Home
animeo IP/RS485 Operating Manual v1.0
Contents
1. Picture 84 Function Settings the Wind Direction function Settings 1 Wind sensor allocation Click on the Select button to the right to open the Sensor allocation dialog Allocate the wind sensors by double clicking or by drag and drop to the list to the right If more than one sensor is chosen the sensor with the highest wind speed value will be read from At least one sensor must be allocated 2 Wind direction sensor allocation Click on the Select button to the right to open the Sensor allocation dialog Allocate the wind direction sensors by double clicking or by drag and drop to the list to the right 3 Speed threshold The wind speed needed to activate the normal wind functionality 4 On delay The time the wind speed must exceed the wind speed threshold before activating the wind function Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 68 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Snow Off delay The time the wind speed must be less than the threshold before deactivating the wind function Wind direction Select from which cardinal facade direction the wind should come from to trigger the protected angle functionality Tolerance How much tolerance or deviation from the wind direction angle that should be included in this functionality Protected
2. User manual animeo IP RS485 1 0 Visual Configuration Software to make a full commissioning of RS485 and operate the system Rev 1 0 Language English Somfy Date 2014 03 05 Digital Network Changes can be done without notice 2012 SOMFY SAS All rights reserved Somfy Manual for animeo IP Table of Contents Table Or CONTENER animeo IP Visual Configuration software sra PC Requirements for the Visual Configuration Software occcccnccnnononcnnncnnnonacanonanononacnnnacnnnnrcnonacnanono Hovore Manta ee ette Before Commissioning Understanding animeo IP occcoccccnncccnnnoncnonarinonanononannnonaccnn cono narononananon Commissioning the act of creating the ConfiguratiON ooccccnncncnnnannnonacnnonaninonannnonanonarinonananono The auto COVE ea O E telde aiocatino teca SY SECM He SU ICU Nicea ZONE TOW TR VY Oi aspirado scada Zones how you should plan to maximize the usage of the different ZON8S ccccocccccnncnnnnnancnos Facade Based Configuration or Group Based Configuration cccccccecccccsessceeececeeceeeeseeeseeeness How to physically connect the Building Controller to your PC oonccccnncncnnoccncnnccnnnnccnonacinnanononaso Starting the animeo IP Visual Configuration software cccccessccccessseccccescceeeuseceeeuseceeeneceeseuseceseuneees MA A e o o e aa neecaramoumuatannneton te neasareasves Top part 1 the Menu and Navigation Bar cccccccccssssecc
3. Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 21 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Making the Excel file The ActuatorlD is mandatory when making the excel file All other entries such as cardinal direction facade floor and room are optional but we recommend that you enter them as well since it will ease your commissioning a lot in the later stages See picture below for an example G18 fe A C O F 458907 North West West 1 102 0606BF North West West 1 102 a 123456 East East 3 304 6 450 78 East East 3 305 Fi 2060606 East East 3 306 E 060606 South West West 2 205 g 565656 10 Picture 14 Make New Configuration Example of how the Excel file should be made Saving the Excel file When you save the Excel file it is important that you save it in the correct format text Tab delimited Go to the file menu select Save as Choose this option as file type and give the file a good name and save it somewhere you remember Excel may ask some strange questions First select OK then No and finally Cancel if a new save dialog appears x Save As ES OD gt Computer No backup T Samuel gt v Search Samuel p Organize v New folder b FA Microsoft Excel Name Date modified Type Lo bilder pa oss 2011 05 26 0
4. Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 27 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Motor location motor identification via Somfy s Visual Click finder In the wizard you will now see the facade you defined as a matrix see picture below It is now that you will identify the exact location of the motors that is which window on the facade that each motor belongs to The identification is done via Somfy s Visual Click finder Somfy s Visual Click finder works like this Click on the big play button to start the method Some motors will move to a 50 position e half the window will be covered by the solar shading 3 Identify the windows where solar shadings have moved to 50 Click on the corresponding cells in the matrix shown in the wizard 5 When you have finished selecting the cells in the matrix then click on the next cycle button in the bottom center of the wizard where you usually continue to the next step in the wizard 6 Continue with steps 2 to 5 above until the wizard informs you that it has identified where all the motors are on the facade in questions Note that when the first facade is being made this method will cause all motors to YD move As motors are identified for each facade in sequence identified motors will not move Motor positi
5. It is untouched Note When making a New Configuration on an existing system locks and active functions will be disabled Start Commissioning Make New Configuration Creating a new Configuration starts from the Make New Configuration Wizard where the first commissioning steps are taken The outcome of this wizard ensures that certain vital steps are taken and that the location of the motors is found in which window a particular motor is installed The following steps in the Configuration Wizard ensure secure commissioning Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 18 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP it asks if the user can confirm that end limits have been set on all motors solar shadings it asks if the user can confirm that all solar shading motors have power after discovery a test is made to send all solar shading motors to 50 in order to see that all motors have been discovered positioning of the motors the process of identifying in exactly which window a solar shading motor is installed checks and setting the turn direction of the motors In the Configuration Wizard the user can choose to make a facade based or a group based commissioning When you start the Commissioning Wizard you are first greeted by a welcome view Click Next to naviga
