APCUPSD User Manual
Contents
1. Customizing Event Handling When apcupsd detects anomalies from your UPS device it will make some decisions that usually result in one or more calls to the script located in etc apcupsd apccontrol The apccontrol file is a shell script that acts on the first argument that apcupsd passes to it These actions are set up by default to sane behavior for all situations apcupsd is likely to detect from the UPS However you can change the apccontrol behavior for every single action To customize so create a file with the same name as the action which is passed as a command line argument Put your script in the etc apcupsd directory These events are sent to the system log optionally sent to the temporary events file etc apcupsd apcupsd events and they also generate a call to etc apcupsd apcecontrol which in turn will call any scripts you have placed in the etc apcupsd directory Normally etc apcupsd apccontrol is called only by apcupsd Consequently you should not invoke it directly However it is important to understand how it functions and in some cases you may want to change the messages that it prints using wall We recommend that you do so by writing your own script to be invoked by apccontrol rather than by modifying apccontrol directly This makes it easier for you to upgrade to the next version of apcupsd In other case you may want to write your own shell scripts that will be invoked by apccontrol For exa
2. computer Inside the Connector UPS DIB I RJ45 pini oignal Pink C uleue 4 DSR gt diode resistor 6 DTR gt gt 0 kill power 8 Orange i DCD lt 4 H 2 Re lt ee o low battery 3 Brown a RIS gt INJA 8 RI lt o on battery 2 Black 9 CTS lt 4 s signal 5 GND ground T Rec 3 TxD chassis o ground Chassis GND Not connected The RJ45 pins are looking at the end of the connector 10 98S 76543 42 2 940 0128D Cable Wiring Supported BackUPS XS1000 BX 1000 Possibly other USB models Models Contributed Jan Babinski jbabinsk at pulsarbeacon dot com by 940 0128D is functionally similar to the 940 0128A cable except for NC on 6 DTR and 2 RD on the computer side Unverified Try setting apcupsd to UPSTYPE dumb and UPSCABLE 940 0128A APC Part 940 0128D DB9 Computer RJ45 10 UPS 5 1 Ce olo oron oo00000000 i rOmOmom ome 9 6 10 L 1 RI 9 lt 4 CTS 8 lt E 2N2222 NPN Ni ee ME Cc VVVV gt lt 2 OnBatt RTS 7 gt 2k 1N5819 VVVV gt lt 3 LowBatt G aa B DEDEDE E 2N2222 NPN DTR 4 gt gt 8 KillPwr GND 5 7 Signal GND Shield 4 Chassis GND 940 0127B Cable Wiring Supported BackUPS XS1000 BX 1000 Possibly other USB models Models Contributed Jan Babinski jbabinsk at pulsarbeacon dot com by Standard USB
3. You can display different bar graphs by selecting different variables from the drop down menus at the top of each of the three bar graphs As with multimon if you have your local host configured in the etc apcupsd hosts conf file you can execute it from a Unix shell from the source cgi directory as follows upsstats cgi As with multimon quite a few lines of html should then be displayed upsfstatus cgi If you would like to see all of the STATUS variables available over the network click on the Data field of the desired system and your browser will display something like the following APC 23 O01 048 1110 DATE 2 He Dee O2 l7ys27s2i Cir 1999 HOSTNAME matou sibbald com RELEASE amp 3 57 WSosiearik CABLE Custom Cable Smart MODEL SMART UPS 1000 UPSMODE Stand Alone UPSNAME B WIE S _ IDI SIN LINEV Se 6 VOLTES MAXLINEV 224 9 Volts IMOCINPEILINIEW 5 2 3 VOLTS INNA SOMOM QULBUIYV 3 223 6 VOLTS OAD E Claes 6 2 Percent Load Capacity BATTV 3 27 9 Volts BCHARGE 100 0 Percent MBATTCHG 5 Percent TIMELEFT 167 0 Minutes MINTIMEL 3 Minutes SENSE High DWAKE 060 Seconds DSHUTD 020 Seconds LOTRANS gt 96 0 Votes HITRANS 5 235350 Voles RETPCT 050 0 Percent STATFLAG 0x08 Status Flag STATUS ONLINE ITEMP B 35 11 Meiesiemeul ALARMDEL Low Battery LASTXFER U command or Self Test SELFTES aN
4. The first two cases Ident and Batt date are somewhat special in that you tell the UPS you want to change the value then you supply 8 characters that are saved in the EEPROM The last ten item are programmed by telling the UPS that you want it to cycle to the next permitted value In each case you indicate to the UPS that you want to change the EEPROM by first sending the appropriate query command e g c for the UPS ID or u for the Upper Transfer voltage This command is then immediately followed by the cycle EEPROM command or In the case of the UPS ld or the battery date you follow the cycle command by the eight characters that you want to put in the EEPROM In the case of the other ten items there is nothing more to enter The UPS will respond by OK and approximately 5 seconds later by a vertical bar to indicate that the EEPROM was changed NIS Network Server Protocol The NIS network server in apcupsd is capable of sending status and events data to clients that request it The communication between the client and the server is performed over a TCP connection to the NISPORT normally port 3551 The client opens a connection to the server and sends a message to which the server will reply with one or more messages Each message consists of a 2 byte length in network byte order followed by that many bytes of data Both the client gt server and server gt client messages follow this format apcupsd supports two comma
5. Query the UPS for all known values Perform a Battery Runtime Calibration Abort Battery Calibration Monitor Battery Calibration progress Program EKEPROM Enter TTY mode communicating with UPS Quit cn Gal PS Gey kor Select function number 1 Item 1 will probe the UPS for all values known to apcupsd and present them in rather raw format This output can be useful for providing technical support if you are having problems with your UPS Item 2 will perform a Battery Runtime Calibration This test will only be performed if your battery is 100 charged Running the test will cause the batteries to be discharged to approximately 30 of capacity The exact number depends on the UPS model In any case apctest will abort the test if it detects that the battery charge is 20 or less The advantage of doing this test is that the UPS will be able to recalibrate the remaining runtime counter that it maintains in its firmware As your batteries age they tend to hold less of a charge so the runtime calibration may not be accurate after several years We recommend that perform a Battery Calibration about once a year You should not perform this calibration too often since discharging the batteries tends to shorten their lifespan Item 3 can be used to abort a Battery Calibration in progress if you some how became disconnected Item 4 can be used to restart the monitoring of a Battery Calibration if you should some how become disconn
6. Mek 2 RxD k 2 o low battery 7 RTS gt 7 4 4 8 RI lt 8 o on battery 9 CHS lt 9 Ss 5 GND 5 o ground 3 TxD 3 me 940 0128A Cable Wiring Supported Older USB BackUPS ES and CS Models Contributed Many thanks to all for your help by Though these UPSes are USB UPSes APC supplies a serial cable typically with a green DB9 F connector that has 940 0128A stamped into one side of the plastic serial port connector The other end of the cable is a 10 pin RJ45 connector that plugs into the UPS thanks to Dean Waldow for sending a cable Apcupsd version 3 8 5 and later supports this cable when specified as UPSCABLE 940 0128A and UPSTYPE dumb However running in this mode much of the information that would be available in USB mode is lost In addition when apcupsd attempts to instruct the UPS to kill the power it begins cycling about 4 times a second between battery and line The solution to the problem thanks to Tom Suzda is to unplug the UPS and while it is still chattering press the power button on the front of the unit until the unit beeps and the chattering stops After that the UPS should behave normally and power down 1 2 minutes after requested to do so Thanks to all the people who have helped test this and have provided information on the cable wiring our best guess for the cable schematic is the following APC Part 940 0128A
7. Now halt or reboot echo Smessage ct rastooocrt y taiem echo On the next boot fsck will be skipped elif forcefsck A then echo On the next boot fsck will be forced E 1 te TS EHONC TUN ONSIO 7 9 S Hots el SHOXOMUOVSIO UO UOC iS Pcl o CUlOs Claas Ht 1 OVO UNONSIO o res el SHOXOMUOVSIO Es ariel CUO S Guam Ps hs UOOUOSIO 9 Priel GiUlOs Clann Paseo CUO S Cis Eos OPEP dR AA The purpose of modifying the system halt files is so that apcupsd will be recalled after the system is in a stable state At that point apcupsd will instruct the UPS to shut off the power This is necessary if you wish your system to automatically reboot when the mains power is restored If you prefer to manually reboot your system you can skip this final system dependent installation step by specifying the disable install distdir option on the configure command see below for more details The above pertains to Red Hat systems only There are significant differences in the procedures on each system as well as the location of the halt script Also the information that is inserted in your halt script varies from system to system Other systems such as Solaris require you the make the changes manually which has the advantage that you won t have any unpleasant surprises in your halt script should things go wrong Please consult the specific system dependent README files for more details Please note that if you install fro
8. Recommended Options for most Systems For most systems we recommend the following options o CONE WS prefix usr sbindir sbin enable usb and you can optionally build and install the CGI programs as follows configur prefix usr sbindir sbin enable usb nable cgi with cgi bin home httpd cgi bin Compilers and Options Some systems require unusual options for compilation or linking that the configure script does not know about You can specify initial values for variables by setting them in the environment Using a Bourne compatible shell you can do that on the command line like this CFLAGS 02 Wall LDFLAGS configure Or on systems that have the env program you can do it like this env CPPFLAGS I usr local include LDFLAGS s configure Or for example on the Sun Solaris system you can use setenv CFLAGS 02 setenv LDFLAGS 0O configure You can get a listing of all available options by doing configure help or simply see the previous section of this manual Operating System Specifics With the exception of Linux SUSE and Linux Red Hat systems used by the developers we rely on users to help create installation scripts and instructions as well as to test that apcupsd runs correctly on their system As you can imagine most of these people are system administrators rather than developers so they are very busy and don t always have time to test the latest releases With that in
9. STESTI 5 336 DLOWBATT 02 Minutes DIPSW Te OS lt O10 MD sito me owi teh REG1 0x00 Register 1 REG2 Ox00 Register 2 REG3 0x00 Register 3 MANDATE s 01 11 99 SERIALNO GS9903001147 BATTDATE 01 11 99 NOMOUTV 230 0 NOMBATTV 24 0 HUMIDITY N A AMBTEMP N A EXTBAmNHS 8 0 BADBATTS N A FIRMWARE 60 11 1 APCMODEL IWI NID JARI 8 Wel Dec O24 WVe2y7e25 Cane Qe You should get pretty much the same output mixed in with html if you execute upsfstats cgi directly from a Unix shell in the cgi subdirectory as explained above for upsstats cgi and multimon cgi A Tip from Carl Erhorn for Sun Systems It is possible to run the CGI code to monitor your UPS using the answerbook HTTP server that runs on Solaris As long as your server has the Answerbook2 web server installed and running you can insert the cgi scripts into the cgi directory of the web server and access the cgi using something like http hostname 8888 cgi multimon cgi CGI Credits Many thanks go to Russell Kroll rkroll exploits org who wrote the CGI programs to work with his UPS Monitoring system named Network UPS Tools NUT Thanks also to Jonathan Benson jbenson technologist com for initially adapting the upsstatus cgi program to work with apcupsd We have enhanced the bar graph program and hope that our changes can be useful to the original author in his project Security Issues e apcupsd runs as root e If you have NE
10. Configuration Directives Used by the Network Information Server 70 71 71 72 72 72 72 73 73 74 74 74 75 75 75 77 78 78 78 79 79 79 80 80 81 81 82 83 83 84 85 86 86 86 87 88 88 89 Configuration Directives used during Power Failures 90 Configuration Directives used to Control System Logging 92 Configuration Directives for Sharing a UPS 92 Configuration Directives Used to Set the UPS EEPROM 93 apcupsd Status Logging 94 Status report format 94 Status Report Example 94 Status Report Fields 95 Logging the STATUS Information 98 The Shutdown Sequence and its Discontents 98 Shutdown Sequence 99 Shutdown Problems 100 Master Slave Shutdown 100 Startup 100 Windows Considerations 101 APC smart protocol 101 Description 101 RS 232 differences 101 The Smart Protocol 101 Dip switch info 107 Status bits 107 Alert messages 107 Register 1 108 Register 2 108 Register 3 109 Interpretation of the Old Firmware Revision 109 Interpretation of the New Firmware Revision 110 EEPROM Values 110 Programming the UPS EEPROM 111 NIS Network Server Protocol 112 Apcupsd RPM Packaging FAQ 113 Credits 114 Contributors 114 Important Legal Disclaimer No person should rely on the contents of the APCUPSD Manual the manual without first obtaining advice from APC Technical Support The manual is provided on the terms and understanding that 1 the authors contributors and editors are not responsible for the results of any act
11. If you own your UPS for long enough you will inevitably need to replace the UPS battery or battery cartridge An APC battery cartridge comprises two batteries physically stuck together with double sided tape and wired in series After the decision to replace the batteries you will face another decision almost immediately whether to purchase genuine APC replacement batteries or not There are pros and cons to purchasing genuine replacement APC batteries APC Battery Pros e APC batteries are supported by APC e APC batteries come with all the necessary hardware e APC batteries come as pre made cartridges e APC batteries will physically fit your UPS APC Battery Cons e APC batteries cost up to 4 times the cost of third party batteries There are also pros and cons to purchasing third party batteries Third Party Battery Pros e A third party battery may cost up to 1 4 the price of APC batteries A third party battery may have a higher capacity for the same physical size Third Party Battery Cons e You will need to recycle your battery hardware cables connectors etc e You will need to create your own battery cartridges with double sided tape e You will need to ensure the third party battery is the right physical size e You will need to ensure the third party battery is the right capacity e Use of a third party battery will void APC s Equipment Protection Policy e Use of a third party battery may void UL CSA VDE and other safety
12. OK Also sounds the beeper for 2 seconds test Battery 27 87 Varies based on current level of charge See also voltage Nominal Battery Voltage Internal 036 0 Units are degrees C Temperature Runtime l then Runs until battery is below 25 35 for Matrix calibration Updates the j values Only works at 100 battery charge Can be aborted with a second D Automatic self 336 Writable variable Possible values test interval e 336 14 days e 168 7 days e ON at power on note extra space e OFF never Line 60 00 Units are Hz Value varies based on locality frequency usually 50 60 Cause of last O Possible values transfer to P battery eR unacceptable utility voltage rate of change e H high utility voltage e L low utility voltage e T line voltage notch or spike e O no transfers since turnon e S transfer due to U command or activation of UPS test from front panel e NA transfer reason still not available read again Measure UPS FF not decoded yet Alarm enable Measure UPS OF 00 not decoded yet Alarm status Shutdown OK or Send twice with gt 1 5s delay between chars Older with grace units send instead of OK Length of grace period no period is set with Grace Period command UPS will return remain off and NOT power on if utility power is restored Input line 118 3 Value varies based on locality Does not always voltage read 000 0 on line failure Maximum line 118 9 This is the max voltage si
13. ero apctnsc epet tosl s Come rw r r 1 root root 11822 Aug 25 14 31 etc apcupsd apcupsd ups cont In my case upsO is the UPS powering the UPS server running the multiple apcupsd instances so only upsO should initiate a shutdown of the local machine The differences between the confs are minor since both UPSes are USB although that is not a requirement mixing cable types works fine too adk0212 mail apcupsd diff u apcupsd upsO conf apcupsd upsl conf Mapep Ups ORCO 2007 08 03 08 39 26 000000000 0400 apcupsd upsl conf 2007 08 25 14 31 17 000000000 0400 UPSNAME ups0 UPSNAME upsi DEVICE dev ups0 DEVICE dev ups1l SCRIPTDIR etc apcupsd SCRIPTDIR etc apcupsd null PWRFAILDIR etc apcupsd PWRFAILDIR etc apcupsd null NOLOGINDIR etc NOLOGINDIR etc apcupsd null ANNOY 300 ANNOY 0 SINISLORE BSS SPOR eS oo EVENTSFILE var log apcupsd events EVENTSFILE var log apcupsd 2 events The important difference to note is that ups1 has its SCRIPTDIR PWRFAILDIR and NOLOGINDIR set to a special null directory that have created This directory contains a copy of the event handling scripts modified to avoid shutting down the local machine Details below Also the UPSes are given different EVENTSFILE and NISPORT settings Plus disable the annoy feature on ups1 Since the state of that UPS does not impact local users there s no reason to annoy them h
14. or with an incorrect platform and have it install and run it would not contain correct dependency information for the rpm database The platform define may be edited in the spec file directly by default all defines are set to 0 or not set For example to build the RedHat 7 x package find the line in the spec file which reads Sdefine rh7 0 and edit it to read SCE imera a Alternately you may pass the define on the command line when calling rombuild rpmbuild ba define build_rh7 1 apcupsd spec remount raSloyblaLikel define joyblalikel sel F LPE AER 5 SEIS ePm How do I control whether usb support gets built Up through version 3 12 by default standard serial port support was built and the apcupsd std package was produced The usb package pre configured the configuration files for usb devices and installed a couple additional tools in etc apcupsd but the usb driver was built regardless To get the usb package and support in those versions either set the Sdefine usb 0 to define usb 1 in the spec file directly or pass it to rpmbuild on the command line rpmbuild pal define build_rh7 1 define build_usb 1 apcupsd spec With the release of 3 14 USB support is now considered standard and the apcupsd std and apcupsd usb packages are obsoleted in favor of a single apcupsd package configured for usb connected UPS s The serial port driver is still built and can be configured accordingly after installation If you are per
15. the mouse control program for command windows was using the serial port without using the standard Unix locking mechanism As a consequence both apcupsd and gpm were reading the serial port Please ensure that if you are running gpm that it is not configured with a serial port mouse on the same serial port Cables You can either use the cable that came with your UPS the easiest if we support it or you can make your own cable We recommend that you obtain a supported cable directly from APC If you already have an APC cable you can determine what kind it is by examining the flat sides of the two connectors where you will find the cable number embossed into the plastic It is generally on one side of the male connector To make your own cable you must first know whether you have a UPS that speaks the apcsmart protocol or a dumb UPS that uses serial port line voltage signalling If you have an smart UPS and you build your own cable build a Smart Custom cable see Smart Custom Cable for SmartUPSes If you have a voltage signalling or dumb UPS build a Simple Custom cable see Simple Custom Voltage Signalling Cable for dumb UPSes If you have a BackUPS CS with a RJ45 connector you can build your own Custom RJ45 cable see Custom RJ45 Smart Signalling Cable for BackUPS CS Models Smart Custom Cable for SmartUPSes You do not have this cable unless you built it yourself The Smart Custom cable is not an APC product SMART CUSTOM CAB
16. FreeBSD OpenBSD NetBSD Windows Solaris and Mac OS X Darwin If you plan to use a USB connection please read the appropriate subsection in its entirety You can skip this section if your UPS has a serial RS232 C or Ethernet interface or if you are not running one of the platforms listed above Linux USB Configuration Known Linux USB Issues Problem Linux 2 4 series kernels older than 2 4 22 RH 9 RHEL 3 do not bind the USB device to the proper driver This is evidenced by proc bus usb devices listing the UPS correctly but it will have driver none instead of driver hid This affects RHEL3 among others Workaround Upgrade linux kernel to 2 4 22 or higher Alternately you apply the linux 2 4 20 killpower patch and linux 2 4 20 USB reject patch patches to your kernel and rebuild it These patches can be found in the examples directory in the apcupsd source distribution Problem Mandrake 10 0 and 10 1 systems with high security mode enabled running kernel secure kernel use static device nodes but still assign USB minor numbers dynamically This is evidenced by hiddev0 USB HID v1 10 Device instead of hiddev96 in dmesg log Workaround Boot standard kernel instead of kernel secure or disable CONFIG_USB_ DYNAMIC MINORS and rebuild kernel secure Problem USB driver linux usb c fails to compile reporting errors about HID_MAX_USAGES undefined This is due to a defect in the linux kernel hiddev h header
17. If you are in doubt delete it then rerun the make install to ensure that you haven t deleted anything needed by the new apcupsd Please note that the files specified above assume the default installation locations As a final check that the make install went well you should check your halt script in etc rc d on SUSE systems and in etc rc d init d on Red Hat systems to see that the appropriate lines have been inserted in the correct place Modification of the halt script is important so that at the end of the shutdown procedure apcupsd will be called again to command the UPS to turn off the power This should only be done in a power failure situation as indicated by the presence of the etc powerfail file and is necessary if you want your machine to automatically be restarted when the power returns On a Red Hat system the lines containing the apcupsd should be inserted just before the final halt command Remount read only anything that s left mounted echo Remounting remaining filesystems if any readonly MOUTate eawke exo sum orintinos le whales reac inme Eco mount n o ro remount line done See if this is a powerfail situation if f etc apcupsd powerfail then echo echo APCUPSD will now power off the UPS echo etc apcupsd apccontrol killpower echo echo Please ensure that the UPS has powered off before rebooting echo Otherwise the UPS may cut the power during the reboot echo iii
18. In general each of these directives is required except that the DEVICE directive is ignored for UPSCABLE ether and not required for UPSCABLE usb UPSTYPE driver The name of a driver Should be one of dumb apcsmart net usb pcnet snmp or test This describes your interface type The UPSTYPE directive can be defined during installation by using the with upstype option of the configure program UPSCABLE cable Defines the type of cable connecting the UPS to your computer Possible generic choices for lt cable gt are simple smart ether usb Or a specific cable model number may be used 940 0119A 940 0127A 940 0128A 940 0020B 940 0020C 940 0023A 940 0024B 940 0024C 940 1524C 940 0024G 940 0095A 940 0095B 940 0095C M 04 02 2000 The with upscable option of configure canbe used to set a default for this directive during the your build DEVICE device Specify which device is used for UPS communications For serial ports it is usually something like dev ttySO For USB ports you may leave the name of the device blank no specification and apcupsd will automatically search the standard locations for the UPS Normally the configure program will set an appropriate default value You may also specify the with serial dev option of the configure program to set this directive at build time If you have specified UPSTYPE net then the device name to be specified consists of hostname port where the
19. LINEV 6 232 7 Wodlies MAXLINEV 236 6 Volts MINLINEV 231 4 Volts I EINIIRIHO 8 Eo ONORA OUDE ULV 43 20a7 ea Violktes LOADPCT 11 4 Percent Load Capacity BA EV s Alo T Volers BCHARGE 100 0 Percent MBATTCHG 5 Percent TIMELEFT 112 0 Minutes MINTIMEL 3 Minutes SENSE Low DWAKE 060 Seconds DSHUTD 180 Seconds LOTRANS g 204 0 yolrs HITRANS s 25350 Wolies REMEC 050 0 Percent STATFLAG 0x08 Status Flag STATUS ONLINE I TEMP gt BS 2 Minicereneul ALARMDEL Low Battery LASTXFER U command or Self Test SELFTES B INO STESTI 8 OSG DLOWBATT 02 Minutes DIPSW s OOO Dia Sake Cin REG1 Ox00 Register 1 REG2 0x00 Register 2 REG3 0x00 Register 3 MANDATE s 017 05 99 SERIALNO GS9902009459 BATTDATE 01 05 99 NOMO UAE eee S00 NOMBATTV 24 0 HUMIDITY N A AMBTEMP N A EXTBATTS 0 BADBATTS N A FIRMWARE 60 11 1 APCMODEL IWI NID AVRIC 88 Iie Dee S Ias34e33 Caw 1999 For the various smaller cheaper APC USB UPSes such as the CS ES you will get much of the information that is presented above but not all of it For example you will not get MAXLINEV MINLINEV LINEFREQ and in particular the LOADPCT will be zero when you are running on mains LOADPCT will display when the UPS is on batteries You must remember that the non SmartUPSes are much simpler and less expensive and therefore produce less inf
20. Server Client Configuration Using the Net Driver NIS Network Information Server mode allows for communication between instances of apcupsd running on different hosts Only one of those hosts the server needs to talk to the UPS directly The others clients obtain information about the state of the UPS by querying the server NIS is not related to Sun s NIS YP services NIS clients and servers require that apcupsd be compiled with the Net Driver enable net This is typically enabled by default The NIS server is connected to the UPS and should be configured exactly as a standalone configuration but with NETSERVER on In all other respects the server should be configured in standalone mode You may also set the NIS server specific options NISIP to restrict which IP address of the server which apcupsd listens on The default 0 0 0 0 means to list on all of the server host s IP addresses NISPORT default 3551 to set which TCP port the server listens on and EVENTSFILE and EVENTSFILEMAX to provide information about the last few events to clients You may also need to modify your firewall rules on the server s host to allow traffic to the NISPORT For the NIS client computer you will have a configuration that looks something like what follows What is important is that you get the information from an UPSCABLE ether with UPSTYPE net over the network and you must specify the address of a NIS server using DEVIC
21. USB or a serial port If you have an old style voltage signaling UPS please skip to the next section Simulated Power Fail Test When apcupsd detects a problem it generates an EVENT which consists of sending a message to the system log then invoking the apccontrol script normally in etc acpupsd apccontrol to handle the event In order to create an event remove the serial port plug from the back of your computer or from the back of the UPS Within 6 seconds apcupsd should detect the lack of serial port communications and broadcast a wall message indicating that the serial port communications was lost Warning communications lost with UPS lost At the same time it sends the same message to the system log and to the temporary EVENTS file etc apcupsd apcupsd events Plug the serial port plug back into your computer and within about 12 seconds apcupsd should reestablish communications and broadcast and log the following message Communications with UPS restored If these messages are logged but not broadcast either you have your mesg permission set to no see man wall or man mesg or there is a problem with apccontrol If you are running a window manager such as GNOME and don t have a console window open you may not receive the wall messages However you should find them in your system log file normally var log messages and in the temporary EVENTS file etc apcupsd apcupsd events For example to observe these events
22. and port only by adding a line like this to your kernel config file ugen eve w pori L ielkeveis 1 The flags 1 forces the ugen to attach instead of anything else detected there Configure and build that kernel as per the references below and your UPS will now attach as a ugen device when plugged into that port Don t forget to cd dev and MAKEDEV ugen1 and 2 and so on if you have more than one generic usb device on your system OpenBSD you will lose use of USB keyboard and mouse Disable uhidev ums wsmouse ukbd wskbd uhid Enable ugen For detailed information on rebuilding your kernel consult these references FreeBSD http www freebsd org doc en_US IS08859 1 books handbook kernelconfig html NetBSD http www netbsd org guide en chap kernel html OpenBSD http Awww openbsd org faq faq5 html Building Verifying Device Detection and Driver After building a properly configured kernel reboot into that kernel and plug in your UPS USB cable You should see a dmesg log message like the following ugen0 American Power Conversion Back UPS RS 1500 FW 8 g6 D USB FW g6 rev 1 10 1 06 addr 2 Note that the ugen driver is called out If you see uhid instead it probably means you did not properly disable the uhid driver when you compiled your kernel or perhaps you re not running the new kernel You can also check with usbdevs d to get a list of USB devices recognized by the system as well as the dr
23. be built by a regular user but you must make a few changes on your system to do this If you are building on your own system then the simplest method is to add write permissions for all to the build directory usr src redhat To accomplish this execute one of the following commands as root depending on your distribution RedHat SUSE or Mandriva respectively Chino cle Raa T77 usr sre recneit chmod R 777 usr src packages chmod R 777 usr src RPM If you are working on a shared system where you can not use the method above then you need to recreate the usr src redhat or other directory tree with all of it s subdirectories inside your home directory Then create a file named cpmmacros in your home directory or edit the file if it already exists and add the following line topdir home myuser redhat Credits The success of apcupsd is due to the many people that helped in development testing and in many other ways Thank all the developers that worked hard to make APCUPSD one of the best piece of software for UPS management Contributors Current Code Maintainer and Project Manager Adam Kropelin akropel1 rochester rr com RPM Packager D Scott Barninger CGI and HTML fixer William King wrking dadaboom com Former Project Manager Kern Sibbald kern sibbald com Project Starter and Former Code Maintainer Andre Hedrick andre linux ide org Former Code Maintainer and Project Manager Riccardo Facchetti riccardo ma
24. cannot insert the appropriate code in the halt script when you start apcupsd normally from the etc rc d init d apcupsd script use the kill on powerfail option This will cause apcupsd to program the UPS to shutoff the power just before it apcupsd does the system shutdown Please note that this is not the most ideal solution Read on to understand why A very important consideration is that you must set the EEPROM in your UPS so that it waits a sufficient time for the system to halt before it shuts off the UPS power When using a USB connection apcupsd automatically sets this value to 60 seconds When using a serial connection to a SmartUPS you must configure the value in the UPS EEPROM by hand using apctest Shutdown Problems Obviously if your halt script is not properly modified apcupsd will not be able to shut off the power to the UPS and if the power returns before the batteries are exhausted your system will not automatically reboot In any case your machine should have been cleanly shut down Master Slave Shutdown In master slave configurations however the master cannot be 100 percent sure that the slaves have all shutdown before it performs the power off To avoid this situation be sure to configure any slaves clients to shut down before the master by setting different TIMEOUT BATTERYLEVEL Or MINUTES parameters in the config file Also on a slave machine you do not want to use the modified hal
25. certifications according to APC If you do decide to use third party replacement batteries please do not choose the cheapest available generic SLA batteries These batteries will almost without exception not last as long as brand name batteries and will need replacing within 12 18 months instead of 3 5 years Even when using brand name replacement batteries make sure that you choose the UPS version aka standby which may cost slightly more but which will last significantly longer in typical UPS usage long periods of standby punctuated with infrequent deep discharges The brands of battery found in genuine APC battery cartridges have included Panasonic and B amp B Battery aka Best amp Best Battery and BB Battery Yuasa aka Genesis is also a recommended brand albeit a bit on the pricey side Note When substituting a third party battery with a higher capacity than the original make sure that it still physically fits in the UPS casing If the battery does not fit do not be tempted to install it externally The UPS may not be able to charge it in a timely manner and or it may damage the UPS charging circuitry without appropriate modifications which are generally beyond an end user s capability Battery Installation Although you can do a hot swap of your batteries while the computer and any other connected equipment is running it may not be very satisfactory because the UPS will not always detect that the batteries have been swa
