SIC Card UF-SNMP810 - Emerson Network Power
Contents
1. P Data Analysis System Configure About goseeesescsoceceessssesessesssseeg O Overview Metering O Control Configuration Delete UH11 UPS Base Information Status Alarm Internal Temperature 26 10 C LS GIA Input Type UH11 UPS Input Voltage 225 00 Y Comm la RS232 Input Frequency 50 00 Hz Address le Output Comm Param 4800 n 8 1 Output Voltage 220 00 Y Output Current 220 00 A Output Frequency 50 00 Hz a Load 80 00 Battery Battery Voltage 120 00 Y i 80 00 AS UPS Mode On Line Battery Mode Float charging ERE 2000 06 01 19 11 03 UH11 UPS ups Rectifier Fault 2000 06 01 19 10 57 UH11 UPS A ups Asynchronous more alarms gt Active alarms Figure 4 5 Metering page Site Interface Web SNMP Agent Card User Manual 4 6 Controlling And Configuring Equipment Remotely 4 6 1 Chapter 4 Monitoring Method 1 Through Web Browser 17 In the operating data list green status value means the corresponding equipment signal is normal red status value means the corresponding equipment signal is in alarm Controlling Equipment Remotely Select the main menu Equipment Monitor click UH11 UPS under Device and select Control and the remote control page will appear as shown in Figure 4 6 This page displays the remote control parameter list basic information and active alarms EMERSON Network Power Account admin 142 100 9 91 System Time Device x Se
2. Chapter 4 Monitoring Method 1 Through Web Browser 21 4 9 2 Configuring Data Record 4 10 4 10 1 Select the main menu Data Analysis click Setting and the data record setting page will appear as shown in Figure 4 12 In this page you can change the data record time interval EMERSON English Equipment Monitor Alarm Manage Data Analysis System Configure Current Setting Max Record Time 14 Day 2 Hour 30 Minute Time Interval 0 Hour 10 Minute 0 Second Status K Account admin IP Address 142 100 9 91 Data Record Setting Time Interval O Hour l Minute O Second Range 1 minute 24 hours Figure 4 12 Data record setting page In the display area the upper part displays Current Setting including Max Record Time and Time Interval the lower part displays Configuration where you can change the current settings If you need to change the time interval of the data record select Time Interval type the new time interval and click the Submit button to save the change The setting range is from one minute to 24 hours The default setting is 10 minutes Configuring SIC Card System Configuring User Password User password is used to verify the authority of the user who attempts to use Web browser to access the SIC card so as to prevent illegal access and control and ensure the safety of the equipment operation User authorization The system has two users only
3. 5 Click the Confirm button and the intelligent equipment or sensor will be added under Device and Sensor as appropriate LI Note 1 There are two naming rules for the intelligent equipment and sensors under Device and Sensor 1 The name of the main equipment which accommodates the SIC card is the equipment type itself For example UH11 UPS in Figure 4 3 2 The names of the intelligent equipment and sensors connected to the COM1 and COM2 interfaces of the SIC card are composed of the corresponding equipment type and address For example IRM S02TH 1 in Figure 4 3 consists of the equipment type IRM SO2TH and address 1 2 The monitoring pages in this manual take UH11 UPS and IRM S02TH 1 as examples As different types of intelligent equipment and sensors have different monitoring parameters the data in the monitoring pages you actually see may not be exactly the same as those in this manual 4 5 Viewing Equipment Status Method 1 Select the main menu Equipment Monitor click UH11 UPS under Device and the overview page will appear as shown in Figure 4 4 The overview page displays the main operating data graphs basic information and active alarms of the equipment Site Interface Web SNMP Agent Card User Manual 16 Chapter 4 Monitoring Method 1 Through Web Browser ei EMERSON Network Power Account admin IP Address 142 100 9 91 System a 2009 05 11 21 46 50 Time Device X Sensor Y I
4. IBM NetView Novell ManageWise SunNet Manager Installing Equipment MIB If you wish to use an NMS to access the SIC card to monitor the intelligent equipment and environment you need to use the MIC import function of the NMS to load the MIB of the intelligent equipment For the loading method refer to the user directions of the NMS You may get the equipment MIB from O the CD delivered with the SIC card O the local customer service center of Emerson O our website www emersonnetworkpower com cn 5 3 Applying For Management Authority To enable the NMS to manage the intelligent equipment and environment through the SNMP agent function provided by the SIC card first of all you must apply to the system administrator of the SIC card for management authority ask the system administrator to add the NMS into the NMS access control list of the SIC card For procedures refer to the 1 Adding NMS part in 4 10 2 Configuring Authentication Mode Select the main menu System Configure click Authentication the page shown in Figure 4 14 will appear Through Figure 4 14 you can change the authentication mode of the SIC card into local authentication RADIUS authentication or RADIUS local authentication Through these authentication modes you can control the account whether has the authority to access SIC page In local authentication mode you can log in the SIC card through the built in admin and user account In RADIUS authentication mode you can
5. Refer to the part Using TTY to login SIC card in 3 1 1 Using TTY Or Telnet To Login SIC Card 5 TTY and serial port can communicate well Question 3 What shall I do if lose my password Answer Use the USB communication cable accessory to connect the computer USB interface and the SIC card USB interface then use the reset function to resume default password setting See 3 3 Using Reset User To Configure Basic SIC Card Parameters Through TTY Question 4 Why can some computers visit the card while some others cannot but these computers can visit one another Answer Incorrect SIC card gateway setting If the card default gateway is 0 0 0 0 the card can be accessed only by the computers in the same network segment Please reset the card gateway according to gateway of the computer Even though the gateway is set correctly if firewall is installed in your network you will also meet with this problem If so contact your network administrator Q s amp A s In Web Monitoring Question 1 When type in Web browser the IP address of the computer connected to the equipment installed with the SIC card the prompt cannot find server appears why Answer Suppose the IP address is correct maybe 1 The SIC card is not running If this is because the intelligent equipment is off please turn on the equipment and try again 2 Network connection has not been built Use the ping command to check whether your computer can connect to
6. Telnet Access Status x Account admin IP Address 10 163 210 218 Account Authentication Console Network Console Configuration SNMP Telnet Access E Mail Telnet Port 23 23 5000 32768 Date amp Time O SSH Access SSH Port a Identification E 22 5000 32768 Reboot Figure 4 16 Network parameter setting page The upper part of the page displays Current Console Settings through Mode you can view the terminal access mode of the current configuration the lower part of the page displays Console Configuration you can select Telnet Access or SSH Access Site Interface Web SNMP Agent Card User Manual 24 4 10 4 Chapter 4 Monitoring Method 1 Through Web Browser If you need to change the terminal access mode select Telnet Access or SSH Access and change the access port Telnet access has the port number 23 default or 5000 32768 SSH access has the port number 22 default or 5000 32768 After changing the terminal setting the SIC card does not need to restart and the terminal access mode will be valid in time then the link built through the original access mode will automatically disconnect LI Note 1 SSH2 is the SSH version supported by SIC card which only supports the authentication mode of user name password 2 When selecting the terminal access mode SSH you need the client supporting SSH2 then configure the correct host IP address IP address of SIC card
7. operations but can only view the operating parameters and alarm data PS state and input output signals 4 If you want to modify a table you must configure all the writable properties of it and submit them to the SIC card Only in this way can your modifications be accepted 5 In the case of control failure due to lack of authorization or community string error the NMS will receive an AUTH_FAILURE trap Site Interface Web SNMP Agent Card User Manual 36 Chapter 6 Monitoring Method 3 Through SiteMonitor Chapter 6 Monitoring Method 3 Through SiteMonitor SiteMonitor is an SIC card centralized management software developed by Emerson Network Power Co Ltd Through TCP IP protocol you can use SiteMonitor to obtain the real time data and alarm data of the intelligent equipment and environment from the SIC card control the equipment and configure operating parameters SiteMonitor can manage up to ten thousand pieces of intelligent equipment To use SiteMonitor to manage intelligent equipment and environment through the SIC card you need to open the IE browser on the computer installed with SiteMonitor and configure the IP address of the SIC card into SiteMonitor For details on how to use SiteMonitor to monitor the intelligent equipment and environment refer to SiteMonitor UPS Monitoring Software User Manual Site Interface Web SNMP Agent Card User Manual Chapter 7 Guarding Computer With Network Shutdown 37 Chapter 7 Guarding Co
8. 3 4 Command supported by TTY and Telnet in super user 3 2 2 Configuring Basic Parameters Type a command behind sic_admin If the command is incorrect the system will prompt command not found If you have typed a command corresponding to a parameter the system will prompt you to configure the parameter At first the system will display the current setting and prompt you to select the command ID to confirm or modify the current setting as shown in Figure 3 5 1 confirm current setting 2 modify current setting Figure 3 5 Command ID selection prompt LO Note When typing a command you may just type the first several letters of it the SIC card can identify them for example pi for ping 1 Password change the password of the super user admin LU Warning Keep in mind the password of admin If you forget it you can use the USB accessory to connect the SIC card Then use the reset user to log in the password of admin will be resumed to the default password admin Site Interface Web SNMP Agent Card User Manual Chapter 3 Configuring SIC Card Basic Parameters Because admin has the highest authority to ensure the safety of the connected equipment and sensors we suggest you change the password of admin immediately after installing the SIC card Configuration method type password after sic_admin Configuration steps see Figure 3 6 Sic_admin pass Changing p admin Please use a combination of upper EE bters and numbe
9. After changing the authentication mode the SIC card does not need to restart and the authentication mode will be valid in time then input the corresponding account to log in according to the prompt authentication mode As shown in Figure 4 15 the SIC card uses the authentication mode of RADIUS Local Connect to 110 163 710 218 51 local then radius User name E ne Remember my password Figure 4 15 Login window of authentication mode prompt LO Note 1 When selecting RADIUS Only or RADIUS then Local you need a server to realize the RADIUS protocol and must ensure that the shared cipher code is the same as that of the RADIUS server otherwise the RADIUS authentication will be invalid When the shared cipher code of the master RADIUS server is incorrect for safety reason the SIC will not continue to get information from the slave server considering there is a third party attack 2 To ensure the safety of the RADIUS authentication you should modify the shared cipher code of the RADIUS server and SIC card regularly 4 10 3 Configuring Terminal Access Mode Select the main menu System Configure click Console the page shown in Figure 4 16 will appear Through this page you can change the debugging terminal remote login mode of the SIC card into Telnet or SSH lt a EMERSON English Power Equipment Monitor Alarm Manage Data Analysis System Configure eeng Current Console Settings Mode
