1. ptitude Observer On line Device Configurator Part No 32170800 Revision J User Manual Copyright 2013 by SKF Reliability Systems All rights reserved Aurorum 30 977 75 Lulea Sweden Telephone 46 0 31 337 10 00 Fax 46 0 920 134 40 SKF Reliability Systems SKF Condition Monitoring Center Aurorum 30 977 75 Lulea Sweden Telephone 46 0 31 337 10 00 FAX 46 0 920 134 40 For technical support contact TSG EMEA skf com for customers in Europe Middle East and Africa Telephone 46 0 31 337 6500 or TSG Americas skf com for customers in North America South America and Asia Telephone 1 800 523 7514 Telephone in Latin America 55 11 4448 8620 Visit us at our web site www skf com cm SKF is a registered trademark of the SKF Group Table of Contents Introduction 1 4 CM Network Configuration File 2 5 Creating meias ni A E nonne nnn annan nen anno natron net a 2 5 Berte ene EEE EE 2 7 Serial Interface 3 8 Getting Started by Attaching Cable us sara 3 8 Start Serial Interface cssssseecccescececseseccaseececeeneeceeeseeceaaesessgeeeesseseseageeeessaneeeees 3 9 Serial Interface for IMx or MasCon16 CM ser steere enerne ennnerenrnerenrnrnn 3 10 TSI Serial Interface for IMX R srerrrtrvrnvnvennnnvvennennnnnnvnnvnnvensrrrennsnnrensen 3 12 Serial Interface for IMx M Protection xersevnnansvnnnannvvvnnnansrvnnnnnnsrvnnnnn 3 13 Select COM Port for Mx
2. TSI Serial Interface for IMx R only Select COM Port fi v Sending file to DAD eer re Received ok Relflash Flash programming started EEEEEERelflash OK Device id 01 Config crc d9ce3528 Project NIV Entering normal run mode Command Ascii row pause in Milliseconds 30 Send file Figure 4 12 Example of a successful download of firmware version 1 0 0 or 1 1 0 10 If the download is successful the unit will reboot and run the new version of firmware 11 If an error occurs retry the procedure ptitude Observer On line Device Configurator 4 19 User Manual Revision J IMx R TSI Firmware Download Firmware Version 1 2 0 Firmware Version 1 2 0 The following steps will guide you with downloading a new firmware version 1 2 0 to an IMx R unit 1 Connect IMx R to a computer by using a null modem cable A USB to RS 232 converter may be required Refer to Getting Started by Attaching Cable in Serial Interface section for IMx R TSI part connection 2 Start Observer on line device configurator 8 4 0 and click on Start IMx R TSI serial interface Refer to TSI Serial Interface for IMx R 3 To download firmware the IMx R unit needs to be powered up If the unit has not powered up already power up the IMx R unit TSI Serial Interface for IMx R Select COM Port v IMx R TSI Cro OK Enter download password Loading app OK FW Cre OxchOfed67 0k Version 1 2 bui
3. CONF IGY ANALYST IMX M TSICFG READOUT BIN Size 2378 bytes 0x59 Cfg updt only allowed in Disarm mode Enter config password Preparing flash memory Relflash Flash erasing started E Relflash OK Please send configuration file Ascii row pause 0 Figure 7 39 Example of configuration file transmission for IMx M 8 The transmission of the configuration file will start immediately ms Get Config Update Contig Update Firmware Ady debug modes 1 Slave version 2 Update master fw I Enable debug vw Capture to disk 7 44 ptitude Observer On line Device Configurator User Manual Revision J IMx M Unit Protection Configuration Serial Interface for IMx M Protection Select COM Port 4 X Relflash OK Please send configuration file Received ok Relflash Flash programming started E Rebooting Cause 0x50 IMx M C SKF CMC AB Version 0214 Build Aug 27 2012 12 43 46 FW CRC OxCO8E6239 CRC Ok BoardType I0 MyMcuddr Scanning for I2C devices 3C 3D 50 52 53 54 55 SC SD DisarmSlot 01 DisarmCh 0000 Selftest Ok Diag Ok Disp OK IV Capture to disk Asci row pause 0 ms Get Config Update Config Update Fimware CE Close Figure 7 40 Example of a successful configuration file transmission for IMx M 9 Ifthe download is successful the unit will restart with the new IMx M Protection part configuration v Ensure to read a
4. R Select COM Port Sending file to DAD STARTING DOWNLOAD SENDING FILE Size 188458 bytes download SafeState 00 Rebooting Cause 0x01 IMx R TSI Cre Ok Enter download password Preparing flash memory Relflash Flash erasing started ERelflash OK Please start file transmission Command Ascii row pause in Milliseconds fo Download config Figure 4 15 Example of download firmware version 1 2 0 7 The transmission of the firmware file will start immediately Wait for the completion 4 22 ptitude Observer On line Device Configurator User Manual Revision J IMx R TSI Firmware Download Firmware Version 1 2 0 TSI Serial Interface for IMx R Select COM Port fi vi Sending file to DAD Relflash Flash programming started EEEEEERelflash OK Loading app Ok FU Cre OxchOfed67 0k Version 1 2 build 1907 on Mar 24 2010 14 22 38 IAR 0141 Key ffffffffffffff Cstack Ok Istack Ok Config OK Unit id 01 Config cre 6fcee7a4 Customer NTV CfgVer 000 000 011 Entering normal run mode Command Ascii row pause in Milliseconds Jo Download config Figure 4 16 Example of a successful download firmware version 1 2 0 8 If the download is successful the unit will reboot and run the new version of firmware ptitude Observer On line Device Configurator User Manual Revision J 4 23 IMx R TSI Firmware Download Firmware Version 1 3 0 or Later Ve
