1. using the escape button S to select the position and the up amp down PI buttons to select the numerical value from 01 16 Press enter to confirm and advance Next the correlation between the inputs and outputs must be defined in the program In 01 will be displayed Press I to toggle through the positions and use the GB and FI keys to select the value Press to confirm and advance Ou 01 will display next Again using the escape key S toggle to the appropriate position Use the LB and FI keys to select the value Press enter to confirm and advance Repeat this procedure for each set of Inputs and Outputs up through a maximum of 16 Press the enter key amp to confirm Press laf to advance to the next program step sequence Alarm Set point Programming Up to 4 alarm set points may be configured You may configure each set point using the following parameters in order as shown below LoS f o SONEN maS Minimum set point limit 7 3 in Maximum set point limit GEE j n 3 3 Set point setting www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL H4S wee Hysteresis selection oF Fd ons S Off Delay Value 0 255s ond as On Delay Value 0 255s rij nE nd ij Relay Selection normally energized or de energized arr da eur ddao uPL dol Alarm Type off down up up with latch down with latch uowa fot Fal Pro
2. mor Hn Gren non ai Color of display during alarm red orange green none If none is selected basic display color remains www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL Navigating through this program sequence Minimum Set Point The lowest value below which it is not possible to program a set point ela CHIL When gt is first displayed you have reached the Set point program sequence Press to enter program The first parameter Minimum Set point im oO 4 E m L 13 4 amp Limit will be displayed To skip this step and advance to the next parameter press the enter key Otherwise press the escape key to select the proper numerical position to enter a value Press the up down arrow keys if to select the numerical value for each position When completed press enter to confirm and advance to next programming sequence Maximum Set Point The highest value above which it is not possible to program a set point HS f D afe Maximum Set Point Limit Using the same procedure as above press the escape key l to toggle to the appropriate position Then use the up down arrows E to select the appropriate value for each position Press to confirm your choice and advance to the next programming step Set Point The actual value that must be reached to trigger an output BEE 0 When is displayed press the
3. amp key to toggle to the desired numerical position Use the LA J keys to select the appropriate value for each position Press to confirm and advance to the next parameter in the program sequence www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL Hysteresis The point at which an active alarm output must revert to for the alarm output to turn off Example If an up alarm set point is 10 5 and you want to have the alarm reset at 10 3 then the Hysteresis value to set in the program must be 2 not 10 3 You need not be concerned about whether that value is to be ina positive or negative direction That is automatically configured when you select the Down Alarm or Up Alarm LH 5 i n afe When Hysteresis is displayed use the amp key to toggle to the desired numerical position Using the keys select the value for each position Then press to confirm and advance to the next step Off Delay oFF Lo T A When Off Delay is displayed you may opt to choose a value of 0 255 seconds Use the amp J key to toggle to the desired position and select the correct value with the keys Press enter to confirm and advance to the next step On Delay nd When On Delay is displayed you may opt to choose a value of 0 255 seconds by using the same procedure as Off Delay Ap Relay Configuration The set point alarm relay may be configured as Normally En
4. by toggling the key Changing the value of each digit is accomplished using the GA and I arrows When completed press to confirm this step If the password you entered is not correct you will not be allowed access to program Factory default password is set to 0000 Note Choice of a password value is significant Values from 0000 to 4999 protect direct access to both set points and all other parameters A password value from 5000 to 9000 allow direct access to alarm set points only Negotiating the Programming Menu After password is verified you are in the Programming Mode After approximately 20 seconds the unit will revert to RUN mode if no further entry is made Movement across the flow chart see product carton instruction sheet for BD35 and BD40 to a specific parameter heading is accomplished using the and PJ arrow keys 3Pressing the UP key tabs from left to right across the flow chart Pressing the key tabs from right to left Upon reaching the desired parameter to configure press The display will indicate the current setting for the first sub parameter in this group Each successive amp will scroll through the remaining sub parameters To change a setting press thel or EI keys when a value of a sub parameter is displayed followed by to confirm the change and advance to the next sub parameter www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL P
