Home

Power Modular Equipment Controller for BACnet Networks

image

Contents

1. expansion to meet application needs All the Power MEC models for BACnet Networks support industry standard BACnet IP networks through a direct connection to 10 100 Base T for ALN communications Power MEC Controller 1200EB In addition to control of the 32 points on the input output point board this controller supports analog and digital point expansion modules which can be mounted remote from the controller This capability expands the point capacity of the Power MEC and provides for cost effective placement of the point terminations close to the load Power MEC Controller 1200EFB The Power MEC EFB version adds three connections to the APOGEE P1 FLN for a total of 96 devices supervised by the Power MEC or it may be configured for a single BACnet MS TP connection supporting up to 96 devices Power MEC Controller 1200ELB The Power MEC ELB version adds LONWORKS compatibility at the FLN It is equipped with a Neuron Microprocessor and FTT 10A Transceiver Instead of three connections to the APOGEE FLN it has a single connection for a LONWORKS network The ELB versions have a LONWORKS network database server embedded This database maintains a dynamic real time representation of the LONWORKS network including connections bindings node status and configuration parameters values Page 2 of 19 Hardware The Power MEC consists of the following major components e Input Output Point Board e
2. R State_Text Yes O Priority_Array Yes O Relinquish_default Yes O Time_Delay Yes Alarm O Notification Class Yes Alarm Yes O Alarm_Values Yes Alarm O Fault_Values Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Notification Class Object Type Property_Identifier Supported Writable Required Optional Object Identifier Yes R Object Name Yes R Object Type Yes R Description Yes Yes O Notification Class Yes R Priority Yes Yes R Ack_Required Yes Yes R Recipient_List Yes Yes R Siemens Industry Inc Page 17 of 19 Page 18 of 19 Schedule Object Type Property_Identifier Supported Writable Required Optional Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Present_Value Yes Yes R Description Yes Yes O Effective Period Yes Yes R Weekly_ Schedule Yes Yes O Exception_Schedule Yes Yes O Schedule_Default Yes Yes R List_Of_Object_Property_References Yes Yes R Priority_For_Writing Yes Yes R Status_Flags Yes R Reliability Yes R Out_Of_Service Yes Yes R Trend Log Object Type Property_Identifier Supported Writable Required Optional Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Description Yes Yes O Log_Enable Yes Yes W Start Time Yes Yes O Sto
3. Yes R Object_Property_Ref Yes R Event_State Yes R Event_Enable Yes Yes R Acked_Transitions Yes R Notification Class Yes Yes R Event_Time_Stamps Yes R File Object Type Property_Identifier Supported Writable Required Optional Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Description Yes O File_Type Yes R File Size Yes Yes R Modification Date Yes R Archive Yes Yes W Read only Yes R File Access Method Yes R Multi state Output Object Type Property Identifier Supported Writable Required Optional Object Identifier Yes R Object Name Yes R Object Type Yes R Present Value Yes Yes Ww Description Yes Yes O Device_Type Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes Yes R Number_Of_ States Yes R State_Text Yes O Siemens Industry Inc Priority_Array Yes R Relinquish_default Yes R Time_Delay Yes Alarm O Notification Class Yes Alarm Yes O Feedback Value Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Multi state Value Object Type Property_Identifier Supported Writable Required Optional Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Present_Value Yes Yes R Description Yes Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes Yes R Number_Of_ States Yes
4. Control Routines The Power MEC provides stand alone Direct Digital Control DDC to deliver precise HVAC control and comprehensive information about system operation The controller receives information from sensors in the building processes the information and directly controls the equipment The following functions are available e Adaptive Control an auto adjusting closed loop control algorithm which provides more efficient adaptive robust fast and stable control than the traditional PID control algorithm It is superior in terms of response time and holding steady state and at minimizing error oscillations and actuator repositioning e Closed Loop Proportional Integral and Derivative PID control e Logical sequencing e Alarm detection and reporting e Reset schedules Built in Energy Management Applications The following applications are programmed in the Power MEC and require simple parameter input for implementation e Automatic Daylight Saving Time switchover e Calendar based scheduling e Duty cycling e Economizer control e Equipment scheduling optimization and sequencing e Event scheduling e Holiday scheduling e Night setback control e Peak Demand Limiting PDL e Start Stop Time Optimization SSTO e Temperature compensated duty cycling e Temporary schedule override Siemens Industry Inc Specifications Dimensions Modular Equipment Controller Analog Point Expansion Modu
