintain frequent communication with the users so as to really understand what the users want and expect This can either make or break the whole project In addition a 17 technical contacts with the instruments manufacturer and the company developing the firmware can be extremely valuable and should be sought after 4 1 User requirements The stakeholders must provide a document specifying their functional requirements and constraints Usually this is simply a listing of the devices functionality with the added details on functionality that they would like to have implemented on top The devices might implement a large array of fun
24. h device Tracking the state allowed us to avoid problems that could rise from simulta neous operations The FSM is a not a piece of software per se but rather a specification of what state should the monitoring station report in any situation Not all of the FSM states are implemented by every integration but for those that are the specification must be followed The states of the FSM are unigue meaning that no two numbers should indicate the same state The only exception are 4 and 16 which both indicate reguest error This is due to historical reasons as one device type that has been inte grated may respond with either one When implementing the FSM number 4 should be used to indicate the reguest error state Forced Synchronizati Close the Panel 256 e g after reset Open Panel Synchrontzation e Timed sl 64 Finish Synchronization 0 Ne Close the Panel 8 le Success Synchronization 7 P A J ke J Fi Close the Panel Send Request Write To DB injtidlization pr R y equest Error f ji Request OK OK from foreign request 4116 ke 1 2 Send Reguest Initialize values for consistency Error from foreign request Illustration 5 REMUS Finite State Machine The task of keeping the FSM in the correct state at all times is left to the developer Commonly the state is changed directly but certain events such as change in the mon itoring station mode can have the side effect of changing th
25. ils may come up with other modes too especially on ones artificially in troduced This is an important detail and must not be forgotten In its appendices the document must include sequence diagrams of all complex func tions such as the acquisition of historical measurement data and alarms Similarly a full list of data point elements with their data type addressing string and their purpose has to be included If the list of data point elements grows too big it may be exported to a separate document and referenced on the technical specification A separate doc ument also makes it easier to add more details about the data point elements such as the direction of data flow to the element and the end points of data held within It can be useful to know if the value originates from the driver or the device and whether it is stored in the database or not 4 4 Device type design Devices in WinCC OA are represented as instances of data point types REMUS makes use of JCOP frameworks template data point type creation process and the structure of each device type is stored in the REMUS database The details of these structures can be refreshed from a special panel created for this purpose The design consists of mul tiple levels It details the amount of channels and sub devices that can be associated with the device as well restricts the types of devices that can act as sub devices In 20 addition it has the full structure of data point
26. measurement is stored the iterator will not be moved and if the queue is full the iterator will fall behind the latest entry effectively losing all 4000 measurements in between 24 To minimize the chance of this happening it was decided to limit the maximum frequency of measurements to once per sixty seconds This limit also meant that the 4000 entries now covered over two days and 18 hours of measurements providing a pleasant buffer Although the device itself does not support modes it was decided that three artificial modes were to be implemented on driver level The driver would support measurement mode as the regular working mode maintenance mode and silent mode that would be used to simulate off mode and prevent any data collection including measurements alarms or faults 24 This would effectively leave the device in a standalone mode and would allow swapping of devices without leaving fault events in the logs With REMUS the measurement data and events would now be stored in the unified monitoring database along with data from all the other device types LB112 supports a wide array of measurement units among which are mrem h milliroentgen equiva lent in man per hour and pCi m3 picocuries per cubic meter 16 28 Support for these two historical units was dropped as adding them to the supported units would 29 have made little sense On LB112 this unit is really just a tag as the actual end unit depends on the c
