SmartZone Gateway-Enabled MS Series Rack PDU
Contents
1. 9 F roducbPInepecliOIT toe ee erem dett Me 9 Plug Connection cesa ata cela iat as oe SA orcas UD D M AAACN 9 seid ie le UU LI 9 Vertical Mounting axes eS EO VES E EE 10 Horizontal Mounting does coe e ee ten eoe e E ode ebd ba eo CE ERE uade 12 SmartZone 1RU Inline Meters 12 OpuotalACGeSSO IBS 228822 tute t a aee cer e esee te AT es 13 Additional Required eee t ro c e ow eta 14 Safety Precautions mec E 14 SBIVICILIQ ar esu uto lecce Lo c UE Lr LL Ce Ee ONE 14 Product Safety WOaITlligs tala 14 RUES 22 15 Environmental Specifications 16 aM aera DM RA ARETE 16 c ences LL P A alps ee et A At LL a d RA tft 17 ECD Display rete eee noL tt lU phe Acer iA n ono LC 17 ISOSOPBEULOD then ct dah 17 Mode Button Operation iioi Seco ite tia Oboe ted ae Ee ie 18 Boolloader ns tects steht ts A e PE Ee LL 18 Firmware Recovery Mode 18 Application S Lau t I tke RE LEN tek wR 18
2. Internal Error Notification 0 0 0 22 2 2 c coco ccccccccc ec ec ec cc ccccececececeeeceeeeeeees 19 Gateway User Interface seen 20 Access the PDU Graphical User Interface 20 Using the PDU Graphical User Interface 21 Appendix A Temperature Sensor Adapter Installation 22 New Installations A co i Boe te 22 Existing Installations 3 renis Jane oeste heu recor a dudum nn 23 Fitting the Adapter In line 22 o ae dando Ded pusiste 23 Gateway Enabled MS Series Rack PDU User Manual SmartZone Gateway Enabled MS Series Rack PDU Gateway Enabled MS Monitored and Switched Series Rack PDUs manage and dis tribute power to multiple power devices through a single power connector This PDU allows you to access configure and manage power consumption and environmental parameters from remote locations The MS Series PDU monitors per phase power voltage and current per branch current and includes the ability to switch the power to each outlet off or on SmartZone Gateway Enabled PDUs are available in a wide range of configurations and power connections and outlets and can be mounted vertically or horizontally Contacting Panduit For Technical Support on PDU h
3. serial number MAC Address IP Address and electrical readings The display automatically scrolls through the readings which include e Start Up messages e Configuration serial product number messages e Error Status messages Aggregate data e Single Phase data 3 Phase Delta data or 3 Phase Wye data e Branch current data if the unit has breakers During normal operation the mode button may be used to quickly advance through the LCD display pages Reset Button Push the Reset button using a non metallic item similar in size to a paper clip to reset the PDU device AN Warning a metallic item such as a paper clip is not recommended as a reset tool The reset tool should be inserted perpendicular to the surface of the device and pressed until the button is reached and is actuated The reset tool should bump into the button within 1 8 of an inch of being inserted and should be lightly depressed and held for at least 1 second The reset tool should never be inserted more than 1 4 of an inch Resetting the PDU device starts the bootloader Wait between 1 and 30 seconds for the Display Backlight to blink on and off at a rate of 2 blinks per second The bootloader stays in this mode for at least 4 seconds 8 blinks if no user operation is detected 17 Gateway Enabled MS Series Rack PDU User Manual Mode Button Operation Bootloader Startup When the user presses and holds the Mode button the Display Backlight switch
4. gateway firmware to the latest release See Hardware for details 299 Gateway Enabled MS Series Rack PDU User Manual Existing Installations Follow these instructions when the sensor is already installed along with the gateway 1 Unplug the current temperature sensor from the gateway noting the location where it resided 2 Insert the adapter into that location 3 Plug the sensor into the end of the adapter 4 5 The gateway firmware must be updated to the latest firmware See Hardware for Perform these steps for all other temperature sensors to be changed details Before the adapter is fitted After the adapter is fitted Fitting the Adapter In line This procedure is not recommended but it may be the only solution in some cases ae Gateway Enabled MS Series Rack PDU User Manual 1 Using a patch lead from the gateway and an RJ45 Jack to Jack through connector on its non gateway end plug the adapter RJ45 Plug into the through connector 2 Plug either the RJ45 plug of a temperature sensor into the jack on the adapter ora patch lead with the temperature sensor on the end 24