5. Power Supply e Controller Board Input Output Point Board The input output point board contains 32 points that perform A D or D A conversion signal processing point command output and communication with the controller board The terminal blocks are removable for easy termination of field wiring The analog input points are selectable to be 0 10V 4 20 mA 1K RTD or optional 100K Thermistor The analog output points are also selectable to be either 0 10V or 4 20 mA The digital inputs are dry contact with four being pulse accumulator inputs The digital outputs support 110 220V Form C rated relays Power Supply The power supply provides regulated power to the input output point board and active sensors The power supply is internal to the Power MEC housing simplifying installation and troubleshooting The power supply works with the controller board to ensure smooth power up and down sequences for the equipment controlled by the I O point board and analog and digital point blocks even through brown out conditions Status LEDs indicate 24 Vac supplied from the power supply and 24 Vdc supplied to the input output point board Controller Board The controller board is a microprocessor based multi tasking platform for program execution and communications with the I O point board and with other Power MECs and field panels over the ALN The Power MEC can also support analog or digital point expansion modules which provide for
6. SIEMENS Technical Specification Sheet Document No 149 203 December 2 2009 Power Modular Equipment Controller for BACnet Networks 00000000 1 9v 9 wed J n D mE 4 Figure 1 Power Modular Equipment Controller Description The Power Modular Equipment Controller MEC for BACnet Networks is an integral part of the APOGEE Automation System The controller is a part of a family of high performance modular Direct Digital Control DDC supervisory equipment controllers It is classified as a BACnet Building Controller B BC and supports BACnet IP and BACnet MS TP protocols The Power MEC operates stand alone or networked to perform complex control monitoring and energy management functions without relying on a higher level processor The Power MEC communicates with other field panels or workstations on a peer to peer Automation Level Network ALN and supports native BACnet IP communications over 10 100 MB Ethernet networks The Power MEC can optionally provide central monitoring and control for distributed Field Level Network FLN devices wired or wireless Siemens Industry Inc Based on the Power MEC part number selected the FLN may support RS 485 for configurable BACnet MS TP or P1 support or LonTalk protocol support Features e BACnet Testing Laboratories BTL certified Classified as BACnet Building Controllers B BC using the BACnet IP protocol and or BACnet MS TP e Sever
7. Your feedback is important to us If you have Document No 149 203 Building Technologies Division comments about this document please send them to Printed in U S A 1000 Deerfield Parkway sbt_technical editor us sbt siemens com Page 7 of 19 Buffalo Grove IL 60089 4513 U S A BACnet Protocol Implementation Conformance Statement Products Product Model Number Protocol Revision Software Revision Firmware Revision Power BACnet Modular 1200 EFB 135 2004 N A 3 2 Equipment Controller 1200 ELB 1200 EB Vendor Information Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 www sbt siemens com Product Description An integral member of the APOGEE product family the Power MEC for BACnet Networks is a high performance modular Direct Digital Control DDC supervisory equipment and primary building controller The Power MEC operates stand alone or networked to perform complex control monitoring and energy management functions without relying on a higher level processor The Power MEC communicates on a 10 100 MB Ethernet BACnet IP network It can optionally provide central monitoring and control for distributed Field Level Network FLN devices BACnet Standardized Device Profile Annex L Supported Device Profile as BACnet Operator Workstation B OWS P uw BACnet Building Controller B BC cre Aeration correa cre ation Spete Corr