5. Sending file to DAD SENDING FILE Size 1200 bytes Relflash Flash programming started ERelflash OK IMx R TSI Cre OK Enter download password Loading app Ok FU Cre OxchOfed67 0k Version 1 2 build 1907 on Mar 24 2010 14 22 38 IAR 0141 Key ffffffffffffff Cstack Ok Istack Ok Config OK Unit id 01 Config cre 6fcee7a4 Customer NTV CfgVer 000 000 011 Entering normal run mode Command meoo Ascii row pause in Milliseconds Jo Download Firmware Close Figure 5 28 Example of a successful configuration file transmission with IMx R firmware 1 2 0 11 If the download is successful the unit will restart with the new TSI configuration Make sure to check the TIS configuration information ptitude Observer On line Device Configurator User Manual Revision J 5 35 IMx R Unit TSI Configuration With Firmware Version 1 3 0 or Later Version With Firmware Version 1 3 0 or Later Version The following steps will guide you how to configure TSI for IMx R units with the firmware version 1 3 0 1 Connect IMx R to a computer by using a null modem cable A USB to RS 232 converter may be required Refer to Getting Started by Attaching Cable in Serial Interface section for IMx R TSI part connection 2 Start Observer on line device Configurator 8 4 0c or later version 3 Click on Start IMx R TSI serial interface Refer to TSI Serial Interface for IMx R 4 It is strongly
6. number above 2 Ensure that the port is not in use by any other hardware installed in the computer ptitude Observer On line Device Configurator User Manual Revision J IMx R TSI Firmware Download 4 IMx R TSI Firmware Download This section guides you how to download TSI firmware to IMx R units There are different instructions depending on the firmware version Firmware Version 1 0 0 or 1 1 0 The following steps will guide you with downloading a new firmware version 1 0 0 or 1 1 0 to an IMx R unit 1 Connect IMx R to a computer by using a null modem cable A USB to RS 232 converter may be required Refer to Getting Started by Attaching Cable in Serial Interface section for IMx R TSI part connection 2 Start Observer On line Device Configurator 8 3 0 or earlier version and click on Start IMx R TSI serial interface Refer to TSI Serial Interface for IMx R 3 To download firmware the IMx R unit needs to be powered up If the unit has not powered up already power up the IMx R unit TSI Serial Interface for IMx R only Negl x Select COM Pott fi v Sending file to DAD Device id 01 Config crc d9ce3528 Project NIV Entering normal run mode Command ee Ascii row pause in Milliseconds 30 Send file Close Figure 4 10 Example of boot up text of IMx R with firmware version 1 0 0 or 1 1 0 4 The IMx R displays a version and other text on the RS 232 TSI serial port upon boot up The ex
7. output window e Lock is a toggle button which locks unlocks the contents on the output display window This can be useful if a user wants to copy and paste information from the output window e Command is where you can enter commands or instructions manually More information on IMx M Protection commands can be found in IMx M User Manual e ASCII row pause in milliseconds is the pause between each ASCII row Normally there is no need to change e Get Config reads back the configuration file currently in use by the IMx M unit e Update Config downloads a configuration file to IMx M unit refer to IM M Unit Protection Configuration e Update Firmware downloads protection firmware to IMx M unit Refer to IMx M Protection Firmware Download e CF displays all the circuit faults along with descriptions of the current slot e Close closes the Serial Interface for IMx M Protection screen e Adv debug modes Advanced debug modes should only be used by experienced installation engineers in cooperation with SKF Condition Monitoring Center ptitude Observer On line Device Configurator 3 13 User Manual Revision J Serial Interface Start Serial Interface e Capture to disk saves responses or messages you get from commands and interfaces to a disk if checked Select COM Port for IMx M How to Find Windows Allocated COM Port Number e Open Control Panel window and select System e Select Hardware then Device Manager e Dou
8. 012 09 19 08 18 Oxd679f2d6 Bin F1Mx M ProtCfq Slott 2012 09 20 08 20 Oxa7c3093c Bin G IMx M ProtCfg Sloti 2012 09 20 08 21 Oxebff5402 Bin G IMx M ProtCfg Sloti 2012 09 20 08 22 0x840e1b74 Bin pe IMx M_ProtCfg__Slot2__2012 08 20_09_09_Ox6fdb4cb4 Bin 3 Imx M_ProtCfg__Slot2__2012 08 22_13_47_0x66bc3416 Bin gIMx M_ProtCfg_ Slot2 2012 08 22 13 48 OxdcSbea 6a Bin 4 IMx M_ProtCfg_Slot2__2012 08 29_12_24_0xcd723325 Bin Fa IMx M_ProtCfg_Slot2__2012 08 29_12_56_0x9aead5fb Bin F1Mx M ProtCfq Slotz 2012 08 29 13 14 0x69b937c9 Bin F1Mx M ProtCfg Slotz 2012 08 29 13 22 Oxff20da2c Bin Fad IMx M ProtCfg Slot2 2012 08 29 13 25 0x2b024511 Bin lt il 58 IMx M_ProtCfg_ 3 1Mx M ProtCfg P 1Mx M ProtCfg P 1Mx M ProtCfg P 1x M ProtCfg Fe 1Mx M ProtCfg 38 1mx M ProtCfg pe IMx M ProtCfg P 1Mx M ProtCfg 1Mx M ProtCfg 38 IMx M ProtCfg F1Mx M ProtCfg 1Mx M ProtCfg gt My Network Places File name Files of type I Open as read only IM ProtCig 5 lot2 2012 08 22 13 48 0 v Binary files BIN he Cancel Figure 7 38 Example of configuration file selection screen for IMx M 7 Choose a Bin file with which you wish to configure the IMx M unit Serial Interface for IMx M Protection Select COM Port Sending file to DAD Scanning for I2C DisarmSlot 01 DisarmCh 0000 devices 3C 3D 50 52 53 54 55 5C SD STARTING DOWNLOAD Sending file C SENDING FILE config Rebooting Cause SKFY I ARY IMXM
9. 9127126 FES I 2110 09 12 09 17 Des nes En MP Teich 12912126 JEG 0 2010 04 12 S Ae theo bt fin Had T y 18127126 PEG OD 20 Ole 2 OG 36 Dof baat Bir HR To Fosen bin 2 syte 207 EEE Jie nR Tc 128011 MTV 82010042 16 7 Fiet ol h re Dinar thew BIN Cigver O00 069 011 Entering normal run mode Figure 5 30 Example of configuration file selection screen with IMx R firmware 1 3 0 9 Choose a Bin file with which you wish to configure the unit ptitude Observer On line Device Configurator 5 37 User Manual Revision J IMx R Unit TSI Configuration With Firmware Version 1 3 0 or Later Version TSI Serial Interface for IMx R Select COM Port fi Sending file to DAD STARTING DOWNLOAD SENDING FILE Size 1200 bytes config SafeState2 001a 0000 Rebooting Cause 0x01 Enter config password Preparing flash memory Relflash Flash erasing started ERelflash OK Please send configuration file Received ok Relflash Flash programming started ERelflash OK SafeStatez2 001b 0000 Rebooting Cause 0x01 Command pe Ascii row pause 0 ms Get Config Download Firmware Close Figure 5 31 Example of configuration file transmission with IMx R firmware 1 3 0 10 The transmission of the TSI configuration file will start immediately 5 38 ptitude Observer On line Device Configurator User Manual Revision J IMx R Unit TSI Configuration With F
