Home

USER MANUAL & MAINTENANCE GUIDE

image

Contents

1. COMMON FLT amp STEADY YELLOWS There is an open circuit fault in the wiring of the zone indicated ZONAL FLT TEADY YELLOW COMMON FLT amp STEADY YELLOW There is a short circuit fault in the wiring of the zone indicated ZONAL FLT amp FLASHING YELLOW GEN S C FLASHING YELLOW COMMON FLT amp STEADY YELLOW There is an open circuit fault in the wiring of one or both of the sounder SND FLT STEADY YELLOW circuits COMMON FLT amp STEADY YELLOW There is a short circuit fault in the wiring of one or both of the sounder SND FLT amp FLASHING YELLOW circuits GEN S C FLASHING YELLOW COMMON FLT amp STEADY YELLOW A processor fault has occurred To reset turn keyswitch on then back off If SYSTEM FLT STEADYYHLOW problem persists consult your dealer COMMON FIRE STEADYRED A manual evacuation has occurred ONLY The sounders will be active COMMON FIRE STEADYRED A fire has occurred in the zone indicated amp ZONE FIRE amp STEADYRED The sounders will be active The F A R E output will be active F A R E ACTIVE STEADYRED COMMON FIRE STEADYRED A fire has occurred in the zone indicated The F A R E output will be active amp ZONE FIRE amp STEADYRED The sounders have a delay set and will become active after the F A R E ACTIVE STEADYRED programmed delay To override the display press delay override GEN DISABLE amp STEADY YELLOW DEL STEADY YELLOW GEN DISABLE FLASHING YELLOW The panel is ready for selecting disable or test mode F
2. Fault light flashes when the panel detects an earth FAULT FAULT FAULTIDISABLEMENT B d E COWON SYSTEM a E fault short circuit to earth on the wiring to any part of the FAULT FAULT DELAY FAULT control panel GENERAL INDICATIONS SUPPLY GENERAL FARE Common Sounder Fault FAULT s c ACTIVE COMMON EARTH SOUNDER FA R E FIRE FAULT FAULT COMMON SYSTEM SOUNDER REPEATER FAULT FAULT DELAY FAULT GENERAL INDICATIONS POWER The Sounder status light flashes when there is a wiring fault on the Sounder Circuits Depending on where the fault has occurred one or all of the Alarm Sounders may no longer be operative If the fault is a short circuit fault then the S C LED will also be lit SUPPLY GENERAL FARE F A R E Fault FAULT sic ACTIVE cue C uo M The F A R E status LED lights when there is a wiring fault COMMON SYSTEM SOUNDER REPEATER on the F A R E Circuit POWER FAULT FAULT DELAY FAULT If the fault is a short circuit fault then the S C LED will also be lit GENERAL INDICATIONS POWER eu gee FARE Repeater Fault COMMON EARTH SOUNDER FARE The Repeater fault LED Lights when the panel can not FIRE FAULT FAULT FAULTIDIGABLEMENT communicate with a serial repeater connected to the panel COMMON SYSTEM SOUNDER REPEATER FAULT FAULT DELAY FAULT On power up the panel looks for a signal from a repeater If it GENERAL INDICATIONS does not see one it assumes there is no repeater connected If
3. LED is lit check if there is a power cut to the building Check that the mains supply to the fire alarm has not been turned off All other fault indications will need the service engineer s attention Call the engineer as soon as possible Note that when the alarm is in a fault condition the majority of the system will still function correctly Extra vigilance should be paid in the area with the fault The alarm may not be operational in this area Turning the key to the on position and pressing the Silence Tone button can silence the panel s internal buzzer If the fault is INTERMITTENT and comes and goes the panel will buzz every time the fault happens If this is not acceptable you may be able to disable the zone that has the fault see page 11 Approved Document No GLT MAN 121 PAGE 2 Issue 1 0 Authorised GH Date 25 04 2007 PREMIER M PLUS 48 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK CONTENTS 1 FIRE ALARM CONTROL PANEL SAFETY 1550 5 4 How to use this Fire Alarm Panel safely 2 THE PURPOSE OF A FIRE ALARM 4 Introduction to fire alarms FACP amp ITS INTEGRAL PSE 5 What the end users responsibility is including daily weekly quarterly amp annual checks 4 PANEL INDICATIONS amp CONTROLS essen nennen 6 A list of indicator LEDs a