26. disabled ANNOYDELAY time in seconds Specify delay time in seconds before apcupsd begins requesting logged in users to get off the system during a power failure This timer starts only after the UPS is running on batteries This timer is reset when the power returns The default is 60 seconds Thus the first warning to log off the system occurs after 60 seconds on batteries assuming that NOLOGON is not set to disable NOLOGON disable timeout percent minutes always Specifies when apcupsd should prevent user logins The type specified allows you define the point when apcupsd will create the nologin file and thus when user logins are prohibited Once the nologin file is created normal users are prevented from logging in Control of when this file is created is important for allowing systems with big UPSes to run as normally until the system administrator determines the need for preventing user logins The feature also allows the system administrator to hold the ANNOY factor until the nologin file is created The default is always disable if no NOLOGON directive is specified The nologin file will be created in the directory specified by the NOLOGINDIR directive described below As far as can tell the only useful types are disable and always since the difference in the time when the logout warning is given and shutdown occurs for the other types is very short KES disable prevents apcupsd from creating the nologin file Con
27. file on 2 6 5 and higher kernels Workaround Upgrade to apcupsd 3 10 14 or higher These versions contain a workaround for the defect Problem On some systems such as Slackware 10 0 no USB devices will show up see the next section Workaround Add the following to rc local mount t usbdevfs none proc bus usb Problem 2 6 kernels use udev and some distributions to not configure it to automatically create dev usb hiddev as they should causing apcupsd to fail to locate the UPS Workaround Edit the file etc udev rules d 50 udev rules and add the following KERNEL hiddev NAME usb hiddevsn More details are provided in the following section Verifying Device Detection and Driver To make sure that your USB subsystem can see the UPS just do this from a shell prompt cat proc bus usb devices This information is updated by the kernel whenever a device is plugged in or unplugged irrespective of whether apcupsd is running or not It contains details on all the USB devices in your system including hubs internal and external input devices and UPSes You should get some output back that includes something like this featuring a BackUPS RS 1000 T Bus 02 Lev 01 Prnt 01 Port 00 Cnt 01 Dev 3 Spd 1 5 MxCh 0 D Ver 1 10 Cls 00 gt ifc Sub 00 Prot 00 MxPS 8 Cfgs 1 P Vendor 051d ProdID 0002 Rev 1 06 S Manufacturer American Power Conversion See roduict
28. fully supported and by following the standard installation instructions given above you should experience few or no problems SUSE SUSE systems are fully supported and by following the standard installation instructions given above you should experience few or no problems Sun Solaris Please read this before attempting to compile or install the beta software It contains important information that will make your efforts easier Before running configure please be sure that you do not have usr ucb on your path This may cause the configure to choose the wrong shutdown program If configure detects that usr usb is on your path it will print a warning message Please follow the advice to avoid shutdown problems Your normal UNIX user ID must own the source tree directories and you must have the normal development tools in your path This includes make the compiler the M4 preprocessor the linker and ar or ranlib If the user you are logged in as can compile and link a C program from a source file then you have all the required tools available You will want to install the executables in a directory that remains mounted during the shutdown Solaris will unmount almost everything except the root directories Since the ability to power the UPS off requires access to the executable programs they need to be in a directory that will never be unmounted And since they should also be in a directory that normal users cannot get into s
29. hostname is the fully qualified name or IP address of the host NIS server and the port optional is the port to use to contact the server If you specified UPSTYPE snmp then the device name becomes hostname vendor community Please see the Support for SNMP UPSes chapter in this manual for more details POLLTIME time in seconds The interval in seconds at which apcupsd polls the UPS for status This rate is automatically set to 1 second if the UPS goes on batteries and reset to your specified value when the mains power returns This setting applies both to directly attached UPSes UPSTYPE apcsmart usb dumb and networked UPSes UPSTYPE net snmp Lowering this setting will improve apcupsd s responsiveness to certain events at the cost of higher CPU utilization The default of 60 is appropriate for most situations This directive was formerly known as NETTIME LOCKFILE path to lockfile This option tells aocupsd where to create a lockfile for the USB or serial port in the specified directory This is important to keep two programs from reading or writing the port at the same time Please note that although the directive name is LOCKFILE you are actually specifying the lock file path apcupsd automatically appends the name of the device when creating the file On most systems this directive is automatically set by the configure program You may also explicitly set it during the build process by using the with lock dir option of the conf
30. in the temporary EVENTS file you might do a tail f etc apcupsd apcupsd events Note if you have installed from the RPM the proper events file may be var log apcupsd events You can find the actual filename by checking your apcupsd conf file before running the test If you do not observe these messages you should correct this problem before proceeding with additional tests Simulated Power Fail Test At this point you should verify that in the event of a power fail apcupsd properly calls apccontrol This test is appropriate for all models of UPSes smart or dumb To avoid the possibility that apcupsd might shut down your system locate where apccontrol resides on your system normally etc apcupsd apccontrol Move this script to another location e g apccontrol save and replace it with the script found in examples safe apccontrol When that is done ensure that your UPS battery is fully charged and that you have at least 5 minutes of remaining runtime on the batteries This can be done by examining the values of the BATTCHG and TIMELEFT variables in the printout of apcaccess status Athough this should not be necessary as an extra precaution you can shutdown your machine remove the plug from the UPS you are testing and plug your machine into another UPS or directly into the wall Doing so will ensure that the UPS doesn t cut the power to your machine at a bad time Remember at the end of the testing to plug your
31. insures that the UPS will not restore power to its loads until it has recharged it battery to a prescribed percentage This parameter should be set to a value greater than value that the APCUPSD daemons configured BATTERYLEVEL shutdown of any connected servers This will ensure that when the UPS restores power any additional power failures will successfully re trigger a server shutdown Configure Event Trap Receivers Requires apcupsd 3 12 0 and later By default APCUPSD will poll the SNMP UPS card once per minute In this case server notification of UPS alarms could potentially be delayed one minute Event trap catching mitigates this shortcoming Any UPS alarms are instantly sent to prescribe servers connected SNMP UPS These servers are referred to as Event Trap Receivers The SNMP UPS card can be configure to send event traps to a maximum of four receivers that will catch these events Event trap receivers IP address can be set using a telnet terminal or web browser interface Also be aware that servers configured to be Event Trap Receivers should have static IP set Severs obtaining IPs from DHCP server will not catch instantaneous Events if the IP address changes from the address set in the SNMP UPS Connecting APCUPSD to a SNMP UPS The previous sections describe configuration of the actual SNMP card The remaining sections describe configuration of the APCUPSD to communicate using SNMP Protocol To enable the SNMP support it is
32. it is a good sign that apcupsd is working Assuming that the output looks reasonable check the following variables LINEV This is the line voltage and it should be a value that is appropriate for your equipment In the USA it is typically about 120 Volts while in Europe it is about 220 Volts BATTV Unless you have additional battery packs this should be near 24 Volts plus or minus 5 Volts STATUS This is the status of the UPS and it should normally be ONLINE A very disturbing tendance is for some of the newer Mar 2004 RS and ES UPSes to have no Voltage information This is an annoying bug but not serious On the other hand some of those UPSes now have no battery charge information BCHARGE If BCHARGE is zero in your listing and you are running a Smart or a USB UPS then you will have to set the BATTERYLEVEL directive in your apcupsd conf file to 1 If you see a message to the effect of APCACCESS FATAL ERROR in apcaccess c at line 336 tcp_open cannot connect to server localhost on port 3551 It means that you have probably not enabled the Network Information Server in your configuration file for apcaccess to work This is done by setting NETSERVER and NISPORT in your apcupsd conf file as shown above Communications Test At this point you should ensure that apcupsd is handling the connection to the UPS correctly This test assumes you have a UPS that speaks apcsmart protocol over either
33. make 4 Figure out if you have one of the easy setups If you have a USB UPS and a supported operating system and you want to use one UPS with one computer that s an easy setup APC supplies the cable needed to talk with that UPS along with the UPS All you need to do is check that your USB subsystem is working see USB Configuration if so you can go to the build and install step 5 If you have a UPS designed to communicate via SNMP over Ethernet that is also a relatively easy installation Details are provided in Support for SNMP UPSes 6 If you have a UPS that communicates via an RS232C serial interface and it is a SmartUPS then things are relatively simple otherwise your life is about to get interesting 1 If you have a vendor supplied cable find out what cable type you have by looking on the flat ends of the cable for a number such as 940 0020A stamped in the plastic 2 If you don t have a vendor supplied cable or your type is not supported you may have to build one yourself see Cables Here is hoping you are good with a soldering iron 7 Now you are ready to read the Building and Installing see Building and Installing apcupsd section of the manual and follow those directions If you are installing from an RPM or some other form of binary package this step will probably consist of executing a single command 8 Tweak your etc apcupsd apcupsd conf file as necessary Often it will not be 9 Change the BIOS settings
34. mind we believe that you will find that a lot of very valuable work has been already done to make your installation much easier and probably totally automatic Below you will find a list of operating systems for which we have received installation files e Debian see Debian e FreeBSD see FreeBSD e HPUX see HPUX e NetBSD see NetBSD e Mac OS X Darwin see Mac OS X Darwin e OpenBSD see OpenBSD e Red Hat see Red Hat Systems e Slackware see Slackware e SUSE see SUSE e Solaris see Sun Solaris unknown see Unknown System e Win32 see Windows Systems Debian This port is complete and is being used by several users Since Debian build and install procedures are somewhat particular we have put the extra Debian information into the following two subdirectories platforms debian examples and platforms debian packageinfo You can also find the official Debian packages on the Debian site at https packages debian org stable apcupsd https packages debian org testing apcupsd https packages debian org unstable apcupsd FreeBSD This port is complete and is being used by several users You will need to install and use GNU make aka gmake instead of the BSD make supplied with the system On the FreeBSD OS there is no known way for a user program to get control when all the disks are synced This is needed for apcupsd to be able to issue the killpower command to the UPS so that the UPS shuts
35. multiple UPSes in use you may wish to consolidate the monitoring of all of these UPSes onto a single machine which we shall call the UPS server Generally one of the UPSes is powering the UPS server itself and possibly other machines as well The remaining UPSes are powering additional machines Apcupsd can work quite well in this environment by running one instance of apcupsd on the UPS server for each UPS to be controlled That is you install a single copy of apcupsd but launch it multiple times using different configuration files and scripts Older versions of apcupsd required you to actually compile the daemon multiple times with different configure options This is no longer required as all necessary adjustments can be made in apcupsd conf Additionally you will run one instance of apcupsd on each of the machines you wish to be shut down You will configure each of these apcupsd s to use the net driver to read UPS status from the proper instance of apcupsd on the UPS server See NIS Server Client Configuration Using the Net Driver for more information on the net driver and setting up net clients Multiple UPS Example There are many ways one could set up multiple apcupsd instances Here will present the way have used with great success on Red Hat Linux have two apcupsd conf files this is for a 2 UPS setup easily expandable to N adk0212 mail apcupsd 1s l etc apcupsd conf GW ae AC OL Looe 11799 Awo OOS SOM
36. recommend that you find a better cable because all APC UPSes support more than just On Battery Please note that we are not sure the following diagram is correct This diagram is for informational purposes and may not be complete We don t recommend that use it to build you build one yourself APC Part 940 0023A Signal Computer UPS DB9F DB9M DCD 1 2 3 3K ohm TxD 3 HEHH l DTR 4 GND 5 4 k 9 940 0024C Cable Wiring Onebabecry Ground Common Supported SmartUPS all models with DB9 serial port Models If you wish to build the standard cable furnished by APC 940 0024C use the following diagram APC Part 940 0024C Signal Computer WEIS DB9OF DB9M RxD 2 2 TxD 3 1 DCD i ane DTR 4 aa GND 5 9 RTS 7 Z CTS 8 om 940 0095A Cable Wiring Supported APC BackUPS Pro PNP Models TxD Send RxD Receive Ground Contributed Chris Hanson cph at zurich ai mit edu by This is the definitive wiring diagram for the 940 0095A cable submitted by Chris Hanson who disassembled the original cable destroying it in the process He then built one from his diagram and it works perfectly APC Pant 940 0095A UES mene Computer end 47k 47k BATTERY LOW 5 gt R1 R2 lt DTR DSR CTS 4 6 8 amp eee 2N3906 PNP ve smc DCD L Low Batt in Zl Ws B 4 7k SHUTDOWN 1 gt te R4 ee lt lt ESD
37. see Arranging for Reboot on Power Up on your computer so that boots up every time it gets power This is not the default on most systems 10 To verify that your UPS is communicating with your computer and will do the right thing when the power goes out read and follow the instructions in the Testing see Testing Apcupsd section 11 If you run into problems check the apcupsd users email list archive for similar problems This is an excellent resource with answers to all sorts of questions See http sourceforge net mailarchive forum php forum_name apcupsd users 12 If you still need help send a message to the apcupsd users email list apcupsd users lists sourceforge net describing your problem what version of apcupsd you are using what operating system you are using and anything else you think might be helpful 13 Read the manual section on Monitoring and Tuning your UPS Supported Operating Systems apcupsd supports many UNIX like operating systems as well as several variants of Windows Due to lack of API standardization USB support is not available on every platform See Platform Support below for details In general it is recommended to obtain a prebuilt package for your platform Given how apcupsd must integrate into the shutdown mechanism of the operating system and the rate at which such mechanisms are changed by vendors the platform ports in the apcupsd tree may become out of date In some cases binary packages a
38. the m option to set them when creating the pipe Then you modify your etc syslog conf file to direct the appropriate levels of messages where you want them To accomplish the above my syslog conf file looks like exclude all apcupsd info by default info local0 none var log messages Everything for apcupsd goes here local0 info local0 notice var log apcupsd data local0 notice local0 warn var log apcupsd status local0O warn var log apcupsd events local0 warn var log messages The Windows Version of apcupsd The Windows version of apcupsd has been tested on Win95 Win98 WinMe WinNT WinXP and Win2000 systems This version of apcupsd has been built to run natively on Windows no Cygwin or other emulation layer needed Even though the Win32 version of apcupsd is a port that relies on many Unix features it is just the same a true Windows program When running it is perfectly integrated with Windows and displays its icon in the system icon tray and provides a system tray menu to obtain additional information on how apcupsd is running status and events dialog boxes Once installed apcupsd normally runs as a system service This means that it is immediately started by the operating system when the system is booted and runs in the background even if there is no user logged into the system Installing Apcupsd on Windows Normally you will install the Windows version of apcupsd from the binaries Star
39. this signal is normally low but goes high when the UPS switches to batteries 3 gt Mains down line fail See Note 1 below 5 Low battery S Note 1 below 6 gt Inverse of mains down signal See Note 2 below 7 lt Turn on off power only on advanced UPSes only Note 1 these two lines are normally open but close when the appropriate signal is triggered In fact they are open collector outputs which are rated for a maximum of 40VDC and 25 mA Thus the 4 7K ohm resistor used in the Custom Simple cable works quite well Note 2 the same as note 1 except that the line is normally closed and opens when the line voltage fails The Back UPS Office 500 signals The Back UPS Office UPS has a telephone type jack as output which looks like the following Looking at the end of the connector 6S 4a 2 1 It appears that the signals work as follows UPS Signal meaning 1 brown lt Shutdown when set by computer for 1 5 seconds 2 black On battery power 3 blue gt Low battery 4 red Signal ground 5 yellow lt Begin signalling on other pins 6 none none Analyses of APC Cables 940 0020B Cable Wiring Supported Simple Signaling such as BackUPS Models Contributed Lazar M Fleysher by Although we do not know what the black box semiconductor contains we believe that we understand its operation many thanks to Lazar M Fleysher for working this out This cable can only be used on
40. usb flag to configure After building install Apcupsd as root using make install then perform a reconfigure boot reboot r During installation Apcupsd will automatically configure your USB subsystem to attach APC USB devices to the ugen driver This is a critical step and must be completed by a reconfigure boot Note that the USB config changes will be reversed if you remove Apcupsd using make uninstall Verifying Device Detection and Driver After installing Apcupsd as described above and performing a reconfigure boot plug in your UPS USB cable You should see a series of dmesg log messages similar to the following Dec 5 17 50 50 sunblade usba ID 912658 kern info USB 1 10 device usb51d 2 operating at low speed USB 1 x on USB 1 10 root hub input 4 ugen0 at bus address 3 Dec 5 17 50 50 sunblade usba ID 349649 kern info American Power Conversion Smart UPS 1000 FW 600 1 D USB FW 1 2 AS0127232356 Dec 5 17 50 50 sunblade genunix ID 936769 kern info ugen0 is pci 1f 0 usb c 3 input 4 Dec 5 17 50 50 sunblade genunix ID 408114 kern info pci 1f 0 usb c 3 input 4 ugen0 online Note that the ugen driver is called out If you do not see any dmesg entries related to your UPS ensure that it is turned on and that the USB cable is connected at both ends Also verify that you installed Apcupsd as root using the make install command and that you performed a reconfigure boot afterward Device Nodes Apcupsd communi
41. via the serial port but was unable to do so Before continuing you must correct this problem Some of the possible sources of the problem are e You have not configured the correct serial port name on the DEVICE directive in your apcupsd configuration file e The serial port that you have chosen has logins enabled You must disable logins on that port otherwise the system prevents apcupsd from using it Normally the file etc inittab specifies the ports for which a getty process is started on Sun machines the serial port program equivalent to getty is called ttymon You must disable this for the port that you wish to use e Make sure you are doing your testing as root otherwise you may have permissions problems accessing the serial port e You may have cabling problems either with an incorrect cable or the incorrect cable specification directive in the configuration file e You may have a problem with the etc apcupsd acpupsd conf file For example check that you have specified the correct type of UPS and the correct networking directives For more details see the After Installation section e If you have a SmartUPS 5000 RM 15U or similar model that comes with a Web SNMP management card in one of the Smart Slots this card may interfere with the serial port operation If you are having problems please remove this card and try again Supposedly V3 0 of the card firmware has been corrected to properly release the ser
42. voltage signalling UPSes and provides the On Battery signal as well as kill UPS power Most recent evidence Lazar s analysis indicates that this cable under the right conditions may provide the Low Battery signal This is yet to be confirmed This diagram is for informational purposes and may not be complete We don t recommend that use it to build you build one yourself APC Part 940 0020B Signal Computer WEIS DB9OF DB9M GRS 8 2 On Battery DTR 4 1 Kill power GND 5 A 4 Ground D gt 9 COMON DCD i AI 5 Low Battery AAS RTS 7 pwolololy a semi conductor 940 0020C Cable Wiring Supported Simple Signaling such as BackUPS Models This cable can only be used on voltage signalling UPSes and provides the On Battery signal the Low Battery signal as well as kill UPS power You may specify UPSCABLE 940 0020C This diagram is for informational purposes and may not be complete We don t recommend that use it to build you build one yourself APC Part 940 0020C Signal Computer UPS DB9OF DB9M CIS 8 2 On Battery DER 4 1 Kill power GND 5 x 4 Ground s 9 Common RES PES a V8 5 Onm 5 Low Battery or semi conductor 940 0023A Cable Wiring Supported Simple Signaling such as BackUPS Models This cable can only be used on voltage signalling UPSes and apparently only provides the On Battery signal AS a consequence this cable is pretty much useless and we
43. we need to modify a system script This script is sbin rcO We do not have access to every version of Solaris but we believe this file will be almost identical on every version Please let us know if this is not true At the very end of the sbin rcO script you should find lines just like the following unmount file systems usr var and var adm are not unmounted by umountall because they are mounted by rcS for single user mode rather than mountall If this is changed mountall umountall and rcS should also change sbin umountall sbin umount var adm gt dev null 2 gt amp 1 sbin umount var gt dev null 2 gt amp 1 sbin umount usr gt dev null 2 gt amp 1 echo The system is down We need to insert the following lines just before the last echo see if this is a powerfail situation ii erc apcupsci powera Je then echo echo APCUPSD will power off the UPS echo etc apcupsd apecontrol killpower ECO echo Please ensure that the UPS has powered off before rebooting echo Otherwise the UPS may cut the power during the reboot echo ia We have included these lines in a file called rcO solaris in the distributions sun subdirectory of the source tree You can cut and paste them into the sbin rcO file at the correct place or yank and put them using vi or any other editor Note that you must be root to edit this file You must be absolutely sure you have them in t
44. will act as network clients which poll the server for information about the UPS Note that NIS is not related to Sun s directory service also called NIS or Yellow Pages The third configuration is where a single computer controls multiple UPSes In this case there are several instances of apcupsd on the same computer each controlling a different UPS One instance of apcupsd will run in standalone mode and the other instance will normally run in network mode This type of configuration may be appropriate for large server farms that use one dedicated machine for monitoring and diagnostics Here is a diagram that summarizes the possibilities Configuration types Stand alone configuration Computer running serial or USB cable apesusd in ower standalone mode m Typical Master Slave Configuration Computer A running serial or USB cable apcsusd in master mode Ethernet Computer B running apesusd in ower slave mode P Ethernet Computer C running apesusd in slave mode Multi UPS configuration serial or USB cable Computer A running apcs usd a in slave mode Ethernet serial or USB cable Computer B running apcsusd ower in slave mode UPS UPS UPS UPS If you decide to set up one of these more complex configurations see the dedicated section on that particular configuration USB Configuration Apcupsd supports USB connections on all major operating systems Linux
45. you can do for all UPS models before doing the Full Power Down Test First modify the etc apcupsd apccontrol file so that in the killpower case the line that re executes apcupsd with the killpower option is commented out The original line probably looks something like S APCUPSD killpower when it is commented out it looks like S APCUPSD killpower Now when you pull the power plug and either the timer expires or the batteries are exhausted see the next section for more details the system should be fully shutdown After performing this test please be sure to restore etc apcupsd apccontrol to its previous state Full Power Down Test To complete the testing you should do a power fail shutdown of your system This test is applicable to all UPS models Please do a backup of your system or take other precautions before attempting this to avoid the possibility of lost data due to a problem I have been through this at least 10 times and never once had problems but we all know that someday something will go wrong Before proceeding please ensure that your halt script or the equivalent has been properly updated by the install process to contain the logic to call apcupsd killpower Of apccontrol killpower when it detects a power failure situation the presence of a etc powerfail file See the Building and Installing apcupsd section of this manual or the README files for additional details about the halt modifications necessar
46. 1 All bits are valid on the Matrix UPS SmartUPS models only support bits 6 and 7 Other models do not respond Bit Meaning when bit 1 0 In wakeup mode typically lasts lt 2s 1 In bypass mode due to internal fault see Register 2 or Register 3 2 Going to bypass mode due to command 3 In bypass mode due to command 4 Returning from bypass mode 5 In bypass mode due to manual bypass control 6 Ready to power load on user command 7 Ready to power load on user command or return of line power Register 2 Matrix UPS models report bits 0 5 SmartUPS models only support bits 4 6 SmartUPS v s and BackUPS Pro report bits 4 6 7 Unused bits are set to 0 Other models do not respond Bit Meaning when bit 1 0 Fan failure in electronics UPS in bypass Fan failure in isolation unit Bypass supply failure Output voltage select failure UPS in bypass DC imbalance UPS in bypass Battery is disconnected Relay fault in SmartTrim or SmartBoost NI OD on A Ol N Bad output voltage Register 3 All bits are valid on the Matrix UPS and 3rd generation SmartUPS models SmartUPS v s and BackUPS Pro models report bits 0 5 All others report 0 4 State change of bits 1 2 5 6 7 are reported asynchronously with and messages Bit Meaning when bit 1 Output unpowered due to shutdown by low battery Unable to transfer to battery due to over
47. 1970s the technology moved to Absorbed Glass Mat AGM where the separators between the lead plates are made of highly porous micro fine glass fibres which absorb and immobilise the acid and prevent it from spilling A crack or hole in the casing of a VRLA battery using AGM technology will not result in a measurable electrolyte spill Spill containment with VRLA batteries is therefore not meaningful or appropriate AGM has became the preferred VRLA technology for use in standby or float applications and is used in UPSes in the telecommunications power and many other mission critical industries where the power supply must not be interrupted APC UPSes use VRLA batteries VRLA batteries are designed to recombine hydrogen and oxygen and emit only extremely small amounts of hydrogen under normal operating conditions Normal room ventilation is sufficient to remove any hydrogen so special ventilation is not required Battery Life Most brand name UPS batteries should last 3 5 years Some APC Back UPS models may have a shorter battery life expectancy Refer to the user s manual of your APC Back UPS to determine the exact battery life expectancy or contact APC Technical Support Below are some APC guidelines for ensuring optimum battery life expectancy 1 Make sure that you keep your APC UPS in a cool dry location with plenty of ventilation Ideally the temperature where your UPS is kept should not exceed 75 Deg F 24 Deg C Also for ventilation
48. 34 239 22A u A 4 3 103 110 112 11A u T 4 3 253 257 26 265 1 D 4 3 106 105 LOO 097 L M 4 3 L77 L72 169 Lez 1 A 4 3 092 090 088 086 1 T 4 3 208 204 200 196 e 4 4 2 00 1S 560 0 D i 3 LS J AL 3 100 It il 3 230 2A0 220 225 M 1 5 208 5 4 4 1 H M L L q 4 4 2 02 05 O7 10 p 4 4 3 020 180 300 600 k 4 4 1 0 T L N r 4 4 3 000 060 180 300 E 4 4 3 SSG ALG TRONE ORE CMD UPSlink Command u upper transfer voltage 1 lower transfer voltage e return threshold o output voltage Ss sensitivity p shutdown grace delay q low battery warning k alarm delay r wakeup delay E self test interval DFO 4 all countries D omestic I nternational A sia J apan M North America servers RSP Total number possible answers returned by a given CMD FSZ Max number of field positions to be filled FVL Values that are returned and legal Programming the UPS EEPROM There are at this time a maximum of 12 different values that can be programmed into the UPS EEPROM They are Command Meaning c The UPS Id or name x The last date the batteries were replaced u The Upper Transfer Voltage l The Lower Transfer Voltage e The Return Battery Charge Percentage o The Output Voltage when on Batteries s The Sensitivity to Line Quality p The Shutdown Grace Delay q The Low Battery Warning Delay k The Alarm Delay r The Wakeup Delay E The Automatic Self Test Interval
49. 8 of the female DB9 connector 3 Pin 8 on the female connector is also wired to pin 5 on the male DB9 connector Solder both ends 4 Solder the other pins pin 5 on the female DB9 to pin 4 on the male connector pin 1 on the female connector to pin 2 on the male connector and pin 7 on the female connector to pin 1 on the male connector 5 Double check your work We use the DTR pin 4 on the female connector as our 5 volts power for the circuit It is used as the Vcc pull up voltage for testing the outputs on any UPS by APC in voltage signalling mode This cable may not work on a BackUPS Pro if the default communications are in apcsmart mode This cable is also valid for use on a ShareUPS BASIC Port It is reported to work on SmartUPSes however the Smart Cable described above is preferred To have a better idea of what is going on inside apcupsd for the SIMPLE cable apcupsd reads three signals and sets three Reads CD which apcupsd uses for the On Battery signal when high CTS which apcupsd uses for the Battery Low signal when high RxD SR which apcupsd uses for the Line Down signal when high This signal isn t used for much Sets DTR which apcupsd sets when it detects a power failure generally 5 to 10 seconds after the CD signal goes high It clears this signal if the CD signal subsequently goes low i e power is restored TxD ST which apcupsd clears when it detects that the CD signal has gone low after havin