8. al versions of controllers to match application requirements e Remote mounted external analog and digital point expansion modules for added point expansion which may be independently operated as FLN devices or directly controlled on an optional point expansion bus e Proven program sequences to match equipment control applications e Built in energy management applications and DDC programs for complete facility management e Comprehensive alarm management historical data trend collection operator control and monitoring functions e Sophisticated Adaptive Control a closed loop control algorithm that auto adjusts to compensate for load seasonal changes e Message control for terminals printers pagers and workstations e Optional Hand Off Auto HOA control switches e Option for compatibility with LONWOoRKS networks e Optional P1 Wireless FLN support Page 1 of 19 HOA CONTROL DIGITAL INPUT SWITCHES CONNECTORS HOA LED 1 DIGITAL OUTPUT T CONNECTORS J oavac POWER CONNECTOR ANALOG OUTPUT CONNECTORS 24VDC SENSOR POWER SHIELD TERMINATION ANALOG INPUT FLN CONNECTORS CONNECTORS 3 EXPANSION BUS CONNECTOR EXP ETHERNET PORT MMI PORT STATUS LEDS BATTERY COVER MECO103R1 Figure 2 Power Modular Equipment Controller components and key features The Power Modular Equipment Controller Several styles of controllers provide flexibility and
9. ansitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Analog Output Object Type Property_Identifier Supported Writable Required Optional Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Present_Value Yes Yes Ww Description Yes Yes O Device_Type Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes R Units Yes R Siemens Industry Inc Page 11 of 19 Page 12 of 19 Min_Pres_Value No O Max_Pres_Value No O Resolution Yes O Priority_Array Yes R Relinquish_default Yes R COV_lncrement Yes Yes O Time_Delay Yes Alarm O Notification Class Yes Alarm Yes O High_Limit Yes Alarm Yes O Low_Limit Yes Alarm Yes O Deadband Yes Alarm O Limit_Enable Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Analog Value Object Type Property_Identifier Supported Writable Required Optional Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Present_Value Yes Yes R Description Yes Yes O Status Flags Yes R Event State Yes R Reliability Yes O Out_Of_Service Yes R Units Yes R Priority_Array Yes O Relinquish_default Yes O COV Increment Yes Yes O Time Delay Yes Alarm O Notification Class Yes Alarm Yes O High_Limit Yes Alarm Yes O Low_Limit Ye
10. e AS ENNRK III NNNM o SweSmeieaS Page 8 of 19 Siemens Industry Inc Supported BACnet Interoperability Building Blocks BIBBs Data Sharing Lll ea GRMMMDREMMM Dems eus T Cosas wuswmmweweys C oemws oanstean Cosmea oaase Cosme mswmWwewa oswmws usw ema J esca msmmaea SCHED I B Scheduling Internal B SCHED E B Scheduling External B ib Alarm and Event Management AE N A Alarm and Event Notification A AE N I B Alarm and Event Notification Internal B AE N E B Alarm and Event Notification External B AE ACK A Alarm and Event ACK A LORS AE ACK B Alarm and Event ACK B Ha AE ASUM B Alarm and Event Alarm Summary B AE ESUM A Alarm and Event Enrollment Summary A AE ESUM B Alarm and Event Enrollment Summary B AE INFO A Alarm and Event Information A AE INFO B Alarm and Event Information B rmm Teng Stewre aoa Termes res Toaravewromavoayeo Terseras rms rororo ewe e NetworkManagement O Network Management NM CE A Network Management Connection Establishment A bo 4 Siemens Industry Inc Page 9 of 19 Device Management Device Management O ones bessere OveneoeieSrawa ones Beeren wame oover C 5 5088 bessere omes 5 enccs deve varsosmon Dovescormuneaonconos Lees Deme T erra beeewwwee tee ess fd u
11. fier Yes R Object_Name Yes R Object_Type Yes R Description Yes Yes O Present_Value Yes Yes W In Process Yes R All Writes Successful Yes R Action Yes Yes R Action Text Yes Yes O Device Object Type Property Identifier Supported Writable Required Optional Object_Identifier Yes R Object_Name Yes R Object_Type Yes R System_Status Yes R Vendor_Name Yes R Vendor Identifier Yes R Model Name Yes R Firmware Revision Yes R Application Software Version Yes R Location Yes O Description Yes O Protocol_Version Yes R Protocol_Revision Yes R Protocol Services Supported Yes R Protocol Object Types Supported Yes R Object List Yes R Max APDU Lenght Accepted Yes R Segmentation Supported Yes R Max Segments Supported Yes O Local_Time Yes O Local_Date Yes O Daylight_Savings_Status Yes O APDU_Segment_Timeout Yes O APDU_ Timeout Yes R Number_Of_APDU_Retries Yes R Device_Address_ Binding Yes R Database_Revision Yes R Configuration_Files Yes O Last_Restore_Time Yes O Backup_Failure_Timeout Yes Yes O Active COV Subscriptions Yes O Siemens Industry Inc Page 15 of 19 Page 16 of 19 Event Enrollment Object Type Property_Identifier Supported Writable Required Optional Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Description Yes Yes O Event_Type Yes R Notify_Type Yes Yes R Event_Parameters Yes