4. SAFETY ISSUES There is no need to open this fire alarm during normal operation Any work carried out on this system must be performed by a competent person who is familiar with this type of system This equipment will operate safely provided it has been installed correctly in compliance with the Installation Manual It is recommended that the system is serviced frequently It is customary to arrange a regular maintenance contract with a competent organisation Ask the installation company for recommendations The system needs a thorough maintenance check annually at the very minimum If any part of this Fire Alarm Control Panel becomes damaged contact the company responsible for system maintenance to arrange repair replacement European Union Directives Conformance Statement This product has been manufactured in conformance with the requirements of all applicable EU Council Directives The Declaration of Conformance for this product is located at the following Address GLT Exports Ltd 72 78 Morfa Road Hafod Swansea SA1 2EN United Kingdom 2 THE PURPOSE OF A FIRE ALARM SYSTEM A Fire Alarm System is used to provide an early warning of a fire so that the property can be evacuated and the fire extinguished if it can be safely tackled or the local fire brigade called according to the company evacuation procedure Alarms can come from Smoke or Heat Detectors or manually be a person operating a Manual Call Point Split the sy
5. s relevant to the particular fault The Panel s Fault relay will also activate Typical faults are described below Common Fault POWER SUPPLY GENERAL FARE FAULT E OCINE The Common Fault LED is a common indicator that lights e FAD or EL when there is a Fault on any part of the Fire Alarm Systems ENIM SG ESTNE DA It is usually lit in tandem with at least one other fault light FAULT FAULT DELAY FAULT which conveys more precise information on the type of Fault detected GENERAL INDICATIONS If this light is lit by itself it indicates a Keyswitch fault FIRE FAULT D DISABLI El FAULT DISABLED Zone Fault The relevant Zone Fault light flashes when there is a wiring problem on a Zone or detector has been removed from its base It should be noted that any alarms raised on the fault zone s may not be recognised by the Fire Alarm Panel until the Fault Conditions have been cleared It can take up to 60 seconds from repairing a fault for the display to clear THREE UE Do TT RO HE DET TTTTTTTTTTTTITTTIHTITIT T RI HOT an LER ELTE TELE E Short Circuit Fault POWER SUPPLY GENERAL FA R E FAULT s c ACTIVE i gt 2 SNEER FARE If the Fault is a short circuit fault then the S C LED will be lit FIRE FAULT FAULT FAULTOISABLENENT This GEN S C LED will be lit for S C faults on the zone COMMON SYSTEM SOUNDER REPEATER and sounder circuits It can take up to 10 seconds from repa
6. the back of this manual Power Supply Equipment General Description The PREMIER M 48 FACP has an integral linear power supply capable of supplying 3 amps in total It contains a current limited output for charging sealed lead acid batteries 7 Ah maximum The PSE is monitored for main supply failure the battery not taking a charge and low battery voltage If the battery voltage drops below approximately 20VDC a fault condition the battery charging current will be turned off thus stopping charging This PSE is only capable of supplying power to the CIE and is not designed for any other use Approved Document No GLT MAN 121 PAGE 4 Issue 1 0 Authorised GH Date 25 04 2007 PREMIER M PLUS 48 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 3 USER RESPONSIBILITIES amp MAINTAINENCE OF THE FIRE ALARM SYSTEM INCLUDING THE FACP amp ITS INTEGRAL PSE According to the British Standard Code for Fire Detection and Alarm Systems for Commercial Buildings BS5839 Pt 1 2002 the owner or person having control of the premises should appoint a responsible person to oversee the effective operation of the Fire Alarm System Clause 47 1 Below is a summary of the main functions the Responsible Person is expected to carry out This summary is not intended to replace Section seven User responsibilities of BS5839 Pt 1 2002 available from BSI or your local library It is meant to give a brief outline of user responsibilities for the safe