50. 9 OC 86 46 630 3 I SUA7501 04 B6 14 82 06 651 12 1 SUA750RMI2U OV BI SObe 82 86 G19 12 1 SUA1L500I1 09 wo 1s AL Oi 601 653 1 SUA1500RMI2U 08 B4 10 Al 8E GL o 3H SUA2200I1 0S ie L2 133 26 654 12 51 SUA2200RMI2U OF we di S1 A6 665 4 1 SUA2200XLI OA B7 OF m7 66 690 oa SUA3000RMI2U 04 B9 OF 70 AA 666 4 1 SUA3000RMXLI3U OA B6 OF 89 XX OOo Kn SUOL1000I 06 B6 1B A6 SUOL2000XL ODED MES 52 A655 51 SURT1O0OOXLI OA BB 19 A8 4E AR T SURT3000XLI 06 BG Or 56 ASO 5 Bo Ik SURT5000XLI 05 BA 15 96 SA ASN SURT7500XLI OS Be 20 97 63 SURT1O0OO0OOXLI 06 B8 19 AB 476 12 W SUM1500RMXLI2U OCRE SOD VAS 62 ANO 5 Bo I SUM3000RMXLI2U 03 B7 OD A5 6A She Sh a AE BP500AVR 26 Oe Pherae all The instructions for resetting the battery constant are as follows Shutdown the apcupsd daemon Run apctest Choose option 6 to enter terminal mode Enter Y UPS should respond SM Enter 1 one not el wait 4 seconds Enter 1 one not el UPS should respond PROG Enter 0 zero not oh UPS should respond with current constant oOo N OO A O N Write down the existing value so that if something goes wrong you can at least put it back to that value 9 Enter plus or minus to increment decrement the value 10 Enter R to reprogram constant value UPS should respond Bye 11 Enter Y UPS should respond SM 12 Enter 0 zero not oh UPS should respond with the new constant 13 Enter Esc to exit terminal mode 14 Choo
51. APC GPS Daemon APCUPSD User Manual Adam Kropelin Kern Sibbald Apcupsd is a UPS control system that permits orderly shutdown of your computer in the event of a power failure March 28 2014 23 31 53 This manual documents apcupsd version 3 14 x Copyright 2004 2014 Adam Kropelin Copyright 1999 2005 Kern Sibbald Copying and distribution of this file with or without modification are permitted in any medium without royalty provided the name Apcupsd the copyright notice and this notice are preserved Apcupsd source code is released under the GNU General Public License version 2 Please see the file COPYING in the main source directory For more information on the project please visit the main web site at http Awww apcupsd com Important Legal Disclaimer 6 How To Use This Manual 7 Basic User s Guide 7 Quick Start for Beginners 7 Supported Operating Systems 8 Platform Support 8 Supported UPSes and Cables 9 Choosing a Configuration Type 10 Configuration types 10 USB Configuration 12 Linux USB Configuration 12 Known Linux USB Issues 12 Verifying Device Detection and Driver 13 Device Nodes 14 Miscellaneous 16 BSD USB Configuration 16 Known BSD USB Issues 16 Platforms and Versions 16 Kernel Configuration 16 Verifying Device Detection and Driver 17 Device Nodes Windows USB Configuration Platforms and Versions USB Driver Installation Verifying Device Detection and Driver Solaris USB Configuration Platforms and Versi
52. ATUS log files The default is etc apcupsd This option simply sets the default of the appropriate path in the apcupsd conf file which can be changed at any later time This option allows you to specify where apcupsd will create the serial port lock file The default is system dependent but usually var lock This option simply sets the appropriate path in the apcupsd conf file which can be changed at any later time This option allows you to specify where apcupsd will create the powerfail file when a power failure occurs The default is system dependent but usually etc with serial dev device nam with nis port port with nisip ip address with net port port with upstype type with upscable cable disable install distdir This option allows you to specify where apcupsd will look for the serial device that talks to the UPS The default is system dependent but often dev ttySO This option simply sets the appropriate device name in the apcupsd conf file which can be changed at any later time This option allows you to specify what port apcupsd will use for the Network Information Server the CGI programs The default is system dependent but usually 3551 because that port has been officially assigned to apcupsd by the IANA This option simply sets the appropriate port in the apcupsd conf file which can be changed at any later time This option allows you to specify the value
53. BackURSMRS a O OOM EWE iG See DmUSE mR Wi Ss S SerialNumber JB0308036505 Cee Gellics I CEG 1 Atr a0 MxPwr 24mA TEE QO Alt 0 EPs 1 Cls 03 HID Sub 00 Prot 00 Driver hid The important things to check for are the s lines describing your UPS and and the I line showing what driver is handling it If on the 1 line Driver is listed as Driver none then you do not have the HID driver loaded or the driver did not attach to the UPS One common cause is having a Linux kernel older than 2 4 22 such as a stock RedHat 9 or RHEL 3 kernel If this is the case for your system please upgrade to at least kernel version 2 4 22 and try again If you are already running a 2 4 22 or higher kernel please read further for instructions for other possible courses of action Here is another example this time featuring a Back UPS 350 T Bus 01 Lev 01 Prnt 01 Port 00 Cnt 01 Dev 2 Spd 1 5 MxCh 0 D Ver 1 10 Cls 00 gt ifc Sub 00 Prot 00 MxPS 8 Cfgs 1 P Vendor 051d ProdID 0002 Rev 1 00 S Manufacturer American Power Conversion S T ErOdUCt BICk VRST OSOREN S2 ll USI IEN Tel S SerialNumber BB0115017954 C Ifs 1 Cfg 1 Atr a0 MxPwr 30mA I If 0 Alt 0 EPs 1 Cls 03 HID Sub 00 Prot 00 Driver hid E Ad 81 1I Atr 03 Int MxPS 8 Ivl 10ms In general if you see your UPS model in the s field which means Manufacturer Product and SerialNumber and you see Driver hid inthe I field you know the UPS has bee
54. E The client apcupsd will then poll the NIS server specified in DEVICE every POLLTIME seconds formerly NETTIME apcupsd conf vl 1 UPSCABLE ether UPSTYPE net OCKFILE var lock DEVICE server network address 3551 UPSCLASS standalone UPSMODE disable POLLTIME 10 The DEVICE is set to server address port where server address is the fully qualified domain name or IP address of the apcupsd NIS server and port is the NISPORT that the server is listening on The default is 3551 but older versions of apcupsd used port 7000 If you set POLLTIME too large your client may not see the change in state of the NIS server before the server has shutdown Normally you have at least 30 seconds of grace time between the time the NIS server decides to shutdown and the time it no longer responds Your slave must poll during this interval Any client run using the Net driver will shutdown when its own timers expire or when the NIS server shuts down whichever occurs first This means that if you want the slave to shutdown before the server you need only set BATTERYLEVEL MINUTES or TIMEOUT on the client for a faster shutdown than the values defined on the NIS server This can often be useful if the slave is less important than the master and you wish to reduce battery power consumption so that the master can remain up longer during a power outage NIS client
55. ELFTEST The results of the last self test and may have the following values e OK self test indicates good battery e BT self test failed due to insufficient battery capacity e NG self test failed due to overload e NO No results i e no self test performed in the last 5 minutes STESTI The interval in hours between automatic self tests STATFLAG Status flag English version is given by STATUS DIPSW The current dip switch settings on UPSes that have them REG1 The value from the UPS fault register 1 REG2 The value from the UPS fault register 2 REG3 The value from the UPS fault register 3 MANDATE The date the UPS was manufactured SERIALNO The UPS serial number BATTDATE The date that batteries were last replaced NOMOUTV The output voltage that the UPS will attempt to supply when on battery power NOMINV The input voltage that the UPS is configured to expect NOMBATTV The nominal battery voltage NOMPOWER The maximum power in Watts that the UPS is designed to supply HUMIDITY The humidity as measured by the UPS AMBTEMP The ambient temperature as measured by the UPS EXTBATTS The number of external batteries as defined by the user A correct number here helps the UPS compute the remaining runtime more accurately BADBATTS The number of bad battery packs FIRMWARE The firmware revision number as reported by the UPS APCMODEL The old APC model identification code END APC The time and date that the STATUS record wa
56. However normally you will want apcupsd started automatically when your system boots On some systems with installation support e g SUSE and Red Hat the installation procedure will create a script file that you will be automatically invoked when your system reboots On other systems you will have to invoke apcupsd from your rc local script On Red Hat systems this script file that automatically invokes apcupsd on system start and stops is etc re d init d apcupsd To start apcupsd manually as you will probably do immediately following the installation enter the following cise re C init Capeu Stare To understand how this file is automatically invoked at system startup and shutdown see the man pages for chkconfig 8 On SUSE systems the script file that automatically invokes apcupsd on system start and stops is etc rc d apcupsd To start apcupsd manually as you will probably do immediately following the installation enter the following eec cena fapcupsdesitatt Normally when properly installed apcupsd will be started and stopped automatically by your system Unfortunately the details are different for each system Below we give the commands for selected systems Alternatively there are simple stopapcupsd and startapcupsd scripts in the examples directory or you can modify one of the scripts in the distributions directory to meet your needs To stop apcupsd you can do the following On Red Hat systems etc rc
57. LE Signal Computer UPS DESF DB9M RxD 2 2 TD Send TxD 6 1 RxD Receive GND 5 9 Ground When using this cable with apcupsd specify the following in apcupsd contf UPSCABLE smart URS GE Ee ape sma DEVICE dev ttySO or whatever your serial port is If you have an OS that requires DCD or RTS to be set before you can receive input you might try building the standard APC Smart 940 0024C cable listed below see 940 0024C Cable Wiring Simple Custom Voltage Signalling Cable for dumb UPSes You do not have this cable unless you built it yourself The Simple Custom cable is not an APC product For dumb UPSes using voltage signalling if you are going to build your own cable we recommend to make the cable designed by the apcupsd team as follows SIMPLE CUSTOM CABLE Signal Computer WEIS DESE 4 7K ohm DB9M DTR 4 DTR set to 5V by Apcupsd CTS 8 r 5 Low Battery GND 5 4 Ground DCD T 2 On Battery RIS 7 1 Kill UPS Power List of components one needs to make the Simple cable 1 One 1 male DB9 connector use solder type connector only 2 One 1 female DB9 25F connector use solder type connector only 3 One 1 4 7K ohm 1 4 watt 5 resistor 4 rosin core solder 5 three 3 to five 5 feet of 22AWG multi stranded four or more conductor cable Assembly instructions 1 Solder the resistor into pin 4 of the female DB9 connector 2 Next bend the resistor so that it connects to pin
58. S l 1N4148 A K lt IRES 7 Shutdown POWER FAIL 2 gt lt IRD IR 2 9 Om Barr GROUND 4 9 gt lt lt a GIN Operation e DTR is cable power and must be held at SPACE DSR or CTS may be used as a loopback input to determine if the cable is plugged in e DCD is the battery low signal to the computer A SPACE on this line means the battery is low This is signalled by BATTERY LOW being pulled down it is probably open circuit normally Normally the transistor is turned off and DCD is held at the MARK voltage by TxD When BATTERY LOW is pulled down the voltage divider R2 R1 biases the transistor so that it is turned on causing DCD to be pulled up to the SPACE voltage e TxD must be held at MARK this is the default state when no data is being transmitted This sets the default bias for both DCD and SHUTDOWN If this line is an open circuit then when BATTERY LOW is signalled SHUTDOWN will be automatically signalled this would be true if the cable were plugged in to the UPS and not the computer or if the computer were turned off e RTS is the shutdown signal from the computer A SPACE on this line tells the UPS to shut down RxD and RI are both the power fail signals to the computer A MARK on this line means the power has failed e SPACE is a positive voltage typically 12V MARK is a negative voltage typically 12V Linux appears to translate SPACE to a 1 and MARK to a 0 940 0095B Cable Wiring Suppo
59. Stop any running apcupsd help Show the apcupsd help dialogue box It is important to note that under normal circumstances the user should never need to use these options as they are normally handled by the system automatically once apcupsd is installed However you may note these options in some of the pif files that have been created for your use Installation Serial Line UPSes Overview of Serial Interface UPSes If you have a UPS that communicates via serial port you need to do two things before you can even think about configuring the software First you need to figure out whether it s a dumb voltage signalling UPS or speaks the apcsmart protocol Second if you have an interface cable from APC you need to figure out what kind it is If you don t have such a cable you need to build one A straight through serial cable won t work According to Bill Marr the Belkin F5U109 also sold as F5U409 also works with apcupsd for kernel versions 2 4 25 or higher and kernels 2 6 1 and higher These newer kernels are needed to have the patch that makes the mct_u232 Magic Control Technology module and other adapters work with RS 232 devices that do not assert the CTS signal Connecting a Serial Line UPS to a USB Port By using a special adaptor you can connect your serial line UPS to a USB port If you would like to free up your serial port and connect your existing serial port UPS to a USB port it is possible if you have one of the later k
60. T and MATRIX the output is written in a format very similar to what PowerChute writes That is MinLineVoltage MaxLineVoltage OutputVoltage BatteryVoltage LineFrequency LoadPercent UPSTemperature AmbientTemperature Humidity LineVoltage BatteryCharge toggle Any value that is not supported by your UPS such as AmbientTemperature and Humidity will be blank or possibly as 0 0 In any case the commas before and after that field will still be output The toggle value alternates from 0 to 1 on each line This was added at user request so that no two adjacent samples are identical An actual example from the log file is New 2 IZsasc0S meee ACTS SA43 224 9 227 oop 22052 41 614 00500 1000 SU O77 7226527 SU 0 Al Status Logging Status logging consists of logging all available information known about your UPS as a series of ASCII records This information is also made available by the apcupsd network information server For more details on STATUS logging see the apcupsd Status Logging section for details EVENTS Logging Events logging consists of logging events as they happen For example successful startup power fail battery failure system shutdown See the Customizing Event Handling section for more details Implementation Details In order to ensure that the data logged to syslog can be directed to different files have assigned syslog levels to each of our four types of data as follows 1 DEBUG logging h
61. TSERVER ON in your apcupsd conf file which is the default be aware that anyone on the network can read the status of your UPS This may or may not pose a problem If you don t consider this information privileged as is the case for many there is little risk In addition if you have a perimeter firewall or NATting router with typical settings only users on your local network access to your UPS information You may also restrict access using using firewall settings see below or TCP Wrappers see below Firewall Settings If you are running apcupsd as an NIS server you will need to ensure that the clients can reach it by opening up NISPORT default TCP 3551 on any firewall running on the server You may wish to configure your firewall s to only allow connections from your local network or specifically from the masters slaves and servers as needed TCP Wrappers If your operating system does not support a host based firewall a firewall running on the local machine then you may try to get some of the functionality of such a firewall with TCP Wrappers As of apcupsd version 3 8 2 TCP Wrappers are implemented if you turn them on when configuring configure with libwrap With this code enabled you may control who may access your apcupsd via TCP connections the Network Information Server This control is done by modifying the file etc hosts allow This code is implemented but untested If you use it please send us some feed
62. UPS detects line voltage distortions such as spikes notches dips and swells as well as distortions caused by operation with inexpensive fuel powered generators By default the UPS reacts to distortions by transferring to on battery operation to protect the equipment that you are plugging into the UPS Where power quality is poor the UPS may frequently transfer to on battery operation Battery longevity and service life of the UPS may be conserved by reducing the sensitivity of the UPS as long as your equipment can operate normally under the conditions detailed below Any type of voltage disturbance includes High Low No RMS Voltage Total Harmonic Distortion THD Change in Voltage over Time dv dt Frequency Hz out of tolerance High Sensitivity Mode In the event of any type of voltage disturbance the UPS will transfer to battery power and watch the AC line until it can transfer back to line The transfer time in this mode depends on how far the line voltage deviates from the sinewave reference Medium Sensitivity Mode In the event of a RMS _ voltage out of tolerance High Low No and RMS rate of change disturbances dv dt in the line voltage the UPS will transfer to battery power and watch the AC line until it can transfer back to line In this mode the transfer times are longer but still within acceptable limits to insure the continuity of a computer s operation Low Sensitivity Mode In the event of a RMS voltage out of tolerance dis
63. URS OO 60 SmartUPS 1000 72 Smart UPS 1400 where NN now Nn has possible meanings N Class of UPS in Back UPS Pro 5n Smart UPS fia Onart URS RNE n Level of intelligence N1 Simple Signal if detectable WAG N2 Full Set of Smart Signals N3 Micro Subset of Smart Signals where M Possible Level of Smart Features unknown 1 Stand Alone 8 Rack Mount 9 Rack Mount where L National Model Use Only Codes D Domestic ils volts I International 230 Votes A Asia 100 Volts J Japan 100 Volts M North America 208 Volts Servers EEPROM Values Upon sending a Z your UPS will probably spit back approximately 254 characters something like the following truncated here for the example UD43132135138129uM43229234239224uA43110112114108 It looks bizarre and ugly but is easily parsed The is some kind of marker ident character Skip it The rest fits this form e Command character use this to select the value e Locale use b to find out what yours is the last character 4 applies to all e Number of choices 4 means there are 4 possibilities coming up e Choice length 3 means they are all 3 chars long Then it s followed by the choices and it starts over Matrix UPS models have between each grouping for some reason Here is an example broken out to be more readable CMD DFO RSP FSZ FVL u D 4 5 L27 L20 135 136 u M 4 3 229 2
64. Windows systems the domain resolution does not seem to work if you have not configured a DNS server in the Network section of the Control Panel This problem should be apparent only when running a slave configuration In this case when you specify the name of the master in your apcupsd conf file apcupsd will be unable to resolve the name to a valid IP address To circumvent this problem simply enter the address as an IP address rather than a hostname or alternatively ensure that you have a valid DNS server configured on your system On WinNT WinXP and Win2K systems you can examine the System Applications log to which apcupsd writes Windows error messages during startup Regardless of which Windows system you are running apcupsd logs most error messages to c apcupsd etc apcupsd apcupsd events This type error messages such as configuration file not found etc are written to this file Note that on some systems WinXP possibly others Apcupsd is unable to write to this file when running as a service Email Notification of Events It is possible to receive email notification of apcupsd events using some simple Visual Basic scripts contributed by Ed Dondlinger lt edondlinger thepylegroup com gt The scripts are automatically installed in the etc apcupsd directory of your apcupsd installation but are disabled by default To enable them first open them in a text editor such as Notepad and edit the USER VARIABLES section to set your email pre
65. a lot of care to ensure that all components are using the same port To enable the apcupsd Network Information Server which is normally the default you set NETSERVER on NESPORT esol in your apcupsd conf file The full form of the apcaccess command is apcaccess status localhost 3551 where only apcaccess status should normally be needed localhost may be replaced by any machine name fully qualified domain name or IP address which means that apcaccess can access any UPS on the network running the Network Information Server The status command line option of apcaccess will produce a full printout of all the STATUS variables used by apcupsd This can be very helpful for checking the condition of your UPS and to know whether or not apcupsd is properly connected to it Please note that if you invoke apcaccess within the first 30 seconds of launching apcupsd you will likely get an error message such as APCACCESS FATAL ERROR in apcaccess c at line 336 tcp_open cannot connect to server localhost on port 3551 This is because apcupsd is still in the process of initializing the UPS The solution is to wait at least 30 seconds after starting apcupsd before launching apcaccess For a SmartUPS 1000 apcaccess will emit the following output DATE g ne Dee OS 12534220 Car 1999 HOSTNAME matou RELEASE g So lo Ogara CABLE Custom Cable Smart MODEL SMART UPS 1000 UPSMODE Stand Alone UPSNAME B UES ALDEN
66. aceron OCEHNETOMNB TE MADER clear DER ACCiLOMm LOCI LLOMELS IITs set RIRS apcserial c condition save_dumb_status cable CUSTOM_SIMPLE action ioctl TIOMBIC DTR clear DER ACE Onn tO Cele Gl MEI Crm Reis ecleariRIS cable 0020B 0020C 0119A O127A 0128A ack font HOCce Il CEOME TE Dsl clear DTR cable 0095A 0095B 0095C ACciLoMm 1ECel ELOMEBIC IRIS Clle ewe IRIS action ioctl1 TIOMBIC CD clear DCD aCe Onn sO Cele Ghl MEshCrmmRelns ecleanriRTS apcserial c condition check_serial cable CUSTOM_SIMPLE action OnBatt CD action BattLow CTS action LineDown SR cable 0020B 0020C 0119A O127A 0128A action OnBatt CIS action BattLow CD action LineDown 0 cable 0023A action Onbatt CD action BattLow SR action LineDown 0 Cale 00 SSAy OOO Sera OOo se action OnBatt RNG action sate lowe CD action LineDown 0 apcserial c condition killpower Gables CUSTOMES IMP Ey OOS aA eNO OS Br a0 ae acivsom alocte il COMERS IRS set RTS Jeton elo Ctl GRO M EBS assis set TxD cable 0020B 020C 0119A 0127A 0128A action alociell TOMEI IS IDI set DTR Recalibrating the UPS Runtime set PnP mode killpower ready to receive power bit killpower killpower killpower low batt killpower a second time kills power kills power Note In a future release of apcupsd this procedure w
67. achine that collected the UPS data UPSNAME The name of the UPS as stored in the EEPROM or in the UPSNAME directive in the configuration file VERSION The apcupsd release number build date and platform CABLE The cable as specified in the configuration file UPSCABLE MODEL The UPS model as derived from information from the UPS UPSMODE The mode in which apcupsd is operating as specified in the configuration file UPSMODE STARTTIME The time date that apcupsd was started STATUS The current status of the UPS ONLINE ONBATT etc LINEV The current line voltage as returned by the UPS LOADPCT The percentage of load capacity as estimated by the UPS BCHARGE The percentage charge on the batteries TIMELEFT The remaining runtime left on batteries as estimated by the UPS MBATTCHG If the battery charge percentage BCHARGE drops below this value apcupsd will shutdown your system Value is set in the configuration file BATTERYLEVEL MINTIMEL apcupsd will shutdown your system if the remaining runtime equals or is below this point Value is set in the configuration file MINUTES MAXTIME apcupsd will shutdown your system if the time on batteries exceeds this value A value of zero disables the feature Value is set in the configuration file TIMEOUT MAXLINEV The maximum line voltage since the UPS was started as reported by the UPS MINLINEV The minimum line voltage since the UPS was started as returned by the UPS OUTPUTV The
68. adding the kill on powerfail to the apcupsd invocation This method is not preferred because the UPS is commanded to power down without delay This creates the potential for UPS powering down before the server calling for UPS power down completes its shutdown However in the case of Microsoft Windows OS this is the only method available for powering down the UPS e Restart your apcupsd With this setup your UPS operations should be safe apcupsd System Logging The apcupsd philosophy is that all logging should be done through the syslog facility See man syslog This is now implemented with the exceptions that STATUS logging for compatibility with prior versions is still done to a file and EVENTS logging can be directed to a temporary file so that it can be reported by the network information server Logging Types apcupsd splits its logging into four separate types called 1 DEBUG 2 DATA 3 STATUS 4 EVENTS Debug logging consists of debug messages Normally these are turned on only by developers and currently there exist very few of these debug messages Data Logging This feature is somewhat outdated and not often used Data logging consists of periodically logging important data concerning the operation of the UPS For the definitive definition of the format see log_data in apcreports c The format varies according to the UPS model and the information available from the UPS For UPS models NBKPRO SMART SHARESMAR
69. al port to which the UPS is connected This can take the form of COM1 etc on Windows or dev XxXx on UNIX systems You should use the APC supplied serial cable P N 940 0625A that ships with the UPS Other smart type cables may work but only 940 0625A has been formally tested at this time Note that most UPSes ship with MODBUS support disabled by default You must use the UPS s front panel menu to enable MODBUS protocol support before apcupsd will be able to communicate with the UPS You may need to enable the Advanced menu option before the MODBUS protocol option will be visible Testing Apcupsd The following testing procedures apply for the most part to SmartUPSes whether USB or serial If you have a dumb voltage signalling UPS your testing procedures will be somewhat different and you should see the section on Testing Serial UPSes see Testing Serial Line UPSes Process Status Test After you start apcupsd execute the following command js Eez or the equivalent for your system You should see something similar to the following output 632 2 S 0 00 sbin apcupsd f etc apcupsd apcupsd conf 841 S 0 00 _ sbin apcupsd f etc apcupsd apcupsd conf 842 S 0 00 _ sbin apcupsd f etc apcupsd apcupsd conf This indicates that apcupsd is up and running and has started the two standard threads in addition to the main thread If you see only one instance of apcupsd running don t worry about it as this is normal on
70. ally be created during the shutdown sequence to prevent additional users from logging in see the NOLOGIN configuration directive Even though apcupsd has requested the system to perform a shutdown it continues running When the system signals apcupsd to do exit it does so This is part of the normal system shutdown at least on Unix and Linux systems and the exact time that apcupsd receives the termination signal depends on how the shutdown links usually in etc rc d are set Note that on Windows NT systems apcupsd apparently continues to run as a Service even though the machine is shutdown During the shutdown of the system after apcupsd has been forced to exit one of the last things done by the system shutdown is to call the halt script which is usually in etc rc d halt or etc rc d init d halt or possibly in sbin init d rc 0 depending on your system If apcupsd was properly installed this standard halt script was modified to include a bit of new logic just before the final halt of the system lt first tests if the file etc apcupsd powerfail exists and if it does it executes etc apcupsd apccontrol killpower It is this last step that will cause apcupsd to be re executed with the killpower option on the command line This option tells apcupsd to inform the UPS to kill the power This final step is important if you want to ensure that your system will automatically reboot when the power comes back on The actual code used on th
71. alues factory except identity or battery change date Not settings available on SmartUPS v s or BackUPS Pro Capability various Cycle forward through possible capability values cycle UPS sends afterward to confirm change to forward EEPROM Capability various Cycle backward through possible capability values cycle UPS sends afterward to confirm change to backward EEPROM nnn Shutdown OK or UPS shuts down after grace period with delayed and return wakeup after nnn tenths of an hour plus any wakeup delay time Older models send instead of OK Ox7f Abort OK Use to abort S K shutdown Register 1 see below See Register 1 table i Register 2 see below See Register 2 table 0 Battery See Resetting the UPS Battery Constant constant 4 2 Prints 35 on SmartUPS 1000 5 2 Prints EF on SmartUPS 1000 6 2 Prints F9 on SmartUPS 1000 7 DIP switch See Dip switch info positions 8 Register 3 see below See Register 3 table 9 Line quality FF Possible values e 00 unacceptable e FF acceptable gt Number of SmartCell models return number of connected external packs Other models return value set by the user battery packs use Measure UPS NO NO Degrees C Writable Variable Possible values 55 Upper temp 50 45 05 Use to change values limit Measure UPS NO NO Degrees C Writable Variable Possible values 55 lower temp 50 45 05 U
72. an excessively long calibration Remove battery packs or increase the load space heaters are good dummy loads to obtain a reasonable time length for the calibration under an hour if possible At the start of a calibration the Matrix microprocessor saves the Estimated Run Time displayed The unit will then go to battery power until the capacity is 25 After this run time has been completed the original Estimated Run Time is compared with the actual run time It will then increase or decrease this value to correspond to the new run time achieved If at any time during the discharge one of the following rules is violated the calibration will be aborted or corrupted Pam SST CASUAL SUMAN ee Ea S pae Paa ossai 3 Load must be above 25 4 Load must not fluctuate more than 5 5 The UPS must be allowed to run down to 25 battery capacity PowerChute or apcupsd and Accessories must be removed since they can abort the calibration prematurely For a dumb or simple signalling UPS eg a Back UPS This could be done if you have changed your equipment load or battery Stop the PowerChute or apcupsd software from running disconnect the serial cable between the computer and UPS Next unplug the UPS from the wall suggest not disconnecting but simply turning off the utility power thereby preserving the earthing and let it run on battery until it reaches low battery Once it reaches low battery plug it back into the wall outlet turn th
73. and build Apcupsd normally as described in Building and Installing Apcupsd Be sure to include the enable usb flag to configure After building install Apcupsd as root using make install and then reboot During installation Apcupsd will automatically install a simple dummy kext driver designed to prevent Apple s monitoring software from taking over the UPS It is necessary to reboot in order to activate the kext Note that this kext will be automatically removed if you uninstall Apcupsd using make uninstall allowing Apple s monitoring tool to once again access the UPS Verifying Device Detection and Driver After installing Apcupsd as described above and rebooting plug in your UPS USB cable You should notice that Darwin does NOT display the battery monitor tool in the menu bar You can also check Apple Menu gt About This Mac gt More Info gt USB to ensure that your UPS appears in the list of USB devices Building and Installing apcupsd In general it is recommended to obtain a prebuilt binary package for your platform Given how apcupsd must integrate into the shutdown mechanism of the operating system and the rate at which such mechanisms are changed by vendors the platform ports in the apcupsd tree may become out of date In some cases binary packages are provided by the apcupsd team RedHat Mandriva SuSE Windows Mac OS X For other platforms it is recommended to check your vendor s package repository and third par
74. ard is ready for general configuration This is accomplished by telneting to the SNMP Card telnet lt IPaddress gt Login using apc for both the username and password and the following menu will display KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KK KEK KKKKKKEKKKKKEK American Power Conversion Network Management Card AOS v2 6 4 co Copyrsgne 2004 RoS Reserved Smart UPS amp Malerix UP S APP Veror Name 3 Date 07 03 2006 Contact Time 04 43 33 Location User Administrator Up Time 5 0 Days Wil korres 57 Malmiiness Scari War INae Ace Smart UPS 1000 named On Line No Alarms Present sees Conesol Consol 1 Device Manager 2 Network 3 System 4 Logout lt ESC gt Main Menu KENTER Refresh lt CTRL L gt Event Log gt KKK KKK KK KK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKK KKKKKKKKKKKEK Select Option 2 for Network Next select Option 1 for TCP IP settings At this point the following settings will be to be specified e Verify System IP lt IPaddress gt e Specify Subnet Mask i e 225 225 225 0 e Specify Default Gateway e Specify Host Name e Specify Domain Name Specifying these parameters will complete the General Parameters setup Additionally the SNMP Network Management Card can now be connected to from a web browser for monitoring and additional configuration Set SNMP card Shutdown Pa