10. NMS 3 Deleting NMS To delete an NMS click the NMS IP address in the NMS information list in the page shown in Figure 4 17 and the page shown in Figure 4 19 will appear Click the Delete button and the NMS is deleted from the NMS information list EJ Note After you delete an NMS it cannot access the SIC card Conducting trap test Select the main menu System Configure click SNMP Configuration and select Trap Test and the trap test page will appear as shown in Figure 4 20 amp EMERSON Equipment Monitor Alarm Manage Data Analysis System Configure goocecccocccescccceccceeeesesesecsssosoe Access Control Trap Test A AA English To 142 100 8 132 Account admin IP Address 10 163 210 218 Account Authentication Console Network SNMP E Mail Date amp Time Identification Reboot Figure 4 20 Trap test page Select the NMS IP address from the To drop down box and click the Confirm button to conduct the trap test If the test is successful the prompt Success will appear Site Interface Web SNMP Agent Card User Manual Chapter 4 Monitoring Method 1 Through Web Browser 27 4 10 5 Configuring E Mail Parameters And Conducting E Mail Test Configuring E Mail Server Select the main menu System Configure click E Mail Configuration and the E Mail server configuration page will appear as shown in Figure 4 21 In this page you can set the SMTP server address address
11. access port Telnet access has the port number 23 default or 5000 32768 SSH access has the port number 22 default or 5000 32768 After changing the terminal setting the SIC card does not need to restart and the terminal access mode will be valid in time then the link built through the original access mode will automatically disconnect EJ Note 4 SSH2 is the SSH version supported by SIC card which only supports the authentication mode of user name password 5 When selecting the terminal access mode SSH you need the client supporting SSH2 then configure the correct host IP address IP address of SIC card and access port in the client 6 Only the super user user name is admin is allowed to log in Telnet through Telnet or access SIC card in SSH mode The default password of super user is admin case sensitive Configuring SNMP Agent Parameters And Conducting Trap Test For the details on how to use the NMS to monitor your intelligent equipment and environment refer to the NMS user directions In operation please note the following points 1 The community string used in getting UPS data must be the same as the read community string set in the SIC card 2 The community string used in configuring parameters and controlling equipment must be the same as the write community string set in the SIC card 3 If you are granted the read only authority you will not be able to use the NMS to perform control or configuration
12. alarm amp for serious alarm The figure following the icons K and 4 represents the alarm number Site Interface Web SNMP Agent Card User Manual Chapter 4 Monitoring Method 1 Through Web Browser 15 4 4 Adding Equipment The SIC card can automatically search the connected intelligent equipment and sensors The intelligent equipment and sensors the SIC card searched out are displayed respectively under Device and Sensor in the display area as shown in Figure 4 3 For those not searched out you need to click the Add Device button at the lower left corner of the monitoring homepage to enter the equipment adding page shown in Figure 4 3 and add them under Device and Sensor as appropriate EMERSON e English WS Equipment Monitor Alarm Manage Data Analysis System Configure Add Device Device Type IRM SO2TH Y Account admin Port COM1 b IP Address 142 100 9 91 Ree 2 1 247 leier SEN Communication Rate 2400 bps v Device X UH11 UPS Add Device Figure 4 3 Equipment adding page Procedures are as follows 1 Select the intelligent equipment type or sensor type from the Device Type drop down box 2 Select the port of the SIC card connected to the intelligent equipment and sensor from the Port drop down box 3 Type the address of the intelligent equipment or sensor in the Address box The address should be exclusive 4 Select the communication baud rate from the Communication Rate drop down box
13. alarms Remote configuration parameter list EMERSON Network Power Basic information English Equipment Monitor Alarm Manage a Data Analysis System Configure About siccard O Overview O Metering O Control O Configuration Delete Account admin O UPS turn off delay sec 120 120 600 Base Information IP NEE Status IA Address DS O UPS automatic restart delay sec 0 0 43200 Type UH11 UPS System 4 np s Comm Port R5232 Time Automatic restart enable enable dias o Battery self test duration sec 5 1 600 COM GERS Device D O Master Slave Single Master Master Slave alternate work time day H as Confirm Sensor UPS Mode On Line z Battery Mode Float charging Y IRM S02TH 1 HE DET 2000 06 01 19 11 03 UH11 UPS td ups Rectifier Fault 2000 06 01 19 10 57 UH11 UPS ups Asynchronous more alarms gt Add Device Active alarms Figure 4 7 Remote configuration page In the remote configuration parameter list the parameter values are the current remote configuration parameter values If you need to change the value of a parameter type or select the new value in the corresponding box and click the Confirm button to submit the configuration command to the SIC card If the parameter value is saved successfully the prompt Success will appear otherwise the prompt Communication Interrupt Remote Control Failed wil
14. and access port in the client 3 Only the super user user name is admin is allowed to log in Telnet through Telnet or access SIC card in SSH mode The default password of super user is admin case sensitive Configuring SNMP Agent Parameters And Conducting Trap Test Configuring SNMP Agent Parameters Select the main menu System Configure click SNMP Configuration and the access control parameter configuration page will appear as shown in Figure 4 17 In this page you can add configure and delete an NMS amp 7 f SE English EMERSON NMS information list 4 English e Equipment Monitor Alarm Manage Data Analysis System Configure eeng O Access Control Trap Test 142 100 8 132 Read Write Status X Enabled public private Account admin IP Address 10 163 210 218 Account Authentication Console Network SNMP E Mail Date amp Time Identification Reboot Figure 4 17 Access control parameter configuration page Site Interface Web SNMP Agent Card User Manual Chapter 4 Monitoring Method 1 Through Web Browser 25 1 Adding NMS If you need to allow an NMS to access the SIC card you must add this NMS to the NMS information list shown in Figure 4 17 In the page shown in Figure 4 16 click the Add button and the display area will display in the lower part the Access Control Configuration pane as shown in Figure 4 18 E EMERSON English Equipment Monitor Alarm Manage Data Analysis
15. e FireFox Tools gt Options choose Web Features from the left navigation bar select the checkbox next to Enable JavaScript and click OK Web page Cache setting Browsers use Cache called temporary file in IE to increase web page display speed When you visit web pages in the Cache the browser will check whether there is any new version of them in Web server according to the configuration below e Check every time visiting pages e Check every time starting the browser e Automatic e No check When visiting the SIC card the configuration must be Automatic Otherwise the monitoring web pages cannot be displayed normally For example the newly opened web page is still the web page before you exit the browser last time The configuration steps for common Web browsers are as follows O Internet Explorer View gt Internet Options gt General gt Internet Temporary Internet files gt Settings gt Check for newer version of stored pages gt Every visit to the page e FireFox Tools gt Options gt cache select the editbox next to check_doc_frequency and input 1 Definition and browser font setting We recommend you to set the monitor definition to 1024x768 or above Otherwise the monitoring page might not be displayed fully Site Interface Web SNMP Agent Card User Manual Chapter 4 Monitoring Method 1 Through Web Browser 13 If your monitor definition is 1024x768 but you still cannot view the full page please decrease the browser
16. in Figure 4 24 will appear Click the Delete button and the recipient is deleted from the recipient list Conducting E Mail test Select the main menu System Configure click E Mail Configuration and select E Mail Test and the E Mail test page will appear as shown in Figure 4 25 English Gm E Mail Server E Mail Recipient E Mail Test To fanliu emersonnetwork com cn k Status x Account admin IP Address 10 163 210 218 Account Authentication Console Network SNMP E Mail Date amp Time Identification Reboot Figure 4 25 E Mail test page Select the recipient address from the To drop down box and click the Confirm button to conduct the E Mail test If the test is successful the prompt Success will appear 4 10 6 Configuring Network Parameters Select the main menu System Configure click Network Configuration and the network parameter configuration page will appear as shown in Figure 4 26 In this page you can change the IP address subnet mask and default gateway of the SIC card EMERSON Y English Netwoe k Power Equipment Monitor Alarm Manage Data Analysis System Configure Current Network Settings Mode Static IP Address 110 163 210 218 Status x Subnet Mask 255 255 254 0 Account admin Default Gateway 10 163 210 1 MAC Address 00 09 f5 03 f3 3a IP Address 10 163 210 218 Account Authentication Console Network Network Configurati
17. mode login with user name admin and admin s password For a new SIC card the default password is admin 4 After login set the card s IP address and other network parameters The card will be rebooted automatically and later on you may access the card using the new IP address 5 Restore the network parameters of the computer 8 2 Q s amp A s In Running Question 1 Why the yellow indicator of the SIC card does not illuminate Answer The card is not connected to the network Please connect it to the network After building up network connection when the card is receiving data from the network the yellow indicator will blink when it is not receiving data the yellow indicator will keep illuminating Question 2 The SIC card is running but when I start TTY and intend to configure the SIC parameters why no login information appears on the screen Answer Press the Enter key and the login information should appear If not please verify that the card is running green indicator is on and check that 1 the intelligent equipment is connected to the computer with USB cable Site Interface Web SNMP Agent Card User Manual 8 3 Chapter 8 Q s amp A s 39 2 the USB driver has been properly installed and the serial port CP2101 USB to UART is on the menu COM amp PT in Device Manager 3 the serial port set in TTY is the same as the one connected to the intelligent equipment 4 the serial port set in TTY is correct
18. or 5000 32768 After changing the terminal setting the SIC card does not need to restart and the terminal access mode will be valid in time then the link built through the original access mode will automatically disconnect Site Interface Web SNMP Agent Card User Manual 42 Chapter8 Q s amp A s RA Note 7 SSH2 is the SSH version supported by SIC card which only supports the authentication mode of user name password 8 When selecting the terminal access mode SSH you need the client supporting SSH2 then configure the correct host IP address IP address of SIC card and access port in the client 9 Only the super user user name is admin is allowed to log in Telnet through Telnet or access SIC card in SSH mode The default password of super user is admin case sensitive Configuring SNMP Agent Parameters And Conducting Trap Test 2 Community string error In this case the NMS will receive an AUTH FAILURE trap The community string used in sending request must be the same as that set in the access control parameters of the SIC card Refer to the Configuring SNMP Agent Parameters part in 4 10 2 Configuring Authentication Mode Select the main menu System Configure click Authentication the page shown in Figure 4 14 will appear Through Figure 4 14 you can change the authentication mode of the SIC card into local authentication RADIUS authentication or RADIUS local authentication Through these authentication modes you ca
