NETWORK POWER MONITOR R9 / NPM-R9

image

Contents

1. Add your Primary DNS address Add your Primary SMTP address Add your email address of this server Click Apply and OK Go to Notifications in the left tree menu Select email by double click or add email if not present In the email window add your To email address and click test If successful OK will appear in the bottom of the email window Right click on the NPM icon on the local map monitoring screen Go to services Double click on the service you would like to receive an email from Tick enable use notifications and select email in the list Click apply Also double check Right click NPM icon go to settings under Polling tab make sure use notifications an email is selected SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 10 TFTP Boot loader NPM R9 supports TFTP Boot loader for upgrading device software remotely over a network The MAC address of the unit is hard coded into software for safety reasons so first obtain a hex file from us for the specific unit Send e mail to info microinstruments co za state serial number of unit displayed on home page via web browser and the type of unit eg NPM R8 and the fault detected in software or why you need the software modified We will then send you a hex file with the appropriate MAC address to be uploaded Simply download the Mi TFTP file up loader from our website The Mi TFTP file up loader automatically insert the TFTP commands needed
2. Switch 4 ON SMS will include the status of Relay 4 and Relay 5 if on or off Switch 4 OFF SMS will not include Relay status in the message SNMP TFTP GSM NETWORK POWER MONITOR R9 NPM R9 Setup of GSM module Insert a SIM card and install the reset jumper for the first time power the NPM R9 After about 10 sec remove the Reset jumper all number cleared Notice the STATUS led will glow and the NETWORK led will flash at a fast rate After about 8 sec if the unit finds a Network connection the NETWORK led will start to blink slowly Wait about 30 sec before sending an sms Send a text message Save to the units number to save your number as the Primary control number Gsm Relay 27622966215 Fri 13 11 2015 Save O 14 13 The unit will reply with Primary number saved Send a text message Add 2782 secondary number on the system to the unit to save the secondary number g amp A Gsm Relay 27622966215 Fri 13 11 2015 Add 27828711202 O 14 15 Unit replies with Secondary number saved SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 Send a text message Status to enquire the status of the unit Wed 11 11 2015 Status O 10 11 Fri 13 11 2015 R5on O 14 17 e Relay 2 is ON Send a text message R5off to switch R 5 to the off position The unit will reply with a Relay 5 off message Send a text message with R4
3. Ties z Cose Ust Tee Table 4H amp Module fall x od Simple Oid Type Value Modules 1 iso org dod intemet mgmt mib 2 system sys Descr 0 1361211149 octet sting NPM R8 SNMPv2 MIB R 2 180 0rg dod rtemet mgmt mib Z system sysObyect D 0 1 36 1 2 1 1 20 object id 1s0 0rg dod ntemet pnvate erterpnses 4550 1 SNMPV2 MIB R 2 iso org dod intomet mgmt mib 2 aystom ayap Time ayeUp Timelnatance 136121130 timcticko 00 03 42 01 SNMPv2 MIB R 4 iso ora dod intemet mar mib 2 system sysContact 0 1136121140 octet string admin SNMPv2 MIB R E 5 iso org dodintemet mgmt mib 2 system sysName 0 136 121 150 octet sting Micro instruments SNMPv2 MIB R 6 iso org dod intemet mgmt mib 2 system sysLocation 0 136 121 16 0 octet sting Remote SNMPv2 MIB R 7 iso 0rg dod intemet mgmt mib 2 system sysServices 0 1 3 6 1 2 1 1 7 0 integer 7 SNMPv2 MID N 8 isn nrg dad intamet private ertemrises 46501 1110 136141455011110 octet string SNMPv1 2Agert SNMPv2 SMI R 9 iso org dod intemet private ertemprises 45501 1 1 2 0 136141455011120 octet string ve SNMPv2 SMI R 10 iso org dodintemet private enterprises 45501 1 1 3 0 1 3 6 1 4 1 45501 1 1 3 0 octet sting apr 15 SNMPv2 SMI R 11 s0 01g dod sntemet private enterprises 45501 1 2 1 1 1 0 1 3 6 1 4 1 45501 1 2 1 1 1 0 integer 0 SNMPV2 SMI R 12 ieo org dod intemet private enterprieee 45501 1 2 1 1 1 1 1 3 6 1 4 1 45501 1 2 1 1 1 1 integer 1 SNMPv2 SMI R 13 iso org dod intemet private enterprises 45501 1 2 1 1 2 0 1361414