7. upkeep of the Fire Alarm System The number in brackets shows the relevant BS5839 Pt 1 2002 clauses The responsible person must Have sufficient authority to carry out the duties associated with being the responsible person 47 2 a Check the system at least once every 24 hours to ensure there are no faults present 47 2 b Ensure there are arrangements for testing and maintaining the system 47 2 c Ensure the log book is up to date and available for inspection 47 2 d Instruct all relevant occupants on the basic operation of the system including start evacuation silence alarms silence faults and system reset 47 2 6 Take appropriate action to limit the rate of false alarms 47 2 f Ensure that all detectors and manual call points remain unobstructed at all times 47 2 0 Liase with maintenance personnel to ensure that cleaning maintenance or building work does not interfere with the functioning and reliability of the fire alarm system 47 2 h 9 Ensure any changes to the system are recorded with updated drawings operating instructions etc 47 2 i 10 Ensure that there are spare parts especially Call point elements held on site 47 2 j 1 amp 2 With the PREMIER M PLUS 48 Range of Fire Alarm Panels we recommend the following tests are carried out Daily Inspection e Check that the green Power LED is lit e If there are any yellow fault LEDs lit or the green Power LED is not lit report the fault s
8. 007
9. AST 4HZ GEN DISABLE FLASHS030YELLOW The user is scrolling through zones to select which one to disable or user ZONEFAULT FLASH3030 YELLOW has just enabled the zone ZONEDISABLE FLASH30 3 0 YELLOW GEN DISABLE STEADY YELLOW The indicated zone is disabled ZONE FAULT STEADY YELLOW ZONE DISABLE STEADY YELLOW GEN DISABLE STEADYYELLOW The Sounders are delayed by the amount set on the Rotary switch SW1 DEL STEADY YELLOW GEN TEST FLASH3030YELLOW The user is scrolling through zones to select which one to Test ZONEFAULT FLASH30330 YELLOW ZONETEST FLASH30330 YELLOW GEN TEST STEADY YELLOW The indicated zone is in Test Mode ZONE FAULT STEADY YELLOW ZONE TEST STEADY YELLOW 4 4 CHECKING THE PANELS INDICATION LEDS Turn the key switch to Controls Enabled position then press the LED test button All the LEDs on the front panel will light and the panel s internal buzzer will also sound If any LED Does not light up Report the fault to the engineer Approved Document No GLT MAN 121 Authorised GH Issue 1 0 PAGE 7 Date 25 04 2007 PREMIER M PLUS 48 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 5 THE FIRE CONDITION 5 1 HOW THE PREMIER M 48 INDICATES AN ALARM TES TEST FIRE FAULT D DISABLE 70 FIRE FAULT DISABLED ZONES SUPPLY GENERAL FARE po BOWER FAULT S C ACTIVE COMMON pz EARTH SOUNDER FA R E FIRES FAULT FAULT FAULT DISABLEMENT COMMON SYSTEM SOUNDER REPEATER FAULT FAULT DELAY FAULT GENERAL IN
10. DICATIONS POUT TTT T i p When the PREMIER M 48 Fire Alarm Panel is set into alarm by a Detector or Manual Call Point located a zone that is not already in alarm it will Light the General Fire LED and appropriate Zone Fire LED s on the front of its enclosure Sound Internal buzzer Start the Alarm Sounder s F A R E and Auxiliary RELAY outputs provided there is no Delay set on the sounders The building evacuation procedure should now be followed IMPORTANT NOTE If a zone has been disabled it cannot be triggered into Alarm This should be remembered when disabling part of the system see Disabling zones or sounders later in this manual 5 2 TO TURN OFF THE ALARM SOUNDERS e Alarm Sounders may be silenced by turning the control key to Control Enable position and momentarily pressing the Start Stop button The Alarm Sounders will cease to sound but the light s for the Zone s in Alarm and the red General Fire light will stay lit The Auxiliary Fire relay will remain active The Panels internal buzzer can also be silenced by pressing the Silence int flt button button 2 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE If another detection Zone is activated after the Alarm Sounders have been silenced the panel will e Restart the sounders e Lightthe Zone Fire LED s for any new Zone s in alarm e Keep the light s for the previous Zone s in fire and Gen