27. n the correct variables on the driver Along with the data these readers would hold addressing metadata to route the values to the correct data points and after being fully analyzed the readers themselves would be fed to an auxiliary function that would extract this information and pass the resulting data to be sent to the event manager The multithreaded nature of the driver in contrast to the single threaded API calls required the addition of auxiliary functions and static buffers Data to be sent to data points was stored in a static queue from which one entry would be passed to the event manager each time it would call workProc 30 As with previous drivers measurements and events acquired or generated by the driver would be written to injection files Another static queue was created to which each individual thread would add entries Then a file writer loop was created that would get new entries from this queue and would write them to files The task of injecting them to the database is delegated to a cron job running SQL Loader as before The below architecture guaranteed better communication with the API and the file system Illustration 10 Threads As the users had not provided us a draft of the user interface inspiration was once again taken from a previous integration The user interface went through multiple it erations of minor changes as users requested elements to be moved around Finally an agreement was reached and
28. nt System Large Hadron Collider The On Line Isotope Mass Separator Formerly Isotope Separator On Line Detector Systems Control And Data Acquisition 7 Human Machine Interface Monitoring Station Scripting language used by WinCC OA Joint Controls Project 8 Application Programming Interface 1 INTRODUCTION CERN is a European research organization located at the Franco Swiss border near the city of Geneva It operates the largest collection of colliders and accelerators facilitat ing researchers from around the globe The experiments at CERN produce ionizing radiation from collisions and interaction with the surrounding elements and run the risk of releasing noxious gasses to the environment and while sewage and industrial wastewater is discharged to sewage stations in the area some surface and cooling wa ter is released to the nearby rivers 1 The Occupational Health amp Safety and Environmental Protection Unit is tasked with monitoring these risks to limit the exposure of people and the environment to a rea sonable achievable level 6 As a part of this effort the radiation protection and the environmental sections of the unit monitor the environment and radiation at the re search facility and its immediate surrounding area A collection of devices are distrib uted around CERN and outside its premises Some of these devices come with soft ware for remote control and possibly data acquisition while others are strictly s
29. nterviews reflexive journals and anal ysis of document and materials 33 Quantitative research investigates phenomena using statistical mathematical or com putational techniques It tries to find connections between observations and can be used to prove or disprove hypothesis created using qualitative research Though meas urement is commonly stated as central to the quantitative research it is accepted that it can t be used as its sole basis 32 Use of both qualitative and quantitative methods may provide more accurate results Quantitatively produced conclusions can be better understood using qualitative methods while quantitative methods can be used to pro duce precise and testable expressions of qualitative ideas 34 In software projects both qualitative and quantitative methods are used A recent de velopment has been the growing popularity of a user centric approach that includes the end users in the project from the very beginning The approach strives to identify the wants needs and limitations of the end users that are then given extensive attention throughout the design and development process 36 The users may be interviewed or asked to do self documentation Action research is done to identify the actions taken by users to achieve their day to day goals In addition continuous feedback is given by 15 the users throughout the project in the form of validation and testing 35 Such an approach is often necessar
30. o send the parameters in an order that would not disturb its state 4 6 User Interface The user interfaces of all REMUS integrations follow the same format 15 On the left hand side of the user interface there is a faceplate showing real time values and state of the device The faceplate also has buttons for defining configuring parame terizing and commanding the device The layout of the state indicators and values is specified by the users but that is as far as they have power over it The format of configuration and parameterization panels depend on the amount of parameters and the maximum number of sub devices and channels associated to the device type In spiration for these panels should be taken from the previous integrations with the top of the panel holding metadata and controls for requesting historical configurations and parameterizations Bottom of the panel then holds controls for applying refreshing and clearing the values on the panel In addition a Retrieve button may be present in the bottom to request latest values from the device By keeping the experience con sistent less user training will be required and the overall user experience will be better 24 REMUS 1 5 1 MEE 261042015 09 27 03 eg Environmental Monitoring Gi Summary Views Air Quality Monitoring Air Monitoring Stray Radiation Water Monitoring Smartinterface Operational Reserve waers MS Name D Pmsmot 867 MSID Ty