4. add a function Type the Name as NPM_Mains New Function Name INPM soe ok Description Cancel oid 1_ 3 6 1 4 1 45501 1 3 x 0 F Apply Remove Code Copy Notes K Copy and paste the text below as above note the OID is the Mains OID oid 1 3 6 1 4 1 45501 1 3 3 0 Click apply and ok In the right hand side navigation window of the Dude double click Probes Click the sign to add a Probe Under Probes create a new probe SNMP4 TFTP NETWORK POWER MONITOR R9 NPM R9 GSM New Probe L EE Name NPM soo oo Type Function Cancel Agent defaut z ooo Apply A Coy Notes Available oox Eror oox Pae Type the name exactly as the function created earlier NPM_Mains Change Type to Function Agent default Copy and paste the text below one by one and insert Available NPM_Mains Error if NPM_Mains 1 Mians OFF Value NPM_Mains Leave Unit blank Rate minute Click Apply and ok Right click the device icon on the monitoring screen and select Settings Go To services Click the sign to add a service Under Probe select NPM_Mains Select the probe interval and probe timeout time and set the Probe down count to 1 Click apply and ok to exit At this time switching the Mains power off to the unit will result in the monitoring Icon in t
5. device icon on the monitoring screen and select Settings Go To services Click the sign to add a service Under Probe select NPM_Alarm Select the probe interval and probe timeout time and set the Probe down count to 1 Click apply and ok to exit At this time Activating the Alarm input to the unit will result in the monitoring Icon in the Dude to turn Orange and indicate at the top of the icon that it is a active Alarm that occurred NETWORK POWER MONITOR R9 NPM R9 SNMP4 TFTP GSM Add a probe and function to the dude for low Battery Voltage To be notified by the Dude for a change in low Battery status add a function and a probe In the right hand side navigation window of the Dude double click Functions Click the sign to add a function Type the Name as NPM_Volts New Function Name INPM soooc Description oid 1 3 6 1 4 1 45501 1 3 x 0 Remove Copy Notes K Copy and paste the text below as above note the OID is the Battery voltage OID oid 1 3 6 1 4 1 45501 1 3 4 0 Click apply and ok In the right hand side navigation window of the Dude double click Probes Click the sign to add a Probe Under Probes create a new probe New Probe T Name INPM sos oo Type Function Ji an Agent default v aaa Apply Remove Copy Notes Available jooo Error jooo Rate
6. port from the Charge current port If the load to the equipment is coming from the Battery pack then Charge out can be bridged directly to LOAD IN LOAD OUT will go to the main power feed point of your equipment V1 External Vdc input can be used to monitor eg DC DC converters or Solar Panels The external 0 60Vdc input is polarity protected on the board and the customer can wired and for the input in any way The input is protected by a 72V TVS diode for spikes and over voltage The Battery power input and 220Vac Mains input is protected against surge and over voltage SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 4 GSM module and functions ci Meid min The NPM R9 GSM module interfaces to the main board via a 20way ribbon cable and no other connections necessary The 4 way dip switch on the pcb allows the user with the following Switch 1 ON SMS will be send if mains fails and when mains returns Switch1 OFF NO SMS will be send regarding mains status Switch 2 ON SMS will be send if the Alarm input goes open circuit Switch2 OFF NO SMS will be send regarding Alarm status Switch 3 ON SMS will be send if Battery volts falls below a certain level Auto calculating 11 5V for 12v system 23 0V for a 24V system 33 5V for a 36V system and 46 0V for a 48V system Switch 3 OFF NO SMS will be send regarding Battery status
7. to communicate with the target device and is transparent to the user making it easier to use TFTP Run the program Enter the device IP address browse for the hex file location and click on UPLOAD you will be notified upon successful data transfer The unit will re program itself and re boot with the new software and changes Security has been added if the connection is lost while uploading to the unit it will ignore the TFTP session