11. LEDs will be lit When a zone processes an alarm signal the panel will indicate fire in the usual way but the sounders will not be active until the delay period has expired To override this delay press Delay Override Switch which will cause the external sounders to energise If there is no delay programmed the Delay Override Switch has no function 8 4 A FIRE ALARM CONDITION ON A DELAYED PANEL When an alarm occurs on a Delayed Panel the panel will e Light its General Fire and appropriate Fire Zone light s e Sound its Internal buzzer e Turn on the F A R E output e Start the Delay countdown sequence e Wait until the end of the delay and then start the sounders 8 5 OVERRIDING A DELAY IN THE EVENT OF A GENUINE FIRE ALARM If on investigation the cause of the Alarm is found to be a true fire hazard pressing the Delay Override will active the Alarm Sounders and Outputs with immediate effect 8 6 RESET THE SYSTEM IN THE EVENT OF A FALSE ALARM If on investigation the cause of the Alarm is found to be false turn the Key switch to the Controls Enabled position and press reset button 8 7 TO TURN OFF THE SOUNDER DELAY To turn off the sounder delay set the rotary switch to the 0 position Approved Document No GLT MAN 121 PAGE 12 Issue 1 0 Authorised GH Date 25 04 2007 PREMIER M PLUS 48 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK Approved Document No GLT MAN 121 PAGE 13 Issue 1 0 Authorised GH Date 25 04 2
12. Premier VI FIRE ALARM CONTROL PANEL DESIGNED TO COMPLY WITH EN54 PT2 amp PT4 1997 USER MANUAL amp MAINTENANCE GUIDE PREMIER M PLUS 48 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK What to do if the Fire Alarm Panel shows an Alarm Red LED Write down which LEDs are lit either in the log book or on a piece of paper for transferring to the log book later Follow the building procedures for fire alarm activation When the building has been evacuated the sounders can be silenced by turning the key to the on position and pressing the Start Stop Sounder button then pressing the Silence Tone button If there is no sign of fire investigate the area that reported the fire CAREFULLY Check for a detector or a call point with its RED LED lit If a detector caused the alarm look for any innocent phenomena that could have activated it Steam cooking food exhaust smoke excessive dust etc can all activate a smoke detector If anything is found try to clear the room by opening a window If a fire is discovered either tackle it with fire extinguishers if suitably trained or call the fire brigade To reset the panel press the reset button If the panel goes back into alarm silence the sounders and call the engineer What to do if the Fire Alarm Panel shows a Fault Yellow LED Write down which LEDs are lit either in the log book or on a piece of paper for transferring to the log book later If the supply fault
13. Zone 1 LEDs will flash 3 Press scroll switch until the LEDs are flashing at the disabled zone 4 Press SELECT and this will cause the General Disablement LED to flash with a 3 quick flash then off pattern 5 Turn control Key to Off position and this will turn off the General Disablement and Zone Disablement LEDs Approved Document No GLT MAN 121 PAGE 11 Issue 1 0 Authorised GH Date 25 04 2007 PREMIER M PLUS 48 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 8 USING SOUNDER DELAYS 8 1 WHAT IS A SOUNDER DELAY In certain circumstances it may be desirable to have a delay between the panel detecting a fire and starting its external sounders to allow the responsible person to check the cause of the alarm to stop building evacuation by an obvious false alarm If the cause of the Alarm is found to be a true fire hazard the Delay can be overridden and the Alarm Sounders activated immediately Alternatively in the case of a false alarm the Panel can be reset 8 2 SOUNDER DELAY SETTING On the PREMIER M 48 panel the sounder delay is global That is all zones will be delayed by the same amount The delay can be set between 1 minute and 9 minutes by adjusting rotary switch SW1 install manual or the delay can be left off sounders activate immediately by leaving rotary switch at position 0 8 3 HOW THE PANEL INDICATES SOUNDER DELAY If a Delay has been programmed into the Panel the General Disablement amp SOUNDER DELAY
