Home
WM1400 WM1700 Users Manual
Contents
1. In a household situation we suggest that you house your Inverter and other power generating equipment in a purpose built shed sited remotely from the home and as far away as possible from any radio transmitters or receivers Also make sure that the exhaust from your generator or other sources of heat or fumes are kept well away from the WM Inverter Any inverter mounted under a single skin metal roof is unacceptable as condensation may form under the roof and drip onto the inverter You must have a suitable battery bank 12V DC for WM1400 12 and 24VDC for WM1700 24 that is maintained and operated to the battery manufacturer s recommendation To ensure operation to WM specification the battery bank should have a minimum capacity See table 3a Ask your supplier if in doubt Smaller capacity batteries can be used but may result in degraded performance of the WM Inverter under heavy surge conditions Table 3a Suggested minimum battery size WM 1400 WM1700 240Ah 160Ah 3 1 System Diagram gt gt Regulator Regulator 3 2 Installation Example a Main Switch Earth Leakage CB o oTo A _ oo N E a ELCB Protected Circuits WM INVERTER A 3 uses A 7 Both positive and N negative poles of the battery must be fused unless one pole is earthed Consult your sy
2. DS Sense DS Watts 12W Set Parameters LO DC Volts Lo DC Volts 22 0 Set Parameters AC Output VOLTS This display allows you to select whether the keypad audio alarm will sound during an overload or other alarm condition Use the UP or DOWN keys to toggle between ON or OFF state This is set to ON at the factory Demand Start When in STANDBY mode the inverter will require a load of 4 watts or greater to turn on to full 240V power This setting can be adjusted between 4 to 16 watts In most cases the default setting of 4W will be suitable If the inverter remains on continuously increase this value until inverter goes into demand start pulsing mode You may need to try a few different settings to find the most appropriate value for your installation Use the UP or DOWN keys to change this value The WM inverter will cut out and a message will be displayed if the battery voltage falls below this setting for more than 10 seconds The inverter will restart if reset or when the battery volts rise above 24 0V for WM1700 and 11 5V for WM1400 Use the UP or DOWN keys to change the value Default values are 22 0 volts for 24V operation and 11 0 volts for 12V operation AC Volts 240V Allows the AC output voltage to be set in a range of 220V to Set Parameters 240V if an output voltage other than 240V is required Users outside Australia should check with their system designer for the correct setting Use the UP or DOWN keys t
3. If you believe that the load is not excessive check around the Inverter case and heatsink for obstructions to airflow as this will cause the Inverter to heat up much quicker and shut down sooner than normal Also check that the clearances around the WM inverter are as specified in the INSTALLATION section of this manual 6 System Maintenance To get the optimum performance from your WM inverter particularly under heavy appliance loads it is essential that the battery bank and the DC wiring all be in good condition The small amount of time spent on the maintenance tasks below will maximise the reliability of your system A 6 1 WM Inverter Maintenance Periodic maintenance of the WM inverter involves little more than checking for unobstructed operation of the cooling fans which are located on the sides of the inverter Note that cooling air is drawn in through the vents in the side of the inverter Suggested inverter maintenance should include Check for unobstructed fan operation Clear away any dust or foreign matter from the fan grill using a soft bristled brush Do not direct high pressure compressed air at the fan blades Note that the fan is designed to come on during heavy power demand Check between fins of the heatsink Clean out any accumulated foreign objects for example insect nests dust build up etc 6 2 Battery Maintenance IMPORTANT A When worki When working on batteries of such high capacity it is essent