8. 0 1 3 6 1 4 1 45501 1 3 7 0 SNMPv2 SMI R 27 iso org dod intemet private enterprises 45501 1 3 7 0 0 0 1 3 6 1 4 1 45501 1 3 7 0 0 0 SNMPy2 SMI R 28 iso org dod intemet private enterprises 49901 1 3 U U U 0 1 3 6 1 4 1 49901 1 3 0 U 00 SNMPVZSMI K 25 iso org dod intemet private enterprises 45501 1 3 7 0 0 0 0 0 1 6 1 4 1 45501 1 3 7 0 0 0 0 0 SNMPV2 SMI N 30 isn ong dad intemet private entemrises 45501 137 NO NN NN 136 14145501 1370 ON ANN SNMPv SMI R 31 iso org dodintemet private enterprises 45501 1 3 7 0 0 0 0 0 0 0 1 3 6 1 4 1 45501 1 3 7 0 0 0 0 0 0 0 SNMPy2 SMI R X stopped OID table number of services 10 45501 1 3 1 0 Relay 4 status integer 0 off 1 on 45501 1 3 2 0 Relay 5 status integer 0 off 1 on 45501 1 3 3 0 Mains status integer 0 off 1 on 45501 1 3 4 0 Battery voltage octet string 45501 1 3 5 0 Charge current octet string 45501 1 3 6 0 External Temperature sensor octet string 45501 1 3 7 0 External DC Volts V1 octet string 45501 1 3 8 0 LOAD Current to equipment octet string 45501 1 3 9 0 Alarm status integer 0 off 1 on or active 45501 1 3 10 0 LCD display text string octet string SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 To add a device to the Dude and add all settings In the top screen Click on and click on device to add a device enter the device IP and click next and finish right click on the device icon select appearance i
9. 5501121120 integer 0 SNMPy2 SMI R 14 iso org dod intemet private enterprises 45501 1 2 1 1 2 1 1 3 6 1 4 1 45501 1 2 1 1 2 1 integer 0 SNMPv2 SMI R 15 iso org dod intemet private enterprises 455U1 1 2 1 1 3 0 1 3 6 1 4 1 49001 1 2 1 1 3 0 ip address 0 0 0 0 SNMPVZSMI K 16 is0 0rg dod intemet private cnterpriscs 45501 1 2 1 1 3 1 1 3 6 1 4 1 45501 1 2 1 1 3 1 ip addreaa 0 0 0 0 SNMPv2 SMI R 17 iso org dod intemet private entemrises 45501 1 2 1 1 4 0 13614145501121140 octet string SNMPv2 SMI R 18 iso org dod intemet private enterprises 45501 1 2 1 1 4 1 1 3 6 1 4 1 45501 1 2 1 1 4 1 octet sting SNMPy2 SMI R 19 iso org dod intemet private enterprises 45501 1 3 1 0 1 3 6 1 4 1 45501 1 3 1 0 integer 0 SNMPy2 SMI R 20 isu org dod irtee private erlenprises 45501 1 3 2 0 1 3 6 1 4 1 45501 1 3 20 ileya 0 SNMPv2 5MI R 21 iso 0rg dod intemet private enterprises 45501 1 3 3 0 1 3 6 1 4 1 45501 1 3 3 0 integer 0 SNMPv2 SMI R 22 iso org dod intemet private enterprises 45501 1 3 4 0 1 3 6 1 4 1 45501 1 3 4 0 octet string 134V SNMPv2 SMI R 23 iso org dod intemet private enterprises 45501 1 3 5 0 1 3 6 1 4 1 45501 1 35 0 octet string 00 04 SNMPy2 SMI R 24 180 0rg dod intemet pnvate enterpnses 4550 1 3 6 0 1 3 6 1 4 1 45501 1 3 6 0 integer 0 SNMPVZSMI R 25 ieo org dod intemet private enterpriese 45501 1 3 7 0 1 3 6 1 4 1 45501 1 3 7 0 octet eting B 13 4 V 1 00 0AMAINS OF T 32 4D SNMPv2 SMI R 26 iso org dod intemet private enterprises 45501 1 3 7 0
10. NETWORK POWER MONITOR R9 NPM R9 s Micro INSTRUMENTS g ELECTRONIC DEVELOPMENT 7 www microinstruments co za L N Tel 012 548 1615 Fax 0866 16 2222 Innovative Electronics for a Changing World INDEX 1 SYSTEM DESCRIPTION 2 BOARD CONNECTIONS terminals and indicators 3 CONNECTION DIAGRAM 4 GSM module and functions 5 START UP GUIDE and passwords 6 HOME PAGE 7 STATUS PAGE 8 RELAY CONTROL PAGE 9 NETWORK CONFIGURATION PAGE 10 SNMP CONFIGURATION PAGE SNMP 11 TFTP Boot loader firmware upgrade via Ethernet MODELS 12 48Vdc 30 Amp charge sense 30 Amp Load sense 12 48Vdc 100 Amp charge sense 30 Amp Load sense SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 1 SYSTEM DESCRIPTION Main Board SNMP4 TFTP NETWORK POWER MONITOR R9 NPM R9 GSM The NPM R9 NETWORK POWER MONITOR R9 was designed to assist Network and Wireless Network specialists with Power related information via Ethernet and GSM Communication Battery Voltage Charging Current Load current to equipment Mains 220Vac Status 1x External dc input voltage Alarm input and temperature information is available Embedded Web pages for monitoring and configuration of the system The unit supports the SNMP V1 and SNMP V2C communication platform to be compatible with SNMP monitoring software platforms The NPM R9 is powered by C language firmware and the code was written to function as a co operative RTOS Real t