12. for MEC Expansion 549 210 or FLN Digital Point Expansion Module 8DI 4DO 24V with HOA for MEC Expansion 549 211 or FLN Accessories Description Product Number HOA Upgrade Kit Analog Point Block 4AI AAO 549 520 HOA Upgrade Kit Digital Point Block 4DI ADO 549 518 HOA Upgrade Kit Digital Point Block 8DI 4DO 549 519 MMI Extension Cable RJ 11 male to female for printers or terminals outside of 545 712 enclosure MMI Cable DB9 female to RJ 11 6 pin for no flow control operator interface 540 143 connections Page 6 of 19 Siemens Industry Inc Service Boxes and Enclosures PX Series Service Box 115V 24 Vac 50 60 Hz 192 VA PXA SB115V192VA PX Series Service Box 115V 24 Vac 50 60 Hz 384 VA PXA SB115V384VA PX Series Service Box 230V 24 Vac 50 60 Hz 192 VA PXA SB230V192VA 19 Enclosure UL Listed NEMA Type 1 Enclosure 34 Enclosure UL Listed NEMA Type 1 Enclosure Documentation Power Modular Equipment Controller Owner s Manual 125 2183 Powers Process Control Language PPCL User s Manual 125 1896 Information in this document is based on specifications believed correct at the time of publication The right is reserved to make changes as design improvements are introduced APOGEE and Insight are registered trademarks of Siemens Industry Inc Other product or company names mentioned herein may be the trademarks of their respective owners 2009 Siemens Industry Inc Siemens Industry Inc
13. gital Point Expansion module 4DI ADO 17 VA 24 Vac Enclosure Type NEMA 1 Ambient Operating Environment 32 F to 120 F 0 C to 49 C 93 RH Non condensing Mounting Surface Building Wall or Structural Member Agency Listings UL 864 UUKL ULC C100 UUKL7 UL 916 PAZX Agency Compliance Siemens Industry Inc FCC Compliance Australian EMC Framework European EMC Directive CE European Low Voltage Directive LVD BACnet Testing Laboratories BTL Certified Page 5 of 19 Ordering Information Controller Range Description Product Number Power MEC 1200EB 8DI 8DO 8AI 8AO point expansion support HOA 549 632 ready BACnet IP ALN Power MEC 1200EFB 8DI 8DO 8Al 8AO point expansion support FLN 549 634 support HOA ready BACnet IP ALN Power MEC 1200ELB 8DI 8DO 8AI 8AO point expansion support 549 636 LONWoRKS network HOA ready BACnet IP ALN Point Expansion Modules Description Product Number Analog Point Expansion Module 4AI AAO 24V HOA ready for MEC 549 214 Expansion or FLN Analog Point Expansion Module 4AI A4AO 24V with HOA for MEC Expansion 549 215 or FLN Digital Point Expansion Module 4DI 4DO 24V HOA ready for MEC Expansion 549 212 or FLN Digital Point Expansion Module 4DI 4DO 24V with HOA for MEC Expansion 549 213 or FLN Analog Point Expansion Module 8AI 24V for MEC Expansion or FLN 549 209 Digital Point Expansion Module 8DI 4DO 24V HOA ready
14. le Digital Point Expansion Module NEMA Type 1 Enclosures 18 Utility Cabinet Enclosure 19 Enclosure 34 Enclosure 11 4 H x 9 5 W x 3 75 D 289 mm x 241 mm x 95 mm 6 H x 9 5 W x 3 75 D 152 mm x 241 mm x 95mm 6 H x 9 5 W x 3 75 D 152 mm x 241mm x 95mm 18 H x 14 W x 6 D 457 2 mm x 356 6 mm x 152 4 mm 19 H x 22 W x 5 75 D 482 6 mm x 558 8 mm x 146 1 mm 34 H x 22 W x 5 75 D 863 6 mm x 558 8 mm x 146 1 mm Processor Motorola MPC 1200EB 1200EFB 1200ELB 860T Processor Clock Speed 48 MHz Memory Size 64 MB RAM 8 MB Flash 72 MB Total Battery Backup of RAM 14 days typical field replaceable AA Alkaline A D Resolution analog in 12 bits D A Resolution analog out 8 bits Local Communication Interface RS 232 port Network Communication Speed Automation Level Network Field Level Network Point Expansion Bus BACnet IP ALN 10 100 Base T P1 FLN or BACnet MS TP FLN 9600 19200 38400 LonWorks FLN 38 4 Kbps 38 4 Kbps Voltage Requirements Service Box 115V Service Box 230V Controller or Expansion Module 115 Vac 15 60 Hz 596 230 Vac 1596 50 60 Hz 5 20 Vac to 30 Vac 47 Hz to 63 Hz Power Consumption Power Modular Equipment Controllers 50 VA Analog Point Expansion module 8Al 17 VA 24 Vac Analog Point Expansion module 4AI AAO 14 VA 24 Vac Digital Point Expansion module 8DI ADO 20 VA 24 Vac Di
