ADAPT Parasol b

image

Contents

1. POQOQQ0000000 o 35 www swegon com q Joseied 1IdVAV ADAPT Parasol b Ordering key Type of ceiling Dimensions of the face plate mm Lay in T Bar system 600 module 1200 module cc 600 592x592 1192x592 cc 600 SAS130 15 584x584 1184x584 cc 625 617x617 1242x6017 cc 650 642x642 1292x642 cc 675 667x667 1342x667 Clip in metal tile 600 module 1200 module cc 600 598x598 1198x598 cc 625 623x623 1248x623 The tolerance is mm The units can be ordered in various functional versions Function A Cooling and supply air B Cooling heating and supply air X Cooling electric heating and supply air Factory fitted ADC supplied as standard ADC Airflow variant Single module unit ADAPT Parasol 600 ADAPT Parasol 600 PF Two module unit ADAPT Parasol 1200 ADAPT Parasol 1200 PF PF PlusFlow extra high airflow Software con figuration The product can be supplied with certain software settings precontig ured from the factory For example Contractor demarcation Swegon s supply demarcation is at the connection points for water and air as well as for wiring the room control equipment see Figures 31 32 33 34 35 and 36 37 38 39 Occupancy flow and temperature set point Nozzle setting ways L M or H L Low airflow M Medium airflow H High airflow Colour The units are supplied painted
2. Chilled water must always be kept at a level that ensures that no condensation will form Heated water max Designations P Capacity W l Temperature of the primary air C t Temperature of the room air C tn Mean water temperature C AT Temperature differential t t K AT Temperature differential t t K AT Temperature differential between the cooling water inlet flow and return K AT Temperature differential between the heating water inlet flow and return K V Water velocity m s q Flow l s o Pressure drop Pa Ap Pressure drop Pa Supplementary index k cooling v heat I air commis sioning corr correction Nozzle pressure commissioning pressure p q k p Nozzle pressure Pa q Fl de prim rluft l s Ka Pressure drop constant for nozzle setting see Tables 1 4 Swegon reserves the right to alter specifications 2015 12 16 www swegon com ADAPT Parasol b Cooling Default The cooling capacities have been measured in conform ance with EN 15116 Standard and have been recalculated for a constant water flow according to Diagram 2 3 Calculating formulae Cooling Below are formulae that enable the user to calculate what comfort module is best suited for the application The values for the calculations can be taken from the tables Pressure drop in cooling coil Ap q kp Ap Pressure drop in cooling coil kPa ON Flow of chilled water l s
3. Min cooling Pressure dPa Force summer night cool ADAPT EA analog min ADAPT EA analog max ADAPT EA offset s 8 l s 10 Allforce off l s 10 100 8 8 8 8 8 8 8 E Write settings to file Selected controller URCI Master SWICCT can be downloaded from www swegon se both the software and a separate manual 13 2015 12 16 www swegon com Swegon reserves the right to alter specifications q joseueg Jdvav ADAPT Parasol b Typical installations Figure 19 Typical room 1 shows ADAPT Parasol in an office room Extract air via transfer air grille balance at zone level 1 ADAPT Parasol comfort module with supply air cooling and heating e Pressure sensor e Communication unit controller e Damper with motor Figure 20 Typical room 2 shows ADAPT Parasol in an office room Supply and extract air in balance 1 ADAPT Parasol comfort module with supply air and cooling e Pressure sensor e Presence detector e Temperature sensor 2 CONTROL Zone damper e Communication unit controller 4 Cooling water and heating water 2 CONTROL Zone damper 5 Extract air via transfer air grille to the corridor gt Chilled water 6 External sensor module occupancy and temperature sensor 4 Extract air via ADAPT Damper slave controlled from ADAPT Parasol 5 Grill or fully opened extract air register EXC 6 Sound attentator CLA SORDO 14 Swegon reserves the right to alter specifications 2015 12
4. Width 584 592 598 617 623 642 667 mm Height ADAPT Parasol 600 220 mm ADAPT Parasol 600 PF 250 mm ADAPT Parasol 1200 220 mm ADAPT Parasol 1200 PF 250 mm Dimensions of the units have a tolerance of 2 mm Power consumption Power consumption for dimensioning transformer Actuator 6 VA Damper motor 2 VA Controller 1 VA Sensor Module 1 VA Allways included in product Example A ADAPT Parasol 1192 B HF 6 2 1 1 10 VA 6 VA for cooling OR heating actuator as the normally operate in sequence Example B ADAPT Parasol 1192 B HF 6 6 2 1 1 16 VA For Radiator Heat and Cold draught protection means 6 6 VA for actuators as they don t operate in sequences 18 1 184 1 192 1 198 1 242 Swegon Recommended limit values Pressure levels Working pressure coil max 1 600 kPa Test pressure coil max 2 400 kPa Applies to module without installed control equipment Nozzle pressure 50 150 Pa Recommended lowest nozzle pressure if coil heat is used p 70 Pa Recommended lowest nozzle pressure with the face plate in the high capacity position p 70 Pa Water flow Ensures evacuation of any air pockets in the system Cooling water min 0 030 I s Heating water min 0 013 I s Temperature differentials Chilled water temperature increase 2 5K Heated water temperature decrease 4 10K Temperature differences are always expressed in Kelvin K Flow temperature Chilled water o 60 C
5. Yellow Alarm Temperature sensor Figure 16 Sensor module viewed from the front FRET EPELE FPFE Y e PFFTFA Figure 18 The CABLE CONVERTER USB RJ12 RS485 cable can be easily used for connecting a computer to the module for e g entering software settings The cable can be connected either to a socket on the rear of the Sensor module as illustrated or directly to the controller How this is done is described in the SWICCT user s manual Flashing Green Condensation alarm Green Yellow Comfort alarm not acute 3 parallel RJ12 ports Modbus for connecting a Figure 17 Sensor module viewed from rear 12 Swegon reserves the right to alter specifications controller for instance another sensor module or computer by means of Cable converter USB RJ12 Addressing the sensor module 10 sensor modules can be connected to each master unit Each one must have its own unique address in order to work Switch for termination resistance Set Switch 1 to the ON position for the last sensor module in the loop 2015 12 16 www swegon com ADAPT Parasol b Swegon SWICCT SWICCT SWegon Indoor Climate Configuration Tool is the software that makes the entering of settings into the con troller a simple task Here you can make all the necessary settings for the Product for example e Base settings for temperature e
6. 5 04 0220 Table 4 Cooling capacity ADAPT Parasol 1200 PF Nozzle Nozzle Primary Cooling capacity of pri Cooling capacity water W Pressure drop con pressure setting 1 airflow mary air W for AT Om es stant air water rate l s an sse 2 faer s16 646 77s 393 a60 522 583 634 761 0022 C emn see 28 aaa 72 is ase Lan lars 538 601 664 842 0 022 aan a7 0 459 ora 760 ov7 a68 539 on ose 759 761 0022 70 4 32 507 676 eas 101a asi 554 634 707 787 842 0022 Tor uu sas 33 392 523 esa res aco sai 612 690 760 574 0022 aan 22 34 520 693 866 i040 sar 600 oes 763 848 761 0022 nei 759 36 575 767 959 st a5 615 roa 791 e70 842 0022 1 For particulars on the sizing of alternative nozzle settings use Swegon s ProSelect sizing program available at www swegon com 2 Room attenuation 4 dB 3 The specified capacities are based on operation in the high capacity mode Operation with the face plate set to the normal posi tion reduces the water capacity of the ADAPT Parasol 600 by about 5 and that of the ADAPT Parasol 1200 by about 10 The water capacity can vary depending on installation and how the airflow deflectors are set The primary air capacity is not affected N B The total cooling capacity is the sum of the airborne and waterborne cooling capacities Table 5 Cooling capacity for natural convection Unit mm Coolin