19. the card Refer to your OS manual for the usage of the ping command If you cannot ping successfully check whether the card IP address is wrong Question 2 Why does the system prompt connection timeout while the browser is visiting the SIC card Answer Too many network users including Web users and NMSs The card can respond only 10 Web users and 5 inquiring NMS concurrently Please close or stop some Web browsers or NMSs and try again Question 3 Why are the intelligent equipment status and SIC card configuration displayed on Web browser inconsistent with the actual situation Answer It might be caused by 1 incorrect computer time 2 incorrect card time 3 incorrect cache setting of the Web browser 4 web page time error Please set the card time computer time and browser cache correctly and delete all temporary web pages on your computer Question 4 The browser sometimes prompts web page error and cannot continue while sometimes not why Answer This problem usually occurs when you have just started to browse the SIC card and the browser is downloading the monitoring homepage from the SIC card while at this point you click other link on the homepage and the download process is thus interrupted Please wait till correct status data appear on the homepage before you carry out other operations Site Interface Web SNMP Agent Card User Manual 40 Chapter8 Q s amp A s Question 5 I have typed correct user name and pas
20. 123 Secondary RADIUS Server Secondary RADIUS Secret Figure 4 14 Authentication settings page The upper part of the page displays Current Authentication Settings through Mode you can view the authentication mode of the current configuration the lower part of the page displays Authentication Configuration you can select Local Only RADIUS Only RADIUS then Local that is RADIUS Local If you select RADIUS Only or RADIUS then Local you need to input the IP address and shared cipher code of the RADIUS server To ensure the stability of the RADIUS authentication the SIC card provides two RADIUS servers Site Interface Web SNMP Agent Card User Manual Chapter 4 Monitoring Method 1 Through Web Browser 23 which are master and slave The SIC card first get the information whether the login account is valid from the master RADIUS server When the master RADIUS server is unavailable network failure or the return information shows that the login account is invalid the SIC card will turn to get information whether the login account is valid from the slave RADIUS server If any RADIUS server admits the login account is valid then this account can access the SIC page otherwise not allowed You can determine whether configure the slave RADIUS server according to your need After selecting the authentication mode and inputting the required information click the Confirm button to save it
21. 33 Chapter 6 Monitoring Method 3 Through SiteMonNitor ccccccccccoccnccnncccconononcnnnnnonononnnnnnnnonononnnnnnnnnnnnnnnnnnnnnnonononarenininnns 36 Chapter 7 Guarding Computer With Network Shutdown nnnnnnneannnnnnnnennnnnnnnnsnnnrnnnnnsnnnrrrrnnnennrrrrennsnnnrrrrnnsnnnrrrrennnnnnni 37 Chapter S EE 38 G QS GAS Mi Wee EE 38 O20 S EA Se In RUINA to a a ea e dal cee at aol oe ate 38 8 3 O S Gc AS IA WED Monto Te EE 39 8 4 O s amp A S In NMS Monitoring occ fccsce ce ccccck cess adeocccnsccodeenidacsatcocsapesecsecuccesanectoceacduedssceechanessssnacecasccodeenidaceaccecbareseece 40 8 5 0 s amp A s In SiteMonitor Montong 2 10 eegene Eege 44 8 6 Q s 8 A s In Using Network Shutdown oocccccccccnnccccccccconononnnnncnnnnnnnnnnnnonononnnnnnnnnnnnnnnnnnnnnnnnnnonnnnnnnnnnnnnnnnnnnnnninnnnnss 44 1 1 Chapter 1 SIC Card Description 1 Chapter 1 SIC Card Description This chapter gives a brief introduction to the SIC card including its functions technical specifications models and appearance Function The SIC card is a network management card lt can make your Emerson intelligent equipment real network equipment such as UPS air conditioner static transfer system STS server power management system SPM and so on The SIC card can also connect to IRM series sensors to provide environment monitoring function In the case of equipment alarm it notifies the user by recording sending Trap message or sending E M
22. 57 UH11 UPS fy UPS Asynchronous more alarms gt Add Device Display area Figure 4 2 Monitoring homepage Site Interface Web SNMP Agent Card User Manual 14 4 3 Chapter 4 Monitoring Method 1 Through Web Browser The monitoring homepage provides a language selection drop down box at the upper right corner During interface operation whenever you wish to change the display language you may click this drop down box to select the language LU Note The default display language is the language of the current browser LJ Warning If you are super user or have control authority do remember to close the browser before you leave Otherwise if somebody else uses your account to issue equipment control command the consequence might be serious Monitoring Homepage Main menu area and display area As shown in Figure 4 2 the monitoring homepage consists of the main menu area and display area 1 Main menu area The main menu area displays the main Web monitoring function options of the SIC card Equipment Monitor Alarm Manage Data Analysis System Configure About Click a function option button and the monitoring page of the corresponding main menu will appear 2 Display area The display area displays the page information of the selected main menu Status icons As shown in Figure 4 2 the monitoring pages present the equipment status and sensor status with three icons L for normal status A for general
23. Administrator user name admin and User user name user Neither of their user names can be changed You can only change their passwords The user authorization is shown in Table 4 1 Table 4 1 User authorization User Authority Administrator M Configuration M Control WM Viewing LJ Configuration J Control M Viewing Changing user password EJ Note 1 Administrator can change the passwords of both Administrator and User User has no such authority 2 The default passwords of Administrator and User are respectively admin and user To ensure system security after installing the SIC card please use the authority of Administrator to login the SIC card and change the passwords Meanwhile it 1s suggested that you change the passwords regularly Site Interface Web SNMP Agent Card User Manual 22 Chapter 4 Monitoring Method 1 Through Web Browser Select the main menu System Configure click Account Management select Administrator or User and the page shown in Figure 4 13 will appear Type the current password and new password and re type the new password then click the Submit button The password may contain any characters including Chinese characters in length limited within 20 characters EMERSON English Network Power Equipment Monitor Alarm Manage Data Analysis System Configure Administrator User Status x Account Name admin Account admin Input Current P
24. Method 1 Through Web Browser Chapter 4 Monitoring Method 1 Through Web Browser This chapter tells how to use Web browser to monitor the intelligent equipment and environment in real time control and configure the intelligent equipment remotely view alarm information configure SIC card system parameters and view SIC card version information Checking Web Browser Settings Before using Web browser to monitor the intelligent equipment and environment please verify that your Web browser meets the requirement listed in this section Browser type and version The SIC card supports the following browsers O Internet Explorer 5 0 or above e FireFox 1 0 or above The SIC card might support other browser types compatible with HTTP1 1 HTML4 0 and JavaScript1 0 but this is not for sure The SIC card supports Chinese and English If you select Chinese the browser must support simplified Chinese GB2312 character set but not necessarily be Chinese version If your browser cannot display Chinese please upload or install corresponding software components Future version SIC card will support more languages Enabling graphic and animation display Your browser must be able to display graphic and animation Enabling JavaScript Your browser must allow JavaScript The setting method is as follows e Internet Explorer Tools gt Internet Options gt Security gt Custom Level scroll down to Scripting gt Active Scripting select Enable and click OK
25. P address so that the current IP address will be allocated to the SIC card in future IP address allocation For obtaining the MAC address refer to 4 10 6 Configuring Network Parameters 5 version view the SIC card application version and operation system version Viewing method type version after sic_admin as shown in Figure 3 11 Site Interface Web SNMP Agent Card User Manual 10 Chapter 3 Configuring SIC Card Basic Parameters sic _admin verzion Application Module VWersion YLOOROOODOO Date 2008 04 04 Time 19 10 00 Linux 05 Version 2 4 20_mvls1 integrator Date 2007 10 22 Time 18121 13 i1c_admint Figure 3 11 View SIC card version Interface description Application Module the application of the SIC card Linux OS the operating system adopted by SIC card 3 3 Using Reset User To Configure Basic SIC Card Parameters Through TTY 3 3 1 Basic Commands TTY in reset user supports the commands shown in Table 3 3 Table 3 3 Command supported by TTY Command Description pal Resume user password network parameter authentication mode terminal access mode to diaul After you log in the SIC card type the command help or after sic_reset and press the Enter key the system will prompt all the commands and their descriptions as shown in Figure 3 12 sic_resetHy Following commands are supported E alias for help help a a ne lp all ged auen cation console ticipate admin admi
26. RM S02TH 1 Add Device Main operating data graphs Equipment Monitor Alarm Manage m Overview Basic information English e Data Analysis System Configure Abot O Metering O Control Configuration Delete Input Voltage 225 00 V Load 80 00 Output Voltage 220 00 V Battery Capacity 80 00 Base Information Status L 1 A 1 Type UH11 UPS Comm Port RS232 Address 0 Comm Param 4800 n 8 1 UPS Mode On Line Battery Mode Float charging 2000 06 01 19 10 57 Alarms 2000 06 01 19 11 03 UH11 UPS 9 UPS Rectifier Fault UH11 UPS ups Asynchronous more alarms gt Active alarms Figure 4 4 Overview page This page can display up to six active alarms To view more active alarms and historical alarms click the more alarms gt button at the lower right corner to enter the Alarm Manage main menu Refer to 4 8 Viewing Alarms Method 2 Select the main menu Equipment Monitor click UH11 UPS under Device and select Metering and the metering page will appear as shown in Figure 4 5 The metering page displays the operating data list basic information and active alarms of the equipment EMERSON Network Power Equipment Monitor Account admin IP 142 100 9 9 Address 142 1 9 91 system een Time Device x Sensor Y IRM S02TH 1 Add Device Operating data list Alarm Manage Basic information English
27. SIC Card UF SNMP8 10 User Manual For APM ITA EPM LTS NX NXC 30 40kVA NXr And GXE Series UPS z AAA RUN LAN COMI _COM2 MAHE ES iiia EMERSON Network Power A EMERSON Network Power Application Scope This manual is the user directions of the Site Interface Web SNMP agent card SIC card for short V1 00 It will guide you through the installation configuration operation and troubleshooting of the SIC card The operation of the SIC card involves the monitored equipment Web browser and network management system NMS This manual only deals with the SIC card related operations As for the use of other operation systems please refer to relevant manuals Reading Guide This manual briefly introduces the SIC card and provides use directions including installation configuration and operation ending with an appendix The manual contains eight independent chapters and an appendix Except for the first chapter you may choose to read all chapters according to you needs However if it is the first time you use the SIC card we suggest you read through the manual to get an overall understanding The following is the reading guide of each chapter Reading guide Provides a brief introduction to the SIC card including its functions technical Chapter 1 SIC Card Description specifications models and appearance This chapter will greatly help you to understand the following chapters Introduces the sys
28. System Configure Access Control Trap Test NMS IP Address Access Type Trap Level Read Communit Write Communit on m 142 100 8 132 Read Write Enabled public private Status Account admin IP Address 10 163 210 218 Account Authentication Console Network SNMP Access Control Configuration E Mail NMS IP Date 2 Time Access Type Read Write k e e B v identification Trap Level Enabled Read Community ublic Reboot E E Write Community private Figure 4 18 Adding NMS The access control parameters include NMS IP Access Type Trap Level Read Community and Write Community 1 NMS IP The IP address of the NMS computer which you wish to allow to access the SIC card for example 71 19 8 29 2 Access Type The authority for the NMS to access the SIC card There are three options e Read write The NMS can read and write the SIC card e Read only The NMS can only read the SIC card O Disable The NMS cannot access the SIC card Generally give read write authority to the NMS which you want to use to control the equipment and give read only authority to others 3 Trap Level Whether the SIC card will send trap message that is alarm to the NMS in the case of an intelligent equipment or sensor alarm e Enabled The SIC card will send all alarm information to the NMS O Disabled The SIC card will not send any alarm information to the NMS 4 Read Communi
