Home

User Manual - Honeywell Analytics

image

Contents

1. Utilization of the 6 minute period may adversely affect the source tube service life Fire Range DIP SWITCH DIP SWITCH 7 8 DESCRIPTION open open Set to detect an industry standard 1 sq ft fire at 15 ft on axis closed open Set to detect an industry standard 1 sq ft fire at 30 ft on axis open closed Set to detect an industry standard 1 sq ft fire at 45 ft on axis Factory setting closed closed Set to detect an industry standard 1 sq ft fire at 60 ft on axis 16 Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 4 1 4 2 4 3 4 4 4 5 SECTION 4 OPTIONAL ACCESSORIES Air Shield for Applications in Contaminated Environment Part No DASA1 P For installation in areas with high levels of airborne contaminants the Detector Air Shield should be mounted to the Flame Detector housing The Airline fitting accepts 14 O D nylon tubing for an instrument grade air supply of 5 to 15 psi 6 cubic ft per minute PC Software Kit 2029 INTERFACE KIT PC DOS Software Kit installation facilitates access to FirePic and SnapShot and provides Detectors operation monitoring capability through the Detector s RS485 connections The Kit includes an Interface Box a PC software diskette an RS485 and RS232 cables and a 120 VAC 12 VDC charger Optional 220 VAC 12 VDC charger is also available upon r
2. 4 5m 15 ft e Jet fuel A 0 1 m one square foot pan fire at a distance of 18 2m 60 ft with the Detector sensitivity setting of 18 2m 60 ft e JP 5 0 1 m one square foot pan fire at a distance of 18 2m 60 ft with the Detector sensitivity setting of 18 2m 60 ft e JP 4 0 18 m two square foot pan fire at a distance of 30 4m 100 ft with the Detector sensitivity setting of 18 2m 60 ft e JP 8 0 18 m two square foot pan fire at a distance of 30 4m 100 ft with the Detector sensitivity setting of 18 2m 60 ft The Detector incorporates a 120 degree conical Field of View The fire emissions received by the Detector diminish at extreme range and edges of the field of view It is recommended that the Detector be pointed at the fire threat area for the fastest response times to the smallest size fire When multiple Detectors are used to cover large areas the Field of Views should overlap to insure complete coverage of the fire threat area The Field of View is not however limited to 120 degrees Larger fires outside the 120 degree Field of View may cause the SS4 A A2 to alarm This is based on the Inversed Square Law for radiated energy a larger size fire outside the Detection Range and field of view may cause the Detector to alarm Refer to Figure 1 Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 1 5 18 2
3. Model SS4 A A2 Detector uses 24 Volts DC at a maximum current of 75 mA with the 4 20 mA option the maximum supply current is 95 mA Make sure the Panel s power supply can withstand the load current of the total number of Detectors connected to it For example if 10 ten Model SS4 A A2 Detectors are connected to a single Panel s power supply multiplying 75 mA by 10 the power supply must be able to withstand at least 750 mA 10 0 75 A 10 This load current must also be taken in consideration for calculating the Panel s 24 hour power backup requirements Installation Procedure 2 2 1 Configuring and Wiring Detectors To configure and wire a Model SS4 A A2 Detector or to replace the Detector module the module must be removed from the enclosure After the configuration settings and wiring connections have been completed the module should soon be re installed in the enclosure to avoid contamination from the environment NOTE Avoid touching the Detector sensors at the front of the Detector module If touched accidentally they should be cleaned per instructions of Section 3 2 2 2 2 Removing Detector From Its Enclosure a With electrical power off verify that electrical power is off by making sure that the Detector s LEDs do not blink for at least 15 seconds loosen the Allen head screw at the base of the metal enclosure top lens cover b Remove the cover and set it aside along with the O ring avoiding contamination Loosen the three
4. Power Fire NO 4 Fire Relay Prem Fire NC 2 Fire COM 1 Fire Delay NC 4 Verify Fire Delay COM 3 Rel ay Fire Delay NO 2 Fire Delay COM 1 1 DC RETURN eh e FireBus Out 4 24VDC Fault CIM 4 1 DC RETURN Fault NC 3 2 RS485 Fault Relay ll COM 2 3 RS495 FireBus In Foult NO 1 4 24VDC Fault relay is shown in the energized condition during normal operation No Fault Figure 2 Model SS4 A A2 Detector Wiring Bottom View of SS4 A A2 Detector Module 2 2 5 Wiring the SS4 A A2 Detector for 4 or 20 mA Current Mode Operation Optional For applications requiring a 4 20 mA analog output order the Detector with the Optional 4 20 mA Module Assembly P N MA420 4 The module must be Factory installed and certified along with the Detector The following analog output levels are available from the Detector equipped with the MA420 4 Module The module is capable of driving a maximum load impedance of 283 Ohms NORMAL Operation 4 0 6mA ALARM 20 0 6 mA FAULT lt 0 6 mA To use the analog output of an SS4 A A2 make the following connections 24 V DC J2 pin 4 24 V DC RTN J2 pin 1 Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 4 20 mA output J5 pin 4 4 20 mA RTN J1 pin 1 The fire Alarm and fault relays of a Detector equipped with the MA420 4 Module are not usable However the Detector s Verify Relay