5. stays in this mode for at least five seconds If no button operation is detected the application continues to normal system operation If the customer presses and holds the Mode button for five seconds the following mes sage displays on the LCD Hold MODE button more than 5 seconds to reset to defaults If the customer continues to press and hold the Mode button the following message dis plays on the LCD Reset to defaults is detected Please release MODE button The customer should release the Mode button at this point The following message dis plays on the LCD Device is Resetting to factory defaults If the customer does not operate the Mode button as described above the application continues normal system operation Internal Error Notification After system start up is complete the LCD screen may blink during normal operation of the unit This typically indicates a temporary or persistent internal error condition If the condition is persistent the LCD screen displays the word STATUS followed by a hexadecimal code similar to the following STATUS 0x009000080 The hexadecimal code is a composition of per outlet control per outlet monitoring and per phase monitoring status For example if a three phase Per outlet Monitoring or Switched unit loses a power phase the status screen will reflect that communication to those boards has been lost For definitions and recommended actions on status codes provide the
6. A Warning For permanently connected equipment a readily accessible disconnect device should be incorporated external to the equipment Rack PDUs must be protected by a branch circuit protective device rated at the max imum rating of the product specified on the product rating label To avoid risk of overload do not plug additional multiple outlet power distribution devices into the power distribution unit socket outlets This equipment is intended only for installation and use in a Service Access Location in accordance with the following installation and use instructions This equipment is designed to be installed on a dedicated circuit 14 Gateway Enabled MS Series Rack PDU User Manual e The dedicated circuit must have circuit breaker or fuse protection Rack PDUs have been designed without a master circuit breaker or fuse to avoid becoming a single point of failure It is the customer s responsibility to provide adequate protection for the dedicated power circuit Protection of capacity equal to the current rating of the Rack PDU must be provided and must meet all applicable codes and regulations In North America protection must have a 10 0004 interrupt capacity Warning Always disconnect the power supply cord before opening to avoid elec trical shock Pans DANGER High leakage current Ground connection is essential before con necting supply DANGER Double Pole Neutral Fusing The plug on the power
7. PANDUIT SmartZone Gateway Enabled MS Series Rack PDU User Manual Release 1 0 Issue 1 0 Gateway Enabled MS Series Rack PDU User Manual Copyright 2014 Panduit Corp All rights reserved No part of this book shall be reproduced stored in a retrieval system or transmitted by any means electronic mechanical photocopying recording or otherwise without written permission from Panduit No patent liability is assumed with respect to the use of the information contained herein Although every precaution has been taken in the preparation of this book Panduit assumes no responsibility for errors or omissions Neither is any liability assumed for damages resulting from the use of the information contained herein Gateway Enabled MS Series Rack PDU User Manual Table of Contents SmartZone Gateway Enabled MS Series Rack PDU 4 Contacting Panduit iiu ores sie ee seus pd s rump M alas Anite bbl Md ce nace tact 4 SVMDOIS WSO UTERE PE 4 Equipment Overview sssuusssssssmmmIRRRRRIRRRRRIRIIIIIeIIIeIllllllllllll 6 BOX COMEMS A octet t A LES CR ALD d ADS REA Rr LC 6 Cable Detalls 22 2 6 Model Numbers iot es Lotes eet ee 7 Pre Installati h soa us eode ies a ess aha i alaha 8 Installati n stoke yee Si Lettre aA apes aA
8. ardware and associated software please contact Pan duit Technical Support using one of the following methods 1 866 721 5302 toll free Monday Friday 7 30 am 5 00 pm CST systemsupport panduit com Symbols Used Symbol Description Danger Electric Shock Hazard 4 Warning Possible Safety Hazard Primary Earth Ground Gateway Enabled MS Series Rack PDU User Manual Description Gateway Enabled MS Series Rack PDU User Manual Equipment Overview The power inlet cord s connects the PDU to the electrical power source The LCD dis plays the current load for each input feed or electrical phase per input feed Box Contents The SmartZone Gateway Enabled Rack PDU box contains the following Gateway Enabled Rack PDU Configuration Cable CD Mains Adapter External Grounding Stud Cable Details 63A single and three phase feed cable 10mm 0 40 inches conductors HO7 cable type terminated with 1P 3 pin 63A commando and 5 63A com mando IEC60309 32A single and three phase feed cable 6 0mm 0 23 inches conductors HO7 cable type terminated with 1P 3 pin 32A commando and 5 32A com mando IEC60309 16A single and three phase feed cable 2 5mm 0 10 inches conductors HO7 cable type terminated with 1P 3 pin 16A commando 5 16A com mando IEC60309 13A single phase feed cable 1 5mm 0 06 inches cable type ter mi