75. as level LOG_DEBUG 2 DATA logging has level LOG_INFO 3 STATUS logging has level LOG_NOTICE 4 EVENTS logging has levels LOG_WARNING LOG_ERR LOG_CRIT and LOG_ALERT It should be noted that more work needs to be done on the precise definitions of each of the levels for EVENTS logging Currently it is roughly broken down as follows LOG_WARNING general information such as startup etc LOG_ERR an error condition detected e g communications problem with the UPS LOG_CRIT a serious problem has occurred such as power failure running on UPS batteries LOG_ALERT a condition that needs immediate attention such as pending system shutdown The default Facility for syslog logging is DAEMON although this can be changed with the FACILITY directive in apcupsd conf In the following example we should the facility as localo More work needs to be done to the code to ensure that it corresponds to the above levels As a practical example of how to setup your syslog to use the new logging feature suppose you wish to direct all DATA logging to a file named var log apcupsd data all EVENTS to the standard var log messages file to be mixed with other system messages and at the same time send all EVENTS to var log apcupsd events and finally you want to send all STATUS logging to the named pipe var log apcupsd status First as root you create the named pipe mkfifo var log apcupsd status Change its permissions as necessary or use
76. at releas ie ak if test cat f grep release cie 3 sel Y Ua VinimeSwioriselxe chen DISTVER Enterprise cat f grep release Guile 6 el YY else DISTVER cat etc redhat release grep release Cug 5 el 4 V efai Source function library etc re d init d functions case Wisi skin Seana rm f etc apcupsd powerfail gm E fece nolocim ror Comi ta Sicc sioeuloscl eiaxculoscl noice p Clo inst basename conf acing in MSicaicicsline WS EMOn SS E daemon sbin apcupsd f Sconf P var run apcupsd Sinst pid RETVAL echo SRETVAL eq 0 amp amp touch var lock subsys apcupsd Sinst done stop ror Comi im jetC apcupsa apcupscdy Cont eGo inst basename Sconf echo n Shutting down UPS monitoring Sinst killproc p var run apcupsd S inst pid apcupsd echo rm E var run apcupsd Sinst pid rm f var lock subsys apcupsd Sinst done rr restart force reload 50 stop sleep 15 0 start rF reload echo 0 reload not implemented exit 3 ae status for conf in etc apcupsd apcupsd conf do inst basename conf status p var run apcupsd Sinst pid apcupsd Sinst RETVAL if S RETVAL eq 0 then NISPORT grep NISPORT lt Sconf sed e s NISPORT 0 9 1 sbin apcaccess status localhost SNISPORT egrep STATUS UPSNAME EL done 7 echo Usage 0 start stop restart status exit 1 on esac exit 0 That s about all t
77. automatically sent to the system log file Instead it is written as a series of data records in a specific file normally etc apcupsd apcupsd status After each write the file is rewound so that the size of the file remains constant The STATUS file is kept for backward compatibility and will be eliminated in a future version of apcupsd The preferred method for obtaining this information is from apcaccess or by using the CGI interface see apcupsd Network Monitoring CGI Programs To make reading the status data reliable via a named pipe the first record written contains a version number the number of records that follow the first record and the total number of bytes in those subsequent records An actual example of such a status file etc apcupsd apcupsd status is shown below Consequently the first record always consists of 24 bytes 23 characters followed by a newline This record starts with APC and as indicated in the example is followed by 37 records consisting of 906 bytes The last record begins with END APC and contains the date and time matching the DATE record When this data is written to a file it is written as two records the first record and all the other records together In reading the file it can be either be read a record at a time or in one big read When this data is written to syslog it is written a record at a time The first record is the first 24 bytes By having the number of records and the size in th
78. ave the following files in the special null directory adk0212 mail apcupsd ls l1 etc apcupsd null total 32 SEWE A i woo wooe 4 5 Abe 3 O8324 eloceoneeoll rwxr xr x 1 root root 475 Aug 3 08 28 changeme EWE XA X iroot root SO Mine 8 Wee 2 COn a ues EWY XA X iroot root MOOS Ano eNe 26 acommnok SEWE A Il OOK COO 8 Aug 3 08 22 doshutdown rwxr xr x 1 root root 470 Aug 3 08 27 offbattery SWIG XA Se WTO Olen IG Olen S Oe ALIC mS OCH AW monibalttciay The important change here is the addition of a doshutdown script which overrides apccontrol s shutdown action adk0212 mail null cat etc apcupsd null doshutdown exit 99 The exit 99 tells apccontrol to skip its normal processing for that event apccontrol itself is unchanged it is a direct copy of the original The other scripts are also direct copies and have simply been modified to generate status email from NISPORT 3552 instead of 3551 also have a custom init d start stop script to manage multiple instances The start stop and status handlers are modified to iterate over all etc apcupsd apcupsd conf files This is derived from the standard apcupsd redhat rc script I Aaka el apcupsd This shell script takes care of starting and stopping the apcupsd UPS monitoring daemon Chive onic aes lomo Om description apcupsd monitors power and takes action if necessary if test f etc whitebox release then f etc whitebox release else f etc redh
79. back Configuring YourEEPROM If you have a SmartUPS there are depending on the UPS at least 12 different values stored in the EEPROM that determine how the UPS reacts to various conditions such as high line voltage low line voltage power down grace periods etc In general for the moment we do not recommend that you change your EEPROM values unless absolutely necessary There have been several reported cases of problems setting the Low Transfer Voltage Consequently if at all possible do not attempt to change this value Using apctest to Configure YourEEPROM To make the EEPROM changes with apctest you must first stop the apcupsd daemon After apcupsd is stopped you may invoke apctest as root We recommend that you change the EEPROM as little as is absolutely necessary since it is a somewhat delicate process that has occasionally produced problems i e improper EEPROM values are displayed after the update apctest will present a menu of options which are generally self explanatory Note that USB connections will show a difference set of options than smart serial connections Maintaining Your UPS Batteries Battery Technology Sealed Lead Acid SLA batteries otherwise known as Valve Regulated Lead Acid VRLA batteries were originally known as dry batteries When first introduced in the 1950s they used a gel electrolyte The otherwise free acid was immobilised with a fine silica powder and formed a gel substance In the
80. bin is the default However please be aware that if you want to follow Sun s filesystem conventions you would use the following contigune prefix opt apcupsd sbindir etc opt apcupsd sbin sysconfdir etc opt apcupsd with cgi bin opt apcupsd cgi bin The way to setup the sbin directory as the executables directory is to pass configure the sbindir sbin option No other arguments should be required and your setup and platform should be detected automatically by configure Once you have run configure you will need to do a gmake Once the make has completed with no errors you must su to root to complete the install After the su you may not have a path to the make program anymore In that case you should do the gmake install step as gmake install Once the install completes you must edit the sbin rcO script as detailed below then exit from the su ed shell In order to support unattended operation and shutdown during a power failure it s important that the UPS remove power after the shutdown completes This allows the unattended UPS to reboot the system when power returns by re powering the system Of course you need autoboot enabled for your system to do this but all Solaris systems have this by default If you have disabled this on your system please re enable it To get the UPS to remove power from the system at the correct time during shutdown i e after the disks have done their final sync
81. cable for USB capable models with 10 pin RJ45 connector APC Part CAO Q USB Computer RJ45 10 UPS sss oooo0o000000 l 1 4 10 J es SVAD IL FW DATA 2 9 DATA DATA 3 10 DATA GND 4 7 Signal GND Shield 4 Chassis GRND Win32 Implementation Restrictions for Simple UPSes Due to inadequacies in the Win32 API it is not possible to set clear get all the serial port line signals apcupsd can detect CTS DSR RNG and CD It can set and clear RTS and DTR This imposes a few minor restrictions on the functionality of some of the cables In particular LineDown on the Custom Simple cable and Low Battery on the 0023A cable are not implemented Internal Apcupsd Actions for Simple Cables This section describes how apcupsd 3 8 5 March 2002 treats the serial port line signals for simple cables apCactlon ne condition power failure detected cable CUSTOM_SIMPLE aceron sAo eell IOCMBINS IDLE set DTR enable power bit apecaceilon c condition power back cable CUSTOM_SIMPLE action ioctl TIOCMBIC DTR action soci MTOCMsIC Sur lear DTR clear power bit lear ST TxD Q Q apcserial c condition serial port initialization cable 0095A 0095B 0095C ACEO LoEcell ELOMELC IRIS CGile eue IRIS cable 0119A 0127A 0128A
82. cates with the UPS through the USB generic device ugen The reconfigure boot performed after Apcupsd installation will ensure the correct device nodes are created Once your UPS has been recognized in dmesg as shown above you can check dev usb to see if the device nodes have appeared user sunblade ls dev usb 51d 2 Cime r LO entrlOstat devstat IEE OREN alse OPiS Ea 51d 2 is the vendor product id for APC UPSes Mac OS X Darwin USB Configuration Platforms and Versions Apcupsd supports USB UPSes on Mac OS X Darwin 10 4 x and higher Both Intel and PowerPC platforms are supported Building Apcupsd with USB Some specific packages are necessary when building Apcupsd with USB support on Darwin You must install libusb 0 1 12 which can be obtained from MacPorts http Wwww macports org formerly DarwinPorts or Fink http fink sourceforge net or downloaded and built by hand http www libusb org You must not use libusb 1 x or higher apcupsd does not support the new 1 0 APIs nor any version earlier than 0 1 12 earlier versions have a bug that apcupsd triggers Generally that means you must use exactly 0 1 12 Note that Apcupsd is sensitive to the install location of libusb so beware if you change it from the default Apcupsd should be built using gcc preferably from the XCode development tools Currently the maintainer is using gcc 4 0 1 from XCode 2 4 Other versions of gcc from other sources may also work Configure
83. ce name in the apcupsd conf file 2 The device name is not defined on your system Suggestions for proceeding For the first item check what your serial port device should be named You might be able to find the name with an ls dev Normally there will be hundreds or even thousands of names that print If that doesn t produce anything useful you can try step 2 Perhaps your device is not defined To get more information on your devices try man MAKEDEV or find name MAKEDEV It is often located in dev MAKEDEV Looking at the documentation may tell you what the correct name is or at least allow you to create the device How do ensure that the slaves shutdown before the master Slaves make their shutdown decision independently from the master Therefore you can use the TIMEOUT MINUTES and BATTERYLEVEL settings in the slaves apcupsd conf to configure them to shut down before the master How do ensure that my database server is correctly shutdown You simply add whatever commands are necessary in the appropriate case statements in etc apcupsd apccontrol which is a standard script file that is called to actually do the shutdown Alternatively you can add your own script file that will be called before doing the commands in apccontrol Your script file must have the same name as the appropriate case statement in apccontrol it must be executable and it must be in the same directory as apccontrol
84. configure statement to ensure that the modules you want are built and that everything is placed into the correct directories On Red Hat a fairly typical configuration command would look like the following CFLAGS g 02 LDFLAGS g configure enable usb with upstype usb with upscable usb prefix usr sbindir sbin with cgi bin var www cgi bin enable cgi with log dir etc apcupsd By default make install will install the executable files in sbin the manuals in usr man and the configuration and script files in etc apcupsd In addition if your system is recognized certain files such as the startup script and the system halt script will be placed in appropriate system directories usually subdirectories of etc rc d Verifying a Source Installation There are a number of things that you can do to check if the installation make install went well The fist is to check where the system has installed apcupsd using which and whereis On my Red Hat system you should get the following lines preceded with a indicate what you type which apcupsd sbin apcupsd whereis apcupsd apcupsd sbin apcupsd etc apcupsd etc apcupsd conf etc apcupsd status usr man man8 apcupsd 8 gz usr man man8 apcupsd 8 If you find an apcupsd in usr sbin usr local sbin usr lib or another such directory it is probably a piece of an old version of apcupsd that you can delete
85. cters SENSITIVITY H M L H High most sensitive setting M Medium L Low least sensitive setting WAKEUP 000 060 180 300 The time delay in seconds that the UPS waits after the return of utility power before waking up and restoring power to the connected equipment SLEEP 020 180 300 600 The time delay in seconds for which the UPS waits or sleeps after it receives a request to power off the connected system LOTRANSFER lt voltage gt Low line voltage causing transfer to battery power or activation of SmartBoost Allowable values depend on the last letter of the firmware or APCMODEL Typical values are LOS 103 100 097 Wy 172 168 182 092 090 06S Wee 208 204 200 196 HP EU where D domestic USA M Canada A Asia and International HITRANSFER lt voltage gt High line voltage causing transfer to battery power or activation of SmartTrim Allowable values depend on the last letter of the firmware or APCMODEL Typical values are lay 150 1353 136 229 B34 239 Bea ioe 11O MIZ MIA 255 2597 261l 205 HP z UO where D domestic USA M Canada A Asia and International RETURNCHARGE 00 15 50 90 Percentage of battery charge needed for the UPS to restore power to the connected equipment BEEPSTATE 0 T L N Alarm delay Zero delay after power fails When power fails plus 30 seconds When low battery occurs 5 INGWwWeTe Z2eHo LOWBATT lt minutes gt Low batte
86. cupsd on Windows Upgrading Post Installation Problem Areas 48 49 50 51 51 51 53 55 56 57 59 59 62 62 62 62 63 64 64 65 65 65 66 66 66 66 67 67 67 68 68 68 69 69 70 70 70 70 Email Notification of Events Killpower under Windows Power Down During Shutdown Command Line Options Specific to the Windows Version Installation Serial Line UPSes Overview of Serial Interface UPSes Connecting a Serial Line UPS to a USB Port Testing Serial Line UPSes Establishing Serial Port Connection Once you have established serial communications Troubleshooting Serial Line communications Bizarre Intermittent Behavior Cables Smart Custom Cable for SmartUPSes Simple Custom Voltage Signalling Cable for dumb UPSes Custom RJ45 Smart Signalling Cable for BackUPS CS Models Other APC Cables that apcupsd Supports Voltage Signalling Features Supported by Apcupsd for Various Cables Voltage Signalling The Back UPS Office 500 signals Analyses of APC Cables 940 0020B Cable Wiring 940 0020C Cable Wiring 940 0023A Cable Wiring 940 0024C Cable Wiring 940 0095A Cable Wiring 940 0095B Cable Wiring 940 0119A Cable Wiring Serial BackUPS ES Wiring 940 0128A Cable Wiring 940 0128D Cable Wiring 940 0127B Cable Wiring Win32 Implementation Restrictions for Simple UPSes Internal Apcupsd Actions for Simple Cables Recalibrating the UPS Runtime Configuration Directive Reference General Configuration Directives
87. d the apcupsd css file in the directory apcupsd etc apcupsd on the same drive letter as the web server s cgi bin directory If you installed apcupsd into C apcupsd the default and your web server s cgi bin directory is also located on the c drive no further changes are necessary If you installed apcupsd into a different directory or your web server cgi bin is on another drive you will need to relocate hosts conf and apcupsd css from the apcupsd_ install location to apcupsd etc apcupsd on the appropriate drive multimon cgi This program monitors multiple UPSes at the same time A typical output of multimon cgi as displayed in your Web browser might look like the following The machines monitored as well as the values and their column headings are all configurable see etc apcupsd hosts conf and etc apcupsd multimon conf upsstats cgi By clicking on the system name in the multimon cgi display you will invoke upsstats cgi for the specified system which will produce a bar graph display of three of the monitored values For example Tha Dec 02 19 14 44 CRT 1999 Battery Capacity Utility Voltage Z ofuPs oad x 100 25 125 1 80 260 100 60 245 5 Last UPS Self Test NO Last Test Date N A 40 230 50 Utility Voltage 228 8 VAC 27 5 20 215 25 0 200 0 100 0 228 8 VAC 62 Di 10 18 CET 1999 Di 16 30 CET 1999 Thu Dec 02 08 16 30 CET 1999 Dec 02 08 16 53 CET 1999 Dec 02 08 16 53 CET 1999
88. disabled on SU370ci and 400 113 Audible alarm delayed 30 seconds 2 2 Output transfer set to 115 VAC from 120 VAC or to 240 VAC from 230 VAC 1 UPS desensitized input voltage range expanded 4 7 Unused at this time Status bits This is probably the most important register of the UPS which indicates the overall UPS status Some common things you ll see e 08 On line battery OK e 10 On battery battery OK e 50 On battery battery low e SM Status bit is still not available retry reading Bit Meaning when bit 1 Runtime calibration occurring Not reported by Smart UPS v s and BackUPS Pro SmartTrim Not reported by 1st and 2nd generation SmartUPS models SmartBoost On line this is the normal condition On battery Overloaded output Battery low N O om A Ol N O Replace battery Alert messages These single character messages are sent by the UPS any time there is an Alert condition All other responses indicated above are sent by the UPS only in response to a query or action command Character Meaning Description Line Fail Sent when the UPS goes on battery repeated every 30 seconds until low battery condition reached Sometimes occurs more than once in the first 30 seconds Return from UPS back on line power Only sent if a has been sent previously line fail Low bat
89. do most of the initial testing with your computer plugged into the wall rather than your UPS Thus if the UPS power is suddenly shut off your computer will continue to run We also recommend using safe apccontrol as described below until you are sure that the signaling is correct Also note that if you launch the execution of apcupsd while your voltage signaling UPS is on battery power it is very likely that your UPS will immediately shut off the power This is due to the initialization of the serial port line signals which often looks to the UPS like a shutdown command Finally double check the state of your cabling and UPS indicator lights frequently during testing For voltage signaling UPSes apcupsd is not currently able to detect whether or not the serial cable is connected In addition some simple signaling UPSes with certain cable combinations are not able to detect the low battery condition For more details please see Voltage Signalling Features Supported by Apcupsd for Various Cables Establishing Serial Port Connection Once you have compiled installed and invoked apcupsd you should wait to allow apcupsd to configure itself and establish contact with the UPS If you see a message similar to the following about 30 seconds after starting apcupsd apcupsd FATAL ERROR in apcserial c at line 156 PANIC Cannot communicate with UPS via serial port it means that apcupsd tried for about 30 seconds to establish contact with the UPS
90. dows APC smart protocol The APC UPS protocol was originally analyzed by Pavel Korensky with additions from Andre H Hendrick beginning in 1995 and we want to give credit for good hard work where credit is due After having said that you will see that Steven Freed built much of the original apcupsd information file The start of this chapter of the apcupsd manual in HTML format was pulled from the Network UPS Tools NUT site http www networkupstools org ups protocols apcsmart html It has been an invaluable tool in improving apcupsd and consider it the Bible of APC UPS programming In the course of using it have added information gleaned from apcupsd and information graciously supplied by APC Description Here s the information on the elusive APC smart signaling protocol used by their higher end units Back UPS Pro Smart UPS Matrix UPS etc What you see here has been collected from a variety of sources Some people analyzed the chatter between PowerChute and their hardware Others sent various characters to the UPS and figured out what the results meant RS 232 differences Normal 9 pin serial connections have TxD on 3 and RxD on 2 APC s smart serial ports put TxD on pin 1 and RxD on pin 2 This means you go nowhere if you use a normal straight through serial cable In fact you might even power down the load if you plug one of those cables in This is due to the odd routing of pins DTR and RTS from the PC usually wind up d
91. e Red Hat version is See if this is a powerfail situation teen oD Cua Ss Oeics if f etc apcupsd powerfail then i wap Cupsan as echo Tie Rn CUO S Canis echo APCUPSD will now power off the UPS Yi ASN ONCTSI ORS A echo Sah ASEH OKAY ORS iA etc apcupsd apccontrol killpower Uh SEY VERT ONSITE 19 8 echo USEF OKAY ORS 9 echo Please ensure that the UPS has powered off before rebooting Viel CHE ONS TSI ORSO LO YS echo Otherwise the UPS may cut the power during the reboot 7S et TSH OKAY ORS echo AA CUD C UO Ss Claw fea Vist HOVE NGI OSC 19 8 The above code must be inserted as late as possible in the halt script On many systems such as Red Hat all the disk drives were unmounted then remounted read only thus permitting access to the etc files and the apcupsd executable If your system does not explicitly remount the disks you must remount them in read only mode in the code that you add Examples of code fragments that do this can be found in the distributions suse subdirectory of the source If you are not able to insert the above code in your halt script because there is no halt script or because your halt script calls the init program as some Unix systems do you can either just forget about powering off the UPS which means that your machine will not automatically reboot after a power failure or there is yet another alternative though not at all as satisfying as inserting code in the halt script Only if you
92. e d init d apcupsd stop On SUSE systems etc rce d apcupsd stop Please see the Testing Apcupsd chapter for more details on insuring that apcupsd is running properly Configuration Examples A Simple USB Configuration If you have a USB UPS the essential elements of your apcupsd conf file should look like the following apcupsd conf v1 1 UPSCABLE usb URS IAGE aus DEVICE LOCKFILE var lock UPSCLASS standalone UPSMODE disable Notice that we have not specified a device In doing so apcupsd will try all the well known USB ports We strongly recommend you use this empty device address form unless you have a good reason to do otherwise Please use the explicit specifications of a device only if you know exactly what you are doing In general it is much easier to let apcupsd find the device itself Please see USB Configuration for detailed help on setting up your system to work with a USB UPS A Simple Configuration for a Serial SmartUPS If you have a Smart UPS using the serial cable supplied by APC or you build a CUSTOM SMART cable outlined in the cables chapter a very simple configuration file would look like the following ap eCupsdncontiz aval E UPSCABLE smart UPS iPHC Sinaltsite DEVICE dev ttyso LOCKFILE var lock UPSCLASS standalone UPSMODE disable Normally you would have many more configuration directives to completely customize your installation but this example show
93. e falls below the specified percentage The default is 5 percent This directive is ignored for dumb voltage signalling UPSes To totally disable this counter set BATTERYLEVEL 1 in your apcupsd conf file MINUTES battery runtime in minutes If MINUTES is specified during a power failure apcupsd will shutdown the system when the remaining runtime on batteries as internally calculated by the UPS falls below the time specified The default is 3 This directive is ignored for dumb voltage signalling UPSes It should be noted that some UPSes report an incorrect value for remaining runtime when the battery is fully charged This can be checked by examining the TIMELEFT value as printed in the output of an apcaccess status command If the value is zero or otherwise unreasonable your UPS is probably broken In this case we recommend that you disable this timer by setting MINUTES 1 in your apcupsd conf file TIMEOUT time in seconds After a power failure apcupsd will halt the system when TIMEOUT seconds have expired A value of zero disables this timer Normally for all Smart UPS models and dumb UPSes with cables that support low battery detection this should be zero so that the shutdown time will be determined by the battery level and or remaining runtime see above or in the case of a voltage signalling UPS when the battery is exhausted This command is required for dumb UPSes that do not provide a batte
94. e first record the complete status can be reliably reassembled Status Report Example An example of output from a BackUPS RS 1500 follows APC 001 037 0906 DATE 8 Stm Aor 26 Weazie 22 BDE 2009 HOSTNAME mail kroptech com VERSION 3 14 2 10 September 2007 redhat UPSNAME ups0O CABLE USB Cable MODEL b Back UeS ins L500 UPSMODE Stand Alone START EIME Sun Apr 26 Or 22346 ED 2009 STATUS ONLINE LINEV 3 12220 Volks LOADPCT 24 0 Percent Load Capacity BCHARGE 100 0 Percent TIMELEFT 144 5 Minutes MBATTCHG 5 Percent MINTIMEL 3 Minutes MAXTIME 0 Seconds SENSE Medium LOTRANS s 097 0 iO Wate HITRANS s Iss 0 Wwollies ALARMDEL Always BATTV S 2653 Volts AASSTXFER Low line voltage NUMXFERS 0 TONBATT O seconds CUMONBATT 0 seconds XOFFBA N A SELFTEST NO STATFLAG 0x07000008 Status Flag MANDATE 2003 05 08 SERIALNO JB0319033692 BATT DATE eZ OOM SO 9S 25 NOMINV g 120 NOMBATTV 24 0 FIRMWARE 8 g6 D USB FW g6 APCMODEL Back UPS RS 1500 TND ABE 8 Sy Wore 26 17422352 BDE 2009 Status Report Fields The meaning of the above variables are APC Header record indicating the STATUS format revision level the number of records that follow the APC statement and the number of bytes that follow the record DATE The date and time that the information was last obtained from the UPS HOSTNAME The name of the m
95. e that if you close or disable the tray icon this does not stop or disable the apcupsd service which will continue to monitor the UPS and shutdown the computer when appropriate To stop or disable the service use the service control panel apctray has the capability of monitoring multiple apcupsd instances using apcupsd s Network Information Server NIS It will create a new icon for each instance being monitored By default apctray monitors the local apcupsd localhost on port 3551 To add additional monitors you can right click an existing icon and choose Add Monitor To remove a monitor right click its icon and choose Remove Monitor To change thr settings for an existing monitor ip address port refresh rate right click its icon and choose Configure apctray can be installed standalone without apcupsd if you wish to use it only to monitor remote apcupsd instances This can be convenient for keeping an eye on a room full of UPSes from your desktop Download and run the normal apcupsd installer and simply uncheck all components except apctray Then add as many monitors as you wish as described above Testing Apcupsd on Windows It would be hard to overemphasize the need to do a full testing of your installation of apcupsd as there are a number of reasons why it may not behave properly in a real power failure situation Please read the Testing Apcupsd section of this document for general instructions on testing the Win32 versi
96. e that your web server can access it At many sites the Apache server is not running as root so you must be careful to ensure that that etc apcupsd hosts conf and etc apcupsd multimon conf are world readable To invoke multimon in your Web browser enter http your site cgi bin multimon cgi You should get something similar to the screen shot shown below If you wish additional control over the colors type faces and sizes of the multimon output you may simply edit the apcupsd css file to specify the styles you prefer Using the CGI Programs on Windows The CGI programs compiled for Windows are included in the Windows package starting with apcupsd 3 14 7 The CGI programs included with the Windows package are intended to be run on Windows If your web server is running on Linux or another operating system you will need to obtain binary packages for that platform or build them from source instead The windows build of the CGI programs has been tested with the Apache web server for Win32 They should also work with MS Internet Information Server IIS To use the programs copy the contents of the cgi directory from your apcupsd installation directory to the cgi bin directory of your web server Consult your web server s documentation for how to enable CGI programs to be executed Sometimes special security settings are required Configure the hosts conf file as described above The programs expect to find the hosts conf file an
97. e utility power back on and let it recharge Recharge time can take up to 4 hours Resetting the UPS Battery Constant In some cases none of the battery runtime calibration methods result in the UPS reporting a reasonably correct battery runtime It has been speculated that this is because the battery constant value has drifted so far from normal that the microprocessor in the UPS cannot correct it The good news is that if you are located in the USA all you have to do is contact APC Technical Support and they will send you a serial port dongle which plugs into the serial port of your UPS and reprograms the battery constant value for you to the correct value The bad news is that for many users outside the USA this service does not appear to be available It is however recommended that you first try contacting APC Technical Support to verify the correct battery constant value The APC representatives in the Support Forum on the APC website are also very helpful in this regard If all else fails the information below is for you WARNING Only the values for the Smart UPS 700 model SU700 and Smart UPS 1400 model SU1400 both with international firmware and therefore international voltage have been verified YOU gentle reader USE THIS INFORMATION AT YOUR OWN RISK in the full knowledge that you may render your UPS inoperable and perhaps irreparable and you will have no one to blame but yourself Caveat Utilitor The battery constant is t
98. ected during the test Item 5 is used to program the EEPROM Please see the Configuration Directives Used to Set the UPS EEPROM chapter of this manual for the details Item 6 will initiate a direct communication between your terminal and the UPS at which point you can enter raw UPS commands Please be aware that you should be careful what commands you enter because you can cause your UPS to suddenly shutdown or you can modify the EEPROM in a way to disable your UPS The details of the raw Smart mode UPS commands can be found in the APC Smart Protocol chapter of this manual Item 7 will terminate apctest Monitoring and Tuning your UPS After you have verified that your UPS is working correctly you will probably want to query the state of its health occasionally The tools apcupsd gives you to do this include one command line utility apcaccess and a GUI you can use through a Web browser You can also use apctest to tune some parameters of the UPS itself apcaccess apcaccess is a program normally found in sbin apcaccess that permits you to print out the complete status of your UPS apcaccess will use the Network Information Server to obtain the necessary information You can specify a second optional argument to apcaccess in the form of host port where the port is optional The default is Localhost 3551 Please note that in versions prior to 3 10 6 the default NIS port was 7000 so if you are mixing versions you will need to take