4. 6 SPLECTronic WM1400 12 and WM1700 24 Pure Sine Wave Inverter sevectronic Sine Wave Inverter Serial No Purchase Date Note Your warranty can only be valid once your warranty card is completed and returned to Selectronic Australia Suite 5 20 Fletcher Road Mooroolbark VIC 3138 You will find the warranty card within the packaging Selectronic Australia Pty Ltd WM series Installation and User Manual Doc CS0132_06 TABLE OF CONTENTS Ts INTOUCTON siii a 3 2 Warranty Card aa ae a a ia dial eaei ia 3 3 INSTA AU OM seciieiinisticisedsnvnisedednuatenrandiswnseduntoncarestedeseusddedasansinuatinbedsurestudetoudindandsianeemauidneunnucins 3 3 1 System DIAGN AIM ster ctetet ts ahcat sates of ees eee tase agen cadea reer ee A a Aaa ats as at odie eee 4 32 Installation Example cano tea 4 3 3 System Battery RUSO nac tia 5 SBS is A a Ma she dae tenia Eaa 5 3 9 Connection amp ANG WINN certo Kaaa Te 6 4 Operation iiciin aranana aeieea aeara aoaea aA Eaa li ad ld 7 A Demand Starr ir o ata 7 A ere ae eee 10 5 Fault In Ging isso as 10 6 System Maintenance esis scaatvesscedsnansseawdazearscsnasusiveuscedsaauedenndeaseus saanacacsveuswedwaauinns 12 6 1 WM Inverter Maintenance ooococonnccccnnoccccnonccononocononnncnnnncnnnnncc cnn cnn cnn cnc cancer 12 6 2 BaneryWalintenanCe cp A eed EE E A a EAA Ee EESE 12 7 Radio Frequency Inteerenco atico dns 13 E nenn ernnnernaremnrrr nnne rn aenneren 13 Bel Keypad WIN i e A a ba 14
5. 8 2 Keypad Front Panely oaaae Gots aay ara a aa ves aa anaia Eaa Eara Ena aaa AESA aE 14 8 3 Readings Keypad Grey KeYS luisa id a 14 8 4 Handy lo la e dE 15 8 5 Settings Keypad Light Blue KeyS ooooocconnccononcccnooccconoccccnncccccnoncconanncnnnnccnnnnnc nana 15 SC OPIONS A tree hinisey alee E S ee lea tale ata T 16 Gt AGH OSUCS AA O ER st dette eaa a cenit ae aa hierdie he 17 eHe RY S 002 gio 2 gt een ecm eg ROE ze ie OE TRC AEN ENTE ROP Ce ARO aE 17 9 WM1400 12 WM1 700 24 Electrical Specifications cccsseceseseeeeeeeeeeeseeeeeseeeeeneeees 18 10 Mounting Template i aiiiicccccccasiisiseciscdcsadesseissstecavedtavawitusssecusadenewdsuedcsauadisiaateesbaaducatehousnnes 19 FAA PR CIO anaa a aa aaa aaa aaa iaaa 19 12 Product Warranty and Conditions coomccccncocnnnncnncnanaccnnnnnananenenane cenar nn nera 20 13 Selectronic Authorised Service NetWorK cooocnccononccconncccnnnconanononnnnnnnnennn amen nr nn 21 1 Introduction Thank you for your purchase of a WM Series Selectronic Sine wave inverter Your WM Inverter is a state of the art high performance True Sine Wave DC AC Inverter Many hours of development time have been invested in the WM Series so that we can provide you with a reliable high quality inverter The output from your WM Series inverter is as good as if not better than mains power If looked after properly the WM Inverter will give you many years of reliable service 2 Warranty C
6. P No SA KP 03 from your supplier Serial Port Data Cable Wire Colour Function Pin Number 1 White with green stripe Transmit AS 2 Green Transmit 3 White with orange stripe Receive Seria Pot 4 Blue 15V S 5 White with blue stripe OV OO E 6 Orange Receive hi 7 White with brown stripe 8 Brown 8 1 Keypad Wiring Keypad from rear DOR4ON 8 2 Keypad Front Panel Display not shown for clarity NO0 4200 NO Serial Port RJ45 located on base of the inverter Energy Management MkII Remote Keypad O ALARM INVERTER STATUS TIME BATTERY AC LOAD INPUT READINGS READINGS CONTROL CURRENT SHUNT 1 CURRENT SHUNT 2 CURRENT SHUNT 3 AG SETTINGS OPTIONS lt READINGS Se GENERATOR ae Keypad Grey Keys Keypad Light Blue Keys NOSTICS NEXT UP DOWN lt DISPLAY Keypad Dark Blue Keys 8 3 Readings Keypad Grey Keys The displays provide the following information Press the indicated Keypad Grey Key Battery readings DC Volts 27 4V Readings AC Load readings AC Volts 240V Readings Displays the DC Battery volts This provides you with an indication of the condition of your battery bank This reading gives an indication of the AC voltage produced by the inverter This reading
