Home
Quantum Q-Admin Guide (040383)
Contents
1. Set All Occupancy After Hours Name Begin After Hours To After Hours Active Time 6 00 PM Evaluate O Weekdays F Sun V Mon F Tues Ywed T Thur W Fri E Sat x 2 Set levels for the outputs Quickly Set Levels Type Name Level Evaluate Occupancy After Hours Office Building First Floor Open Office Areas Open Office E North Occupancy After Hours Fee M South Occupancy After Hours Office Building Fourth Floor Electrical Closet Unaffected lt m Occupancy After Hours Office Building Fourth Floor Open Office Areas Open Office Occupancy After Hours Office Building Fourth Floor Open Office Areas Open Office Unaffected South Occupancy After Hours Office Building Second Floor Copy Room Unaffected v Occupancy After Hours Office Building Second Floor Electrical Closet Unaffected C 655 ildinn A Save L Cancel lt Back Next gt Save and Close wizara AE m e Logged in Time Thursday March 24 2011 5 50 48 PM _ Step 4 Define Weekly Events Weekly events occur regularly every week based on the selected weekdays for example an event can be set to occur every Monday Wednesday and Friday To add a new event 1 Click New Event The bottom of the screen will populate with event details Each output assigned to the Time Clock will app
2. The Occupancy tab allows the user to view the current state of and change settings for occupancy and After Hours Areas with Occupancy Sensors If an area has occupancy sensors the possible states are occupied unoccupied and disabled Areas can be grouped together and dependency can be configured during initial setup in Q Designm When at least one sensor in an occupancy group is occupied all areas in the occupancy group go to their occupied level and any dependent areas also go to their occupied level When all sensors in all areas of an occupancy group go unoccupied all areas in the occupancy group go to their unoccupied level If the occupancy state is disabled occupancy events will not be processed Areas without Sensors After Hours Mode After Hours mode is used as an intelligent off setting for a lighting control system It allows occupants in a space to continue using that space even after the prescribed off time while preventing the lights from being left on needlessly When the lights are scheduled to turn off the user is given a visual warning blink warn sequence a few minutes before the lights are turned off If occupants wish to continue using the space they simply press a button to keep the lights on longer Otherwise the lights turn off until either the system is notified that the space is in use again or the system leaves the After Hours mode After Hours is useful when a space may be used after the
3. Enabled Edit Location Settings March Sunday 4 E Office Building Se Office Building Se Week Time Dwa J E speciai toune E speciai Routine E speciai Routines office Building Office Building Fou Office Building Fourth Floor O Office Building Fourth Floor Second week y 02 00 6 00 PM Office Building Se Add City Country United States of America State Pennsylvania City Northampton Latitude 0 Nr Longitude 9 Er Time Zone Eastern Time Day Begins at 12 00 AM Sunrise 7 00 AM Sunset 7 18 PM F Adjust for daylight Savings Daylight savings time adjustment minutes Set Clock Ahead Sunday x in January at 00 00 Set Clock Back irst week Sunday x in January x at 00 00 Second week m Third week Save Cancel Fourth week see Les Last week Logged in User admin Logged in Time Thursday March 24 2011 5 50 48 PM The Location Settings display is used for configuring geographical position and time zone The following system features are affected by location settings Night Lights Can be programmed to begin or end based on sunrise sunset Time Clocks Can be programmed to execute based on sunrise sunset Hyperionm Uses location settings and time zone information to determine the precise position of the sun Green Glancee Uses location
4. Logged in User admin Logged in Time Thursday March 24 2011 4 17 12 PM Graphical view allows the user to select view areas by selecting within a graphical floorplan as shown Multiple graphical pages can be used Each page typically displays a floor in a building Pages can be hotlinked to each other For example one graphical page might be a birds eye view of a campus with clickable regions for each individual building acting as hyperlinks Each hyperlink would then take the user to another page having images of each floor of a building which would then have clickable regions linking the user to graphical pages consisting of a top view of a single floor the user would then click on areas within the floor view to select individual areas to control and monitor To change the view click the dropdown menu at the top next to You are viewing and select another page In the example shown the user has selected to display the second floor page and its associated areas The graphical floorplan view is an optional feature configured by Lutron Contact Lutron Support at 1 800 523 9466 for details 10 Quantum Q Adminn User Manual S4 LUTRON a AIL as Control and Monitoring Control x X Control amp Monitoring j Reports Administration E central 5 Occupancy Daylighting Time Clock 4 Hyperion Solar Clock Load Shedding Diagnostics 9 The current area selected s Office Building Second Floor
5. N Password PPPPPPPPPL 7 sLUTRON Quick Reference Guide Frequently Used Q Adminm Features This list is a quick reference guide for the most frequently used features in the Q Adminm software by facility managers Area Scene Modification How do I modify a scene ina selected space zone 12 Occupancy Modification How do modify the settings of a selected occupancy sensor 18 Daylight Target Set Point Modification f someone complains that their lights are too low in a space with Daylighting what can Ido 20 Time Clock Changes How do define what lights will do turn on turn off a based on area occupancy and time of day Pee eee es b Be w 2O Hyperion Solar Clock Modification How do I change the times that my shades move 33 Diagnostics How do know when a lamp or ballast has failed a 2 nn m nn nn nn 48 Reports What reports can generate How do I generate them 2 2 2 m nn DU se LUTRON A Quantum Q Adminm User Manual 5 Quantume System Diagram Lighting Hubs Devices Power panels Quantume processor Client Software Server Q Adminm Q Managerm control and monitor server Keypads Controls Interfaces Quantum processor Shades Quantume processor 6 Quantume Q Adminn User Manual De LUTRON a AIL a Login Login Upon launching the Q Adminm appli
6. Time Clock Wizard Step 1 Overview Add Edit Delete Step 2 Add Edit Delete Choose the action you would like to perform Step 3 Assign Output Add New Time Clock Enter the name for the new time clock Time Clock Step 4 Define Weekly Events Step 5 Define Special Events Step 6 Finish Edit Existing Time Clock Change Occupancy Settings Project Time Clock After Hours Delete Existing Time Clock Delete Click on Next to advance to the next step lt Back Next Save and close wizard Step 2 Add Edit Delete Add edit or delete Time Clocks Select whether you want to add edit or delete a Time Clock To add a Time Clock click the first radio button type in the Time Clock name and click Next To modify a Time Clock click the second radio button click the Time Clock to modify and click Next To delete a Time Clock click the third radio button select the Time Clock to delete from the dropdown menu and click Delete 26 Quantume Q Adminim User Manual sv LUTRON o AIL as Creating Modifying Time Clocks Time Clock Wizard Step 1 Overview Assign Outputs Step 2 Add Edit Delete You are modifying After Hours Step 3 Assign Output Step 4 Define Weekly Events Below is the list of the lights shades and other outputs this time clock will control Step 5 Define Special Events To add outputs click Add Remove Out
7. xIs JPEG Document jpg Comma Separated Text Document csv No Areas 2 Office Building Second Floor Open Office Areas Export the report data at eAdata eneray_usage_reportaoiioaz0 xs_ gaan aE Office Building Second Floor Conference Rooms Open file after Export use over the Export e Last 7 days pe Apply Cancel Logged in User admin Logged in Time Wednesday April 20 2011 3 29 06 PM Saving Printing and Exporting Reports Reports can be printed and saved to files Exporting to Excel format xls requires Microsofte Excele 2003 or newer to be installed alternatively reports may be exported in csv format All reports can be exported in tabular format to xis or csv Only reports that have a graphical view can be exported to the jog image format To save a report that has been created 1 Click Save or Save As 2 If saving for the first time or doing Save As you will be prompted for the report name Change the default name if desired and click Save To print a report 1 Click Print 2 Select the desired printer choose options if desired and click OK To save a report to a file 1 Click Export 2 Select the desired output format Excel spreadsheet JPEG image or CSV spreadsheet 3 Choose the output filename by typing in the text box and or using the Browse button 4 To open the file
8. No Load Shed Power Usage 3 76 kw Building Lighting Power Usage 20 Allow Areas Load Current Goal L shed ae s m w L EST FLOOR S 1 0 wa ie a116 Cafeteria 116 Z 20 20 North West Dining Area Z 20 20 west 1 Dining Area Z 20 20 go __ west 2 Dining Area Demo Area m majas Z p 1 LA Projection Area 8 20 20 8 N sa K Private Dining B 20 20 lien E A as etn sn es ar eae si ht ie tpt nhs thls ls T at Sh ow a een Town Square B 20 20 6 r F i i Food Court B 20 20 F 2 20 20 L 121A Cafeteria Cue 121A 4 anr a Master Load Shed Control Z 3 Load Shed is currently Enabled 4 E a or a a I or L L L L L S s Ki Y LS LS RS RZ Y K Disable Load Shed Time hours Click to show hide curves R me Current Power Usage No Load Shed Demand Goal Logged in User admin Logged in Time Wednesday April 20 2011 4 31 55 PM Load shedding allows the building manager to monitor whole building lighting power usage and apply a load shed reduction to selected areas thereby reducing a building s peak power usage Load shedding can be done for the whole project for groups of areas or for individual areas at levels between 0 and 90 0 is the same as no load shedding To change load shedding targets for areas 1
9. Start Tuesday April 05 2011 IB Time Frame B Start Tuesday April 12 2011 Apply Cancel Lighting Power Trend Comparison Report How does the power usage of selected area compare over selected time frames This report shows power usage for a particular area over two different time spans For example this can be used to compare energy of this week with last week To create a Lighting Power Trend Comparison Report 1 Select the area by using the dropdown menu on the right 2 Choose the first date by using the Time Frame A Start Date dropdown menu 3 Choose the second date by using the Time Frame B Start Date dropdown menu 4 Select the time span in the Duration dropdown menu 5 Click Apply Available Reports Z Q Admin le x imaam baliin LLI TON X Control amp Monitoring Reports _ New 7 Open X View 9 Lamp Maintenance Report 001 X PS H save As d Save amp Print Export Lamp Maintenance Report 001 Lamp Maintenance Report Areas reporting failed lamps Thursday June 09 2011 3 44 29 PM Which Areas are reporting failed lamps Areas Failures Office Building lt E Fourth Floor SM Northwest Quad af Conference Rooms Only show me areas in Office Building B E Conference Room 46 xpand All Collapse All Show Area Numbers Find Area 0 Office Building First Floor 8 Second Floor lt EH Open Offic
10. Choose an area using the area tree in the grid on the right side 2 Select the Allow Load Shed checkbox to load shed the area or deselect it to prevent the area from being load shed 3 Type a number from O to 90 in the Goal column This is the percentage of the lighting level you want to reduce the area by 0 no reduction 90 maximum reduction 4 Repeat for other areas for which you want to change load shedding 5 Click Save amp Apply To enable disable load shedding 1 Click Enable Load Shed to enable load shedding for the entire project The button text will change to Disable Load Shed 2 Click Disable Load Shed to disable load shedding for the entire project The button text will change to Enable Load Shed Typing a new number in the Set Demand Goal to textbox changes the demand goal red line This represents a reference line for the building manager When building power usage gets close to or above the line adjust the load shedding for various areas to higher percentages to reduce demand 42 Quantum Q Adminim User Manual se LUTRON a AIL as Diagnostics Q Admin X Control amp Monitoring 2 Reports _QAdministration Control A Occupancy Daylighting Time Clock Hyperion Solar Clock Load Shedding I Diagnostics Lone toi LUT RON The system
11. Duration Test B link B QS Link i Duration Test will test emergency batteries to make sure they meet Manual Testi SE Office Building Second Floor Electrical Closet ESN 001 Se L their rating test lasts up to hour K ga Stoop 1 DALI wf Office Building First Floor Open Office Areas Open To run a test right now click on Choose the Emergency Units to test Manual Test This will prompt you to Selected Emergency unit specify which groups to test Office Building First Floor Open Office Areas Open O Emergency Units part of the following groups A Office Building Second Floor Open Office Areas Oper OQ office Building Second Floor Conference Rooms Conf Group 1 Manual Test Group 2 V Group 3 Stop All Tests F Group 4 F Group 5 Group amp Group 7 2 Status Awaited A A device somewhere below this device has a problem To run a manual test 1 Select a ballast within the group in the grid optional 2 Click Manual Test 3 Select the type of test to run function test or duration test 4 Choose Selected Emergency unit to test the specified ballast as selected on the diagnostics screen Otherwise choose Emergency Units part of the following groups and check which groups to test 5 Click OK to begin the test To stop any test on a group manual or scheduled 1 Click any ballast in the group 2 Click Stop All T
12. Office Building Fourth Floor Open Office Areas Open Office South After Hours Active Office Building Fourth Floor Electrical Closet After Hours Active Day Begins at 12 00 AM Sunrise 7 00 AM Sunset 7 18 PM Logged in User admin Logged in Time Thursday March 24 2011 5 50 48 PM Test Events allows you to simulate a Time Clock event live to confirm that it controls the outputs programmed to it To test a Time Clock event 1 Select a Time Clock event in the grid 2 Click the Test Event button 30 Quantume Q Adminim User Manual Sie LUTRON o AIL KT Enable Disable Selected Time Clocks 12 Lanauage Enalish United States 1 UTRON X Control amp Monitoring J Reports _sgAdministration gt Control Occupancy Daylighting B Time Clock A Hyperion Solar Clock Load Shedding Diagnostics 9 You are viewing After Hours Pending Changes _ x Change Occupancy Settings Pending Changes Project Time Clock Disabled Pending Changes After Hours Pending Changes Go To Today I lt March 2011 gt M I want to P View Events Collapse All 7 00 am At Sunrise End After Hours Set Up Time Clock Events 7 14 21 28 5 Test Events 6 00PM 6 00 PM Begin After Hours Enable Disable Selected Time Clock D Review Location Settings The After Hours is currently
13. S Conference Rooms Conference Room 222 GW Private Offices Z Private Office 211 Z Private Office 212 S Private Office 213 S Private Office 214 Private Office 215 a g Restrooms Z Mens Restroom Y Womens Restroom Elevator Lobby Z Kitchen Y Copy Room Electrical Closet 1 Select an area from the left The minimum light level for this area is 40 Fe 2 Set the minimum light level for this area Fc 40 ica esp Thumbnail Do you want to Recommission Daylighting in this area Recommission HE pig Logged in User admin Logged in Time Tuesday April 19 2011 5 14 12 PM Switched daylighting Switched daylighting is commissioned in Q Adminm Minimum light level can be viewed and set for each area To change the minimum light level 1 Select an area 2 In the right pane select Adjust the Daylighting Minimum Level 3 Change the level using the text box or up down buttons 4 Click Apply SE LUTRON a Quantume Q Adminm User Manual 21 Control amp Monitoring Daylighting Step 1 Overview Daylight Commissioning Step 2 Record Light Level with Lights On You are working in area Office Building Second Floor Conference Rooms Conference Room 221 Step 3 Record Light Level with Commissioning must be done under the following conditions Lights Off There is no direct sunlight in the space Step 4 Set Minimum Light Level Daylight is reasonably constant sunny
14. not have been purchased with your system Contact Lutron if you are interested in purchasing additional features such as Q Reportingm LUTRON nts Orhan User Manual 7 Q Adminm Overview Overview Q Adminm can run on a client or server PC see Appendix for supported versions of Microsofte Windowse It communicates with the Runtime and Reporting modules on the Q Managerm server The Runtime module manages communication between the Q Managerm server and the Quantume lighting hubs collecting all status information e g lights on off areas occupied unoccupied etc from the system The Reporting module logs system activity and power information used in reports and Green Glancee Up to 6 clients can access Control amp Monitoring and Reports from Q Adminm at the same time Main Tabs and Program Features The Q Adminm application is separated into three parts as seen in the major tabs below The Language hyperlink at the top allows changing the language The question mark icon to the right displays the current version of Q Adminm and the date it was released Q Admin h Control amp Monitoring IM Reports _ggAdministration gt Control A Occupancy Daylighting Time Clock 4 Hyperion Solar Clock gt Load Shedding Diagnostics A gt gt Control amp Monitoring Overview This tab includes features used both to control and to monitor the live state of various system features e g lights and s