5. the inside face of the module 2 With the UCABLE now installed on the Input module connect a line cord power source to the power supply module BPH or BPL and power up the meter The display will illuminate 3 Connected the DB9 end of the UCABLE to the serial port on your PC or laptop The display will change It may go completely dark or it may revert to just a single digit being illuminated All this is normal 4 Launch the UDMsoftware Once launched this software may be left open to accommodate the programming of additional UDM meters lf the DB9 is connected prior to power being applied to the meter the unit will not be recognized Programming will be locked out The unit will appear to be dead Follow the sequence above in order to assure reliable communication between the UDM and your PC laptop www sordselectric com
6. use of a digital filter results in higher stability of the displayed value There are two types of filter parameters FPL The firstis and it defines the operating range of the filter Generally Fil S represents the resolution in digits wanted to assign to the display It is suggested to set this parameter to evaluate the amplitude of the fluctuation on the display and use this value as Fil S If for example a display value fluctuates between 2 5 and 3 4 it means that the fluctuation is 9 digits and the Fil S must be set as 9 18 is displayed you may elect to program filter values by pressing the Fit When E key This results in 774 being displayed Using the amp J key toggle to the desired position and select the value to enter by using the keys Press to confirm and advance to the next step in the sequence www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL W Ea irs m The second filter parameter is It represents the filtering coefficient The higher the value of Fil C the smoother the curve of the displayed value There is no theoretical rule to define this parameter but it is suggested to start with the same value of the Fil S coefficient and then increase it until the desired Stability is reached The digital filter affects the values retransmitted via both serial communications and analog output Fill hy 3 rs Once lis displayed u
7. E D msec If all zeros 0000 is selected Auto will be displayed and the value will be automatically calculated from 100ms 999 9 ms Press to confirm Press LS to advance to next program step sequence Cold Junction Compensation CJC Temperature Compensation Available only when TRX input module is installed TRX module with Thermocouple tC requires configuration of Cold Junction Compensation CJC Press GA key to advance to CJC Then to enter www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL i TRX CIC nAuko afn Press key to select Auto Auto Press to confirm Press G to advance to next program step sequence Manual compensation should only be used in special applications Consult factory Configuring the Display diSP UDM85 only UDM 35 BD35 base unit displays may be configured as 3 1 2 digit 1999 or 3 digit dummy zero 9990 When diSP is displayed press G2 Then press keys to make selection Press EJ to confirm Press to advance to next program step sequence Selection of Display Color CoLr UDM40 only UDM40 BD40 base unit offers three display colors When CoLr is visible on the display press G2 Cole E prEd tarAn UurEn Use keys to select RED rEd Orange orAn or Green GrEn Press to confirm Press DB to advance to next program step sequence www sordselectric com Sords E
8. Sords Electric 216 765 4230 CARLO GAVAZZI CARLO GAVAZZI Automation Components UDM 35 40 Digital Panel Meter Programming Guide www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL Index Description 2 Programming Fundamentals 3 Access to Programming Mode Password Protection 4 Programming 5 18 Inputs 5 6 Temperature Compensation 6 7 Display Configuration 7 Scaling the Inputs 8 Decimal Point Position 9 Display Span Configuration 9 Linearization 11 12 Alarm Set Point Configuration 12 16 Digital Filtering 16 17 Analog Output Retransmission of Display Value 17 18 Serial Port Output 18 Fahrenheit Celsius Conversion 19 External Command Function 20 UDMSoft User Guide 21 www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL UDM Description The UDM 35 40 series is a universal Digital Panel Meter that has been developed to meet the most advanced application requirements The UDM 35 offers Quick assembly and maintenance using plug amp play modules Quick amp easy parameter programming and parameter cloning to other UDMs by means of UDMSoft or PC HyperTerminal Powerful variable control by means of up to four 4 alarm outputs Alarms can be up down functions with automatic reset up down with manual reset and down alarm with disable function at power up The UDM 40 offers the same features as the UDM 35 with the foll
9. ct value 2 and press E enter to confirm all choices and advance to the next program sequence HR mes will be displayed Press to toggle to hundreds position and use keys to select 1 Press to toggle to each remaining position and select 0 for each When completed press to confirm and advance to the next program sequence JPE A girl uo a will be displayed Using the keys choose either A for 20mA output full range or U for 10v output In this example the selection would be A Press to confirm Press G to advance to the next program step sequence Serial Port Output When is displayed you may elect to configure a serial port address and Add baud rate Press will be displayed Using the key toggle to the desire position and select the proper value s using the keys Press to confirm r Sigt d B b g A When se is displayed use the keys to select the desired baud rate indicated in kbits sec Press l to confirm Press GA to advance to the next and last program step sequence www sordselectric com Sords Electric 216 765 4230 CONVERTING CELSIUS TO FAHRENHEIT The UDM35 40 digital panel meters use the Celsius temperature scale However the displayed value can easily be scaled to indicate Fahrenheit values by using the following guidelines The LoE and HiE are always expressed as Celsius values To display Fahrenhei