7. rolls back the demand start setting to 4 Watts Low Volts Adjust LED 5 green FLASHING To avoid total discharging of your battery the WM inverter shuts down at a pre set low voltage As all batteries are different so too is the minimum voltage they should be discharged to The WM inverter will leave the factory with a setting of 22 0 Volts you may change this setting if required Hold the Mode button down until LED 5 is FLASHING indicating you are ready to adjust this setting Now press the Mode button until the desired value is sought LED s 1 4 will return to Status Indication after 10 seconds if a key is not pressed Low Volts Cut out LED 1 LED 2 LED 3 LED 4 20 0 Volts ON 20 2 Volts Slow flash ON 20 4 Volts Medium flash ON 20 6 Volts Fast flash ON 20 8 Volts Fastest flash ON 21 0 Volts ON 21 2 Volts Slow flash ON 21 4 Volts Medium flash ON 21 6 Volts Fast flash ON 21 8 Volts Fastest flash ON 22 0 Volts ON 22 2 Volts Slow flash ON 22 4 Volts Medium flash ON 22 6 Volts Fast flash ON 22 8 Volts Fastest flash ON 23 0 Volts ON After 23 0 Volts the next button press rolls back the Low DC Volts Cut out setting to 20 0 Volts 4 4 Handy Hint It is very important that you become familiar with the functioning of your Inverter Since most Inverters are not within sight it is not always easy to know what STATUS your inverter is
8. suitably trained and qualified personnel should disconnect any DC power connection including battery cell connections and only with suitable procedures and safety precautions The length of cable from the inverter to the battery should not exceed 2 meters in length longer cable runs may result in reduced performance Both positive and negative battery cables should be run together Cables should be no more than 50mm apart Diagram 3 4a Min 500m gt LITLI Battery Bank _ 2m max 3 5 Connection 8 AC Wiring A Before making any wiring connections check that the main DC switch on the front panel is in the OFF position e LEVER DOWN Your electrician should firstly connect the AC wiring via the three terminal junction box Hardwiring to the integral junction box will provide a more reliable long term connection as opposed to plugging in to a power point Carefully observe the correct connections Please refer to the installation diagram 3 4a RATINGS LABEL F JUNCTION BOX SN PS SERIAL Ne Ry Base Panel BROWN ACTIVE red dot right connector GREEN YELLOW EARTH E centre connector BLUE NEUTRAL left connector The lid of the junction box has knockouts to allow conduit entry Make sure this connection is tight and safe Re fit junction box cover NOTE All AC wiring must be carried out by a licensed electrician and must conform to wiri
9. will vary depending on how large a load is connected or if the battery voltage is very low Pressing the AC LOAD READINGS button again will move you to the next AC Amps screen AC Load readings second button press AC Amps 2 5A Readings Other keypad grey keys Not Installed 8 4 Handy Hint The AC Amps reading shows the total current drawn from the AC output by the appliances connected to the inverter This reading is also handy for knowing how much power a particular appliance draws Pressing the AC LOAD READINGS button again will move back to the previous AC Volts screen Pressing any of the keys TIME GENERATOR CONTROL INPUT READINGS CURRENT SHUNT 1 CURRENT SHUNT 2 CURRENT SHUNT 3 will result in this screen being displayed The functions are not available on the WM Inverter To determine the total watts your inverter is supplying multiply the AC Volts x AC Amps l e in the above example 240 x 2 5 600 watts 8 5 Settings Keypad Light Blue Keys Press the Keypad SETTINGS Light Blue Key then the ENTER Dark Blue Key Please note Once the parameters have been successfully entered i e you have stepped right through the set parameters menu then if the inverter is turned off or the DC power is disconnected from the inverter the parameters which have been entered will be saved and held in permanent memory Keypad Buzzer Buzzer ON Set Parameters
10. 1 Total Harmonic Distortion lt 4 Efficiency Input Output Isolation 1 875VAC Operating Temperature 10 C to 50 C Range MECHANICAL Notes The above specifications are based on unity power factor The DC Input is electrically isolated from the AC Output Through a policy of continued development specifications are subject to change without notice 10 Mounting Template i 384 0 Diagram measurments are in mm A 11 Warning THE OUTPUT VOLTAGE FROM AN INVERTER IS JUST AS LETHAL AS GRID POWER Itis necessary for your safety to ensure that all Remote Area Power System installations meet and comply with the relevant provisions and requirements of AS3000 wiring standards and AC wiring is installed by a Registered Electrical Contractor 