10. Con16 Config Dad Device type IMs Configure by Software v Device number 1 v Network options C Obtain an IP address automatically Use the following IP address IPNumber 10 0 fo fi 1 Subnet mask 255 J255 255 go Gateway 0 0 fo Jo Observer Monitor IP 10 0 0 J 1 Observer Monitor Port 1 000 Ethernet Factory Defaults Do Figure 2 2 Create IMx MaxCon16 Config screen Device type is the type of unit for which you are about to create a network and ID configuration file Configure by defines how the IP address and unit ID of the unit are to be configured It can be done by DIP Switches on the main board of the IMx MasCon16 unit or by software Note that IMx R units are configured by Software only Hardware Switches means that the on line device shall retrieve its device number from the hex retary switches located on the circuit board of the unit The hex rotary switches have to be set manually For more information about this refer to Network Configuration section of the corresponding user manual such as IMx W User Manual IMx S User Manual etc Software means that the on line device shall retrieve its device number generated by the software Device number is required when you select Configured by Software option It is the unique identifier required to make Gptitude Observer Monitor communicate with the on line device 2 6 ptitude Observer On line Device Configurator Us
11. M xertertvrrrnvennnnnnnnannvennnnnrvnrenvevernsrensrnrrnnsensessen 3 14 IMx R TSI Firmware Download 4 17 Firmware Version 1 0 0 or 1 1 0 errevvovnnnnnnnnvnvnnnnnnnnnnnnnnnnnansnsrnnsnnnnsnarsrnnnnnnnen 4 17 Firmware Version 1 2 0 sssccssssecessecesscecsseeecseeceeeeccsaeeeeseecesaeesesaeeeseeeecseesssaeeeaes 4 20 Firmware Version 1 3 0 or Later Version trcessscsseeseeceeeceanecseeeeeeeeauaeseeeeeeeeanasees 4 24 IMx R Unit TSI Configuration 5 28 With Firmware Version 1 0 0 or 1 1 0 cccsecceseeeeeeeeeeeseeeeseeeeeeeseeeseeseeeeeaseasesseeeeea 5 28 With Firmware Version 120 sirene aa E ea A E EAE EAEan 5 32 With Firmware Version 1 3 0 or Later Version trrresesseseeeeeeeeeaseaeeeeeeeseaseneseeeeeees 5 36 IMx M Protection Firmware Download 6 40 IMx M Unit Protection Configuration 7 43 ptitude Observer On line Device Configurator TOC 3 User Manual Revision J Introduction 1 Introduction The Gptitude Observer On line Device Configurator allows the user to perform all kinds of operations against SKF MasCon16 and IMx systems This includes all types of on line devices including WindCon MasCon16R IMx R and IMx M This tool is the only way to set the network configuration and identification for the on line device You can also view what the on line device is measuring right now clear measurement data and show current measurement configuration 1 4 ptitude Observer On line Device Configurator User Manual Revi
12. Mx M unit the unit needs to be powered up and must be in disarm mode Important System must be in disarm mode before Protection configuration update procedure takes place Ensure to read Protection Configuration Update chapter in IMx M User Manual thoroughly and understand it Serial Interface for IMx M Protection Select COM Port 4 Ne _CLEAR Lock a IMx M MyIntID 0001 CRC Ok Enter download password IMx M C SKF CMC AB Version 0214 Build Aug 27 2012 12 43 46 FW CRC OxCO8E6239 CRC Ok BoardType IO MyMcua dr 00 myIntID O1 mySlotID 01 myHexID OF Scanning for I2C devices 3C 3D 50 52 53 54 55 5C 5D Adv debug modes DisarmSlot 00 DisarmCh 0000 Selftest Ok Diag Ok Disp OK I Enable debug Command vw Capture to disk Ascii row pause 0 ms Get Config Update Config Update Fimware Close Figure 7 37 Example of boot up text of IMx M unit 5 The IMx M displays a version and other text on the USB port upon boot up The exact boot up text depends on the firmware version 6 Click on Update Config button The password for the dialog is secret A dialog for opening files will appear ptitude Observer On line Device Configurator 7 43 User Manual Revision J IMx M Unit Protection Configuration Look in G config v ef E od Recent My Computer Pad IMx M ProtCfq Sloti 2012 09 17 15 03 0x8e6299a7 Bin Fad IMx M ProtCfq Sloti 2
13. On line Device Configurator and click on the icon of Start serial interface for IMX or MasCon 16 For IMx R TSI part serial interface start ptitude Observer On line Device Configurator and click on the icon of Start IMx R TSI serial interface For IMx M Protection part serial interface start ptitude Observer On line Device Configurator and click on the icon of Start IMx M protection serial interface ptitude Observer On line Device Configurator 3 9 User Manual Revision J Serial Interface Start Serial Interface Serial Interface for IMx or MasCon16 CM This section describes the serial interface for Condition Monitoring part of IMx and MasCon16 units All the commands or instructions you can send with the serial interface have equivalent text commands which you can enter manually if desired Serial interface Select COM Port v CLEAR LOCK Data operations Remove data Update network config Commands Syntax Help Set debug On Off SEE RESET aa p e Show Config Get Events Adv debug modes Command I Enable debug Close Figure 3 4 Serial interface for IMx MasCon16 screen e Select COM port indicates serial port interface for communication For IMx M refer to Select COM Port for IMx M in order to find out COM port number or to change COM port number e Clear clears the output window e Lock is a toggle button which locks unlocks the contents on the output display wind