14. accordance with the testing and inspection requirements of the relevant National wiring regulations in the UK this is the IEE Wiring Regulations The Batteries should be replaced because SLA batteries have a working life of 5 years Approved Document No GLT MAN 121 PAGE 5 Issue 1 0 Authorised GH Date 25 04 2007 PREMIER M PLUS 48 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 4 PANEL INDICATIONS amp CONTROLS TEST TEST FIRE FAULT D DISABLE ZONES FIRE FAULT DISABLED ZONES SUPPLY GENERAL FARE FAULT sic ACTIVE COMMON EARTH SOUNDER FARE FIRE FAULT FAULT COMMON SYSTEM SOUNDER REPEATER FAULT FAULT DELAY FAULT GENERAL INDICATIONS START STOP EXTERNAL SOUNDERS FUNCTION Ses CEJ FAULT TONE LED TEST OVERRIDE SOUNDER DELAY Two levels of control are available to the User s of this Fire Alarm Panel 4 1 GENERAL CONTROLS When the Panel is in its Normal state the indicator lights on the front of the enclosure give a comprehensive overview of the System s current status Any Fire and Fault conditions are clearly displayed and any disablements highlighted For detailed descriptions of what each indicator means please refer to the table on the opposite page The only functions that can be performed by the User when the Panel is in its Normal state are e Overriding any Delays which may have been programmed into the Panel by pressing the Sounder Override button e Putting the Panel
15. e that zone during the risk period and then enable it again afterwards During a disablement of a zone s no fire or fault signal will be processed for that zone s Only zone s in a non alarm state can be disabled that is zones already in fire cannot be disabled External sounders can also be disabled as could be required in certain conditions 7 2 TO DISABLE A ZONE AND OR EXTERNAL SOUNDERS 1 Turn control key to Controls Enable position 2 Press FUNCTION switch momentarily this will cause General Disablement LED to flash fast This means the panel is in disable enable mode 3 Press scroll switch once and this will cause the General Disablement LED Zone1 fault and Zone 1 Disablement to flash with a 3 quick flash then off pattern 4 Press SELECT to disable this zone or SCROLL to move to another zone 5 The scroll order is Detection Zone 1 48 Zone fault amp zone disabled LEDs on then Common Sounders Then F A R E circuit 6 Select zone to be disabled The LEDs will now flash 3 quick flashes then ON This shows that this zone has been disabled 7 Switch controls key to off position then both the disabled Zone Disablement LED and the General Disablement LED will remain lit steady 7 3 TO ENABLE A ZONE AND OR EXTERNAL SOUNDERS 1 Turn key to Controls enable position since a zone is already disabled at this time the General Disablement LED with stay lit steady 2 Press FUNCTION followed by SCROLL
16. eral Fire lit 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING e With the control key in Controls Enabled position momentarily pressing the Start Stop will cause the Alarm sounders to sound Pressing the Start Stop button again will Silence the Alarm Sounders Note If the Alarm Sounders have been disabled pressing the Stop Start button will have no effect 5 5 RESETTING THE PANEL e Check the cause of the alarm activation If the cause of the alarm was an activated call point reset it if resettable type or fit a new glass element if glass type If the cause of the alarm was by detector activation e g cooking smoke the smoke will have to be cleared from the room before the panel can be reset Reset the panel by pressing the reset button after the sounders and panel buzzer have been silenced e If the call point is still active or the detector is still smoky this will cause another alarm straight after the panel is reset so will set off the alarm bells again Approved Document No GLT MAN 121 PAGE 8 Issue 1 0 Authorised GH Date 25 04 2007 PREMIER M PLUS 48 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 6 THE FAULT CONDITION 6 1 DIFFERENT TYPES OF FAULT The fire alarm monitors itself and any equipment connected to it for any faults that can occur If a fault occurs the Panel responds by activating its Internal buzzer and lighting the General Fault light and any other Fault light