15. 2 2222 71 View Schedules Test Events 2 2 2 2 34 Enable Disable Hyperionm 2222220 35 Appendix 22000 79 SOUP Han oa Hae a re Bere en 36 Load Shedding 2 2 2222 42 Contact Information 81 Diagnostics 2 0 000000 0000020 43 DALI Emergency Status 22222222 45 Manual Tests bees eee ee eS 49 se LUTRON A Quantum Q Adminm User Manual 3 How to Use This Guide This guide is divided into manageable sections which will allow you to easily walk through the process of controlling and monitoring your building using the Q Adminm software You will notice that this guide contains text and corresponding pictures screen shots Also note the appearance of the indicator hand It will help to guide you through the process from screen to screen See example below Example Text Login Upon launching the Q Adminm application the Login screen will appear Enter your username and password and click Login Click Advanced to show two options as shown on the right These options will allow you to publish a new database or to change your password To start Q Adminm in another language click the Language hyperlink and choose a language The default login is admin admin1 For more on users and passwords please see the section Administration gt Users 4 Quantume Q Adminn User Manual Q Admin Language English United States LUTRON User Name
16. 8 s 7 8 3 10 Ar 2 23 15 16 17 18 19 20 21 12 13 14 15 16 17 18 10 11 12 13 14 15 16 14 15 16 47 18 19 20 Occup 22 23 24 25 26 27 28 19 20 21 22 23 24 25 17 18 19 22 21 22 23 21 2 23 24 25 2 27 29 Eg 31 26 27 28 23 30 24 25 26 27 28 23 30 28 23 30 31 31 September October _ November E December _ Occupanl S TUTE SIJE M TRET ESEMS T WNE S MEEO RS 1 2 3 1 1 2 3 4 5 1 2 3 4 a 6 7 L 3 10 2 3 4 5 6 7 8 6 7 8 9 10 11 12 4 5 6 7 8 3 10 a1 2 13 14 15 16 17 9 10 11 12 13 14 15 13 14 15 16 17 18 19 11 12 13 14 15 16 17 0 18 93 20 21 22 23 24 17198 19 20 21 22 20 21 22 23 en ea 26 18 19 20 21 22 23 24 ccupad 25 26 27 28 29 30 3 45 26 27 28 29 27 28 2 30 25 26 27 28 SS EJ 31 l 30 31 c Wizard Step 5 Define Special Events Special events are events that will occur on specific dates such as holidays or once a month occurrences Normal weekly events will still occur on days that are not part of a special schedule To define special events 1 Click on Show Special Calendar to modify the schedule 2 In the yearly calendar select or unselect days by clicking them to add or remove from the special schedule A single day in the year may only be part of a single special schedule Special schedules will recur on the same date every year 3 After creating a special schedule click Save and then add events as before Up to five special schedules can be defined Special schedules are unique to the Time Clock they are defin
17. 9 X Switch to Tabular View Occupancy I want to Monitor occupancy status Enable Disable occupancy Change occupancy settings Occupancy for this area is currently Enabled 1 Set occupancy state to Enabled Disabled 2 Set level for area Go to occupied level Go to unoccupied level Don t change level Apply Cancel Sensor timeout is in addition to any timeout manually set at the sensor Logged in Time Thursday March 24 2011 5 50 48 PM The Occupancy screen allows the building manager or security guard to monitor the occupancy status of each area and make occupancy setting changes as follows Current area occupancy state can be monitored occupied unoccupied disabled inactive Area occupancy can be disabled or re enabled to override occupancy control or in case of occupancy sensor problems To enable or disable occupancy 1 Select an area 2 In the right pane click Enable Disable occupancy 3 Select whether you want to enable or disable occupancy by choosing the appropriate radio button 4 Select whether the area should immediately go to the occupied or unoccupied level or do nothing 5 Click Apply LUTRON Quantums Q Admin User Manual 17 Control amp Monitoring Occupancy and After Hours The current area selected is Office Building Second Floor Electrical Closet You are viewing Building 2nd Floor N Switch to Tabular View Woccupi
18. Power amp Energy Usage Lamp Maintenance System Activity System Troubleshooting Diagnostics Report 003 Diagnostics Report 004 Sensor Connection Report 002 Diagnostics Report 005 Diagnostics Report 006 Diagnostics Report 007 Diagnostics Report 008 Sensor Connection Report 003 Sensor Connection Report 004 Diagnostics Report 013 Diagnostics Report 2nd Floor March 2011 Opening Reports To open a saved report 1 Click Open in the Reports tab 2 Click the selected report 3 Click OK The report will be loaded in a new subtab under the View tab se LUTRON A Quantume Q Adminn User Manual 51 T Q Admin X Control amp Monitoring Reports 3Administration New icf Open view 9 Diagnostics Report 2nd Floor March 2011 X Lighting Energy Usage Report 036 X P H Save as d Save amp Print Gy export Lighting Energy Usage Report 036 Lighting Energy Usage Report Report Generated on Wednesday April 20 2011 3 38 40 PM Graphical view Area Energy kwh Tabular View Office Building Second Floor Open Office Areas Open Difice North Office Building Second Floor Open Office Areas Open Office South 494 Office Builing Second Floor Conference Rooms Conference Room 221 49 7 How much energy did the lighting in 639 Export Report Data Li Click here to select Areas Choose the format in which you want the report data to be exported Excel Sheet
19. Savings Comparison Green Glancee displays energy savings in terms of kWh real power money coal not burned and carbon dioxide not emitted Green Glancee can be set to use some none or all of these comparisons based on which are in the Comparisons To Be Displayed box Money saved is determined by price of electricity and unit of currency which can be set at the bottom of the screen Instantaneous Power Savings Total Savings Relative to Full On 3 65 MW h 364 6 Total Savings Relative to Full On 351on Carbon dioxide 1 8 ton Coal ji not Burned 3 5 ton Carbon dioxide not Emitted A LUTRON a Quantume Q Adminm User Manual 73 Administration Green Glance Configuration ss SLUTRON X Control amp Monitoring Reports 39Administration 7 Users Back up Publish Processor Update Wizard Areas Displayed Display Control Savings Comparisons Weather Display Project Info Building Features Design Team The Green Glance display can show current weather information for the location entered below W Display the Weather Current Location Settings Coopersburg Pennsylvania Edit Location Settings C9 Location Settings Country United States of America State Pennsylvania ity Coopersburg Latitude 49 5 N Longitude 75 4 Time Zone Eastern Time _ LZ Adjust for daylight Savings Minutes Set Clock Ahead Set Clock
20. Solar Clock Load Shedding Diagnostics e The current area selected is Office Building Second Floor Open Office Areas Open Office North You are viewing ME office Building j S CTR View Expand All 4b F Lights Shades lapse All I want to how Ar mbers View the status of shades Area Status Gj office Building S nat Floor lopen Office Areas Hopen Office North open Office South MM Electrical Closet 5P second Floor B open Office Areas Select a shade preset Set a shade to a position 1 Select an area from the left 2 Select a shade group to adjust Shade Group Preset Sunscreer Morpen Office South SM Conference Rooms Conference Room 221 Conference Room 222 S Derivate Offices Private Office 211 Private Office 212 Private Office 213 Private Office 214 Private office 215 Restrooms Mens Restroom womens Restroom f Elevator Lobby Kitchen a Copy Room electrical Closet 8 third Floor l Hopen Office Areas 3 Select a preset to move the shades to Preset Apply Quickly change all shades in the area Open Close Lights On a Lights Off Logged in User admin Logged in Time Thursday March 24 2011 4 17 12 PM For areas with shades the position of shade groups can be controlled and monitored All shade groups in an area can be sent to open o
21. Turn OFF under Quickly change area lighting To send all lights in an area to a level 1 Select an area 2 On the right pane select the Lights tab and the Area Level subtab 3 Select a level by typing in the box using the slider or using the up down arrows 4 Click Apply For areas that have been zoned Predefined lighting scenes can be controlled and monitored To send an area to a scene 1 Select an area 2 On the right pane select the Lights tab and the Area Scene subtab 3 Select a scene from the dropdown list 4 Click Apply A LUTRON a Quantume Q Adminn User Manual 11 Control and Monitoring Control East Downlights Incand nt 1 North Downlights gt z6 r a wnlig ncandesce o wnlig v Scene Configuration f l 1 Select the scene you would like to configure Hl File or fy Scene 18 Scene 003 x 2 Lights in area should F Unaffected E unaffected F Unaffected Not change when zones are adjusted Change when zones are adjusted South Downlights West Downlights 3 Select the zone to adjust F Unaffected Master zone level control E w Save Cancel nini Close Area lighting scenes can be modified in real time To modify an area s scenes 1 Select an area 2 In the right pane click Scene Configuration The Scene Configuration window will o
22. are saved Green Glancee should be restarted Green Glancee Configuration Areas Displayed The Areas Displayed tab allows an administrator to define the areas to be displayed in Green Glancee To change the name of the building as displayed in Green Glancee type the desired name under Building Name To choose which areas are displayed in Green Glancee 1 Click Click here to select Areas The Select Additional Areas pop up will display as shown 2 Expand the area tree as necessary and select the desired areas using the checkboxes 3 Click OK To change the name of an area as displayed in Green Glancee type the desired name in the column Green Glancee Area Display Name se LUTRON a Quantume Q Adminn User Manual 71 Administration Green Glances Configuration Areas Displayed Display Control Savings Comparisons I Weather Display Project Info Building Features Design Team The Green Glance display can automatically cycle between various pages This is useful if the display is not set up so that the viewer can select the page they wish to view The auto cycle feature also prevents screen image burn in on certain display types Default Page on Start Up 30 Days I Enable auto cycle Available Pages Pages To Be Cycled Cycle Time 3 Hours Compare 30 Days 4 minute lt 24 Hours Project Information 7 Days 30 Days 1 Year Cumulative adiz Compare 24 Hour
23. left To change the view click the area at the top next to You are viewing and select another area Selecting an area under You are viewing will hide all other areas from the display In the example shown the user has selected to only display areas on the second floor A LUTRON a Quantume Q Admin User Manual 9 Control and Monitoring Graphical View ol X Control amp Monitoring Reports JAdministration E Zana 3 occupancy Daylighting Time Clock Hyperion Solar Clock Load Shedding Diagnostics The current area selected is Office Building Second Floor Open Office Areas Open Office North You are viewing Building 2nd Floor Y Hluights On 4 Lights Shades Wichts off 1 Select an area from the left view to control the lights Current Selection 7 61 Second Floor IS C Open Office Areas e Nortt Area Scene Area Level Zone Open Office South are active scene is Conference Rooms Conference Room 221 Conference Room 222 2 8 Private Offices Private Office 211 Private Office 212 Private Office 213 Private Office 214 2 Private Office 215 2 Select a new scene Scene Select a Scene X Apply Quickly change area lighting Mens Restroom GoTo Scene 1 Womens Restroom Elevator Lobby Kitchen 7 Copy Room Electrical Closet GoTo Off Scene Configure Scenes Scene Configuration Thumbnail
24. of 58 EngravingPosition 3 24 20 PM gt Sending File 31 of 58 PresetAssignment 3 24 20 PM gt Sending File 32 of 58 DaylightingSensorConnection 3 24 21 PM gt Sending File 33 of 58 InfraredSensorConnection 3 24 21 PM gt Sending File 34 of 58 ContactClosureInputSensorConnection 3 24 21 PM gt Sending File 35 of 58 SceneController 3 24 21 PM gt Sending File 36 of 58 SwitchLeg 3 24 21 PM gt Sending File 37 of 58 FixtureAssignment 3 24 21 PM gt Sending File 38 of 58 Sensor 3 24 21 PM gt Sending File 39 of 58 Enclosure 3 24 21 PM gt Sending File 40 of 58 ControlStation 3 24 21 PM gt Sending File 41 of 58 Zone 3 24 21 PM gt Sending File 42 of 58 Area 3 24 21 PM gt Sending File 43 of 58 DaylightingGroup 3 24 21 PM gt Sending File 44 of 58 DaylightingRegion 3 24 21 PM gt Sending File 45 of 58 OccupancyGroup 3 24 22 PM gt Sending File 46 of 58 PartitionWall 3 24 22 PM gt Sending File 47 of 58 GainGroup 3 24 22 PM gt Sending File 48 of 58 DaylightingSetPointLevelAssignment 3 24 22 PM gt Sending File 49 of 58 TimeClockEventModeAssociation 3 24 22 PM gt Sending File 50 of 58 TimeClockEvent 3 24 22 PM gt Sending File 51 of 58 RoutineEventAssociation 3 24 22 PM gt Sending File 52 of 58 SingleActionProgrammingModel 3 24 22 PM gt Sending File 53 of 58 DualActionProgrammingModel 3 24 22 PM gt Sending File 54 of 58 Scene 3 24 22 PM gt Sending File 55 of 58 Preset 3 24 23
25. service 80 Quantum Q Adminim User Manual S4 LUTRON a Worldwide Technical and Sales Assistance If you have questions concerning the installation or operation of this product call the Lutrone Technical Support Center Please provide the exact model number when calling Model number can be found on the product packaging Example QSE IO U S A Canada and the Caribbean 1 800 523 9466 Other countries call 1 610 282 3800 Fax 1 610 282 1243 Visit us on the web at www lutron com Lutron EcoSystem GRAFIK Eye Green Glance Pico Quantum and Sivoia are registered trademarks and Hyperion Q Admin Q Design Q Graphic Q Manager Q Reporting and Q Runtime are trademarks of Lutron Electronics Co Inc Microsoft Windows SQL Server Visual C and Excel are registered trademarks of Microsoft Corporation in the United States and or other countries Pentium is a registered trademark of Intel Corporation in the U S and or s el UTRON other countries ae Lutron Electronics Co Inc 2014 Lutron Electronics Co Inc Made and printed in the U S A 7200 Suter Road P N 040383 Rev B 04 2014 Coopersburg PA 18036 USA Quantum Q Adminn User Manual 81
26. settings for weather display The Location Settings display can be accessed from the Time Clock and Hyperionm screens by clicking Edit Location Settings in the right pane after selecting Review Location Settings To enter your location 1 Click Edit Location Settings and in the popup window select your country state province and city This will automatically populate your latitude longitude time zone and daylight savings information 2 If your city is not available click Add City and enter the appropriate details 3 Click Save when completed Remember to perform a database backup see the Administration section for details to save changes to disk 32 Quantume Q Adminim User Manual S4 LUTRON a Hyperion Solar Clock x pe Lance Erae nied san LU TRO X Control amp Monitoring Reports Administration gt Control Occupancy Daylighting Time Clock Hyperion Solar Clock Load Shedding Diagnostics 9 Ares Office Building Second Floor Open Office Areas Open Office North Enabled GoTo Today raie lt May 2011 gt Expand All View settings Se ER 5 Colapse All Setup Hyperion C 2 BB ah eo 7 Hyperion Event 1 Ir 10 Se oo c 9 17 Sunscreen 11 TE DEON Evata 24 Hyperion Event 2 Enable Disable Hyperion 6 35 AM gt 31 Sunscreen 31 Review Location Settings Hyperion Event 3 7 35 AM Sunscreen 88 View
27. the Hyperion events for the selected area Hyperion Event 4 in the grid at the left 8 35 AM Sunscreen 100 r Hyperion settings for selected area Hyperion Event 5 5 35 PM Sunscreen 73 Work surface height 40 in Max sunlight 60 in 6 35 PM keaz penetration Sunscreen 11 Min time between 60 min movements gt Logged in User admin Logged in Time Thursday March 24 2011 5 50 48 PM Overview Hyperionm is an automated shading system that adjusts Sivoiae QS shades throughout the day based on the sun s position The shades reduce glare and solar heat gain in the space creating a comfortable and productive work or learning environment Hyperionm maximizes the amount of available daylight entering a space enhancing the energy saving potential of daylight harvesting lighting systems and can also reduce energy costs associated with HVAC systems Screen Layout The Hyperionm Solar Clock screen allows the user to view and test the Hyperionm schedule for any area enable disable Hyperionm and to configure Hyperion settings The screen layout is similar to the Time Clock screen On the left a calendar is used to select different days In the middle is a full list of Hyperionm events for that day which displays when shades move and what level they move to On the right pane radio buttons are used to view settings setup Hyperionm test Hyperion events enable disable Hyperionm and review location settings se LUTRON a Quant
28. 0 PM Office Building Second Fioor Electrical Closet After Hours Active Clock en C IG Special Routine3 Office Building First Floor Open Office Areas Open Office North After Hours Active 4 Office Building First Floor Open Office Areas Open Office South After Hours Active gt TS aaa Office Building Third Floor Open Office Areas Open Office North After Hours Active Launch Time Clock Wizard Office Building Third Fioor Open Office Areas Open Office South After Hours Active Office Building Fourth Floor Open Office Areas Open Office North After Hours Active Office Building Fourth Floor Open Office Areas Open Office South After Hours Active Office Building Fourth Floor Electrical Closet After Hours Active Day Begins at 12 00 AM Sunrise 7 00 AM Sunset 7 18 PM Logged in User admin Logged in Time Thursday March 24 2011 5 50 48 PM To create or modify a Time Clock click Set Up Time Clock Events on the right and click the Launch Time Clock Wizard button Use Back Next to navigate through the wizard At any time press Save and Close Wizard when complete Any changes made in the wizard will be saved to the live database and to the system Note After making changes you should go to Administration and backup the project database to a file Step 1 Overview Select Show Example to view an example Time Clock Quantum Q Adminnm User Manual 25 LUTRON Creating Modifying Time Clocks