6. op ime 11 B Stop after fo Minutes Picture 93 Function Settings Sun Settings 1 Enabled Per default the function is enabled but you can disable the function if necessary 2 Sun sensor allocation Click on the Select button to the right to open the sensor allocation dialog Allocate the sun sensors by double clicking or by drag and drop to the list on the right 3 Onthreshold The sun intensity needed to activate the sun function A normal value is 20 25klux 4 Off threshold The threshold the sun intensity must go below to deactivate the sun function A normal value is 15 klux 5 On delay the time the sun intensity must exceed the On threshold before activating the sun function A normal value is 2 min 6 Off delay The time the sun intensity must be lower than the Off threshold before deactivating the sun function A normal value is 20 60 min 7 Position The position the solar shadings will take when the sun function goes active You can choose between Regular Position and Sun tracking position These are explained more in detail below 8 Time Period Additionally you can set which days and time span this function should be active For sun function this feature can be used wisely for example having one sun function Copyright O 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 5 A 2011 000 31500 77 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by So
7. 001 460028 000 S A 2011 000 31500 74 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Solar Heating This function is used to make use of heat coming from the sun to lower heating costs This scenario occurs when it is quite cold outside but the sun is strong You have to know a bit about the window glass performance to set this function properly Normally this function is used outside occupancy hours The functions conditions are if the indoor temperature is lower than the threshold and the sun intensity is higher than the sun threshold then the solar shadings can be programmed to take an appropriate position You can have up to 8 of this function in a Comfort Zone gt Get Heat Function enabled Temperature sensor used Ww _ 4 Temperature 1 Sensorbox 1 NAAA Sun sensor used C pl CA gs eee SUMA SERSOnmoxk L Temperature threshold ls Sun threshold as kuz On delay la Off delay EM Position Specific position Y Generic position Position 0 i Angle E Time period Active period Whole day Specific time Start time on Y oo Stop time Mo Picture 91 Function Settings Get Heat Settings 1 Enabled Per default the function is enabled but you can disable the function if necessary 2 Temperature sensor allocation Click on the Select button to the right to open the Sens
8. 33 Commissioning Finishing the Wizard upload Configuration to the BUCO ooccccccncccnnncnncnnnnninnnos 34 CMGI UH NO e a seston octet O os settee teat ies oc aes amar sae e nectar cee dees 34 Configuration Part 1 Group Based scscccsssssessossveconscescuenssseseosvectenssscsseusestoussscuenesscneuussreses 34 Configuration Part 1 Facade Baseliuaii ia owned dapsone N 35 Configuration Part 2 Generic Sete ai di 38 GENERIC Solar Shading POSO Sii ida tii 38 Generic Ime PEro S stg anceauitulans a a se eadigutcacons oud aca A 38 Configuration Part 3 Binding FUNCTIONS tO ZONES ccccccessecceccesececeeeeceecensceceeeeceseuneceeseneeeetas 39 Security and Comfort short reminder of the concept Of ZONES ccoocccnccnnccnnncnnncnnnnnnonnnnnacononanonoss 39 A RO 39 Make setings tora UCI ao ico 40 Configuration Part 4 Upload Configuration to Building Controller oooooooonoonommmemomm o 41 Make Upload ains anar 41 Configuration Part 5 Configuring Remotes Switches cccccooooccnnnncnonacononnnonaronnnonanononononaninos 41 Configuration Part 6 Arranging facades cocoononcnconociononacicnnonaoronnonariononasionconarrnonariononariononnarenoss 41 Move and Tese a TACACE aa 42 Merge tacades eonen a a a eahaneatuteak 42 Configuration Part 7 Extend Project change the Configuration cccccccsssecceessececeeeeeeeeeeeeees
9. 44 Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Managing remotes and switches iia ada 44 OC AZ ONG Soer r E r NA 44 L calCommanas and PONY cecer aa a a sales hates A N ose 45 To add remove or replace a Remote SWwitcCh oooccccnnconoccnnnnnnononoconnnonanoconnnonanonnnonnnncnnnnnnnanononnos 45 PICU TRO WNOUS O PRD POPE E O aaeeeteniaanetenanen aerator asamaceea 45 E eee 45 REMOVE REMOTE fairies cers aches ttre ceed el cena la ac ee et asa ade O ct ac dca Sk E 45 To view the Remotes in the SySteM ceeccccessececceseccccesccecsuesececeeeceeseesecessuseeeeeeceeseuecetsegecesseeees 46 To add or remove Motors linked to a REMOtEC ccccccssssssseseccccceceeaaeeseeeccceessaeeseseeeessaaeaeeeeeess 46 Settings TOR a REMOTE ds 47 Wilt Ua Remote SERVIC arica a a a a 47 Views in the animeo IP Visual Configuration software ooocccconnccnnononcnnnnnnncnnnnnncnnnonanononononnnonaronnonanonnos 48 Facades NM iia 48 Mastering th Zone PHONE aa 48 GrOUDS VIEW A E RR 51 LIS EMI aida 52 Generales ii Sos 53 Un SEN Stats 53 Location and TINE ata 53 Gone 54 Pass WOTA fopersessssak yaad cee secenanate a heels sehen pant aremnea seeks 54 A oid aa a a te tineuedn a 57 FUNCTION SEUS VIEW iii 58 LOES VIEW A E 58 SENO TOE PRO
10. 460028 000 S A 2011 000 31500 94 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Logs View where you can see system and sensor logs records of events that have happened in the system Motor View where you can see and manage all the motors within the system Advanced gt o System Hardware View shows a window where you can see the backbone of the system and all its hardware e Help gt About shows a window where you can read about software versions legal aspects and other topics concerning the Somfy animeo IP system Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice 95 Somfy Manual for animeo IP Legal information ANIMEO IP END USER LICENSE AGREEMENT ATTENTION PLEASE READ THE ANIMEO IP SOFTWARE LICENSE AGREEMENT CAREFULLY BY DOWNLOADING INSTALLING OR USING THE ANIMEO IP SOFTWARE YOU INDICATE ACCEPTANCE OF AND AGREE TO THE TERMS AND CONDITIONS OF THIS AGREEMENT IF YOU DO NOT ACCEPT THESE TERMS AND CONDITIONS DO NOT DOWNLOAD INSTALL OR USE THE ANIMEO IP SOFTWARE AND RETURN THE ANIMEO IP SOFTWARE TO SOMFY ANIMEO IP SOFTWARE LICENSE AGREEMENT The following license agreement is between You and Somfy SAS a French company with a share capital of 20
11. All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 51 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP SecurityZone 1 Active Function Position Has functions Ia gt ODO Picture 59 Example of groups in Groups View List View This is a view that you can reach from the big tabs with blue icons on the top bar fa In this view you can supervise the system status on many levels You have all the H different zones the animeo IP is supporting and all the motors that are included in the configuration You can also manually control the system by selecting an item in any list and clicking on the PC Command buttons see section PC Manual Control further below or right clicking to activate the context menu where you also get options to manually control the system Furthermore you can double click on any item in the list to open corresponding views or windows for a quick access to make changes or retrieve deeper information about the system component in question Picture 60 The Lists View Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 52 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP General Settings Some settings in animeo IP are not linked to any syste