5. may still be used as a separate Fire Alarm output Refer to Table 2 Configuration DIP Switch Settings to set DIP switches properly NOTE J1 is a loop through connection to J2 The 24 V supply is connected to J2 pin 4 The red lead connection of the MA420 4 must stay in J1 pin 4 Also the 8 66 K Ohm supervising resistor must remain connected at the Fire Alarm relay contacts J4 pin 4 to J4 pin 1 or a Fault condition will occur Figure 3 SS4 Detector Module with MA420 4 Installed Rear View 2 2 6 Wiring the Detector Relays a b Insert relay cables into the Detector enclosure base through one of the conduit openings Refer to Figure 6 Fire Alarm Relay Connect wires for Fire Alarm to the appropriate J4 terminals of the Detector For Normally Open relay contacts install wires into pins 3 and 4 and firmly tighten down the slotted screws with a small screwdriver The Fire Alarm relay is de energized during normal operation and will energize when detecting a fire Fault Relay Connect wires for Fault to the appropriate terminals of the J5 connector For Normally Closed relay contacts install wires into pins 3 and 4 and firmly tighten down the slotted screws with a small screwdriver The fault relay is energized during normal operation and with no fault detected as shown in Figure 2 The fault relay will de energize when a fault is detected 2 2 7 Replacing the Detector Module in the Enclosure a Carefully re in
6. of OperatiON ooooccccnccoocccnnnconncanannncnnnncnonnnnnnncnnnnnnns 3 Troubleshooting diaaa a a a id 12 18 www honeywellanalytics com Contact Honeywell Analytics Europe Middle East Africa India Life Safety Distribution AG Javastrasse 2 8604 Hegnau Switzerland Tel 41 0 44 943 4300 Fax 41 0 44 943 439 India Tel 91 124 4752700 gasdetection honeywell com Americas Honeywell Analytics Inc 405 Barclay Blvd Lincolnshire IL 60069 USA Tel 1 847 955 8200 Toll free 1 800 538 0363 Please Note Fax 1 847 955 8210 While every effort has been made to ensure accuracy in this publication detectgas honeywell com no responsibility can be accepted for errors or omissions Data may change as well as legislation and you are strongly advised to Asia Pacific obtain copies of the most recently issued regulations standards and Honeywell Analytics Asia Pacific guidelines This publication is not intended to form the basis of a contract 701 Kolon Science Valley 1 43 Digital Ro 34 Gil Guro Gu Seoul 152 729 Korea Tel 82 0 2 6909 0300 Fax 82 0 2 2025 0329 HI an analytics ap honeywell com one e Technical Services EMEAI HAexpert honeywell com US ha us service honeywell com AP ha ap service honeywell com Issue 3_1510 001_Rev H_06 2013 H_MANO931_EMEAI www honeywell com 2013 Honeywell Analytics 13072
7. straightforward due to the built in self testing feature Therefore the maintenance consists mainly in keeping the Detector window lens clean and performing periodic testing required by the manufacturer of the Fire Control and Suppression System Detector Technical Specifications 1 21 Mechanical Specifications Enclosure Material Copper Free Aluminum 316 Stainless Steel Physical Dimensions Assembly 4 35 in 110 49 mm Height X 4 81 in 122 24 mm Diameter Mounting Holes 1 4 in 6 35 mm Diameter 5 50 in 139 70 mm Center to Center Conduit Entries Two 2 9 in NPT or Two 2 25 mm Weight Aluminum 3 lbs 11 oz 1 7 kg approximately Stainless Steel 7 lbs 7 oz 3 4 kg approximately Enclosure Rating IP66 NEMA 4 NEMA 4X Vibration Meets or exceeds Mil Spec 810C Method 514 2 Curve AW 1 2 2 Electrical Specifications Input Voltage Range 18 VDC to 32 VDC Normal Operation Current 60 mA nominal 205 mA nominal with heater Maximum Fire Alarm Current 85 mA maximum 235 mA maximum with heater Relay Contact Rating 1 Amp 24 VDC resistive Analog Current Output 0 to 20 mA Source or Sink User Selectable 400 Ohms Max Load 0 0 mA lt 0 6 mA Fault 2 0 mA 0 6 mA Dirty Window Lens 4 0 mA 40 6 mA Normal Safe no Fault no Fire 20 0 mA 0 6 mA Verified Fire Alarm Screw Terminal Wire Sizes 12 AWG to 22 AWG 2 50 mm to 0 762 mm Use stranded conductors not solid core Model SS4 A A2 Multi Sp
8. the Detector to declare a Fire on events where UV is not present or is obscured In applications where UV absorbing fumes are commonly present in high concentrations these fumes are usually toxic and should require masks or breathing equipment the Detector will function The Factory setting for IR Only is Disabled WARNING IR only setting should be used only in special indoor applications 5 Fire Detection Range Setting 15 30 45 or 60 ft The Factory setting is 45 ft This setting should be changed only if the Detector is located too close to the fire threat area and in the presence of abnormally high UV Testing 1 6 1 Special Conditions for Testing The SS4 Detector should be tested immediately after installation after repair or maintenance involving wiring or module replacement after periodic maintenance or after lens contamination has been identified 1 6 2 Automatic Testing Automatic SLR BIT Built In Test through the lens self testing is performed during Detector operation for virtually all internal electronic systems at the selected Test Period Section 1 5 3 One of the Red LEDs will remain illuminated Fault to indicate contamination of the window lens missing the protective Self test grill or when removing the enclosure cover 1 6 3 Manual Testing For manual testing the SS4 A A2 Detectors may be exposed to an actual industry standard open flame or to a Test Lamp simulating a fire It is mandatory to use the