31. ork reduces the develop ment effort and the required resources for maintenance The framework provides tools for structured device creation CERN user authentication database integration and ad ditional support for common industrial application layer communication protocols 8 Being built on WinCC OA it has inherited some of the design decisions and is easily customizable for individual use cases In addition the framework s modular nature al lows projects to use only what is needed thus creating faster and sleeker systems A WinCC OA application consists of several processes that are called managers These managers are used to handle user interfaces the internal database and communication A single manager called the event manager is responsible for data flow between all other managers including all client user interfaces and for the synchronization of data between redundant servers The event manager can become a major bottleneck as it is single threaded 3 4 22 It is possible to run multiple instances of the event manager even on separate servers to split the load However the events must eventually be syn chronized to the main event manager thus only delaying the problem It is wise to keep this in mind when designing and developing software with WinCC OA There are three major ways of extending WinCC OA Simplest are the interpreted scripts written in CONTROL WinCC OA s internal scripting language CONTROL is quite limit
32. p of WinCC Open Architecture the section could leverage the organization s prior experience and the existing support system The system was named REMUS a reverse acronym standing for Radiation and Environment Monitoring Unified Supervision In early 2013 I joined the team taking over the function of integrating instruments requiring custom drivers At the moment one monitoring instrument was in the pro cess of being integrated but the person tasked with the integration was at the end of his contract and had no time to define a process of integration Thus the secondary objective was to document a process of integration specifically for REMUS that could also work as a reference for new members of the team 2 REMUS 2 1 WinCC Open Architecture SIMATIC WinCC Open Architecture is an extremely flexible SCADA system that allows custom tailored SCADA solutions to be produced fairly quickly 8 9 The product used to be called PVSS ProzeB Visualisierungs und Steuerungssystem but after ETM got acquired and became a subsidiary of Siemens AG PVSS was integrated to the SIMATIC HMI family and was renamed WinCC OA to simplify international marketing 2 In this thesis the terms WinCC OA and PVSS are used interchangeably For some time CERN has used WinCC OA as the basis of their supervisory control and data acquisition systems for which the EN ICE group has created the JCOP frame work By providing a higher level of abstraction the framew
33. pe Eo D n Firmware E Zone J Frevessin Ste _ Location D ser r251 MeasurementMode Rate Meter Probe Toggle Th Disabled Status Parameters General Status Memory overwrite Consistency Communication Gi Interlock Data uptodate Driver Silent Meas Chid Type O 10035 LB 6360 ole 10037 Ee Came time Went time Men 26 04 2015 04 37 34 26 04 2015 01 47 40 Alarm off not Define Configure NOX_AQMVvEo1 26 04 2015 01 27 19 26 04 2015 01 27 50 ox aamvaot 2604 2015 01 26 55 26 04 2015 01 27 55 Command Parametrize 3 AOMVI0T 26042015 01 24 43 Syst Alarm off not ack Syst 26042015 01 27 19 tem Fault Environment non Illustration 9 REMUS User Interface The User Interface Specification must document the general appearance explain the meaning of each element states of each state indicator and the purpose of each button While the user interface will see many changes throughout the project and this docu ment will go through multiple iterations an initial validation should be received from users before any real work on the user interface is undertaken This validation is an insurance against users suddenly changing their minds later on in the project 4 7 Development The development phase of any integration will depend on the device specifications and the designs made but