12. Based Configuration For each facade a zoom in feature is available and it is in that zoomed in state where the Zones can be modified When a facade is zoomed in it looks the same But there is now the possibility to select individual motors or zones via the Select mode toolbar above the facade Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 48 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Picture 56 Facade zoomed in with the Select mode toolbar at the top You can either choose to select motors within Comfort Zones Security Zones or individually When a motor is selected the window or matrix cell will get a blue frame and a small check icon in the upper right corner In Configuration Mode a zoomed in facade looks a bit different with additional toolbars to master the zones and motors Picture 57 Zoomed in facade in Configuration Mode These three additional toolbars are Motor Comfort Zone Security Zone Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 49 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP session Rename Replace Select PEREN 9 Motor O Comfort zone Security zone Pictur
13. If that is the case then uncheck the Use default credentials checkbox and enter the User and Password credentials given to you by the IT department in the building Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 56 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Unit settings Location Time General Network General network settings Use DHCP Recomended IP Address Subnet mask Client proxy credentials for updates and weatherinto Use default credentials TE Ss Picture 65 General Settings window Network Click on the OK button when you have made all your settings In Configuration mode all these settings are accessible Sensor status View In this view you can monitor the current values being outputted by the sensors in the system You can filter to see only specific Sensor boxes or all You can click on the different tabs to show different kinds of sensor Sun sensors Key lock Sensor box name Input Sensorbox 1 8 Sensorbox 1 Sensorbox 1 Sensorbox 1 Sensorbox 1 Sensorbox 1 sensorbox 1 Sensorbox 1 Picture 66 The Sensors View showing the Suns sensors Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 57 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by
14. N Peo ee 75 A ita E cage eitar eat scant Bost senasens EN N 76 ES E a E E T E E E A E T E E A A A E neuuas A EA caged E AN 77 Position Regular and S m trackihg secina E eebaeel died deaueeeie nuns 78 Custom Detalla oa NN 80 SERVICE PACA o 80 Energy Service Pack area on bi ias 81 Web Remotes Service Package usd lcd 81 Create a Web Temo iS 82 Copyright O 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 4 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Ereate Web User att O E A 82 Select Web femote ereonomisa ie 83 local Command Om aca cn A A ae ea 83 Making virtual copies of real REMOTES vin 83 FHoorplans Service Packard dnd 83 Ada T ROOPAN dr aAWNE eona E 84 Navigating in the Forli A A A ii 84 tems tO INSertinto TNE FOO iii 85 nsertitems DY drog and COD aaa 86 Resize and rotate inserted dicos 86 Remove tems from the Floor plan cecccccssscccceeseccccesecccceseccceeesececsuecesseescessesecessegeceeseeeeeetegs 86 Highlight guides on the Floor planN ccccccoccnccnnccnncnoncnnnnononnnnnnanonnonanonononacnnnononnnnnncnnnonarnnnenanonons 86 Making remote bindings in the Floor plan ocoocccnccnoccnnonaconononanonnnonaconnnnnronnnnocononancnnnnnnccnnonos 86 Control motors 1romitne FIG Ol Pla a 86 Navigating between floors Pladur 87 Edit the Floor plan draWINE io aora 87 Deleted
15. Somfy SAS without prior notice Somfy Manual for animeo IP Function Status View In this view you can monitor the status of all the functions in a Security Zone and its Comfort Zones have To the left you have a list of all Security Zone in the configuration Click on them to show their current status Comfort functions Fire ComfortZone ComfortZonel S cutityZones Major Error Comfort Timer Default PC Building Lock Default Key Building Lock PC Security Zone Lock Local PC Command Picture 67 The Functions Status View Logs View In this view you can search through the history of all events that have taken place in the system The view has two main parts Sensors Log and System Log Select the log type you want see by means of the tabs in the upper left corner D Sensors log In the Sensors view you can select from which sensor you want to see historical data You will get a Note If the Visual Configuration software has not been connected to the BuCo for a long time the synchronization can take a while The logs are automatically updated while the Visual Configuration software is connected to the BuCo diagram that shows you the min blue max green values and the average value red Hover over the diagram to get different detailed data You can also narrow the time interval covered by the data Go to the bottom part and two white squares will appear Drag these inwards to decrease the time frame shown
16. System log In the System log you can see all events that have happened which tends to be a lot You can filter this information by selecting a special zone within the system or using the Type filter Also a Time filter is available to easier pin point your search Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 58 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP JE mimi Sensors Sensors System Zone filter Show rones AAA IE P im 2 25 2011 1 40 55PM_ Function Comfort Timer activated on actuator 060237 group ComfortZon 4 3 25 2011 1 35 54 PM Function Comfort Timer activated on actuator 060237 group ComfortZon 4 3 25 2011 1 30 53 PM Function Comfort Timer activated on actuator 060237 group ComfortZon 4 3 25 2011 1 25 52 PM Function Comfort Timer activated on actuator 060237 group ComfortZon 4 3 25 2011 1 20 51 PM Function Comfort Timer activated on actuator 060237 group ComfortZon 4 3 25 2011 1 15 50 PM Function Comfort Timer activated on actuator 060237 group ComfortZon 4 3 25 2011 1 10 49 PM Function Comfort Timer activated on actuator 060237 group ComfortZon 4 Avg value 15 Min 14 Max 15 11 34 13 4 E 4 4 Type filter Ti System El Errors El Function El Actuator Time filter Period oo TM
17. That way the tool knows where to go Cancel Previous Picture 9 Make New Configuration Connect Commissioning Project settings The more you can describe the system the easier your commissioning will be since you get help from your own explanations So enter correct names and information Also you have to set the project location which is a must to get a weather forecast and for the sun tracking function Passwords must also be set to protect the configuration and the system as a whole Click on the buttons at the right side to open small windows that help you to make these important settings Click on the Next button when you are ready to go to the next slide Your settings are saved as soon as you type them Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 19 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP information will be used to calculate summer and winter time automatically Installer contact Installer phone Installer email System configured by When will installer information be used It can be wise to fill in these fields in case anything would happen In the software the user will be able to look at this information Picture 10 Make New Configuration Project settings Commissioning End limits on motors It is of gr