9. 2 swivel mount or swivel release bolt on the SM4 Position the enclosure in such a way that the conduit openings are located horizontally at the bottom Point the enclosure in the desired direction and tighten the appropriate hardware Swivel Mount Plate Swivel mount Swivel Mount Plate 772 95 2 00 4 26 4 86 o O 1 2 13 Stud 0 295 Dia 4 7 approx Figure 4 Model SM2 Swivel Mount 10 Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 Figure 5 Model SM4 Stainless Steel Swivel Mount 1 50 Lo va a E 3 4 A NPT 0 T me P 2 09 gt 1 10 I 4 66 Figure 6 Model SS4 A A2 Detector Enclosure Side View 11 Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 0 25 DIA Two Places p 4 75 pe 5 50 a 6 12 Figure 7 Model SS4 A A2 Detector Enclosure Rear View 12 Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 3 1 3 2 SECTION 3 TROUBLESHOOTING AND MAINTENANCE Model SS4 A A2 Detector Faults The Model SS4 A A2 Detector issues a Fa
10. Fire Sentry handheld UV IR Test Lamp Model No s FT 2045 or FT 2145 with SS4 Fire Detectors The FT 2045 and FT 2145 Test Lamps are housed in an Explosion Proof enclosure powered by internal rechargeable batteries and designed for indoor and outdoor use For additional information on the Test Lamp refer to FSC Specification SP0242 for the FT 2045 or FSC Specification 1505 008A for the FT 2145 NOTE Other manufacturers UV IR Test Lamps should not be utilized to test FSC Detectors conversely the FT 2045 and FT 2145 Test Lamps should not be utilized for testing other manufacturer s Detectors Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 2 1 2 2 SECTION 2 INSTALLATION Installation Instructions This section describes the installation of the Model SS4 A A2 Detector for the Stand Alone relay mode It is recommended that junction boxes be used to wire the Detectors Determine the configuration settings for the device s and the number of connections to be used Fire Fire Verify Fault and Power depending on the desired Detection Range and the Fire Control Panel type used refer to the Fire Control Panel Manual for details 2 1 1 Installation Precautions The following precautions should be observed during installation of Model SS4 A A2 Detectors 1 Make sure that the external electrical power is turned OFF before connecting the D
11. Installation Guide and Operating Manual Honeywell Fire Sentry Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector STAND ALONE RELAY MODE or 4 20 mA Output Option Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 APPROVALS TABLE OF CONTENTS SECTION 1 TECHNICAL DESCRIPTION oonnccccocccccnonaccccnonaocacnnaaco nana 1 1 1 1 2 1 3 1 4 1 5 1 6 Features and Specifications 1 1 1 General Description cad 14522 Application A Ea a 1 1 3 DetectorLocas tiie eh se FS2000 System Operation OVEFVIEW coocooccccccccononconnccnnncononcnnnos 1 4 1 Model SS4 A A2 Detector cccccccceceeeeeeeeeececeeecececeeeseeeeeeeeeeseeeeeeeeeseeeeeeeeeeeeeeeeeeeeeceeeeeeeees es 4 1 4 2 Detection Range and Field of ViewW coomonooncconnnnnnnonnocanonononnnnnnnroncnnonnnnonnnroncncnnnnncnnnrcncnnnnos 4 Configuration SettingS cssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssen E AAA O OA 1 6 1 Special Conditions for Testing secese e cevkaveesdechace Ee EREE EEE SEAE REREN 6 1 6 2 Automatic Testing were 136 3 Manual Testing tddi SECTION 2 INSTALLATION occcoccccccinncccnnnnnco
12. Philips head captive screws located on the top circuit board d Carefully lift out the module sliding it along the three metal standoffs o 2 2 3 Configuring the Detector Module Set the DIP switches located on the center PC board of the Detector module to desired settings Refer to Section 1 5 and Table 2 for DIP switch settings Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 2 2 4 Wiring the Detector Module a Insert the cables into the metal enclosure base through one of the conduit openings Refer to Figure 6 b Connect the 24 Volt DC power supply wires to pins 1 and 4 of the J1 or J2 connector observing the correct polarity Refer to Figure 2 Firmly tighten down the two slotted screws with a small screwdriver taking care not to over tighten the screws Pins 2 and 3 of the J1 and J2 connectors are the RS 485 interface used only for downloading the FirePic from the Detector s non volatile memory or for viewing the Tri Mode Plot It is recommended to wire pins 2 and 3 to a separate junction box and properly identify them for future use A color coded multi connector shielded UL rated cable with 18 to 24 gauge wire is recommended for connecting to J1 or J2 The following color coding is suggested as a guideline Pin 1 Pin 2 Pin 3 Pin 4 Black Green or Blue White or Yellow Red DC RETURN RS 485 RS 485 24 VDC