10. ergized or Normally ELY Dn i ind De Energized When is displayed press either or PJ key to make your choice Press to confirm and advance to the next step The configuration of Alarm type allows for selection of OFF or disabled DOWN alarm DOWN alarm with disable at power on UP alarm UP alarm w latch DOWN alarm w latch When the displays shows use the keys to make your choice Press EJ to confirm and advance to the next step in the sequence 14 www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL Configuring the Display Color for Alarm Event UDM40 BD40 only When is displayed the color of the display may be set to be RED ORANGE or GREEN during the alarm event Selecting NONE results in the basic display color being used during alarm event Use the keys to make your selection and press to confirm Press G to advance to the next program step sequence Digital Filtering The digital panel meters are extremely fast to follow the trend of input signals and to display the relevant values Unlike in analog panel meters which tend to filter the input and present a more stable indication the fluctuations in digital panel meters can be quite fast and prevent the user from clearly reading the displayed value Fluctuations can also be introduced when the resolution of the displayed value is higher than the input resolution The
11. le we can divide the curve into 9 segments 9 segments 1 corresponding to the vertical axis The os menu must be activated and the number of linearization points set 10 in this example Then the input output coordinates must be determined and entered into the program In this example going from right to left on drawing Input 1 shown on drawing as 1 0 displayed as in 01 4 Output 1 displayed as ou 01 1 0 Likewise in 02 shown on drawing as 0 9 4 5 ou 02 0 9 Fast forward to in 09 12 ou 09 0 2 and in 10 20 ou 10 0 1 It is important to note that the first and last linearization points must correspond to those points defined in the scale menu In this example in 01 LoE ou 01 Lo d in 10 HIiE ou 10 Hi d Inputs are noted on the X axis and the analog current values along the Y axis Input 1 0 has a value of 4 The second input 0 9 has a value of 4 5 etc 12 141618 20 mA 46 6 10 n Snmax Non linear input www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL Navigating amp Programming within the Linearization Menu ina L in As appears press followed by E and FI keys to choose to E none SHES ignore or enable linearization Press to confirm your choice and advance to next step If you chose YES you will be prompted to 6 a enter the number of Linearization Points
12. lectric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL Scaling the Inputs i When EET is displayed access Is available for configuring the electrical input range the decimal point position and display span as follows Electrical Inout Range HIE and LoE Allows the operator to define an electrical input range different from the standard range setup at the inP programming step As example a UDM with a full scale 20mA 19 99mA setting it is possible to select an electrical input range from 4 00mA Lo E to 19 99mA Hi E by proceeding as follows When EET is displayed press LoE will appear x U lt F134 Using the key toggle to select a digit then press the Lor Pilkey to choose the desired value Using the key repeat as necessary until all digits have proper values Press EJ HIE will now appear y fi lt 2 r mag Using the same procedure as above toggle through the digits using the key and choose the desired values with the Gor PI key Press amp J to confirm and advance to the next parameter Decimal Point Position www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL Decimal Point Position dP The decimal point position is relative to the Display Value which will be discussed next When dP is displayed press Using the GA and keys select the decimal point position and press to confirm and advance to nex
13. owing additional benefits Display color adaptable to Green Red and Amber e Management of non linear signals using the available 16 point linearization capability 6 Alarm status at a glance using a sequence of display colors that can be programmed by the user www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL UDM 35 40 Programming Fundamentals There are no jumpers to consider when programming the UDM 35 40 The programming mode allows the user to define all of the instrument s parameters Shown below are a description and the UDMxx display symbol for each basic parameter grouping Password for access to programming GIER g Input Probe Selection Signal Range current voltage temperature resistance o Cold Junction Compensation aa o Display Selection diSP e Display Color CoLr Scaling of Input Value LALI f o Input Signal Linearization oz Alarm Set Point SP1 SP4 Digital Filtering Analog Output Scaling e Serial Port Configuration ETB o External Command from Input Contact www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL Access to Programming Mode Press and hold amp for 2 seconds Display will indicate password Within 2 seconds four zeros 0000 will be displayed as follow m A This is your prompt to enter your password Each individual digit is selected from left to right