18. You can have a Disable local control timer that is active from one day to the next If Reset local control action is chosen you cannot make a time span since the reset is triggered once at a certain time 5 Delete Click on the red squares with the white x on the right hand side to delete a timer 6 Active period Additionally you can set for all timers added which days they should be active This is done via the list box located bottom left of the timers Local Command Timer El Function enabled 05 00 to 12 00 03 oS 06 07 BB la m so ae Reset local control Pa Everyday h Add timer Picture 89 Function Settings Local Command Timer Disable and Reset Local Command Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 73 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Comfort Functions in priority order Ts J Note When using several function of the same sort in the same Comfort Zone these are prioritized as well For example if 4 sun functions are used in the same Comfort Zone the first sun function in the list will have the highest priority and hence will override the other ones To overcome this priory use the Active Period feature for each function Comfort Timer This timer is used to set the solar shadings in a specific position in certai
19. are some concepts that must be understood and questions that need to be answered before you start the commissioning of a project with animeo IP Commissioning the act of creating the Configuration The process of setting up and finding hardware such as Motors and Sensors defining the system as a whole is making the Commissioning During this process the structure of the system Configuration is defined Most of the Commissioning is made via Wizards in the animeo IP software Afterwards the Commissioning the structure of the system needs to be filled with functionality and bindings We simply call this Configuration The auto discovery feature The animeo IP system can auto discover components that are connected to the system This feature will make the commissioning much quicker The following components can be discovered Somfy RS485 motors The discovery process will detect all units and thereafter the position of the motors will be detected by the patented state minimization method This method will create facades where the motors are located The detection of motors can be done from outside or inside floor by floor or even room by room Afterwards the different parts of a facade can be merged into one big facade by dragging the different parts on top or side of each other Sensors The different sensor boxes Outside sensor box Inside sensor box and Compact sensor will be discovered automatically In a wizard the user can select which inpu
20. assign motors to the Group To the left in the sidebar s toolboxes you can find the Motors list Select a motor that should be inside the created Group drag it onto the Comfort Zone you want to populate and release the mouse button You can now see how the motor is inside the Comfort Zone Proceed to drag all the motors that should be in this Group into this Comfort Zone Repeat steps 1 3 until you have defined the whole building in parts of Groups In the Motors list you can check so that only unassigned motors are shown This will reduce the list as you populate Comfort Zones The list should be empty when you are finished Configuration Part 1 Facade Based The configuration you have made so far if you did all the steps in the Virgin Wizard has discovered and assigned motors sensors and switches You have defined the facades or parts of the facade in Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 35 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP different matrixes Now you need to define in more detail how the Security and Comfort Zones should be in each of these parts Close the Welcome Center to reach the main window If you have just done the Virgin Wizard then you should be automatically in Configuration Mode Otherwise click on the Configuration Mode button in the bottom ba
21. better understand the status colors and patterns used The four colors Security color Security functionality is marked red and when a Security function is active the Security Zones gets red and the motors as well In some cases the Security color blinks Facade 1 Picture 73 Example of how Security Colors looks like Comfort color Comfort functionality is marked green and when a Comfort Function is active the Comfort Zones gets green and the motors as well SecurityZone 1 7 Facade 1 ion ncti osition Position o ions Ia RRO f Has ions 10 ComfortZone if ne 1 a 5 2 one e Picture 74 Example of how Comfort Colors looks like Local Command color Local command functionality is marked with yellow color If a Local command is active it will be shown in a yellow color on Comfort Zones and motors Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 61 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Facade 1 SecurityZone 1 1 SecurityZone 2 e Active Function i Active Function 7 e Position Ml Position Has functions fry gt ROO i Has functions D gt 2 Picture 75 Example of how Local Command Colors look like PC Command color When a PC Command is used it is shown in a purple color The zones get purple and also the motors Fac
22. can I reuse the remote settings done for new Web remotes Once all the physical Remotes have been discovered and linked to Motors you can make a virtual copy of the motor links to a Web remote First create a new Web remote Double click on it in the Remotes toolbox to open the Remote View Now drag and drop the real physical remote into the Remote View The copy is now made Note that changes to the physical one will not be transferred to the Web remote after the copy is made Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 88 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Case 6 Using Floor plans is there a way to manage motor links to remotes In the Remote toolbox you have to define all remotes but in the Floor plan view you can make the links between motors and other remotes The Remote View will pop up when you make these links System maintenance The animeo IP system supports simple ways to update or replace hardware if they get damaged or that new feature is wanted Firmware Upgrade While in Configuration mode under the main menu Tools gt Advanced gt Firmware Upgrade the system can be upgraded with a new firmware software The reasons for this can be that hardware delivered can have older versions installed that do not support newer functionality and features There are two w