15. odules In addition to the points on the input output board the Power MECs support analog and digital Point Expansion Modules The controller can support a maximum of any combination of eight modules They can be mounted next to or remote from the controller depending upon the job requirements The total length of the wiring run for Point Expansion Modules is a maximum of 200 feet 61 meters on the MEC expansion bus Point Expansion Modules are also compatible with the APOGEE P1 FLN Point Expansion Module details are e Analog Point Expansion Module 4Al 4AO e Analog Point Expansion Module 8Al e Digital Point Expansion Module 4DI 4DO e Digital Point Expansion Module 8DI 4DO The analog input points are user selectable to be 0 10V 4 20 mA 1K RTD or optional 100K Thermistor input The analog output points are also user configurable to be 0 10V or 0 20 mA The digital inputs are dry contact with four of the inputs being pulse accumulator points The relayed digital output points support 110 220V Form C relays Figure 4 Analog and Digital Point Expansion Modules Page 3 of 19 Modular Equipment Control with Application Flexibility The Power MECs are high performance controllers with complete flexibility to allow the owner to customize each controller with the exact program for the application In addition each controller can be sized to meet the hardware requirements for the application The control
16. onents The enclosures include a perforated backplane for mounting of the PXC series controllers Power Modular Equipment Controllers Point Expansion Modules or other electronic or pneumatic components Two sizes are available 19 and 34 that can house the Power MEC e 19 enclosure hinged door and key lock e 34 enclosure hinged door and key lock e 18 enclosure pull box type utility cabinet for accessories not for MEC The enclosures are constructed of metal to accommodate secure conduit fittings and protect components against electrical transients The enclosure allows space for easy wire routing and terminations Service Box Service boxes are available for mounting in the 19 or 34 enclosures Models provide step down power from either 115 Vac or 230 Vac to 24 Vac and offer protection against electrical transients The service boxes are sized in various power ratings to provide one or two Class 1 Power Limited terminations for use inside the enclosure to power controllers and I O modules and one Class 2 termination for use outside the enclosure to power remote devices The 115 Vac versions provide two 115 Vac outlets for accessory devices such as modems and laptops Optional sidewall kits are available for service box installation in other NEMA Type 1 or better enclosures such as motor control cabinets Siemens Industry Inc Figure 3 PX Series Enclosure Assemblies Analog and Digital Point Expansion M
17. p_Time Yes Yes O Log_DeviceObjectProperty Yes O Log Interval Yes O Client_COV_Interval Yes O Stop_When_Full Yes Yes R Buffer_Size Yes R Log_Buffer Yes R Record_Count Yes Yes Ww Total_Record_Count Yes R Notification Threshold Yes Alarm Yes O Records Since Notification Yes Alarm O Last_Notify_Record Yes Alarm O Event_State Yes Alarm R Notification Class Yes Alarm Yes O Event Enable Yes Alarm O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Siemens Industry Inc Data Link Layer Options BACnet IP Annex J Foreign Device ANSIKTAEIBN R5485 ARONET Cause pd rae MS TP master Clause 9 baud rate s 9600 bps 19200 bps 38400 bps 76800 bps Segmentation Capability Able to transmit segmented messages Window Size 32 Able to receive segmented messages Window Size 32 Device Address Binding Is Static Device Binding supported Yes Router Clause 6 BACnet IP Annex J to BACnet MS TP Annex H 3 BACnet Tunneling Router over UDP IP Networking Options BACnet IP Broadcast Management Device BBMD Does the BBMD support registrations by Foreign Devices Yes Character Sets Siemens Industry Inc ANSI X3 4 ISO 10646 UCS 2 IBM Microsoft DBCS ISO 10646 ICS 4 ISO 8859 1 JIS C 6226 Page 19 of 19
18. point expansion capability to match the application requirements The controller board scans field data optimizes control parameters and manages operator requests for data An RS 232 operator terminal port with a quick connect phone jack RJ 11 is included with each controller board for operator devices such as a Local User Interface LUI simple CRT terminal laptop PC or printer Siemens Industry Inc The 1200EFB controllers support 3 FLN trunks for communications with a total of 96 FLN devices or one BACnet MS TP trunk supporting up to 96 devices The 1200ELB controllers support 1 FLN trunk for communications with a maximum of 126 LONWORKS devices The program and database information stored in the Power MEC RAM memory is battery backed This eliminates the need for time consuming program and database re entry in the event of an extended power failure When battery replacement is necessary the controller board illuminates a battery low status LED and can send an alarm message to selected printers or terminals The firmware including the operating system is stored in non volatile flash ROM memory Flash ROM is easily upgradeable at the job site This provides for ease of upgrade as new firmware updates are made available Brownout protection and power recovery circuitry protect the controller board from power fluctuations PX Series Enclosure Assemblies PX series enclosures house both electronic and pneumatic comp