34. ple mistakes were found on the device s documentation To quickly asses the actual constraints and responsiveness of the device a java class was created Develop ing this software helped us get better acquainted with the protocol and the tool was also useful in later stages of the development for testing the product and for debugging the devices During these tests we found additional limitations and some lacking con straints on the device Values received by the device were not sanitized in any way and variables expecting numbers could be passed character values instead thus bypassing 28 the naive range limitations 25 The device also showed reduced responsiveness under active communication leading to its internal clock losing time 24 5 2 Technical documentation The Berthold LB 112 stores its measurements in a circular queue that is capable of holding up to 4000 entries These entries are ASCII encoded strings holding a time stamp device status at the time of measurement and both raw and integrated measure ment values and their respective units from both probes Access to the queue happens through an iterator allowing requesting the value of the current entry and moving backwards and forwards one measurement at a time 16 If the queue is full new entries will overwrite the oldest ones and the iterator will be moved to the next one However if the act of reading an entry from the device happens at the exact same time as anew
35. rtunately it was not possible to make a complaint as the wiring order had not been stipulated on the contract Prior wiring problems had not been noticed as a representative from the com pany had always done the trigger configuration on MEVIS after the devices had been installed adjusting them according to the wiring of each device It was decided that the wiring should be standardized and the expected mapping was then documented on the REMUS LB 112 User Manual s appendix on setting up the device for integration 28 In an effort to unify the devices the radiation protection group gradually started to update all of the devices to the new firmware The communication problems caused event logs to be flooded with faults and for a year continuous efforts were made to reduce them by working around the new limitations and by increasing fault thresholds thus masking shorter communication outages In the end all devices were reverted to the previous version of the firmware as the problems exhibited far outweighed the benefits 33 6 CONCLUSIONS The purpose of this project was to investigate the process of monitoring instrumenta tion integration to the REMUS SCADA system taking a broad view of the necessary steps and common pit falls The integration of one such instrument gave in depth view of the process and the challenges involved with interfacing with monitoring eguip ment By encouraging user participation the project was finished
36. ructure is very stable some problems with communication do happen Routers crash and supposedly routine maintenance from IT can have disastrous side effect The end product must be able to withstand these situations without losing data or producing fallacious alarms or faults Having been tested by the developers the product must be tested by someone with little to no prior involvement to the project After working on the product for an extended amount of time it is easy to use the device and the software in the intended way but it is important to also test how it behaves when one does not follow the expected pat tern After the product has passed the test procedure with no remarks it must be validated by the users Prior to the product validation process the test procedure should be val idated with the stakeholders as they may want to add some test cases to it This process takes a long time as they will have much less experience with REMUS 4 9 Deployment and maintenance Once the product is ready and it has been validated by the users the code is frozen and the version number is incremented to 1 0 0 On REMUS the versioning scheme the first number is dedicated to the initial release and massive overhauls second number for new features and last one for minor patches and bug fixes Until the product is deployed the binary should be frozen to this version The full process of deployment is covered fully elsewhere 17 and is outside
37. s OPC Client Files Local copy of Watt OA critical tables 3 J In house Devers A i developed Drivers FESA Monitoring Instruments Alarm Units Etc Data point update System Request Response Application xml files Authentication I Wing Witte Witte Windows ka Users a S S REMUS Terminal Server SF Cluster Linux Users Illustration 3 REMUS Architecture In the REMUS SCADA system the representation of each monitoring unit is split to three parts the monitoring station the devices and the channels The unit as a whole is monitoring system or MS for short A monitoring station encapsulates the devices and channels that make up that unit A channel is a channel of measurement It is an identifier that is used to store and map the events and measured values to their corre sponding monitoring stations devices and locations A device is an actual physical device It may be the main monitoring device or a sub device such as a detector A monitoring system may have an arbitrary amount of sub devices and channels In the below illustration one can see a possible structure of a monitoring station entity 12 MS Device Channel Channel Device l Device Device Illustration 4 Possible structure of a monitoring station Channe Channe Channe Channel While WinCC OA provides a user interface for declaring data point types that