29. 11 220 26 PM System Status lice Burg Second Floor West 2 Dining Area Demo Area DINING AREA 3 SOLAR SHADE 2 sent to 52 4 20 2011 2 15 26 PM System Status Office Building Second Floor North West Dining Area DINING AREA 1 SOLAR SHADE 1 sent to 55 gt Apply 4 20 2011 2 15 26 PM System Status Office Building Second Floor North West Dining Area DINING AREA 1 SOLAR SHADE 2 sent to 55 gt 4 20 2011 2 15 26 PM System Status Office Building Second Floor West 1 Dining Area DINING AREA 2 SOLAR SHADE 2 sent to 55 4 20 2011 215 26 PM System Status Office Bulking Second Floor West 1 Dining Area DINING AREA 2 SOLAR SHADE 1 sent to 552 4 20 2011 2 01 53PM Occupant Office Building Second Floor Cafeteria Cue 1214 KITCHEN DDOR Button 4 was Released 4720 2011 201 50PM System Status Des Building Second Floot Cafeteria Cue 121A changed to Scene Dff Scene 4 20 2011 2 01 50PM Occupant Office Building Second Floor Cafeteria Cue 121A KITCHEN DOOR Button 4 was Pressed 4 20 2011 201 50PM System Status Office Building Second Floor Cafeteria Cue TZIAWKITCHEN SERVING AREA CANS sent to 0 Logged in User admin Logged in Time Wednesday April 20 2011 3 29 06 PM System Activity Report What activity occurred in selected areas over time period This report gives a list of activity that has happened in the Quantume system or in specified areas over a given period of time The report will display all events of th
30. 120412 office Building Second Floor Open Office Areas Open Office North 3 06 Address 6 EcoSystem Digital Ballast 041200412 Voffice Building Second Floor Open Office Areas Open Office North 3 07 Address 7 EcoSystem Digital Ballast 04120412 A office Buildina Second Floor Open Office Areas Open Office North 3 08 Address 8 EcoSystem Digital Ballast 041270412 d V office Building Second Floor Open Office Areas Open Office North 3 09 Address 9 EcoSystem Digital Ballast ETS Y Office Building Second Floor Open Office Areas Open Office South 3 10 Address 10 EcoSystem Digital Ballast 041270412 WA Office Building Second Floor Open Office Areas Open Office South 3 11 Address 11 Ecosystem Digital Ballast 0 4 12 0 4 12 ial Device that is responding does not appear in database New firmware available for this device L A device somewhere below this device has a problem Logged in User admin Diagnostics allows the building manager to check on the status of all equipment in the lighting control system View Diagnostics 9 Logged in Time Wednesday April 20 2011 4 27 35 PM Devices will be listed with a reporting status of OK missing or unknown Check or uncheck the filters above the grid OK Unknown Not in Database Not Responding to show or hide devices with those states At any time click the Show Report link above the grid to show the same information in a report form which can be saved expor
31. 7 00 AM Sunset 7 18 PM Logged in User admin Thursday March 24 2011 I want to Ex All View Events Collapse All 7 00 am At Sunrise Time Clock Event 02 K ST TOE Test Events 7 00 PM Time Clock Event 01 Office Building Second Floor Elevator Lobby With Evaluate 0 Enable Disable Selected Time Clock Office Building Second Floor Elevator Lobby Oce Vac Active A j Office Building Second Floor Elevator Lobby With Evaluate 25 Review Locations Sellings Office Building Second Fioor Kitchen With Evaluate 25 Office Building Second Floor Kitchen With Evaluate 0 Office Building Second Floor Kitchen Oce Vac Active Office Building Second Floor Copy Room Oce Vac Active Office Building Second Floor Copy Room With Evaluate 25 Office Building Second Fioor Copy Room With Evaluate 0 Office Building Second Floor Open Office Areas Open Office 25 a North With Evaluate Office Building Second Floor Open Office Areas Open Office 0 North With Evaluate one Building Second Floor Open Office Areas Open Office Oce Vac Active Norti Office Building Second Floor Open Office Areas Open Office 25 South With Evaluate Office Building Second Floor Open Office Areas Open Office 0 South With Evaluate Office Building Second Floor Open Office Areas Open Office Occ Vac Active South Office Building Second Floor Conference Rooms Conference Oce Vac Active Room 221 Office Building Second Floor Conf
32. Back Month Day Of Week March lt Sunday Week Time Second week 02 00 Add City Save Cancel Green Glancee Configuration Weather Display Determine whether or not Green Glancee will display the current local weather and set the project location using the Edit Location Settings button Weather display requires Internet connectivity in order to connect to the Lutrone Weather Server Coopersburg 93 2 F Mostly Cloudy with Showers 10 625 mph due W Coopersburg 932 F Mostly Cloudy with Showers 10 625 mph due W 74 Quantume Q Admin User Manual BC LUTRON o Administration Green Glances Configuration X Control amp Monitoring l Reports _ggAdministration 2 Users Back up Publish Processor Update Wizard Areas Displayed Display Control savings Comparisons Weather Display Project Info Building Features Design Team V Display the Project Information Tab Commission Date 5 4 2011 By Project Title Project Web Site Press Test button to launch your default browser and test access to this website Test Project Description Building Thumb Full Image Assign New Image Assign New Image Save Cancel Project Info Enter information relevant to the project including commission date title website and description and upload a building thumbnail and image These wi
33. Conference Rooms Apply Cancel Lighting Power Usage Report How does the power usage of selected areas compare over time period This report shows a bar graph comparing multiple areas energy usage over time To create a Lighting Power Usage Report 1 Select the areas to compare by using the Click here to select Areas link 2 Choose the timeframe by using the dropdown menu on the right 3 Click Apply 2 LUTRON A Quantum Q Adminn User Manual 55 Available Reports Q Admin Laes Enaieh United states LU TRON Control amp Monitoring Reports 3Administration J New LF Open A view 9 Diagnostics Report 2nd Floor March 2011 2nd Floor Area Comparison Lighting Power Usage Report 022 Lighting Power Trend Comparison Report 008 X Pa Save As Save amp Print G export Lighting Power Trend Comparison Report 008 Lighting Power Trend Comparison Report Report Generated for Area Office Building on Wednesday April 20 2011 3 43 19 PM Graphical view an Tabular view 7 Time Frame A Start Date Tuesday April 05 2011 Time Frame B Start Date NX 5 Tuesday April 12 2011 gt Duration 3 1 Week v 2 9 H A u T EA R A EE E 16 C d ee a oe EA ce E g 88 3 g S 8 SSR 3 E ee E S g Pe 8 8 Be E E S E 28 2 g E 38 52 as amp gs iG S S SSL BEN ER SI B BS S RS Time Frame A
34. Controls connected to the Quantume hub that are located in the occupant space include wall controls and shades 3 Ballast Controllers Ballast controllers connect to ballasts and sensors located in fixtures throughout a section of a floor Typically one ballast controller will control up to 128 ballasts 44 Quantums Q Adminm User Manual BC LUTRON o AIL a View DALI Emergency Status pr J RATE Lanauage Enaish United States S ELU X Control amp Monitoring j Reports Administration gt Control 7 Occupancy Daylighting Time Clock Hyperion Solar Clock gt Load Shedding 9 The system has detected one or more problems So To Toda 4 Diagnostics The system will update the status of DALI Emergency Units in the grid below based on when functional and duration tests are I want to performed These tests may be scheduled by clicking on the Setup Wizard or by running tests manually BR D View Diagnostics Show Devices with Status View DALI Emergency Status MM ok 76 Problem Functional Test Group 1 Setup Expand All To define which Emergency Units Collapse All Show Report Customize Columns belong to which test groups and schedule test times click on Setup Device Group Problem Wizard Second Floor Hub B Office Building Second Floor Electrical Closet Processor Panel 001 Setup Wizard SB AsLink B QS Link E S S Manual Testing B Office Building Second Floor E
35. Daylighting screen allows the building manager to control and monitor daylighting as follows Daylighting can be enabled or disabled To enable disable daylighting 1 Select an area 2 In the right pane click Enable Disable Daylighting 3 The right pane will display the selected area s daylighting state and will have a button to change it 4 Click the Enable Daylighting or Disable Daylighting button A LUTRON a Quantum Q Adminm User Manual 19 Control amp Monitoring Daylighting j Q Ad g x Lanausae Enaish Unted States SL UI TRON X Control amp Monitoring Reports _sgAdministration The current area selected is Office Building Second Floor Private Offices Private Office 214 You are viewing Building 2nd Floor X Switch to Tabular View Moayiighting Enabled EN Daylighting Woay ishting Disabled Current Selection 7 91 Second Floor 7 9 Open Office Areas 2 Open Office North Open Office South z Conference Rooms 2 Conference Room 221 S Conference Room 222 SJ Private Offices f Private Office 211 Private Office 212 Z Private Office 213 Private Office 214 S Private Office 215 J Restrooms Mens Restroom I want to View Daylighting Status Enable Disable Daylighting Adjust the Daylighting Target Set Point 1 Select an area from the left The current daylighting target set point for this ar 85 2 Set the daylighting target set po
36. E 1 sent to 45 gt Filter Events A 2 4120 2011 245 23PM System Status Dies Bulking Second Floo North West Dining Area DINING AREA 1 SOLAR SHADE 2 sent to 45 Gl ge Se 10 11 12 13 14 15 17 18 19 BJ 2 22 24 25 26 27 28 29 Building Manager Activity iy Status Activity Device Failure Activity 4 20 2011 2 45 23 PM System Status Office Building Second Floor West 1 Dining Area DINING AREA 2 SOLAR SHADE 2 sent to 45 4 20 2011 2 45 23 PM System Status Dlfice Bulding Second Floor West 1 Dining Area DINING AREA 2 SOLAR SHADE 1 sent to 45 gt 4 20 2011 2 40 23 PM System Status Office Buildina Second F Floor west 2 Dining Area Demo Area DINING AREA 3 SOLAR SHADE 2 sent to 45 1020 24023 PM System Status Dice Building Second aaisa 2Dining Area Demo AreaDINING AREA 3 SOLAR SHADE 1 1 sent to 45 4 20 2011 2 30 26 PM System Status Office Building Second Floor North West Dining Area DINING AREA 1 SOLAR SHADE 1 sent to 50 gt 4 20 2011 2 30 26 PM System Status Dies Bulking Second Floor Narth West Dining Area DINING AREA 1 SOLAR SHADE 2 sent to 50 4 20 2011 2 30 26 PM System Status Office Building Second Floor weest 1 Dining Area DINING AREA 2 SOLAR SHADE 2 sent to 50 4 20 2011 2 30 26 PM System Status Office Building Second Floor west 1 Dining Area DINING AREA 2S0LAR SHADE 1 cent to 50 4 20 2011 2 20 26 PM System Status Office Building Second FloortWest 2 Dining Area Demo Area DINING AREA 3 SOLAR SHADE 1 sent to 52 gt 4 20 20
37. Enabled I want to disable the time clock D Until the End of the Day Until I Enable It Again Disable Time Clock O Weeky G Holidays Special Routine 1 O Special Routine 2 EI Special Routine 3 Special Routine 4 4 gt Day Begins at 12 00 AM Sunrise 7 00 AM Sunset 7 18 PM Logged in User admin Logged in Time Thursday March 24 2011 5 50 48 PM Time Clocks can be enabled and disabled through the system e g through keypad button presses CCl toggle switches or sequences These are programmed in Q Designm after a Time Clock has been created in Q Adminm Once a Time Clock is disabled all Time Clock events for the given Time Clock will stop occurring until that Time Clock is re enabled To disable an enabled Time Clock indefinitely 1 Choose a Time Clock in the You are viewing dropdown 2 Choose the Enable Disable Selected Time Clock option in the right pane 3 Choose the Until Enable It Again option in the right pane 4 Click Disable Time Clock The Time Clock will remain disabled until explicitly re enabled To disable an enabled Time Clock until the end of the day 1 Choose a Time Clock in the You are viewing dropdown 2 Choose the Enable Disable Selected Time Clock option in the right pane 3 Choose the Until the End of the Day option in the right pane 4 Click Disable Time Clock The Time Clock will re
38. Enalish United States 3 LUTRO X Control amp Monitoring Reports gAdministration gt Control A Occupancy Daylighting Time Clock Hyperion Solar Clock Load Shedding Diagnostics o Hyperion Wizard Step 1 Overview and Defaults Step 2 Facing Directions Step 3 Window Types Step 4 Area Setup Step 5 Nighttime Settings Step 6 Override Settings Shade Closed Height Enter the different window types that are covered by shades that will be controlled by Hyperion Select the most common window type as the default Window Type Name Shade Closed Height inches Shade Open Height inches Default Window Type 1 30 120 d Window Type 2 20 120 a Add New Click on Next to advance to the next step R lt Back Save and Close Wizard Logged in Time Thursday March 24 2011 5 50 48 PM Logged in User admin Hyperion Wizard Step 3 Window Types In order to figure out how light will penetrate into each space we need to know the size and relative position from the floor for each window For most buildings a few window sizes and positions are used We call these window types Enter in the window types Size and relative position from the floor that will be used for Hyperion controlled spaces 38 Quantum Q Adminim User Manual Sie LUTRON o AIL as Hyperion Solar Clock Control amp Monitoring earnest nn _ gt conta 1 amp 7 Oceupaney Davlgh
39. Inactive Test events allow you to simulate time clock event right now to confirm that it Office Building Third Floor Open Office Areas Open Office North Occupancy Inactive Kr aE vod lente programmed Office Building Third Floor Open Office Areas Open Office South Occupancy Inactive Office Building Fourth Floor Open Office Areas Open Office North Occupancy Inactive Select the time clock event from the left to Office Building Fourth Floor Open Office Areas Open Office South Occupancy Inactive test and click on Test Event Office Building Fourth Floor Electrical Closet Occupancy Inactive 6 00 PM Begin After Hours Test Event Office Building Second Floor Elevator Lobby After Hours Active Office Building Second Floor Kitchen After Hours Active B Holidays Office Building Second Floor Copy Room After Hours Active Special Routine 1 Office Building Second Floor Open Office Areas Open Office After Hours Active s S South U Special Routine 2 6 00 PM Office Building Second Floor Electrical Closet After Hours Active Special Routine 3 Office Building First Floor Open Office Areas Open Office North After Hours Active 4 Office Building First Floor Open Office Areas Open Office South After Hours Active Office Building Third Floor Open Office Areas Open Office North After Hours Active Office Building Third Floor Open Office Areas Open Office South After Hours Active Office Building Fourth Floor Open Office Areas Open Office North After Hours Active
40. Open Office Areas Open Office North You are viewing ME Office Building X Switch to Graphical View Expand All 4 Y Lights Shades llapse All 1 Select an area from the left view to control the Show Area Numbers lights Find area Area Scene Area Level Zone Current Scene The lights are currently B First Floor an Alopen Office Areas 2 Select a light level open Office North Open Office South E ectrical Closet B Second Floor RA SM open Office Areas Open Office North open Office South Scene 001 i Conference Rooms Conference Room 221 Conference Room 222 8 Private Offices Private Office 211 Private Office 212 Private Office 213 Private Office 214 Private Office 215 Restrooms Mens Restroom Apply m Quickly change area lighting Turn ON L Turn OFF Womens Restroom levator Lobby kitchen copy Room electrical Closet Third Floor g aopen Office Areas hnd erh L d tights On W Lights Off The Control screen allows the building manager to control and monitor the lighting system as follows Area lights can be monitored for on off status All lights in an area can be turned on off or sent to a specific level 0 100 To turn all lights in an area on or off 1 Select an area 2 On the right pane select the Lights tab and the Area Level subtab 3 Click Turn ON or
41. PM gt Sending File 56 of 58 TimeClock 3 24 23 PM gt Sending File 57 of 58 ShadeGroup 3 24 23 PM gt Sending File 58 of 58 DaliEmergencySwitchLegController 3 24 23 PM gt Performing Post Transfer Steps 3 24 23 PM gt Sending Link Command to Processor s 3 24 23 PM gt Transferring to Components Expected Component Total 2100 3 24 23 PM gt Post transfer steps complete 3 24 23 PM Total Components Expected to Transfer 2100 m Stop RHD a 77H Publish Project Files Transfer to System To begin the transfer process click Start If the Audit Check is enabled it will scan the database for both critical errors and warnings If there are any problems detected these will be displayed to the user in a popup with options to print or export the details If there are warnings but no critical errors the user can choose to proceed with transfer or to cancel A critical error in an audit check will prevent transfer After the audit completes if selected the live database will be transferred i e uploaded to all the processor systems that were selected on the Select Systems page Note When transferring a new configuration to the system local controls e g keypads occupancy sensors daylight sensors etc will not function Transfers typically take between 15 and 45 minutes to complete Once the transfer is complete please review the display for any errors If there are errors you may need to check system wiring and