13. Volt DC power for the Detector and RS 485 digital communication Refer to Fire Sentry document MN0003 entitled FS2000 FIRE EARLY WARNING SYSTEM INSTALLATION and OPERATIONS GUIDE For special remote alarm applications users may also connect directly to the Detector s Fire alarm relay NOTE When the Model SS4 A A2 Detector is connected to the FS2000 System using FireBus communication the Controller automatically disables the Detector s Fault relay Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 1 4 Overview 1 4 1 Model SS4 A A2 Detector Version SS4 A There are two 2 LEDs on the Model SS4 A Detector that indicate the state of the Detector During normal operation both LEDs will blink every 10 seconds If the Detector alarms to a fire it energizes the Fire relay and turns on both LEDs in the following sequence One LED is turned on immediately and the second LED will rapidly blink for several seconds indicating that the Detector s FirePic spectra is being permanently stored in the Detector s solid state memory FirePic is the several seconds of Detector spectral data which precedes an alarm event Once the FirePic data is stored the second LED will remain on For this version the fire alarm LEDs turn on and remain on until power to the unit is cycled turned off and on again If the Detector has a Fault it de energizes the Fau
14. ccccccocccccnonccccononncononinoconos 12 Piola tana 14 POS ES 7 Stat tr tad roca da td 3 A E 7 14 Detector Fault High Temperature ocooooooccccncnccnononncnnnnnononannnnncnnnnnnnnannns 12 Input Volt cc 12 A 12 Roldan cian Aee aa N diodo Iaido E 12 Selfe Checking cia 12 Detector Repall oooocccccnconococccccnnconannnnnnccnnnno nana ocn nnnnnnnnnnnns 13 ESD ENA E A E do laico EE 6 EEUU TT EN EE ATTA T 2 FireBus Wiring occ a aid 6 E c2 csshstt AA tet cadets 6 Installation cubero 6 Conduit isaiah a tees cian 6 BIS tE LO EEES E E EEE de 6 Enclos re iii Raae aae eE E ARA ANE RERET 9 Precaution e A be a E a ae E aA eee oe 6 Procedures munna E 6 Static Damage iieri io de diene accede 6 Junction BOX cccooococncccnncccncoconncnnnnnonnnonnncnnnnnnonononncnnnnnnnninons 6 Layout Planning v scsteenecee cine ceiiees acai ceneees 6 Maintenance nicotina 12 Optional Accessories ooooooooocccccconocoaoccnnnccnncnnnnnnccnnnnnnnnnn cnn 16 Personnel Qualified cooooccnncnonccccononnnccnnncncnnnnos 13 PO Wes idea 6 Relay A tiearecs She tak Oe a stieaed the bate 14 Fil Csi feces dictan laico dd ts ved cutee ta cod dade devoto we ate 14 Removing Modules eeeeeeeeeeeeeeeeeeeeeeneeeeeeeeeeeenaeeeeeess 7 Stand Alone si cccts csceien G anita HA 2 Static Damage s eckes ect ehh cae eed arroen E Ea a bli 6 Swivel M T irian ia a a aaraa aaan Naar E ai 9 TeSt LAMP EE E E T E T 16 TES OOOO A E a A A EA T e AE 3 4 5 Theory
15. ectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 1 2 3 1 2 4 Environmental Specifications Operating Temperature Standard 40 F to 185 F 40 C to 85 C Operating Humidity Range 0 to 98 RH 100 RH condensing for short periods of time Storage Temperature 67 F to 221 F 55 C to 105 C Performance Specifications Field of View 120 Horizontal and Vertical conical Sensitivity One 1 sq ft heptane reference fire at 60 feet Speed of Response 2 to 5 seconds typical High Speed Response Less than 0 5 seconds to fireball type fires if selected Spectral Sensitivity 0 4 to 3 5 micron wavelengths TriBand Dual IR Plus 1 2 5 Hazardous Area Classifications 1 2 6 North America ATEX IECEx Class I Division 1 Groups A B C amp D Class I Zone 1 Class II Division 1 Groups E F 8 G AEx d IIC xx Il 2G Ex d IIC xx Class III 112D Ex tD A21 IP66 T135 C T4 Ta 40 C to 110 C xx T4 Ta 40 C to 110 C T5 Ta 40 C to 75 C T5 Ta 40 C to 75 C T6 Ta 40 C to 60 C T6 Ta 40 C to 60 C InMetro Ex d IIC xx Gb xx T4 Ta 60 C to 110 C T5 Ta 60 C to 90 C T6 Ta 60 C to 75 C Additional Certifications FM verified and approved to meet FM 3260 Radiated Energy Sensing Fire Detectors for Automatic Fire Alarming Signals Heater circuit turns ON only when temperature drops below
16. equest 4 20 mA Option MA420 4 The 4 20 mA module is by Factory Mutual FM recognized device to be used with all approved SS4 type Detectors Fire Sentry is required by FM to install this device at the factory and certifies this option along with the Detector Refer to Section 2 2 5 for system wiring details NOTE Converting Field units of the SS4 Stand alone relay type to the 4 20 mA version requires the unit be returned to the factory for installation and certification Detector Mounts SM2 or SM4 The heavy duty steel Swivel Mount SM2 or extra duty Stainless Steel Swivel Mount SM4 may be utilized for mounting the SS4 type Detectors Refer to Section 2 3 for details Test Lamp FT 2045 or FT 2145 This battery powered portable explosion proof handheld test source for remote activation of the SS4 type Detectors simulates the radiant energy emitted by an actual fire in order to test the Detectors operation without the need for an open flame The unit is rechargeable with a 120VAC 12VDC charger Optional 220 VAC 12 VDC charger is also available upon request 17 Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 Cleaning PrOducCtS cooocccccnncooccccnccnnncononnncnnncnonnnnnnncnnnnnnns 13 GONQUIE dia 6 Detector Clio i ateicin iii an ele 12 Enclosures 2 a a a A he tte 9 LEDS Croata dan eta Beth 3 Maintenance Schedule ccc