29. The SIC card first get the information whether the login account is valid from the master RADIUS server When the master RADIUS server is unavailable network failure or the return information shows that the login account is invalid the SIC card will turn to get information whether the login account is valid from the slave RADIUS server If any RADIUS server admits the login account is valid then this account can access the SIC page otherwise not allowed You can determine whether configure the slave RADIUS server according to your need After selecting the authentication mode and inputting the required information click the Confirm button to save it After changing the authentication mode the SIC card does not need to restart and the authentication mode will be valid in time then input the corresponding account to log in according to the prompt authentication mode As shown in Figure 4 15 the SIC card uses the authentication mode of RADIUS Local Connect to 10 163 210 218 FA 51C local then radius User name E Ke C_ Remember my password Figure 5 2 Login window of authentication mode prompt LU Note 3 When selecting RADIUS Only or RADIUS then Local you need a server to realize the RADIUS protocol and must ensure that the shared cipher code is the same as that of the RADIUS server otherwise the RADIUS authentication will be invalid When the shared cipher code of the master RADIUS server is incorrect for s
30. ace see Figure 1 1 of the SIC card The SIC card can cascade connect up to three pieces of intelligent equipment and six sensors Site Interface Web SNMP Agent Card User Manual 3 1 3 1 1 Chapter 3 Configuring SIC Card Basic Parameters Chapter 3 Configuring SIC Card Basic Parameters You may configure the basic parameters of the SIC card through Hyper Terminal TTY or Remote Login Telnet or SSH including the card IP address and super user password If the card is installed for the first time or you do not know the card IP address you must use Hyper Terminal to configure the basic parameters of the card If you know the card IP address you can configure the card basic parameters through Telnet This chapter tells how to configure the basic parameters of the SIC card through TTY and Telnet LJ Note 1 The configuration modes TT Y Telnet SSH of the SIC card basic parameters have the same interface 2 The default remote login access mode of SIC card is Talent If you want to change it set it through Web browser refer to 4 10 3 Configuring Terminal Access Mode 3 The SSH version supported by SIC card is SSH2 and only user name password is identified Login amp Logout Using TTY Or Telnet To Login SIC Card Using TTY to login SIC card TTY is a system tool of Windows For the creation and start of TTY please refer to relevant computer OS manual When creating TTY note that the serial port No is the one that connect
31. afety reason the SIC will not continue to get information from the slave server considering there is a third party attack 4 To ensure the safety of the RADIUS authentication you should modify the shared cipher code of the RADIUS server and SIC card regularly Site Interface Web SNMP Agent Card User Manual Chapter 5 Monitoring Method 2 Through NMS 35 5 3 2 Configuring Terminal Access Mode Select the main menu System Configure click Console the page shown in Figure 4 16 will appear Through this page you can change the debugging terminal remote login mode of the SIC card into Telnet or SSH D EMERSON Y English Equipment Monitor Alarm Manage Data Analysis System Configure eeng Current Console Settings Mode Telnet Access Status x Account admin IP Address 10 163 210 218 Account Authentication Console Network Console Configuration SNMP Telnet Access E Mail Telnet Port 23 23 5000 32768 Date amp Time O SSH Access E SSH Port 307 Identification 22 5000 32768 Reboot Figure 5 3 Network parameter setting page The upper part of the page displays Current Console Settings through Mode you can view the terminal access mode of the current configuration the lower part of the page displays Console Configuration you can select Telnet Access or SSH Access If you need to change the terminal access mode select Telnet Access or SSH Access and change the
32. ail The SIC card provides three approaches for you to monitor your intelligent equipment and equipment room environment o Web browser You can use Web browser to monitor your intelligent equipment and equipment room environment through the Web server function provided by the SIC card e NMS You can use NMS to monitor your intelligent equipment and equipment room environment through the SNMP agent function provided by the SIC card O SiteMonitor SiteMonitor is a piece of network management software for equipment room power and environment You can use SiteMonitor to monitor your intelligent equipment and equipment room environment through the TCP IP interface provided by the SIC card The SIC card can also work with the Network Shutdown computer safe shutdown program developed by Emerson Network Power Co Ltd to provide automatic safe shutdown function for your computer installed with Network Shutdown so as to prevent data loss 1 2 Technical Specifications O Network type automatically adapt to 10 100MB s Ethernet e Concurrent Web browsers number 10 e Concurrent NMS number 10 e Protocol SNMP v2c and SNMP vi e Concurrent SiteMonitor and Network Shutdown number 200 e E Mail recipient number 10 e Total alarm records 2048 pieces e Total data records 2048 pieces Site Interface Web SNMP Agent Card User Manual 1 3 Chapter 1 SIC Card Description Models amp Appearance The SIC card is a built in card available in
33. assword IP Address 10 163 210 218 Input New Password Account Repeat Input New Password Authentication Console Network SNMP E Mail Date amp Time Identification Reboot Figure 4 13 Password change page 4 10 2 Configuring Authentication Mode Select the main menu System Configure click Authentication the page shown in Figure 4 14 will appear Through Figure 4 14 you can change the authentication mode of the SIC card into local authentication RADIUS authentication or RADIUS local authentication Through these authentication modes you can control the account whether has the authority to access SIC page In local authentication mode you can log in the SIC card through the built in admin and user account In RADIUS authentication mode you can log in the SIC card through the account admitted by RADIUS server In RADIUS local authentication mode you can log in the SIC card through all valid accounts from the two authentication modes EMERSON Y English e Network Power Equipment Monitor Alarm Manage Data Analysis System Configure siccad Current Authentication Settings Mode Local Only Status x Account admin IP Address 10 163 210 218 Account Authentication Console Network Authentication Configuration SNMP Local Only E Mail O RADIUS Only O RADIUS then Local Primary RADIUS Server 127 0 0 1 Date amp Time Identification Reboot Primary RADIUS Secret testing
34. conoonnnnnnnnnonononnnnnnnnnonnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnennnnnnnnnnnos 18 4 7 Viewing Sensor Status ANd Parameters nn0001nnnnnnnnennnennennrnnnrnrensnnnrrrrnnsrnnrrrrensnnnrrrrrnnsnnnrrrennennnrrreennnnnnrreee 19 AG WIG WING PAN INNS sec oe teats ste a a os asia be Se ah de add 19 ARB VIEWING ACIIV CCA ANINS doin 19 46 2 VIEWING HIS toca ALARMS wis ticacers ort es sane et A A id a 20 4 9 Viewing And Configuring Data Hecord meeen 20 ALO VIC WING Dala Recorrido o ls tit ri 20 4 9 2 Comiguring Data Record o EE 21 4 10 Configuring SIC Card En do dad dal le 21 4101 Gomigurna User PASS WOM BEE 21 A 10 2 Gontiguring Authentication Mode a ti 22 410 3 Gontiguring Terminal Access Mode viu it 23 4 10 4 Configuring SNMP Agent Parameters And Conducting Trap Test 24 4 10 5 Configuring E Mail Parameters And Conducting E Mail Test 27 4 10 6 Configuring Network Parameter 29 410 7 COMMGUIING System Maa o al e conta eae ial 30 4 1038 Gonfiguring Identification INfORMANON scsi id 31 ArT O29 Sy SIEM REVOO ascii unida sida ot id oi odia 31 4 11 Viewing SIC Card Version Intormaton 32 Chapter 5 Monitoring Method 2 Through NMS acisssennenei a E Ea e Ea E E EEN 33 5 1 Protocol And NMS Supported By SIC Card 33 5 2 Installing EQUINA CAM eh BS cad scented esac cw ca tee een 33 5 3 Applying For Management Authority cccccceccccsseececeseeeeceeeeeseneeeeeeeeeeseaeeeeseeeeeseaueeesseeessaueeessaeeeesseeeessaneessaess
35. e master RADIUS server is unavailable network failure or the return information shows that the login account is invalid the SIC card will turn to get information whether the login account is valid from the slave RADIUS server If any RADIUS server admits the login account is valid then this account can access the SIC page otherwise not allowed You can determine whether configure the slave RADIUS server according to your need After selecting the authentication mode and inputting the required information click the Confirm button to save it Site Interface Web SNMP Agent Card User Manual Chapter 8 Qs amp As 41 After changing the authentication mode the SIC card does not need to restart and the authentication mode will be valid in time then input the corresponding account to log in according to the prompt authentication mode As shown in Figure 4 15 the SIC card uses the authentication mode of RADIUS Local Connect to 110 163 710 218 Es aM 51C local then radius User name E Ke Remember my password Figure 8 2 Login window of authentication mode prompt LO Note 5 When selecting RADIUS Only or RADIUS then Local you need a server to realize the RADIUS protocol and must ensure that the shared cipher code is the same as that of the RADIUS server otherwise the RADIUS authentication will be invalid When the shared cipher code of the master RADIUS server is incorrect for safety reason the SIC will not c
36. ed Question 3 I just cannot use an NMS to add another one in Access Control list of the SIC card why Answer Only the system administrator can add delete or modify NMS Besides you must submit all writable properties of the NMS when you do this 8 5 Qs amp A s In SiteMonitor Monitoring Question How can SiteMonitor manage intelligent equipment through the SIC card Answer Use the configuration function of SiteMonitor to add the SIC card IP address to the configuration file of SiteMonitor and start SiteMonitor then you can use it to manage intelligent equipment 8 6 Q s amp A s In Using Network Shutdown Question How can Network Shutdown get information from the SIC card in the case of UPS alarm Answer Run Network Shutdown and enter the SIC card IP address to build up connection between the card and the computer Site Interface Web SNMP Agent Card User Manual I _ as AAA Emerson Network Power a business of Emerson NYSE EMR a global company that leads by applying a unique combination of industry expertise technology and resources to make the future of our customers enterprises and networks possible Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems embedded computing and power integrated racks and enclosures power switching and controls infrastructure management and connectivity All solutions are supported global
37. end E Mail to a person you must add this person to the recipient list in Figure 4 22 Click the Add button in the page shown in Figure 4 22 and the Recipient Setting pane will appear in the lower part of the display area as shown in Figure 4 23 where you can configure the recipient parameters Site Interface Web SNMP Agent Card User Manual Chapter 4 Monitoring Method 1 Through Web Browser amp EMERSON Y English Equipment Monitor Alarm Manage Data Analysis System Configure E Mail Server E Mail Recipient E Mail Test fanliu emersonnetwork com cn Enabled Warning Status K Pivevevesvavsvsevevsvsvarsazevsvsvsvsenenseseg Add Account admin IP Address 10 163 210 218 Account Authentication Console Network SNMP E Mail To Address Date amp Time E Mail Generation Disabled v Identification Alarm Severity Warming v Reboot Delete Figure 4 23 Adding recipient The recipient parameters include To Address E Mail Generation Alarm Severity 1 To Address The E Mail address allowed to receive E Mails from the SIC card For example martin su emersonnetwork com cn 2 E Mail Generation Whether to enable the SIC card to send E Mail that is alarm to the recipient in the case of intelligent equipment or sensor alarm e Enabled The SIC card will send alarm to the recipient O Disabled The SIC card will not send any alarm to the recipient 3 Alarm Sev