14. rogramming the Input Modules Press and hold amp for 2 seconds Display will indicate PASS password Within 2 seconds four zeros 0000 will be displayed This is your prompt to enter your password If zero 0000 is your password simply press EJ to confirm You have approximately 20 seconds to begin programming before the unit reverts back to run mode To enter a unique password see Access to Programming Mode above Input Selection Press the LB key once to advance to Input When the TRX module is installed you must first indicate probe choice TRX input modules offer three Probe Prob choices thermocouple tc RTD rtd plus resistive rES Use L8 or I keys to make selection e i rid TES kel Press Ea Use keys to select Range r1 r2 r3 r4 r5 r6 according to table below and on instruction sheet Press G2 r H n F Pt100 200 850 C I J 50 760 C Pt100 200 0 200 0 C ros f K 200 1260 C Pt250 200 0 200 0 C F E 200 1000 C_ Pt500 200 0 200 0 C S 50 1750 C Pt1000 200 0 200 0 C i b F T 200 400 C Ni100 60 180 C www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL LSX and HSX input modules offer True RMS trnS or DC measurement dC Use keys to make selection Press G23 LSX HSX tig Erns dt Pressi PJ keys to select Input signal integration time value intt 4 Auko SOG 9999 P
15. se the E key to toggle to the desired position Use the EJ keys to select the value to enter Press Ea to confirm Press to advance to the next program step sequence Analog Output Programming Many times the displayed value must be retransmitted as an analog output The relationship between parameters is as follows Low Display Value gt gt gt gt gt Low Analog Output lod L of g ee H oe rpala a m g a High Display Value gt gt gt gt gt High Analog Output CEP LEPE H la Fj C a i To assure proper coordination and retransmission it is important to note that the parameters are programmed as a percentage of the analog output full scale value 20mA or 10 Vdc according to the TYPE selection see below Therefore to set 4mA as Lo A the correct value to be entered must be 20 20 of the full scale 20mA range The Hi A must be 100 100 20mA Because of this programming technique it is possible to set a reverse slope analog output characteristic www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL Programming example Retransmit a 4 20mA signal proportional to the following displayed values Lo D 0 andHi D 18 When is displayed the Analog Output program may be addressed Press Loh ES to enter sequence aS ig displayed Press to toggle to the first position Use the E keys to select value 0 Press E to toggle to the left to tens position Using keys sele
16. t step Lod and Hid the display span parameters Display Span Lod and Hid Allows the user to define the actual display span in engineering units corresponding to the previously defined electrical input range HIE and LoE The Lod value represents the minimum displayed value Hid represents the maximum displayed value y y fi lt 5 Gf PPE 0 J13 i m s Ej When Lod appears press amp key to toggle to proper digit Use the Land Pikeys to select desired value Repeat procedure until all digits have been set press to confirm and advance to the next step Hid Repeat the same procedure to select and confirm the Hid values Press to confirm Press L to advance to the next program step sequence www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL Linearization Introduction a yond When oe is displayed a signal from a non linear transducer sensor may be modified by setting the input in 01 in 16 and output ou 01 ou 16 linearization points so that the accuracy of the displayed value is maximized This programming step is available when using the UDM40 and LSX HSX input modules only On the illustration below the nominal output characteristics of an analog inductive proximity sensor is 4 20mA Note the non linear curve The nominal characteristics need to be divided into a number of segments In this examp
17. t values manually convert the LoD to a Fahrenheit value and then convert the HiD to a Fahrenheit value Ex LoE is 0 HIE is 100 Manual conversion to Fahrenheit LoD would be 32 F HiD would be 212 F www sordselectric com Sords Electric 216 765 4230 UDM 35 40 PANEL METER USER MANUAL External Command Function When z is displayed the user may elect to dedicate a Command signal contact closure from the input module terminals 6 amp 7 to perform one of the following C1 HOLD Function C2 Disable Keypad C3 Reset latch Alarms Press to select Command sequence Choose either C1 C2 or C3 by using the LA EI keys to make your selection Press to confirm www sordselectric com Sords Electric 216 765 4230 UDMsoft Programming The software is menu driven Just fill in the blanks with your parameters There is little explanation required It is actually a simple process Any confusion and concern that has surfaced has surrounded the issue of setup with the PC laptop The following segment is meant to clarify how to establish solid communication between UDM and PC Do not connect or disconnect either end of the UCABLE when the input signal is connected to the input module This may result in failure of the input module the BD35 40 display and possibly the PC Follow these steps when using UDMsotft 1 With no power connected Plug in the UCABLE to the INPUT module only You will see the connector port on