17. into the Accessed state see below 4 2 ACCESSED CONTROL AVAILABLE TO AUTHORISED USERS ONLY To avoid unauthorised changes to critical parts of the Fire Alarm System controls such as silencing the Sounders resetting an Alarm condition and implementing Disablements are only accessible via a secure method of entry which puts the panel into the Accessed state To put the Panel into the Accessed State Turn the key to the control enable position please note the key should not be removed when in this position To leave the Accessed state turn the key back to the off position Information on how to use the accessed control can be found on Pages 8 to 11 of this User Manual Approved Document No GLT MAN 121 PAGE 6 Issue 1 0 Authorised GH Date 25 04 2007 PREMIER M PLUS 48 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 4 3 SUMMARY OF LED COMBINATIONS AND THEIR MEANING Use the table below to determine the condition of the panel LEDs LIT LED CONDITION PANEL STATUS POWER STEADY GREEN The panel is supplied with power and has no faults fires System Normal COMMON FLT STEADY YELLOW Problem with keyswitch connections ONLY COMMON FLT 8 STEADY YELLOW There is a problem with either the mains supply or the battery backup SUPPLY FLT STEADY YELLOW COMMON FLT amp STEADY YELLOW There is a wiring problem One of the cables is touching the earth screen EARTH FLT STEADY YELLOW
18. iring FAULT FAULT DELAY FAULT a fault for the display to clear GENERAL INDICATIONS SUPPLY GENERAL FARE Power Supply Fault POWER FAULT S C ACTIVE pp y EARTH SOUNDER FA R E FAULT FAULT FALDSAREMENT The Power supply Fault light flashes when the Mains supply COMMON SYSTEM SOUNDER REPEATER has failed or the standby batteries or its charger is faulty If FAULT ANI DELAY FAULT the mains supply fails the panel will only operate for the standby period dictated by the size of the batteries fitted If GENERAL INDICATIONS the batteries or charger fails at the same time as the Mains the Panel will be inoperative SUPPLY GENERAL FARE System Fault POLEN FAULT s c ACTIVE y COMMON EARTH SOUNDER FARE The System Fault LED lights when the Panel s micro processor FIRE es DER has Reset typically after excessive electrical interference or if DM Be ee RUE the contents of its memory have been corrupted This fault can only be cleared by turning the key switch from off position to GENERAL INDICATIONS control enable position and then back to the off position again If the fault re occurs within two minutes this is indicative of a corrupt memory and expert advice should be sought Approved Document No GLT MAN 121 PAGE 9 Issue 1 0 Authorised GH Date 25 04 2007 PREMIER M PLUS 48 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK SUPPLY GENERAL FARE Earth Fault POWER FAULT s c ACTIVE Eus EARTH py SOUNDER FARE The Earth
19. mp Control Buttons on the PREMIER M PLUS Fire Alarm Panel 4 1 GENERAL CONTROLS 4 2 ACCESSED CONTROL AVAILABLE TO AUTHORISED USERS ONLY 4 3 SUMMARY OF LED COMBINATIONS AND THEIR MEANING 4 4 CHECKING THE PANELS INDICATION LEDS 5 THE FIRE CONDITION 2 22 22 Irene cuiu Brei eoo acon 8 5 1 HOW THE PREMIER M PLUS 48 INDICATES AN ALARM 5 2 TO TURN OFF THE ALARM SOUNDERS 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E EVACUATE 5 5 RESETTING THE PANEL 6 THE FAULT CONDITIONS i a anaia iae 9 6 1 DIFFERENT TYPES OF FAULT 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS T DISABLEMENTS So C 11 7 1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM 7 2 TO DISABLE A ZONE AND OR EXTERNAL SOUNDER 7 8 TO ENABLE A ZONE AND OR EXTERNAL SOUNDER 8 USING SOUNDER 12 8 1 WHAT IS A SOUNDER DELAY 8 2 SOUNDER DELAY SETTING 8 3 HOW THE PANEL INDICATES SOUNDER DELAY 8 4 A FIRE ALARM CONDITION ON A DELAYED PANEL 8 5 OVERRIDING A DELAY IN THE EVENT OF A GENUINE FIRE ALARM 8 6 RESET THE SYSTEM IN THE EVENT OF A FALSE ALARM 8 7 TO TURN OFF THE SOUNDER DELAY Approved Document No GLT MAN 121 PAGE 3 Issue 1 0 Authorised GH Date 25 04 2007 PREMIER M PLUS 48 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 1 FIRE ALARM CONTROL PANEL