23. can undo a merge by choosing Revert from Building Controller in the Main menu File as long as no Upload has been made in between Facade 1 2 al A E ee ee et ee wet tres ore gt i j i d A A ee Bie ee es rra ton ay r i l D ai ae ah ied tore er ed A a rd wr esi gt j j i E i es s co Picture 49 Merging from top left Picture 50 Merging from bottom right Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 43 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Picture 51 Merged result from top left Picture 52 Merged result from bottom right Remember to go back to Binding Mode by clicking on the Binding mode button when you have finished with the arrangements Configuration Part 7 Extend Project change the Configuration If you want to change or add something that is related to the basic structure of the configuration then you must do these changes via the Extend Project Wizard In this wizard you can Create a new or edit an existing facade Configure unassigned motors Discover and add more motors that have recently been connected to the animeo IP system Add sensors that were not previously used or connected to the animeo IP system All steps inside the Extend Project Wizard are b
24. expand a Security Zone merging motor s from another Security Zone select the Security Zone in questions or the motor s to be included and click the Redefine Button A dialog will appear asking which Security Zone that should be the target zone Select the Security Zone that will take over inherits the motors and click on Select button to continue Sometimes a new Comfort Zones needs to be created and you will be asked to name it Note It could happen that a Security Zone or Comfort Zone have motor members spread E out in the facade not being next to each other Use the Select Mode to check how the Zones are created and where the zone motor members are Groups View You can reach this view from the big tabs with blue icons on the top bar This view will ele show the Configuration s zones in Groups i Note When Fa ade Based configuration is chosen the Groups View will also be visible but in y this case no changes can be done via this view The Security Zones are marked with a red line Inside them zone status is shown such as active functions position and which functions the zones has Also the Comfort Zones are presented below with a green line The statuses of the Comfort Zones are also visible The motors linked to each Comfort Zones are presented at the bottom of the Comfort Zones To reveal the motors click on the arrow at the bottom right The motor status is also shown here Copyright 2003 2012 SOMFY SAS
25. is a possibility to move all motors and sensors from a Sub Controller to the BuCo In this case the bus wires need to be tapped into the BuCo s buses Use this option if you want to exclude a Sub Controller from the system Replace a Sub Controller with Sensor Salvage the function configuration To replace a Sub controller with a sensor that is used in a function and in order to not erase this function follow the steps below Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 91 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP 10 11 12 13 14 15 First locate the old Sub Controller and physically replace it with a new one Please keep track of boxes IDs or MAC address to easier identify them later on Connect the Ethernet cable the sensor bus and lastly the power cable Note do not connect the motor bus yet Wait and see so that the Sub Controller starts and gets a heartbeat two green flashes every second Go back to the PC and the animeo IP Visual configuration software and go to the Extend wizard and go through the steps You need to be in Configuration mode then go the top menu Tools gt Extend Configuration Go to the Extend wizard again and go through all the steps this time the Sensor box connected will appear as a new Sensor box Select all sensors used in tha
26. notice of six months by registered mail This termination shall be effective on expiration of the six months notice If You fail to comply with any term or condition of this license agreement Somfy shall send You notice by registered mail You shall have 30 days from receipt of such notice to remedy the failure If not remedied this license agreement shall be forthwith terminated without prejudice to damages This license agreement may be terminated upon written notice by Somfy should the Software and or its Documentation become or in the opinion of Somfy is likely to become the subject of a claim of infringement of a patent trade secret copyright or other intellectual property right This license agreement shall be terminated automatically if You do not use and or purchase Somfy Controllers any more In all the above cases of termination You commit to destroy the Software and its Documentation and the back up copy if any upon either the date of effect of the termination or Somfy s request to do so You acknowledge that this termination shall not raise any right whatsoever to Your benefit 6 Consideration This license agreement is granted to be used by You together with Somfy Controllers purchased by You Therefore this license agreement is granted with no itemized consideration 7 Export Requirements You shall not export or re export or allow the export or re export of the Software and its Documentation or any copy in violati
27. question may not be connected or wrongly connected or unpowered Click the Discover system button to search for system components installed in the building What does Discover really do During a Discover the system will call for system components such as Motors Motors are actuators things that acts All actuators that hears the call will respond and say to the system lam here I am a motor I am open for configuration This actuator will then be added to a list of actuators that we later will use to find actuators position and in the end to be added in the configuration Also sensorboxes and sensors will be detected by this discover Picture 16 Make New Configuration Discover step If all seems fine then click on the Ok button to confirm Then continue the wizard Commissioning Test In this step a test will be made so that you can visually confirm that all discovered solar shading motors do move Click on the Test button to start the test Now you have to take a look around to see that all motors have moved to a 50 position Answer the question when you have the answer Click on the answer that corresponds to your observation Continue the wizard if everything is correct Now we will make a test to see if all Solar shadings move Click on the Test button to send all solar shadings to a 50 position Why do we make this test Doing the test is an easy way