12 Product Warranty and Conditions These warranty conditions apply to the WM SE and SA range of Inverters for sales within Australia and New Zealand This product is warranted by the manufacturer for a period of 60 months from date of purchase to the original purchaser only The manufacturer will bear the cost of parts and labour to repair any faults found within the terms and period of this warranty Faulty product or parts must be returned to Melbourne Australia at the owner s expense for claim under warranty No allowance is made for the cost of labour or travelling time required to disconnect or reinstall faulty parts Cost of freight to return par
11. ard Before proceeding any further it is extremely important that you complete your warranty card NOW This will enable us to immediately register your 5 year warranty period By accurately completing your warranty card you will provide us with valuable information that will assist us in keeping up with your alternative energy needs Please take a few moments to fill in the warranty card Your efforts will be greatly appreciated 3 Installation The installation of your inverter is extremely important Failure to follow the recommended installation instructions may void your warranty If in doubt ask your supplier installer Installation should only be performed by suitably qualified personnel AC wiring can only be carried out by licensed electricians After unpacking check for any damage that may have occurred during transit Should you observe are any signs of damage contact your supplier immediately The Inverter must be installed in a dry cool well ventilated and dust free environment Please leave at least 300mm clearance around the sides and top of the Inverter and approximately 200mm at the base as this will aid the natural cooling of the Inverter The air vents on the underside of the WM Inverter also need to be kept clear of obstructions 300mm CIN UU NL UL LLL LLO Minimum Wall WH 300mm SELECTRONIC SINE WAVE INVERTER
12. facturer If service is required please contact your installer or retailer before taking any further action 13 Selectronic Authorised Service Network Australian Repair Centres Selectronic Australia Suite 5 20 Fletcher Road Mooroolbark Victoria 3138 Australia Ph 61 39727 6600 Fax 61 3 9727 6601 www selectronic com au service selectronic com au Solar Inverters Rainbow Power Company 30 Ospery Drive 1a Alternative Way Urunga Nimbin NSW 2455 NSW 2480 Australia Australia Ph 61 2 6655 3930 Ph 61 2 6689 1430 www solarinverters com au www rpc com au New Zealand Repair Centre Power Technology 295 Lincoln Road Henderson Waitakere City New Zealand Ph 64 9 836 6744 www powertech co nz 6 SPLECTronic Suite 5 20 Fletcher Road Mooroolbark Victoria 3138 Australia Phone 61 3 9727 6600 Fax 61 3 9727 6601 Web www selectronic com au Email sales selectronic com au 003619
13. ial that you wear protective clothing some form of eye protection and rubber soled work boots Please regard your batteries with a great deal of caution and if in any doubt entrust this work to your installer Visual inspection Every week carry out a thorough visual inspection of all battery wiring taking particular note of the condition of inter connections between cells Check Bolts Check that the stainless steel inter connecting bolts are tight and have minimal corrosion If corrosion is evident carefully follow the following procedure a Disconnect the system battery fuse before working on the battery bank b Unbolt the stainless steel bolts and nuts of any corroded connections and thoroughly clean the joint with a wire brush or file taking extreme care not to short circuit any battery cells with any tools c Re assemble and smear a small amount of Vaseline or similar grease over the surface of the joint to slow down any future corrosion Specific Gravity for flooded batteries only Every month or as directed in your battery instruction manual measure the specific gravity SG of each cell using your hydrometer to ensure that all cells are performing correctly Any serious imbalance should be reported to your system designer in case remedial action needs to be taken 7 Radio Frequency Interference Radio Frequency Interference RFI can be a problem for owners of inverters RFI in a domestic situation may produce noi