42. QuantuMe Q Adminm Guide 7 s lt LUTRON Table of Contents Getting Started Reports How to Use This Guide 4 Creating New Reports 2 2 222 222 50 Quick Reference Guide Frequently Used Opening Reports 51 Q Adminm Features 2 5 Saving Printing Exporting 52 Quantume System Diagram 2 2 2 6 Report Options 2222 53 Login 22 7 Available Reports 00 54 Light Energy Usage 2 2222 aa 54 Program Features Lighting Power Usage 55 Main Tabs and Program Features 8 Lighting Power Trend 222222222 56 Control and Monitoring 9 Lamp Maintenance 57 Tabular View ee 9 System Activity ua a aa 58 Graphical View 10 Diagnostics oo 59 Control 11 Sensor Connection 60 Occupancy amp After Hours 22202020 16 DALI Emergency Units 61 Daylighting 2 0 0 0 0 004 19 Time Clocks 2 ee ee 23 Administration Viewing Time Clocks 2222 2 2 2220 24 Users 0 LLL 62 Creating Modifying Time Clocks 25 CreateaNewUser 2 62 Testing Time Clocks 2 2s 30 Delete Modify InactivateaUser 63 Enable Disable Selected Time Clocks 31 Backup Files oo a 000 64 Review Edit Location Settings 32 Publish oo 65 Hyperionm Solar Clock ee 33 Processor Update Wizard 222222220 69 Overview o nn 33 Green Glancee Configuration
43. Step 3 Assign Outputs Define which system loads shades and other outputs are controlled by the selected Time Clock The text box at the top allows you to change the name of the Time Clock To assign outputs to a Time Clock 1 Click Add Remove Output to display a window with all controllable outputs in the project database 2 To add outputs a Select the type of output in the dropdown b Navigate to the output in the area tree c Check the output you want to add 3 Click OK when finished The grid below the Add Remove Output link shows what outputs are selected for control by the selected Time Clock A LUTRON a Quantume Q Adminim User Manual 27 Creating Modifying Time Clocks K Control amp Monitoring ud Reports 3 inistration oo se 1 stem Day TERE amp ya sola ck Sim Sang 1 1 inet Time Clock Wizard ZT U LRS HS Define Weekly Events Step 2 Add Edit Delete You are modifying After Hours Step 3 Assign Output Below is list of weekly time clock events defined for this time clock To edit an event select the event and click on Edit Event To define a new event click on New Event Weekly Schedule Sun Mon Tue Wed Thur Fri Sat Step 4 Define Weekly Events Step 5 Define Special Events Event Step 6 Finish Time Quickly Set Levels Set level value for all the outputs of selected type 1 Define when the new event will occur
44. Type in the group number from 1 to 7 46 Quantume Q Adminim User Manual sv LUTRON o AIL as DALI Emergency Status Setup kanns Ener Ured au SLU TRON ap napaan en Control amp Monitoring Reports Fr ame E Setup Test Times Step 1 Define Emergency Groups Define which day of the week each emergency group is to be tested Step 2 Setup Test Times Group 1 Sunday m i 00 AM Group 5 Thursday lli 00 AM Step 3 Configure Prolong Time Group 2 Monday U fi 200 AM Group 6 Friday j 00 AM Group 3 Tuesday IlL 00 AM Group 7 Saturday IlL 00 AM Group 4 Wednesday y 1 00 AM Function Tests Define when emergency units are to be function tested Function tests verify that emergency units are responding properly check for lamp failures and verify that the emergency circuit is working They do not verify that the battery operates within its rated limits Perform Function Test Manual Only Every Other Week Weekly Monthly Duration Tests Define when emergency units are to be duration tested Duration tests verify that emergency batteries operate within their rated limits During Perform Duration Test Manual Only Quarterly Annually Monthly Every 6 months Step 2 Setup Test Times The Setup Test Times step determines what weekday and time of day each test group will be tested and how often function and duration tests
45. afterward in the default spreadsheet or image application check Open file after Export 5 Click Export 52 Quantume Q Adminim User Manual De LUTRON a Reports Q Admin L Lauce Erinus L UT RON Control amp Monitoring Reports 3Administration New Open view e Diagnostics Report 2nd Floor March 2011 X Lighting Energy Usage Report 036 X Pa lH Save as d Save Print Gy export Lighting Energy Usage Report Graphical view O Tabular view Select the areas to include How much energy did the lighting in Expand All Collapse All Click here to select Areas Show Area Numbers Find area Area Selected lt Gomes Building Y First Floor No Areas second Floor 1 5 1 Sopen Office Areas 2 Office Building Second Floor Open Office Areas open Office North ffice Building Second Floor Open Office Area Open Office South Bf Conference Rooms use over the _ Conference Room 222 Last 7 days v Gprivate Offices OK Cancel Apply Cancel Logged in User admin Logged in Time Wednesday April 20 2011 3 29 06 PM Report Options Reports can be run with different options for example the report above can be run for one or more areas over a specified time period To choose areas displayed in a report 1 Click Click here to select Areas 2 Check one
46. as Open Office Occupancy Inactive gt j lt South Review Location Settings 7 00 AM Office Building Second Floor Electrical Closet Occupancy Inactive Office Building First Floor Open Office Areas Open Office North Occupancy Inactive Segue Fae T RRA atc aat Office Building First Floor Open Office Areas Open Office South Occupancy Inactive Time Clock Events may be scheduled to ar reoccur on a weekly basis or on specific Office Building Third Floor Open Office Aress Open Office North Occupancy Inactive d E oes 2 ates Click on button below to launch the Office Building Third Floor Open Office Areas Open Office South Occupancy Inactive Time Clock Wizard Office Building Fourth Floor Open Office Areas Open Office North Occupancy Inactive Office Building Fourth Floor Open Office Areas Open Office South Occupancy Inactive Office Building Fourth Floor Electrical Closet Occupancy Inactive The Time Clock Wizard will allow you to Add Edit and Delete Time Clock Events on 6 00 PM Begin After Hours existing Time Clocks or create new Time Office Building Second Floor Elevator Lobby After Hours Active Gone Office Building Second Floor Kitchen After Hours Active Office Building Second Floor Copy Room After Hours Active The wizard will also allow you to choose E Special Routine Sms Building Second Floor Open Office Aress Open Office After Hours Active which outputs lights shades contact 2 Sout closure outputs are controlled by each Time 6 0
47. aste Water Reduction Reducing all waste streame by 5 annually 76 Quantume Q Admin User Manual Ba Green Building Features Energy Conservation Making our facilities more energy efficient by converting heating systems and of course retrofitting office areas with Lutron products Recycling Increasing our recycling streams including a goal of 100 recycling of cardboard paper and electronic scrap Waste Water Reduction Reducing all waste streams by 5 annually 7 sLUTRON Administration Green Glance Configuration x LUTRON Areas Displayed Display Control i Savings Comparisons Weather Display Project Info I Building Features Design Team Architect Architect 1 Architect 2 Architect 3 MEP Engineers MEP Engineer 1 MEP Engineer 2 MEP Engineer 3 Lighting Designers Lighting Designer 1 Lighting Designer 2 Lighting Designer 3 i Design Team The user can type in the names of the building design team to display to the user in Green Glancee This information is displayed in Green Glancee for informational purposes Design Team Design Team Architect lt lt e Architect MEP Engineer MEP Engineer CB e i Bi T a CB4 ee g ee l CB3 mn un nn mn Equipment Provider Lutron Eloetronie Co tne Lighting Design ore ew Equi
48. atus Office Building Second Floor North West Dining Area DINING AREA 1 SOLAR SHADE 2 sent to 38 gt 4 20 2011 31524PM System Status lie Bulding Second Floor West 1 Dining Area DINING AREA 2 SOLAR SHADE 2 sent to 8 4 20 2011 3 15 24 PM System Status Office Building Second FloortWest 1 Dining Area DINING AREA 2 SOLAR SHADE 1 sent to 38 J 4 20 2011 315 24PM System Status Office Bulding Second Floor North West Dining Area DINING AREA 1 SOLAR SHADE 1 sent to 38 al 4 20 2011 3 00 26 PM System Status Office Building Second Floor West 2 Dining Area Demo Area DINING AREA 3 SOLAR SHADE 2 sent to 39 Custom K 4 20 2011 30026 PM System Status Dlfice Bulding Second Floor West 2 Dining Area Demo Area DINING AREA 3 SOLAR SHADE 1 sent to 39 Start Date M d yyyy End Date M d yyyy 4 20 2011 3 00 23 PM System Status Office Building Second Floor Narth West Dining Area DINING AREA 1 SOLAR SHADE 2 sent to 41 BO 12 00 00 AM 4 20 2011 30 23PM System Status Office Building Second FloorSWest 1 Dining Area DINING AREA 2 SOLAR SHADE 2 sent to 41 Seo S 4 20 2011 Mi 4 20 2011 3 00 23PM System Status Office Building Second Floor West 1 Dining Area DINING AREA 2 SOLAR SHADE 1 sent to 41 4 20 2011 3 00 23 PM System Status Office Building Second Floor North West Dining Area DINING AREA 1 SOLAR SHADE 1 sent to 41 Sun Mon Tue Wed Thu Fri 4 20 2011 2 45 23 PM System Status Office Building Second Floor North West Dining Area DINING AREA 1 SOLAR SHAD
49. cation the Login screen will appear 1 Language Selection To start Q Adminm in another language click the Language hyperlink at the top right corner and choose a language 2 Login Upon launching the Q Adminm application the Login screen will appear prompting for your user name and password The default login is user name admin and password admin1 For more on user accounts and passwords please see the section Administration gt Users 3 Advanced Login Options Click Advanced to show two options These options will allow you to publish a new database or to change your password immediately after login Q Admin Ea Language English United States LUTRON User Name Password 0 Login Cancel lt lt Advanced Advanced options hidden by default E I After login publish new project database I After login prompt to change password Special Note to Administrator Before launching the Q Adminm application two modules must be launched on the lighting control server The first module is Q Runtimem this is responsible for communicating to the Quantume lighting processors to allow control and monitoring of the lighting system The second module Q Reportingr is optional but is required to access reporting and Load Shedding features Q Runtimem and Q Reportingm should be kept running at all times so system activity and energy usage will be logged Also note that Q Reportingm may
50. configuration or correct the project file in Q Designm While the update is in progress all other tabs will be disabled After a publish or transfer Q Adminm will need to be restarted 68 Quantum Q Adminim User Manual S4 LUTRON a Administration Processor Update Wizard i Zn Language English United States LUTR N X Control amp Monitoring Reports 39Administration 2 Users Back up Publish Processor Update Wizard Green Glance Configuration 9 Processor Update Wizard Choose systems to update to processor OS version 2 0 31 Z First Floor Hub Processor Panel 001 Processor 1 Unable to communicate Processor Panel 001 Processor 2 Unable to communicate EN Second Floor Hub Processor Panel 001 boot 1 1 14 os 2 0 25 T Third Floor Hub Processor Panel 001 Processor 1 Unable to communicate Processor Panel 001 Processor 2 Unable to communicate 1 Fourth Floor Hub Processor Panel 001 Processor 1 Unable to communicate Processor Panel 001 Processor 2 Unable to communicate Update Processors One or more processors did not respond Try these troubleshooting tips 1 Ensure all processors are powered up 2 Ensure all network connections are made 3 Ensure all processors have been addressed Click the button below to go to the processor addressing wizard Processor Update Wizard Select Systems The Processor Update Wizard is used to update processors in the lighting co
51. ction or duration tests were run for each unit 1 Click Customize Columns 2 Select the columns you want to be displayed in the grid To define groups click the Setup Wizard link on the Diagnostics screen This will open the DALI Emergency Setup Wizard To view a printable report click the Show Report link above the grid A LUTRON a Quantum Q Adminm User Manual 45 DALI Emergency Status Setup 3 Define Emergency Groups Step 1 Define Emergency Groups Emergency groups define which emergency units are tested together at one time Emergency groups should be defined as follows Step 2 Setup Test Times Automatically Choose Emergency Groups Let me Define Emergency Groups Step 3 Configure Prolong Time For each emergency unit define which group 1 7 it is part of Area S fFirst Floor aopen Office Areas Open Office North 001 002 Open Office South electrical Closet BMW second Floor Step 1 Define Emergency Groups The system provides seven groups of ballasts which allows for example testing each group on a particular day of the week The user can let the system define which ballasts are in which groups default or the user can define groups manually by entering a group number for each ballast To add a ballast to a specific DALI emergency test group 1 Select Let me Define Emergency Groups 2 Select a ballast in the grid 3
52. d Green Glance Configuration F I want to back up the project database Specify the path and file name lut where you would like to save a copy of the Project Database D Quantum Projects Building_Backup_2_0_25_May_4_2011 lut Browse 7 I want to back up the graphical floor plan Save graphical floor plan file as D Quantum Projects Building_Backup_2_0_25_May_4_2011 fpb 7 Browse Save The Backup screen allows an admin user to save the project database and or graphical floorplan It is very important after making any configuration change to perform a backup of the project database Actions that modify the project and require a backup to save changes include the following Scene Configuration Changing default occupancy After Hours or daylighting levels Daylight commissioning Configuring Time Clocks Configuring Hyperion Configuring DALI emergency tests Modifying user accounts Modifying Green Glancee Configuration To backup the live project and or graphical floorplan file 1 Check I want to back up the project database if desired 2 Choose the destination file by using the Browse button and or typing in the textbox 3 Check I want to back up the graphical floor plan if desired 4 Choose the destination file by using the Browse button and or typing in the textbox 5 Click Save 64 Quantum Q Adminim User Manual De LUTRON a s as Admini
53. des Close sheers only Close sheers and open blackouts Leave the shades as they are Click on Next to advance to the next step lt Back next gt Save and Close wizard Hyperion Wizard Step 5 Nighttime Settings Specify when the Hyperionm schedule will begin and end every day Outside of these times Hyperionm will not move the shades Times can be set either as fixed times e g 5 35 a m or as astronomic times e g at sunrise 30 minutes before sunset etc Set what should happen when the Hyperionm schedule ends every day open all shades close sheers sunscreens only close sheers Sunscreens and open blackouts or leave shades unaffected in which case shades will stay where they are when Hyperion ends 40 Quantum Q Adminim User Manual sv LUTRON o AIL as Hyperionm Solar Clock Hyperion Step 1 Overview and Defaults Override Settings Step 2 Facing Directions Step 3 Window Types Specify what should happen to Hyperion in an area when a user manually controls the shades in that area Step 4 Area Setup When shades are manually controlled in an area Hyperion will be Step 5 Nighttime Settings Disabled for C 30 minutes Disabled until the end of the Hyperion schedule nighttime settings will still take place Step 6 Override Settings Click on Next to advance to the next step Hyperion Wizard Step 6 Override Settings Any manual movement of a s
54. e Q Adminm and Green Glancee on any clients and the Reporting Server on the server to restart Click Start to perform the publish This will load the files to the runtime module on the server To perform a database transfer to the lighting system click Next to proceed to the Select Systems screen If you do not wish to transfer to the lighting system click Cancel This will reload Q Adminm with the newly published file This should only be done if changes have been made to the graphical floorplan 66 Quantum Q Adminim User Manual De LUTRON a Administration Publish s as a er Lanquage English United States Z 3 LUTRON R Control amp Monitoring Reports Administration Users Back up Publish Processor Update Wizard Green Glance Configuration Publish Project Files Select Systems to Transfer to Select All Select None Choose a File 1 First Floor Hub Processor Panel 001 Processor 1 Unable to communicate Processor Panel 001 Processor 2 Unable to communicate Transfer to Server IV Second Floor Hub Processor Panel 001 boot 1 1 14 os 2 0 25 ix Third Floor Hub Processor Panel 001 Processor 1 Unable to communicate Processor Panel 001 Processor 2 Unable to communicate O Fourth Floor Hub Transfer To System Processor Panel 001 Processor 1 Unable to communicate Processor Panel 001 Processor 2 Unable to communicate Audit Check J Perform Audit Check Bef
55. e Areas S Open Office North Open Office South gt amp 9 Conference Rooms GE Partitioned Conference Room 47 lele lM MM ES Z Partitioned Conference Room 47A amp Private Offices Restrooms if Elevator Lobby i Kitchen al Copy Room XD Electrical Closet Third Floor Fourth Floor eg E Apply Cancel Lamp Maintenance Report Which Areas are reporting failed lamps This report run against a specified area lists the number of failed lamps in that area or if it is a folder area the number of failed lamps in each of its child areas Areas with no failures are not displayed To create a Lamp Maintenance Report 1 Select an area in the dropdown 2 Click Apply se LUTRON a Quantume Q Adminm User Manual 57 Available Reports Q Admin Language Enalsh United states SELL TRON X Control amp Monitoring 7 Reports _gpAdministration New open T A view e Lighting Power Usage Report 022 Lighting Power Trend Comparison Report 008 Lamp Maintenance Report 013 System Activity Report 036 X Sensor Connection Report 005 4 P 4p isave as save print G Export System Activity Report 036 System Activity Report Report Generated on Wednesday April 20 2011 4 21 24 PM What activity occurred in Click here to select Areas ADINING AREA 3 SOLAR SHADE 2 sent to 35 Breas ADINING AREA 3 rT SHADE 1 sent to 35 gt 4 20 2011 3215 24 PM System St