7. E orae opara e e nam uu oza T a vor 202 303 aor sor on vor ooze a aa a aaa zsa ase sis car rez 189 oom fw 196 20 oa 2a5 azo 56 eee s19 277 00m Cf tne ts a Pras 297 a9 ses 76 e67 189 00a wnt 23 2 25 Pre 320 art es 775 oe 277 ooa Coor uu 96 20 130 as7 se6 su oat 709 10 00a a ou e a ie o eo es r oe te T oo Ooo E es 29 o oa se err ent ioo 277 ooze Table 7 Heating capacity ADAPT Parasol 600 PF Nozzle Nozzle set Primary Sound Heating capacity T W for AT Pressure drop constant pressure airflow level air water V5 soa Sete te ea Te sora ua 21 2 woe anv 339 ass 575 oa 313 oos Cf tae 279 a7 o a3 360 asa est 770 395 oos wine 337 a7 100 aa ave zx cea e20 476 001 ates 200 aia sez 73 267 305 ooe aie s aaa arr a see rr on ar core as as aa 294 asa ot 775 oo 305 oor aie 45236 v46 305 a68 a5 80s o77 a76 ooe 1 For particulars on the sizing of alternative nozzle settings use Swegon s ProSelect sizing program available at www swegon com 2 Room attenuation 4 dB 3 The specified capacities are based on operation in the high capacity mode Operation with the face plate set to the normal position reduces the water capacity of the ADAPT Parasol 600 by about 5 and that of the ADAPT Parasol 1200 by about 10 The water capaci
8. Enclosed version for circulating air e Cleanable air duct e Fixed measurement tapping with hose e Painted in base shade of white RAL 9003 e Suitable for T grid systems with modular dimensions 600 625 and 675 mm T section 24 mm optional e Contractor demarcation at the connection points for water and air according to dimensional drawings e Contractor demarcation for electric connection point according to dimensional drawings e At connection points pipe contractor connects to plain pipe end 012 mm cooling or 12 mm heating If the unit is fitted with indoor climate control equip ment pipe contractor connects to external thread DN 1 2 e Ventilation contractor connects ducting to connection piece 125 mm Parasol 1200 PF 160 mm e Pipe contractor fills bleeds tests the pressure and assumes responsibility for the design water flows reaching each branch of the system and the index unit e Ventilation contractor conducts initial adjustment of the airflows Factory mounted accessories e Transformer Power ADAPT VA e Valves and actuators for cooling and heating SYSTVDN215 straight valve with actuator ACTUATOR b 24V NC SYSTVDN215 straight valve ACTUATOR b 24V NC actuator e Sensors CO sensor VOC sensor e Sensormodule Sensormodule square Sensormodule circular Swegon Accessories e Transformer SYST TS 1 xx pcs e Transformer POWER Adapt xx st e Temperature sensor CONDUCTOR T IG xx pcs e V
9. demand controlled ventilation with all its poten tial for savings combined with the comfort module s high capacity and performance for air conditioning rooms All this packaged in one compact unit Is simple to install 2 Swegon reserves the right to alter specifications Swegon Flexibility The easily adjustable nozzles in combination with Swe gon s ADC Anti Draught Control offer maximum flex ibility for future changes in the room layout All sides of the unit can be set independently of one another and this enables the comfort module to distribute more air or less air to each of the four sides and deliver the air in the preferred direction in the room Design The face plate of the ADAPT Parasol is available in three different perforation patterns As standard the face plate has round perforations arranged in a triangular pattern however other optional patterns are available to special order Draught fee indoor climate The ADAPT Parasol distributes air in four directions at low air velocity The low air velocity is created by distribut ing air cooler than room temperature over a large area The special design of the outlet creates a turbulent flow enabling the supply air to be quickly mixed with the room air The comfort module s closed design with a circulation opening for recirculated air in the face plate of the module also contributes to its excellent mixing performance The ADAPT Parasol is available in t
10. on each side and can be set for both high and low airflows Swegon reserves the right to alter specifications Swegon Range of Application The ADAPT Parasol is ideal as a standard application in the following typical premises e Offices and conference rooms e Classrooms e Hotels e Restaurants e Hospitals e Shops e Shopping centres With its numerous possible settings the functions of the ADAPT Parasol can easily be adapted to new businesses or changes in the design of the premises Simple to install The ADAPT Parasol s small compact units are designed to fit the most common modular ceiling dimensions and this makes them simple to install The small dimensions offer benefits in handling especially at the building site with easier installation and reduced health and safety issues Market standardised modular dimensions The products available to order have modular dimensions to fit the standardised 600 625 and 675 mm centre to centre ceiling dimensions There are also mounting frames for plasterboard ceilings as well as solutions for clip in type ceilings Always in stock The ADAPT Parasol s standard variants with the most common functions are available from stock to keep deliv ery times short 2015 12 16 www swegon com Swegon ADAPT Parasol b All components in the product can be installed directly from the factory Electrical connections All factory fitted components are wired to wiring ter
11. on increased heat demand Selection of sequence Water Air e The control sequence involves prioritising waterborne cooling before airborne cooling e For an occupied room the airflow is steplessly regulated between min and max depending on the room tempera ture or the air quality if an air quality sensor is used e f the room needs to be cooled ensure first that the airflow generates sufficient pressure in the module which will allow the water valve to open The reason for this is to ensure comfort in the room i e to prevent cold down draughts from the product e After that the water valve is allowed to open to supply chilled air to cool the room If there is still a cooling demand when the cooling valve is fully open the built in air damper opens to cool more with air Flow Water Air QO a ities Max occupancy flow Pr ar va or a 7 s Min P cooling valve 2 gt Lo Min occupancy flow Valve 100 open Vacancy flow Valve 0 open Occupancy with cooling demand Figure 6 1 Occupancy temperature rises 2 The room temperature reaches level for cooling demand air damper opens in order to reach minimum pressure which alllows cooling valve to open Cooling valve is allowed to open 4 Cooling valve is fully open but there is still a cooling demand in the room the air damper opens in order to cool with more air 5 Cooling valve and air damper fu
12. stuck During the exerci sing process all the valves wired to the controller open to the max setting for 6 minutes and then close The valves of the cooling system are exercised first after that the valves of the heating system are exercised Frost protection The function involves starting heating operation at 10 C to prevent the risk of damage that otherwise could occur due to freezing 2015 12 16 www swegon com ADAPT Parasol b Specific nozzle settings To specity optimised nozzle settings always begin trom the side where the cooling water connections are located From there proceed in a counter clockwise direction and specify side after side See Figures 11 and 12 If you like you can order the units preset from the factory does not apply to units held in stock 3 IMMMMMMT 3 MMMMMMt MMMMMMMMMMMMP YY VV VVVVVV vv v 1 Figure 11 Top view Pages 1 4 Figure 12 Top view Pages 1 4 ADAPT Parasol 600 ADAPT Parasol 1200 4 2 35 I s p 70 Pa Figure 14 Example 2 A 5 7 iis B 15 25 l s Figure 13 Example 1 A 2 1 Ils B 15 4 l s Example 1 Nozzle setting LHLH produces the lowest possible No Occupancy flow sides 1 3 open This produces a min flow No Occupancy flow of 4 2 I s and a max flow of 35 I s at p 70 pa Example 2 If it is instead more important to obtain the highest pos sible max tlow capacity the nozzles should be set to the HHHH position i e fully open on a