38. some general advice may be given When connecting data points to callback functions data points that change rapidly should have their separate connection The function WinCC OA uses to get data point values can cause serious performance problems and any update to a data point that is connected to a function will trigger an internal function to get the values of all the other 25 data points connected to the same function Furthermore if the function is called again before the previous operation has finished the operation is added to a queue If the frequency of these calls is higher than what can be processed the queue will keep growing and with it the consumed memory Once maximum queue size is reached a portion of queued calls will be dropped leaving only the newest entries 27 At the end of development a user manual is prepared documenting how to access the functionalities provided by the product A major part of this manual are the procedures how to install new devices of this type to REMUS including the initial settings on the device and its communication module if one exists to ensure proper functioning of the devices For most parts the manual is consistent with other integrations and this is by design Every integration should have the same flow look and feel as the others so that the user experience is consistent throughout REMUS It is very important to keep the code well commented and documentation up to date and the
39. t ja helpottamaan uusien ty ntekij iden koulutusta INDEX E CR REEL GR LE EE 6 AR ING E 8 GH Ne WanC TN e EE 8 2 2 REMUS SCADA System isimni inae R 10 2 3 DREMUS Pinte EEN 13 3 RESEARCH ENN LTE 14 4 THE INTEGRATION PROCEDURE ei ele eege ie ele 16 AL RISER Ee 17 4 2 DIA YSU EE 18 4 53 EE Te 18 AA Device type desin nsun ekle saata punka E EEE a 19 4 S et EE EE 20 4 6 BE e 23 4T Deyelopment eege eege eeh 24 4 8 Testing and validation lt uvs lt ssa aa saas maa eana ea La aaa Oa eaa Nd a avaa aa 25 4 9 Deployment ECHTER eege che eege 26 5 INTEGRATING BERTHOLD LB 112 MICRO GAMMA LOGGER 27 schlo lt ee 27 5 2 Technical documentation usvsaaussaaa aasian assa saan stesaasadaddedasnsoadeeasvoas 28 53 DIT anne We SIS EES 29 Stock eebe erageet a ane 30 2092 T stingand Deploy eebe Eege 31 5 6 Maintenances sich oor ege Ee 32 Gy CONCEUSIONS maan assa tassa ve a iaeei S n pata ea aiai 33 7 END Le RE 36 FER EIR NEE 37 Abbreviations CERN HSE DGS SEE RP CO EN ICE REMUS EDMS LHC ISOLDE SCADA HMI MS CONTROL JCOP API European Organization for Nuclear Research Occupational Health amp Safety and Environmental Protection Unit Safety Engineering and Environment Group Radiation Protection Group Computing Section Engineering Department Industrial Controls amp Engineering Group Radiation and Environment Monitoring Unified System Engineering and Equipment Data Manageme
40. tand alone devices 19 A unified system would make working simpler and by having the same look and feel the use would be more intuitive 7 Previous attempts have been made to update and unify the supervision of monitoring instruments at CERN 6 but the outsourced effort was not a success The end product did not scale well had very poor performance no reliability and negligible adaptability Updates to this product are slow and expensive and the maintenance disruptive 19 In late 2011 work was started on a new system by the HSE SEE Computing section of CERN The system would be created with four basic pillars in mind reliability scala bility performance and adaptability Reliability in this case would be paramount as false or missing radiation alarms and incorrect measurement data would be simply unacceptable The system would have to scale massively to facilitate the devices and the gargantuan amount of data acquired from them CERN already utilizes tens of thousands of detectors and this number is continuously growing 10 The Joint Con trols Project had run extensive tests that found PVSS scalable and especially stable 11 This made it a prime candidate for the new system In addition REMUS was designed with a light interface only loading what was necessary This compartmen talization made it also highly adaptable and permitted the delegation of some of the administration effort to a few trusted end users By building on to