56. e area does not use sensors choose the After Hours Timeout and Blink Warn Timeout The After Hours Timeout is the time the lights will remain on before performing a blink warn to tell the occupant that lights are going to turn off shortly The Blink Warn Timeout is the time the lights will remain on after a blink warn before going to off or a custom unoccupied level if the occupant does not press a button on a wall control 5 Choose whether or not the settings should take effect immediately For example if the area is already occupied and you change the occupied level to 50 should it go to 50 as soon as you click Apply or only on the next occupied event 6 Click Apply 18 Quantume Q Adminm User Manual S4 LUTRON a AIL a Control amp Monitoring Daylighting A LUTRON X Control amp Monitoring i Reports Administration gt Control 4 Occupancy Z Baylighting Q Time Clock X Hyperion Solar Clock Load Shedding Diagnostics The current area selected is Office Building Second Floor Private Offices Private Office 212 You are viewing Building 2nd Floor Switch to Tabular View Blpaylighting Enabled Daylighting BBaylighting Disabled T want to Current Selection 3 9 Second Floor 2 0 Open Office Areas Enable Disable Daylighting Open Office North E 5 Open Office South 1 Conference Rooms Z Conference Room 221 S Conference Room 222 2 49 Private Offices S Private Office 211 Dayligh
57. e day The default visor position is full open 100 A visor position helps to reduce glare from other indirect light sources e g a neighboring building To change Hyperion area settings 1 Select each area in the top grid and the bottom grid will be populated with that area s shade groups 2 For each shade group in an area set the checkbox at the right if the shade group will be affected by Hyperionm 3 If a shade group is affected by Hyperionm set the window type facing direction and visor position By default the settings from step 1 will be used but for any area you may choose to use different settings by clicking Customize the Hyperionm settings for this area at the bottom This will allow you to choose a work surface height maximum sunlight penetration and minimum time between movements specific to that area Hyperionm Solar Clock Control amp Monitoring E Hyperion Wizard Step 1 Overview and Defaults Nighttime Settings Step 2 Facing Directions Step 3 Window Types Start of Hyperion Schedule Specify the time of day generally in the morning when Hyperion should become active Step 4 Area Setup Time Fixed Time lt Step 5 Nighttime Settings 7 00AM Step 6 Override Settings End of Hyperion Schedule Specify the time of day generally in the evening when Hyperion should become inactive 00 30 v After x Sunset r When the Hyperion schedule ends the system should Open all sha
58. e specified types that happened in the specified areas within the date range Activity filters are as follows Occupant Activity Areas going occupied unoccupied wall controls being pressed Time Clock Activity Time Clock events being executed Building Manager Activity Q Adminm activity including login logout and real time changes to the lighting system Status Activity Zone level changes area scene changes etc Device Failure Activity Devices becoming unresponsive Lamp Failure Activity Lamp failures reported by EcoSysteme DALI ballasts Sensor Activity Occupancy sensor state changes occupied and unoccupied Ballast Failure Auto Replacement Activity Shows when ballast failures have occurred or when new ballasts have been installed and auto replaced System Errors Error codes reported by the system BACnet Activity Lights shades and other system objects changed through BACnet To create a System Activity Report 1 Select one or more areas by using the Click here to select Areas link 2 Choose the time span for which to display activity by using the over the dropdown menu If selecting Custom specify the start date and end date 3 Select the desired activity types to show by clicking the checkboxes under Filter Events 4 Click Apply 58 Quantum Q Adminim User Manual P LUTRON o Available Reports Q Admin Language Enaioh United states SELL TRON Con
59. e time between movements defaults to 60 minutes 36 Quantum Q Adminim User Manual De LUTRON a Hyperion Solar Clock K Control uii RE EEE Hyperion Wizard Step 1 Overview and Defaults Step 2 Facing Directions Step 3 Window Types Step 4 Area Setup Step 5 Nighttime Settings Step 6 Override Settings TRUE NORTH L Back Field gt 315 Specify the different facing directions present in your building s These are the compass orientations of any sides of your building s that have shades controlled by Hyperion The angle should be measured perpendicular to the windows facing outward Be sure to measure your facing directions using true north rather than magnetic north for best results Facing Direction Name North Facing Hyperion Wizard Step 2 Facing Directions Specify the different facing directions present in your building s These are the various different compass orientations of any sides of your building s that will have shades controlled by Hyperionm Facing directions are used to determine how the sun will penetrate into an area during any given time of a particular day It is important to measure facing directions correctly as all Hyperionm shade movements will be based on these directions For best results be sure to measure your facing directions using true north rather than magnetic north se LUTRON a Quantume Q Adminm User Manual 37 Hyperion Solar Clock ol x N Lanauage
60. ear in the event list 2 Define the event name what days and times the event will happen on and what actions will happen in the system when the event executes The time dropdown allows you to choose either a fixed time e g 5 41 p m or an astronomic time e g 12 minutes after sunset 3 The grid in step 2 shows what level each output will be sent to The default unaffected means that output will not be affected by the Time Clock event To quickly set many different outputs to the same level e g all areas to scene 1 click the Quickly Set Levels hyperlink In the window that displays choose the output type in the first dropdown menu and choose the level in the second dropdown menu 4 The evaluate checkbox is valid only for occupancy If evaluate is checked the Time Clock event enables disables occupancy it will first re evaluate if the area is occupied and go to the appropriate level if unchecked lights will not change until the next occupancy event and if occupancy is enabled 5 When finished adding an event click Save you may have to scroll down to see this button 28 Quantume Q Adminim User Manual aM LUTRON o AIL as Creating Modifying Time Clocks X Control amp Monitoring Reports Administration oe ER Eger Seren ere 7 Pen gt conta 1 Daviohing ITS Hype Load Shedding Diagnostics Time Clock Wizard Step 1 Overview I want to Step 2 Add Edit Del
61. ed 4p 4 Occupancy Wunoccupied I want to Wisavied Monitor occupancy status Ditnactive Enable Disable occupancy Current Selection 3 9 Second Floor E La Open Office Areas Open Office North Open Office South E C Conference Rooms i Conference Room 221 Conference Room 222 Private Offices E Private Office 211 Private Office 212 Private Office 213 Private Office 214 S Private Office 215 E C Restrooms Change occupancy settings 1 Select an area from the left Current settings for this area are Occupied Level 75 Unoccupied Level 0 After Hours Timeout 60 Minutes After Hours 5 Minutes 2 Select New Settings SZ Mens Restroom Occupied Level P5 X Womens Restroom S Elevator Lobby Unoccupied Level 0 P S Kitchen 4 gt x S Copy Room After Hours Timeout 60 v Minutes Blink Warn Timeout 5 Minutes 3 Select how to apply Apply and update area based on new levels Apply and wait for the next transition to take place to change light levels Apply Cancel Thumbnail a 1 1 1 1 U 1 1 1 1 1 a Logged in User admin Logged in Time Thursday March 24 2011 5 50 48 PM Area occupancy settings can be changed in real time To change occupancy settings 1 Select an area 2 In the right pane click Change occupancy settings 3 Type in the desired occupied level unoccupied level 4 If the area uses sensors choose the sensor timeout If th
62. ed in E g the Holiday schedule in one Time Clock may be different than the Holiday schedule of another Time Clock Step 6 Click Save and Close Wizard Save and Close Wizard will make the Time Clock changes to the live Quantume system To make the changes in the lut file remember to perform a project database backup in the Administration tab A LUTRON a Quantum Q Adminm User Manual 29 Testing Time Clocks ae Paon sss 27LU TRON A Hyperion Solar Clock Load Shedding Diagnostics 9 You are viewing After Hours Pending Changes Go To Toda Thursday March 24 2011 I want to feMarch201y gt S ras om View Events i oe cr aa eee oes a EEE m At Sunrise End After Hours Set Up Time Clock Events 6 7 8 9 10 11 12 SS ZZ _ I IUI S Office Building Second Floor Elevator Lobby Occupancy Inactive Test Events 13 14 15 16 17 18 19 Office Building Second Floor Kitchen Occupancy Inactive 20 21 22 23 25 26 Office Building Second Floor Copy Room Occupancy Inactive Enable Disable Selected Time Clock 27 28 29 30 31 Office Building Second Floor Open Office Areas Open Office Occupancy Inactive lt gt South Review Location Settings 7 00 AM Office Building Second Floor Electrical Closet Occupancy Inactive Office Building First Floor Open Office Areas Open Office North Occupancy Inactive 2 5 Office Building First Floor Open Office Areas Open Office South Occupancy
63. en transferring a new configuration to the system local controls e g keypads occupancy sensors daylight sensors etc will not function Transfers typically take between 15 and 45 minutes to complete To choose a project to publish 1 Under Project Database choose the second radio button specify that you want to choose a file 2 Choose the existing file to load by using the Browse button and or typing in the textbox To choose a graphical floorplan to publish 1 Under Graphical Floor Plan choose the second radio button specify that you want to choose a file 2 Choose the existing file to load by using the Browse button and or typing in the textbox By default the first radio buttons are selected for both project and graphical floorplan In this case the published file will remain the same To choose to remove a published graphical floorplan 1 Select the third radio button I do not want to use a graphical floorplan 2 To proceed with the publish click Next Administration Publish Lanquage English United States Z 3 LUTRON K Control amp Monitoring Reports 33Administration Users Back up Publish Processor Update Wizard Green Glance Configuration 9 Publish Project Files Choose a File Transfer File to Server Start Select Systems Transfer To System Publish Project Files Transfer to Server Publishing a database will cause all other clients i
64. erence Rooms Conference 0 Room 221 With Evaluate Office Building Second Floor Conference Rooms Conference 25 Room 221 with Evaluate Office Building Second Floor Conference Rooms Conference 0 Room 222 with Evaluate Office Building Second Floor Conference Rooms Conference 25 Room 222 With Evaluate Office Building Second Floor Conference Rooms Conference Oce Vac Active Room 222 Office Building Second Floor Private Offices Private Office 211 Oce Vac Active Office Building Second Floor Private Offices Private Office 211 0 With Evaluate Office Building Second Floor Private Offices Private Office 211 25 With Evaluate Office Building Second Floor Private Offices Private Office 212 Occ Wac Active Office Building Second Floor Private Offices Private Office 212 0 with Evaluate Office Building Second Floor Private Offices Private Office 212 25 with Evaluate Office Building Second Floor Private Offices Private Office 213 25 with Evaluate Office Buildina Second Floor Private Offices Private Office 213 Occ Vac Active Office Building Second Fioor Private Offices Private Office 213 0 with Evaluate Office Building Second Fioor Private Offices Private Office 214 Occ Vac Active 7 00 PM Office Building Second Floor Private Offices Private Office 214 0 with Evaluate gt ke V m r Logged in Time Thursday March 24 2011 5 50 48 PM To view Time Clocks select View Events on the right side o
65. erion Wizard Step 1 Overview and Defaults Step 2 Facing Directions Step 3 Window Types Step 4 Area Setup Step 5 Nighttime Settings Step 6 Override Settings Maximum Sunlight Penetration at work surface height Work Surface Height Te Select system wide defaults for Hyperion below These settings can all be overridden on an Area by Area basis if desired Work Surface Height inches 40 Maximum Sunlight Penetration inches 60 Minimum Time Between Shade Movements minutes 60 gt Click on Next to advance to the next step Next gt Save and Close Wizard Logged in User admin Logged in Time Thursday March 24 2011 5 50 48 PM Setup Hyperion To configure Hyperionm select Setup Hyperionm in the right pane and click Launch Hyperionm Wizard The Hyperionm Wizard can be used to configure Hyperionm in multiple areas Hyperion Wizard Step 1 Overview and Defaults Set system wide defaults for Hyperionm This is a quick way to change the settings for all areas that use the defaults Work surface height and maximum sunlight penetration define how far into the space direct sunlight will be allowed to penetrate Hyperionm will continually adjust shades to ensure direct sunlight does not exceed the maximum sunlight penetration depth at the work surface height Minimum time between shade movements defines how often Hyperionm moves shades automatically To minimize distractions th
66. ests A LUTRON a Quantume Q Adminm User Manual 49 X Control amp Monitoring Reports gAdministration Een open view e a Select a standard report definition from the list below Standard Reports Lighting Power amp Energy Usage How much energy did the lighting in selected areas use over time period How does the power usage of selected areas compare over time period How does the power usage of Selected Area compare over Selected Time Frames Lamp Maintenance Which Areas are reporting failed lamps System Activity What activity occurred in selected areas over time period System Troubleshooting What devices are currently not responding and need attention What sensors are not properly connected What DALI Emergency Units are not operating properly according to the last test that was run OK Creating New Reports Reports allow the building manager to gather real time and historical information about the system including power usage lamp device and sensor status and system activity To run a new report 1 Click New under the Reports tab 2 Click the type of report desired in the Standard Reports 3 Click OK A new page will load for the new report 4 Select the report options filters and click Apply Z Q Admin Select a saved report from the list below If you want to configure a new report select New in the menu above T Saved Renas T Lighting
67. ete Use my normal weekly events on every day of the year SAP Sb ASST R U US Define time clock events that will occur on holidays and other special dates in place of normal weekly events Step 4 Define Weekly Events Step 5 Define Special Events 1 Select the Special Schedule to define Holidays Rename Schedule Step 6 Finish 2 To schedule special dates click Show Special Calendar Show Special Calendar Below is a list of time clock events defined for the Holidays special schedule To edit a Special Calendar _ _ gt A ee ewe me Ml m ey Click on the dates on the calendar when the Holidays E will occur D Holidays New El Special Routine 1 To remove a highlighted date Click on it again Special Routine 2 Ess Special Routine 3 De O Special Routine 4 lt 2011 gt Time January February March April SNr SE SS WS SS es WER FEIS M ERS B 1 2 3 4 5 12 32 5 1 2 Pl 2 E 4 5 6 7 8 6 2 8 L 10 1 2 6 Z 8 9 10 11 12 3 4 5 6 7 8 3 9 10 11 12 13 14 15 13 14 15 16 17 18 19 13 u 15 16 17 18 19 10 if 12 13 14 15 16 16 17 18 19 20 21 22 20 21 22 23 24 25 26 20 21 22 23 24 25 26 17 18 19 20 21 22 23 2 Set lev i 23 24 25 26 27 28 29 27 28 27 28 29 30 31 24 25 26 27 28 29 30 T 30 31 OF Ma June Jul August Occupai SM AW Se E SS NENF FS cs OM ET 3 1 2 3 4 5 6 7 i 2 3 4 1 2 1 2 3 4 5 6 8 3 10 1 2 13 14 5 6 L 8 9 w n 3 Z 5 6 7
68. f the Time Clocks screen Select a Time Clock in the You are viewing dropdown and select a day from the calendar on the left By default today is selected All the Time Clock events for the selected day will be listed in the middle pane Click a different day on the left to view that day s Time Clock events Click Expand All or click the to show details of all actions that will happen when a Time Clock event is executed On the left is the output name and on the right is the level the output will go to 24 Quantums Q Adminm User Manual 7 sLUTRON AIL as Creating Modifying Time Clocks X Control amp Monitoring j Reports _sgAdministration gt Control A Occupancy Daylighting 3 Time Clock You are viewing After Hours Pending Changes z Hyperion Solar Clock Load Shedding Diagnostics kenne zei Anis ELUTRON 9 Thursday March 24 2011 Go To Today I want to lt March 2011 gt Expand All View Events ls mT WTF 5 Collapse All i Z 2 g At Sunrise End After Hours Set Up Time Clock Events ee S Office Building Second Floor Elevator Lobby Occupancy Inactive Test Events 13 14 15 16 17 18 19 Office Building Second Floor Kitchen Occupancy Inactive 3 5 20 21 22 23 23 25 26 Office Building Second Floor Copy Room Occupancy Inactive Enable Disable Selected Time Clock 27 28 29 30 31 Office Building Second Floor Open Office Are