99. ed But it s easy to prevent this and you should Disconnect the UPS and boot the system When you get to a login prompt log in as root Type the following command eeprom coml noprobe true or eeprom com2 noprobe true depending on which com port your UPS is attached to Then sync and shutdown the system normally reattach the UPS and reboot This should solve the problem However we have some reports that recent versions of Solaris 7 amp 8 appear to have removed this eeprom option and there seems to be no way to suppress the serial port probing during boot At this point you should have a complete installation The daemon will load automatically at the next boot Watch for any error messages during boot and check the event logs in etc apcupsd If everything looks OK you can try testing the package by removing power from the UPS NOTE if you have a voltage signalling UPS please run the first power tests with your computer plugged into the wall rather than into the UPS This is because dumb serial port UPSes have a tendency to power off if your configuration or cable are not correct As a user your input is very helpful in solving problems with the package and providing suggestions and future directions for the development of the package We are striving to provide a useful package that works across all platforms and welcome your feedback Unknown System During the configure if apcupsd does not find one of the systems f
100. el Configuration Users of OpenBSD NetBSD and some versions of FreeBSD will need to rebuild the kernel in order to enable the ugen driver and disable the uhid driver uhid is not sufficient for apcupsd at this time and we need to prevent it from grabbing the UPS device You should make the following changes to your kernel config file FreeBSD v5 4 and below v6 0 you will not lose use of USB keyboard and mouse Disable uhid Enable ugen FreeBSD v5 5 v6 1 and above you will not lose use of USB keyboard and mouse Disable nothing Enable ugen This is the default configuration for a GENERIC kernel on many platforms so you most likely will not need to recompile NetBSD v3 x and below you will lose use of USB keyboard and mouse Disable uhidev ums wsmouse ukbd wskbd uhid Enable ugen NetBSD v4 0 and above You can use apcupsd on single USB port without disabling the USB keyboard and mouse on other ports though all other devices will be disabled on the port you pick for your UPS First decide which hub and port you wish to use You can find out the hub and port numbers for any particular physical connector by plugging a USB device into it and looking at the messages printed by the kernel you should messages something like this uxx0 at uhubO port 1 uxx0 lt some device name gt To use your APC UPS on this port configure the kernel to prefer attachment of the ugen driver over other drivers on this hub
101. enough to configure the correct device in your apcupsd conf configuration file The directive needed for this configuration is DEVICE lt host gt lt port gt lt vendor gt lt community gt where the directive is made by four parts All but the first may be omitted completely or left empty to accept the default e host IP address or DNS hostname of the UPS required e port Remote SNMP port optional default 161 e vendor The type of SNMP MIB available on the UPS optional default autodetect Allowable choices for vendor are e APC APC PowerNet MIB used on most APC brand UPSes e RFC RFC1628 MIB used by some non APC UPSes e MGE MGE MIB used by many MGE brand UPSes blank Autodetect Append _NOTRAP to the vendor name to disable SNMP trap catching ex APC_NOTRAP See SNMP Trap Catching community The read write community string usually private You can specify a read only community string usually public if you do not require killpower support If the community string is omitted apcupsd will attempt to autotedect by trying private and public optional default autodetect A NIS Server Client Master Slave configuration with multiple servers is still applicable However an alternative configuration is possible with an SNMP enabled UPS In this arrangement all connected servers will be configured as a standalone server Each will independently communicate to the UPS One primary server w
102. ernels You simply get a serial to USB adapter that is supported by the kernel plug it in and make one minor change to your apcupsd conf file and away you go Kern adds Thanks to Joe Acosta for pointing this out to me The device that Joe Acosta and Kern are using is Ogear GUC232A USB 2 serial adapter Bill Marr informs us that it also works with a Back UPS Pro 650 and the 940 0095B cable At Kern s site running Red Hat 7 1 with kernel 2 4 9 12 he simply changed his etc apcupsd apcupsd conf configuration line to be DEVICE dev ttyUSBO Depending on whether or not you have hotplug working you may need to explicitly load the kernel modules usbserial and p12303 In Kern s case this was not necessary Testing Serial Line UPSes If you have a serial line UPS there are some tests you should run before the general ones described in the Testing Apcupsd section To test your computer s connection with a serial line UPS you first need to establish that the serial line is functioning and then that the UPS is responding to commands This can be a bit tricky especially with a dumb voltage signalling interface because it is completely quiescent when there are no commands being passed and the command repertoire doesn t include any self tests Because it is easy to configure a serial cable incorrectly in such a way as to cause premature shutdowns of the UPS power we strongly recommend especially for voltage signaling dumb UPSes that you
103. ferences including address server information etc Then rename the script files without the example suffix Scripts are supplied for onbattery offbattery and commfailure events You can copy the scripts to other filenames and modify the email body text to respond to other events as described in Customizing Event Handling Killpower under Windows If your batteries become exhausted during a power failure and you want your machine to automatically reboot when the power comes back it is useful to implement the killpower feature of the UPS where apcupsd sends the UPS the command to shut off the power In doing so the power will be cut to your PC and if your BIOS is properly setup the machine will automatically reboot when the power comes back This is important for servers This feature is implemented on Unix systems by first requesting a system shutdown As a part of the shutdown apcupsd is terminated by the system but the shutdown process executes a script where apcupsd is recalled after the disks are synced and the machine is idle Apcupsd then requests the UPS to shut off the power killpower Unfortunately on Windows there is no such shutdown script that we are aware of and no way for apcupsd to get control after the machine is idled If this feature is important to you it is possible to do it by telling apcupsd to immediately issue the killpower command after issuing the shutdown request The danger in doing so is that if the mach
104. find and change the appropriate configuration parameter to permit instant power on Normally this is located under the BOOT menu item and will be called something such as Restore on AC Power Loss of Full On The exact words will vary according to the ROM BIOS provider Generally you will have three options Last State Power On and Power Off Although Last State should normally work we recommend setting your computers to Power On This means that whenever the power is applied they are on The only way to shut them off is to pull the plug or to have a special program that powers them off sbin poweroff on Linux systems If after making all the changes suggested above you cannot get your computer to automatically reboot you might examine your halt script etc rc d init d halt in the case of Red Hat Linux and see if the final line that performs the halt or reboot contains the p option for powering down the computer It should not with the logic used by apcupsd but if it does the p option could cause your computer to power off while the UPS is still suppling power i e before the UPS kills the power Depending on the setting of your BIOS it may prevent your computer from restarting when the power returns As already mentioned this should not apply but in case of problems it is worth a try Making sure apcupsd Is Running The simplest way to invoke apcupsd is from the command line by entering sbin apcupsd To do so you must be root
105. forming an upgrade it will of course not replace your current config file The build directive Cleiciiaes Monille mso IL is no longer recognized What other defines are used There is a define for the initdir for the daemon control script On RedHat or Mandrake systems this is set to etc rc d init d On SuSE systems this is set to etc rc d You would only need to edit this if packaging for a platform that uses a different directory A second define controls whether the Gnome monitoring application new in the 3 14 release is built This application requires the Gtk2 version to be gt 2 4 If you want to build the apcupsd gapcmon package add define build_gapcmon 1 A third define controls whether the SNMP driver is built If you want to build the net snmp driver add define build_snmp 1 Can I supply packages for other platforms you do not publish Yes there are tools provided for contributors to supply rpm packages for platforms for which support is provided in the spec file but for which the development team chooses not to release binary packages usually due to lack of interest or lack of an available platform Please see platforms contrib README in the source package I m getting errors about not having permission when I try to build the packages Do need to be root No you do not need to be root and in fact it is better practice to build rom packages as a non root user Apcupsd s packages are designed to
106. g gone high i e power is restored RTS which apcupsd sets for the killpower signal to cause the UPS to shut off the power Please note that these actions apply only to the SIMPLE cable The signals used on the other cables are different Finally here is another way of looking at the CUSTOM SIMPLE cable ARICUR SD oLMPLES CUS LOM ICABINE Computer Side Description of Cable UPS Side DIS DEPASE DB9m DB25m 4 20 DERI Sviee below n c 8 5 CTS low battery below lt 5 7 2 3 RxD no line voltage below lt 3 2 5 7 Ground Signal 4 20 ii 8 CD on battery from UPS lt 2 3 T 4 RTS kill UPS power 1 8 a e 1 Frame Case Gnd optional 9 22 Note the lt and gt indicate the signal direction When using this cable with apcupsd specify the following in apcupsd conf UPSCABLE simple UPSTYPE dumb DEVICE dev ttyS0O or whatever your serial port is Custom RJ45 Smart Signalling Cable for BackUPS CS Models If you have a BackUPS CS you are probably either using it with the USB cable that is supplied or with the 940 0128A supplied by APC which permits running the UPS in dumb mode By building your own cable you can now run the BackUPS CS models and perhaps also the ES models using smart signalling and have all the same information that is available as running it in USB mode The jack in the UPS is actually a 10 pin RJ45 However you can just as easily u
107. he Basic User s Guide If your operating system is older or if you have an old fashioned serial line UPS you ll have to read about serial installation see Installation Serial Line UPSes If you need more details about administration for unusual situations such as a master slave or multi UPS setup you ll need to read the sections on those topics as well Finally there are a number of technical reference sections which gives full details on things like configuration file directives and event logging formats You should begin by reading the Quick Start see Quick Start for Beginners instructions Basic User s Guide Quick Start for Beginners apcupsd is a complex piece of software but most of its complexities are meant for dealing with older hardware and operating systems On current hardware and software getting it running should not be very complicated The following is a help guide to the steps needed to get apcupsd set up and running as painlessly as possible 1 Check to see if apcupsd supports your UPS and cable see Supported UPSes and Cables 2 Check to see if apcupsd supports your operating system see Supported Operating Systems 3 Plan your configuration type see Choosing a Configuration Type If you have just one UPS and one computer this is easy If you have more than one machine being served by the same UPS or more than one UPS supplying power to computers that are on the same local network you have more choices to
108. he hex number in the column labelled 0 presumably for register 0 in the following table UPS Model As 6 Hex Firmware SUSO EE F8 Bl SU400 ina PS Oy El SU600 EA F4 9F 15 5 SU900 igs FG Or ED SUL25O EE FA 9F ES SU2000 ip il ie Oe FD SU450 700 20 2 IN 96 O77 RMR of ii 1 SU450XL 700XL 28 EE F8 9F 700XL 27 Si 9 i SU1000 INET 3S ine ig 7X0 OB 60 dit I SU1LOOOXL 34 EE FC 9A 2B 61 9 1 SU1400 SS 11a IO SYA Og AL 5 SU1400RM 28 ED FA 89 SU1L400R21BX135 08 B4 10 A3 SU1400RMXLI3U 45 F6 F4 80 Usa L SU1400RMXLI3U ZORE TEDES Teea l SU2200I1 35 EE FB AF SHO 5 LA a SU2200XL 3000 35 EE FB AF 3000 17 SHO LA a SU3000RMXLI3Ub1k 35 F3 F4 AF a 93 da SU5000I white 20 F2 FA 91 1F AAO AT SU1400XL XLI RM 45 F6 E4 80 SU4201 25 95 Of 35 16 lk 5 fo I SU420SI1 OEMS OAR SE SU620I1 29 QS OB BA 1A BP420SI OEM Ia OAS SE 06 AE Ube et BP650SI 10 97 0C 9i OA ers peal POW ete Siecle kien 0 MU Carooan Ome Ey 265 So IL Power Stack 450 OD 96 10 99 36 216 5S o IL SC250RMI1U OC 95 Or B3 32 V35 04 5 A SCc4201 OH Iam OAOE IRG TEE SCO Om I 97 8 OY 1A Oaza E SEMO OOM 08 95 10 4 8A UST ool SCARS OOM O7 95 14 wip 1E USE oko E SULOOOXL iy ims 199 DS MATRIX 3000 5000 E9 F5 BO SU700RMI2U O7 BL OD 92 8A 152 450 SULOOORMI2U 0S Bo OD CV 8E nS Got ode SU1400RMI2U 08 B4 10 A3 92 162 5301 SUA1LOOOTLI O7 BS 13 BG OA 652 12 1 SUA1LOOOXLI OB BD OF 7F 4A GSil 4 Bo I SUA750XLI OA B
109. he right place If your sbin rcO file does not look like the lines shown above do not modify the file Instead email a copy of the file to the maintainers and we will attempt to figure out what you should do If you mess up this file the system will not shut down cleanly and you could lose data Don t take the chance You will then need to make the normal changes to the etc apcupsd apcupsd conf file This file contains the configuration settings for the package It is important that you set the values to match your UPS model and cable type and the serial port that you have attached the UPS to People have used both dev ttya and dev ttyb with no problems You should be sure that logins are disabled on the port you are going to use otherwise you will not be able to communicate with the UPS If you are not sure that logins are disabled for the port run the admintool program as root and disable the port The admintool program is a GUI administration program and required that you are running CDE OpenWindows or another XWindows program such as KDE Solaris probes the serial ports during boot and during this process it toggles some handshaking lines used by dumb UPSes As a result particularly for simple signalling dumb UPSes it seems to kick it into a mode that makes the UPS think it s either in a calibration run or some self test mode Since at this point we are really not communicating with the UPS it s pretty hard to tell what happen
110. heir own decisions PowerChute Network Shutdown Driver PCNET As of 3 14 Apcupsd supports the PowerChute Network Shutdown protocol This is an alternative to SNMP for use with APC s AP9617 family of network smartslot modules Note that the older AP9606 modules do not support PCNET To enable PCNET support configure with the nable pcnet flag This is typically enabled by default The required apcupsd conf settings are straightforward apcupsd conf v1 1 UPSCABLE ether UPS iP Emenee LOCKFILE var lock DEVICE ipaddr user passphrase UPSCLASS standalone UPSMODE disable The DEVICE setting specifies the IP address of the UPS as well as the username and authentication passphrase to use Note that the username and passphrase are not the Web SNMP login credentials They are separate settings The default username on a new card is apc and the default passphrase is admin user phrase To change the passphrase log in to the Web UI and go to the UPS tab then to PowerChute gt Configuration This assumes firmware v3 3 1 Other versions may place the setting elsewhere The password must be a minimum of 15 characters long The web UI will silently ignore shorter passwords and does not give an error message There is no apparent way to change the username Note that you may leave DEVICE blank and Apcupsd will accept information from any PCNET UPS on the network however it will be ver
111. here is to it There are still some rough edges to clean up but overall this is a ot easier with apcupsd 3 14 x than it used to be Support for SNMP UPSes To run apcupsd with a SNMP UPS you need the following things e An SNMP UPS for example a Web SNMP AP9716 or PowerNet SNMP AP9605 card installed into the SmartSlot Apcupsd also has support for some non APC SNMP UPSes using RFC1628 or MGE MIBs however the majority of the information in this section is for APC UPSes Planning and Setup for SNMP Wiring SNMP packet requests are relayed to the UPS from monitoring APCUPSD servers over Ethernet via a switch hub or router Protecting these Ethernet devices with UPS supplied power is necessary to ensure reliable SNMP communication during power failures Servers may fail to shutdown quietly during power failures if SNMP communication is lost Planning and Setup for SNMP Configuration To establish communication to the UPS SNMP card installed in the UPS the SNMP card will need the following e Assign SNMP card IP Address e Set SNMP card General Parameters e Set SNMP card Shutdown Parameters e Set SNMP card Event Trap Receivers apcupsd 3 12 0 and later Assign SNMP Card IP Address The following instructions come from the APC knowledge base The Network Management Card AP9617 AP9618 AP9619 must be configured with network settings before it can communicate on the network Once the cards have been configured with an IP addre
112. highly recommended if you have more than one UPS connected to the same server since rearranging your USB cables or even upgrading the kernel can affect the order in which devices are detected and thus change which hiddev node corresponds to which UPS If you use the symlink by serial number approach the link will always point to the correct device node You can use udevinfo a p sys class usb hiddev0 to get more information on the fields that can be matched besides serial number To find the available attributes to match note that the serial is NOT always the UPS serial on the box or in the USB connect message in var log messages use udevadm info attribute walk name dev usb hiddev0O An additional device node related problem is the use of dynamic minors Some distributions such as Mandrake 10 ship with a kernel having CONFIG_USB_DYNAMIC_MINORS turned on This is not ideal for running with apcupsd and the easiest solution is to turn CONFIG_USB_DYNAMIC_MINOoRS off and rebuild your kernel or find a pre built kernel with it off For a kernel with CONFTG_USB_DYNAMIC_MINORS turned on to work with apcupsd you must enable devfs The following will tell you if devfs is enabled 9 ps ax greo cevs which should give something like the following 599 2 S 0 00 devfsd dev What complicates the situation much more on Mandrake kernels is their security level since CONFIG_DYNAMIC_USB_MINORS is turned on but on higher securi
113. ial port e Ensure that you have no other programs that are using the serial port One user reported that he had problems because the serial port mouse gpm was using the same port as apcupsd This causes intermittent seemingly random problems e Try connecting your UPS to another machine If it works then you probably have a bad serial port card As unlikely as this may sound at least two of our users have had to replace bad serial port cards e Try doing an lsof dev ttySo0 where you replace the dev ttys0 with your serial port name If you get no output the port is free or there is no physical port If you get output then another program is using the port and you should see which one e Try doing a dmesg grep tty This may show you if a program has grabbed the port Thanks to Joe Acosta for the suggestion e If all else fails make sure your system is configured for serial port support The first thing to do is to look at your log file usually var log messages because apcupsd writes more detailed information to the log file whenever there is an error If you have a UPS that uses apcsmart protocol you can manually test the serial communications with the UPS by starting a serial port communications program such as minicom tip or cu with the settings 2400 8N1 2400 baud 8 data bits no parity 1 stop bit Be extremely careful what you send to your UPS as certain characters may cause it to power down or may even cause da
114. igure program Configuration Directives Used by the Network Information Server None of these directives are required for proper operation of apcupsd NETSERVER on off This configuration directive turns the network information server on or off If it is on apcupsd will spawn a child process that serves STATUS and EVENTS information over the network This information is currently used by the Web based CGI programs The default is on This option is required to be turned on for net clients and apcaccess to function NISIP P address This directive specifies the IP address of the network interface on which the NIS server will listen for incoming connections Default value is 0 0 0 0 which means the NIS will listen for connections on all network interfaces If your machine has more than one interface you can specify the IP of a single interface to limit connections to only that interface Furthermore you can specify the loopback address 127 0 0 1 to accept connections only from the local machine You may also use the with nisip option of the configure program to set this directive during the build NISPORT port This configuration directive specifies the port to be used by the apcupsd Network Information Server The default is platform dependent but typically 3551 which we have received from IANA as the official apcupsd networking port This value should only be changed if it conflicts with an existing se
115. ill automatically search for your device in the standard places If you specify a DEVICE it should be the name of the device that apcupsd is to use to communicate with the UPS If the first time you execute apcupsd you get a message to the effect that the Apcupsd USB driver is missing it means that you most likely forgot to put enable usb on your configure command line The Configuration Examples chapter of this manual provides the essential characteristics of each main type of configuration file After those elements are correct apcupsd should run and then it is only a matter of customization of your setup Arranging for Reboot on Power Up The final consideration for a automatic reboot after a full power down is to ensure that your computer will automatically reboot when the power is restored This is not the normal behavior of most computers as shipped from the factory Normally after the power is cut and restored you must explicitly press a button for the power to actually be turned on You can test your computer by powering it down shutting off the power pull the plug then plugging the cord back in If your computer immediately starts up good There is nothing more to do If your computer does not start up manually turn on the power by pressing the power on button and enter your computer s SETUP program often by pressing DEL during the power up sequence sometimes by pressing F10 You must then
116. ill be chosen to manage the task of commanding the UPS to power down All remaining secondary servers will be configured to quietly power down before the primary server issues the UPS power down command Building with SNMP support Follow the instructions in Building and Installing apcupsd being sure to include the following options in addition to any others you need on the configure line configure enable snmp SNMP Trap Catching apcupsd 3 11 14 introduces support for SNMP trap catching Previous versions polled the UPS status once per minute leading to significant delays before UPS state changes were recognized With SNMP trap handling apcupsd monitors the SNMP trap port and will re poll the UPS whenever a trap is received This happens for example when the UPS switches on or off battery In order for this feature to work you must configure your UPS to deliver traps to the server running apcupsd This is generally done by connecting to your SNMP card via a web browser or telnet connection You will need to enter your server s IP address as a trap receiver and make sure trap delivery is enabled Trap catching can lead to problems if you are already running another SNMP trap daemon on your server Only one daemon can listen to the trap port so whichever one is started first will succeed and the others will fail Apcupsd will fall back to polling behavior if it is unable to open the trap port You can also forcibly disable tra
117. ill be replaced by a daemon operation that can be performed on all types of UPS This section does not apply to voltage signalling or dumb UPSes such as the older BackUPS models Smart UPSes internally compute the remaining runtime and apcupsd uses the value supplied by the UPS As the batteries age after say two or three years the runtime computation may no longer be accurate since the batteries no longer hold the same charge As a consequence in the event of a power failure the UPS and thus apcupsd can report a runtime of 5 minutes remaining when in fact only one minute remains This can lead to a shutdown before you might expect it because regardless of the runtime remaining that is reported the UPS will always correctly detect low batteries and report it thus causing apcupsd to correctly shutdown your computer If you wish to have the UPS recalibrate the remaining runtime calculations you can do so manually as the current version of apcupsd does not support this feature To do so e Shutdown apcupsd e contact your UPS directly using some terminal program such as minicom tip or cu with the settings 2400 8N1 2400 baud 8 bits no parity 1 stop bit Be extremely careful what you send to your UPS as certain characters may cause it to power down or may even cause damage to the UPS Try sending an upper case Y to the UPS without a return at the end It should respond with sm If this is not the case read the chapter on testing If yo
118. imes it is necessary to reset this microprocessor especially after the installation of new batteries Stop the PowerChute plus or apcupsd software from running and disconnect the serial cable There must be at least a 30 load attached to the UPS during this procedure but the process will cause the UPS to shut off and cut power to its outlets Therefore attach a non critical load to the UPS and then force the UPS on battery by disconnecting it from utility power suggest not disconnecting but simply turning off utility power thereby preserving earthing Allow the unit to run on battery until it turns off completely Make sure a 30 load is present Plug the UPS back into the wall outlet switch utility power back on and allow it to recharge it will recharge more quickly turned off and with no load present Once the unit has recharged the runtime remaining calculation should be more accurate Remember that if the unit is an older model then the runtime will not improve significantly Background An APC Smart UPS has a microprocessor which calculates runtime primarily based on the load attached to the UPS and on its battery capacity On the right side of the front display panel there is a vertical graph of five LEDs Each LED is an indication of battery charge in increments of twenty percent 20 40 60 80 100 bottom to top For example if the battery charge is 99 then only four of the five LEDs are illuminated To ensure that an ope
119. inally introduced for Smart UPS models thus the name apcsmart this class of UPS is in decline rapidly being replaced in APC s product line by USB and MODBUS UPSes usb A USB UPS speaks a universal well defined control language over a USB wire Most of APC s lineup now uses this method as of late 2003 and it seems likely to completely take over in their low and middle range The most recent APC UPSes support only a limited set of data over the USB interface MODBUS see below is required in order to access the advanced data net This is the keyword to specify if you are using your UPS in Slave mode i e the machine is not directly connected to the UPS but to another machine which is and it is connected to the Master via an ethernet connection You must have apcupsd s Network Information Services NIS turned on for this mode to work Platforms on which apcupsd is regularly developed and tested Platforms for which apcupsd team distributes binary packages Port included in apcupsd source tree but may be out of date unmaintained or broken 4 USB not supported On snmp SNMP UPSes communicate via an Ethernet NIC and firmware that speaks Simple Network Management Protocol dumb A dumb or voltage signaling UPS and its computer communicate through the control lines not the data lines on an RS232C serial connection Not much can actually be conveyed this way other than an order to shut down Voltage signaling UPSes a
120. ine is not sufficiently idled when the killpower takes place the disks will need to be rescanned and there is a possibility of lost data however small Generally UPSes have a shutdown grace period which gives sufficient time for the OS to shutdown before the power is cut To implement this feature you need to add the p option to the apcupsd command line that is executed by the system Currently the procedure is manual You do so by editing the registry and changing the line c apcupsd apcupsd exe service found under the key HKEY_LOCAL_MACHINE Software Microsoft Windows CurrentVersion RunServices to c apcupsd apcupsd exe servic 2 If you have a Smart UPS you can configure the kill power grace period and you might want to set it to 3 minutes If you have a dumb UPS there is no grace period and you should not use this procedure If you have a Back UPS CS or ES these UPSes generally have a fixed grace period of 2 minutes which is probably sufficient Power Down During Shutdown Our philosophy is to shutdown a computer but not to power it down itself as opposed to having the UPS cut the power as described above That is we prefer to idle a computer but leave it running This has the advantage that in a power fail situation if the killpower function described above does not work the computer will continue to draw down the batteries and the UPS will hopefully shutoff before the power is restore thus permitting an automatic reboo
121. ini file Find the line that looks something like the following multi 0 disk 0 rdisk 0 partition 1 WINNT Windows NT Workstation Version 4 00 and add the following to the end of the line NoSerialMice COM1 or COM2 depending on what you want to use The new line should look similar to multi 0 disk 0 rdisk 0 partition 1 WINNT Windows NT Workstation Version 4 00 NoSerialMice COM1 where the only thing you have changed is to append to the end of the line This addition will prevent the operating system from interfering with apcupsd Starting Apcupsd on Windows The installer will give you an opportunity start the Apcupsd service immediately If you choose to start it manually you may do so by selecting the Start Apcupsd link from the Start gt Programs gt Apcupsd folder On Windows NT 2000 XP you may alternatively go to the Control Panel open the Services folder select Apcupsd UPS Server and then click on the Start button as shown below Services Senice tus Startup Close Start C Stat Starter Alerter Startec st st d d tated d Stated Automatic Startup HW Profiles Startup Parameters ne Help If the Services dialog reports a problem it is normally because your DEVICE statement does not contain the correct serial port name You probably should also click on the Startup button to ensure that the correct defaults are set The dia
122. ions taken on the basis of information in the manual nor for any error in or omission from the manual and 2 the authors contributors and editors are not engaged in rendering technical or other advice or services The the authors contributors and editors expressly disclaim all and any liability and responsibility to any person whether a reader of the manual or not in respect of anything and of the consequences of anything done or omitted to be done by any such person in reliance whether wholly or partially on the whole or any part of the contents of the manual Without limiting the generality of the above no author contributor or editor shall have any responsibility for any act or omission of any other author contributor or editor How To Use This Manual This is the manual for apcupsd a daemon for communicating with UPSes Uninterruptible Power Supplies made by American Power Conversion Corporation APC If you have an APC made UPS whether sold under the APC nameplate or OEMed for example the HP PowerTrust 2997A and you want you get it working with a computer running Linux Unix or Windows you are reading the right document This manual is divided into parts which increase in technical depth as they go If you have just bought a state of the art smart UPS with a USB or Ethernet interface and you are running a current version of Red Hat or SUSE Linux then apcupsd is very nearly plug and play and you will have to read only t