17. etector 2 Printed circuit board components of the Detector are susceptible to damage from electrostatic discharge Do not handle the Detector s module and its printed circuit boards without adequate grounding and observing all necessary measures to prevent the effect of electrostatic discharge ESD 2 1 2 Conduit Installation When planning the conduit follow these recommendations 1 If only one of the two 3 4 inch NPT conduit openings on the Model SS4 A A2 Detector enclosure is used seal the unused opening with a threaded plug and approved sealing material 2 In areas where moisture may accumulate install an approved conduit trap or drain 3 A seal should be installed 6 from the enclosure wall for all applications requiring a Class I Div 1 Explosion Proof rating 2 1 3 Wiring Recommendations To prevent intermittent connections Fire Sentry Corporation recommends using junction boxes Install a junction box near each Detector location Wire each Detector to its junction box Use screw down terminal strips inside the junction box to make the connections from the Detector s terminals to an FM Approved or UL listed Fire Alarm Panel Also use FM UL Approved junction boxes and terminal strips NOTE Avoid wire splices However if wire splices are necessary all splices should be soldered Utilization of good wiring practices will simplify installation improve reliability and facilitate maintenance 2 1 4 Power Supply Considerations The
18. lt relay and turns one 1 LED on the LED will not light if the Fault is a No Power Fault If the Fault condition such as a Low Voltage Fault is eliminated the Detector will automatically return to Normal Operation NOTE Faults caused by excessive input voltage or due to temperatures outside the operating temperature range require factory re certification Re certification is required if a Fault is indicated by both LEDs rapidly blinking with frequency about 2 Hz Version SS4 A 2 The operation of this unit is identical to the SS4 A except the fire alarm LEDs turn off once the fire threat is eliminated without power cycling of the device 1 42 Detection Range and Field of View The SS4 A A2 detection range is field adjustable between 4 5m 15ft and 18 2m 60 ft in 4 5m 15 ft increments to an industrial standard of one square foot Gasoline Kerosene or isopropyl Alcohol pan fire within 5 seconds The Detector is also optimized for the following specific type of fuels and will alarm to the resultant fire within five 5 seconds Careful attention should be given to the Detector sensitivity setting for these types of fires e Silane Gas 254mm 10 fire height using a 4 74mm 3 16 orifice at a distance of 4 5m 15 ft with the Detector sensitivity setting of 4 5m 15 ft e Propane Gas 254mm 10 fire height using a 9 5mm 3 8 orifice at a distance of 4 5m 15 ft with the Detector sensitivity setting of
19. m 13 7m 91m 4 5m Goft 45ft 30ft 15ft 120 Degrees Figure 1 Field of View Horizontal and Vertical Sensitivity to 1 Sq Ft Gasoline Pan Fire Configuration Settings The SS4 A A2 Detector may be reconfigured in the field and thus optimized for special applications The configuration of the Detector is set using DIP switches located on the middle circuit board of the Detector Module The DIP switch settings for each configuration are listed in Table 2 These configurable options include 1 Fire Verify Relay The Verify Relay may be disabled or enabled with several Verify Time settings It also may be set to act as another Fire Relay The Verify Time may be set from 5 to 30 seconds in 5 seconds increments The Factory setting Verify Relay Disabled When the Verify Relay is enabled and Verify Time is set the Verify Relay will energize and the Fire Relay will de energize if the fire conditions are still present at the end of the Verify Time period In the opposite case the Detector will wait for 5 seconds plus another Verify Time period to test for the fire conditions This wait and verify cycle will repeat 10 times or until the presence of the fire is confirmed This concludes the verification process If the presence of the fire is not established the Fire Relay will remain energized unless Non Latching mode is set In case a subsequent fire is detected the entire verification process will be repeated The state of the Fire and Ve
20. ninia 7 2 1 2 2 2 3 Installation InstructiONS ooooooooonocnononnanncoonacnononaacnononancncoonannncoonanncconnnnncconncnccoaancnccoancnncoaarannccaaccnccnnas 2 1 1 Installation Precautions 5 33 4 5 c083 te avandeods ai aa aeaa EE AEE EEEa SEE EDEA ENEE ara TASER 7 2 1 2 Conduit Installation usd dados 7 2 1 3 Wiring Recommendations cadenas 7 21 4 Power Supply Considerations a i iana a a ra ESE E EE SA EEE ERE a 7 Installation Procedures ssssssssesssscsssossesssos ssescssssec ssossesocessos sssosesssor sossrossessssossssssesissecorosses sos sssosossso 2 2 1 Configuring and Wiring DetectorS cconoonoconnccnnnonononcnnncconnnononcnnnnccnonnnnnnnnnnccnnnnnannncnnnccnnnnannnnnns 7 2 2 2 Removing Detector From lts Enclosure 8 2 2 3 Configuring the Detector MOdUIe 5 iccicsivevies ccesdesscceviasecntaddavoesviaseseaediaooetvdessscdosuaousedeasgeossaess 7 2 2 4 Wiring the Detector Module ooooocccnnnoooccconoconnnnnnncnnononnnnonanronnnnnncnnonnnrcnnnncnnnnonnnncnnnncnnnnnns 8 2 2 5 Wiring the SS4 A A2 Detector for 4 or 20 mA Current Mode Operation Optional 8 2 26 Wiring the Detector Relays cistitis aeara na rae nds sieves ae ssapdussovundesiocseddavovisbonsseesdasess 9 2 2 7 Replacing the Detector Module in the Enclosure cccccccssssssnececceeeesessnaeeeeeeeeeesensaeeeeeeeeeees 9 Enclosure Installation Optional cccc