69. ffice North Incandescent 1 Open Office South Beia 6 i j North Downlights Electrical Closet T South Downlights B Second Floor 9 j j j West Downlights Bopen Office Areas g open Office South Scene 001 3 Select a light level E SW Conference Rooms _ conference Room 221 Conference Room 222 5 Private Offices Private Office 211 i Private Office 212 Private Office 213 Private Office 214 private Office 215 B Restrooms Mens Restroom Womens Restroom Elevator Lobby itchen Copy Room ls Electrical Closet SQ Third Floor B open Office Areas ss Apply Quickly change zone lighting Turn ON Turn OFF tights On Lights Off Logged in User admin Logged in Time Thursday March 24 2011 4 17 12 PM Levels of individual zones can be controlled and monitored To change a zone s level 1 Select an area 2 In the right pane select the Lights tab and the Zones subtab 3 Select a zone 4 Select the desired level using the slider or text box 5 Click Apply Alternately click Turn ON or Turn OFF to quickly send a zone to full on 100 or full off 0 se LUTRON a Quantume Q Adminm User Manual 13 Control and Monitoring Control X Control amp Monitoring Reports _ggAdministration B Zamal 3 occupancy Daylighting Time Clock Hyperion
70. fine a separate time clock for each of the following e Campus Parking Lot Lights e Shades e Cafeteria Lights Below is an example showing how you might define the Campus Parking Lot Lights Time Clock Campus Parking Lot Lights Time Clock 1 Assign Outputs to Time Clock I want to control all my exterior parking lot areas which include e Exterior Parking Lot 1 e Exterior Parking Lot 2 e Exterior Parking Lot 3 2 Define Weekly Events During a normal week want my Campus Parking Lot Lights to operate as follows Days of the Week One hour Before Sunrise Turn Lights On Monday Friday Turn Lights Off Monday Friday Turn Lights On Monday Friday Turn Lights Off Monday Friday 3 Define Special Events During a holiday I want my Campus Parking Lot Lights to operate as follows Turn Lights On 10 30 p m Turn Lights Off Other Time Clock Applications After Hours Time Clock Days ofthe Week Begin After Hours Monday Friday 7 00 p m End After Hours Monday Friday Disable Nighttime Occupancy Time Clock Days ofthe Week Disable Occupancy Monday Friday 7 00 p m Enable Occupancy Monday Friday Viewing Time Clocks You are viewing Change Occupancy Settings Pending Changes Language English Unted States 4 LUTRON G Holiday Special Routine 1 O Special Routine 2 Special Routine 3 Special Routine 4 Day Begins at 12 00 AM Sunrise
71. gered from a Time Clock event typically in the evening The Time Clock event will change an area s occupancy mode to After Hours Active After Hours is usually ended from a Time Clock typically in the morning The Time Clock event will change an area s occupancy mode to After Hours Inactive This will return the area to its occupied level for daytime operation See Control amp Monitoring gt Time Clock for details on setting up After Hours time clock events 16 Quantums Q Adminm User Manual se LUTRON z Control amp Monitoring Occupancy and After Hours X Control amp Monitoring g Reports Administration 7 Occupancy lt Q Daylighting Time Clock 4 Hyperion Solar Clock gt Load Shedding Diagnostics The current area selected is Office Building Second Floor Open Office Areas Open Office North You are viewing Building 2nd Floor Woccupied unoccupied Hi visabled Ditnactive Current Selection 3 9 Second Floor Open Office Areas Fl Open Office N Open Office Sout 7 6 Conference Rooms E Conference Room 221 Conference Room 222 5 9 Private Offices Private Office 211 S Private Office 212 S Private Office 213 S Private Office 214 Private Office 215 E a Restrooms 91 Mens Restroom Womens Restroom Elevator Lobby S Kitchen S Copy Room S Electrical Closet Thumbnail sea Logged in User admin lt LUTRON
72. hade in an area will disable the Hyperion schedule in an area Select whether to disable the Hyperionm schedule for a fixed time or for the rest of the day when a manual override occurs Save and Close Wizard will save the Hyperionm schedule to the live database and transfer the information to all processors in the system To save changes to disk see the Administration gt Backup section Once finished view and test the new schedule If any changes are required you may revisit the Hyperionm Wizard and tweak any settings as desired LUTRON a Quantume Q Adminm User Manual 41 Load Shedding R Q Admin fe fey LLanguane Enafsh Urited States LUTRON X Control amp Monitoring Reports _ggAdministration X Control Occupancy Daylighting Time Clock X Hyperion Solar Clock Load Shedding Diagnostics 9 Load Shedding is Enabled Building Lighting Power Usage KO Maximum Power Usage 11 83 kw 1 Set Demand Goalto kw 2 Adjust Load Shed Amount To allow load shed check the Allow Load Shed check box for each area to be load Current Power Usage 3 29 kw shed The current column will display the current load shed amount 0 to 90 The higher the load shed amount the more power will be saved To change the load shed Current Load Shed Savings 0 47 kw amount type a new amount in the Goal column click on Save Note load shedding must be enabled before saved settings are applied
73. hades as well as features to set up scheduled operation Time Clock and Hyperionm Solar Adaptive Shading Load Shedding and hardware diagnostics X Control amp Monitoring IM Reports Administration E control 2 Occupancy Daylighting Time Clock 4 Hyperion Solar Clock Load Shedding Diagnostics Reports Overview Reports allow the building manager to gather real time and historical information about the system All reports can be saved printed and exported to a file Exporting to Excel format xIs requires Microsofte Excele 2003 or newer to be installed alternatively reports may be exported in csv format X Control amp Monitoring l Reports _sgAdministration iNew Open View Administration Overview The Administration tab provides functions for administrators to configure and commission the system including user management backup publish and transfer processor firmware upgrade and Green Glancee configuration The Administration tab only appears for users who have been assigned the role Admin X Control amp Monitoring Reports 3gAdministration Ei Users Back up Publish Processor Update Wizard Green Glance Configuration AIL as Control and Monitoring Tabular View x X Control amp Monitoring j Reports _ggAdministration gt Control A Occupancy Daylighting Time Clock amp Hyperion Solar Clock Load Shedding Diagnostic
74. ing Second Floor Conference Rooms Conference Room 221 2 7 Address 7 EcoSystem Digital Ballast 0412 0812 te V Office Building Second Floor Conference Rooms Conference Room 221 2 8 Address 8 EcoSystem Digital Ballast 04120412 W Office Building Second Floor Conference Rooms Conference Room 221 2 9 Address 9 EcaSystem Digital Ballast 0412042 A Office Building Second Floor Conference Rooms Conference Room 221 2 10 Address 10 EcoSystem Digital Ballast 0 4 12 0 412 gt Office Building Second Floor Conference Raoms Conference Room 221 2 11 Address 11 EcoSystem Digital Ballast 04120412 office Building Second Floor Conference Roams Conference Room 221 2 12 Address 12 EcoSystem Digital Ballast 04120412 BOY Office Building Secand Flaor Conference Rooms Conference Room 221 QUANTUM PANEL CAFETERIA DBI Loop 3 DigtalBallast Bus Controls 10 4 12 0 4 12 Y Office Building Second Floor Open Office Areas Open Office North 3 01 Address 1 EcoSystem Digital Ballast oat2mat2 Office Building Second Floor Open Office Areas Open Office North 3 02 Address 2 Ecosystem Digital Ballast 041270412 Office Building Second Floor Open Office Areas Open Office North 3 03 Address 3 EcoSystem Digital Ballast 041270402 Office Building Second Floor Open Office Areas Open Office North 3 04 Address 4 Ecosystem Digital Ballast 041270412 i office Building Second Floor Open Office Areas Open Office North 3 05 Address 5 EcoSystem Digital Ballast 04
75. int for this area T a5 f Apply Z Womens Restroom Elevator Lobby S Kitchen Copy Room if Electrical Closet Thumbnail om yc Logged in User admin Logged in Time Tuesday April 19 2011 5 14 12 PM Dimmed daylighting Daylight set points can be changed for each daylit area This is particularly useful when new departments with different lighting requirements move into a space The daylighting target set point for an area ranges from O to 100 percent To change the daylighting target level 1 Select an area 2 In the right pane select Adjust the Daylighting Target Set Point 3 Change the level using the slider text box or up down buttons 4 Click Apply 20 Quantums Q Admin User Manual RUA 2 sLUTRON Control amp Monitoring Daylighting h Control amp Monitoring j Reports _ggAdministration gt Control 9 Occupancy 9 Daylighting Time Clock 4 Hyperion Solar Clock Load Shedding Diagnostics 9 The current area selected is Office Building Second Floor Conference Rooms Conference Room 221 You are viewing Building 2nd Floor v Switch to Tabular View ww m Moayiighting Enabled AK d Daylighting Wb vlighting Disabled I want to Current Selection Second Floor amp g Open Office Areas a Open Office North View Daylighting Status Enable Disable Daylighting La Open Office South Adjust the Daylighting Minimum Level
76. is waiting for a response t Diagnostics The system will periodically refresh the state of all items displayed in the arid To refresh the status of an item manually right click on the item and select refresh ee Show Devices with Status View Diagnostics Wok 99 Unknown X Not in Database I Not Responding Expand All View DALI Emergency Status Collapse all Show Report Customize Columns Show Area Numbers Device Device Type Firmware Available Current Available Rev a B A Office Building Second Floof Cenference Rooms Conference Room 221 QUANTUM PANEL CAFETERIA Processor 1 Processor SBink B DBI Link BW Office Building Second Floor Conference Rooms Conference Room 221 QUANTUM PANE Digtal Ballast Bus Controller 0 8 06 0 8 06 2 office Building Second Floor Conference Rooms Canference Room 221 2 4 EcoSystem Digital Ballast r 7 V Office Buildina Second Floor Conference Rooms Conference Room 221 2 2 Address 2 EcoSystem Digital Ballast 0 4 12 0 412 Q office Building Second Floor Conference Rooms Conference Room 221 2 3 Address 3 EcaSystem Digital Ballast gt Office Building Second Floor Conference Raoms Conference Room 221 2 4 Address 4 EcoSystem Digtal Ballast 04120412 d Office Buildina Second Floor Conference Rooms Conference Room 221 2 5 Address 5 EcoSystem Digital Ballast 04120412 ij A Office Building Second Floor Conference Rooms Conference Room 221 2 6 Address 6 EcoSystem Digital Ballast 04 120412 V Office Build
77. ish United States ELl X Control amp Monitoring Reports s3Administration El Users Back up Publish Processor Update Wizard Green Glance Configuration The current user selected is Joe Joe User User Accounts 4 First Name Role Status Q User Profile Abraham i Admin Active x 1 Select a user account on the left to view edit profile Regular Active details Kelly ii Admin Active Dan if Regular active Login Id Joe Roger Jackson Regular Inactive First Name Joe Last Name User Role Admin Control and Configuration F Ask for password change at next login W User account active Reset account password Save Changes Add Delete The Users screen allows new user accounts to be created and existing user accounts to be edited There are two user roles Regular and Admin Regular users do not have access to the Administration tab To create a new user 1 Click Add 2 Fill in the text fields on the right First Name and Last Name are optional 3 Select the user s role 4 Click Reset account password 5 Enter and confirm the desired password 6 If desired check Ask for password change at next login 7 Click Save Changes continued on next page 62 Quantume Q Adminim User Manual De LUTRON a AIL as Administration Users x Language English Unted States 3 4 LLU TRON Con
78. lectrical Closet ESN 001 Serial 00002255 Stoop 1 DALI To run a test right now click on vn Fr S z e T Manual Test This will prompt you to Office Building First Floor Open Office Areas Open Office North 002 Address 1 specify which groups to test V Office Building First Floor Open Office Areas Open Office North 001 Address 2 WS Office Building Second Floor Open Office Areas Open Office North 005 Address 3 OQ office Building Second Floor Conference Rooms Conference Room 221 009 Address 4 Manual Test Stop All Tests 2 Status Awaited A A device somewhere below this device has a problem Test is past due for this device Logged in User admin Logged in Time Friday April 29 2011 3 49 57 PM The View DALI Emergency Status section of the Diagnostics screen allows the user to configure and monitor tests for DALI emergency units This feature will be displayed if the Quantume system includes DALI Emergency units Two types of tests are run for DALI emergency ballasts 1 Functional Test This is a short test that verifies emergency units are responding properly and lamps have not failed 2 Duration Test This is a longer test that verifies that batteries driving emergency units are operating properly The calendar shows all days in which test runs are scheduled Hovering over a highlighted day shows what specific tests functional duration or both are happening for which ballast test groups To show the last date fun
79. ll be displayed to the user in the Project Information tab of Green Glancee unless the user unchecks Display the Project Information Tab This information is displayed in Green Glancee for informational purposes Lutron CB5 Lutron CB5 Lutron Caf Located on the first floor of CB 5 the Lutron Caf is used as a cafeteria and meeting place for Lutron employees It opened in February 2005 with food service by Brock amp Company The first building on Lutron s Coopersburg campus was constructed in 1969 CB 5 completed in May 2002 is the fifth and Commission Date June 2008 www lutron com quantum2 se LUTRON a Quantume Q Admin User Manual 75 Administration Green Glance Configuration gt Areas Displayed i Display Control Savings Comparisons Weather Display Project Info Building Feature 1 Building Features Title l Description Building Feature 2 Title Description Building Feature 3 Title Description Design Team Building Features Save Cancel J The user can type in building features to display to the user in Green Glancee This information is displayed in Green Glancee for informational purposes Green Building Features Energy Conservation Making our faites more ener ur recycling streams including a e recycling Of cardboard paper and leotronio sorap W
80. lt today is selected All the Hyperionm events for the selected day will be listed in the middle pane Click a different day on the left to view that day s Hyperionm events Click Expand All or click the to show details of all Hyperion shade movements that day To Test a Hyperion Event Testing Hyperionm events allows the user to simulate the selected Hyperionm event live to confirm that it controls the correct shade group s in the expected manner 1 Choose the Test Hyperionm Events in the right pane 2 Select an area in the area dropdown 3 Click the Hyperionm event you want to test 4 Click Test Hyperion Event The shades in the area will go to the levels defined in the Hyperion event 34 Quantum Q Adminim User Manual De LUTRON a Hyperion Solar Clock 07 x Lane Lane Ener ne au Z LUTRO X Control amp Monitoring Reports Administration X Control A Occupancy Daylighting Time Clock X Hyperion Solar Clock Load Shedding Diagnostics o Area Office Building Second Floor Open Office Areas Open Office North Enabled aa lt May 2011 gt Expand All View settings Collapse All Setu rion Hyperion Event 1 ip Hyper H Sunscreen Test Hyperion Events Hyperion Event 2 Enable Disable Hyperion 6 35 AM l Sunscreen 31 Review Location Settings Hyperion Event 3 7 35 AM Sunscreen 88 Hyperion is currently Hyperi
81. main disabled until 11 59 p m It will then be automatically re enabled To enable a disabled Time Clock 1 Choose a Time Clock in the You are viewing dropdown 2 Choose the Enable Disable Selected Time Clock option in the right pane 3 Click Enable Time Clock Review Edit Location Settings B Q Admii a X l S KA Lanquaae Enalsh Unied Sate ELU TRON X Control amp Monitoring J Reports Administration X Control amp Occupancy Daylighting B Time Clock A Hyperion Solar Clock gt Load Shedding Diagnostics 9 You are viewing After Hours Pending Changes X 6 Location Settings S Thursday March 24 2011 Go To Today 4 ee Country United States of America ED lt March 2011 gt Expand All View Events a r En Collapse All State Pennsylvania x A 2 m s 5 5 At Sunrise City Set Up Time Clock Events oe 8 6 r r 13 44 15 16 17 18 19 Office Building Sei isade 5 m Office Building S c 5 20 21 22 23 4 25 26 Office Building S BRE lt Enable Disable Selected Time Clock 27 28 29 30 31 Office Building S a 75 4 W lt South Review Location Settings 7 00 AM Office Building se Time Zone Eastern Time Adjust for daylight Savings Current Location Settings 60 Minutes Coopersburg Pennsylvania Set Clock Ahead Set Clock Back Month Day Of Week Daylight Savings
82. n Green Glance Configuration ssa LUTRON Areas Displayed Display Control I Savings Comparisons I Weather Display Project Info I Building Features Design Team Green Glance Screen Preview Maximum length for building and area name display is 42 characters CB5 Engineering CB5 Cafeteria Y Building name Area namg C9 Select Additional Areas Select additional areas to include Expand All Building Name Office Building _ Maximum Length is 30 characte Collapse All Find area In addition to showing lighting power savings for your entire building please define ott Areas Selected Click here to select Areas a Office Building Green Glance Area Displ L W First Floor Maximum Length is 27 chard 4 I Second Floor Office Building Second Floor Open Office Areas Open Office Areas l J Open Office Areas Area Path Office Building Second Floor Conference Conference Rooms Rooms U C Conference Rooms Office Building Second Floor Copy Room Copy Room L gl Private Offices Office Building Second Floor Electrical Closet Equipment Room Select the default area Office Building x save canei Administrators can use the Green Glancee Configuration to set up how the Green Glancee application will work After any changes