14. in An easy way to determine this is to plug a small child s night light neon type into a power point that is easily visible or replace any power point with a neon indicator type This will indicate the inverter s operation by flashing when the inverter is in Demand Start mode and remaining on when the inverter is brought on by a load 5 Fault Finding Inverter stays on even when no appliance is being used Some appliances such as Microwave Cookers or Video Recorders still draw current when not in use This is to power their displays This is a common problem known as a phantom load but it can be easily overcome with the WM inverter When trying to isolate a phantom load these appliances will need to be switched off at the power point Sequentially switch off appliances at their power points while checking to see if the inverter returns to demand start mode after a 10 second delay See Handy Hint if your inverter is located remotely Once you have found the offending appliance adjust the sensitivity see Demand Start Adjustment of the demand start up until the Inverter turns off Once this is done re check that small loads will still bring the Inverter on when required Inverter will not come on when a small appliance is switched on This means that your demand start sensitivity is set too high With the appliance in question switched on adjust the demand start sensitivity see Demand Start Adjustment until the WM inve
15. ng regulations or relevant wiring standards Verify that the DC switch on the front panel is in the OFF position down Connect the battery cables RED BATTERY POSITIVE BLACK BATTERY NEGATIVE These connections should be tight If using nuts bolts and washers they should be stainless steel At this point re check the connections before proceeding any further WARNING If the WM Inverter emits a very loud tone the battery leads have been connected in reverse polarity Immediately disconnect the leads and reconnect with the correct polarity Do not under any circumstances turn on the inverter DC switch when the buzzer is sounding as permanent damage to the WM inverter will result If all is well you can now turn the DC switch ON up DEMAND START STATUS 16 Watts AC Volts ON 12 Watts AC Overload 8 Watts DC Volts Low High 4 Watts TEMP Overload Demand Start Adjust Alarms Off Low Volts Adjust DC Switch fa L L Front Panel 4 Operation 4 1 Demand Start When you first apply power the WM Inverter will be in Demand Start mode there will be a quiet pulsing sound The WM Inverter is now ready for use Demand Start mode means that the WM Inverter is producing pulses of power to sense when an appliance is switched on The Demand Start feature allows the inverter to automatically turn on and off as
16. o change the value This value is set to 240V at the factory End Settings TEE Indicates the end of the set parameters menu Press any grey keypad key to return you to the STATUS menu Your settings will be automatically saved 8 6 Options Keypad Light Blue Keys Press the Keypad OPTIONS Light Blue Key This display allows access to logged alarms a Press the OPTIONS key to scroll through logged alarms If there are no logged alarms only this screen will be displayed When in this END ALARMS screen press any grey keypad key to return you to the STATUS menu Logged alarms are Low DC Volts High DC Volts AC Current Overload Current Limit High Transformer Temperature High Heatsink Temperature 8 7 Diagnostics Keypad Light Blue Keys Press the Keypad DIAGNOSTICS Light Blue Key The following screens allow the user to look at various internal inverter values These are not able to be changed from the keypad Press NEXT key Press the NEXT key to access diagnostics screens Diagnostics This diagnostic number relates to the transformer temperature Tx Temp 4 Note the reading is NOT in degrees Celsius Diagnostics HS Temp 53C Indicates Heatsink temperature Note the reading IS in degrees Diagnostics Celsius D S 1 2 This diagnostic number relates to the Demand Start current level Diagnostics Selectronic C Indicates the Inverter model microprocessor code revision and WM1700 1 00 2000 yea