13. the No occupancy mode function is active the system automatically switches over to the energy save mode The system returns to the Occupancy mode and normal operation when occupancy Is registered again In the energy save mode no occupancy mode the valve actuator is controlled to regulate the chilled water flow or hot water flow according to the status on other sen sors in the room but normally with a greater permissible deadband from the temperature setpoint for cooling or heating than in the occupancy mode whilst the air is controlled to the min flow setting Holiday When the Holiday operating mode is active the system automatically switches over to the energy save mode just as in the case of the No Occupancy mode but with scope for allowing further greater temperature differential Con trolled trom a main control system Swegon reserves the right to alter specifications 2015 12 16 Swegon Stand by idle mode When the control system registers that a window is open the controller switches over to the Stand by mode When the window is closed the controller switches over to the Occupancy mode The controller is in the Stand by mode the room temperature is kept above 10 C frost protec tion Emergency mode In the event of a fire alarm the controller opens or closes the air damper in the extract air duct depending on how the control system is set In the Emergency mode cool ing and heating are switched of
14. 015 12 16 www swegon com ADAPT Parasol b Figure 25 Water connections with factory fitted valves An ADAPT Parasol 1200 is shown in the example Figure 28 Suspension of a two module unit Figure 29 Assembly piece SYST MS M8 1 ceiling mount and Figure 26 Water connections without factory fitted valves Iresded rod An ADAPT Parasol 1200 is shown in the example R BE a Figure 30 All controll equipment is gathered on the same side to simplity the work during installation and service Controller and pressure sensor are mounted to a bracket easy removable by loosing two screws see arrows Figure 27 Air connection piece Variant ADAPT Parasol 600 A 125mm ADAPT Parasol 600 PF A 160mm ADAPT Parasol 1200 A 125mm ADAPT Parasol 1200 PF A 160 mm 17 Swegon reserves the right to alter specifications 2015 12 16 www swegon com q joseued LdvVaV ADAPT Parasol b Technical data Total cooling capacity max 2 055 W Heating capacity water max 2 00 W Heating capacity electric max 1 000 W Airtlow Single module units 7 34 1 5 Two module units 7 85 I s Length Single module units 584 592 598 617 623 642 667 mm Two module units 1 248 1 292 1 342 mm
15. 16 www swegon com ADAPT Parasol b Swvegoon ADC All comfort modules are supplied with ADC air deflectors ADC stands for Anti Draught Control which enables you to set the diffusion pattern of the air being distributed to avoid risk of draught A number of ADC sections with four air deflectors per section are arranged on each side of the unit Each section is adjustable from a straight set ting to 40 air deflection to the right or left in increments 5 of 10 This offers enormous flexibility and can be easily adjusted without affecting the sound level and the static pressure The water capacity is reduced by 5 10 when the ADC is adjusted to fan Fal shape Figure 22 Possible settings for the ADC Fan shape Figure 23 Possible settings for the ADC X shape Figure 21 ADC setting range from 40 to 40 in increments of 10 Figure 24 Possible settings for the ADC Straight airflow setting 15 Swegon reserves the right to alter specifications 2015 12 16 www swegon com q Joseied IdVAV ADAPT Parasol b Installation Recommended types of ceiling The ADAPT Parasol is designed to fit in most T Bar and Clip in type ceiling systems in terms of length and width To guarantee a quality finish in T Bar ceiling system we recommend T profiled sections with a width of 24 mm Suspension The ADAPT Parasol has four mounting brackets for suspension and is installed u
16. ADAPT Parasol D Energy saving comfort module for Swegon s WISE System for demand controlled ventilation Quick facts Quick guide p gt gt Comfort modules for demand controlled ventilation and Primary airflow Swegon s WISE system Pressure range Energy efficient operation since the room is ventilated Total cooling capacity heated and cooled exactly as called for by the load Heating capacity neither more or less g Capacity Highest possible comfort with provision for individual Size control on the product or at room level Waterborne cooling energy and waterborne or electric heat Draught free indoor climate 4 way air distribution and Swegon s ADC Anti Draught Control provide maxi mum comfort and flexibility both today and for future needs Simple installation commissioning and maintenance Complete product with all components and accesso ries installed from the factory EUROVENT CERTIFIED PERFORMANCE www eurovent certification com www eurovent certification com www certiflash com Up to 85 I s 50 to 150 Pa Up to 2 055 W Water Up to 2 00 W Electric Up to 1 000 W 600 and 1200 with adapters for a number of ceiling systems Swegon q joseied ldVaV ADAPT Parasol b al i 5 i25 281 12522 77 2_ WM Ly UT A Milf WY WM MY Uy Yj i ADAPT Parasol comfort module The ADAPT Parasol is based on a standard Parasol but is eq
17. AT 20 K and the primary airflow 16 l s a heating capacity of P 585 W trom a single module unit with LHLH nozzle settings which is sufficient for meeting the heating load Heating water With a heating capacity requirement of 488 W and AT 6 K the necessary water flow is obtained in Diagram 5 0 019 I s The pressure drop of the heated water is calculated on the basis of a water flow of 0 019 I s and the pressure drop constant k 0 0241 which is taken from Table 6 The pressure drop will then be Ap q k_ X 0 019 0 0241 0 62 kPa As an alternative the pressure drop can be read in Diagram 6 Electric heating The 488 W heating load can also be met with ADAPT Parasol electric heating variant X1 which generates 500 W heating capacity 28 Swegon reserves the right to alter specifications 2015 12 16 www swegon com ADAPT Parasol b Table 10 Cross talk Typical R values between office rooms with ADAPT Parasol where the partition wall extends with its top edge against the suspended ceiling with excellent sealing prop erties Assumes that the partition wall will have at least the same R value as that given in the table Sus With pended ADAPT ceiling R dB Parasol R dB Light acoustic suspended ceiling Mineral wool or perforated steel aluminium cof fers or screen Light acoustic suspended ceiling Mineral wool or perforated steel aluminium cof fers or screen The suspended
18. ackage together with its intelligent control system where numerous adaptations can be made contribute to making the product very flexible and future proof As an example it is noteworthy that all the units can operate as master or slave simply adjustable by changing a parameter together with repositioning an RJ cable This means that in the event an open plan office for example is divided up into office cells the extra work involved in adapting the product to the new operating conditions is minimized ADAPT Parasol PlusFlow If you need both high cooling capacity and high airflows then the ADAPT Parasol 600 1200 PF is the right choice ADAPT Parasol PF installed in a conference room for instance can reduce the number of installed products by 50 The module can handle large airflows and at the same time has the same high cooling and heating capacity as a Standard ADAPT Parasol of course with maintained high level of comfort in the room High capacity With its high capacity the ADAPT Parasol utilizes 40 50 less ceiling area for handling the cooling energy demand in a normal office compared with a traditional climate beam Simple to adjust By means of built in nozzle regulation with numerous possible settings the ADAPT Parasol offers optimum com tort and can be easily adapted to meet a change in room size or operations conducted inside the premises The comfort module can be set so that different air volumes are diffused
19. alternative nozzle settings use Swegon s ProSelect sizing program available at www swegon com 2 Room attenuation 4 dB 3 The specified capacities are based on operation in the high capacity mode Operation with the face plate set to the normal posi tion reduces the water capacity of the ADAPT Parasol 600 by about 5 and that of the ADAPT Parasol 1200 by about 10 The water capacity can vary depending on installation and how the airflow deflectors are set The primary air capacity is not affected N B The total cooling capacity is the sum of the airborne and waterborne cooling capacities 21 Swegon reserves the right to alter specifications 2015 12 16 www swegon com q Joseied LdVaAV ADAPT Parasol b Table 3 Cooling capacity ADAPT Parasol 1200 Nozzle Nozzle Primary Cooling capacity of Cooling capacity water W Pressure drop con pressure setting 1 airflow primary air W for AT for AT 83 stant air water rate I s Pirin 24 22 aie 282 353 423 200 seo esa 733 eos 416 00220 nt 356 26 256 3a2 a27 sta 520 506 678 753 ez7 50a 00220 Pam 342 26 251 33a ate 501 557 a5 723 813 e909 416 00220 C f rem a2 2 29 304 405 506 608 580 663 753 842 022 504 00220 Coor uu ms 20 1z 168 210 252 471 544 ez 606 768 184 00220 f an 395 2 28479 a s60 603 697 790 875 966 416 00220 Pan ara a2 34a aso 574 eae 627 715 810 908 989