123. ir option of the configure program to change the default at compile time KILLDELAY time in seconds If KILLDELAY is set apcupsd will continue running after a shutdown has been requested and after the specified time in seconds apcupsd will attempt to shut off the UPS the power This directive should normally be disabled by setting the value to zero but on some systems such as Win32 systems apcupsd cannot regain control after a shutdown to force the UPS to shut off the power In this case with proper consideration for the timing the KILLDELAY directive can be useful Please be aware if you cause apcupsd to kill the power to your computer too early the system and the disks may not have been properly prepared In addition apcupsd must continue running after the shutdown is requested and on Unix systems this is not normally the case as the system will terminate all processes during the shutdown SCRIPTDIR path to apccontrol dir This option configures the directory in which apccontrol and other event scripts are located Normally the configure program will set an appropriate default value for your platform often etc apcupsd PWRFAILDIR path to powerfail dir When apcupsd shuts down your system it creates a temporary flag file which is used by the operating system halt scripts to know if this shutdown is due to a power failure This directive configures which directory the flag file will be writte
124. is 1 if the computer on which apcupsd is running is powered by the UPS and 0 if not At the moment this value is unimplemented and always 0 The following event names are supported annoyme When a shutdown is scheduled and the time specified on the ANNOYME directive in the apcupsd conf file expires this event is generated Default wall a message changeme When apcupsd detects that the mains are on but the battery is not functioning correctly this event is generated It is repeated every x hours Default wall a message commfailure This event is generated each time the communications line with the computer is severed This event is not detected on dumb signaling UPSes Default wall a message commok After a commfailure event is issued when the communications to the computer is re established this event will be generated Default wall a message doreboot This event is depreciated and should not be used Default Shuts down the system using shutdown h or similar doshutdown When the UPS is running on batteries and one of the limits expires time run load this event is generated to cause the machine to shutdown Default Shuts down the system using shutdown h or similar emergency Called for an emergency system shutdown What triggers such a shutdown is unclear After completing this event apcupsd will immediately initiate a doshutdown event Default wall a message failing This event is generated when the UPS is ru
125. is event does nothing but it can be overridden to notify users etc e After the configured ONBATTERYDELAY apcupsd calls etc apcupsd apccontrol onbattery which normally sends a message to all users informing them that the UPS is on batteries e When one of the conditions listed below occurs apcupsd issues a shutdown command by calling etc apcupsd apccontrol doshutdown which should perform a shutdown of your system using the system shutdown 8 command You can modify the behavior as described in Customizing Event Handling The conditions that trigger the shutdown can be any of the following e Running time on batteries have expired TIMEOUT e The battery runtime remaining is below the configured value BATTERYLEVEL e The estimated remaining runtime is below the configured value MINUTES e The UPS signals that the batteries are exhausted A shutdown could also be initiated if apcupsd detects that the batteries are no longer functioning correctly This case though very unusual can happen at any time even if there is proper mains voltage and etc apcupsd apccontrol emergency is called Just before initiating any shutdown through the apccontrol script apcupsd will create the file etc apcupsd powerfail This file will be used later in the shutdown sequence to recall apcupsd after syncing of the disks to initiate a power off of the UPS If the etc nologin file has not already been created it will norm
126. ision 50 9 D See Interpretation of the New Firmware Revision Decoding the example e 50 SKU variable length e 9 firmware revision eD country code D USA International A Asia J Japan M Canada UPS local id UPS_IDEN Writable variable Up to 8 letter identifier for keeping track of your hardware Return 00 Writable variable Minimum battery charge threshold before UPS will return online after a soft shutdown Possible values e 00 00 UPS turns on immediately 01 15 e 02 25 03 90 Battery level 099 0 Percentage of battery charge remaining Nominal 024 The battery voltage that s expected to be present battery in the UPS normally This is a constant based on voltage the type number and wiring of batteries in the UPS Typically 012 024 or 048 Measure UPS 042 4 Percentage Only works on models with ambient Measure UPS SmartSlot card humidity Measure UPS 00 Bitmapped hex variable Mapping dry contacts e 10 contact 1 e 20 contact 2 e 40 contact 3 e 80 contact 4 Estimated 0327 Value is in minutes Terminated with a colon runtime Alarm delay 0 Writable variable Controls behavior of UPS beeper Possible values e 0 5 second delay after power fail T 30 second delay e L alarm at low battery only N no alarm Low transfer 103 Writable variable UPS goes on battery when voltage voltage drops below thi
127. ivers they are associated with For example usbdevs d adda UHCi soot AUD MTA uhub0 addr 2 Back UPS RS 1500 FW 8 g6 D USB FW g6 American Power Conversion ugen0 Device Nodes Apcupsd communicates with the UPS through the USB generic device ugen You may or may not need to manually make ugen device nodes in dev depending on what OS you are using FreeBSD No manual intervention needed FreeBSD automatically creates the ugen nodes on demand NetBSD By default NetBSD only creates nodes for the first ugen device ugen0 Check usbdevs d to see which device your UPS was bound to and then create the appropriate node by running cd dev MAKEDEV ugenN where ugenN is the ugen device name shown by usbdevs It is probably a good idea to create several sets of ugen nodes in case you add more USB devices OpenBSD Similar to NetBSD OpenBSD creates nodes for ugen0 and ugen1 Check usbdevs d to see which device your UPS was bound to and then create the appropriate node by running cd dev MAKEDEV ugenN where ugenN is the ugen device name shown by usbdevs It is probably a good idea to create several sets of ugen nodes in case you add more USB devices Windows USB Configuration Platforms and Versions Apcupsd supports USB UPSes on Windows XP and newer including 64 bit systems USB Driver Installation USB connected UPSes on Windows require a special driver In most cases this driver is automatically ins
128. lation is very simple and straight forward Simply double click the installer executable and follow the instructions See The Windows Version of apcupsd for further details Installation from Source Installation from source might have to be be done different ways depending on what system you are running The basic procedure involves getting a source distribution running the configuration rebuilding and installing For building the system we suggest that you run the configure and make processes as your normal UNIX user ID The make install must be run as root But if your normal ID has an environment setup for using the C compiler it s simpler to do that than to set up root to have the correct environment apcupsd requires gcc and g compilers as well as GNU make Other compilers or BSD make will not work GNU make is sometimes installed as gmake The configure script will check for this and will inform you of what command to use to invoke GNU make The basic installation from a tar source file is rather simple Unpack the source code from its tar archive Go into the directory containing the source code Run configure with appropriate options as described below make or gmake as instructed by configure su i e become root oak WOOD Stop any running instance of apcupsd The command to do this will look like system dependent path apcupsd stop 7 uninstall any old apcupsd This is important since
129. les See the apcupsd System Logging section of this manual for additional details Configuration Directives for Sharing a UPS The following directives apply to sharing an UPS using a ShareUPS hardware module Most users will not use this mode UPSCLASS standalone shareslave sharemaster The default is standalone and should be used for all machines powered by the UPS and having a serial port or other direct connection to the UPS This is the normal case Use shareslave if and only if you are using a ShareUPS and connected to a BASIC Port with Simple Signal This code is not fully tested Use sharemaster if and only if you are using a ShareUPS and connected to the ADVANCED Port Smart Signal control This code is not fully tested UPSMODE disable share For normal standalone operations you will set UPSMODE disable to indicate that you are disabling the ShareUPS support Use share for two or seven additional simple signal ports on a SmartAccessories tm internal external box for SmartUPSes The share and sharenet code is not fully tested Configuration Directives Used to Set the UPS EEPROM These directives have no effect on the operation of apcupsd but are reserved for use by apctest when bulk programming the values of the UPS EEPROM configuration variables in a Smart UPS model UPSNAME lt string gt Name of UPS Maximum of 8 characters BATTDATE mm dd yy dd mm vy Last battery replacement date Maximum of 8 chara
130. load Main relay malfunction UPS turned off In sleep mode from command maybe others In shutdown mode from S command Battery charger failure Bypass relay malfunction N oO o A Ol NI O Normal operating temperature exceeded Interpretation of the Old Firmware Revision The Old Firmware Revision is obtained with the V command which gives a typical response such as GWD or IWI and can be interpreted as follows Old Firmware revision and model ID String for SmartUPS amp MatrixUPS This is a three character string XYZ where X Smart UPS or Matrix UES ID Code range 0 9 and A P 1 unknown O Matrix 3000 5 Matrix 5000 the rest are Smart UPS and Smart URS Xi 2 250 3 400 4 400 6 600 7 900 8 1250 9 2000 A 1400 B 1000 C 650 D 420 E 280 F 450 G 700 H 700XL I 1000 J 1000XL K 1400 L 1400XL M 2200 N 2200XL O 3000 P 5000 where Y Possible Level of Smart Features unknown G Stand Alone T Stand Alone PRR W Rack Mount where Z National Model Use Only Codes D Domestic PES Violkes I International 230 MViolktes A Asia 100 Volts J Japan 100 Volts Interpretation of the New Firmware Revision New Firmware revision and model ID String in NN M L is the format where NN UPS ID Code 12 Back UPS Pro 650 PE TECk UP Serr OmnOOl0 D2 somos
131. logue box that appears should have Startup Type set to Automatic and Logon should be set to System Account If these values are not set correctly by default please change them otherwise apcupsd will not work For WinXP and Win2K systems the dialogs are a bit different from those shown here for WinNT but he concept is the same You get to the Services dialog by clicking on Control Panel gt Administrative Tools gt Component Services The apcupsd service should appear in the right hand window when you click on Services Local in the left hand menu window That should complete the installation process When the system tray icon turns from a question mark into a plug right click on it and a menu will appear Select the Events item and the Events dialogue box should appear There should be no error messages By right clicking again on the system tray plug and selecting the Status item you can verify that all the values for your UPS are correct When the UPS switches to the battery the battery icon will appear in the system tray While the UPS is online if the battery is not at least 99 charged the plug icon will become a plug with a lightning bolt in the middle to indicate that the battery is charging Apctray Starting with version 3 14 2 the tray icon is provided by a separate program called apctray This cleanly separates the user interface from the daemon service and is required for tray icon support on Windows Vista Not
132. m RPMs for a slave machine you will need to remove the changes that the RPM install script made similar to what is noted above to the halt script This is because on a slave machine there is no connection to the UPS so there is no need to attempt to power off the UPS That will be done by the master Configure Options All the available configure options can be printed by entering configure help When specifying options for configure if in doubt don t put anything since normally the configuration process will determine the proper settings for your system The advantage of these options is that it permits you to customize your version of apcupsd If you save the configure command that you use to create apcupsd you can quickly reset the same customization in the next version of apcupsd by simply re using the same command The following command line options are available for configure to customize your installation prefix path This defines the directory for the non executable files such as the manuals The default is usr sbindir path This defines the directory for the executable files such as apcupsd The default is sbin You may be tempted to place the executable files in ustr sbin or usr local sbin Please use caution here as these directories may be unmounted during a shutdown and thus may prevent the halt script from calling apcupsd to turn off the UPS power Though your data will be protected in this ca
133. machine back into the UPS You can also minimize the risk from an unexpected shutdown by using a journaling filesystem such as Linux s EXT3 All modern disk drives park themselves safely when they power down rather than ploughing up oxide on your disk s recording surface Thus unexpected power less has to hit very narrow timing windows in order to trash an EXT3 transaction To begin the test pull the power plug from the UPS The first time that you do this psychologically it won t be easy but after you have pulled the plug a few times you may even come to enjoy it If all goes well apcupsd should detect the power failure and print several warning messages The first should appear after 5 to 6 seconds and read Warning power loss detected Then generally 6 seconds later apcupsd is sure that it isn t a transient effect so it sends Power failure Running on UPS batteries After a few more seconds total around 15 seconds plug the power cord back in and ensure that apcupsd is aware that the power has returned It should print Power has returned If you do not observe the above messages please correct the situation before proceeding The most likely cause of problems are apcupsd doesn t recognize the power failure because the configuration directives are not correct E g wrong cable e The file etc apcupsd apccontrol doesn t exist or is not marked as executable System Shutdown Test This is an intermediate test that
134. mage to the UPS Try sending an upper case Y to the UPS without a return at the end It should respond with sm If this is not the case review the possible problems listed above If you fat finger the Y and enter y instead no cause for alarm you will simply get the APC copyright notice Once you are sure that serial port communications is working proceed to the next test Once you have established serial communications Once you have established that apcupsd can talk to the UPS over the serial part go do the series of functional tests described in the main Testing section see Testing Apcupsd Troubleshooting Serial Line communications The most frequently encountered problem with voltage signalling UPSes e g BackUPS 650 is that you have incorrectly specified which cable is being used All cables furnished by APC have the cable number stamped on the side of the computer connector end of the cable Using this number with apcupsd will normally work fine If you do not know what cable you have you can use the apctest program to determine the type of the cable For simple signaling UPSes you should not use simple in the cable specification i e UPSCABLE simple unless you have made the cable yourself according to the wiring diagram given in the cables chapter of this manual Bizarre Intermittent Behavior In one case a user reported that he received random incorrect values from the UPS in the status output It turned out that gom
135. most non Linux systems and on Linux 2 6 x kernels If you do not find that apcupsd is in the above list the most likely problem is a configuration file glitch If no messages were printed you should check your system log normally var log messages where you will find one or messages indicating the nature of the problem Logging Test Once you have established that the proper processes are running do a tail of the system log file normally var log messages tail var log messages You should see output that looks similar to the following Dec 5 17 01 05 matou apcupsd 5917 apcupsd 3 7 2 startup succeeded These messages should also appear in the temporary file etc apcupsd apcupsd events if you are using the default configuration file If you have installed the RPM they will probably be in var log apcupsd events apcaccess Test This test consists of running apcaccess to see if apcupsd is properly updating its internal variables Please note that you must enable the apcupsd Network Information Server in your configuration file for apcaccess to work This is done by setting NETSERVER on NS POR ms sSiomrk in your apcupsd conf file To run the apcaccess test use the following command ApCaeeesicmciecaeus Depending on the type of UPS you have you will get slightly different output but an example For a Smart UPS is as follows APC 001 048 1088 DATE 5 ied Dee OS 16649524 BSE 1999 HOSTNAME daughter RELEASE O
136. mple when a power fail occurs you may want to send an email message to root To write your own routine for the powerout action you create shell script named powerout and put it in the lib directory normally etc apcupsd When the powerout action is invoked by apcupsd apccontrol will first give control to your script If you want apccontrol to continue with the default action simply exit your script with an exit status of zero If you do not want apccontrol to continue with the default action your script should exit with the special exit code of 99 However in this case please be aware that you must ensure proper shutdown of your machine if necessary Some sample scripts onbattery and mainsback that email power failure messages can be found in etc apcupsd after an install or in the platforms etc directory of the source code apccontrol Command Line Options When apcupsd detects an event it calls the apccontrol script with four arguments as apccontrol event ups name connected powered where event is the event that occurred and it may be any one of the values described in the next section ups name is the name of the UPS as specified in the configuration file not the name in the EEPROM connected is 1 if apcupsd is connected to the UPS via a serial port or a USB port In most configurations this will be the case In the case of a Slave machine where apcupsd is not directly connected to the UPS this value will be 0 powered
137. n into The chosen directory must be writable by the user apcupsd is running as normally root and must not be cleared or unmounted early in the shutdown sequence Normally the configure program will set an appropriate default value for your platform often etc apcupsd You may also specify the with pwrfaildir option of the configure program to change the default at compile time Configuration Directives used to Control System Logging STATTIME time in seconds This directive supplies the time interval in seconds between writes to the STATUS file If set to zero the STATUS file will not be written Please note that in a future version of apcupsd the STATUS file code will disappear since its functionality has been replaced by the Network Information Server and by apcaccess status aS a consequence it is normally disabled by setting it to zero STATFILE file This directive specifies the file to be used when writing the STATUS information The default is etc apcupsd apcupsd status DATATIME time in seconds This directives supplies the time interval in seconds between writes of PowerChute like data information to the log file See the DATA Logging section of this manual for additional details FACILITY log facility The FACILITY directive can be used to change the system logging class or facility The default is DAEMON This parameter can be useful if you wish to direct the apcupsd system logging information to other than your system default fi
138. n recognized and is bound to the correct driver If your UPS doesn t appear in the list at all check the obvious things The UPS must be powered on and a cable must be properly seated in both the data port of the UPS and one of your machine s USB ports Many UPSes have phone ports to provide surge protection for phones or modems make sure you haven t plugged your USB cable into one of those rather than the data port which will usually be near the top edge of the case Also ensure that the correct drivers are loaded Under Linux 2 4 x you can check this out easily by examining the proc bus usb drivers file Here s how you can do that cat proc bus usb drivers and you should get usbdevfs hub TiC Mme aeee hid On Linux 2 6 x make sure the sysfs filesystem is mounted on sys and do ls 1 sys bus usb drivers where you should get total 0 Cheypcie XA X 2 TOC root OM Mayas oom nasal GEWE XA X Zee root O May 1 18 55 hiddev Ghee XA X 2T OOE root O May 1 sito hub drwxr xXr X 2 COO root OMay 1 8s o5 usb GEWX XA X ZOO root O May 1 U8soS usb s or perhaps something like total 0 Chapee Sek 2 Toor oore OW Jana 6 15 27 Inalekcley Chap eae A OO root WO Jaana 6 15 29 milo Chip 2 mood oort Q vain 6 15 289 veo Chapa A ROOr Toor WO vein 6 15 27 UEIS Cha pKe ek 2 moor CoE 0 Jan 6 15328 wsiloiniicl If your 2 6 x system does not have the sys bus usb directory either you do not have sysfs mounted on sys or the USB m
139. nce the last time this voltage query was run Minimum line 118 1 This is the min voltage since the last time this voltage query was run Output 118 3 Also see on battery output voltage voltage Power load 023 5 Relative to capacity of the UPS Status flags 08 Bitmapped see status bits below Turn dumb BYE Only on 3rd gen SmartUPS SmartUPS v s BackUPS Pro Must send enter smart mode command to resume comms Soft OK Command executes after grace period UPS goes shutdown online when power returns Only works when on battery Simulate then See Alert messages section for info on and power failure Old firmware GWD or IWI See Interpretation of the Old Firmware Revision revision Self test OK Tests battery like pushing button on the front panel Results stored in X Self test OK Possible values results OK good battery e BT failed due to insufficient capacity e NG failed due to overload e NO no results available no test performed in last 5 minutes Enter smart SM This must be sent before any other commands will mode work See also turn dumb command to exit smart mode Shutdown n a Send twice with gt 1 5s delay between chars UPS immediately switches load off immediately no grace period Protocol info long string Returns three main sections delimited by periods e Protocol version Alert messages aka async notifiers e Valid commands Firmware rev
140. nds sent as the body of a message 1 status The status command requests that the server send a copy of all status values in the form displayed by apcaccess After the client sends the status command the server will reply with a series of messges each one containing one line of apcaccess status data The end of the command series is indicated by an empty message length of 0 2 events The events command operates the same as status except the server replies with lines from the log of recent events As an example the following bytes would be sent by a client to solicit the status Os OOM 006 0ra 0274A 06L 0274 075 0213 The first two bytes are the data length 6 in network byte order The 6 bytes of data that follow are the ASCII characters for status The server will respond to this command with a series of its own messages containing the status data Apcupsd RPM Packaging FAQ How do I build Apcupsd for platform xxx The apcupsd spec file contains defines to build for several platforms RedHat 7 x rh7 RedHat 8 0 rh8 RedHat 9 rh9 Fedora Core fedora_core RedHat Enterprise Linux and clones rhel3 and rhel4 SUSE 9 amp 10 Suse and Mandrake mdk The package build is controlled by a define set at the beginning of the file These defines basically just control the dependency information that gets coded into the finished rpm package So while you could technically build a package without defining a platform
141. nning on batteries and the battery power is exhausted The event following this one will be a shutdown Default wall amessage loadlimit This event is generated when the battery charge is below the low limit specified in the apcupsd conf file After completing this event apcupsd will immediately initiate a doshutdown event Default wall a message powerout This event is generated immediately when apcupsd detects that the UPS has switched to batteries It may be due to a short powerfailure an automatic selftest of the UPS or a longer powerfailure Default wall a message onbattery This event is generated 5 or 6 seconds after an initial powerfailure is detected It means that apcupsd definitely considers the UPS to be on batteries The onset of this event can be delayed by the ONBATTERYDELAY apcupsd conf configuration directive Default wall a message offbattery This event is generated when the mains return only if the onbattery event has been generated Default wall amessage mainsback This event is generated when the mains power returns after a powerout condition The shutdown event may or may not have been generated depending on the parameters you have defined and the length of the power outage Default nothing remotedown This event is generated on a slave machine when it detects either that the master has shutdown or that a onbattery situation exists and the communications line has been severed Default wall a message r
142. odule s have not been loaded Check proc mounts to make sure sysfs is mounted A USB UPS needs all of these drivers the USB device filesystem the USB hub the Human Interface Device subsystem driver and the Human Interface Device driver If you are compiling your own kernel you want to enable CONF IG_USB CONFIG_USB_HID CONF IG_USB_HIDDEV CONFIG_USB_DEVICEFS as well as at least one USB Host Controller Driver CONEUGRUSBE UE Ciaer Clas GleinuiE7aOne CONRMGCRU SB Calas Ci mn IGU een Ore CONF IG_USB_UHCI CENU ARAR CONF IG_USB_OHCI Cpm 2e 4a Device Nodes Apcupsd accesses USB UPSes via the hiddev device nodes Typically these are located in dev hiddevN dev usb hiddevN or dev usb hiddev hiddevNn where N is a digit O thru 9 Some distributions some Debian releases possibly others do not provides these device nodes for you so you will have to make them yourself Check dev dev usb and dev usb hiddev and if you cannot find the hiddevN nodes run as root the examples make hiddev script from the apcupsd source distribution Modern Linux distributions using the 2 6 kernel create device nodes dynamically on the fly as they are needed It is basically a hotplug system giving a lot more power to the user to determine what happens when a device is probed or opened It is also a lot more complicated Some early 2 6 distributions Fedora Core 3 for one do not include hiddev rules in their default udev rule
143. oe CABLE APC Cable 940 0024C MODEL APC Smart UPS 600 UPSMODE Stand Alone UPSNAME SU600 LINEV a 122 1 VOLTS MAXLINEV 12353 Volts MINLINEV L225 i Woes LINEFREQ COMORE Z OUTPUTV UZ2 J Volts LOADPCT 32 7 Percent Load Capacity BATTV ZO nom Volts BCHARGE 095 0 Percent MBATTCHG 15 Percent TIMELEFT 19 0 Minutes MINTIMEL 3 Minutes SENSE Medium DWAKE 000 Seconds DSHUTD 020 Seconds LOTRANS HOGROM Volts HITRANS 129 0 Owes REE Cr 010 0 Percent STATFLAG 0x08 Status Flag STATUS ONLINE ITEMP 34 6 C Internal ALARMDEL Low Battery LASTXFER Unacceptable Utility Voltage Change SELFTES NO STESTI 336 DLOWBATT 05 Minutes DIPSW 0x00 Dip Switch REG1 N A REG2 N A REG3 0x00 Register 3 MANDATE 06713107495 SERIALNO 15035861 BATTDATE 0570579 NOMOUTV LiLS NOMBATTV 24 0 HUMIDITY N A AMBTEMP N A EXTBATTS N A BADBATTS N A FIRMWARE N A APCMODEL 6TD END APC ine Dee 05 16549525 BST 1999 For a simple signaling or dumb UPS such as BackUPS your output will be very minimal as follows DEGC DATE RELEASE UPSNAME CABLE MODEL UPSMODE START LINEFAIL BATTSTAT STATFLAG END APC IME 001 012 0319 Mom reb lg QHs TL50 CSE 2002 So Sind UPS_IDEN APC Cable 940 0128A BackUPS Stand Alone Mon Feb 18 09 11 45 CST 2002 OK OK Ox008 Status Flag Mom reb Le QA 150L CSE 2002 If you see the above output
144. of your Web server Once built and loaded they will give you the status of your UPS or UPSes via a web browser Normally only multimon cgi is directly invoked by the user However it is possible to directly invoke upsstats cgi and upsfstats cgi upsimage cgi should never be directly invoked as it is used by upsstats cgi to produce the bar charts Setting up and Testing the CGI Programs Before using multimon and the other CGI programs first ensure that apcupsd is configured to run the Network Information Server This is done by setting NETSERVER on in etc apcupsd apcupsd conf This switch is on by default Next you must edit the hosts file etc apcupsd hosts conf and at the end add the name of the hosts you want to monitor and a label string for them For example MONITOR matou Server MONITOR polymatou Backup server MONITOR deuter Disk server matou polymatou and deuter are the network names of the three machines currently running apcupsd Please note that the network names may either be IP addresses or fully qualified domain names The network name or IP address may optionally be followed by port where the port is the NIS port address you wish to use This is useful if you are running multiple copies of apcupsd on the same system or if you are running in a mixed vendor environment where the NIS port assignments differ An example could be the following MONITOR matou Server MONITOR polymatou Back
145. off the power To accomplish the same thing on FreeBSD systems make sure you have a SmartUPS and that your UPS shutdown grace period is set sufficiently long so that you system will power down usually 2 minutes the use the kill on powerfail option on the apcupsd command line HPUX Status of this port is unknown NetBSD You will need to install and use GNU make aka gmake instead of the BSD make supplied with the system Mac OS X Darwin On OS X Darwin apcupsd can be built with configure defaults The USB driver can be enabled as per the directions on Mac OS X Darwin USB Configuration Apcupsd may be usable on OS X with a smart serial device but certainly does work as a NIS client or using a USB interface The startup information will be installed in Library StartupItems apcupsd which is part of darwin s SystemStartup OpenBSD You will need to install and use GNU make aka gmake instead of the BSD make supplied with the system Ensure that you read the distributions openbsd README file before running apcupsd There are some critical differences in how the OpenBSD implementation operates when the UPS batteries are exhausted Failure to take this into account may result in the system not being fully halted when power is lost Red Hat Systems Red Hat systems are fully supported and by following the standard installation instructions given above you should experience few or no problems Slackware Slackware systems are
146. on However on Win32 systems there is no Unix system log file so if something goes wrong look in the file c apcupsd etc apcupsd apcupsd events where apcupsd normally logs its events and you will generally find more detailed information on why the program is not working The most common cause of problems is either improper configuration of the cable type or an incorrect address for the serial port Additionally check the application event log if you re running a platform that supports it such as Windows 2000 or XP Upgrading An upgrade may be accomplished by uninstalling the old version using the Add Remove Programs Control Panel or clicking the Uninstall Apcupsd link from Start gt Programs gt Apcupsd Near the end of the uninstall you will be prompted about removing configuration and event files You should answer No in order to preserve your existing apcupsd conf file After the uninstall completes you may install the new version of Apcupsd as described above If you preserved your existing apcupsd conf file the new apcupsd conf will be installed as apcupsd conf new Post Installation After installing apcupsd and before running it you should check the contents of the config file c apcupsd etc apcupsd apcupsd conf You will probably need to change your UPSCABLE directive your UPSTYPE and possibly your DEVICE directives Please refer to the configuration section of this manual for more details Problem Areas On some
147. ons Building Apcupsd with USB Verifying Device Detection and Driver Device Nodes Mac OS X Darwin USB Configuration Platforms and Versions Building Apcupsd with USB Verifying Device Detection and Driver Building and Installing apcupsd Installation from Binary Packages RPMS Microsoft Windows Installation from Source Verifying a Source Installation Configure Options Recommended Options for most Systems Compilers and Options Operating System Specifics Debian FreeBSD HPUX NetBSD Mac OS X Darwin OpenBSD Red Hat Systems Slackware SUSE Sun Solaris Unknown System Windows Systems After Installation Checking Your Configuration File 18 18 18 18 18 18 18 18 19 19 19 19 19 20 20 20 20 20 20 22 23 25 26 26 27 27 27 27 27 27 27 27 28 28 30 30 30 30 Arranging for Reboot on Power Up Making sure apcupsd Is Running Configuration Examples A Simple USB Configuration A Simple Configuration for a Serial SmartUPS A Simple Configuration for a Simple Signaling or Dumb NIS Server Client Configuration Using the Net Driver Differences between NIS Client Server and the old now removed Master Slave modes PowerChute Network Shutdown Driver PCNET MODBUS Driver Testing Apcupsd Process Status Test Logging Test apcaccess Test Communications Test Simulated Power Fail Test System Shutdown Test Full Power Down Test apctest Monitoring and Tuning your UPS apcaccess Apc