41. the scope of this thesis 27 5 INTEGRATING BERTHOLD LB 112 MICRO GAMMA LOGGER The Berthold Technologies LB112 Micro Gamma logger is a radiation monitor log ger and alarm unit all in one Up to two radiation detectors either probes or radiation chambers can be connected to it The device has an inbuilt MOXA modem and can be communicated with by serial over TCP IP 16 This device had been in use at CERN for some time but it had not been integrated to the previous unified supervisory system It was the second device to be integrated to REMUS 5 1 Analysis Unfortunately in the case of LB 112 the users had not prepared any documents for us and due to time constraints they were created by the team itself One month was spent getting comfortable with the device Users of the current software were then ap proached to acquire real life use cases So far they had used MEVIS the remote control and data acquisition software provided by Berthold but due to the constant connectiv ity problems and the confusing user interface they had often opted for local interven tion instead 29 This meant that there was effectively no log of parameterization changes or the users responsible for them This also meant that the users had not gotten used to the functionality provided by MEVIS and removing unnecessary and danger ous functionality was fairly easy During the analysis and the formation of requirements and the technical specification multi
42. urkimsher 2005 Scaling up PVSS Geneva Switzerland CERN M Lechman et al 2013 Managing Infrastructure in the ALICE Detector Con trol System Geneva Switzerland CERN B Galloway amp G Hancke 2012 Introduction to Industrial Control Networks IEEE Communication Surveys and Tutorials 14 15 16 17 18 19 20 21 22 23 24 25 26 27 38 D Forkel et al 2009 ARCON RAMSES Current Status and Operational Risk Geneva Switzerland CERN G Segura amp A Ledeul 2013 REMUS User Interface Principles and Conven tions https edms cern ch document 1283589 Berthold Technologies 2009 LB 112 Micro Gamma Two Channel Data Log ger Manual Switzerland R P Silvola amp A Ledeul 2015 How To Migrate REMUS to a new version https edms cern ch document 1491499 Adrien Ledeul 2015 How To Create new REMUS Device Type https edms cern ch document 1290009 G Segura amp A Ledeul 2013 REMUS Project Proposal https edms cern ch document 1290748 G Segura amp R P Silvola 2015 REMUS Database Data Injection https edms cern ch document 1327197 G Segura amp N Jacinto amp K Szkudlarek amp A Ledeul 2012 REMUS Database https edms cern ch document 1274246 A Ledeul amp G Segura 2014 Radiation and Environment Supervision amp CERN https edms cern ch document 1438380 ETM 2010 PVSS Driver Development Riku Pekka Silvola 2013 LB11
43. y as the developers are commonly not the end users of the product making it difficult for them to intuitively foresee what are the end require ments and constraints User centered design lends itself well for software development when the end users are well defined as is the case for REMUS 16 4 THE INTEGRATION PROCEDURE Analysis document Required vs Possible Device behavior Software components Driver Manager Technical Specification User Interface Functional design Architecture design Test procedure UI Specification User manual Test records Analysis gt Design gt Development gt Testing gt Acceptance gt Deployment User requirements Functional Constraints UI description Test records Validation Manuals Procedures Product documentation Product Manuals Communication protocol Illustration 6 Device integration process The process of device integration follows a fairly straight forward pattern Once the device has been chosen by the stakeholders it is their responsibility to produce a re guirements specification documenting the constraints reguired functionality and the user interface With the requirements and device s documentation in hand a feasibility analysis is made to match the required with the possible After the proposal has been validated by the stakeholders a technical specification is written to document the func tional and architectural d
44. y communicate with the device As some protocols require valid checksums on messages this might even be a necessity This software may also be useful later on for debugging purposes 4 3 Technical specification The technical specification should document in detail what will be implemented and how it ties into the existing system Any functionality that adds to or diverges from prior integrations must be documented as well as any functionality supported by the device that is not going to be supported For an example an instrument might support 19 the measurement units becquerel and curie REMUS has been built in a way that it is simple to add support for new measurement units but as NIST actively discourages the use of non SI units 5 support for curies can be safely dropped Another example would be the device modes At the time of writing REMUS supports nine modes These are Off Measure Test Simulation Maintenance Calibration Without Mode Silent and Degraded However one would be hard pressed to find any device support ing all of these modes and even in that case they would doubtfully call them by the same names Thus the document must specify which device mode maps to which REMUS mode and in addition what is the expected functionality in that state For some devices maintenance mode may simply mean that the measurements are tagged with the mode maintenance but others might not even do measurement in this mode Similar deta