20. alve actuator ACTUATOR b 24V NC xx pcs e Valve SYST VDN215 xx pcs e CO sensor DETECT Qa xx pcs e VOC sensor DETECT VOC xx pcs e External sensor module SENSORMODULE aaaaaaaa xx pcs e Cable 2xRJ12 SYST CABLE RJ12 6 LED xx pcs e Cable USB RJ12 CABLE CONVERTER USB RJ12 xx pcs e Network cable LINK Wise xx pcs e Connection box CONNECT Adapt xx pcs e Key card circuit breaker SYST SENSO xx pcs e Connection piece air SYST AD1 aaa xx pcs e Connection piece air 90 SYST CA aaa 90 xx pcs e Assembly piece SYST MS M8 aaaa b ccccc xx pcs e Flexible connection hose SYST FH aaa bbb 12 xx pcs e Venting nipple push on SYST AR 12 xx pcs e Plasterboard ceiling frame PARASOL c T FPB aaaa xx pcs e Tool for nozzle adjustment SYST TORX 6 200 xx pcs e Perforated face plate PARASOL c T PP a bb xx pcs For more intrmation see the separate sections in the Water borne Climate Systems catalogue and ADAPT Para sol Technical Manual at our website www swegon com 3 Swegon reserves the right to alter specifications 2015 12 16 www swegon com q Joseied IdVAV
21. ceiling is lined with 50 mm thick mineral wool Light acoustic suspended ceiling Mineral wool or perforated steel aluminium cof fers or screen Vertical 100 mm thick mineral wool panel as sound insulation between the office cubicles Perforated plasterboard ceiling panels in T section grid system Acoustic insulation on the top side 25 mm thick Seal the plasterboard suspended ceiling 45 with insulation on top side Overview Rockwool 70 kg m Gullfiber 50 kg m Swegon reserves the right to alter specifications 2015 12 16 Swegon Natural attenuation and end reflection natural attenuation AL dB including end reflection Table 11 Natural attenuation AL dB ADAPT Parasol 600 Octave band Hz Nozzle setting Table 12 Natural attenuation AL dB ADAPT Parasol 600 PF Octave band Hz E X Table 13 Natural attenuation AL dB ADAPT Parasol 1200 Octave band Hz al rT a no e Doleta Table 14 Natural attenuation AL dB ADAPT Parasol 1200 PF Octave band Hz aani ea 25 x m 230 9 ops s B 29 www swegon com q oseled LdVaV ADAPT Parasol b Swegon Dimensions and weights Table 15 Dimensions ADAPT Parasol 600 Length L mm Width W mm 584 592 598 617 623 584 592 598 617 623 642 667 642 667 Table 16 Weight ADAPT Parasol 600 L 2 592 ADAPT Parasol Dry weight Figure 33 ADAPT Parasol 600 viewe
22. connection 12x1 0 mm Cu Male threads DN15 1 2 32 Swegon reserves the right to alter specifications Swegon Air connection ADAPT Parasol 600 1200 e0000 Figure 41 Connection with bend viewed from end panel Mounted connection piece SYST CA xxx 90 ADAPT Parasol 600 ADAPT Parasol 600 PF ADAPT Parasol 1200 ADAPT Parasol 1200 PF 2015 12 16 H 460 125 H 495 160 H 460 125 H 495 l 160 www swegon com ADAPT Parasol b Sweegon Accessories factory fitted Valve with actuator SYST VDN215 with ACTUATOR b 24V NC for cooling and heat ing A Fitted and wired to the controller See separate product datasheet at www swegon com wg l Detect Qa Co sensor Analogue carbon dioxide sensor to be fitted concealed from view above the face plate See separate product datasheet at www swegon com Detect VOC sensor Modbus connected air quality sensor to be fitted concealed from view above the face plate POWER Adapt 20 VA transformer wn 230 V 50 60 Hz input voltage r m 24 V AC output voltage j 20 VA capacity IP33 rated enclosure The factory fitted accessories above can also be ordered as individual items of equipment Accessories SYST TS 1 72 VA Transformer Double insulated protective transformer 230V AC 24 V AC See separate product datasheet at www swegon com CONDUCTOR T TG temperature sensor External temperat
23. d from side laid Water connections ADAPT Parasol 600 These are examples of the most common sizes of the ADAPT Parasol For other variants we refer to our ProSelect program at www swegon com Excluding sensor module 0 1kg 192 192 O00000 o If 78 35 240 270 220 250 Figure 34 ADAPT Parasol 600 water connections W2 Figure 31 ADAPT Parasol 600 viewed from end panel ADAPT Parasol 600 PF 600 B1 fa V rme retur V rme tillopp Kyla tillopp Heating return Heating supply Cooling supply QO Kyla retur Cooling return Figure 35 Label ADAPT Parasol 600 Al Chilled water inlet connection 12x1 0 mm Cu A2 Chilled water return connection 12x1 0 mm Cu Male threads DN15 1 2 B1 Heated water inlet connection 12x1 0 mm Cu B2 Heated water return connection 12x1 0 mm Cu Male threads DN15 1 2 c c min 468 max 547 Observe the following For the single module unit it is important that the chilled 1o ff il water is connected to the correct pipe connection The k direction of water flow is necessary for obtaining full capacity The required direction of water flow is marked by arrows on the end wall of the unit Figure 32 ADAPT Parasol 600 viewed from above 30 Swegon reserves the right to alter specifications 2015 12 16 www swegon com ADAPT Parasol b Swegon Dimensions and weig
24. d on operation in the high capacity mode If the face plate is set to the normal position this will reduce the water capacity of the ADAPT Parasol 1200 PF by between 5 and 12 The water capacity can vary depending on the installation and how the air deflectors are set The primary air capacity is not affected N B The total heating capacity is the sum of the airborne and waterborne heating capacities If the primary air temperature is lower than the room temperature it causes negative impact on the total heating capacity 27 Swegon reserves the right to alter specifications 2015 12 16 www swegon com q oseled ldVaV ADAPT Parasol b Calculation example heating In a separate office room with dimensions b x dx h 2 4 x 4 x 2 7 m the same room as in the example for cooling energy there is also a heating energy demand of 450 W in the winter The primary air flow should be the same as in the summer case 16 I s and the duct pressure is now also kept constant Design room temperature t 22 C heating water tem perature Supply return 45 39 C and the primary air temperature t 20 C produces AT 6K AT 20K AT 2 K Solution Heating The primary airflow of 16 l s in combination with the primary air temperature of 20 C produces a negative impact on the heating capacity 1 2 x 16 x 2 38 W The required heating capacity trom the heated water thus increases to 450 38 488 W From Table 6 we obtain from
25. es It pos sible to save a large air volume when the module operates in the No occupancy mode which in this case involves 4 6 I s As an alternative the nozzles can be set to the HHHH set tings This then delivers more air when the room is unoc cupied less savings but an over capacity of air volume and cooling to utilise if for example there are often visitors to the office Chilled water With the cooling capacity requirement of 326 W for the cooling water obtain in Diagram 1 the required water flow With a temperature increase of AT 2 K the water flow will be 0 039 I s In Diagram 2 we can read that a water flow of 0 039 l s does not produce a fully turbulent outflow but that the capacity must be corrected by a reduction factor of 0 97 The loss of capacity can be compensated by calculating the comfort module s required cooling capacity as fol lows P 326 0 97 336 W A new water flow can be obtained from Diagram 1 q 0 040 I s The pressure drop for the heating water is calculated on the basis of a water flow of 0 040 I s and pressure drop constant k 0 020 which is taken from Table 1 The pressure drop can now be read to be 4 0 kPa from Diagram 4 Swegon reserves the right to alter specifications 2015 12 16 www swegon com 23 q Joseied IdVAV ADAPT Parasol b Heating Heating function The comfort module s capability of quickly mixing the pri mary air with the room air makes the ADAPT Parasol