38. er address E Mail account and E Mail password EMERSON English vw Equipment Monitor Alarm Manage Data Analysis System Configure E Mail Server O E Mail Recipient O E Mail Test SMTP Server Status x From Address Account admin D identity Confien IP Address 10 163 210 218 E E mail Account Account E mail Password Authentication Console Network SNMP E Mail Date amp Time Identification Reboot Figure 4 21 E Mail server configuration page The SMTP server address must be an IP address If the SMTP server requires identity confirmation you must set the E Mail account and E Mail password Configuring E Mail Recipient Select the main menu System Configure click E Mail Configuration and select E Mail Recipient and the E Mail recipient configuration page will appear as shown in Figure 4 122 In this page you can add delete and modify recipient SZ o English ze gn Recipient list Equipment Monitor Data Analysis System Configure O E Mail Server E Mail Recipient O E Mail Test To Address E Mail Generation Alarm Severit fanliu emersonnetwork com cn Enabled Warning Alarm Manage Status x Account admin IP Address 10 163 210 218 Account Authentication Console Network SNMP E Mail Date amp Time Identification Reboot Figure 4 22 E Mail recipient configuration page 1 Adding recipient If you need to allow the SIC card to s
39. erface Web SNMP Agent Card User Manual 32 Chapter 4 Monitoring Method 1 Through Web Browser 21 Figure 4 31 Reboot progress bar 4 11 Viewing SIC Card Version Information Select the main menu About and the SIC card version information page will appear as shown in Figure 4 32 This page displays the version and update time of the application module and Linux operating system EMERSON Network Power English Equipment Monitor Alarm Manage Data Analysis System Configure Application Module Version 100B003D000 Update Time 2009 04 28 14 01 00 Linux OS Version 2 4 20_myl31 integrator Update Time 2007 10 22 18 21 13 Figure 4 32 SIC card version information page Site Interface Web SNMP Agent Card User Manual 9 1 9 2 Chapter 5 Monitoring Method 2 Through NMS 33 Chapter 5 Monitoring Method 2 Through NMS Through the SNMP agent function of the SIC card you may use an NMS to view the parameters and alarm information of the intelligent equipment and environment in real time configure the operating parameters and control the equipment In case of equipment or environment alarm the SIC card will send trap information to the NMS This chapter tells how to use an NMS to monitor your intelligent equipment and environment Protocol And NMS Supported By SIC Card The SIC card currently supports SNMP v2c and SNMP v1 NMSs supporting SNMP v1 and SNMP v2c can access the SIC card like HP OpenView
40. erity The severity of the alarms that will be sent to the recipient e Warning The SIC card will send warning alarms and critical alarms to the recipient e Critical The SIC card will send only critical alarms to the recipient After configuring the preceding recipient parameters click the Confirm button and this recipient is added to the recipient list 2 Modifying recipient If you need to modify the parameters of a recipient click the recipient address in the recipient list in the page shown in Figure 4 22 and the page shown in Figure 4 24 will appear After modifying the recipient parameters click the Confirm button to save the change EMERSON English Equipment Monitor Alarm Manage Data Analysis System Configure E Mail Server E Mail Recipient E Mail Test a o Status X fanliu emersonnetwork com cn Enabled Warning olalus Add Account admin IP Address 10 163 210 218 Account Authentication Console Network SNMP E Mail To Address fanliu emersonnetwork com cn Date amp Time E Mail Generation Enabled v Identification Alarm Severity Warning v Ze Figure 4 24 Modifying and deleting recipient Site Interface Web SNMP Agent Card User Manual Chapter 4 Monitoring Method 1 Through Web Browser 29 3 Deleting recipient If you need to delete a recipient click the recipient address in the recipient list in the page shown in Figure 4 22 and the page shown
41. escription After you enter the command setip the system will display the current SIC card network mode IP address subnet mask and gateway address Command ID 1 means to confirm the current settings that is not to change them Command ID 2 means to change them Obtain an IP address automatically The system prompts you to select whether to obtain the IP address automatically or manually set it Entering Y or y means to obtain the IP address automatically entering N or n means to manually set it If you select to manually set it you need to set the IP address subnet mask and gateway If the network address you entered is illegal the system will prompt input wrong IP Address please input again or input wrong NetMask please input again or input wrong GateWay please input again If your setting is wrong for three times the system will prompt input wrong more than 3 times and exit the setip command If the command ID you enter is invalid the system will prompt command is wrong please input again In this case please enter a valid command ID After you obtain the IP address automatically or manually set it the system will be rebooted automatically Q Note If you need to use the Dynamic Host Configure Protocol DHCP function you should contact your network administrator to make sure the system has a DHCP server It is suggested that you contact your network administrator to bind the MAC address of the SIC card with the obtained I
42. etwork time protocol TFTP trivial file transfer protocol Contents Chapter Tol Card Desc ido tates ieee 1 ERUNGO a EE 1 12 Technical SOCCIICAN OMS ti e la a a o alada oe alts 1 13 Models eler ale 2 Chaber zok Gard Instalan EE 3 2 1 System e UU EE 3 22 le ele Lef Special aan 3 2 3 e ME den An NEE 3 2 AVIS telly tC Cald gees ce A A aed eee ew sede ee 4 Chapter 3 Configuring SIC Card Basic Parameters cccccccssseecccceeeceueeseeeeeeeeeaaeeseeceeeeeseeeeeeeeeeseaeeeseeeeeeessaeaeeeeeessssaaaeess 5 Solo Loa Bolo 9 EE 5 3 14 Using TTY Or Telnet To Login SIC Card miii e a A e e 5 E o A E PE PO eee eee eer eee 6 3 2 Using Super User To Configure Basic SIC Card Parameters Through TTY Or Telnet n nn0nnnnnnonnnnnnennnnnnnnnnne 7 321 A Eet 7 3 2 2 Conliguring Basic Parameters ci di ld 7 3 3 Using Reset User To Configure Basic SIC Card Parameters Through ITIN 10 a eo Ee ee HIM Le EE 10 3 92 CONNGUENG BASIC Parametros 10 Chapter 4 Monitoring Method 1 Through Web Browser 12 4 1 Checking Web Browser Gettngs nnee 12 4 2 Jsing Web Browser TO Log SIG Sad dci 13 43 Monitoring ee une Le Sii indi is 14 A A Addis da diodo old 15 4 5 VIEWING Equipment EE 15 4 6 Controlling And Configuring Equipment Remotely occcooccooccccnnccccoconnncnnnncnonononononnnonononnnnnnnnnnnonnnanennnnnnonnnanennnns 17 46 1 GOntrolImgEquipment Remote EE 17 4 6 2 Configuring Equipment Remotely oocccccnccccccconccnnncc
43. font and close less useful tool bars to increase the valid display area 4 2 Using Web Browser To Login SIC Card Login Start the Web browser type the IP address of the SIC card and the login interface will appear as shown in Figure 4 1 Enter Network Password Please type the User Mame and Password that you use for SIC UserName Emmin F Password ES Iw Save this password in your password list Cancel Figure 4 1 Login SIC card Enter your user name and password and click the OK button LU Note For the first time you access the new SIC cad through Web browser you must login with super user s name admin and password admin by default Language selection After your user name and password pass the verification the monitoring homepage of the SIC card will appear as shown in Figure 4 2 Main menu area English EMERSON Network Power Equipment Monitor Alarm Manage Data Analysis System Configure About sie cara Overview O Metering O Control O configuration Delete admin Base Information Account 5 142 100 39 91 Status GIA Address Kee Type UH11 UPS System fat A4 AEE Comm Port RS232 Time 2009 05 11 21 46 50 Aras o Comm Param 4800 n 8 1 Input Voltage 225 00 V Output Voltage 220 00 V Battery Mode Float charging Y IRM SO2TH 1 Load 80 00 Battery Capacity 80 00 AE DET Alarms 2000 06 01 19 11 03 UH11 UPS S ups Rectifier Fault 2000 06 01 19 10
44. gure click Identify Configuration and the identification information configuration page will appear as shown in Figure 4 28 In this page you can configure the host name contact information and location of the SIC card EMERSON Network Power Status K Account admin IP Address 10 163 210 218 Account Authentication Console Network SNMP E Mail Date amp Time Identification Reboot 4 10 9 System Reboot English Equipment Monitor Alarm Manage Data Analysis System Configure Identification Name Contact Location Figure 4 28 Identification information configuration page Select the main menu System Configure click Reboot the page shown in Figure 4 29 will appear You can click the Confirm button to restart the SIC card As shown in Figure 4 30 and Figure 4 31 the pages displays the prompt SIC will reboot now Please wait EMERSON Network Power x admin Status Account IP Address 10 163 210 218 Account Authentication Console Network SNMP E Mail Date amp Time Identification Reboot and reboot progress bar and you should wait till the reboot is finished English Equipment Monitor Alarm Manage Data Analysis System Configure This action reboots the Site Interface Card Continue Figure 4 29 SIC reboot page ES A SIC will reboot now Please wait Microsoft Internet Explorer Figure 4 30 Reboot prompt page Site Int
45. he SIC card for the first time how to use TTY to make connection Answer Before inserting the SIC you must start the TTY and use the accessory USB cable to connect the intelligent equipment with the computer Because it takes only about five seconds to start the card you cannot see the start process if you do not run TTY before inserting the card If you do have started TTY before inserting the card but cannot see the process refer to the answer to Question 2 in 8 2 Q s amp A s In Running Besides please install the USB driver in the CD delivered with the SIC card and find the serial port of CP2101 USB to UART on the menu COM amp PT in Device Manager and remember it You need to use this serial port to make connection Question 3 Can I finish the installation without computer at hand to run Hyper Terminal Answer No if you don t know the IP address If you know the IP address or if it is a new card default address 192 168 1 1 you may use the following steps to configure your card through Telnet mode 1 Connect the card to the network 2 Modify the network parameters of a computer located in the same LAN better in the same HUB or switch with the card to get them in the same network section Suppose the card IP address is 192 168 1 1 subnet mask 255 255 255 0 gateway 0 0 0 0 then the computer IP address can be 192 168 1 2 subnet mask 255 255 255 0 gateway 0 0 0 0 3 Reboot the computer connect to the card in Telnet
46. her code is the same as that of the RADIUS server otherwise the RADIUS authentication will be invalid When the shared cipher code of the master RADIUS server is incorrect for safety reason the SIC will not continue to get information from the slave server considering there is a third party attack 8 To ensure the safety of the RADIUS authentication you should modify the shared cipher code of the RADIUS server and SIC card regularly 8 4 3 Configuring Terminal Access Mode Select the main menu System Configure click Console the page shown in Figure 4 16 will appear Through this page you can change the debugging terminal remote login mode of the SIC card into Telnet or SSH D Zi English Equipment Monitor Alarm Manage Data Analysis System Configure Current Console Settings Mode Telnet Access Status x Account admin IP Address 10 163 210 218 Account Authentication Console Network Console Configuration SNMP Telnet Access E Mail Telnet Port 23 23 5000 32768 Date amp Time O SSH Access i SSH Port 22 22 5000 32768 Identification Reboot Figure 8 6 Network parameter setting page The upper part of the page displays Current Console Settings through Mode you can view the terminal access mode of the current configuration the lower part of the page displays Console Configuration you can select Telnet Access or SSH Access If you need to change the terminal access mode selec