21. ns Detector Repair Return the defective module to the factory for repair service THERE ARE NO USER SERVICEABLE PARTS IN A DETECTOR MODULE If the Model SS4 A A2 Module must be shipped back to the factory for repair it MUST be packed in static protective material If not available the Module should be carefully wrapped with aluminum foil An RMA Return Material Authorization is required for all returns to the factory Contact Fire Sentry Customer Service at 714 694 2700 or your Distributor for an RMA number before shipping a unit back to the factory 14 Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 DETECTOR PINOUT DATA TABLE 1 Stand Alone Model SS4 A A2 Detector Connectors Pinouts J1 DETECTOR INPUT POWER PIN 1 DC Return 2 and 3 RS 485 Connection to an optional interface unit for viewing FirePic and TriMode Plot 4 Power 24 Volts DC J2 DETECTOR POWER OUT PIN 1 DC Return 2 and 3 RS 485 Connection to an optional interface unit for viewing FirePic and TriMode Plot 4 Power 24 Volts DC J4 FIRE RELAY PIN 1 Fire Relay Common 2 Fire Relay Normally Closed 3 Fire Relay Common 4 Fire Relay Normally Open J5 _ FAULT RELAY Energized J6 FIRE VERIFY RELAY PIN PIN 1 Fault Relay Normally Open 1 Verify Relay Common 2 Fault Relay Common 2 Verify Relay Normally Open 3 Fault Relay Normally Closed 3 Verif
22. ows appear contaminated fails Built In Test or the Detector fails an end to end test with a handheld UV IR Test Lamp FT2045 or FT 2145 If necessary clean the Detector Module Sensors each time the Detector has been disassembled for wiring or replacement Use a blast of an air hose or an oil free cloth to clean the enclosure window Oil degrades the performance of UV Detectors Occasionally the use of a solvent such as alcohol is acceptable No disassembly of the Detector is required DO NOT USE SILICONE BASED OR COMMERCIAL WINDOW CLEANING PRODUCTS THESE WILL DEGRADE THE MODEL SS4 A A2 DETECTOR PERFORMANCE 13 Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 3 3 3 4 Personnel Training Troubleshooting of the Model SS4 A A2 Detector should be performed only by qualified authorized personnel observing all standard safety practices Although the Detector operates on safe 24 Volts DC the FM Approved or UL listed Fire Alarm Panel s power supply may operate on life threatening 120 or 240 Volts AC WARNING Hazardous voltages may be present during testing procedures Serious injury or death may result due to failure to observe safety precautions CAUTION Model SS4 A A2 Detector modules and its components are susceptible to permanent damage due to electrostatic discharge ESD Do NoT handle a module without adequate grounding precautio
23. rify Relay after the verification process will depend on the choice between Latching and Non Latching modes NOTE When the Verify Relay is enabled and Verify Time is set the Fire Relay will de energize when the Verify Relay is energized 2 Latching Non Latching The Fire Relay and Verify Relay may be set in a Latching or Non Latching mode The Factory setting for the SS4 A is Latching and the SS4 A 2 is Non Latching If the SS4 A or SS4 A 2 Latching mode is selected the Fire or Verify Relay will energize and Red LEDs will remain illuminated until the Detector power is cycled power is turned off then on If the SS4 A Non Latching mode is selected the Fire or Verify Relay will de energize after 10 seconds and the Red LEDs will remain illuminated until power is cycled If the SS4 A 2 Non Latching mode is selected the Fire or Verify Relay will de energize and the Red LEDs will turn off after 10 seconds 3 Test Period This setting pertains to the Through the Lens test period which may be set to 6 or to 30 minutes The Factory setting is 30 minutes The 6 minute period may be required in applications where the lens is frequently obscured NOTE Utilization of the 6 minute period may adversely affect the source tube service life Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 1 6 4 IR Only Enable Disable The IR only setting allows
24. ssssssssssssssssssssssssssccssssssssssscssssssssssssssccssssssssssssssssssssssssssssee LO SECTION 3 TROUBLESHOOTING AND MAINTENANCE cooccccococccconocccnnnnaccnnnnna cnn nana c cn nnn coran cnn cera carac 13 SECTION 4 OPTIONAL ACCESSORIES 3 1 3 2 3 3 3 4 Model SS4 A A2 Detector FaultS mmoomomommmmmmsm 13 Cleaning Windowed Enclosures and Detectors csssssssssssssssssssssssccsssssssssssccsssssssssssssssssssssssses LO Personnel TRAINING se ciadscssssccennccacdscossessesescosdeceSses ecessesdesestesiedecsesdesessnsdececssedesessecdececssededessesdesesssedesesvece LA Detector RED AUN 3ca5ccccs cccseccssdeccoscscossensscescoscssessessectssosesceedsstedecdessesensncescnccsdcesessectscecssecseassec scesesteonsscstel amp DETECTOR PINOUT DATA rr a a aa a a r a a aara aaar aa e aaraa aa aa aaa aaa aga 15 Verification TIME cit a lil idos 16 Latchingr ed e ed td 16 IReOnly Enable ai i cavaaces tease a a ckeacaag iawceha dca aaeis E aE 16 T st Cyclen aaa anida ad 16 Fire Range 16 4 1 4 2 4 3 4 4 4 5 Air Shield for Applications in Contaminated Environment Part No DASA1 P 17 PC Software Kit 2029 INTERFACE KIT sssscccccsssssssssscrsccssscsccssseeeccssssscceees 17 4 20 mA Option MA420 4 ssssceees 17 Detector Mounts SM2 or SM4 17 Test Lamp Part No FT 2045 FT2145 17 Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation G