14. Port 4 F CLEAR LOCK a Sdownl finished ttt Firmware downloaded Programming started please waitintdd FU Versions IOM 0214 1050 0214 1051 0214 1052 0214 1053 0214 1054 0214 1055 0214 1056 0214 1087 0214 RELM 0214 0214 0214 0214 0214 Adv debug modes 0214 0214 0214 0214 MFW CRC 11749521 SFW CRC 00000000 Command IV Capture to disk Ascii row pause 0 ms Get Config Update Config Update Firmware CF Close Figure 6 36 Example of a successful update firmware for IMx M 9 When download is successfully completed then the unit will reboot and run the new version of the firmware Important Disarm must not be released until the unit is running with a proper firmware Ensure to read Protection Firmware Update chapter in IMx M User Manual thoroughly and understand it 6 42 ptitude Observer On line Device Configurator User Manual Revision J IMx M Unit Protection Configuration 7 IMx M Unit Protection Configuration This section guides you how to download Protection part configuration to an IMx M unit 1 Connect IMx M to a computer by using a SKF USB Isolator cable Refer to Getting Started by Attaching Cable in Serial Interface section for IMx M Protection part connection 2 Start Observer On line Device Configurator 9 0 0 or later version 3 Click on Start IMx M protection serial interface Refer to Serial Interface for IMx M Protection 4 To configure an I
15. act boot up text depends on the firmware version Continue to the next step when the IMx R is powered up ptitude Observer On line Device Configurator User Manual Revision J IMx R TSI Firmware Download Firmware Version 1 0 0 or 1 1 0 5 The default value 30 of ASCII row pause in Milliseconds does not need to be changed TSI Serial Interface for IMx R only x Select COM Port 1 v Sending file to DAD Device id 01 Config crc d9ce3528 Project NIV Jul 6 2009 11 38 18 IMx R TSI firmware download Enter password Preparing flash memory Relflash Flash erasing started ERelflash OK Please start file transmission Command Figure 4 11 Example of a start transmission of firmware version 1 0 0 or 1 1 0 6 Enter download in lower case in the Command text box and finish with the Enter key The unit writes out its version in this case Jul 6 2009 11 38 18 7 The unit will ask for the start of the firmware file transmission Click on Send file button A dialog for opening a file will appear 8 Finda mot firmware file that you wish to download and open it The transmission of the firmware file will start immediately and will be busy for 3 minutes with 30 ms row pause Wait for the completion even if the program appears to be unresponsive 4 18 ptitude Observer On line Device Configurator User Manual Revision J IMx R TSI Firmware Download Firmware Version 1 0 0 or 1 1 0
16. ble click on Parts COM amp LPT to see the available USB Serial Port as shown in Figure 3 7 below Device Banraper Fle ction ewe Heip m fS FDA e Bluetooth Rafis E mine Buetooth Device ag Mg Computir Set Cink detest T Deny adapters Ja ODP CO ROM dives Gig Human Trier ace Diskit Sy IDE ATA controller IEEE 1394 Bus host controders Or Eesboard J Mie and other paling devices a H PCHCTA adapters Ports COM b LET Conmumicstions Port COM ECP Printer Port ILPT1 JERI tl Processors H SB Smart cand readers Figure 3 7 COM port device manager 3 14 ptitude Observer On line Device Configurator User Manual Revision J Serial Interface Start Serial Interface How to Change COM Port Number e Continue from the above steps e Double click on USB Serial Port then select Port Settings option USB Serial Port COM4 Properties General Port Settings Driver Details Bits per second Bali Data bits Parity Stop bits E Flow control Restore Defaults A Figure 3 8 Example of COM port settings e Select Advanced and change the COM Port Number ptitude Observer On line Device Configurator 3 15 User Manual Revision J Serial Interface Start Serial Interface a for COMA Figure 3 9 Example of COM port advanced settings COM port number can be changed to any COM port
17. d click on Start IMx M protection serial interface Refer to Serial Interface for IMx M Protection 3 To download firmware the IMx M unit needs to be powered up and must be in disarm mode Important System must be in disarm mode before Protection firmware update procedure takes place Ensure to read Protection Firmware Update chapter in IMx M User Manual thoroughly and understand it Serial Interface for IMx M Protection Select COM Port 4 Ne CLEAR tock A IMx M MyIntID 0001 CRC Ok Enter download password IMx M C SKF CMC AB Version 0214 Build Aug 27 2012 12 43 46 FW CRC OxCO8E6239 CRC Ok BoardType IO MyMcua dr 00 myIntID O1 mySlotID 01 myHexID OF Scanning for I2C devices 3C 3D 50 52 53 54 55 5C 5D Adv debug modes DisarmSlot 00 DisarmCh 0000 Selftest Ok Diag Ok Disp OK I Enable debug Command IV Capture to disk Ascii row pause 0 ms Get Config Update Config Update Fimware Close Figure 6 33 Example of boot up text of an IMx M unit 4 The IMx M displays a version and other text on the USB port upon boot up The exact boot up text depends on the firmware version Continue to the next step when the IMx M is powered up 5 Depending on which firmware version you have in the system or to which firmware version you will be updating you can either select the button Update Firmware faster or enable debug mode and select the button 3 Up
18. date firmware Adv If you are not sure whether the change of firmware requires an advanced firmware update or not always choose 3 Update firmware Adv 6 A dialog for opening a file will appear 6 40 ptitude Observer On line Device Configurator User Manual Revision J IMx M Protection Firmware Download Look in E Exe ef E ar BEETET Recent My Computer File name imxm 21 4 a48 gt dren My Network Files of type Firmware Files 448 vi Cancel Places I Open as read only Figure 6 34 Example of update firmware file selection screen for IMx M 7 Finda a48 firmware file that you wish to download and open it The password for the dialog is secret Serial Interface for IMx M Protection Select COM Port 4 z AMATAANEMEAANAM Sending file to DAD LOCK 0214 0214 0214 0214 0214 0214 0214 0214 0214 11749521 SFW CRC 00000000 download Rebooting Cause 0x46 IMx M MyIntID 0001 Adv debug modes CRC Ok Enter download password Relflash Flash erasing started yersion Ascii row pause 0 ms o Update Config Update Firmware Figure 6 35 Example of update firmware for IMx M 8 The transmission of the firmware file will start immediately Wait for the completion ptitude Observer On line Device Configurator User Manual Revision J 6 41 IMx M Protection Firmware Download Serial Interface for IMx M Protection Select COM