17. oad being drawn from it then LED 2 will come ON The WM Inverter will remain in this condition for 2 minutes after the AC load has been reduced to a safe level LED 2 will flash if the inverter shuts down due to time to shutdown see page 11 e If the WM inverter remains in this condition after two minutes the main DC Power Switch should be turned OFF and then back ON LED 3 DC Volts Low High should normally remain OFF If the inverter shuts down because the battery volts are too high then this LED will come ON It will remain ON until normal battery volts are restored e lf the inverter shuts down due to not enough battery volts then LED 3 will flash e LED 3 will continue to flash until the battery volts have raised sufficiently To remedy this charge the battery by starting the vehicle or using a battery charger or allow the solar or wind to recharge the batteries The low voltage point that the inverter will cut out is adjustable to suit your particular battery see below Low Volts Adjust LED 4 Temperature Overload normally remains OFF If the inverter shuts down due to the black fins on top of the unit getting too hot then this LED will come ON If the inverter shuts down due to an internal component overheating then this LED will FLASH The inverter will come back ON when the temperature has lowered to a safe level e If this LED is coming on regularly either reduce the amount of load on the inverter or try to mo
18. played Please note Once the parameters have been successfully entered if the inverter is turned off or the DC power is disconnected from the inverter the parameters which have been entered will be saved and held in permanent memory and will not need to be re entered Status amp Alarm indicators LED 5 green OFF When power is first applied LED 1 should flash When LED 5 is OFF this indicates the LED 1 4 is showing the inverters STATUS as per written notation to the right of the LED s In this mode there are no adjustments to be made LED 1 Flashing This indicates the WM inverter is in Demand Start mode Insufficient power is being drawn from the inverter so it has gone to SLEEP to save power LED 1 Stays ON The inverter has been commanded to provide power to the load e g a light switch has been turned on so it has gone from SLEEP mode to ON Once the load has been removed e g the light switch is turned off the inverter will wait 10 seconds and return to SLEEP mode e It is good practice to have your WM Inverter in SLEEP mode as often as possible When the WM Inverter is in SLEEP mode it uses 1 10 from the battery When the inverter is in the ON mode it uses at least 0 6 amps from the battery The amount of power required to go from SLEEP to ON is adjustable and is described see below in Demand Start Adjust LED 2 AC Overload should normally remain OFF If the inverter shuts down due to too much AC l
19. r Press any grey keypad key to return you to the STATUS menu 8 8 Inverter Alarms Inverter Alarms are not indicated on the keypad screen The status of the inverter can be checked along with the output voltages and currents The Keypad LED will flash and the buzzer will sound on an Inverter Alarm 9 WM1400 12 WM1700 24 Electrical Specifications Inverter Type PWM Full Bridge power stage with true sine wave AC output SELECTRONIC WM INVERTER SPECIFICATIONS ELECTRICAL PARAMETER WM1400 WM1700 CONDITION Output Power 1 400 watts 1 700 watts Max Continuous 25 C Ambient 1 800 watts 2 250 watts 1 2 Hour Rating 3 600 watts 4 500 watts Max Surge Output Power 1 200 watts 1 500 watts Max Continuous 40 C Ambient 1 600 watts 2 000 watts 1 2 Hour Rating 3 600 watts 4 500 watts Max Surge Voltage Input Range 10 17V DC 20 34V DC Range Input Current 0 05A DC 0 05A DC Stand By 0 7A DC 0 6A DC Inverter ON No Load 136A DC 80A DC Max Continuous 25 C 349A DC 212A DC Max Surge 25 C Demand Start Sensitivity 4 16W User Adjustable Response Time 1 Second Max Factory Setting Factory Setting 4W Low Voltage Shutdown 10 11 5V DC 20 23 0V DC User Adjustable High Voltage Shutdown 17V DC 34V DC Fixed Low Voltage Shutdown 11 0V DC 22 0V DC Factory Setting No Load to Full Load Output Current 5 8A AC 7A AC Max Continuous IA NO erste REF Output Wave Shape True Sine Wave Output Frequency 50Hz 0 0