25. stall the module over the three metal standoffs and screw it down with the three captive screws to the standoffs If necessary clean the Detector sensors and windowed cover per instructions of Section 3 2 Securely screw down the metal enclosure top windowed cover and tighten the Allen head tamper proof screw Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 2 3 Enclosure Installation optional 2 3 1 a Fire Sentry Housing c E CO dE Mounting Plate Installing the Detector on the Swivel Mount SM2 or SS Extra Duty SM4 Swivel Mount Select fasteners for the swivel mounting such that they will secure it to the type of material at the enclosure location Mount the swivel mount to the wall assuring correct orientation Install the mounting bracket onto the Model SS4 A A2 Detector enclosure using the 14 20 or 6 mm screws and nuts provided If oriented correctly the outside contours of the mounting ears on the Detector enclosure and the ends of the bracket will match The large diameter of the threaded insert should face the enclosure Screw the enclosure bracket assembly onto the ball or swivel stud Turn the Detector until the stud bottoms against the enclosure Do not tighten While holding the enclosure tighten the jam nut against the bracket While holding the enclosure loosen the socket head screw on the SM
26. strong mechanical or acoustical vibrations should also be avoided For optimum performance locate the Detector s as close as possible to the potential fire source preferably along the axis of the vision cone Install enough Detectors to completely eclipse the fire hazardous area Assure accessibility for the Detector lens cleaning as well as best possible protection and or cleaning from fog rain ice dust hazardous atmospheres and other adverse elements If necessary utilize the Steel Swivel Mount Model SM2 or 316 Stainless Steel Swivel Mount Model SM4 for greater flexibility in mounting locations See Figures 4 and 5 Stand Alone Operation For Stand Alone operation the Model SS4 A A2 Detector may be connected to a suitably approved transmitter or control system panel The Detector operated in the Stand Alone mode uses the Fire Fault and Verify optional relays to interface to the Fire Security Panels For Stand Alone operation the Detector s Fault relay is automatically configured by the on board microprocessor The input current of the Model SS4 A A2 Detector is about 15 mA higher in the Stand Alone mode compared to FS2000 System operation NOTE The Fault relay is not available when the Detector is wired to the FS2000 System FS2000 System Operation For FS2000 System operation the Detector Fire and Fault signals are sent digitally to the FS2000 System Controller using the four wire FS2000 FireBus The FireBus provides the 24
27. surface of the Detector sensors and the protective grill mounted on the outside of the housing cover If the fault has not been eliminated after re assembly and powering up for 10 to 15 minutes factory service may be necessary f Relay Fault The Detector faults if one of its Relay circuits fails In this case one LED is on until the fault is corrected The user should return the unit to the factory for service g Self Checking Fault The Detector faults if its internal microprocessor finds a failure during self checking of the hardware and software In this case one LED is on until the fault is corrected This type of fault may be caused by a number of reasons The user should verify proper grounding of the device and the absence of noise on the power cables If fault persists the user should return the Detector to the factory for service h Analog 0 current All the above faults will produce an output current loss 0 0 6mA with the 4 20 mA module option Cleaning Windowed Enclosures and Detectors The optical window lens of the Model SS4 A A2 Detector should be cleaned periodically on a regular maintenance schedule For clean area applications perhaps monthly cleaning schedule will be sufficient For extremely contaminated application environments such as truck filling stations with presence of black carboneous smoke daily cleaning schedule may be necessary Clean the window of the Detectors each time they are handled the wind