28. see the system organized in facades choose the Facade Based approach This is also the quickest and most intutive way of finding the motors If you only want to use the floorplan functionality or just want to se the system in groups then you should choose the Group Based approach Previous Next Cancel Picture 18 Make New Configuration Facade or Group Based Commissioning Group Based In the view bellow you will have a list of all the motors that the animeo IP system found In the motor list you can see if the motor is used by the system the serial number the motor has and what solar shading type and application this motor was made for Additionally there is some descriptive information that you can give to each motor for easier identification When you select a motor in the list all the above mentioned properties except for the serial number are accessible and editable in the textboxes to the left It is strongly recommended that you enter descriptive mnemonic names for each motor because it will help you a lot in the later stages of the commissioning Under the motor list you have an option that the selected motor should wink when it is selected This can be good if you want to visually confirm which motor you have selected Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 24 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by S
29. selected by default This design presents only three buttons for the user to control the shades Up Stop Down 30 50 and 70 this design presents an additional three buttons with pre set solar shading positions given in percentages Up Stop Down 30 50 70 and Auto Manu This design includes an additional Auto Manu button where the user can at will go back to Auto mode setting the system to Automatic which will save energy This design is intended to encourage users to proactively save energy Local Command off delay The time stated here is the time span for how long the Local Command will be active before the system goes back to Comfort Mode You can choose to have one unique per remote or use the Global one configured in the General settings view Making virtual copies of real Remotes y One good thing to know is that you can drag in physical remotes into the WEB remote view Ss Doing this will create a virtual copy of the real one This is an easy way to administer WEB remotes This means that the WEB remote will control the same motors as the real one Any changes made to the physical remote will have immediate effect on the virtual one simplifying the management of remotes Floor plans Service Package When this service has been activated the Floor plan functionality is unlocked and visible in the animeo IP Visual Configuration software Enter Configuration mode and go to the Floor plans view by selecting the Floor plan icon i
30. settings for a function For most functions to work they need one or more sensors to listen to Click on the Select button to open the Select Sensors dialog In this dialog you can select which sensors the function will listen to Click on the sensors you want to allocate or select them and use the arrow buttons to transfer them to the Selected Sensors list The function will listen to all the sensors that are in this list Click on the Close button to close the dialog ee Sun 1 Function enabled Sun sensor used Ha On threshold 24000 lux Off threshold 20000 lux On delay 10 oray o vio gt Regular position Specific position ME Pot 100 Angle 45 i Sun tracking position Time penod as Everyday z Whole day Specific time Start time 00 Bos Picture 43 Example of the function settings window Make the function settings you want and close the window The settings you make are saved the instant you change a value Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 40 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Once you have made one function you can in the zone tree toolbox located in the upper left easily drag and drop that function from one zone to another and copy all the settings you have done But you have
31. settings made in the Virgin wizard Use this backup if something happens during upload in the Virgin wizard BeforeCommissing A backup of the Configuration that existed before a new commissioning Use this backup to restore a Configuration if a new commissioning fails or was unintended SystemUpdateBackup This backup is created before a firmware update Use this backup if the Configuration fails to run automatically after a Firmware Upgrade YD Note Only the Configuration will be restored not logs Document the Configuration Print the settings made To document the Configuration and the settings done you can use the Configuration Report View File gt Configuration Report View This view shows a summary of the Configuration the structure of the zones the functions and motors within them Configuration details for Somfy Office Design Center GoSoft General parameters Location 2696503 Longitude 12 26904 Latitude 57 77051 Time zone Europe Stockholm Error e mail admin somfy gosoft com Service e mail admin somfy gosoft com Group hierarchy HH GoSoft M Facade_1 Security E Otommys B Ken amp Stefan E Samuels Facades 1 of 14 Print Close Picture 111 The Configuration Report View Click on the Print button to send the report to a printer or print it in a digital format XPS or PDF Main Menu content e File gt Make New configuration when you want to make a commission
32. shall not remove modify or create any derivative works of the Software and its Documentation including translation b You shall not disassemble decompile reverse engineer or otherwise attempt to derive the source code of the Software except for interoperation purposes as indicated herebelow C You shall not remove or alter the Content of the Software d You shall not make the Software its Documentation or any of its Content available in any manner to any third party for use in the third party s business operations e You shall not redistribute sell rent lease sublicense or otherwise transfer rights to the Software and its Documentation to any third party f You shall not use the Software with products other than Somfy Controllers With reference to b information necessary to achieve interoperability of the Software with others programs will be provided to You by Somfy upon Your written request sent by registered mail You shall observe strict confidentiality with respect to such information If and only if Somfy declines or does not reply to request within 2 months from receipt of such request You may reverse engineer the Software but only to the extent permitted by applicable law and shall inform Somfy in writing prior to doing so 4 Ownership Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 96 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done
33. then you need to be able to see the facades i e a large number of motors at the same time preferable outside the building or floor by floor The biggest advantage of using Facade Based commissioning is that you will quickly find and identify the motors via Somfy s Visual Click finder and also the facade gets defined in the process and will be shown as a graphical facade element in the animeo IP Visual Configuration software On the other hand if you have a blueprint where all the motor IDs are shown and where it is difficult to get a good overview of the motors to be commissioned then a Group Based commissioning is the right way to go In the animeo IP Visual configuration software you have to create and define the groups which are basically the Security Zones and Comfort Zones Once they are created you simply drag and drop the motors that should be included in each zone Facade Based How you should plan There are some general recommendations that should be considered before you divide the building into facades or sections A facade should only have one cardinal direction Facade direction for easy sensor allocation You should be able to see the whole facade section at the same time from your standpoint Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 13 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy M