26. es the right to alter specifications 2015 12 16 www swegon com q JOseied ldVAV ADAPT Parasol b Diagram 4 Pressure drop Water flow Cooling V m s OL I s yo goo 0 1 0 8 0 7 0 6 0 5 0 05 0 4 0 04 0 3 0 03 1 2 3 4 5 10 20 30 40 Ap kPa 2015 12 16 www swegon com Swegon reserves the right to alter specifications ADAPT Parasol b Table 1 Cooling capacity ADAPT Parasol 600 Nozzle Nozzle Primary Cooling capacity of Cooling capacity of the water W Pressure drop pressure setting airflow primary air W for AT for AT 3 constant 1 rate air water 1 5 e ee ea ae Mea E E ooitadt ke k sora u 72 20 s2 69 26 104 196 226 258 287 319 348 101 00200 Pans a 20 96 12 161 193 258 300 338 380 azz 264 199 0 0200 C am 6 2 ia 108 235 1282 278 324 370 a15 261 502 277 00200 Pam se 2a 114 53 191 229 303 sz 396 aaa 292 520 188 00200 Fit 22 25 167 203 278 334 326 378 431 a83 534 sei 277 00200 Coors ut 96 20 69 oz 15 138 255 297 335 377 are 460 101 00200 a a Nozzle Nozzle Primary Cooling capacity of Cooling capacity of the water W Pressure drop pressure setting airflow primary air W for AT constant rate air water I s Bre Se iO E AE anes CAR k UJ OJIA NE OO CO 1 For particulars on the sizing of
27. es with the ADAPT Parasol is that System for demand controlled ventilation the pressure in the nozzles can be kept at a high level and this means controlled throw lengths high capacity and maintained Coanda effect of the air regardless of the operating conditions Via the SuperWISE a communication unit which via Modbus RTU ties all the components in the WISE system together ADAPT Parasol communicates with other WISE products in the system and all the way up to the GOLD air The Swegon CONTROL Zone damper is used for maintain handling unit ing constant pressure in the zone Swegon reserves the right to alter specifications 2015 12 16 www swegon com ADAPT Parasol b Demand controls the climate in the room e Stepless regulation of the airflow as required temperature or the air quality e f an air quality sensor is used it overrides the temperature sensor e Same stepless function regardless of whether it concerns one product in an individual room office or several prod ucts in an open plan office or a conference room e Besides ventilating in an efficient way the room temperature is regulated by means of both waterborne and airborne cooling e Can advantageously discharge heated air from the ceiling all in one product e Can be combined with radiators or floor heating the product then takes this into consideration and regulates the room temperature in an energy efficient way for example by increasing the airflow
28. etween the ADAPT Parasol and the open ing cut in the plasterboard ceiling Tool for nozzle adjustment SYST TORX Tool designed for easy adjustment of the nozzle plates Optional perforation patterns The face plate of the unit is available with three different perforation patterns that make it easily adaptable to suit many different types of installations e g light fittings and extract air registers that share the surface of a suspended ceiling A suspended ceiling containing different types of perforation patterns could be perceived as disturbing to the eye Other patterns are of course available on special order For further details contact your nearest Swegon representative A Face plate standard PB Circular holes arranged in a triangular pattern ORO RORORAORAOCAOCAOCAO oRoBo8o8o8o8e8o808d OROKROKROROKOROKORO OROROROROKROROKORO 0202626262626 26262 0202626202626 26262 B Face plate PD SO8GCSS63G03953008 OSog0 90800020009090 Circular holes arranged in a square pattern with a graduated 9095900980095090 0000000500000000909 border BBES595880595080604 ORORORORORORORORO 0625252 Oo 2626 a 2393030393099923539 C Face plate PE Square holes arranged in a square pattern with a graduated border Swegon reserves the right to alter specifications 2015 12 16 OOO0OO0O0000000
29. f Supply air is normally switched off The Emergency mode can only be managed in control systems that are connected to a main control system via Modbus RTU Commissioning level The First open function involves having the water valves open while the installation work is in progress which simplifies filling pressure testing and venting the water system The function will be automatically deactivated after approx 6 minutes while the system is energised A clicking noise can be heard when the valves and damp ers change over to the NC mode normally closed and the normal control function is activated Further particulars of the commissioning mode can be read in the description of the sensor module on page 12 Summer night cool The function involves the use of cold air trom outdoors tor cooling the room at night to the predefined level The function can only be handled in the control system that Is connected to a main control system via Modbus RTU www swegon com q Joseied 1IdVAV ADAPT Parasol b Functions Change over The function involves the use of only one valve actuator which should be wired to the cooling output terminal This actuator then controls both the heating water and the chilled water which is transported in the same pipe An external temp sensor should be used and this com ponent should take measurements on the pipe through which water always circulates In winter when heating is required t
30. g capacity W for temperature differential room water ATK E a E 5 22 Swegon reserves the right to alter specifications 2015 12 16 www swegon com ADAPT Parasol b Swegon Calculation example cooling A cellular office having dimensions w x d x h 2 4 x 4 x 2 7 m is to be fitted with a comfort module The total cooling demand is estimated to be 50 W m To meet this cooling load an ADAPT Parasol that will generate 50 x 2 4 x 4 480 W is required Design room temperature t 24 C cooling water tem perature inlet flow return 14 16 C and primary air temperature t 16 C generates AT 2K AT 9K AT 8K The required primary air flow to the room q has been determined to be 16 I s A zone damper ensures that the pressure in the duct should be kept at a constant of at 70 Pa The sound level from the unit must not exceed 30 dB A Solution Cooling The cooling capacity of the primary air can be calculated using the following formula P 1 2 AT q P 1 2 8 16 154W The ADAPT Parasol comfort module should therefore be able to generate 480 154 326 W in cooling capacity on the water side In Table 1 we can read that one 592 x 592 mm ADAPT Parasol with LHLH nozzle settings for a primary air flow of 16 l s generates 444 W in cooling capacity on the water side This is thus sufficient for meeting the cooling demand in the room At the same time this nozzle configuration mak
31. he following coil heat exchanger variants Variant A Supply air and waterborne cooling energy from coll Variant B Supply air waterborne cooling energy and heat from coil Variant X Supply air waterborne cooling energy and heat from electric heating elements 2015 12 16 www swegon com ADAPT Parasol b Figure 1 Variant A Cooling and supply air operation Figure 3 Variant X Supply air and heating operation with electric 1 Primary air heating elements also includes cooling function 2 Induced room air 3 Primary air mixed with chilled room air 1 Primary air 2 Induced room air 3 Primary air mixed with heated room air Figure 2 Variant B Heating and supply air operation includes also cooling operation 1 Primary air 2 Induced room air 3 Primary air mixed with heated room air Swegon reserves the right to alter specifications 2015 12 16 www swegon com q joseued LdvVaV ADAPT Parasol b Compact and intelligent unit The ADAPT Parasol is supplied as a compact and intel ligent unit in which the damper and control equipment is integrated into the product Only the power supply and possible connection to a main control system need to be wired from the module The sensor module which is a vital part of the product is a combined presence detector and a temperature sensor Its default location is within the face plate however it can also be mounted on a wall The p