11. d set the Probe down count to 1 Click apply and ok to exit At this time the Icon will turn orange in case of a Over Temperature situation CREATE the Graphs in the DUDE Right hand top left menu click on Charts Click on the sign to add a chart Give the Chart a name that make sense to the user Click on the sign below to add services to the Dude Select source in the window that have opened and select for instance the NPM_Volts NPM as the source Click on apply and ok If you get a Error message Unknown type then please close the window to return to the previous window of Charts and Remove the Chart you will be prompted with Remove this Chart Yes or No Click yes to remove it then click on the undo button top left corner of the dude screen to undo the Chart delete you can now go back to the Chart and add the required data sources for Graphing to it x This isa Dude problem with V 3 6 After all chart data sources was added like NPM_Volts NPM and NPM_Amps NPM the graphing of your voltage and charge current etc will start You can add the temperature mains status whatever you want to the graph The scaling of the graphs might appear wrongly between a scale of 0 to 1 after about 20min the graphing will be scaled between data received from unit SNMP TFTP GSM NETWORK POWER MONITOR R9 NPM R9 SETTING UP EMAIL NOTIFICATIONS IN THE DUDE Top left on screen click on SETTINGS
12. d will return to its off position after 10 sec 3 0f__v 2 1 0f__vV Copyright 2015 Micro Instruments Relay 5 and 4 can be controlled to the on off status and will keep their positions Relay 3 to 1 can only be toggled for 10 second periods and is typically used to reset radios or routers without logging yourself out completely from the remote site after a relay was accidently switched relay 3 to 1 will return automatically after 10 seconds to the off position relay not powered NETWORK POWER MONITOR R9 NPM R9 NE TEE GSM 8 NETWORK CONFIGURATION PAGE OE titp192 168 12 protet contightm P O E Network PowerMonitorrs x alle Micro instruments Network Power Monitor R8 a Home Page Board Configuration Status n i 7 j This page allows the configuration of the board s network settings Relay Control CAUTION Incorrect settings may cause the board to lose network Network connectivity Configuration Enter the new settings for the board below SNMP Configuration MAC Address 00 19 F6 00 1A 1F Host Name NPM R8 Mi Enable DHCP IP Address 192 168 1 2 Gateway 192 168 1 1 Subnet Mask 255 255 255 0 Primary DNS 192 168 1 1 Secondary DNS 0000 Save Config Copyright 2015 Micro Instruments Admin and microi gains access MAC address is displayed and cannot be changed Setup IP address Gateway and Subnet Mask Prima
13. f you want the SNMP agent to respond ate ate ME to the NMS SNMP manager with different read and write community names Network If less than three communities are needed leave extra fields blank to disable Configuration them SNMP Configuration Read Comm1 public Read Comm read Read Comm3 Write Comm1 private Write Comm2 write Write Comm3 public Save Config Copyright 2015 Micro Instruments Admin and microi gains access Configure read and write communities Write communities is functional on the device via SNMP SET and GET functions but is beyond the scope of this user manual as the relay s can also be controlled via the relay control page SNMP4 TFTP NETWORK POWER MONITOR R9 NPM R9 GSM SNMP screenshot from the dude freeware SNMP manager amp admin localhost The Dude 3 6 Preferences Local Server Help Settings aI EMS levices Functions goon DOW cere F works SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 SNMP V2c SNMP walk screenshot X r Bl Re Settings Discover Toos AA er Layer inks amp Snmp Walk 192 168 1 2 Frm server afle Ilan Od as Sat lo 192 168 1 2 v Timeout 3000 ms Sop Profile v2 pubic vlle seel
14. he Dude to turn Orange and indicate at the top of the icon that it is a Mains failure that occurred SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 Add a probe and function to the dude for ALARM failure To be notified by the Dude for a change in alarm status add a function and a probe In the right hand side navigation window of the Dude double click Functions Click the sign to add a function Type the Name as NPM_Alarm New Function Name INPM sooo Description Cancel oid 1 3 6 1 4 1 45501 1 3 x 0 F Apply Remove Code 1 Copy Notes K Copy and paste the text below as above note the OID is the ALARM OID oid 1 3 6 1 4 1 45501 1 3 9 0 Click apply and ok In the right hand side navigation window of the Dude double click Probes Click the sign to add a Probe Under Probes create a new probe New Probe EER Se Name INPM ox Ok Type Function Zz Cancel Agent defauk ET Apply Remove Copy Notes Type the name exactly as the function created earlier NPM Alarm SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 Change Type to Function Agent default Copy and paste the text below one by one and insert Available NPM_Alarm Error if NPM_Alarm 0 Alarm OFF Value NPM_Alarm Leave Unit blank Rate minute Click Apply and ok Right click the