34. to find out that all motors and solar shadings you want to control in the end is actually alive You can see on the facade easily if all solar shadings has moved Picture 17 Make New Configuration Test motors found Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 23 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP a certain part of the building s power is shut down or that a SubCo is unreachable In these cases where the cause is known and the cause will only affect parts of the commissioning the No Continue anyway is the right choice No Continue anyway During commissioning unexpected things can happen Sometimes Commissioning choose type of Configuration You have now arrived at the wizard dialog where you choose what kind of configuration you want to make If you have read the Before commissioning section of the manual you should already know which type of configuration you want to make Choose the type of configuration you want to make by clicking on the radio button or the icon in question Then continue the wizard B animeo IP Visual Configuration Make Configuration Wizard commissioning has never been so easy mS sE What kind of configuration do you want to create Facade Based Group Based Recommended What is the difference If you want
35. to remember to check if the same sensors should be used For more info about the functions in animeo IP see the section Function Settings Configuration Part 4 Upload Configuration to Building Controller So far your configuration only resides in the Visual Configuration software You have to push the configuration to the BuCo to make it work Before uploading a configuration we recommend that you save the configuration as a backup Go to the File menu and select Save configuration and complete the save dialog that appears Make Upload When you are in Configuration Mode three different buttons appear above the Configuration button The one to the right is the Upload button Click on this button when you want to upload a configuration or changes done to a configuration This upload will take a while and you will see some yellow circles spinning during the process Picture 44 Upload button to the right in blue Configuration Part 5 Configuring Remotes Switches If you did the switches and remote part in the virgin wizard you will have the remotes inside the configuration When you are in Configuration Mode all switches and remotes discovered by the Virgin wizard are visible in the Remotes toolbox in the sidebar to the left These remotes presented in the list are for the moment not controlling any motors at all Picture 45 The Remotes toolbox There are also other ways to add remotes or switches to the configuration
36. without prior notice Somfy Manual for animeo IP What does it mean in practise Well if a motor is not powered then it will not be found and it will not be included in the configuration So please check that someone has tested that all motors has power Picture 12 Make New Configuration Motors powered question Commissioning ILT2 motors If the project contains Somfy ILT2 motors you need to do some extra manual handling since Somfy ILT2 motors cannot be auto discovered If the project does not have any ILT2 motors then you can continue the wizard ATTENTION Do not mix ILT2 motors with other RS485 AC motors on the same bus line In this wizard step you can import motor IDs from tab separated file made in Excel or equivalent software You can also manually enter each motor ID Select which method you want to use Note that when you import from file the motors ids are imported behind the scenes There is no confirmation If you try to use a file that is not compatible or enter incorrect motor ids then the fields will become red E o SS Does this system contain any wired SDN motors that does not support auto discovery ILT2 motors Why do I have to do this Some motor actuator interfaces SDN simply does not support motors being discovered automatically to work around this the motor ID numbers has to be manually imported into the system Picture 13 Make New Configuration ILT2 motors
37. 000 E Outside Sensorbox Sensorbox 3 00 26 18 5C F8 6D 53300 Outside Sensorbox Sensorbox 5 Sensorboxes which one should I use Well mostly you will use everything the system finds But sometimes a system perhaps shares sensor network with other systems and then you need to specify excactly which ones you will use Picture 30 Make New Configuration Sensor Boxes discovered Continue the wizard when you are ready Select sensors For each Sensor box you choose to configure you will get a list of sensors that the Sensor box in question supports The animeo IP system can auto detect some of the sensors and these are pre selected Your mission here is to select which sensors you want to use and give each of them a good name Only the wind sensors can have different hardware types default or heated OSB1 Sensorbox 3 Now check the sensors you want to use and Uncheck the ones you don t want to have in the configuration Enter names for them for easier allocation later on Default 7 1 Default Why are some sensors already Some sensors can be auto detectable These are already checked But if you don t want to use them simply uncheck the sensors in question E E EAEE 6 E E Picture 31 Make New Configuration Select which sensors to use Continue the wizard when you are ready Commissioning Switches and Remotes When you choose to continue with the wizard when all Sensor boxes are done you wil
38. 000 000 Euros registered in the Trade amp Commercial Register of Annecy under the n 303 970 230 and having its head office at 50 Avenue du Nouveau Monde 74300 CLUSES and governs Your use of the ANIMEO IP Software You and Somfy hereby agree as follows 1 Definitions Content means without limitations object and source codes trademarks logo designs legends symbols labels copyright any intellectual property rights embedded third party softwares and other proprietary notices included in the Software Documentation means all the documents related to and distributed with the Software Software means the animeo IP software The animeo IP software is dedicated to work exclusively with Somfy Controllers Somfy means Somfy SAS a company organized and existing under the laws of France and having its principal place of business at 50 avenue du Nouveau Monde 74300 Cluses France Somfy Controllers means Somfy building controllers and Somfy motor controllers working with the Software You Your means your company or organisation 2 License Grant Somfy grants to You a non exclusive and non transferable license to use store load install execute and display the Software and its Documentation for final use by You and or Your customer and his subcontractors together with Somfy Controllers You are authorized to make one copy of the Software for backup purposes only 3 Restrictions a You