19. e IMx R has not powered up already power up the IMx R TSI Serial Interface for IMx R only xj Select COM Port 1 v Sending file to DAD Device id 01 Config cre a68fa50a Project NTV Entering normal run mode fe Command confi of Ascii row pause in Milliseconds 30 Send file Close Figure 5 21 Example of boot up text of an IMx R unit with firmware 1 0 0 6 The IMx R displays a version and other text on the RS 232 TSI serial port upon boot up The exact boot up text depends on the firmware version 5 28 ptitude Observer On line Device Configurator User Manual Revision J IMx R Unit TSI Configuration With Firmware Version 1 0 0 or 1 1 0 7 The default value 30 of ASCII row pause in Milliseconds does not need to be changed 8 Enter config in lower case in the Command text box and finish with the Enter key The unit will ask for a TSI configuration file Click Send file button A dialog for opening files will appear Oppna _ Leta i O IMx R configurator er et Em Fe 7 Config tvsr Bin 6 2 Config Bin 7 Config N Senast 3 Confid Typ FDT4 Data File anv nda dok Senast ndrad 2009 07 06 15 40 Storlek 1 17 kB Skrivbord Mina dokument r oe BEE EEG Filformat Firmware Files MOT Binary files BIN z Avbryt v I Oppna som skrivskyddad Command EGGE Ascii row pause in Milliseconds 30 Send file Figure 5 22 Example of IMx R TSI c
20. er Manual Revision J CM Network Configuration File Creating Downloading The valid device number is between 1 and 255 It is important that this device number must be unique There can not be two on line devices with the same unit number Obtain an IP address automatically allows the system to get the IP address Use the following IP address allows the user to enter IP Number Subnet mask and Gateway information manually IP number and Subnet mask are the standard settings for all devices communicating with the TCP IP protocol Therefore configure IP number and subnet mask according to the TCP IP standard Use the 1 button to increase IP number and Device number by one when configuring by Software This can be useful when configuring a large number of units by Software Gateway should be configured according to the TCP IP standard If no gateway should be used set it to the default value of 0 0 0 0 Observer Monitor IP and Observer Monitor Port are the IP number and port number of the computer where ptitude Observer Monitor has been installed The on line device needs to know where the server application is located in order to send and retrieve data Ethernet factory defaults interface sets all the values back to the default values Save prompts you about the location where you want to save the configuration file before it begins to save all the changes made You can save the file anywhere on your local ha
21. igure TSI for IMx R units with the firmware version 1 2 0 1 Connect IMx R to a computer by using a null modem cable A USB to RS 232 converter may be required Refer to Getting Started by Attaching Cable in Serial Interface section for IMx R TSI part connection 2 Start Observer on line device Configurator 8 4 0 3 Click on Start IMx R TSI serial interface Refer to TSI Serial Interface for IMx R 4 It is strongly recommended to shut down all the running tasks before proceeding with the configuration of an IMx R 5 To configure an IMx R unit the unit needs to be powered up If the IMx R is not powered up already power up the IMx R TSI Serial Interface for IMx R Select COM Port v IMx R TSI Cro OK Enter download password Loading app Ok FU Cre OxchOfed67 0k Version 1 2 build 1907 on Mar 24 2010 14 22 38 IAR 0141 Key ffffffffffffff Cstack Ok Istack Ok Config Ok Unit id 01 Config cre 6fcee7a4 Customer NTV CfgVer 000 000 011 Entering normal run mode Command Ascii row pause in Milliseconds 30 Download config Download Firmware Close Figure 5 25 Example of boot up text of an IMx R unit with firmware 1 2 0 6 The IMx R displays a version and other text on the RS 232 TSI serial port upon boot up The exact boot up text depends on the firmware version 7 Enter config in lower case in the Command text box and finish with the Enter key 8 Click on Download config button A dia
22. irmware Version 1 3 0 or Later Version TSI Serial Interface for IMx R Select COM Port 1 x Sending file to DAD Preparing flash memory Relflash Flash erasing started ERelflash OK Please send configuration file Received ok Relflash Flash programming started ERelflash OK SafeState2 001b 0000 Rebooting Cause 0x01 Ok CPUreg OK FW Cre Ox7hd8229e OK Version 1 3 MiR19 build 2585 on Apr 28 2010 14 22 IAR 0141 Key ffffffffffffff Stack OK Relays Ok Config OK ID 02 Plug 3f Config cre b7f6a58e Customer NTV CfgVer 000 000 011 Entering normal run mode Command em SO Ascii row pause 0 ms Get Config Download Firmware Close Figure 5 32 Example of a successful configuration file transmission with IMx R firmware 1 3 0 11 If the download is successful the unit will restart with the new TSI configuration Make sure to check the TSI configuration information ptitude Observer On line Device Configurator User Manual Revision J 5 39 IMx M Protection Firmware Download 6 IMx M Protection Firmware Download The following steps will guide you with downloading a new firmware to an IMx M unit 1 Connect IMx M to a computer by using a SKF USB Isolator cable Refer to Getting Started by Attaching Cable in Serial Interface section for IMx M Protection part connection 2 Start Observer on line device configurator 9 0 0 or later version an