20. rter turns on Inverter shuts down during the day and comes back on late afternoon This is more than likely caused by high battery volts during peak charging times from solar panels Battery volts should never exceed 34 volts for a 24V battery bank and 17 Volts for a 12V battery bank If this is the case have your Solar Regulator checked This could be potentially dangerous so we advise you to consult your system designer immediately Inverter shuts down with low volts If your WM inverter has shut down because of low DC volts it could be due to the following 1 A sustained large load could be causing the battery volts to drop below the cut out voltage a The Battery Bank is too small for the loads you wish to use consult your system designer b A bad connection between the batteries and inverter due to a loose or corroded terminal In this case please refer to the maintenance section of this manual c One or more battery cells could be faulty consult your battery supplier 2 If your battery volts are below 24 0V for a 24V battery bank and 12 0V for a 12V battery bank with no loads connected the batteries most likely require charging Use a hydrometer to check the specific gravity of each cell Consult your battery manual for the correct specific gravity SG readings Inverter shuts down due to HS too hot This is likely under sustained heavy load conditions since the WM inverter shuts down to protect its internal components
21. se or interference on a radio or TV receiver Considerable development time has resulted in a reduction of the RFI generated by the inverter to a level that complies with C tick requirements Compliance to this standard means RFI is low but how well the inverter performs in a particular installation can vary Below are some suggestions to help reduce the effects of RFI in your installation It is recommended that the power system including the inverter be housed at least 15 metres from the home Ensure an earth stake is placed as close to the inverter as possible and connected to the inverter via a short length of wire See the INSTALLATION section of this manual for wiring Avoid running DC cables into the home if at all possible If this cannot be avoided run DC and AC in separate conduits separated by as much distance as practicable All DC wiring cables should be kept together and be as short as possible If your inverter is to be installed in a Mobile Home or similar try to keep your inverter at least one metre away from your radio or audio equipment The further the better Using a Selectronic Keypad with a WM Inverter 8 Serial Port Wiring Using the RJ45 serial port on the bottom of the inverter it is possible to connect an optional Remote LCD to your WM inverter The remote LCD can be placed up to 100m from the inverter and can provide easy access to inverter and system information To obtain this part order
22. stem designer installer Mains Earth 3 3 System Battery Fuse A A system fuse is an extremely important part of any power system this fuse is designed to give one point of complete disconnect in case of a serious fault The fuse should have a sufficient rating so as not to blow under heavy load conditions Your inverter will normally be the biggest load in your system if this is the case a motor start fuse equal to or slightly higher than the maximum continuous current of the inverter should be used As a guide we suggest 160Amp motor start fuses for 12volt systems and 100A for 24volt systems These sizes may have to be increased depending on other components in the system If in any doubt see your supplier or installer 3 4 Batteries A Batteries are very dangerous Please read the safety information provided by the battery supplier Battery acid is dangerous Batteries can emit hydrogen gas which is explosive Batteries connected in series can produce hazardous voltages Disconnecting a DC power connection even on one battery cell can cause dangerous high energy DC arcs which can cause serious burns and eject hot particles and can be difficult to extinguish Disconnecting a DC power connection even on one battery cell can cause renewable sources to produce large voltages much larger than the battery voltage on battery terminals and DC wiring Such voltages can be lethal They can also damage the WM Inverter Only