148. or which it has specific installation programs it will set the Operating System to unknown and will use the incomplete installation scripts that are in platforms unknown You will be on your own or you can ask the developers list apcupsd users lists sourceforge net for installation instructions This directory also contains a hint file for Linux From Scratch which could be helpful for other systems as well Windows Systems Appropriate scripts actually Windows batch files are included with the Apcupsd Win32 installer package After Installation Checking Your Configuration File Once you have installed apcupsd either from a binary package or by building from source your next step should be to inspect your etc apcupsd apcupsd conf file to make sure it is valid You can read the complete reference on configuration directives Configuration Directive Reference but if you are setting up a normal standalone configuration you should only need to check and possibly fix the first three items listed below Your UPSTYPE should be the UPS s protocol type dumb apcsmart usb net pcnet or snmp Your UPSCABLE should be the type of cable you are using DEVICE should be set to the path of the device node usually in dev to use to communicate with the UPS This is used primarily for serial port connections If you have a USB device it is better not to specify a DEVICE directive by leaving it black or commenting it out Apcupsd w
149. ormation Apcupsd Notification and Events When a major event is generated within apcupsd control is passed to the script apccontrol normally found in etc apcupsd apccontrol The event name and a number of other important parameters are passed to the script The major function of the apccontrol script is to perform a shutdown of the system as well as the killpower operation In addition another major task for this script is to notify you by email when certain events such as powerfail occur Since apccontrol is a script you can customize it to your own needs using any text editor To do so you must have a minimal knowledge of Unix shell programming In addition another feature is that you can write your own scripts that will be automatically called by apccontrol before any of its own code is executed Details of the events and how to program them are contained in the Advanced topics section entitled Customizing Event Handling apcupsd Network Monitoring CGI Programs There are four CGI programs multimon cgi upsstats cgi upsfstats cgi and upsimage cgi To have them properly installed you must run the configure command with enable cgi and you should specify an installation directory with with cgi bin or load them manually The default directory for installation of the CGI programs is etc apcupsd which is not really where you want them if you are going to use them Normally they should go in the cgi bin
150. p catching by appending _NOTRAP to your vendor string in the apcupsd conf DEVICE directive Known Problems Currently as of 3 10 0 the code to power off the UPS needs special configuration The killpower command for SNMP UPSes can not be issued during shutdown as typically at some time during shutdown operations the network stack is stopped To overcome this problem it is needed to modify the etc rc d apcupsd system control script to tell apcupsd to issue the power down command killpower to the UPS immediately before apcupsd initiates the system shutdown For this reason it is paramount to set your UPS grace time to a value greater than 120 seconds to allow for clean shutdown operations before the UPS removes the power from its plugs To enable correct shutdown operation during powerdown do the following e Connect to your Web SNMP card using your favorite web browser go to the UPS configuration menu and change the Shutdown Delay parameter to 180 seconds or more depending on how much time your system shutdown requires to umount all the filesystems e Option 1 non windows Edit the server halt script Relocate the ups_kill_power function higher in the shutdown sequence primarily before the command to bring down the ethernet service This is the preferred method for shutting down the UPS The UPS will power down after the prescribed Shut Down Delay time in seconds has elapsed e Option 2 Change etc rc d apcupsd script
151. pped and apcupsd will continue to report Low Battery There are several ways to correct this situation 1 If you have a smart UPS model you can force a self test to make the UPS notice that the battery has been replaced 2 If after a self test the UPS does not detect that the battery has been replaced you can use apctest to do a soft battery runtime calibration For details of doing this refer to the Soft Runtime Calibration section below 3 If after the soft battery runtime recalibration the UPS does not detect that the battery has been replaced you will need to do a manual battery runtime calibration For details of doing this refer to the Manual Runtime Calibration section below Soft Runtime Calibration A runtime calibration causes the UPS to recalculate its available runtime capacity based on its current load Caution a runtime calibration will deeply discharge the UPS batteries which can leave a UPS temporarily unable to support its equipment if a utility power failure occurs Frequent calibrations reduce the life of batteries APC recommends performing a runtime calibration only annually semiannually or whenever the load on the UPS is increased In order to perform a soft runtime calibration it is necessary to wait for the UPS to recharge its batteries to 100 capacity Once this has been done you can then initiate a runtime calibration through apctest APC Documentation Notes 1 In order for the calib
152. procedures or if you are porting apcupsd to another system or you are simply curious you may want to know exactly what is going on during the shutdown process If so please see the Shutdown Sequence section of this manual apctest apctest is a program that allows you to talk directly to your UPS and run certain low level tests display all know values from the UPS s EEPROM perform a battery runtime calibration program the EEPROM serial connection only and enter in TTY mode with the UPS Here we describe how to use it for a SmartUPS The menus and options for USB and simple signaling UPSes are different but mostly self explanatory Shutdown apcupsd if it is running Make sure your etc apcupsd apcupsd conf file has UPSTYPE apcsmart and UPSCABLE has one of the smart cables that are supported Run apctest by invoking it with no arguments It will read your installed apcupsd conf configuration so it knows where to find the UPS and then it will present you with the following output Z0OS 07 50 Ls 1S2 ape sizes lOG 07 gvily 2003 recivere Checking configuration Attached to driver apcsmart sharenet type DISABLE cable type CUSTOM_SMART You are using a SMART cable type so I m entering SMART test mode mode type SMART Setting up serial port Creating serial port lock file Hello this is the apcupsd Cable Test program This part of apctest is for testing Smart UPSes Please select the function you want to perform
153. purposes leave roughly one to two inches on each side for proper airflow 2 The optimum operating temperature for a lead acid battery is 25 Deg C 77 Deg F Elevated temperature reduces longevity As a guideline every 8 Deg C 15 Deg F rise in temperature will cut the battery life in half A battery which would last for 6 years at 25 Deg C 77 Deg F will only be good for 3 years if operated at 33 Deg C 95 Deg F Keep in mind that the battery temperature inside your UPS will always be warmer than the ambient temperature of the location where the UPS is installed 3 Only perform runtime calibrations on your UPS one or two times a year if necessary Some of our customers want to check their systems to verify that their runtime is sufficient However consistently performing these calibrations can significantly decrease the life expectancy of your battery 4 Do not store batteries for extended periods of time New batteries can be stored for 6 to 12 months from date of purchase After this period the battery should be used or it will lose a great deal of its charge It is not advisable to store batteries that have already been in use 5 Do not exceed 80 percent of a UPS unit s rated capacity due to the reduction in run time When you increase your load your runtime decreases In the event of a utility power failure a UPS loaded to full capacity will drain and discharge it s battery quickly and will decrease the life expectancy The Smart
154. rameters There are two shutdown parameters that must be set in the SNMP card to ensure that connected servers shutdown quietly These parameters can be set via the telnet terminal or the web browser interface e Shutdown Delay sec e Return Battery Capacity One of the draw backs of SNMP communication to the UPS is that the Stand alone or Primary server must issue the power down command to the UPS early in server halt procedure This server must issue an early command to the SNMP UPS to power down before its ethernet service is halted This creates a potential problem where the UPS may kill power to any connected servers before these affected servers halt scripts complete a successful shutdown The SNMP Shutdown Delay parameter is used to delay the UPS from killing power to its load by a prescribed period of seconds The delay should be long enough to ensure that the Stand alone or Primary server has enough time to successfully halt The prescribed time should at least be 180 seconds Any additional computers connected to the SNMP UPS must not be configured to issue the command to initiate UPS power down These servers can be thought of as secondary stand alone server The APCUPSD daemons of secondary servers should be configured to initiate server halt a prescribed period of time before the Primary server issues the UPS power down command The Return on Battery Capacity is useful during intermittent sequential power failures This parameter
155. rating system receives a graceful shutdown when using PowerChute plus or a SmartSlot accessory an alert is generated by the Smart UPS indicating that the UPS has reached a low battery condition The alert is audible rapid beeping visual flashing battery LED or LEDs and readable through the graphical interface of PowerChute plus software or a native UPS shutdown program within a particular operating system In order to calculate this low battery condition all Smart UPS products have a preconfigured low battery signal warning time of two minutes this is the factory default setting There are a total of four user changeable settings 2 5 7 or 10 minutes If the low battery signal warning time is set for 2 minutes then the alerts will activate simultaneously two minutes prior to shutdown Similarly if the total runtime for a particular UPS is 30 minutes with a low battery signal warning time set at 10 minutes then the UPS will run on battery for 20 minutes before the low battery alert begins Total runtime is primarily based on two factors battery capacity and UPS load UPS load and runtime on battery are inversely proportional as load increases battery runtime decreases and vice versa When utility power is lost the UPS begins discharging the battery in order to support the attached load Once power returns the Smart UPS will automatically begin to recharge its battery a Matrix UPS It is unnecessary to subject a battery bank to
156. ration to be accurate the output load has to be more than 40 some APC documentation recommends at least 30 Also it is advisable not to increase or reduce the load when the UPS is calibrating its run time 2 Under no circumstances should the UPS be turned off during a run time calibration procedure Once initiated the calibration must be allowed to run until completion 3 The run time calibration procedure is not necessary nor advisable for a new UPS Only old UPSes with batteries that are not subject to discharge for long periods of time should be allowed to perform a run time calibration 4 Matrix UPS and Smart UPS recalculate the runtime related parameters every time the UPS goes on battery When doing a runtime calibration with older batteries APC Technical Support recommend doing a complete discharge and recharge first If you have dumb UPS aka simple signalling like a Back UPS then your only option is to do a manual runtime calibration Manual Runtime Calibration Most of the information in this section is taken from APC s website Any non APC additions have been inserted in square brackets For a smart or smart signalling Back UPS Pro or Smart UPS Fo Perform a Runtime Calibration This is a manual procedure and should not be confused with the runtime calibration performed through PowerChute plus or apctest The batteries inside of the Smart UPS are controlled by a microprocessor within the UPS Somet
157. re details Does apcupsd support Windows Yes don t have a cable which one should build First you must know if you have an apcsmart UPS or a voltage signalling UPS If you have a apcsmart UPS we recommend building a Custom Smart cable see Smart Custom Cable for SmartUPSes If you have a voltage signaling UPS we recommend that you build a Custom Simple cable see Simple Custom Voltage Signalling Cable for dumb UPSes How much CPU resources does apcupsd use Depending on your CPU speed you may see more or less of the CPU consumed by apcupsd On a 400MHz Unix system the CPU usage should fall well below 0 1 On slower systems the percentage will increase proportionally to the decrease in the CPU speed On a 400Mhz Win98 machine the CPU usage will be on the order of 0 5 1 0 This is higher than for Unix systems However compared to the 30 CPU usage by APC s PowerChute the version on the CDROM shipped with my UPS apcupsd s 0 5 1 0 is very modest What language is apcupsd written in It is written in C and C To test apcupsd unplugged the UPS to simulate a power outage After the machine went into the shutdown process plugged the UPS back into the commercial power source This caused the shutdown process to hang after the daemon tried to shut off the ups Have you run into this problem and if so do you have a remedy Question Answer Question Answer Normally once the shutdown process has begun
158. re obsolete you are unlikely to encounter one other than as legacy hardware If you have a choice we recommend you avoid simple signalling UPSes penet PCNET is an alternative for SNMP available on APC s AP9617 family of smart slot modules The protocol is much simpler and potentially more secure than SNMP modbus MODBUS is the newest APC protocol and operates over RS232 links It is also capable of operating over USB but apcupsd does not support this yet MODBUS is APC s replacement for the aging apcsmart aka UPS Link protocol MODBUS is the only way to access detailed control and status information on newer esp SMT series UPSes Choosing a Configuration Type There are three major ways of running apcupsd on your system The first is a standalone configuration where apcupsd controls a single UPS which powers a single computer This is the most common configuration If you re working with just one machine and one UPS skip the rest of this section Your choices become more interesting if you are running a small cluster or a big server farm Under those circumstances it may not be possible or even desirable to pair a UPS with every single machine apcupsd supports some alternate arrangements The second type of configuration is the NIS Network Information Server server and client In this configuration where one UPS powers several computers a copy of apcupsd running one one computer will act as a server while the other s
159. re provided by the apcupsd team RedHat Mandriva SUSE Windows Mac OS X For other platforms it is recommended to check your vendor s package repository and third party repositories for recent binary packages Note that some vendors continue to distribute ancient versions of apcupsd with known defects These packages should not be used Platform Support LINUX RedHat i SUSE Mandriva Mandrake 2 Debian Slackware e Engarde 3 Yellowdog Gentoo WINDOWS e Windows NT 4 4 e Windows 98 ME 2000 e Windows XP Vista including 64 bit e Windows Server 2003 2008 including 64 bit e Windows 7 2 OTHERS Mac OS X Darwin 2 Solaris 8 9 4 e Solaris 10 e NetBSD e FreeBSD OpenBSD e HPUX 34 e Unifix gt 4 QNX 4 Supported UPSes and Cables apcupsd supports nearly every APC brand UPS model in existence and enough different cable types to connect to all of them The UPSTYPE lt keyword gt field is the value you will put in your etc apcupsd apcupsd conf file to tell apcupsd what type of UPS you have We ll describe the possible values here because they re a good way to explain your UPS s single most important interface property the kind of protocol it uses to talk with its computer apcsmart The apcsmart protocol uses an RS232 serial connection to pass commands back and forth in a primitive language resembling modem control codes APC calls this language UPS Link Orig
160. riving the on off line So when you open the port they go high and poof your computer dies The Smart Protocol Despite the lack of official information from APC this table has been constructed It s standard RS 232 serial communications at 2400 bps 8N1 Don t rush the UPS while transmitting or it may stop talking to you This isn t a problem with the normal single character queries but it really does matter for multi char things like 000 Sprinkle a few calls to usleep in your code and everything will work a lot better The following table describes the single character Code or command that you can send to the UPS its meaning and what sort of response the UPS will provide Typically the response shown below is followed by a newline n in C and a carriage return r in C If you send the UPS a command that it does not recognize or that is not available on your UPS it will normally respond with NA for not available otherwise the response is given in the Typical results column Character Meaning Typical results Other info A Model string SMART UPS 700 Spotty support for this query on older models AN TurnonUPS n a Send twice with 1 5s delay between chars Only on 3rd gen SmartUPS and Black Back UPS Pros AZ Permitted long string Gives the EEPROM permitted values for your EEPROM model See EEPROM Values for details Values Front panel Light show
161. rted Many simple signaling aka voltage signaling models such as BackUPS Models This diagram is for informational purposes and may not be complete We don t recommend that use it to build you build one yourself APC Part 940 0095B Signal Computer UPS DB9OF DB9M DTR 4 Cas 8 Sam DSR 6 DCD 1 GND 5 5 4 Ground s 9 Common RI 9J RxD 2 a 2 On Battery TZD O 1 Kill UPS Power 4 7K ohm 940 0119A Cable Wiring Supported Older BackUPS Office Models This diagram is for informational purposes and may not be complete We don t recommend that use it to build you build one yourself INAG Rawat OMOT ORA UPS Computer pins pins Signal Signal meaning 1 brown 4 6 DSR DIR lt Shutdown when set by computer for 1 5 seconds 2 black So 2 Rie ecrs gt On battery power 3 blue ee CD RxD gt Low battery 4 red 5 Ground 5 yellow 7 RTS lt lt Begin signalling on other pins 6 none none Serial BackUPS ES Wiring Supported Older Serial BackUPS ES Models Contributed William Stock by The BackUPS ES has a straight through serial cable with no identification on the plugs To make it work with apcupsd specify the UPSCABLE 940 0119A and UPSTYPE backups The equivalent of cable 940 0119A is done on a PCB inside the unit GOMOUNEEIE SSS SSS SSS BackULS SES DB9 M DB 9F pin signal pin 4 DSR gt 4 4p diode resistor 6 DTR gt 6 gt o kill power il DCD lt
162. rvice in use on your network or if you are running multiple instances of apcupsd on the same machine EVENTSFILE filename If you want the apcupsd network information server to provide the last 10 events via the network you must specify a file where apcupsd will save these events The default is etc apcupsd apcupsd events Currently apcupsd will save at most the last 50 events Periodically once an hour by default apcupsd will check the size of this file When more than 50 events are recorded apcupsd will truncate the file to the most recent 10 events Consequently this file will not grow indefinitely Although we do not recommend it you may change these values by editing apcevents c and changing the appropriate defines Be aware that if you set these values to very large numbers apcupsd may make excessive memory demands on the system during the data access and file truncation operations This filename may also be specified at build time by using the with log dir option of the configure program Configuration Directives used during Power Failures In general none of these directives are required However if you have a voltage signalling dumb UPS with a cable that does not support the Low Battery signal you must set the TIMEOUT directive to force a shutdown BATTERYLEVEL percent of battery If BATTERYLEVEL is specified during a power failure apcupsd will halt the system when the remaining battery charg
163. ry exhausted signal only testing can determine this point For more information see the Testing Apcupsd section of this manual This timer can also be useful if you want some slave machines to shutdown before other machines to conserve battery power It is also useful for testing apcupsd because you can force a rapid shutdown by setting a small value e g 60 and pulling the plug to the UPS TIMEOUT BATT first case or test that is valid Normally SmartUPS users will set TIM shutdown depending on the percentage battery charge remaining BATTERYLEVEL or the remaining battery runtime ANNOY time in ERYLEVEL and MINUTES can be set together without problems apcupsd will react to the INUTES seconds EOUT to zero so that the system is Specify the time in seconds between messages requesting logged in users to get off the system during a power failure This timer starts only when the UPS is running on batteries The default is 300 seconds 5 minutes apcupsd sends the annoy messages by invoking the apccontrol script with the annoyme argument The default is to send a wall message on Unix systems and a popup message in Windows The value of ANNOYDELAY must be greater than the value of ANNOY in order to receive annoy messages this doesn t make sense and means that the default values do not generate annoy messages KES Note that if NOLOGON disable is set the annoy messages will also be
164. ry warning occurs when the specified number of minutes remains before the UPS estimates battery power will be exhausted There are four user changeable settings 2 5 7 or 10 minutes OUTPUTVOLTS lt voltage gt UPS nominal output voltage when running on battery Allowable values depend on the last letter of the firmware or APCMODEL Typical values are BES 208 100 23 240 220 225 HP EU where D domestic USA M Canada A Asia and International SELFTEST 336 168 ON OFF Self test interval in hours 336 2 weeks 168 1 week ON at power on OFF never apcupsd Status Logging There is a good deal of information available about the UPS and apcupsd s status This document describes the format of that information Normally you will get at it via apcaccess but there are other ways as well Status report format STATUS output is in ASCII format with a single data value or piece of information on each line output Because not all UPSes supply the same information the output varies based on the type of UPS that you are using In general if the information is not available for your UPS the line will be missing entirely or the data portion of the output record will contain an N A indicating that the information is not available Status logging consists of periodically logging ALL available information concerning the UPS Since the volume of data is rather large over 1000 bytes per status the STATUS data is not
165. s is enabled Turns on generation of the obsolete NET SNMP driver This driver was the precursor to the current snmp driver and is now obsolete It is available as a fallback if the new driver cannot be used for some reason By default this is disabled Turns on generation of the PCNET PowerChute Network Shutdown driver This driver accesses the UPS over the network using APC s custom protocol This driver can be used as an alternative to SNMP for UPSes equipped with a modern Web SNMP management card This turns on a test driver that is used only for debugging By default it is disabled This option enables building the GTK GUI front end for apcupsd Building this package requires numerous GNOME libraries The default is disabled This option enables building the apcagent menubar application on Mac OS X platforms The default is disabled This option when enabled causes apcupsd to be built with the TCP WRAPPER library for enhanced security In most cases the path is optional since configure will determine where the libraries are on most systems This option allows you to specify where apcupsd will create the nologin file when logins are prohibited The default is etc This option allows you to specify where apcupsd will create the process id PID file to prevent multiple copies from running The default is system dependent but usually var run This option allows you to specify where apcupsd will create the EVENTS and ST
166. s point Manufacture 11 29 96 Format may vary by country MM DD YY vs date DD MM YY Unique within groups of UPSes production runs Serial number WS9643050926 Unique for each UPS Nominal 115 Expected output voltage when running on Output batteries May be a writable variable on Voltage 220 230 240 VAC units Shutdown 020 Seconds Writable variable Sets the delay before grace delay soft shutdown completes 020 180 300 600 Low battery 02 Minutes Writable variable The UPS will report a warning low battery condition this many minutes before it runs out of power r Wakeup 000 Seconds Writable variable The UPS will wait this delay many seconds after reaching the minimum charge before returning online 000 060 180 300 s Sensitivity H Writable variable Possible values e H highest e M medium e L lowest A autoadjust Matrix only t Measure UPS 80 5 Degrees C Only works on models with the ambient Measure UPS SmartSlot card temperature u Upper 132 Writable variable UPS goes on battery when transfer voltage rises above this point voltage v Measure UPS 4Kx Firmware information for Measure UPS board firmware X Last battery 11 29 96 Writable variable Holds whatever the user set in it change date Eight characters y Copyright C APCC Only works if firmware letter is later than O notice Z Reset to CLEAR Resets most variables to initial factory v
167. s work principally by reading the STATFLAG record that is sent by the NIS server present in the output of apcaccess The low 16 bits are the standard APC status flag and the upper 16 bits represent the internal state of apcupsd so the slave can see when the power fails and know when to shutdown It would be possible to have a client also work as a server but that would increase the delay of information getting from the UPS to the secondary client Differences between NIS Client Server and the old now removed Master Slave modes The difference between the NIS mode and the removed master slave mode is that the NIS server has no explicit knowledge of the slaves The NIS server makes its information available via the net NIS and the NIS slaves read it When the NIS server is going to shutdown it makes the information available to any NIS slave that polls it but the NIS server does not explicitly call each NIS slave as is the case in the Master Slave networking described several sections above Think of the difference as push Master Slave vs pull NIS based In the case of M S the master makes all the shutdown decisions and notifies the slaves when they are to shut down or when some other interesting event happens The slaves just do whatever the master says whenever the master says to On the other hand with the NIS based network config you basically publish the UPS status from one server and then your clients view that status and make t
168. s written Logging the STATUS Information If specified in the configuration file the STATUS data will also be written to the system log file Please note that it would not normally be wise to write this data to a normal system log file as there is no mechanism in syslog to rewind the file and hence the log file would quickly become enormous However in two cases it can be very useful to use syslog to write this information The first case is to set up your syslog conf file so that the data is written to a named pipe In this case normally not more than about 8192 bytes of data will be kept before it is discarded by the system The second case is to setup your syslog conf file so that the status data is sent to another machine which presumably then writes it to a named pipe Consequently with this mechanism provides a simple means of networking apcupsd STATUS information Although we mention system logging of STATUS information we strongly recommend that you use apcaccess or the CGI interface to get this information The Shutdown Sequence and its Discontents Shutdown Sequence If you experienced so problems with the testing procedures or if you are porting apcupsd to another system or you are simply curious you may want to know exactly what is going on during the shutdown process The shutdown sequence is as follows apcupsd detects that there is a power problem and it calls etc apcupsd apccontrol powerout By default th
169. s you the minimum required A Simple Configuration for a Simple Signaling or Dumb If you have a simple signaling or dumb UPS such as a BackUPS you will need to know exactly what cable you have and specify it on the UPSCABLE directive Please see the list of UPSes versus cables in the beginning of this document for more information The cable number is normally stamped in the plastic at one end of the cable If you specify the wrong cable it is very likely that at the first power failure your computer will be immediately shutdown This is an unfortunate consequence of the dumb signaling mode To avoid this first replace etc apcupsd apccontrol with safe apccontrol found in the examples directory then test until everything works correctly Once you have the correct cable be sure to remember to reinstall the correct apccontrol file and test that your computer is correctly shutdown during a power failure apcupsd conf v1 1 UPSCABLE number of cable you have UPSTYPE dumb DEVICE dev ttys0 LOCKFILE var lock UPSCLASS standalone UPSMODE disable If your cable does not have low battery detection as is the case with some older models you will also need to define TIMEOUT nnn where you set nn to be the number of seconds on a power failure after which a shutdown is effected Normally you would have many more configuration directives to completely customize your installation but this example shows you the minimum required NIS
170. se to change values limit Measure UPS NO NO Percentage Writable Variable Possible values Upper 90 80 70 10 Use to change values humidity limit Measure UPS NO NO Percentage Writable Variable Possible values lower 90 80 70 10 Use to change values humidity limit Matrix UPS and Symmetra Commands A Run in BYP INV ERR If online BYP response is received as bypass bypass mode mode starts If already in bypass INV is received and UPS goes online If UPS can t transfer ERR received lt Number of 000 Count of bad packs connected to the UPS bad battery packs Load current nn nn True RMS load current drawn by UPS Apparent load nnn nn Output load as percentage of full rated load in VA power y Output Writable variable Possible values voltage 3 selection e A automatic based on input tap e M 208 VAC e 240 VAC AL Front panel Writable variable Possible values language e E English e F French e G German e S Spanish e 1 unknown e 2 unknown e 3 unknown 4 unknown w Run time Writable variable Minutes of runtime to leave in conservation battery UPS shuts down early Possible values e NO disabled 02 leave 2 minutes of runtime 05 leave 5 minutes 08 leave 8 minutes Dip switch info Bit Switch Option when bit 1 0 4 Low battery alarm changed from 2 to 5 mins Autostartup
171. se your system will probably not be automatically rebooted when the power returns enable cgi This enables the building of the CGI programs that permit Web browser access to apcupsd data This option is not necessary for the proper execution of apcupsd with cgi bin path The with cgi bin configuration option allows you to define the directory where the CGI programs will be installed The default is etc apcupsd which is probably not what you want enable apcsmart Turns on generation of the APC Smart driver default enable dumb Turns on generation of the dumb signalling driver code default enable usb Turns on generation of the USB driver code By default this is disabled enable net Turns on generation of the NIS network driver for slaves For each slave this is the only driver needed This driver works by reading the information from the the configured master using the NIS Network Information Services interface enable snmp nable net snmp nable pcnet enable test enable gapcmon nable apcagent with libwrap path with libwrap with nologin path with pid dir path with log dir path with lock dir path with pwrfail dir path Turns on generation of the SNMP driver This driver accesses the UPS over the network using SNMP This is compatible only with UPSes equipped with an SNMP or Web SNMP management card By default thi