23. l appear 4 24 ptitude Observer On line Device Configurator User Manual Revision J IMx R TSI Firmware Download Firmware Version 1 3 0 or Later Version Fila parma Tsk reat L e My Nae Files of hyper Faravare Fest MOT Coel T Open at ject orke Figure 4 18 Example of open file dialog screen for firmware version 1 3 0 6 Find a mot firmware file that you wish to download and open it The password for the dialog is secret ptitude Observer On line Device Configurator 4 25 User Manual Revision J IMx R TSI Firmware Download Firmware Version 1 3 0 or Later Version TSI Serial Interface for IMx R Select COM Port Sending file to DAD fi LUTT TET TETT TT STARTING DOWNLOAD SENDING FILE Size download SafeStatez 0001 Rebooting Cause 188458 bytes 0000 0x01 Enter download password Preparing flash memory Relflash Flash erasing started ERelflash OK Please start file transmission Command Ascii row pause fo ms 7 The transmission of the firmware file will start immediately Wait for the completion Get Contig Download Config i Figure 4 19 Example of Download firmware version 1 3 0 4 26 ptitude Observer On line Device Configurator User Manual Revision J IMx R TSI Firmware Download Firmware Version 1 3 0 or Later Version TSI Serial Interface for IMx R Select COM Port fi Sending file to DAD Relflash Fla
24. ld 1907 on Mar 24 2010 14 22 38 IAR 0141 Key ffffffffffffff Cstack Ok Istack Ok Config Ok Unit id 01 Config cre 6fcee7a4 Customer NTV CfgVer 000 000 011 Entering normal run mode Command Ascii row pause in Milliseconds 30 Download config Download Firmware Close Figure 4 13 Example of boot up text of IMx R with firmware version 1 2 0 4 The IMx R displays a version and other text on the RS 232 TSI serial port upon boot up The exact boot up text depends on the firmware version Continue to the next step when the IMx R is powered up 5 Click Download Firmware A dialog for opening a file will appear 4 20 ptitude Observer On line Device Configurator User Manual Revision J IMx R TSI Firmware Download Firmware Version 1 2 0 Look in release 1 2 v e ex Hr o BAAT Recent 3 Desktop D My Documents My Computer File name ftsi 1 2 0 mot z My Network Files of type Firmware Files MOT bn Places Open as read only Command Ascii row pause in Milliseconds fo Download contig Download Firmware Close Figure 4 14 Example of open file dialog screen for firmware version 1 2 0 6 Finda mot firmware file that you wish to download and open it The password for the dialog is secret ptitude Observer On line Device Configurator 4 21 User Manual Revision J IMx R TSI Firmware Download Firmware Version 1 2 0 TSI Serial Interface for IMx
25. log for opening files will appear 5 32 ptitude Observer On line Device Configurator User Manual Revision J IMx R Unit TSI Configuration With Firmware Version 1 2 0 Look in O release 1 2 FX cont Config NTV 0 0 11 Bin File name Contig Bin My Network Files of type Binary files BIN v I Open as read only Entering normal run mode config Send configuration file Command Ascii row pause in Milliseconds fo Download contig Download Firmware Close Figure 5 26 Example of configuration file selection screen with IMx R firmware 1 2 0 9 Choose a Bin file with which you wish to configure the unit 5 33 ptitude Observer On line Device Configurator User Manual Revision J IMx R Unit TSI Configuration With Firmware Version 1 2 0 TSI Serial Interface for IMx R a x Select COM Port Sending file to DAD STARTING DOWNLOAD SENDING FILE Size 1200 bytes Relflash Flash programming started ERelflash OK Command peoo Ascii row pause in Milliseconds fo Download Firmware Close Figure 5 27 Example of configuration file transmission with firmware 1 2 0 10 The transmission of the TSI configuration file will start immediately 5 34 ptitude Observer On line Device Configurator User Manual Revision J IMx R Unit TSI Configuration With Firmware Version 1 2 0 TSI Serial Interface for IMx R Select COM Pott fi vi
26. nd understand Disarm chapter in IMx M user manual before disarm is released v Ensure there are no circuit faults before disarmed is released v Wait at least 30 seconds before you release disarm ptitude Observer On line Device Configurator 7 45 User Manual Revision J
27. onfiguration file selection screen 10 Choose a Bin file with which you wish to configure the unit ptitude Observer On line Device Configurator 5 29 User Manual Revision J IMx R Unit TSI Configuration With Firmware Version 1 0 0 or 1 1 0 TSI Serial Interface for IMx R only a STARTING DOWNLOAD SENDING FILE Size 1200 bytes Relflash Flash programming started ERelflash OK Figure 5 23 Example of configuration file transmission with IMx R firmware 1 0 0 11 The transmission of the TSI configuration file will start immediately 5 30 ptitude Observer On line Device Configurator User Manual Revision J IMx R Unit TSI Configuration With Firmware Version 1 0 0 or 1 1 0 TSI Serial Interface for IMx R only a STARTING DOWNLOAD SENDING FILE Size 1200 bytes Relflash Flash programming started ERelflash OK Device id 01 Config cre a68fa50a Project NTV Entering normal run mode Figure 5 24 Example of a successful configuration file transmission with IMx R firmware 1 0 0 12 If the download is successful the unit will restart with the new TSI configuration Make sure to check the TSI configuration information ptitude Observer On line Device Configurator 5 31 User Manual Revision J IMx R Unit TSI Configuration With Firmware Version 1 2 0 With Firmware Version 1 2 0 The following steps will guide you how to conf