15. ht hand side navigation window of the Dude double click Functions Click the sign to add a function Type the Name as NPM_Temp New Function Name NPM e Description Cancel oid 1 3 6 1 4 1 45501 1 3 x 0 i Apply Remove Code Copy x Notes K Copy and paste the text below as above note the OID is the Temperature OID oid 1 3 6 1 4 1 45501 1 3 6 0 SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 In the right hand side navigation window of the Dude double click Probes Click the sign to add a Probe Under Probes create a new probe New Probe l bE Name NPM zox Type Function a Cancel Agent defaut v vaal Apply Remove Copy Notes Available joox Type the name exactly as the function created earlier NPM Temp Change Type to Function Agent default Copy and paste the text below one by one and insert Available NPM_Temp Error if NPM_Temp lt 40 0 Over Temp CURRENTLY SET AT 40 deg C you can change the value Value NPM_Temp Leave Unit blank Rate minute Click Apply and ok Right click the device icon on the monitoring screen and select Settings Go To services SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 Click the sign to add a service Under Probe select NPM_Temp Select the probe interval and probe timeout time an
16. if all connected A reflection of the module s LCD display is captured and displayed on this page Battery voltage charge current Mains status on or off and the Load current SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 7 RELAY CONTROL PAGE O DE hp 1921681 2 indexhtm P X waiting for1921681 2 Micro Instruments NPM RS smd v5 36 Version Module Heartbeat p May 14 2015 serial Mi Build Date goor Model 12 48Vdc 30Amp Inputs AAVY Battery Voltage 15 3 V Windows Security server 192 168 1 2 is asking for your user name and password The rts that it is from Protected d password will be sent using basic tion that isn t secure asswort Remember my credentials cancel Admin and microi gains access Ar Oden 192 168 1 2 forms htm 2 G Network Power Monitor R8 gt Micro instruments Relay Control Page B This Page application controlls the external relay board if present Relay 1 to 3 Selecting Toggle will activate the specified relay for 10 secconds and then return the relay to the off position Relay 4 to 5 Control Relay via on off command You can go back to the Home Page to view the Relay status indicated by the Green dot Relay 5 and 6 can be controlled via on off commands and will keep its position 5 0f v 4 Off v Save Relay 3 2 1 can only be toggled an
17. ime operating system 2 BOARD CONNECTIONS GSM Module Reset jumper i i Raay Board PORT 0 60VDC EXTERNAL IN EXTERNAL TEMP Toload ALARM c harger N C Charger 12V 24V 36V 48V Factory Reset jumper insert jumper power up and wait until green led top left corner of Main board flash once External Temperature sensor can be extended with 3 wires Alarm input potential free contact only NETWORK POWER MONITOR R9 NPM R9 3 CONNECTION DIAGRAM of series parallel Batteries oTe Tee eae oker pan iA eri Battery and Charger connection Connect GND of the Battery system to the left hand side terminal marked GND The system will operate from 12 24 36 or 48V battery voltages Connect the first battery 12v of the pack to Terminal B1 Connect the second Battery 24v to Terminal B2 Connect the Third battery 36v of the pack to Terminal B3 Connect the Fourth Battery 48v to Terminal B4 Connect The Charger to the Charge terminal marked Charger IN Connect the terminal marked Charger out to your batteries SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 3 CONNECTION DIAGRAM GSM Module PORT Reset jumper STO Relay Board PORT 0 60VDC EXTERNAL IN EXTERNAL TEMP 220VAC INPUT Charger To BATT To Load The current feed through for LOAD current is a totally isolated current