47. ill diagnose and handle it 4 Setip set the SIC card IP address subnet mask and gateway address If the SIC card is installed for the first time or moved from one LAN to another you must set the card network parameters including the IP address through TTY Configuration method type setip after sic_admin Configuration steps see Figures 3 8 through 3 10 lsic_admintsetijp Mode static IP Address 1927 168 1 1 Subnet Mask t 205 255 255 0 Default Gateway 0 0 0 0 1 confirm current setting 2 modify current setting please select the command id Figure 3 8 Select the command ID Site Interface Web SNMP Agent Card User Manual Chapter 3 Configuring SIC Card Basic Parameters 9 sic_acdmin tzetip Mode static IP Address 192 165 1 1 Subnet Mask 205 205 255 0 Default Gateway 0 0 0 0 li confirm current 2 modify current Please select the command idt2 Obtain an IP address automatically dru The system is going down HUN Figure 3 9 Obtain an IP address automatically sic_admintsetip Me ji de t tatic PIP Address 192 165 1 1 subnet Mask Zod geod geo 0 Default Gateway 0 0 0 0 fi confirm Borer 2 modify current please select the command idt2 Obtain an IP address automatically dc input IP Address 142 100 0 46 Pinput HetMask 1255 255 254 0 input Default Gatebay 142 100 8 1 The system is going down HUN Figure 3 10 Set SIC card IP address Interface d
48. l appear Site Interface Web SNMP Agent Card User Manual Chapter 4 Monitoring Method 1 Through Web Browser 19 4 7 Viewing Sensor Status And Parameters Select the main menu Equipment Monitor click IRM S02TH 1 under Sensor and the status data graphs basic information and active alarms of the sensor will be displayed as shown in Figure 4 8 The basic information of the sensor mainly provides the basic parameters of the sensor besides the sensor name status icon and so on Status data graphs Basic information EMERSON Y English se Equipment Monitor Alarm Manage Data Analysis System Configure Abot Base Information Account admin Sensor Name deer E IP Address 142 100 9 91 Sie Status L e m A den 5 11 Port COM1 ES ALTO Address 1 Device Temperature Max 502G Temperature 26 10 C J EE X UH11 UPS Temperature alarm CC 1 00 Temperature alarm upper limit T 35 00 Temperature alarm upper limit shield Temperature alarm lower limit 7 0 00 Temperature alarm lower limit Enable Sensor 3 Enable shield x Huminity alarm 5 00 Humidity 84 90 Huminity alarm upper limit 80 00 Huminity alarm upper limit shield Enable AO NEO EA Huminity alarm tower Wutz 10 00 2009 05 11 SS initv al imit shi GEES IRM SO2TH 1 8 over huminity Huminity alarm lower limit shield Enable Add Device Active alarms Figure 4 8 Sensor status and parameter page 4 8 Viewi
49. log in the SIC card through the account admitted by RADIUS server In RADIUS local authentication mode you can log in the SIC card through all valid accounts from the two authentication modes Site Interface Web SNMP Agent Card User Manual 34 Chapter 5 Monitoring Method 2 Through NMS EMERSON Y English Equipment Monitor Alarm Manage Data Analysis System Configure eeng Current Authentication Settings Mode Local Only Status wi Account admin IP Address 10 163 210 218 Account Authentication Console Network Authentication Configuration SNMP Local Only E Mail RADIUS Only RADIUS then Local Primary RADIUS Server 127 0 0 1 Date amp Time Identification Reboot Primary RADIUS Secret testing123 Secondary RADIUS Server Secondary RADIUS Secret Figure 5 1 Authentication settings page The upper part of the page displays Current Authentication Settings through Mode you can view the authentication mode of the current configuration the lower part of the page displays Authentication Configuration you can select Local Only RADIUS Only RADIUS then Local that is RADIUS Local If you select RADIUS Only or RADIUS then Local you need to input the IP address and shared cipher code of the RADIUS server To ensure the stability of the RADIUS authentication the SIC card provides two RADIUS servers which are master and slave
50. login interface and the command prompt super user is sic_admin as shown in Figure 3 2 and reset user is sic_reset as shown in Figure 3 3 Site Interface Card Montavistatk LinuxtR Professional Edition 4 1 EEE EEE EEE EE EE EEE EEE EEE EE EEE EEE EEE EEE EE EEE EEE EEE EEE EE EEE EEE EEE EEE EEE ig JO ai al TEE ga s i em Se Ze zeg im Service Terminal for Site Interface Card Copyright ic 2008 2010 Emerson Hetwork Power Co Ltd ALL RIGHTS RESERVED Version 1 0 Date 2008 4 16 Di EEEIEE sic_admin Figure 3 2 Successful login of super user Site Interface Card MontaVvistalR LinuxlFR Professional Edition 3 1 Ce ee ee e Oe de e ee Oe Oe ee ee Oe ee ee e e e o o e e e e E o a ab service Terminal for Site k Copyright c 2008 2010 Emerson Network Power Co Ltd k Ka zk Version 1 0 Hate 2008 4 16 W E Ka KIK oie ee Oe ee ee ee ee o o e e e ae sk ALL RIGHTS RESERVED Hk HE Figure 3 3 Successful login of reset user If your user name or password is incorrect the system will not allow you in and will prompt you to enter them again LO Note 1 Only the super user admin can log in the SIC card through Hyper Terminal or Telnet The default password of admin is admin The password is case sensitive 2 Reset user reset is the user name can access the SIC card through Hyper Terminal The password id reset which can not be changed The password is ca
51. ly by local Emerson Network Power service technicians While every precaution has been taken to ensure the accuracy and completeness of this literature Emerson Network Power assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions All rights reserved throughout the world Specifications subject to change without notice All names referred to are trademarks or registered trademarks of their respective owners 31012110 V2 1 www EmersonNetworkPower com
52. mputer With Network Shutdown The computer safe shutdown program Network Shutdown is developed by Emerson Network Power Co Ltd In case of UPS alarm the SIC card will send alarm information to the preset computer installed with Network Shutdown Network Shutdown receives and processes the alarm information and take the following protective measures to protect the computer according to the user configurations e Notify the administrator e Execute the command file O Save the application files automatically and shutdown the computer For the installation and operation of Network Shutdown refer to Network Shutdown Software UNIX 8 Netware Version User Manual and Network Shutdown Software Windows Version User Manual Site Interface Web SNMP Agent Card User Manual 38 8 1 Chapter8 Q s amp A s Chapter 8 Q s 8 As This chapter introduces the Q s A s in the daily use of the SIC card In case you encounter any problems you are recommended to seek solution in this chapter before seeking technical assistance from the local customer service center of Emerson Q s amp A s In Installation Question 1 The indicators remain off after installation Answer The UPS is shut down or has not been connected to the utility Turn on the UPS If the UPS cannot be turned on check the connection of UPS with the utility and connect the network cable then observe if the indicators turn on Question 2 When using the USB interface of t
53. n 192 162 4 1 255 255 255 0 authenticator EE EE console ai eas tea cian console lo r r r r r o D no om ot c ct oct ct et T 10 WM D Slic_reset Figure 3 12 Command supported by TTY and Telnet in reset user 3 3 2 Configuring Basic Parameters Type a command behind sic_reset If the command is incorrect the system will prompt command not found If you have typed a command corresponding to a parameter the system will resume the default setting of corresponding parameters After every command is executed the SIC card will restart as shown in Figure 3 13 Site Interface Web SNMP Agent Card User Manual Chapter 3 Configuring SIC Card Basic Parameters 11 Sic_reset all The system 1s going down NOL sending SIGTERM to all pr sending SIGKILL to all processes Please stand by while re Restarting system Testing Watchdog Figure 3 13 Command executed in reset user LO Note 1 When inputting command the SIC card can support fast identification that 1s use the front several characters used to distinguish this command to represent the whole command input and without inputting the whole command For example pass means password 2 Reset user reset is the user name can access the SIC card only through Hyper Terminal The password id reset which can not be changed The password is case sensitive Site Interface Web SNMP Agent Card User Manual 12 4 1 Chapter 4 Monitoring
54. n RADIUS authentication mode you can log in the SIC card through the account admitted by RADIUS server In RADIUS local authentication mode you can log in the SIC card through all valid accounts from the two authentication modes D EMERSON English Equipment Monitor Alarm Manage Data Analysis System Configure eeng Current Authentication Settings Mode Local Only Status gt Account admin IP Address 10 163 210 218 Account Authentication Console Network SNMP Local Only E Mail O RADIUS Only O RADIUS then Local Primary RADIUS Server Date amp Time Identification Reboot Primary RADIUS Secret Secondary RADIUS Server Secondary RADIUS Secret Figure 8 1 Authentication settings page The upper part of the page displays Current Authentication Settings through Mode you can view the authentication mode of the current configuration the lower part of the page displays Authentication Configuration you can select Local Only RADIUS Only RADIUS then Local that is RADIUS Local If you select RADIUS Only or RADIUS then Local you need to input the IP address and shared cipher code of the RADIUS server To ensure the stability of the RADIUS authentication the SIC card provides two RADIUS servers which are master and slave The SIC card first get the information whether the login account is valid from the master RADIUS server When th
55. n control the account whether has the authority to access SIC page In local authentication mode you can log in the SIC card through the built in admin and user account In RADIUS authentication mode you can log in the SIC card through the account admitted by RADIUS server In RADIUS local authentication mode you can log in the SIC card through all valid accounts from the two authentication modes amp EMERSON English Equipment Monitor Alarm Manage Data Analysis System Configure Current Authentication Settings Mode Local Only Status X Account admin IP Address 10 163 210 218 Account Authentication Console Network Authentication Configuration SNMP Local Only E Mail O RADIUS Only O RADIUS then Local Primary RADIUS Server Date amp Time Identification Reboot Primary RADIUS Secret Secondary RADIUS Server Secondary RADIUS Secret Figure 8 4 Authentication settings page The upper part of the page displays Current Authentication Settings through Mode you can view the authentication mode of the current configuration the lower part of the page displays Authentication Configuration you can select Local Only RADIUS Only RADIUS then Local that is RADIUS Local If you select RADIUS Only or RADIUS then Local you need to input the IP address and shared cipher code of the RADIUS server To ensure the stability of
56. ng Alarms 4 8 1 Viewing Active Alarms Select the main menu Alarm Manage click Active Alarms and the active alarm page will appear as shown in Figure 4 9 In this page you can view all active alarms of the monitored intelligent equipment and sensors EMERSON zi English e Network Power Equipment Monitor Alarm Manage Data Analysis System Configure HT DEC EEE 2000 06 01 19 11 03 UH11 UPS ups Rectifier Fault m 2000 06 01 19 10 57 UH11 UPS Aups Asynchronous Status Account admin IP Address 142 100 9 91 Active Alarms History Alarms Figure 4 9 Active alarm page Site Interface Web SNMP Agent Card User Manual 20 Chapter 4 Monitoring Method 1 Through Web Browser 4 8 2 Viewing Historical Alarms Select the main menu Alarm Manage click History Alarms and the historical alarm page will appear as shown in Figure 4 10 In this page you can view all historical alarms of the monitored intelligent equipment and sensors amp EMERSON English Equipment Monitor Alarm Manage Data Analysis System Configure es Start Time End Time Name Alarms 2009 05 11 21 45 51 2009 05 11 21 46 30 IRM SO2TH 1 Gover huminity 2009 05 11 21 33 00 2009 05 11 21 34 58 IRM SO2TH 1 Gover huminity Stanis 2009 05 11 21 26 32 2009 05 11 21 27 15 UH11 UPS over Temperature Account admin 2009 05 11 21 26 28 2009 05 11 21 27 15 UH11 UPS ups overload IP Address 142 100 9 91 2009 05 11 21 26 25 2009 05 11 21 27 18 UH11 UPS ups Output Sho
57. nsor Y IRM S02TH 1 Add Device Equipment Monitor Alarm Manag 2009 05 11 21 49 12 Remote control parameter list Basic information 2 English M D Data Analysis System Configure Abot O Overview O Metering O Control O Configuration Delete O Delay Shutdown Base Information Status O Cancel Delay Shutdown SIA Type UH11 UPS O Turn On UPS Instantly Comm Port RS232 Address O O Battery Self Test O Cancel Battery Self Test as O Alarm Silence O UPS Audible Alarm Test Confirm UPS Mode On Line Battery Mode Float charging 2000 06 01 19 11 03 UH11 UPS L UPS Rectifier Fault 2000 06 01 19 10 57 UH11 UPS AN ups Asynchronous more alarms gt Active alarms Figure 4 6 Remote control page In the remote control parameter list you can select a command and click the Confirm button to submit the command to the SIC card If the SIC card successfully sends the command the prompt Success will appear otherwise the prompt Communication Interrupt Remote Control Failed will appear Site Interface Web SNMP Agent Card User Manual 18 Chapter 4 Monitoring Method 1 Through Web Browser 4 6 2 Configuring Equipment Remotely Select the main menu Equipment Monitor click UH11 UPS under Device and select Configuration and the remote configuration page will appear as shown in Figure 4 7 This page displays the remote configuration parameter list basic information and active