20. stem into Zones each covering a different area of a building This will indicate which area of the system is giving the alarm or fault During an alarm the panel will start its sounders and indicate which zone has the fire It will also activate its auxiliary relay Fault Monitoring All circuits must be checked for line integrity If a part of the system has a problem which may affect its operation a fault warning must be given by the fire alarm panel LED amp buzzer indication The fault relay will also activate Disablements An engineer may be required to work on part of a system while the system is still active e g extending a detection zone During such circumstances it would be advisable to disable that zone so that it will not give false alarms Similarly you may wish to disable a zone that has a fault that has not been fixed or a zone covering an area with a temporary unusual environment such as an area which is dusty because of construction work etc Delays In public places it may be desirable to delay the activation of an alarm until the responsible person has verified the cause of the alarm This would avoid a panic evacuation caused by a smoky room or a maliciously activated call point On verification of the alarm the sounders can be started by pressing the override button or the panel can be reset in the case of a false alarm If a delay has been set it must be recorded on the system configuration chart at
21. the panel sees a repeater but then looses its signal it will show a repeater fault 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS If a fault occurs the responsible person should e Turn keyswitch to Controls enabled and press silence fault tone button to silence the fault buzzer e Write down the fault s in the Log Book Take appropriate action to correct the fault Usually by contacting the service engineer On the PREMIER M 48 panel the fault indications except system fault are non latching That is when the fault has been cleared the fault indication will turn off When all faults have been cleared the panel will return to its quiescent normal condition In the event of multiple faults when a fault has been rectified the indicator light for that Fault is automatically turned off If all Faults are cleared the General Fault light will go out and the Panel s Internal Sounder will be silent if not already muted Approved Document No GLT MAN 121 PAGE 10 Issue 1 0 Authorised GH Date 25 04 2007 PREMIER M PLUS 48 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 7 DISABLEMENTS 7 1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM Certain parts of this Fire Alarm Panel can be temporarily disabled i e switched off to suit prevailing conditions For example if there is a risk of a False Alarm in a zone for example an area full of dust because of building work it is possible for the user to disabl
22. to the designated site maintenance engineer Weekly Test you may wish to temporarily disconnect the Aux relay during the following Tests e Setoff a manual call point or sensor to test the Fire Alarm panel responds and all the sounders activate e Do not test the same device each week Test a different zone each week using a different call point or detector so that eventually all the devices will be tested e Reset the System by pressing 1 2 3 Stop sounders Silence fault tone Reset e Turn key to controls enabled Press the LED Test button Check that all LEDs light and the buzzer sounds e Check that no call points or fire detectors are obstructed in any way e g New furniture or decorations Quarterly Test to be carried out by authorised service personnel only e Check that any servicing or repairs required by all previous logbook entries has been undertaken e Visual inspection of the batteries and connections Check the alarm sounders work on battery only e Activate a device from each zone to test the fire alarm As per weekly test Annual Test to be carried out by authorised service personnel only Check every detector call point sounder and all auxiliary equipment for correct operation Check Transformer output Voltage 32 VAC Charger Voltage 28 4V off load adjusted with VR1 8 Battery Voltage 25 27V Every Five Years to be carried out by authorised service personnel only e Carry out a complete wiring check in

Download Pdf Manuals

image

Related Search

Related Contents

Specification and Operating Instructions KLT22Z Thermostat Cold  Lexmark MX812dfe  MBA_WKD - Swegon  Tutorial Introduction  Aastra 571i IP Telephone User Guide  ピコプラス スモーカーライザー取扱説明書  Chapter 15  Descargar Español  Room Fire - Thunderheadeng.net    

Copyright © All rights reserved.
Failed to retrieve file