32. he valve opens if the water in the pipe is warmer than the temperature set point If the water is colder the valve does not open In summer when cooling is required the valve opens if the water in the pipe is colder than the temperature set point Figure 9 e 2 pipe system with chilled water in the summer and heated water in the winter e GT is located where heated or chilled water always circulates e Summer If the room temperature T is higher than the water temperature T the valve opens if there is a cooling demand e Winter If the room temperature T is lower than the water temperature T the valve opens if there is a hea ting demand e GT is wired to the controller as an external tempera ture sensor e In the SWICCT or SuperWISE the operator has enter a setting in the controller indicating that the sensor is to be used for Change Over operation e GT is the temperature sensor that is mounted in the Sensor module e The valve actuator should be wired to the cooling output of the controller 10 Swegon reserves the right to alter specifications SWICCT External temperature sensor use ange over temperature v Not used Room temperature Change over temperature Temperature read only Window contact NO Window contact NC Figure 10 Exercising of valves The function involves exercising the water valves regularly by means of automatic control equipment to prevent them from seizing or becoming
33. how to use external sensors e g for air quality e Airflows e Commissioning g swicct Temperature setpoint settings Controller settings Temperature settings Cooling setpoint OCC Ventilation boost delay Room temperature sensor use Heating setpoint OCC Cooling setpoint NoOCC Heating setpoint NoOCC Cooling setpoint Holiday Heating setpoint Holiday Cooling setpoint SNC Ventilation boost time Occupancy on delay Occupancy off delay Occupancy type Two step colling delay Air cooling sequense Air Water Air Mean value of sensor module s Input 1 usage Extemal temp Not used ChOv 4 Dead Zone low limt 550 ChOV 4 Dead Zone high limit 650 Commissioning Heating setpoint SNC Slave air function Air Water Regulator settings STOP water actuators E amp On OF 3 E Open cooling valve Open heating valve Min unoccupied Min occupied K4actor min flow Mac K4actor max flow 2 Min holliday P band Heating P Band Cooling l4ime Heating Airflow settings an E Valve first open function Pe mn min l s 10 Time Cooling P Band airflow Zero cal pressure sensor Airflow setpoint HOLIDAY Airflow setpoint UNOCC Airflow setpoint OCC Airflow setpoint MAX l s 10 Controller states is 10 Controllers current state 8 6 3 38 3 8 Hime airflaw S Occupied es Vs 10 VOC use Vs 10 Force holiday CO2 VOC min set value CO2 VOC max set value Input 3 usage Not used
34. hts Table 17 Dimensions ADAPT Parasol 1200 Length L mm Width W mm 56 F JR KO E 1184 1192 1198 1242 584 592 598 617 623 1248 1292 1342 642 667 Table 18 Weight ADAPT Parasol 1200 ADAPT Parasol Dry weight moas 298 o9 Figure 36 ADAPT Parasol 1200 viewed from end panel These are examples of the most common sizes of the ADAPT Parasol For other variants we refer to our ProSelect program at www swegon com Excluding sensor module 0 1kg Cre O00900 e OES 19 240 270 220 7 250 A c c 1190 c c min 468 max 547 125 160 pr Figure 37 ADAPT Parasol 1200 viewed from above ADAPT Parasol 1200 PF 63 1167 76 102 Figure 38 ADAPT Parasol 1200 viewed from side ADAPT Parasol 1200 PF 31 Swegon reserves the right to alter specifications 2015 12 16 www swegon com q Joseied ldVaV ADAPT Parasol b Water connections ADAPT Parasol 1200 Figure 39 ADAPT Parasol 1200 water connections O V rme retur V rme tillopp Heating return Heating supply Kyla tillopp Kyla retur Cooling supply Cooling return Figure 40 Label ADAPT Parasol 1200 Al Chilled water inlet connection 12x1 0 mm Cu A2 Chilled water return connection 12x1 0 mm Cu Male threads DN15 1 2 B1 Heated water inlet connection 12x1 0 mm Cu B2 Heated water return
35. ide ally suited for managing both cooling and heating Heat ing premises with air heated above room temperature delivered from the ceiling is in other words an excellent alternative to traditional radiator heating solutions Some of the benefits achieved include lower installation costs simpler installation and perimeter walls free trom piping and radiators When the ADAPT Parasol is set to maintain a high nozzle pressure there will be a certain heating capacity even with low airflow conditions or while the module is operating during weekends for instance when the flow is reduced for a longer period Regardless of the type of heating system installed it is important to consider the operative temperature in a room Most people are comfortable when the opera tive temperature in winter is in between 20 24 C The optimum comfort requirements are normally met when the room temperature Is 22 C This means that in a room with a cold perimeter wall the air temperature must be higher than 22 C to compensate for the radiant cooling In new buildings with normal insulated perimeter walls and normal standards of window glazing the difference between the room air temperature and the operative temperature is small But for older buildings with worse windows it may be necessary to raise the air temperature to compensate for the chilling effect Different operating scenarios can be simulated easily using the Swegon Pro Clim Web software where bo
36. in Swegon s standard shade of white RAL 9003 gloss rating 30 6 Communication Modbus RTU 36 Swegon reserves the right to alter specifications Each side can be set in four different 201 40 41 The pipework contractor connects the connections points for water to the plain pipe ends and fills the system vents it and tests the pressure If the room control equipment is installed from the factory con nect the return pipe for chilled water and heating water respectively to the valve DN 1 2 male threads The ventilation contractor connects ducting to the air connection spigot The electrical installation contractor connects the power 24 V and the signal cables to the wiring ter minals equipped with spring loaded pressure connec tions The maximum permissible cable cross sectional area is 2 5 mm For reliable operation we recommend the use of cable ends with multi pin connectors 5 12 16 www swegon com ADAPT Parasol b Specification text Example of a specification text conforming to VVS AMA Standard KB XX Swegon ADAPT Parasol comfort module for integrated installation in suspended ceilings with the following functions e Cooling e Heating water optional e Heating electric optional e Ventilation e Built in functionality for demand controlled ventilation e Adjustable air direction e ADC Indoor climate comfort control e Integrated circulating air opening in face plate e
37. ll sides A higher max flow will then be obtained however the No Occupancy flow will consequently also be slightly higher These adjustments are only different settings on the Same physical product which makes the unit very flexible and adaptable particularly together with the integrated software Swegon reserves the right to alter specifications 2015 12 16 Swegon K factors for each side can be obtained from Tables 2 5 or from the installation instructions on the Internet however the easiest way to do this Is in ProSelect where you can quickly test various variants Nozzle setting The unique built in nozzle control in the ADAPT Parasol makes it possible to individually set each one of the four sides Depending on the unit s location and the room s primary air requirement the primary air can be guided in all desired directions The direction of the airflow can be easily optimized using the Swegon ProSelect sizing program that is available from www swegon com The required nozzle setting is preset trom the factory but if required it can be simply changed at the site K factor Each nozzle setting has a specific K factor A total K fac tor for the unit can be determined by adding together the K factors for the nozzle settings on each side The relevant K factor for optimized nozzle setting can also be obtained in ProSelect Figure 15 Nozzle setting 11 www swegon com q Joseied IdVdV ADAPT Paras
38. lly open 6 The temperature reaches the room set point the damper and valve close UJ Water Air Room temperature Swegon reserves the right to alter specifications 2015 12 16 www swegon com q JOseied IdVAV ADAPT Parasol b Swegon Selection of sequence Air Water e The control sequence involves prioritising airborne cooling before waterborne cooling e For an occupied room the airflow is steplessly regulated between min and max depending on the room tempera ture or the air quality if an air quality sensor is used e f there is a cooling demand the air damper first steplessly opens to the fully open position if a cooling demand remains the water valve also opens Flow Water Air Max occupancy flow Min occupancy flow Valve 100 open Vacancy flow Valve 0 open Water Figure 7 Alr Room temperature Occupancy temperature rises Room temperature reaches level for cooling demand air damper opens Cooling valve is fully open but cooling is still required in the room the valve opens in order to cool with water Air damper and water valve fully open The temperature reaches the room set point the damper and valve close mB WN Sequence Air quality Flow Air Max occupancy flow Min occupancy flow Vacancy flow Occupancy with increased airflow to improve air quali