58. ntelligent equipment Retain the screws and the cover for use in the future Refer to the user manual of the intelligent equipment for the location of the SNMP interface or intellislot intelligent slot 2 Insert the SIC card into position along the guide grooves on both sides of the SNMP interface or intellislot intelligent slot and tighten the screws 3 Connect the network cable to the RJ45 interface see Figure 1 1 of the SIC card At this point you will see the green indicator LAN indicator turn on When the card is connected to the network and there is ongoing data exchange the yellow indicator RUN indicator will blink indicating the card is working Observe the Hyper Terminal screen on the computer and you will see the SIC card login information as shown in Figure 2 1 Insmod Device Driver Emerson SNMP WDT driver version 1 00 Found AT91 ls PCF8563 Real Time Clock Driver Revision 1 16 Emerson SNMP FLASH driver version 1 00 Emerson SNMP SPI driver version 1 00 sic login Figure 2 1 SIC card login information If the yellow indicator is off please check whether the SIC card is connected to the network and whether there is something wrong with the network cable 4 If you need to monitor more pieces of intelligent equipment or connect the SIC card to sensors please connect the RJ45 interface of the RS485 optional card of the intelligent equipment or the RJ45 interface of the sensor to the COM1 or COM2 interf
59. o your dealer Installation Preparation Before installation 1 Use the delivery accessory USB communication cable to connect the USB interface of the computer to that see Figure 1 1 of the SIC card For the first time the SIC card is installed please install the USB driver from the CD delivered with the SIC card and note down the used serial port number of the computer according to the answer to question 2 in 8 1 Q s amp A s In Installation 2 Start Hyper Terminal and correctly configure the serial port property of the Hyper Terminal according to the instructions provided in the part Using TTY to login SIC card in 3 1 1 Using TTY Or Telnet To Login SIC Card Note that the serial port for Hyper Terminal must be the one connected to the SIC card 3 Prepare a category 5 twisted pair cable for connecting the card to the Ethernet and connect one end to the network LO Note For 100MB Ss Ethernet please use super category 5 twisted pair cable meeting EIA TIA 568 standard Otherwise the network cable length must be limited within 100m and the conducted emission will increase slightly Site Interface Web SNMP Agent Card User Manual 2 4 Chapter 2 SIC Card Installation Installing SIC Card EJ Note The SIC card is hot pluggable you can install 1t without turning off the intelligent equipment Use the following procedures to install the SIC card 1 Remove the cover of the SNMP interface or intellislot intelligent slot of the i
60. on SNMP Obtain an IP address automatically E Mail Use the following IP address i IP Add 410 163 210 218 Date amp Time dia A Subnet Mask 255 255 254 0 Identification Default Gateway 10 163 210 1 Reboot Figure 4 26 Network parameter configuration page The display area displays in the upper part Current Network Settings including Mode IP Address Subnet Mask Default Gateway MAC Address in the lower part Network Configuration where you can select Obtain an IP address automatically or Use the following IP address that is to set the IP address manually To change the network parameters select Use the following IP address and type the new network parameters including IP Address Subnet Mask and Default Gateway and click the Confirm button to save the change Site Interface Web SNMP Agent Card User Manual 30 4 10 7 Chapter 4 Monitoring Method 1 Through Web Browser After you change the network parameters the SIC card will be rebooted automatically Please wait one minute and use the new address to login the SIC card again LO Note 1 Before you select Use the following IP address please confirm with you IT system administrator that DHCP server system is available in the network Meanwhile it is suggested that you contact your network administrator to bind the MAC address of the SIC card with the obtained IP address so that the current IP address will be allocated to the SIC card in futu
61. ontinue to get information from the slave server considering there is a third party attack 6 To ensure the safety of the RADIUS authentication you should modify the shared cipher code of the RADIUS server and SIC card regularly 8 4 2 Configuring Terminal Access Mode Select the main menu System Configure click Console the page shown in Figure 4 16 will appear Through this page you can change the debugging terminal remote login mode of the SIC card into Telnet or SSH EMERSON English KA Equipment Monitor Alarm Manage Data Analysis System Configure About eeng Current Console Settings Mode Telnet Access Status X Account admin IFP Address 10 163 210 218 Account Authentication Console Network Console Configuration SNMP Telnet Access E Mail Telnet Port 23 23 500032768 Date amp Time SSH Access SSH Port 27 Identification i 22 5000 32768 Reboot Figure 8 3 Network parameter setting page The upper part of the page displays Current Console Settings through Mode you can view the terminal access mode of the current configuration the lower part of the page displays Console Configuration you can select Telnet Access or SSH Access If you need to change the terminal access mode select Telnet Access or SSH Access and change the access port Telnet access has the port number 23 default or 5000 32768 SSH access has the port number 22 default
62. re IP address allocation 2 Do not change the network parameters at will If the IP address you configured conflicts with that of other network equipment like computer they cannot be accessed So please consult your network administrator to obtain the network parameters 3 The connection between the SIC card and SiteMonitor Network Shutdown and NMS will be interrupted due to the change of the network parameters Therefore after changing the network parameters please re configure the relevant Site Monitor Network Shutdown and NMS Configuring System Time Select the main menu System Configure click Time Configuration and the system time configuration page will appear as shown in Figure 4 27 EMERSON English Network Power Equipment Monitor Alarm Manage Data Analysis System Configure Current Date amp Time Settings Mode Manual Date 2011 02 11 Status x Time 15 52 05 Account admin Time Zone 08 00 hours Beijing Hong Kang IP Address 10 163 210 218 Account Authentication Console binat SNMP Manual E Mail Date 2011 02 11 Date amp Time Time 15 52 05 Identification O Apply local computer time O Automatic Reboot i See Primary NTP Server Secondary NTP Server i 0 0 0 Time Zone 08 00 hours Beijing Hong Kona Figure 4 27 System time configuration page The display area displays in the upper part Current Data amp Time Settings in the lower par
63. rs Enter new password maximum of 41 ch Warning Warning weak password too simplelcontinuing Re enter new password Password changed sic_admin l Figure 3 6 Modify login password Interface description Input the new password 31 at most the password will not be displayed Confirm the new password If the password is not strong enough the following warning will be displayed Warning weak password too short continuing Warning weak password too simple continuing 2 ping check if the destination address is reachable The ping command is used to test whether data from the SIC card can be sent to certain computer through network Configuration method type ping after sic_admin Configuration steps see Figure 3 7 51c_adm1n p1ng Please enter an IP address 177 0 0 1 PING 127 0 0 1 127 0 0 1 56 data bytes 84 bytes from 127 0 0 1 1cmp_seqg 0 ttl 64 time 0 4 84 bytes from 127 0 0 1 1cmp_seg 1 ttl 64 time 0 3 84 bytes from 127 0 0 1 MA ttl 64 time 0 3 84 bytes from 127 0 0 1 1cmp_seqg 3 ttl 64 time 0 3 127 0 0 1 ping statistics 4 packets transmitted 4 packets received 0 packet loss round trip minfavg fmax 0 3 0 3 0 4 ms s1c_admin _ Figure 3 7 Ping command 3 Setmode The SIC card should be in normal operating state Setmode command is used for resuming the SIC card to normal operating mode if the SIC card has incorrect operating mode Generally the customer service w
64. rt Circuit 2009 05 11 21 26 22 2009 05 11 21 27 22 UH11 UPS ups Charger Fault Current Alarms 2009 05 11 21 26 18 2009 05 11 21 27 25 UH11 UPS ups Inverter Fault History Alarms 2000 06 01 19 10 05 2000 06 01 19 10 50 UH11 UPS 8communication Interrupt Figure 4 10 Historical alarm page 4 9 Viewing And Configuring Data Record 4 9 1 Viewing Data Record Select the main menu Data Analysis click Data Record and the data record page will appear as shown in Figure 4 11 EMERSON English Device List UH11 UPS O Last 1 Hour From 2009 05 11 20 42 09 To 2009 05 11 21 42 09 Status x Export Type Microsoft Excel Document xls Y Export Account admin IP Address 142 100 9 91 Input Voltage V Input Frequency Hz Output Voltage V Output Current 4 Output Frequency Hz Loa Data Record 2009 05 11 21 22 07 225 00 50 00 220 00 220 00 50 00 SC 2009 05 11 21 32 08 225 00 50 00 220 00 220 00 50 00 SC Setting 2009 05 11 21 42 09 225 00 50 00 220 00 220 00 50 00 BC Figure 4 11 Data record page You can select your desired intelligent equipment or sensor from the Device List drop down box and define the data record query period the latest 1 hour by default The data record page can display up to 2048 pieces of data records of the selected intelligent equipment or sensor You can also export the displayed data record in Excel XML or Text format Site Interface Web SNMP Agent Card User Manual
65. s to the SIC card Refer to Question 2 in 8 1 Q s amp A s In Installation to obtain the serial port No Refer to Table 3 1 for serial port configuration Table 3 1 TTY serial port configuration ee IC ES SE Stop bi Flow conto After the SIC card starts up press the Enter key and the system will prompt login information Using Telnet to login SIC card To log in SIC card you can use the Telnet client from the operation system Type the telnet SIC card IP address in the command line for example telnet 10 76 12 228 and the system will prompt login information Using SSH to login SIC card The client for supporting SSH2 is required To successfully log in SIC card you should configure the correct host IP address IP address of SIC card and access port in client then enter the user name and password Login information Figure 2 1 shows the login information Enter the user name and password The password will not be displayed as shown in Figure 3 1 Insmod Device Driver Emerson SNMP WDT driver version 1 00 Found AT91 12c PCF8563 Real Time Clock Driver Revision 1 16 Emerson SNMP FLASH driver version 1 00 Emerson SNMP SPI driver version 1 00 sic login admin Password Figure 3 1 Enter user name and password Site Interface Web SNMP Agent Card User Manual 5 6 Chapter 3 Configuring SIC Card Basic Parameters If you login successfully the system will display the
66. se sensitive 3 For Telnet mode only two users can login at the same time 3 1 2 Logout Manual Logout After configuring the basic parameters of the SIC card you may type the exit or logout command to logout Automatic Logout If you have not done any key operation within five minutes the system will log you out automatically to ensure system safety Re login after logout If you adopt TTY mode you may simply re enter your user name and password to re login but in Telnet mode you have to rebuild Telnet connection Site Interface Web SNMP Agent Card User Manual Chapter 3 Configuring SIC Card Basic Parameters 7 3 2 Using Super User To Configure Basic SIC Card Parameters Through TTY Or Telnet 3 2 1 Basic Commands TTY and Telnet in super user support the commands shown in Table 3 2 Table 3 2 Command supported by TTY and Telnet Command Description Set the SIC card as a normal operating mode View SIC card application version and operation system version After you log in the SIC card type the command help or after sic_admin and press the Enter key the system will prompt all the commands and their descriptions as shown in Figure 3 4 Sic_admin Following commands are supported E alias for help help print online help log logout from the current console change setmode set normal mode setip set ip address t modbus addi vers1on vlew version info E d se Sic_admin Figure