9. d MS Series Rack PDU User Manual 3 Ensure that the cover is replaced and secure before commissioning Vertical Mounting Panduit recommends using the provided external grounding stud for supplementary ground bonding to the rack metalwork 1 Insert the tool less mounting buttons into the fixing holes on the back of the rack cabinet 2 Install the PDU using the bracket mounting buttons and the mounting brackets loc ated at either end of the PDU 10 Gateway Enabled MS Series Rack PDU User Manual 11 Gateway Enabled MS Series Rack PDU User Manual Horizontal Mounting To mount this product horizontally use the RU mountings via the brackets found at either end of the PDU with the provided accessory screws listed below e Horizontal Models North American units 4 10 32 x 1 2 MOUNTING SCREWS 4 12 24 x 1 2 MOUNTING SCREWS Global units 4 M6 x 20mm MOUNTING SCREWS 4 12 24 x 1 2 MOUNTING SCREWS O DO O OD O OO 0O 0n 00 02 00 0 om 00 SmartZone 1RU Inline Meters Install this product to the racks frame via the mounting plate holes found at either end of the PDU using the provided mounting hardware The mounting plate can be adjusted as shown below 12 Gateway Enabled MS Series Rack PDU User Manual Optional Accessories Temperature Sensor External Temperature Sensor Humidity Sens
10. displayed hexa decimal number to Panduit Technical Support 19 Gateway Enabled MS Series Rack PDU User Manual Gateway User Interface The SmartZone Gateway Enabled Rack PDU provides access to configuration power and sensor data through the Gateway Graphical User Interface GUI using a standard browser There are several ways to connect to the device s Gateway GUI depending on your network configuration and the firmware revision of the device If the PDU has firmware revision 2 3 03 or earlier Static IP is the default The con figuration settings in this case are IPv4 Address 192 168 0 253 TPv4 Network 255 255 255 0 IPv4 Gateway 192 168 0 1 If the device has firmware revision 2 3 04 or later DHCP is the default and one of the following scenarios will be used e If you have a DHCP Server available connect to the appliance through that server using the PDU s IP Address Note The IP address for the Rack PDU is displayed on the device s LCD screen after the label IPv4 e lf you do not have a DHCP server you can run one on your To connect to the device use the IP address displayed on the LCD screen e lf you want to use automatic IPv4 address configuration you must activate DHCP on your PC and then connect directly to the PDU This will give you an address on the 169 254 0 0 16 network You can then connect directly using the IP Address displayed on the LCD screen Access the PDU Graphical User In
11. es to one blink per second indicating the bootloader is waiting for one of the following oper ations Ifthe user releases the Mode button after two blinks the backlight goes solid on and stays in the bootloader entering the firmware recovery mode See the Firm ware Recovery Mode section below for more details Ifthe user releases the Mode button after four blinks the backlight goes solid on and attempts to boot the backup firmware image Ifthe user does not operate the Mode button as described above the Display Back light is turned off The firmware updatable application image continues loading Firmware Recovery Mode The Gateway Enabled PDU provides a firmware recovery mode in case a firmware update is interrupted while in progress and fails to complete successfully Note Do not power cycle or restart a device while a firmware update is in progress If a firmware update does not complete successfully and the device fails to be oper ational after 30 minutes contact Panduit Technical Support 1 866 721 5302 toll free Monday Friday 7 30 am 5 00 pm CST systemsupport panduit com Application Startup When the application is ready message is displayed on the LCD Starting up The display backlight blinks quickly three times and remains lit The LCD then displays Hold MODE button to reset to defaults 18 Gateway Enabled MS Series Rack PDU User Manual The application
12. nated with 3 pin UK plug 10A single phase feed cable 1 0mm 0 04 inches cable type ter minated with 3 pin IEC C14 Plug For IEC C 20 inlet PDUs a customer supplied cord is used for connection to the power source The connection end to the PDU has an IEC C 19 plug for connection to the PDU The opposite end of the cord shall have a plug suitable for connecting to the cus tomer supplied receptacle The cord and plug shall be rated for 20A in North America and 16A outside of North America The connection to the PDU should be made prior to connecting to the power source Gateway Enabled MS Series Rack PDU User Manual Model Numbers The following table lists the specifications for the Gateway Enabled Rack PDU model numbers Horizontal IQ Adapter HC wwwVxxA IM wwwVxxA HD wwwVxxA IL wwwVxxA HL wwwVxxA Single Inline HM wwwVxxA GM wwwVxxA HP wwwVxxA GL wwwVxxA HS wwwVxxA Dual Inline Vertical LM wwwVxxA VC wwwV xxA LL wwwVxxA VD wwwVxxA Quad Inline VL wwwVxxA AM wwwV xxA VM wwwVxxA AL wwwVxxA VP wwwV xxA Under the Floor VS wwwVxxA UM wwwVxxA In the tables above www is the voltage for single phase or 3 phase and xx is the pos sible current associated with the voltage Refer to the chart below for valid International and U S values International U S Voltage Voltage Current 10 13 16 20 30 15 20 30 50 240 415 32 48 63 120 208 60 80 Gateway Enabled MS Series Rack PDU User Manual Pre Installa