83. no fast moving clouds The work plane illumination is greater than 20 fc of daylight All work plane meter readings are done at the same place and are measured in FC Click on Next to advance to the next step Logged in Time Thursday March 24 To commission switched daylighting click the Recommission button at the bottom of the right pane and perform the steps in the wizard as follows Step 1 Overview Prerequisites to commissioning switched daylighting are explained Step 2 Record Light Level with Lights On Click Turn On Lights If necessary click Show Sensor Values Once sensor values are stabilized click Next to continue Step 3 Record Light Level with Lights Off This step requires a calibrated light meter Click Turn Off Lights and type in light meter reading s Step 4 Set Minimum Light Level Enter the minimum light level that the area will maintain at all times If desired use a light meter for reference Save Click Save to commit the changes to the system Remember to backup the project to a lut file Administration gt Backup to save a copy to disk 22 Quantume Q Adminim User Manual z4 LUTRON o AIL a Time Clocks Time Clocks are defined to allow automated control of the system via programmed time clock events Multiple time clocks are used to separate control of different areas or different output types lighting shades etc You may for example de
84. nput 5 output QSE DMX QSM Wireless only wired only and wired wireless combo units IR Eye infrared sensor All Lutrone EcoSysteme ballasts and drivers with appropriate EcoSysteme hub All DALI compliant dimmable ballasts with appropriate Lutrone DALI hub Lutrone wired and wireless occupancy and daylight sensors Lutrone wired IR sensors Lutrone wireless Picoe controllers Third Party Interfacing Quantume supports several options for third party interfacing e BACnet over IP One Quantume processor in each system exposes system objects at user s discretion to third party BACnet compatible software Typically used to integrate Lutrone lighting into third party building management software e RS232 Ethernet Integration QSE CI NWK in Quantume system provides integration through RS232 serial port or Ethernet Typically used to receive commands from third party devices such as touchscreens e Contact closures The QSE IO device can send maintained or pulsed signals over its contact closure outputs A third party system can take these as input The QSE IO and QS keypad can receive maintained open close inputs and perform various system actions accordingly se LUTRON a Quantume Q Admin User Manual 79 Appendix Quantum Overview Installation Prerequisites Languages e Quantume supports the following languages English US Spanish French German Chinese Simplified Italian Hardware Prerequisi
85. ntrol system to the latest firmware version This is done when upgrading the lighting system to allow for new functionality and to support newly released Lutrone products Note During the processor firmware upgrade local controls e g keypads occupancy sensors daylight sensors etc will not function After the upgrade completes a publish should be performed for the system to operate A system can only be upgraded if all the processors assigned to it are responding To update processor firmware check one or more responding systems and click Next se LUTRON a Quantume Q Adminm User Manual 69 Administration Processor Update Wizard Language English United States gt lt LUTRO K Control amp Monitoring Reports Administration rt Users Back up Publish Processor Update Wizard Green Glance Configuration 9 Overall Progress Programming Device Firmware Processor Update Wizard mm nn nn Select Systems File 1 of 1 Detailed Progress Hide Details Beginning Processor Firmware Update Process 5 4 2011 5 39 43 PM gt gt Sending firmware file gulliver_os Ifw to system Second Floor Hub Completed Processor Update Wizard Update Processors The Update Processors screen displays the progress of the processor firmware upgrade While the update is in progress all other tabs will be disabled 70 Quantum Q Admin User Manual se LUTRON z Administratio
86. on Event 4 Enabled Sunscreen 100 D Enable Hyperion Event 5 5 35 PM Disable Until End of Hyperion Schedule Sunscreen Disable indefinitely Apply to current area Apply to all areas Hyperion Event 6 6 35 PM Sunscreen Logged in User admin Logged in Time Thursday March 24 2011 5 50 48 PM To Enable Disable Hyperion 1 Choose Enable Disable Hyperion in the right pane 2 Select an area in the area dropdown 3 Select whether you want to enable Hyperionm disable Hyperionm until the end of day or disable Hyperion until it is manually re enabled 4 Click Apply to current area to enable disable only the selected area s Hyperionm schedule or Apply to all areas to enable disable Hyperionm for the entire project Shades controlled by Hyperionm can also be controlled manually Anytime a Hyperion controlled shade moves due to manual control the Hyperionm schedule is overridden temporarily Hyperionm can also be enabled and disabled through the system e g through keypad button presses CCI toggle switches Time Clock events or sequences se LUTRON a Quantume Q Adminm User Manual 35 Hyperion Solar Clock Era SH w Language Enaish Unted States LU TRO kua X Control amp Monitoring j Reports sgAdministration gt Control A Occupancy Daylighting Time Clock Hyperion Solar Clock Load Shedding Diagnostics o Hyp
87. or more areas in the area tree 3 Click OK To change other options in reports use the appropriate controls on the right panel Available options vary by report se LUTRON a Quantume Q Adminm User Manual 53 Available Reports gt Q Admin X Control amp Monitoring Reports Administration New Open T Aen x Diagnostics Report Znd Floor March 2011 X 2nd Floor Area Comparison X P Save As d Save Print Gy export 2nd Floor Area Comparison Lighting Energy Usage Report Report Generated on Wednesday April 20 2011 3 38 40 PM Graphical view Tabular view How much energy did the lighting in 3 Conference Room 221 L 30 5 49 7 kWh e ikh lect Areas 1 Open Office North _ 39 2 63 9 kWh No Areas 2 Office Building Second Floor Open Office Areas 3 Office Building Second Floor Conference Rooms use over the IT dars Enter a name for this report 2nd Floor Area Comparison 2 Open Office south saver Cancel 30 3 49 4 kWh Apply Cancel Logged in User admin Logged in Time Wednesday April 20 2011 3 29 06 PM Lighting Energy Usage Report How much energy did the lighting in selected areas use over time period This report shows a pie chart comparing multiple areas over time It can be used to find which areas are using the most energy To create a Lighting Energy Usage Report 1 Select the areas to compare by using
88. ore Transfer Publish Project Files Select Systems The Select Systems screen displays the state of the processors in the project in preparation for a database transfer All the processor systems hubs in the project file are listed each with one of three states A green checkbox indicates the processor hub is ready for transfer A red X indicates at least one processor in the hub is unable to communicate A yellow indicates the processor hub needs to be upgraded to the latest firmware prior to transfer To perform a processor upgrade use the Processor Update Wizard screen If the Audit Check checkbox is checked database programming will be checked for potential problems at the beginning of the transfer To select which processor systems to transfer to check one or more responding systems and click Next A LUTRON a Quantume Q Adminim User Manual 67 Administration Publish Q Admi lez mmo Lanquage English United States Z 3 LUTRON K Control amp Monitoring Reports 4 Administration m Users Back up P blish Processor Update Wizard Green Glance Configuration 9 Publish Project Files Project transferred successfully to processors 1347 objects have been transferred Choose a File Transferring to Components Transferring Component 132 of 1141 Transfer to Server a Select Systems 3 24 19 PM gt Sending File 29 of 58 Button 3 24 20 PM gt Sending File 30
89. pen 3 Select a scene to configure 4 Choose whether or not zone levels should update in real time as you are adjusting them by selecting one of the radio button options 5 Change the levels of zones within the scene This can be done either through the sliders on the left or the grid on the right 6 To adjust all zones in a scene at the same time click the Master zone level control up down arrows 7 Click Save to save the updated scene to the system Remember to backup the project to a lut file Administration gt gt Backup to save a copy to disk 8 When finished adjusting scenes within an area click Close NOTE Dimmable zones can be set to any intensity from 0 100 or to Unaffected which means that the activation of the scene will not change the intensity of the zone Non dimmed switched zones can be set to On Off or Unaffected 12 Quantum Q Adminm User Manual z4 LUTRON o Control and Monitoring Control T Office Building Second Floor Open Office Areas Open Office North You are viewing ME Office Building Y Switch to Graphical View Expand All 4 Lights Shades oll All 1 Select an area from the left view to control the Show Area Numbers lights Find area Area Current Scene z Area Scene Area Level Zone aM office Building 2 Select a zone below to adjust its level B MfFirst Floor L EMopen Office Areas Zone T 1 East Downlights open O
90. pment Provider Lutron Electronics Co Inc se LUTRON a Quantume Q Adminn User Manual 77 Notes 78 Quantum Q Admin User Manual s4 LUTRON 7 Appendix QuantuMe Overview Overview Quantume Total Light Management is a suite comprised of several applications as follows e Q Designm Used to set up and commission a lighting system Q Graphicm Used to overlay graphical floorplans onto Q Designm databases Q Adminm Used for daily control monitoring and reports on a lighting system Green Glancee Used to monitor energy savings and compare trends Q Runtimem Allows Q Adminm to communicate to lighting system Q Reportingm Logs historical data Required for Green Glancee to run and for Q Adminm to use Load Shedding and Reports System Hardware Quantume supports the following hardware e Quantume processors Two configurable device links per processor Maximum of 16 processors per sub system Typically each floor in a building is a sub system Maximum of 128 sub systems per Quantume project e Lutrone Digital Ballast Interfaces DBI to control EcoSysteme loads e Lutrone Power Panel devices GP LP XP e Lutrone wired QS Devices Energi Savr Nodem All varieties DALI EcoSysteme O 10V and Switching Keypads Keyswitches Shades and shade power supplies GRAFIK Eyee Triac EcoSysteme and DALI both RF and non RF NWK Ethernet Interface IO 10 wired contact closure pins 5 i
91. put to display a list of outputs to choose from To remove an item select an output from the list and click Add Remove Output Step 6 Finish Add Remove Output Type Name Occupancy After Hours Office Building First Floor Open Office Areas Open Office North 600 Occupancy After Hours To add an output check the items you want this time clock to control To remove an output uncheck the items Occupancy After Hours Occupancy After Hours 2 Occupancy After Hours Areas Open Office L Show me only Lighting Areas Occupancy After Hours ghting Area Lighting Zones Occupancy After Hours S O offic Ga c Walls Fir shade Groups Occupancy After Hours p T a Pulsed Output Closures Maintained Output Closures Occupancy After Hours Hyperion Enable State Automatic Sequences Manual Sequences Set Lock State Daylighting Level ae G Q 4 R Occupancy After Hours Occupancy After Hours Occupancy After Hours Areas Open Office KA o After Hours Occupied Level eve Unoccupied Level Lighting DMX 3 Channel Integration DMX 1 Channel Fans onference Room Conference Room 222 i Private Offices Private Office 211 Private Office 212 S Private Office 213 LI na nen 394 3 0 O T Tele Click on Next to advance to the next step
92. r close To send all shade groups in an area to open or close 1 Select an area 2 In the right pane select the Shades tab 3 Click Select a shade preset 4 Under Quickly change all shades in the area click Open or Close to open or close all shades Shade groups presets can be activated and monitored To activate a shade group preset 1 Select an area 2 In the right pane select the Shades tab 3 Click Select a shade preset 4 Choose a shade group 5 In the Preset dropdown choose the desired preset 6 Click Apply 14 _Quantums Q Adminm User Manual BC LUTRON o AIL as Control and Monitoring Control X Control amp Monitoring j Reports _sgAdministration S Zana occupancy lt Daylighting Time Clock Hyperion Solar Clock Load Shedding Diagnostics The current area selected is Office Building Second Floor Open Office Areas Open Office North You are viewing 0 Office Building Expand All Collapse All how Ai D __ Status First Floor Bopen Office Areas open Office North MM Open Office South Electrical Closet SM second Floor Open Office Areas pen Office North Open Office South SM Conference Rooms Conference Room 221 MM Conference Room 222 2 Private offices Private Office 211 Private Office 212 Private Office 213 Private Office 214 Private Office 215 Restrooms Mens Rest
93. room Womens Restroom f Elevator Lobby Kitchen Switch to Graphical View lt Lights Shades I want to View the status of shades Select a shade preset Set a shade to a position 1 Select an area from the left 2 Select a shade group to adjust Shade Group Preset Sunscreen 3 Select a position to move the shades to 25 S Apply Copy Room Electrical Closet third Floor Open Office Areas Lights On Lights Off Logged in User admin Shade groups can be sent to a position To send a shade group to a position 1 Select an area 2 In the right pane select the Shades tab 3 Click Set a shade to a position 4 Choose a shade group 5 Choose a position using the slider text box or up down buttons 6 Click Apply Quickly change all shades in the area Open Close Logged in Time Thursday March 24 2011 4 17 12 PM Many of the above actions can also be done with multiple areas selected e g send all lights in multiple areas to a level activate the same scene in multiple areas move all shades in multiple areas etc To select multiple areas hold the ctrl Keyboard button and click multiple areas NOTE When controlling shades 0 implies that the shade is closed and 100 implies that the shade is fully open LUTRON Quantume Q Admin User Manual 15 Control amp Monitoring Occupancy and After Hours
94. s Compare 7 Days nn Compare 1 Year lt Remove Building Information ee Design Team Move Up Move Down Save Cancel Green Glances Configuration Display Control Display Control allows an administrator to configure Green Glancee default behavior To set the default page that loads when Green Glancee starts select an option under Default Page on Start Up If Enable auto cycle is checked Green Glancee will automatically move from one screen to the next based on the ordering of the pages listed in Pages To Be Cycled Select an option in the Cycle Time dropdown menu to choose how often Green Glancee should stay on each page while cycling AIL as Administration Green Glance Configuration Control amp Monitoring Reports ggAdministration 7 Users Back up Publish Processor Update Wizard Areas Displayed Display Control Savings Comparisons Weather Display I Project Info I Building Features Design Team L 1 Select the savings comparisons to be displayed Available Comparisons Comparisons To Be Displayed kWh Saved Dollars Saved Amount of Coal Not Burned Amount of CO2 Not Emitted lt Remove Move Up Move Down 2 Enter the electricity rate to use for the dollar saved conversion 0 10 Dollars x Per kWh Save Cancel Green Glancee Configuration
95. s 9 The current area selected is Office Building Second Floor Open Office Areas Open Office North You are viewing ME Office Building Second Floor tS S l oy itch hical View Expand All 4 Lights Shades Collapse All 1 Select an area from the left view to control the Show Area Numbers lights Find area ne S Area Scene Area Level Zone Second Floor The currently active scene is B lopen Office Areas Scene 001 2 Select a new scene open Office South Scene 001 a Conference Rooms Zus E Conference Room 221 W Conference Room 222 8 Werivate Offices E Private office 211 Private Office 212 Private Office 213 Private Office 214 Private Office 215 B Restrooms 2 Mens Restroom Scene Select a Scene z Apply Quickly change area lighting GoToScene1 GoTo Off Scene Configure Scenes Scene Configuration Womens Restroom 5 Elevator Lobby i Kitchen F copy Room l mE Electrical Closet Lights On al Lights Off Logged in User admin Logged in Time Thursday March 24 2011 4 17 12 PM The three sub tabs Control Occupancy and Daylighting use the same basic display which has two options tabular view or graphical view optional Tabular view allows you to select view areas by selecting from a hierarchical area tree as shown To select an area in tabular view simply click the area in the tree on the
96. s should continue to remain at their emergency level after normal power is restored This prevents lights switching on off multiple times when power intermittently goes in and out To configure prolong time select the radio button matching the desired prolong time 48 Quantum Q Acminw UserMaval SO AIL as Manual Tests R Control amp Monitoring i Reports agAdministration gt Control A Occupancy Daylighting Time Clock Hyperion Solar Clock gt Load Shedding 9 The system has detected one or more problems Go To Today P Diagnostics je May 2011 gt The system will update the status of DALI Emergency Units in the grid below based on when functional and duration tests are performed These tests may be scheduled by clicking on the Setup Wizard or by running tests manually I want to View Diagnostics Show Devices with Status s View DALI Emergency Status Bw ok VO Problem Manual Test DALI Emergency Units Setup Expand All To define which Emergency Units Collapse All Choose the type of test to run 0 Ese belong to which test groups and lt x schedule test times click on Setup Device 9 Functional Test Wizard B A Second Floor Hub A functional test will test if emergency units are responding connected to a battery and have property operating lamps tup Wizar BA Office Building Second Floor Electrical Closet Processor Panel Q N Setup Wizard