28. ow This can be useful when a user wants to copy and paste information from the output window e Remove data deletes all the measurement data and event log that the On line Device has collected and stored in the memory This command is reasonable to execute just after an installation of an on line device During the installation a lot of data may have been collected to the on line device while connecting sensors or the machinery has not been running As a general rule always run this after finishing an installation to make sure that incorrect data or data that were taken under wrong conditions are removed 3 10 ptitude Observer On line Device Configurator User Manual Revision J Serial Interface Start Serial Interface Update network config updates the on line device firmware or send any other configuration file to the on line device These configuration files most commonly have the extension of M16 or IMx It prompts the user for a configuration file to download Syntax Help gives the user access to syntax help in the current prompt It is a good practice to use this interface before you start downloading any files to ensure that you have established communication with the on line device If you don t get the access to syntax help change the COM port and try it again If it still fails reset the on line device with RESET command on the physical on line device and repeat the procedure once more When you receive the s
29. rd drive The configuration file has the extension of M16 or IMx and is used to update the network configuration of the unit via serial interface Downloading is a simple one time process which is accomplished by the serial interface Refer to the next section Serial Interface ptitude Observer On line Device Configurator 2 7 User Manual Revision J Serial Interface 3 Serial Interface The serial interface in ptitude Observer On line Device Configurator contains functions and instructions that are useful when configuring and performing a service on on line devices This feature is recommended to be run from a portable computer along with a standard serial cable Getting Started by Attaching Cable Attaching a cable to an on line device is different depending on the type of the unit and function Select the corresponding case and follow the instruction listed from below e For WindCon open the casing and attach the first end of the serial cable to the COM port connector This cable has only one possible place to be attached therefore it can not be connected incorrectly e For MasCon16R connect the first end of the serial cable to the J5 RS 232 port Connect the other end to a free COM port on your computer e For IMx M connect the SKF USB Isolator cable to a free USB port of your PC Connect the other end to the IMx M unit s USB port IMx M has two different USB ports USB port for configuration of CM par
30. recommended to shut down all the running tasks before proceeding with the configuration of an IMx R unit 5 To configure an IMx R unit the unit needs to be powered up If the IMx R is not powered up already power up the IMx R unit TSI Serial Interface for IMx R Select COM Port 1 vi IMx R TSI Cro OK Enter download password FW Cre Ox7 bd8229e 0k Version 1 3 MiR19 build 2585 on Apr 28 2010 14 22 59 IAR 0141 Key ffffffffffffff Stack OK Relays OK Configq OK ID 02 Plug 3f Config cre b7f6a58e Customer NTV CfgVer 000 000 011 Entering normal run mode Command Ascii row pause 0 ms Get Config Download Config Download Firmware Close Figure 5 29 Example of boot up text of an IMx R unit with firmware 1 3 0 6 The IMx R displays a version and other text on the RS 232 TSI serial port upon boot up The exact boot up text depends on the firmware version 7 Click on Download config button 8 The password for the dialog is secret A dialog for opening files will appear 5 36 ptitude Observer On line Device Configurator User Manual Revision J IMx R Unit TSI Configuration With Firmware Version 1 3 0 or Later Version Look jr E contig cf Mn Tag DO 1 INE 61 2000 08 27 1839 e ereti Ho TT DOLE MTV 0 DT OG 33 dT i Br PR To DDLI MTV OD DH GL Deset def Bir IMR Teig 001 NTV OD Z0U0H40927 1123 dTe Dm di Hak T PSEC ATV 0 DLO 16 DOG Gode Pace Bin IM oF J L JR MsR Tag 1
31. rsion Firmware Version 1 3 0 or Later Version The following steps will guide you with downloading a new firmware version 1 3 0 or later version to an IMx R unit 1 Connect IMx R to a computer by using a null modem cable A USB to RS 232 converter may be required Refer to Getting Started by Attaching Cable in Serial Interface section for IMx R TSI part connection 2 Start Observer on line device configurator 8 4 0c or later version and click on Start IMx R TSI serial interface Refer to TSI Serial Interface for IMx R 3 To download firmware the IMx R unit needs to be powered up If the unit is not powered up already power up the IMx R unit TSI Serial Interface for IMx R Select COM Pott 1 vi IMx R TSI CrC OK Enter download password FW Cre Ox7 bd8229e 0k Version 1 3 MiR19 build 2585 on Apr 28 2010 14 22 59 IAR 0141 Key ffffffffffffff Stack OK Relays OK Config OK ED 02 Plug 3t Config cre b7f6a58e Customer NTV CfgVer 000 000 011 Entering normal run mode Command Asciirow pause 0 ms Get Config Download Config Download Firmware Close Figure 4 17 Example of boot up text of IMx R with firmware version 1 3 0 4 The IMx R displays a version and other text on the RS 232 TSI serial port upon boot up The exact boot up text depends on the firmware version Continue to the next step when the IMx R is powered up 5 Click Download Firmware A dialog for opening a file wil
32. s can be useful if a user wants to copy and paste information from the output window e Command is where you can enter commands or instructions manually More information on IMx R TSI commands can be found in IMx R User Manual e ASCII row pause in milliseconds is the pause between each ASCII row Normally there is no need to change e Get Config reads back the configuration file currently in use by the unit e Update Config downloads a configuration file to IMx R unit Refer to IMx R Unit TSI Configuration e Update Firmware downloads TSI firmware to IMx R unit Refer to IMx R TSI Firmware Download e Close closes the TSI Serial Interface for IMx R screen 3 12 ptitude Observer On line Device Configurator User Manual Revision J Serial Interface Start Serial Interface Serial Interface for IMx M Protection Serial Interface for IMx M Protection Select COM Pot i CLEAR LOCK Adv debug modes I Enable debug Command IV Capture to disk Ascii row pause 0 ms Get Config Update Config Update Firmware Close Figure 3 6 TSI Serial interface for IMx M screen e Select COM port indicates serial port interface for communication Refer to Getting Started by Attaching Cable in Serial Interface section for IMx M unit USB port for IMx M Protection part configuration Refer to Select COM Port for IMx M in order to find out the COM port number or to change COM port number e Clear clears the