13. or Temperature Humidity Sensor Water Contact Sensor Water Rope Sensor Air Flow Sensor Shock Sensor Digital Input Sensor Passive Infra Red PIR Sensor Door Contact micro switch Door Contact magnetic Standard Electronic Swing Handle Kit Smoke Detector Differential Pressure Transducer Flashing Beacon with Sounder Flashing Beacon with no Sounder HID Access and Control Card Reader Keypad Kit LCD Display Module with Selector Switches PCB only External LCD Display 13 Gateway Enabled MS Series Rack PDU User Manual Additional Required Items e Flathead and Phillips screwdrivers e Appropriate local AC power receptacle to power the PDU e Local active Ethernet port to communicate with the PDU Safety Precautions This section contains important safety and regulatory information that should be reviewed before installing and using the Rack PDU Servicing There are no user serviceable parts inside these products Any maintenance or repair must be performed by approved service trained personnel Opening the unit will void the product warranty Product Safety Warnings Warning Use only in dry locations Indoor use only PDU hardware has an International Protection Rating of IPXO The installer must connect the power distribution unit to an electrical supply that has a protective Earth conductor For pluggable equipment the socket outlet should be installed near the equipment and should be easily accessible
14. supply cord must be installed near the equipment and must be easily accessible Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment gen erates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio com munications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Changes modifications not approved by the responsible party could void the user s authority to operate the equipment 15 Gateway Enabled MS Series Rack PDU User Manual Environmental Specifications Operating Temperature OC to 40C Transportation Temperature 10C to 70C Operating Humidity 15 to 85 non condensing Transportation Humidity 5 to 90 non condensing Bonding This product contains an external earthing screw with a star washer which should be used for supplementary Earth bonding to the rack metalwork Bonding UpsiiouigS Up tanaincuang A BANG tp andincuaing80A eane Over 16A less than or equal to 40 Over 40A less than or equal to 63A 16 Gateway Enabled MS Series Rack PDU User Manual Hardware LCD Display The display shows the firmware version number device model number
15. terface To access the GUI open a web browser and enter the IP Address of the PDU When the login page opens you will be prompted to enter a login and password 20 Gateway Enabled MS Series Rack PDU User Manual PANDUIT Username Password Login Serial Number 16403 Firmware 1 10 18 The default login and password are Login admin Password admin After successful login the GUI opens to the Overview page Using the PDU Graphical User Interface For detailed information on working with the GUI refer to the appropriate SmartZone Gateway User Manual SmartZone E24 Gateway User Manual SmartZone EP042 Gateway User Manual SmartZone EPA064 Gateway User Manual SmartZone EPA126 Gateway User Manual 21 Gateway Enabled MS Series Rack PDU User Manual Appendix A Temperature Sensor Adapter Installation Follow the instructions below to install the ZAHTLADT 02 v1 01 01 temperature sensor adapter module This adapter allows legacy sensors to provide more accurate tem perature readings Note This adapter does not work with the ZETHL 14 temperature sensor New Installations Follow these instructions when you are installing a standard temperature sensor but the upgraded sensor input is required 1 Plug the adapter directly into the back of the gateway at the sensor port to be used for temperature 2 Plug the temperature sensor connector into the adapter 3 Update the
16. tion The Gateway Enabled Rack PDU products covered by this guide are designed to be installed within EIA racks and cabinets Use of this product in other applications is acceptable but other precautions may be required to allow for specific installations not covered by this guideline Gateway Enabled MS Series Rack PDU User Manual Installation The Gateway Enabled Rack PDUs are designed to be installed within 19 rack cabinets Use of this product in other applications is acceptable but other precautions may be required to allow for specific installations not covered here Product Inspection Before installing your PDU ensure that it has been inspected If the product has any vis ible signs of damage please contact Panduit customer support at 800 777 3300 or cs panduit com Please register your product to receive notification of firmware and product updates at http bit ly 1aXKhr1 Plug Connection This product is intended to be connected by the customer and must be installed by a competent person in compliance with all local and national regulations Hardwiring This product is intended to be hardwired by the customer It must be installed by a qual ified electrician in compliance with all local and national regulations 1 To install the power cable remove the securing screws the removable user panel 2 Connect the conductors to the rack PDU terminals in line with the terminal mark ings provided Gateway Enable