23. the load requires When all appliances are switched off the inverter will return to Demand Start mode after approximately 10 seconds This feature is extremely important as it conserves valuable battery power when no appliances are on The amount of power or load that the Inverter needs to start up is adjustable see Demand Start Adjust 4 2 Demand Start Override In this mode the Inverter will be on at all times regardless of whether appliances are connected or not This situation is useful if you have small loads such as a DVD player or digital clock that requires 24 hour power or if loads are too small to be sensed in the Demand Start mode The only disadvantage is that when the appliances are off the WM Inverter will be drawing more power than it would in Demand Start mode DEMAND START STATU a L E D 16 Watts e AC Volts ON 4 7 O LED is on 12 Watts e AC Overload 4 LED Q LED is flashing 8 Watts DC Volts Low High 4 LE D LED is off 4 Watts TEMP Overload LE D Demand Start Adjust Q e O Alarms q Low Volts Adjust P LED A wed 4 Mode Button 4 3 Mode button and LED s Five LED s are provided on the front panel to indicate a number of parameters and allow adjustment of some of these LED 5 tells you what LED 1 4 are displaying Pressing the Mode Button will change the information being dis
24. ts to the customer will be paid by the manufacturer method of freight used will be determined by the manufacturer Under certain circumstances the manufacturer may allow on site repairs to be carried out This will be at the manufacturer s discretion and the manufacturer is not responsible for the cost of any labour or travelling time incurred Unless otherwise specified to the purchaser the benefits conferred by this voluntary warranty are additional to all other conditions warranties guarantees rights and remedies expressed or implied by the Trade Practices Act in your state or territory All installation and user conditions as set down in the instruction manual must be strictly adhered to failure to do so may void your warranty This product is not to be used for Life Support equipment Any faults caused by lightning water or moisture ingress faulty installation using the product in a manner which it is not intended vermin infestation improper voltage alterations to the product which affect its reliability or performance faulty ancillary equipment or faulty generator sets will not be covered under warranty The manufacturer shall bear no responsibility for any consequential loss damage or expense due to any malfunction of the product or the time it is out of service The manufacturer will not be held responsible for any misleading or incorrect information conveyed by any salesperson or installer not directly employed by the manu
25. ve the inverter to a cooler location Demand Start Adjust LED 5 green ON It is sometimes necessary to adjust the auto start sensitivity to overcome what is called Phantom Loads A phantom load is a load that tricks the inverter into thinking it should be ON instead of in SLEEP mode The wiring of a house or a portable stereo system in standby is good examples of a phantom load These loads serve no purpose but can increase battery drain by bringing the inverter ON Hold the Mode button down approximately 1 second LED 5 will turn ON indicating you are ready to adjust this setting The WM Inverter will leave the factory with a setting of 4 Watts Now press the Mode button until the desired value is sought LED s 1 4 will return to Status Indication after 10 seconds if a key is not pressed Each press of the Mode button will increment the Demand Start level The adjustment starts from the previously stored setting LED 1 4 Demand Start Adjustment is indicated by LED s 1 4 Demand Start Wattage LED 1 LED 2 LED 3 LED 4 4 Watts ON 5 Watts Slow flash ON 6 Watts Medium flash ON 7 Watts Fast flash ON 8 Watts ON 9 Watts Slow flash ON 10 Watts Medium flash ON 11 Watts Fast flash ON 12 Watts ON 13 Watts Slow flash ON 14 Watts Medium flash ON 15 Watts Fast flash ON 16 Watts ON Continuous ON ON ON ON After continuous the next button press
Download Pdf Manuals
Related Search
Related Contents
デジタル音声目覚まし時計取扱説明書 Lowrance electronic LMF-400 Network Card User Manual تعليمات التشغيل - Sony Asia Pacific Using DMACII (Chained Transfer) MEAP-Lite CSPご利用に際しての注意点 impa nook DEF2(C) DEALER SERVICE MANUAL UPDATE BULLETIN SUPPLEMENT MODE D`EMPLOI- MAXISTICKS Anti-Moustiques HQ CH06E サンディスク コネクト ワイヤレス メディアドライブ Copyright © All rights reserved.
Failed to retrieve file