172. se a 8 pin RJ45 connector which is more standard ethernet TX and ISDN connector It is easy to construct the cable by cutting off one end of a standard RJ45 8 ethernet cable and wiring the other end three wires into a standard DB9F female serial port connector Below you will find a diagram for the CUSTOM RuUJ45 cable CUSTOM RJ45 CABLE Signal Computer UPS UPS DEHE RJ45 8 RJ45 10 RxD 2 all 2 TxD Send TxD 3 7 8 RxD Receive GND 5 6 7 Ground FG Shield 3 4 Frame Ground The RJ45 8 pins are looking at the end of the connector ETOS 43 21 The RJ45 10 pins are looking at the end of the connector 10 98S 76s 4322 For the serial port DB9F connector the pin numbers are stamped in the plastic near each pin In addition there is a diagram near the end of this chapter Note one user Martin has found that if the shield is not connected to the Frame Ground in the above diagram not in our original schematic the UPS a BackUPS CS 500 El will be unstable and likely to rapidly switch from power to batteries i e chatter When using this cable with apcupsd specify the following in apcupsd conf UPSCABLE smart URS ye Hap cismalst DEVICE dev ttyS0O or whatever your serial port is The information for constructing this cable was discovered and transmitted to us by slither_man Many thanks Other APC Cables that apcupsd Supports apcupsd will also support the following off the shelf cables that are
173. se option 7 to exit apctest Frequently Asked Questions See the bugs section of this document for a list of known bugs and solutions Question Answer Question Answer Question Answer Question Answer Question Answer Question Answer Question Why all the craziness with custom serial cables It was nothing more nor less than a form of customer control For a long time APC wanted to keep other people from talking to its UPSes so it could lock out potential competition for its PowerChute software Scrambling the leads on its serial cables was a cheap way to accomplish this in fact they tended to be wired so that if you tried a straight through cable opening a serial link to the UPS would be interpreted as a shutdown command Hardware companies often think like this they lock up interfaces by instinct cornering a small market rather than growing a bigger one It s fundamentally stupid and self defeating but it s the kind of stupid that tends to sound good at an executive meeting What UPS brands does apcupsd support Currently apcupsd supports only APC UPSes However some companies such as Hewlett Packard put their own brand name on APC manufactured UPSes Thus even if you do not have an APC branded UPS it may work with apcupsd You will need to know the corresponding APC model number apcupsd supports all the popular APC models See the installation and configurations sections of this document for mo
174. sequently any user can login during a power failure condition Also the ANNOY feature is disabled so users will not be warned to logoff the system timeout specifies that apcupsd should prohibit logins after the UPS is on batteries for 90 of the time specified on the TIMEOUT configuration directive Note Normally you don t want to specify a TIMEOUT value so this option is probably not too useful KES percent specifies that apcupsd should prohibit logins when the remaining battery charge percentage reaches 110 or less than the value specified on the BATTERYLEVEL configuration directive Thus if the BATTERYLEVEL is specified as 15 apcupsd will prohibit logins when the battery charge drops below 16 15 X 110 16 minutes specifies that apcupsd should prohibit logins when the remaining runtime in minutes reaches 110 or less than the value specified on the MINUTES configuration directive Thus if MINUTES is set to 3 apcupsd will prohibit logins when the remaining runtime is less than 3 minutes 3 X 110 3 always causes apcupsd to immediately prohibit logins when a power failure occurs This will also enable the ANNOY feature NOLOGINDIR path to nologin dir This directive configures the directory into which apcupsd will write the nologin file as described above for the NOLOGON directive Normally the configure program will set an appropriate default value for your platform often etc You may also specify the with nologd
175. set The bottom line for apcupsd on such a system is that if the hiddevN is not created when you plug in your UPS apcupsd will terminate with an error The solution to the problem is to add a rule to the udev rules file On Fedora FC3 this file is found in etc udev rules d 50 udev rules Start by adding the following line BUS usb SYSFS idVendor 051d NAME usb hiddev n Note that this rule uses obsolete udev syntax and is specific to FC3 and other distributions of similar vintage Then either reboot your system or unplug and replug your UPS and then restart apcupsd At that point a dev usb hiddevNn node should appear and apcupsd should work fine If you have several UPSes or you just want to give your UPS a fixed name you can use rules like the following KERNEL hiddev SYSFS serial JB0319033692 SYMLINK ups0 KERNEL hiddev SYSFS serial JB0320004845 SYMLINK ups1 Note that this rule uses udev syntax that is appropriate only for distros such as RHEL4 and FC4 and others of a similar vintage More recent distros such as FC15 should use something like this KERNEL hiddev ATTRS manufacturer American Power Conversion ATTRS serial BB0100009999 OWNER root SYMLINK ups0 Replace the serial number in quotes with the one that corresponds to your UPS Then whenever you plug in your UPS a symlink called upsO ups1 etc will be created pointing to the correct hiddev node This technique is
176. ss Subnet Mask and Default Gateway the cards can be access managed and controlled from other computers on the network There are two ways to configure the Network Management Card NMC with its initial settings the windows Wizard and Address Resolution Protocol ARP 1 The wizard in included on the CD that comes with the card The wizard must run on a Windows operating system You can configure the card using the wizard over the network via FTP If using the wizard please note the un configured NMC must be on the same subnet as the computer running the wizard 2 Address resolution protocol arp can also be used to configure the NMC The MAC Address of the NMC is needed for this method of configuration The MAC address is located on the quality assurance slip that is shipped with the NMC and is also located on the white sticker on the NMC itself From a computer on the same subnet as the un configured NMC follow the instructions Open up a command prompt and type the following replacing lt IPaddress gt and lt MacAddress gt with the actual values arp s lt iPaddress gt lt MacAddress gt Next use Ping with a size of 113 bytes to assign the IP address defined by the ARP command Se Linux COMmanGie ormat a piNGik TEaddresS e sales Windows command format ping lt IPaddress gt 1 113 Set SNMP card General Parameters After the SNMP Network Management Card is configured with an IP address the SNMP C
177. ster oasi gpa it Serial Communications Andre Hedrick andre linux ide org 2 0 User s Manual Eric S Raymond esr thyrsus com Alpha Port Kern Sibbald kern sibbald com J Rochate jrochate ualg pt testing and machine loan Caldera John Pinner john clocksoft com HP UX Port Carl Erhorn Carl_Erhorn hyperion com Robert K Nelson rnelson airflowsciences com SOLARIS Port Carl Erhorn Carl_Erhorn hyperion com OpenBSD Port Devin Reade gdr gno org NetBSD Port Neil Darlow neil darlow co uk Win32 Port Kern Sibbald kern sibbald com Paul Z Stagner WEB Interfaces Kern Sibbald kern sibbald com Joseph Acosta joeja mindspring com
178. supplied by APC 940 0020 B C Simple Signal Only all models 940 0023A Simple Signal Only all models e 940 0119A Simple Signal Only Back UPS Office and BackUPS ES e 940 0024 B C G Smart mode Only SU and BKPro only e 940 0095 A B C PnP Plug and Play all models e 940 1524C Smart mode Only e 940 0128A Simple Signal Only Back UPS CS in serial mode e All USB cables such as 940 0127 A B Voltage Signalling Features Supported by Apcupsd for Various Cables The following table shows the features supported by the current version of apcupsd for various cables running the UPS in voltage signalling mode Cable Power Loss Low Battery Kill Power Cable Disconnected 940 0020B Yes No Yes No 940 0020C Yes Yes Yes No 940 0023A Yes No No No 940 0119A Yes Yes Yes No 940 0127A Yes Yes Yes No 940 0128A Yes Yes Yes No 940 0095A B C Yes Yes Yes No simple Yes Yes Yes No Voltage Signalling Apparently all APC voltage signalling UPSes with DB9 serial ports have the same signals on the output pins of the UPS The difference at the computer end is due to different cable configurations Thus by measuring the connectivity of a cable one can determine how to program the UPS The signals presented or accepted by the UPS on its DB9 connector using the numbering scheme listed above is WEIS Dim Signal meaning i g Shutdown when set by computer for 1 5 seconds 2 gt On battery power
179. t Nevertheless some people prefer to do a full power down To do so you might want to get a copy of PsShutdown which does have a power down option You can find it and a lot more useful software at http technet microsoft com en us sysinternals bb897541 aspx To use their shutdown program rather than the apcupsd supplied version you simply edit c apcupsd etc apcupsd apecontrol with any text editor and change our calls to shutdown to psshutdown Command Line Options Specific to the Windows Version These options are not normally seen or used by the user and are documented here only for information purposes At the current time to change the default options you must either manually run apcupsd or you must manually edit the system registry and modify the appropriate entries In order to avoid option clashes between the options necessary for apcupsd to run on Windows and the standard apcupsd options all Windows specific options are signaled with a forward slash character while as usual the standard apcupsd options are signaled with a minus or a minus minus All the standard apcupsd options can be used on the Windows version In addition the following Windows only options are implemented service Start apcupsd as a service irun Run the apcupsd application install Install apcupsd as a service in the system registry remove Uninstall apcupsd from the system registry about Show the apcupsd about dialogue box kill
180. t script since it will recall apcupsd which will detect that it is a slave i e no connection to the UPS and will complain that it cannot do the killpower This situation is not harmful just annoying and possibly confusing One possible problem during shutdown can be caused by remnants of old versions Please be sure to delete or rename all prior versions usr local sbin apcupsd or sbin powersc Startup Normally apcupsd is automatically started when your system is rebooted This normally occurs because the startup script apcupsd is linked into the appropriate places in etc rc d On most Linux systems there is a program called chkconfig 8 that will automatically link the startup script This program is invoked by the make install scripts or it is explicitly done for those systems that do not have chkconfig 8 If this is not the case you can either link it in appropriately yourself or explicitly call it from your rc local file The appropriate manual way to startup apcupsd is by executing lt path gt apcupsd start where path is normally etc rc d or etc rc d init d depending on your system Using this script is important so that any files remaining around after a power failure are removed Likewise shutting down apcupsd should be done with the same script lt path gt apcupsd stop Windows Considerations Please see the Killpower under Windows chapter of this manual for considerations pertaining to shutdown and killpower on Win
181. talled when you install Apcupsd However in some cases you may need to install the driver manually For detailed instructions please see the install txt file located in the driver folder of your Apcupsd install Verifying Device Detection and Driver After installing Apcupsd and the Apcupsd USB driver if necessary plug in your UPS USB cable and open the Windows Device Manager You should see a American Power Conversion USB UPS Apcupsd listed under the Batteries section If a device of that name does not appear check that your UPS is powered on and that the USB cable is connected at both ends Reinstall the driver as directed above if needed Solaris USB Configuration Platforms and Versions Apcupsd supports USB UPSes on Solaris 10 and higher Both x86 and SPARC platforms are supported Building Apcupsd with USB Some specific packages are necessary when building Apcupsd with USB support on Solaris You must install the SUNWlibusb and SUNWlibusbugen packages BEFORE attempting to build Apcupsd These packages can be found on the Solaris installation CDROMs and should be installed with the pkgadd utility You also should build using the gcc compiler and ccs make not Sun s compiler The appropriate make utility can be found in usr ccs bin gcc can be installed from packages included on the Solaris installation CDROMs Configure and build Apcupsd normally as described in Building and Installing Apcupsd Be sure to include the enable
182. tery Sent to indicate low battery Not implemented on SmartUPS v s or BackUPS Pro models Return from Sent when the battery has been recharged to some level Only sent if a low batt has been sent previously Abnormal Sent for conditions such as shutdown due to overload or shutdown due condition to low battery capacity Also occurs within 10 minutes of turnon Return from Sent when the UPS returns from an abnormal condition where was abnormal sent but not a turn on Not implemented on SmartUPS v s or BackUPS condition Pro models About to turn Sent when the UPS is about to switch off the load No commands are off processed after this character is sent Not implemented on SmartUPS v s BackUPS Pro or 3rd generation SmartUPS models Replace Sent when the UPS detects that the battery needs to be replaced Sent battery every 5 hours until a new battery test is run or the UPS is shut off Not implemented on SmartUPS v s or BackUPS Pro models amp Check alarm Sent to signal that temp or humidity out of set limits Also sent when one register for of the contact closures changes state Sent every 2 minutes until the fault alarm conditions are reset Only sent for alarms enabled with Cause of Measure UPS alarm may be determined with J Not implemented on SmartUPS v s or BackUPS Pro Variable Sent whenever any EEPROM variable is changed Only supported on change in Matrix UPS and 3rd generation SmartUPS models EEPROM Register
183. that will be placed on then NISIP directive in the configuration file The default is 0 0 0 0 No checking is done on the value entered so you must ensure that it is a valid IP address This option allows you to specify what port apcupsd will use for Master and Slave communications The default is system dependent but usually 6666 This option simply sets the appropriate port in the apcupsd conf file which can be changed at any later time This option allows you to specify the type of UPS that will be connected to your computer The default is smartups This option simply sets the appropriate UPS type in the apcupsd conf file which can be changed at any later time This option allows you to specify what cable you are using to connect to the UPS The default is smart This option simply sets the appropriate UPS cable in the apcupsd conf file which can be changed at any later time This option modifies the apcupsd Makefiles disable installation of the distribution platform directory Generally this used to do a full installation of apcupsd except the final modification of the operating system files normally etc rc d halt etc This is useful if your operating system is not directly supported by apcupsd or if you want to run two copies of apcupsd on the same system This option can also be used by those of you who prefer to manually reboot your system after a power failure or who do not want to modify your system halt files
184. the default install locations may have changed 8 make install or gmake install 9 edit your etc apcupsd apcupsd conf file if necessary 10 ensure that your halt script is properly updated 11 Start the new apcupsd with system dependent path apcupsd start If all goes well the configure will correctly determine which operating system you are running and configure the source code appropriately configure currently recognizes the systems listed below in the Operating System Specifics section of this chapter and adapts the configuration appropriately Check that the configuration report printed at the end of the configure process corresponds to your choice of directories options and that it has correctly detected your operating system If not redo the configure with the appropriate options until your configuration is correct Please note that a number of the configure options preset apcupsd conf directive values in an attempt to automatically adapt apcupsd as best possible to your system You can change the values in apcupsd conf at a later time without redoing the configuration process by simply editing the apcupsd conf file Other configuration options can be used to set up the installation of HTML documentation and optional modules notably the CGI interface that enables the UPS state to be queried via the Web You will find a complete reference later in this chapter In general you will probably want to supply a more elaborate
185. ting with version 3 11 15 the Windows binaries are distributed with a full GUI installer driven by NSIS the Nullsoft Scriptable Install System http nsis sourceforge net Installation is very simple and straight forward Simply double click the installer executable and follow the instructions Configuring Apcupsd on Windows If you are installing Apcupsd for the first time the installer will give you an opportunity to edit the apcupsd conf configuration file to contain the values appropriate for your site Subsequent installations will maintain your existing apcupsd conf so you need not edit it again unless there are new features or syntax changes that must be accounted for The default configuration calls for a USB connected UPS This is the most common connection for modern UPSes especially those used with Windows computers All other apcupsd drivers are available apcsmart dumb net snmp pcnet and can be used simply by editing the configuration file UPSCABLE UPSTYPE and DEVICE settings as described elsewhere in this manual Note that on Windows serial ports are specified using COM1 COM2 etc notation instead of the UNIX style dev tty notation Note also if you are using WinNT or Win2000 the operating system may probe the serial port attempting to attach a serial mouse This will cause apcupsd to be unable to communicate with the serial port If this happens or out of precaution you can edit the c boot
186. turbances High Low No in the line voltage the UPS will transfer to battery power and watch the AC line until it can transfer back to line In this mode the transfer times are longer but still within acceptable limits to insure the continuity of a computer s operation To change the sensitivity of the UPS press the small white sensitivity button on the rear of the UPS Use a pointed object such as a pen to do so The default setting is high press the button once to set the sensitivity to medium and press it again to set it to low pressing it a third time will set it back to high The sensitivity setting change will take effect immediately The green LED next to the button is a sensitivity setting indicator brightly lit is high sensitivity dimly lit is medium and off is low sensitivity Flashing Battery Charge Graph LEDs The battery charge graph LEDs on the front panel of a Smart UPS will flash in unison when the UPS is operating online and the runtime remaining calculated by the Smart UPS microprocessor is less than two minutes more than the low battery signal warning time minimum of two minutes This would usually indicate that you need to either decrease the load or install new batteries If the batteries are new then you need to perform a runtime calibration see below At a pinch you could also decrease the low battery warning time There are four possible settings 2 5 7 or 10 minutes Battery Replacement
187. ty levels devfs is turned off The net result is that in those situations hiddev is completely unusable so apcupsd will not work So in these cases the choices are 1 Reduce the security level setting of the system not sure if this is possible after the initial install 2 Custom build a high security kernel with devfs enabled and make sure devfs is mounted and devfsd is running 3 Custom build a high security kernel with dynamic minors disabled 4 Use udev Miscellaneous If all these things check out and you still can t see the UPS something is more seriously wrong than this manual can cover find expert help If you are unable to list USB devices or drivers you kernel may not be USB capable and that needs to be fixed BSD USB Configuration Known BSD USB Issues Problem FreeBSD lockups Some users have experienced lockups apcupsd stops responding on FreeBSD systems Solution Recent versions of Apcupsd have addressed this issue Please upgrade to apcupsd 3 10 18 or higher Problem FreeBSD kernel panics if USB cable is unplugged while apcupsd is running Solution This is a kernel bug and is most easily worked around by not hot unplugging the UPS while apcupsd is running This issue may be fixed in recent FreeBSD kernels Platforms and Versions The BSD USB driver supports FreeBSD OpenBSD and NetBSD Thanks go to the BSD developers who kept a nearly identical interface across all three platforms Kern
188. ty repositories for recent binary packages before resorting to building apcupsd from scratch Note that some vendors continue to distribute ancient versions of apcupsd with known defects These packages should not be used Installation from Binary Packages RPMS For systems based on RPM packages such as Red Hat and SuSE apcupsd is available in binary RPM format This is the simplest way to install If you have no previous version of apcupsd on your machine and are creating a standalone configuration simply install the RPM with a normal rpm ihv command You re done and can now skip the rest of this chapter and go straight to tweaking your run time configuration file see After Installation If you have a previous installation you can upgrade with a normal rpm Uhv but this may not upgrade the halt script It may be better to do the upgrade as a remove rpm e followed by a fresh install rpm ihv After installation of the binary RPM please verify carefully that etc rc d init d halt was properly updated and contains new script lines flagged with APCUPSD Since there is no standard location for cgi bin the rpm will place the binary CGI programs in the directory etc apcupsd cgi To actually use them you must copy or move them to your actual cgi bin directory which on many systems is located in nome httpd cgi bin Microsoft Windows The Windows version of apcupsd is distributed as a simple double click installer Instal
189. u fat finger the y and enter y instead no cause for alarm you will simply get the APC copyright notice e when you are sure you are properly connected send an upper case D no cr This will put the UPS into calibration mode and it will drain the battery down to 25 capacity 35 for a Matrix at which point it will go back on the mains In doing so it will recompute the runtime calibration e If you wish to abort the calibration enter a second D command e When you are done restart apcupsd In principle you should be able to do this with the computer powered by the UPS but if you wish to be completely safe you should plug your computer into the wall prior to performing the runtime calibration In that case you will need to artificially load the UPS with light bulbs or other means You should supply a load of about 30 to 35 but not more than 50 You can determine the load by looking at the output of the apcaccess status command while apcupsd is running You should not run the recalibration command more than once or twice per year as discharging these kinds of batteries tends to shorten their life span Configuration Directive Reference Configuration directives in etc apcupsd apcupsd conf control the behavior of the apcupsd daemon For most installations it is only necessary to set a handful of general directives The rest can be left at their defaults unless you have an exotic configuration General Configuration Directives
190. unlimit This event is generated when the MINUTES value defined in the apcupsd conf file expires while in a power fail condition The MINUTES is the remaining runtime as internally calculated by the UPS and monitored by apcupsd After completing this event apcupsd will immediately initiate a doshutdown event Default wall a message timeout This event is generated when the TIMEOUT value defined in the apcupsd conf file expires while in a power fail condition It indicates that the total time in a power failure has been exceeded and the machine should be shutdown After completing this event apcupsd will immediately initiate a doshutdown event Default wall a message startselftest This event is generated when apcupsd detects a self test by the UPS Normally due to the 6 second onbattery delay default time self test events are not detected Default nothing endselftest This event is generated when the end of a self test is detected Default nothing battdetach This event is generated when apcupsd detects that the UPS battery has been disconnected Default nothing battattach This event is generated when apcupsd detects that the UPS battery has been reconnected after a battdetach event Default nothing Controlling Multiple UPSes on one Machine The following discussion does not apply to Windows servers Apcupsd on Windows is limited to a single instance and cannot support monitoring multiple UPSes If you have
191. up server MONITOR deuter Disk server MONITOR polymatou 7001 APC USB UPS where the USB copy of apcupsd has been configured to use port 7001 by modifying apcupsd conf Note the default NIS port is 3551 on most platforms To test multimon cgi you can execute it as non root directly from the source cgi build directory To do so enter at a shell prompt multimon cgi If everything is set up correctly it will print a bunch of HTML with the values of the machines that you have put in the hosts conf file It should look something like the following note only a small portion of the output is reproduced here Content type text html lt DOCTYPE HTML PUBLIC W3C DTD HTML 4 0 Transitional EN http www w3 org TR REC htm140 loose dtd gt lt HTML gt lt HEAD gt lt TITLE gt Multimon UPS Status Page lt TITLE gt lt HEAD gt lt BODY BGCOLOR FFFFFF gt lt TABLE BGCOLOR 50A0A0 ALIGN CENTER gt R gt lt TD gt TABLE CELLPADDING 5 gt R gt TH COLSPAN 10 BGCOLOR 60B0B0 gt lt FONT SIZE 2 gt APCUPSD UPS Network Monitor lt FONT gt lt BR SUNE dein 16 Oa Caw O OE A lt TR gt lt TR BGCOLOR 60BOB0O gt lt TH COLSPAN 1 gt System lt TH gt lt TH COLSPAN 1 gt Model lt TH gt lt TH COLSPAN 1 gt Status lt TH gt De a an an If you do not get similar output check the permissions of the etc apcupsd directory and of those of etc apcupsd hosts conf to ensur
192. upsd Notification and Events apcupsd Network Monitoring CGI Programs Setting up and Testing the CGI Programs Using the CGI Programs on Windows multimon cgi upsstats cgi upsfstatus cgi A Tip from Carl Erhorn for Sun Systems CGI Credits Security Issues Firewall Settings TCP Wrappers Configuring Your EEPROM Using apctest to Configure Your EEPROM Maintaining Your UPS Batteries Battery Technology 30 31 32 32 32 32 33 34 34 35 35 35 36 36 38 39 39 40 40 41 42 43 43 44 45 45 46 46 47 47 47 47 48 48 48 48 48 Battery Life Flashing Battery Charge Graph LEDs Battery Replacement Battery Installation Soft Runtime Calibration Manual Runtime Calibration Resetting the UPS Battery Constant Frequently Asked Questions Customizing Event Handling apccontrol Command Line Options Controlling Multiple UPSes on one Machine Multiple UPS Example Support for SNMP UPSes Planning and Setup for SNMP Wiring Planning and Setup for SNMP Configuration Assign SNMP Card IP Address Set SNMP card General Parameters Set SNMP card Shutdown Parameters Configure Event Trap Receivers Connecting APCUPSD to a SNMP UPS Building with SNMP support SNMP Trap Catching Known Problems apcupsd System Logging Logging Types Data Logging Status Logging EVENTS Logging Implementation Details The Windows Version of apcupsd Installing Apcupsd on Windows Configuring Apcupsd on Windows Starting Apcupsd on Windows Apctray Testing Ap
193. voltage the UPS is supplying to your equipment SENSE The sensitivity level of the UPS to line voltage fluctuations DWAKE The amount of time the UPS will wait before restoring power to your equipment after a power off condition when the power is restored DSHUTD The grace delay that the UPS gives after receiving a power down command from apcupsd before it powers off your equipment DLOWBATT The remaining runtime below which the UPS sends the low battery signal At this point apcupsd will force an immediate emergency shutdown lt lt LOTRANS The line voltage below which the UPS will switch to batteries HITRANS The line voltage above which the UPS will switch to batteries RETPCT The percentage charge that the batteries must have after a power off condition before the UPS will restore power to your equipment ITEMP Internal UPS temperature as supplied by the UPS ALARMDEL The delay period for the UPS alarm BATTV Battery voltage as supplied by the UPS LINEFREQ Line frequency in hertz as given by the UPS LASTXFER The reason for the last transfer to batteries NUMXFERS The number of transfers to batteries since apcupsd startup XONBATT Time and date of last transfer to batteries or N A TONBATT Time in seconds currently on batteries or 0 CUMONBATT Total cumulative time on batteries in seconds since apcupsd startup XOFFBATT Time and date of last transfer from batteries or N A S
194. we cannot stop it how do you stop a shutdown that has killed off half of the daemons running on your system Most likely you will be left with an unusable system In addition when apcupsd is re executed in the halt script after the disks are synced it tries to shut off the UPS power but the UPS will generally refuse to do so if the AC power is on Since we cannot be 100 sure whether or not the UPS will shut off the power we don t attempt to reboot the system if we detect that the power is back as it might then get caught by a delayed power off at least for Smart UPSes After running apcupsd for a while get the following error Serial communications with UPS lost What is the problem We use standard Unix serial port read and write calls so once a connection is made we generally have few problems However there have been reports that APC s SNMP Management Card can cause serial port problems If you have such a card we suggest that you remove it and see if the problem goes away It is also possible that some other process such as a getty is reading the serial port get the following error Starting apcupsd power management Mar 20 21 19 40 box apcupsd 297 apcupsd FATAL ERROR in apcserial c at line 83 Cannot open UPS tty dev cua01l No such file or directory What is the problem Answer Question Answer Question Answer The two most likely causes of your problem are 1 You have the wrong serial port devi
195. y When you are ready to do the test either simply pull the plug and wait for the batteries to become exhausted or set the TIMEOUT configuration directive to something like 60 so that the system will shutdown before the batteries are exhausted We recommend doing the full shutdown without using TIMEOUT to correctly simulate a real power failure but the choice is yours I did it once here but now use TIMEOUT 30 If all goes well your system should be shutdown before the batteries are completely exhausted and the UPS should be powered off by apcupsd Please be aware that if you do the full power down you must ensure that your UPS is totally powered off Otherwise it may have been given the command to power off but due to a long grace period it is still waiting If you were to reboot your computer during the grace period the UPS could then suddenly turn off the power this happened to me To avoid this problem always wait for your UPS to power itself off or power if off manually before restarting your computer On my system the UPS is configured as at the factory to have a 180 second grace period before shutting off the power During this type of testing 180 seconds seems like an eternity so please take care to either wait or manually power off your UPS To determine what grace period is programmed into your UPS EEPROM run apcaccess eprom and look at the Shutdown grace delay If you experienced so problems with the above testing
196. y insecure since an attacker could easily send packets crafted to cause your server to shut down Using the ipaddr user and passphrase will prevent this behavior You may need to take steps to ensure networking stays active during your OS s shutdown sequence in order for the PCNET driver to power off the UPS the so called killpower operation On a Linux distro you can use commands such as chkconfig level 0 network on chkconfig level 0 iptables on to make sure networking stays up MODBUS Driver As of 3 14 11 apcupsd supports the MODBUS protocol over RS232 serial interfaces MODBUS is APC s replacement for the aging apcsmart aka UPS Link protocol It is recommended for modern ex SMT series Smart UPS where an RS232 connection is available Not all APC UPSes support MODBUS New 2013 year Smart UPS models are likely to support it out of the box and firmware updates are available for some older models APC Schneider tech support is your best point of contact for determining if a certain model will support MODBUS That said APC knowledge base article FA164737 indicates MODBUS support is available for the majority of the SMC SMT and SMX model lines The required apcupsd conf settings for MODBUS are straightforward apcupsd conf v1 1 UPSCABLE smart UPSTYPE modbus DEVICE dev ttySs0 LOCKFILE var lock UPSCLASS standalone UPSMODE disable The DEVICE setting identifies the seri