39. minals Transformer 7 Pressure sensor Motor for se damper blade h a A A Taelen IE Valves and actuators for cooling and heating ADC 40 to 40 angle Can be preset from the Controller factory Preconfigured from the factory Adjustable nozzle set VOC or CO sensor ting on all four sides Sensor module with Preset from the factory temperature and presence detector Figure 4 All components in the product can be installed directly from the factory temperature measurement from the sensor module mounted in the face plate is not recommended in the case of heating Swegon reserves the right to alter specifications 2015 12 16 www swegon com q Joseied IdVAV ADAPT Parasol b Swegon Chiller and heat pump NESTOR Internal network Central intelligent Internet building automation i ae _ J E al oe A ware Sub Super WISE All Year Comfort system Zone i re c CONTROL Zone CONTROL Zone CONTROL Zone 4 Room a L ba A ADAPT Damper e e e i oye e gl A ba k Ay em ge ed gt AEk Sas GA 4 22 a z me bi r E kee a pa L es I gt G A ANI lt lt Passive air diffusers ADAPT active air diffusers pene ata Figure 5 Component of the WISE system The ADAPT Parasol is a component of Swegon s WISE One of the advantag
40. nd should be ordered sepa rately 16 Swegon reserves the right to alter specifications Swegon Condensation free cooling Since the comfort modules have to be designed to oper ate without condensation no drainage system is required To wire the electric heating elements The wiring instructions are available at www swegon com and are called ADAPT Parasol X m Overheating protection The ADAPT Parasol with electric heating is equipped with two thermal overheat protections The protection with automatic reset switches out the heating elements the zero conductor when the temperature exceeds 60 C When the temperature has dropped to 50 C the protec tion closes the circuit again and reenergizes the heating elements If the temperature instead rises to 75 C after the first overheat protection has tripped the second manually resettable overheat protection will kick in and will also switch off the phase conductor to the heating element To reset the overheat protection the perforated face plate should first be removed The red reset button is situated between the air heater and the end panel through which the cooling water pipes are installed After the overheat protection has been reset click the faceplate back into place CE marking The ADAPT Parasol with electric heating is CE marked in accordance with applicable requirements The CE Dec laration of Conformity Is available at our website www swegon com 2
41. ol b The sensor module The sensor module consists of a presence detector and a temperature sensor in the same unit This component is mounted as standard in the face plate on the ADAPT Parasol but it can also be ordered as an accessory for wall mounting and in that case either recessed in a standard electrical component box or surface mounted on the wall By pressing the appropriate buttons on the sensor module you can adjust the temperature in the room set the ADAPT Parasol to the commissioning mode and read the alarm list 6 light emitting diodes indicate in the normal mode which temperature level has been selected If an error occurs the current alarm is shown as a series of flashes that are translatable using an alarm list Use an RJ12 cable to connect the sensor module to the controller The floor area covered by the presence detector is approx 24 m if it is mounted at a height of 2 7 metres above the floor and in parallel with the floor Entering temperature adjustments To lower the temper ature setting press down the left hand button To raise the tem perature setting press down the right hand button 000000 Each diode corresponds to a one degree increase or decrease of the set point The base setting of temperatures is entered in SWICCT or SuperWISE Presence detector Diodes for temperature commissioning or alarm indication Function buttons Diode indicating function Green Ok
42. pplication The values for the p calculations are specified in Tables 6 9 The cooling or heating capacity of the air P 1 2 q AT P The cooling or heating capacity of the air W q Primary airflow l s AT Temperature difference between primary air t and room air t K V qy AT Swegon Heating capacity of the water P 4186 q AT Heating capacity of the water W Heating water flow l s Temperature difference between the heating water supply flow and return flow K Diagram 5 Water flow heating capacity PW AT 20K 18K 16K 14K 4000 12K 3500 10K 3000 i i i 8 K Pressure drop for heating circuit 2500 Ap k_ 2 P a pv Sas 2000 6 K Ap Pressure drop in heating circuit kPa q Heating water flow l s see Diagram 6 nee AK ka Pressure drop constant for heating circuit see 1000 Tables 6 9 2K 500 0 0 01 0 02 0 03 0 04 0 05 0 06 0 07 q I s 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 v m s Diagram 6 Pressure drop Water flow Heating I s PO v m s qv YO 0 1 1 0 0 05 0 04 0 5 0 03 0 4 0 3 0 02 0 2 0 01 0 1 1 10 100 Apy kPa 25 Swegon reserves the right to alter specifications 2015 12 16 www swegon com q Joseied IdVAV ADAPT Parasol b Table 6 Heating capacity ADAPT Parasol 600 pressure n airflow for AT 3 air water
43. see Diagram 1 K Pressure drop constant for cooling coil see Tables en Cooling capacity of the air P 1 2 q AT P Primary air cooling capacity W q Primary airflow l s AT Temperature difference between primary air t and room air t K Cooling capacity of the water P 4186 q AT Pi Cooling capacity of the water W Ak Chilled water flow l s AT Temperature difference between chilled water supply and return flows K Diagram 1 Water flow Cooling capacity AT K 5 K 4 K 0 10 0 3 0 4 0 5 0 6 0 7 0 8 0 9 q I s v m s Swegon Corrected capacity water flow Different water flow rates to some extent have effects on the capacity output By checking obtained water flow against Diagrams 2 or 3 the capacity indicated in Tables 1 4 may need to be slightly adjusted up or down Po k P Poe Corrected capacity W k Correction factor P Cooling capacity of the water Diagram 2 Corrected capacity Water flow ADAPT Parasol 600 k 1 1 1 0 0 9 0 8 q l s 0 03 004 0 05 0 06 0 07 0 08 0 09 0 10 Re 3000 Re 6000 q 0 033 q 0 066 Diagram 3 Corrected capacity Water flow ADAPT Parasol 1200 H q l s 008 0 09 01 1 0 a l EE 0 8 05 0 06 0 0 03 0 04 O 07 0 Re 3000 Re 6000 q 0 033 q 0 066 19 Swegon reserv
44. sing a threaded rod in each mounting bracket Figure 28 A double threaded rod with a thread lock should be used if there is substantial distance between the overhead slab and the unit The threaded rods and SYST MS M8 assembly pieces Figure 29 must be ordered separately Connection dimensions Water Without valves Cooling plain end Cu 12x 1 0 mm Heating plain end Cu 12x 1 0 mm With factory fitted valves Cooling Male threads DN15 1 2 Heating Male threads DN15 1 2 Air Air connection piece 125mm Connection frame variant PF 160mm To connect air ADAPT Parasol is supplied as standard with an open air connection on the right hand side viewed from the end where the water is connected The air connection piece is mounted on delivery for con nection to the primary air duct see Figure 27 A cover is tactory fitted to the left hand air connection however it can be easily moved to the other side if the air connection piece is to be fitted to the left To connect the water pipes Connect the water pipes using push on couplings or clamping ring couplings if the product is ordered without valves Note that clamp ring couplings require support Sleeves inside the pipes Do not use couplings that have to be brazed for connec tion of the water pipes High temperatures can damage the unit s existing solders Flexible connection hoses for water are available for both plain ends as well as valves a