97. s with status 3 Click Apply se LUTRON a Quantume Q Adminm User Manual 59 Available Reports X Control amp Monitoring Reports _ggAdministration New open View Sensor Connection Report 001 X PR l Save As save amp Print GR Export Sensor Connection Report 001 Sensor Connection Report Report Generated on Wednesday May 04 2011 4 32 42 PM For sensors in the following areas Click here to select Areas Second Floor Hub Office Big Second Floor Open Office Areas Open Office North 001 Address 2 Photo Sensor Not Connected Second Flor Hub Office Bulding Second Floor Open Office Areas Open Ofice Noth 002 Address 3 Infrared Sensor Not Connected Second Floor Hub Office Building Second Floor Open Office Areas Open Office South 001 Address 2 ae Sensor Not Connected Second Floor Hub Office Buiing Second Roor Open Office Areas Open Office South 003 Address 1 Occupancy Not Cor Show Sensor whose Status is ka Unknown 2 Not Connected 7 Not in Database Connected Apply Cancel Sensor Connection Report What sensors are not properly connected This report shows the state of wired sensors occupancy IR and photo as unknown not connected not in database or connected To create a Sensor Connection Report 1 Select one or more areas by using the Click here to select Areas link 2 Select the desired status
98. should be run To define which day of the week each emergency group is to be tested 1 Change the value in the weekday dropdown to choose which day of the week a group is tested 2 Type in a time of day to determine what time a group is tested Choose a day and time when the space is unlikely to be occupied Light levels will be affected during function and duration tests To define how often function and duration tests should be run select the appropriate radio button Function tests can be set to run weekly default every other week monthly or manual only Duration tests can be set to run monthly default quarterly every 6 months annually or manual only If both a function and duration test are scheduled on the same day for a particular test group only the duration test will run as each duration test also performs a functional test A LUTRON a Quantume Q Adminn User Manual 47 DALI Emergency Status Setup gt Configure Prolong Time Step 1 Define Emergency Groups Prolong time is the time emergency units should continue to remain at their emergency level after normal power is restored This prevents lights switching on off multiple times when power intermittently goes in and out Step 2 Setup Test Times x Prolong Time Step 3 Configure Prolong Time None 2 minutes default 5 minutes 15 minutes Half hour Hour 2 hours Step 3 Configure Prolong Time Prolong time is the time emergency unit
99. stration Publish C2 O Admin Lanquage English United States Z 3 LUTRO R Control amp Monitoring j Reports Administration 4 Users Back up Processor Update Wizard Green Glance Configuration Publish Project Files Project Database I want to keep the existing project database I want to publish a new project database Choose a Project Database file lut to publish Transfer to Server C Users sadra Documehts Lutron Quantum Quantum 2 0 25 Des Browse Graphical Floor Plan Select Systems I want to keep the existing graphical floorplan if it exists I want to publish a new graphical floor plan Transfer To System Choose a graphical floor plan file fpb to publish I do not want to use a graphical floorplan This will remove the graphical flooprian from the project The tabular view will still be available but the graphical view will be disabled a C7 HZ7 Publish Project Files Choose a File The Publish screen allows an administrator to publish a project lut file to the lighting control system The project file is created using Q Designm and contains the configuration for a system including lighting zones keypad programming daylight settings occupancy settings nightlight settings etc The user can either republish the current file which will simply perform a full transfer to the system or the user can choose to publish a new file before transferring to the system Note Wh
100. ted to Excel or csv formats and printed To view what devices are currently not responding 1 Make sure the Not Responding checkbox is checked at the top of the screen All other checkboxes can be unchecked to filter the list to only non responding devices 2 Use the diagnostics tree to navigate to which devices are currently Not Responding or click Expand All to show all devices 3 To generate a report that can be printed or saved click on Show Report LUTRON Quantume Q Adminim User Manual 43 Diagnostics Lighting Hubs Devices i OLUTRON QUANTUM i Power panels caa oe SEE SSSSSSSS5 Quantume processor Client Software Server Q Managerm control and monitor server Ns Te Keypads Controls Quantume Processor Interfaces Shades Quantume processor Diagnostics are organized by communications connections to the system in the following hierarchy 1 Manager Server The Q Managerm server runs the Q Adminm software and connects to Quantume hubs These hubs are typically located in equipment closets on each floor of the building 2 Quantume Hubs Quantume hubs contain central processors that connect to lighting control devices on each floor These controls include backroom equipment installed in electrical closets ceilings or floors such as ballast controllers power panels and integration interface equipment
101. tes Server Standalone e Any modern desktop laptop CPU Minimum Pentiume 4 or equivalent e 2 GB RAM e 5 GB free disk space Hardware Prerequisites Client e Any modern desktop laptop CPU Minimum Pentiume 4 or equivalent e 1 GB RAM e 1 GB free disk space Software Prerequisites e 64 bit operating systems are supported in Quantume 2 0 and newer e Supported operating systems Microsofte Windowse XP Microsofte Windowse Vista Microsofte Windowse 7 Microsofte Windowse Server 2003 Microsofte Windowse Server 2008 Microsofte Windowse Server 2008 R2 e The Quantume installer typically named Quantume A B CD exe based on version number will install all software prerequisites as necessary including Microsofte NET Framework 3 5 SP1 Microsofte SQL Servere 2005 Express SP1 Microsofte Visual C e Runtime e The Quantume installer does not require network connectivity Lutron recognizes that lighting is critical to your operations In the event of a lighting disruption you can always contact us Call the number listed below to be connected directly to our Field Service scheduling group Based upon your specific situation our scheduling group will determine the best steps to take to correct the issue Lutron Services Company Service Group 1 800 523 9466 option 2 option 3 option 1 answered 24 7 If you have any questions about additional services that Lutron offers please visit our website at www lutron com
102. the Click here to select Areas link 2 Choose the timeframe by using the dropdown menu on the right 3 Click Apply 54 Quantume Q Adminm User Manual z4 LUTRON o AIL as Available Reports Q Admin Language Enaieh United states lt UI TRON Control amp Monitoring Reports Administration New F Open view 9 Diagnostics Report 2nd Floor March 2011 2nd Floor Area Comparison Lighting Power Usage Report 022 X Pr H Save as H Save print Gy export Lighting Power Usage Report 022 Lighting Power Usage Report Report Generated on Wednesday April 20 2011 3 41 45 PM Graphical view Tabular view How does the power usage of Click here to select Areas 540 No Areas Z 450 1 Second Floor Open Office Areas 2 Office Building Second Floor Open Office Areas 360 gt 3 Office Building Second Floor Conference Rooms 270 compare over men Last 7 days so o Z I L z I L 2 a a amp a amp a amp a amp a a a amp e g e e s S e e e S e e e e e e e S g e e S e e e g e g 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 D E a E a 2 a E 2 a E a a E a 2 a E a 2 a E a 2 2 4 13 4 14 4 15 4 16 4 17 4 18 4 19 E Office Building Second Floor Open Office Areas Open Office South Office Building Second Floor Open Office Areas Open Office North E Office Building Second Floor
103. time when the lights would normally turn off An example of this is found in most office buildings If the lights were originally programmed to turn off at 6 00 p m anyone staying past that time would be in the dark when the lights turn off Automatic shutoff can be distracting and potentially dangerous if the occupants in a space are unexpectedly left in the dark Additionally lights could be left on all night if the occupants manually turn them back on and then forget to turn them off when they leave When the lighting control system has an After Hours mode the situation is quite different Wall controls installed throughout the space allow local control of the lights all day At 6 00 p m the system time clock automatically triggers After Hours mode The lights perform a blink warn sequence to tell the occupants that the system is about to turn the lights off and the off delay timer starts If the user operates one of the wall controls to indicate continued presence the lights will go to the requested level the warning time will reset and the sequence will restart If the off delay expires without a user operating one of the wall controls the lights turn off Operating a wall control after the lights turn off will bring the lights back on and restart the warning time The possible After Hours states are occupied unoccupied disabled and inactive If the state is disabled then After Hours events are not processed After Hours is usually trig
104. ting Time Clock TESTER oad shedding Diagnostics o Hyperion Wizard S ervie efaults C z Step 1 Overview and Defaults S with Shades Facing Direction Step 2 Facing Directions 8 Office Building u f B Step 3 Window Types 8 Open Office Areas Step 4 Area Setup 4 Open Office North North Facing S Open Office South South Facing Step 5 Nighttime Settings Step 6 Override Settings Selected Area Office Building Second Floor Open Office Areas Open Office North Hide Details Shade Group Window Type l Facing Direction L Visor Position L Affected by Hyperion Sunscreen Window Type 1 North Facing 100 d Use the default Hyperion settings Customize the Hyperion settings for this area Work Surface Height in 40 Min Time Between Movements min 60 Max Sunlight Penetration in co lt Back Next gt Save and Close Wizard Logged in Time Thursday March 24 2011 5 50 48 PM _ Hyperion Wizard Step 4 Area Setup For each area controlled by Hyperionm choose the appropriate Facing Direction For areas with multiple fa ades e g a corner office you can select a different facing direction for each shade group For each shade group select the window type covered by the shades Additionally a visor position can be set for each shade group The visor position is the maximum open position shades should move to during th
105. ting in this area is currently Gite Office 212 n Disabled Private Office 213 LU Private Office 214 Private Office 215 C Click on the button below to enable daylightinc 2 0 Restrooms m ee this area Z Mens Restroom a al Womens Restroom Enable Daylighting Elevator Lobby S Kitchen S Copy Room Z Electrical Closet View Daylighting Status Adjust the Daylighting Target Set Point Select an area from the left Thumbnail 4 m Segen Logged in User admin Logged in Time Tuesday April 19 2011 5 14 12 PM The Daylighting screen allows a building manager to control and monitor daylighting for areas Daylighting is a feature in which the system changes the level of electric lights based on the amount of daylight present Regardless of how much daylight is coming in daylighting works to maintain a constant level of total light in a space This total light is expressed as the daylighting target set point which represents the maximum level the electric lights will achieve when no daylight is present Electric lights will dim down from this target set point when daylight is present Quantume also supports switched daylighting in which an area is configured with a minimum light level Once total light falls below the minimum light level the system will switch on the electric lights An area can either use dimmed daylighting or switched daylighting The
106. trol amp Monitoring Reports 3QAdministration Fer Back up Publish Processor Update Wizard Green Glance Configuration 9 The current user selected is Joe Joe User User Accounts gt First Name User Profile 1 Select a user account on the left to view edit profile details Kelly Smith Admin Active Dan Smith Regular Active Login Id oe Roger Jackson Regular Inactive First Name Joe Last Name User Role Admin Control and Configuration F Ask for password change at next login Y User account active Reset account password Save Changes Add Delete To delete a user 1 Select an existing user in the grid 2 Click Delete To modify a user Select an existing user in the grid Fill in the text fields on the right First Name and Last Name are optional Select the user s role Click Reset account password Enter and confirm the desired password If desired check Ask for password change at next login Click Save Changes NOOR WON To inactivate a user 1 Select an existing user in the grid 2 Uncheck User account active 3 Click Save Changes A LUTRON a Quantume Q Adminm User Manual 63 Administration Users x Lanausae Enaish Unted Stes 3 4 LUTRO X Control amp Monitoring Reports _ggAdministration 2 Users Back up Publish Processor Update Wizar
107. trol amp Monitoring Reports _ 3Administration New open H A view e Lighting Power Usage Report 022 x Lighting Power Trend Comparison Report 008 Lamp Maintenance Report 013 System Activity Report 036 Diagnostics Report 014 X 4 Y P lH Save as d Save Print Gy export Diagnostics Report 014 Diagnostics Report Report Generated on Wednesday April 20 2011 3 52 08 PM For devices in the following areas Type Status System Device Name Offices 1214 Private 14 Cc 0661 Floc Pivate Offices 121A Private Office 214 KITCHEN DOOR Serial 00300439A QS Keypad Q5 2Button Walstaton insert Unknown i ER ane Cafe Areas Office Building Second Floor Private Offices Private Offic Show devices with status 9 Unknown 7 Not Responding 7 Not in Database sooty Be Logged in User admin Logged in Time Wednesday April 20 2011 3 29 06 PM Diagnostics Report What devices are currently not responding and need attention The Diagnostics Report displays the same information found in the Diagnostics screen Devices e g keypads shades power panels are listed with their current status unknown not responding not in database or OK To create a Diagnostics Report 1 Select one or more areas by using the Click here to select Areas link 2 Select the desired status types to show by clicking the checkboxes under Show device
108. types to show by clicking the checkboxes under Show Sensor whose Status is 3 Click Apply 60 Quantums Q Admin User Manual 7 sLUTRON AIL as Available Reports x oj ms X Control amp Monitoring Reports 3gAdministration I New Open e Emergency Units Report 001 X 4 id Save As Save amp Print Export Emergency Units Report 001 Emergency Units Report Report Generated on Friday April 29 2011 4 43 06 PM For devices in the following areas Date of Last Function Test Date of Last Duration Test Status Both Tests Past Due i q Both Tests Past Due Click here to select Areas Second Floor Hub Office Building Second Floor Conference Rooms Conference Room Both Tests Past Due Second Foor Hub Office Building Second oor Open Office Areas Open Office Noth Both Tests Past Due Show devices with status Problem E U Apply en DALI Emergency Units Report The DALI Emergency Units Report allows the user to view export and print the status of DALI emergency units To create a DALI Emergency Units Report 1 Select one or more areas by using the Click here to select Areas link 2 Select the desired status types to show by clicking the checkboxes under Show devices with status 3 Click Apply A LUTRON a Quantume Q Adminm User Manual 61 Administration Users oO x TRO BA Language Engl
109. ume Q Adminm User Manual 33 Hyperionm Solar Clock X Control amp Monitoring Reports gAdministration Control A Occupancy gt Daylighting Time Clock ar Clock gt Load Shedding Diagnostics e Area Office Building Second Floor Open Office Areas Open Office North Enabled aa lt May 2011 gt Expand All View settings 5 iM 22 wo FS Collapse All m 2 BA SF 6 7 Setup Hyperion 10 5 35 AM 17 24 31 Hyperion Event 1 H Sunscreen Test Hyperion Events 5 Hyperion Event 2 Enable Disable Hyperion 6 35 AM Sunscreen 31 Hyperion Event 3 7 35 AM N CO VY rk _ _ w wens lt S Sunscreen 88 Hyperion Event 4 J Review Location Settings Testing Hyperion events allows you to simulate the selected Hyperion event right now to confirm that it controls the correct shade group s in the expected manner 8 35 AM Sunscreen 100 Hyperion Event 5 5 35 PM Select the desired Hyperion event at left and click on Test Hyperion Event Sunscreen Hyperion Event 6 6 35 PM Test Hyperion Event Sunscreen Logged in User admin Logged in Time Thursday March 24 2011 5 50 48 PM To view Hyperion Schedules 1 Select View settings on the right side of the Hyperionm screen 2 Select an area in the area dropdown 3 Select a day from the calendar on the left by defau
Download Pdf Manuals
Related Search
Related Contents
取扱説明書 MANUALE UTENTE HAMMER VENTANO XTR User Manual opticodec L`Express styles MANUAL DE INSTRUCCIONES 取扱説明書 - 岩谷産業 Nanolithography Support Note Fujitsu LIFEBOOK T901 Copyright © All rights reserved.