19. program for each Power MEC is customized to exactly match the application Proven Powers Process Control Language PPCL a BASIC type programming language provides direct digital control and energy management sequences to control equipment precisely and optimize energy usage Global Information Access Each Power MEC is equipped with one RS 232 operator terminal port This port supports the connection of a Local User Interface LUI simple CRT terminal laptop PC or printer Devices connected to the terminal port gain global information access Multiple Operator Access Multiple operators can access the network simultaneously Multiple operator access ensures that alarms are reported to an alarm printer while an operator accesses information from a local terminal When using the BACnet IP ALN option multiple operators may also access the controller through concurrent Telnet sessions and or local operator terminal ports Menu Prompted English Language Operator Interface The Power MEC has a simple yet powerful menu driven English Language Operator Interface that provides among other things e Point monitoring and display e Point commanding e Historical trend collection and display for multiple points e Event scheduling e Program editing and modification via Powers Process Control Language PPCL e Alarm reporting and acknowledgment e Continual display of dynamic information Page 4 of 19 Built in Direct Digital
20. ra eeewemereTeaMemen 5 NELINNNTIT TIOD TNNT eres Beer mee emos Dese wwe temamtenrs wars Beeren senpesteseS Leurs eee unnm meocos Beeren Ones centen sraon Standard Object Types Supported nome esae Docs wea Craw wee Dwewa wem wee Lowe s omm s wm Deme s Lm LL wwsmoma Trsa Lewes 5 sw s Dmm 1 Page 10 of 19 Siemens Industry Inc Object Attributes O indicates that the property is optional per the BACnet standard R indicates that the property is required to be present and readable using BACnet services Yes indicates that the property is required to be present readable and writable using BACnet services Analog Input Object Type Property_Identifier Supported Writable Required Optional Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Present_Value Yes Yes R Description Yes Yes O Device_Type Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes Yes R Units Yes Yes R Resolution Yes O COV Increment Yes Yes O Time Delay Yes Alarm O Notification Class Yes Alarm Yes O High_Limit Yes Alarm Yes O Low_Limit Yes Alarm Yes O Deadband Yes Alarm O Limit_Enable Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Tr
21. s Alarm Yes O Deadband Yes Alarm O Limit_Enable Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Siemens Industry Inc Binary Input Object Type Property_Identifier Supported Writable Required Optional Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Present_Value Yes Yes R Description Yes Yes O Device_Type Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes Yes R Polarity Yes R Inactive_Text Yes O Active_Text Yes O Elapsed_Active_Time Yes Yes O Time_Of_Active_Time_Reset Yes O Time_Delay Yes Alarm O Notification Class Yes Alarm Yes O Alarm_Value Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Binary Output Object Type Property_Identifier Supported Writable Required Optional Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Present_Value Yes Yes Ww Description Yes Yes O Device_Type Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes R Polarity Yes R Inactive Text Yes O Active_Text Yes O Elapsed_Active_Time Yes Yes O Time_Of_Active_Time_Reset Yes O Priority_Array Yes R Relinquish_default Yes R Siemens Indu
22. stry Inc Page 13 of 19 Time_Delay Yes Alarm O Notification Class Yes Alarm Yes O Feedback_Value Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Binary Value Object Type Property_Identifier Supported Writable Required Optional Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Present_Value Yes Yes R Description Yes Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes R Inactive Text Yes O Active Text Yes O Elapsed_Active_Time Yes Yes O Time_Of_Active_Time_Reset Yes O Priority_Array Yes O Relinquish_default Yes O Time_Delay Yes Alarm O Notification Class Yes Alarm Yes O Alarm_Value Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Calendar Object Type Property_Identifier Supported Writable Required Optional Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Description Yes Yes O Present_Value Yes R Date_List Yes Yes R Page 14 of 19 Siemens Industry Inc Command Object Type Property_Identifier Supported Writable Required Optional Object_Identi