45. supplied in rolls of 500 m Key card circuit breaker SYST SENSO Key card holder for hotel rooms A SYST MS M8 Assembly piece The assembly piece is used for installation and consists of threaded rods ceiling mounts as well as nuts for all four suspension mounts 34 Swegon reserves the right to alter specifications 2015 12 16 www swegon com ADAPT Parasol b Flexible connection hoses SYST FH Flexible hoses are available with quick fit push on couplings as well as clamping ring couplings for quick and simply connection The hoses are also available in various lengths Note that clamp ring couplings require support sleeves inside the pipes F1 Flexible tube with clamp ring couplings F20 Flexible tube with quick fit push on couplings F30 Flexible tube with quick fit push on couplings on one end and G2OID sleeve nuts on the other end SYST AR 12 push on venting nipple A venting nipple is available as a complement to the flexible hoses with push on couplings The nipple fits directly in the push on hose coupling and can be fitted in an instant Connection piece air insertion joint SYST AD1 SYST AD1 is used as an insertion joint between the ADAPT Parasol and the duct system Available in two dimensions 125 and 160 mm Connection piece air SYST CA duct bend 90 Available in two dimensions 125 and 0160 mm Plasterboard ceiling frame Parasol c T FPB Frame for creating an attractive transition b
46. th the room air temperature and operative temperature are specified Supplying heated air from the ceiling results in some Stratification of the air For a supply flow temperature of max 40 C the stratification is non existent while at 60 C it can be around 4 K in the occupied zone This only applies during the warming up phase when the room is unused and there is no internal load When the room is in use the lighting is on a computer is running and occu pants are in the room the stratification will decrease or disappear depending on the heating energy demand When heating with the ADAPT Parasol it is advisable to use an external temperature sensor or an extra sensor module in the room 24 Swegon reserves the right to alter specifications Swegon Electric heating The ADAPT Parasol variant with electric heating utilizes electric heating elements instead of heating water The tubular heating elements situated inside the heating water pipes of the coil heat the circulated air that passes through the coil Radiant heat constitutes only a small part of the total heating capacity The ADAPT Parasol with electric heating is available in two capacity variants see the table below N B For 1200 modules only Variant X2 2015 12 16 www swegon com ADAPT Parasol b Calculation formulae waterborne heating Below are formulae that enable the user to calculate what com fort module is best suited for the a
47. ty Air Figure 8 1 Occupancy CO VOC content rises aoan ara Room temperature 2 CO VOC content reaches the permissible upper limit value the air damper steplessly opens 3 Fully open air damper 4 CO VOC content reaches the permissible lower limit value the air damper closes 8 Swegon reserves the right to alter specifications 2015 12 16 www swegon com ADAPT Parasol b Operating mode Depending on the status of connected sensors the controller adjusts the outputs trom any of several possible operating conditions The operating conditions based on occupancy in the room the status of the sensor in use or signals from a main control system are described below Operating modes There are numerous functions in the ADAPT Parasol Occupancy mode No occupancy mode Holiday Stand by idle mode Emergency mode Commissioning Summer night cooling Occupancy mode When the ADAPT Parasol receives signals via presence detector that someone is in the room the valve actuator for chilled water or heating water as the case may be is controlled according to the selected temperature setpoint for cooling or heating associated with this operating mode The airflow is controlled to the preselected occu pancy flow but is influenced of course by sensors such as condensation sensors temperature sensors window contacts air quality sensors if required etc No occupancy mode When
48. ty can vary depending on the installation and how the air deflectors are set The primary air capacity is not affected N B The total heating capacity is the sum of the airborne and waterborne heating capacities If the primary air temperature is lower than the room temperature it causes negative impact on the total heating capacity 26 Swegon reserves the right to alter specifications 2015 12 16 www swegon com ADAPT Parasol b Table 8 Heating capacity ADAPT Parasol 1200 Nozzle Nozzle set Primary Sound Heating capacity water W for AT Pressure drop constant pressure ting airflow level air water 3 V5 _aB a 2 r oo En a 2 Son aa e23 0207 ias2 ress a16 00273 o O 35 6 26 Paar as s0 1243 ars 1705 50a 00273 34826 Poe aa ona isas ison e265 416 00273 aaa as sor oas i34 1642 1973 soe 00273 Pf s aca san 990 vase r 1947 416 00273 Pa as 2 o saa vor iaer 762 1994 504 00273 Table 9 Heating capacity ADAPT Parasol 1200 PF Nozzle Nozzle set Primary Heating capacity water W for AT Pressure drop constant pressure airflow 3 air water 992 i 986 77 e02 1302 607 1878 761 0027 Tose 1294 1593 1868 574 0027 1 For particulars on the sizing of alternative nozzle settings use Swegon s ProSelect sizing program available at www swegon com 2 Room attenuation 4 dB 3 The specified capacities are base
49. uipped with functions for demand control of the indoor climate Available as single and two module units Sizes 600x600 600x1200 Modules Supply air and cooling Supply air cooling and heating water Supply air cooling and heating electric Installation Flush mounting in suspended ceiling Function The essential function of the comfort modules is closely related to that of climate beams The major difference is that comfort modules distribute air in four directions instead of two This maximizes the area for the induction of room air with the supply air which enables the modules to deliver a high capacity without occupying more ceiling space than necessary The comfort modules are also opti mized to quickly mix the supplied air with the room which provides better comfort in the room In heating applica tions this technique also ensures heat is conveyed along the ceiling in a better way Demand controlled indoor climate Demand controlled ventilation involves ventilating and conditioning the air in a room precisely to meet our needs no more and no less The potential for savings is sub stantial especially in premises where there is considerable variation between low and high load conditions in rooms and during times when there are few or no occupants which is the case in many premises Offices for example have in many cases an occupancy rate of less than 50 The ADAPT Parasol combines the best attributes from two worlds
50. ure sensor Used for example if the room temperature is to be 5 measured at a location other than by the sensor module or for measuring the tem perature on the main pipe in a change over system External sensor module Sensor module with temperature sensor and presence detector for wall mounting when an extra sensor module is required in the room 1 pc is always supplied with Aos a a the ADAPT Parasol Y e C Cy Available in a circular or rectangular model and is always supplied with both mount ing trame for the most common existing electrical connection boxes as well as a protruding frame for surface mounting 33 Swegon reserves the right to alter specifications 2015 12 16 www swegon com q Joseied IdVdV ADAPT Parasol b Cable SYST CABLE RJ12 6 LED Cable for connection of an external sensor module to the controller or between sensor modules Available in various lengths Cable CABLE CONVERTER USB RJ12 RS485 Cable with built in modem for connecting a PC to the controller Needed for running SWICCT or ModbusPoll for instance Connect ADAPT Connection box for connecting the cable together with a RJ12 connector and cable with multi pin cable ends Can also be used for connecting an ADAPT Damper for extract air LINK Wise Network cable for modbus communication within system WISE The cable meets the EIA 485 standard Shielded fourconductor AWG24 external diameter 09 6 mm grey PVC Note The cable is only