28. uide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 1 1 APPROVALS The Model SS4 A A2 Optical Fire Detectors have been manufactured in compliance with the requirements of the ISO 9002 standard and have received Factory Mutual FM for the United States e CSA for Canada SECTION 1 TECHNICAL DESCRIPTION Features and Specifications 1 1 1 General Description The Model SS4 A A2 Optical Fire Flame Detectors are fast reacting within 5 seconds digital configurable computerized smart units This Detector has sensitivity to Type A B and C flaming fires Detectors of this design process Ultraviolet UV Wide band Infrared IR and Visible VIS spectral ranges from ruggedized Solar blind UV Quantum Effect IR and visible sensors correspondingly They are equipped with SRL BIT Built In Test for optical through the lens of both the sensors and lens The Model SS4 A A2 UV IR and VIS Fire Detectors have false alarm immunity and adjustable alarm range between 15 and 60 ft for a one square foot gasoline pan fire with a 120 degree 60 degrees from the axis conical field of view Their microprocessor based algorithms FirePic SnapShot and Tri Mode Plot assure time programmable alarm verification Fire Signature Analysis and compatibility with standard approved fire alarm panels The Detector also has the flexibility to be re configured in the field Its installation is simple and operation
29. ult or Trouble condition by de energizing its Fault Relay J5 connector The following are Detector Faults a Temperature Fault The Detector faults if the internal temperature during operation rises above 85 C or falls below 40 C causing both LEDs to blink rapidly Corrective action for this type of fault requires factory re certification b Excessive Input Voltage Fault The Detector faults if the input voltage is too high greater than 45 Volts causing both LEDs to blink rapidly Corrective action for this type of fault requires factory re certification c Low Input Voltage Fault The Detector faults if the input voltage is too low The user should check the voltage between Pins 1 and 4 of the power connector J1 or J2 In this case one LED is on until the fault is corrected If the voltage is below 15 Volts the user should check the wiring and the power supply d No Power Fault The Detector faults if the input voltage is interrupted or turned off causing the absence of LED indication The user should measure the voltage between Pins 1 and 4 of the power connector J1 or J2 If none or very low voltage is measured the user should check the wiring and the power supply e Detector Fault The Detector faults if its Optical Sensors fail the automatic built in through the lens test In this case one LED is on until the fault is corrected The user should first clean both inside and outside of the lens thoroughly then clean the exposed
30. y Relay Common 4 Fault Relay Common 4 Verify Relay Normally Closed 15 Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 TABLE 2 Configuration DIP Switch Settings Verification Time DIP a DIP sd DIP pde DESCRIPTION ETRE Verify is disabled and the Verify Relay is unused Factory setting Verify is enabled and the Verify time is 5 seconds open closed open ver is enabled and the Verify time is 10 seconds Latching DIP SWITCH 4 DESCRIPTION open Non Latching mode If Verify is enabled then the Verify Relay will de energize approximately 10 seconds after it energizes lf Verify is disabled then the Fire Relay s will de energize approximately 10 seconds after it energizes The SS4 A2 Factory setting is Non Latching closed Latching mode If Verify is enabled then when the Verify Relay energizes it will remain energized until the Detector is reset If Verify is disabled then when the Fire Relay energizes it ill remain energized until the Detector is reset The SS4 A Factory setting is latching IR Only Enable DIP SWITCH 5 DESCRIPTION open Fire Alarm declaration UV and IR energy Factory setting closed JA Fire Alarm may be declared without UV being detected Test Cycle DIP SWITCH 6 DESCRIPTION open Testing of the Lens occurs every 30 minutes Factory setting Testing of the Lens occurs every 6 minutes
31. zero degrees Fahrenheit 17 C The supply connection wiring shall be rated at least 10 C above the rated service temperature 120 C for T4 applications and 85 C for T5 applications 1 2 7 Other Specifications LED Visual Indicators Powered Detector Dual LEDs blink every 10 seconds Fault Declared One LED turns ON solid until the fault is cured Re calibrate when Both LEDs flash ON and OFF rapidly Fire Declared Both LEDs ON solid one LED blinks during first few seconds Relay Contact Rating 0 5 Amp at 120 Volt AC or 1 A at 24 V DC resistive Fire relay N O and N C contacts Latching Non Latching switch selected Verification relay N O and N C contacts Adjustable time from 0 to 30 seconds Fault relay N O and N C contacts Model SS4 A A2 Multi Spectrum Digital Electro Optical Fire Detector Installation Guide and Operating Manual MAN0931_V3_1510 001_RevH_06 13 1 2 1 3 1 1 2 Applications Applications of the Model SS4 A A2 Detectors include warehouses aircraft hangars petrochemical facilities Silane gas storage Gas turbines and Power plants among others 1 1 3 Detector Locations For unobstructed performance considering Detector locations in application areas avoid sources other than fire which may cause false alarms such as operations utilizing welding or gas torch equipment high power sources of EMI or RFI or artificial lighting pointed directly at the Detector Locations experiencing

Download Pdf Manuals

image

Related Search

Related Contents

H800  GE Security - UTC Fire & Security  取扱説明書 - M  Wi-Fi & Bluetooth    ダウンロード(PDF 2.6MB)  Mode d`emploi  Modine Manufacturing GAS-FIRED HEATERS BD User's Manual  Declaration of conformity 61/2012  Motion Computing R12 User's Guide  

Copyright © All rights reserved.
Failed to retrieve file