67. sword and there is no error message but the homepage does not come next why Answer Because the SIC card homepage is programmed by JavaScript this problem may be caused by the following two reasons 1 You have installed anti virus firewall the software cannot identify normal web pages or web pages that contain virus so the homepage cannot be displayed Please configure or close the firewall software 2 JavaScript is disabled in your Web browser To visit the SIC card web page you must enable JavaScript Refer to the part Enabling JavaScriptin 4 1 Checking Web Browser Settings 8 4 Q s amp A s In NMS Monitoring Question 1 Why timeout error often occurs when NMS is visiting the SIC card Answer This may be caused by the following three reasons 1 The NMS is not in the Access Control list of the SIC card Ask the system administrator to add it in the Access Control list Refer to the Configuring SNMP Agent Parameters part in 4 10 2 Configuring Authentication Mode Select the main menu System Configure click Authentication the page shown in Figure 4 14 will appear Through Figure 4 14 you can change the authentication mode of the SIC card into local authentication RADIUS authentication or RADIUS local authentication Through these authentication modes you can control the account whether has the authority to access SIC page In local authentication mode you can log in the SIC card through the built in admin and user account I
68. t Telnet Access or SSH Access and change the access port Telnet access has the port number 23 default or 5000 32768 SSH access has the port number 22 default or 5000 32768 After changing the terminal setting the SIC card does not need to restart and the terminal access mode will be valid in time then the link built through the original access mode will automatically disconnect UI Note 10 SSH2 is the SSH version supported by SIC card which only supports the authentication mode of user name password 11 When selecting the terminal access mode SSH you need the client supporting SSH2 then configure the correct host IP address IP address of SIC card and access port in the client Site Interface Web SNMP Agent Card User Manual 44 Chapter8 Q s amp A s 12 Only the super user user name is admin is allowed to log in Telnet through Telnet or access SIC card in SSH mode The default password of super user is admin case sensitive Configuring SNMP Agent Parameters And Conducting Trap Test 3 Network error Check the network connection Question 2 When NMS attempts to configure SIC card parameters genErr is replied why Answer genErr occurs when 1 The NMS is lack of control authority 2 The SIC card fails in sending the configuration request of the NMS to the intelligent equipment Please check whether the parameters sent by the NMS are correct and whether a communication failure trap is receiv
69. t Data amp Time Configuration pane where you can set the current date time and time zone of the SIC card with two options of configuration mode available Manual and Automatic 1 Manual select Apply local computer time to obtain the date and time of the computer or type the date and time respectively in the Date and Time boxes In either way the system will automatically obtain the time zone of the computer 2 Automatic That is to choose the time server for timing Please type the IP addresses of the primary NTP server and secondary NTP server and select the time zone The time servers comply with NTP or SNTP time protocol After configuring the preceding parameters click the Confirm button LO Note 1 If no time server is available or the time server has not been configured you must reconfigure the system time after you install the SIC card for the first time or the card is rebooted for reasons like changing IP address so as to ensure that the card time is consistent with the real time 2 If the time server is available and accessible the SIC card time will be automatically calibrated by the time server after you install the card for the first time or the card is rebooted for reasons like changing IP address Site Interface Web SNMP Agent Card User Manual Chapter 4 Monitoring Method 1 Through Web Browser 31 4 10 8 Configuring Identification Information Select the main menu System Confi
70. tem requirement including software environment and hardware environment and installation of the SIC card If you need to install the SIC card in your intelligent equipment please read this chapter and Chapter 3 carefully If you have already installed the SIC card and just want to use Web browser or NMS to monitor your intelligent equipment through the SIC card you may skip this chapter and Chapter 3 Tells you how to configure the basic parameters such as IP address of the SIC Chapter 3 Configuring SIC Card card through Hyper Terminal and telnet After installing the SIC card for the first Basic Parameters time you must configure its basic parameters before you can use it to monitor your intelligent equipment and the environment Tells you how to use Web browser to monitor your intelligent equipment and the Chapter 4 Monitoring Method 1 environment through the SIC card If you need to use Web browser to monitor your Through Web Browser intelligent equipment and the environment through the SIC card please read this chapter carefully Tells you how to use the NMS to monitor your intelligent equipment and the Chapter 5 Monitoring Method 2 environment through the SIC card If you need to use the NMS to monitor your Through NMS intelligent equipment and the environment through the SIC card please read this chapter carefully Tells you how to use the SiteMonitor software to monitor your intelligent equipment Chapter 6 Monitoring Method 3 and the en
71. terface l configuration Site Interface Web SNMP Agent Card User Manual 2 1 2 2 2 3 Chapter 2 SIC Card Installation 3 Chapter 2 SIC Card Installation This chapter deals with the SIC card installation including the system requirement unpacking inspection installation preparation and procedures of the SIC card LJ Warning Some electronic components on the SNMP card are sensitive to static electricity Do not touch the circuit or components with hands or through electrified articles otherwise the card might be damaged Hold the side edges when moving or installing the card System Requirement Hardware requirement e Emerson intelligent equipment with SNMP interface or intellislot intelligent slot matching your SIC card size IRM series sensors Software requirement 1 Local area network LAN metropolitan area network MAN or wide area network WAN 10 MB s or 100MB s Ethernet using TCP IP protocol and HTTP protocol 2 Computer with one of the following installed o Web browser Internet Explorer 5 0 or above FireFox 1 0 or above e NMS compatible with SNMPv1 and SNMP v2c protocols HP OpenView IBM NetView Novell ManageWise or SunNet Manager and so on e Emerson developed SiteMonitor a network management software for equipment room power and environment Unpacking Inspection Open the package of the SIC card take out the delivery list and check the goods against the delivery list Report any discrepancy t
72. the RADIUS authentication the SIC card provides two RADIUS servers which are master and slave The SIC card first get the information whether the login account is valid from the master RADIUS server When the master RADIUS server is unavailable network failure or the return information shows that the login account is invalid the SIC card will turn to get information whether the login account is valid from the slave RADIUS server If any RADIUS server admits the login account is valid then this account can access the SIC page otherwise not allowed You can determine whether configure the slave RADIUS server according to your need After selecting the authentication mode and inputting the required information click the Confirm button to save it After changing the authentication mode the SIC card does not need to restart and the authentication mode will be valid in time then input the corresponding account to log in according to the prompt authentication mode As shown in Figure 4 15 the SIC card uses the authentication mode of RADIUS Local Site Interface Web SNMP Agent Card User Manual Chapter 8 Qs amp As 43 Connect to 110 163 710 218 Ze zi 51 local then radius User name E Ke Remember my password Figure 8 5 Login window of authentication mode prompt LU Note 7 When selecting RADIUS Only or RADIUS then Local you need a server to realize the RADIUS protocol and must ensure that the shared cip
73. two models UF SNMP710 and UF SNMP810 Its appearance is shown in Figure 1 1 Its hardware functions are described in Table 1 1 LI Note The SIC card should be inserted in the SNMP interface or intellislot intelligent slot of the Emerson intelligent equipment The two models of the card look completely the same except that they differ slightly in size to suit the SNMP interface or intellislot intelligent slot of different specifications LAN indicator COM2 interface RUN indicator COM1 interface Front panel Front panel dy EMERSOWN etweorh Powe SIC card interface RJ45 interface USB interface Figure 1 1 SIC card appearance Table 1 1 SIC card hardware description Function Off The network cable is not connected On The network cable is connected On The SIC card is on Blink once every second The communication between the SIC card and the main equipment the RUN indicator yellow intellligent equipment that accommodates the SIC card is normal Blink once every five seconds The communication between the SIC card and the main equipoment is interrupted LAN indicator green COM1 interface Connect to intelligent equipment or sensor COM2 interface RJ45 interface Connect to the network SIC card interface To be inserted into SNMP interface or intellislot intelligent slot of intelligent equipment l Connect to computer by means of the accessory USB communication cable Used for parameter USB in
74. ty Community string for getting SIC card variables the default is public 5 Write Community Community string for getting and setting SIC card variables the default is private LO Note The community strings are the passwords for the NMS to access the SIC card The passwords are case sensitive After configuring the preceding access control parameters click the Confirm button and the NMS is added to the NMS information list Site Interface Web SNMP Agent Card User Manual 26 Chapter 4 Monitoring Method 1 Through Web Browser 2 Configuring NMS To configure the access control parameters of an NMS click the NMS IP address in the NMS information list in the page shown in Figure 4 17 and the page shown in Figure 4 19 will appear After configuring the NMS access control parameters click the Confirm button to save the configuration amp EMERSON English Equipment Monitor Alarm Manage Data Analysis System Configure Access Control Trap Test NMS IP Address Access Type______ ffrapLevel Read Community Write Communit 3 SCC 100 8 132 Ge Write Enabled Ge private Account admin IP Address 10 163 210 218 Account Authentication Console Network SNMP E Mail NMS IP 142 100 8 132 Date amp Time Access Type Read WWrite v identification Trap Level Enabled v Reboot Read Community public Write Community private Figure 4 19 Configuring and deleting
75. vironment through the SIC card If you need to use the SiteMonitor Through SiteMonitor software to monitor your intelligent equipment and the environment through the SIC card please read this chapter carefully Tells you how to use the SIC card and Network Shutdown computer safe shutdown program to protect your computer system in the case of a mains or UPS failure Lists fast Q s amp A s in SIC card operation If you encounter any questions during operation to save your precious time we suggest you quickly look through this chapter for solutions before seeking technical assistance from the local customer service center of Emerson Network Power Co Lid Chapter 2 SIC Card Installation Chapter 7 Guarding Computer With Network Shutdown Chapter8 Q s amp A s Target o User e Technical support personnel operation and maintenance personnel Glossary UPS uninterruptible power supply NMS network management system For example HP OpenView IBM NetView or Novell Network NMS SNMP simple network management protocol MIB management information base HTTP hypertext transfer protocol Web browser such as Internet Explorer FireFox SiteMonitor a network management software for equipment room power and environment developed by Emerson Network Power Co Ltd Network Shutdown a computer safe shutdown program developed by Emerson Network Power Co Ltd Trap SNMP trap non request information sent by SIC card to NMS NTP n