18. is the Charge current OID oid 1 3 6 1 4 1 45501 1 3 5 0 Click apply and ok In the right hand side navigation window of the Dude double click Probes Click the sign to add a Probe Under Probes create a new probe fi New Probe 2 se Name NPM Type Function x Cancel Agent defaut e ees Apply Remove Notes Available poo Error joox Value ooo Unit Rate TEEN Type the name exactly as the function created earlier NPM_Amps Change Type to Function Agent default Copy and paste the text below one by one and insert Available NPM_Amps SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 Error if NPM_Amps Value NPM_Amps Leave Unit blank Rate minute Click Apply and ok Right click the device icon on the monitoring screen and select Settings Go To services Click the sign to add a service Under Probe select NPM_Amps Select the probe interval and probe timeout time and set the Probe down count to 1 Click apply and ok to exit At this time we don t have an alarm on charge current but no it will Graph the charge data in your graph it is possible to add a charge alarm follow the low battery voltage alarm setup for the Charge amps to do create an alarm Add a probe and function to the dude for Over Temperature To be notified by the DUDE of a Over temperature alarm In the rig
19. ll be display where after the current TCPIP stack version will be displayed 192 168 1 2 will appear on the LCD as the default IP address Connect to the IP address via a web browser Tested Google Chrome and Internet Explorer to access the web pages To Factory reset the unit install the jumper provided over both pins behind the LCD display power the unit Display will show model number etc and then go blank notice the run led close to the jumper J9 will give one flash as soon as the board is restored to factory settings Cycle the power to the board to initiate a restart Micro Instruments registered private enterprise number PEN 45501 To login to the Relay control page Network settings or SNMP configuration pages the following passwords must be used admin microi SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 5 HOME PAGE rs lt e P Micro instruments NPM R9 Relay s 5 1 Stack Et v5 36 Relay Control Version Module Heartbeat Nov 13 2015 serial Mi Build Date a Network z 00003 Configuration Charge Inputs sense MAP KAW Y SNMP Configuration Load sense 30Amp Battery Voltage 51 12V The Stack version is displayed the build date of the firmware programmed on to the device the units serial number as well as the model number Charge sense and Load sense maximum Amps the unit can measure is also displayed a 100Amp charge and 30Amp Load model is also available A visual i
20. n the drop down menu double click in the Label window and copy and paste the code below to the label window Device Name device_performance Device ServicesDown copy it in below the above text that appears automatically MAINS oid 1 3 6 1 4 1 45501 1 3 3 0 BATT oid 1 3 6 1 4 1 45501 1 3 4 0 Charge i oid 1 3 6 1 4 1 45501 1 3 5 0 Relay4 oid 1 3 6 1 4 1 45501 1 3 1 0 Relay5 oid 1 3 6 1 4 1 45501 1 3 2 0 Temp oid 1 3 6 1 4 1 45501 1 3 6 0 EXTV1 oid 1 3 6 1 4 1 45501 1 3 7 0 LOAD i oid 1 3 6 1 4 1 45501 1 3 8 0 Alarm oid 1 3 6 1 4 1 45501 1 3 9 0 Select label refresh value to 5 or 10sec Click on arrow next to up green partially down orange and down Red to display colours Click apply and OK Right click the new created icon again and select settings Give a Name to the unit that makes sense to the user and select SNMP profile as V2 public SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 Go to polling and select your probe interval and Probe timeout time Click on apply Under services click the sign Under Probe select ping and apply and ok At this time the Icon for the device should be Green and indicating all values Add a probe and function to the dude for Mains failure To be notified by the Dude for a change in mains status or alarm add a function and a probe In the right hand side navigation window of the Dude double click Functions Click the sign to
21. ndication of the status of Relays 5 to 1 is given and indicated by a green dot if the relay is active powered A module heartbeat indication by a green dot flashes once per second as the software runs through the TCPIP applications Only inputs 1 and 2 is functional and indicated by a for inactive and V for active inputs 3 and 4 is for future expansion AJAX Battery voltage measurements is displayed for quick information regarding battery voltage Left hand menu will navigate to different applications on the unit NETWORK POWER MONITOR R9 NPM R9 SNMP4 TFTP GSM 6 STATUS PAGE p e O Micro Instruments Home Page STATUS build date of the HEX file programmed and serial number Relay Control w i Nov 1 015 serial Mi Network a External Temperature sensor in Degrees Celcius 25 2D Configuration External Voltage 1 input Battery 1 Volts 12V Battery 2 Volts 24V Battery 3 Volts 36V Battery 4 Volts 48V ie IN Current LCD Display image B Battery Voltage I Charge Current to Battery i Load Current to Equipment Mains 220Vac input Status on off Load current reading will be replaced with ALARM if active Manufacturing date and serial number is displayed External temperature sensor is displayed in degrees Celsius External Voltage input V1 is displayed as 0 to 60Vdc Battery 1 to 4 Voltages is given separately from each other