33. sh programming started EEEEEERelflash OK FU Cre Ox bd6229e 0k Version 1 3 MiR19 build 2585 on Apr 28 2010 14 22 IAR 0141 Key fffffffftfftffff OK OK ID 02 Plug 3f Config cre b7f6a58e Customer NTV CfgVer 000 000 011 Entering normal run mode Command Ascii row pause fo ms Get Config Download Config Figure 4 20 Example of a successful download firmware version 1 3 0 8 Ifthe download is successful the unit will reboot and run the new version of firmware ptitude Observer On line Device Configurator 4 27 User Manual Revision J IMx R Unit TSI Configuration 5 IMx R Unit TSI Configuration The IMx R unit TSI configuration process varies depending on the firmware version With Firmware Version 1 0 0 or 1 1 0 The following steps will guide you how to configure TSI for IMx R units with the firmware version 1 0 0 or 1 1 0 1 Connect IMx R to a computer by using a null modem cable A USB to RS 232 converter may be required Refer to Getting Started by Attaching Cable in Serial Interface section for IMx R TSI part connection 2 Start Observer on line device Configurator 8 3 0 or earlier version 3 Click on Start IMx R TSI serial interface Refer to TSI Serial Interface for IMx R 4 It is strongly recommended to shut down all the running tasks before proceeding with the TSI configuration of an IMx R unit 5 To configure an IMx R unit the unit needs to be powered up If th
34. sion J CM Network Configuration File 2 CM Network Configuration File A network configuration file is a file that needs to be loaded into the on line device in order to make the on line device a part of the network It sets an identity on the on line device so that ptitude Observer Monitor knows with which on line device it is communicating This file is basically a text file with the extension M16 or IMx The file has to be created through ptitude Observer On line Device Configurator and downloaded with the integrated serial interface to the on line device Creating Creating a configuration file with ptitude Observer On line Device Configurator is simple 1 First start the ptitude Observer x x On line Device Configurator program located in the SKF ptitude Monitoring Suite kos Observer on line device Configurator 9 0 0 xi m Select desired action Create a Network and ID configuration file for IMx or MasCon16 and save to disk Start serial interface for IMX or MasCon 16 Start IMx R TSI serial interface Start IMx M protection serial interface Figure 2 1 Observer On line Device Configurator main screen 2 From the main menu Click on the icon of Create a network and ID configuration file for IMx or MasCon16 and save to disk ptitude Observer On line Device Configurator 2 5 User Manual Revision J CM Network Configuration File Creating Create IMx Mas
35. t located on the front panel of CPU card USB port for configuration of Protection part located on the front panel of 1 0 card Important SKF USB isolator cables must always be used when connecting to IMx M USB ports e For IMx R connect the first end of the serial cable to the RS 232 port for TSI or to the RS 232 port for CM depending on which serial interface will be performed Connect the other end to a free COM port on your computer RS 232 port for CM part J7 RS232 CM configuration located on the front panel of the unit RS 232 port for TSI part J6 RS232 TSI configuration located on the front panel of the unit e For other IMx connect the first end of the serial cable to the RS 232 port Connect the other end to a free COM port on your computer Important Before going out to do a service or installation in the field make sure that your computer actually has a COM port On some of the new portable computers the COM port has been removed and replaced by a USB port If this is the case you will need a USB to serial converter 3 8 ptitude Observer On line Device Configurator User Manual Revision J Serial Interface Start Serial Interface Start Serial Interface to Observer on line device Configurator 9 0 0 Figure 3 3 Observer On line Device Configurator main screen For Condition Monitoring CM part of IMx MasCon 16 IMx R or IMx M serial interface start ptitude Observer
36. yntax help the on line device is ready to be updated Set debug On Off prints not prints measurement values of which the on line device is currently measuring for example gt PROCESS 69 617386 ANA10000004 on channel 4 DBID 10000004 RESET performs a software reset Show Config displays the current measurement configuration of which the on line device is currently using Get Events stores all events from the unit to a file in user readable format See corresponding IMx user manual for detailed event information Adv debug modes advanced debug modes should only be used by experienced installation engineers in cooperation with SKF Condition Monitoring Center Command is where you can enter commands or instructions manually ptitude Observer On line Device Configurator 3 11 User Manual Revision J Serial Interface Start Serial Interface TSI Serial Interface for IMx R TSI Serial Interface for IMx R Select COM Pot i CLEAR Lock Command Ascii row pause 0 ms Get Config Update Config Update Firmware Close Figure 3 5 TSI Serial interface for IMx R screen e Select COM port indicates serial port interface for communication Refer to Getting Started by Attaching Cable in Serial Interface section for IMx R unit TSI RS 232 port for TSI configuration e Clear clears the output window e Lock is a toggle button which locks unlocks the contents on the output display window Thi