22. on to switch Relay 4 to on position Send a text message R4off to switch R 4 to the off position The unit will reply with a Relay 4 off message Only Relay 4 and 5 can be switched to stay in the on or off position Relay 1 2 and 3 is for reset purposes only SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 Send a text message R1 to reset relay 1 Gsm Relay Fri 13 11 2015 jo 14 19 n Reset Relay 1 ok Relay 1 will energize and after 10sec the relay will de energize Follow the same procedure for Relay 2 and Relay 3 with R2 and R3 Should the LOW Battery function be enabled on the GSM dip switch an automatic Battery low sms will be send as soon as the Batteries fall below a certain level Gsm Relay Fri 13 11 2015 ev Battery below 11 5V SMS will also be send at 34 5V for a 36V system and at 46 0V for a 48V Battery system SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 Use the Erase text message from the original number to remove the primary number and send save from the new primary number to the unit Use the Wipe text message to remove the secondary number and send add 27 for the new secondary number to the unit if needed SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 5 START UP By default the unit is shipped with a default IP address of 192 168 1 2 Micro Instruments Network Power Monitor R9 wi
23. ry DNS and Secondary DNS is not functional and is reserved for future use Save Config NETWORK POWER MONITOR R9 NPM R9 EE http 192 168 1 2 protect reboot htrm NPM RE Network Power Monitor R8 a O Micro instruments Reboot In Progress Status A r i Your settings were successfully saved and the board is now rebooting to Relay Control configure itself with the new settings Your board is now located at http NPM R8 Network SERE eni ad ae Reconnection Instructions 1 Did you change the hostname or IP Sometimes it is necessary to clear the address caches in your web browser and OS From the command prompt in Windows enter nbtstat R to clear the hostname cache close your current web browser open a new web browser and then try to access the web address above or IP address 2 the NPM R8 will be up in 5 sec 3 Copyright 2015 Micro Instruments SNMP4 TFTP GSM After the configuration was saved the Reboot in Progress page will load The unit will reboot and configure and should be live in about 5 seconds SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 9 SNMP Configuration O ia http 192 168 1 2 snmp snmpconfig htm v E Network Power Monitor 8 sls Micro Instruments SNMP Community Configuration Stat Read Write Community String configuration for SNMPv2c Agent Relay Control Configure multiple community names i
24. z SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 Type the name exactly as the function created earlier NPM_Volts Change Type to Function Agent default Copy and paste the text below one by one and insert Available NPM_Volts Error if NPM Volts gt 11 5 BATT LOW YOU can change your battery low level in decimal currently at 11 5V Value NPM_Volts Leave Unit blank Rate minute Click Apply and ok Right click the device icon on the monitoring screen and select Settings Go To services Click the sign to add a service Under Probe select NPM_Volts Select the probe interval and probe timeout time and set the Probe down count to 1 Click apply and ok to exit At this time lowering the Battery input voltage to the unit will result in the monitoring Icon in the Dude to turn Orange and indicate at the top of the icon that it is a low battery condition Add a probe and function to the dude for Charge Current To be able to Graph the charge current In the right hand side navigation window of the Dude double click Functions Click the sign to add a function Type the Name as NPM_Charge SNMP4 TFTP GSM NETWORK POWER MONITOR R9 NPM R9 New Function Name INPM 2ococ ok Description Cancel oid 1 3 6 1 4 1 45501 1 3_x 0 a Apply Remove Code Copy Notes K Copy and paste the text below as above note the OID

Download Pdf Manuals