39. 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP 5 Off delay From the time it must have stopped snowing before the function turns off Rain When it rains some Solar Shading have to be locked in their secure position For interior Solar Shadings this function is not needed CD Rain Rain sensor used F rr A m 5 Rain 1 Sensorbox 1 EN Ofrdelays so Picture 86 Function Settings Rain Settings 1 Rain sensor allocation Click on the Select button to the right to open the Sensor allocation dialog Allocate the rain sensor by double clicking or by drag and drop to the list to the right 2 On delay The time it must have been raining before the function goes active 3 Off delay From the time it stopped raining until the function turns off Frost When it is frosty some Solar Shadings have to be locked in their secure position For interior Solar Shadings this function is not needed Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 70 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP pl Frost Temperature sensor used Temperature 1 Sensorbox 1 Temperature threshold E E On delay EN Off delay 0 Picture 87 Function Settings Frost Settings 1 Temperature sensor alloc
40. 3 36 File folder gt He Favorites de animeo 2 2 2011 05 26 03 36 File folder Le czech 2011 05 26 03 36 File folder gt G Libraries dy mina dok 2011 05 26 03 36 File folder de gosoft snubbarna 2011 05 26 03 32 File folder gt Il Computer Jo Q108799 2011 05 26 03 32 File folder i i 2 2011 05 26 03 32 File folder gt l Network Ly AstroPhoto PS 2011 05 26 03 26 File folder Lo nya datorn 2 2011 05 26 03 26 File folder do TILL HASSE 2011 05 26 02 58 File folder N J nya datorn 2011 05 26 02 56 File folder y Ly ParaSol 2011 05 26 02 49 File folder File name ILT2MotorimportEmpireStateluneExample tbd Save as type Text Tab delimited txt Authors Samuel Spanberger Tags Add a tag Title Add a title Hide Folders Tools Cancel Picture 15 Make New Configuration Example of Excel s Save as dialog Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 7 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Commissioning Discover The animeo IP system can auto discover the components that are connected Click on the Discover button to start the discover sequence This could take a while The wizard will list all the system components it found Check that the numbers match with the numbers of components actually present If the numbers differ then the component in
41. ES Sun tracking positions Position 0 Angle o Picture 40 The Generic Solar Shading Position window Generic Time Periods In this window you manage all the generic Time Periods that you want in the system You can freely set the condition for when the time period is active Use it wisely Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 38 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Time periods in the system Active selected months on selected days Settings v January Y February Y March Every day in selected months Specific weekday in selected months Specific date in selected months Picture 41 The Generic Time Periods window Configuration Part 3 Binding Functions to Zones Now the configuration has the system backbone defined and the facades are divided into different parts which have motors in them Now let s bring the system alive with functions Security and Comfort short reminder of the concept of Zones In a Security Zone you put security functions which mostly are used in a broader scope to cover big segments of the building s facade In a Comfort Zone on the other hand comfort functions are used and these zones are mostly created to support room concerned behavior Comfort Zones exists inside a Security Zone because Securit
42. For more information go to the section Managing remotes Configuration Part 6 Arranging facades Ina Facade Based configuration there is an extra feature that Group Based configuration does not have It is the ability to arrange the facades To activate this functionality you have to click on the Layout Mode button located in the middle of the buttons appearing above the Configuration Mode button on the bottom bar Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 41 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP H Click to enter Layout Made Picture 46 Layout Mode button in the middle Move and resize a facade When you are in Layout Mode you can Move a facade to another position inside the main view Do this by selecting a facade with the left mouse button the cursor will change to an arrow and drag the facade the wanted position Resize a facade when you want to have a bigger or smaller default size of the facade Do this by selecting a facade You can then see small circles in each corner of the facade and a thin line going between them Drag in the circles if you want to resize the facade diagonally or drag the thin line if you want to change the width or height only Picture 47 Facade selected for resize or positioning Merge facades When you a
43. Hood T 87 MOE TER e e o PE E A po a aati asDaesiane a 87 Case1 Customer asks for different sun function behaviors during the day coooccccconocnnnnnocnns 87 Case 2 Create good energy optimal scenarios as the ones in animeo IBH 88 Case 3 Reuse function SETTINGS Made csi coo ia id 88 Case 4 How do undo something in the ConfiguratiOnN cccoooccnncnnnccnnnnnncnnnonaconnnnnnonnonaronnonanonnss 88 Case 5 How can reuse the remote settings done for new Web remotes cccooccccnnccccnnccnnniannnnnss 88 Case 6 Using Floor plans is there a way to manage motor links to remotes c oonccccnnccnnnnicnnnnns 89 SVSECMI Mae Mall Ces nia 89 FEMA WO ORAS sims onda 89 FRO el aceasta a a Sata sana ctdandeg a uatentosuaneeceestatnastactnaneanetec came 89 Replace a MOE dd 89 Replace a Remote anodino nea 90 Replace a SUD CORTO dia 90 R pl ce a Bulldine Controller uni a a 92 Restore CONTE UA e pl eo AS 92 Document the Configuration Print the settings made ccccooooccnncnnnnnnncnnnnnonanicnnnnnononnnnnnnanononnss 93 Mai Men CO Nte li 93 Copyright O 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 5 A 2011 000 31500 5 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP ES SLIN ON A II uo o toe ueerenasenerssuamuatauee mae dsencmeduaeuns aatetass Copyright 2003 2012 SOMFY SAS All rights res
44. P CO Po PE E A 58 A e ne ee oe 58 Sistem ar OW are VI lora tedio ia 59 PC Manual Control manual control Of the SysteM cccoococccncnnoccncnnnaconnnnanonnnnnaconnnnanononanonnnonaronnonanonoss 60 System and function icons status colors and patterns USCO ooccccccnccnncononcnnnonanonnonanonnnonocnnonaronnonanonnos 61 THE TOUR A sae teapous saws neues sana tas NANON 61 SOCUIITY CONOR aee or 61 COM OVE COON trata ot 61 EOC Al COMMING COR 61 PC COMMIT ANACO OR 62 Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 3 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP lege oro PPM Er PEE PE PO A eee arnt te arene 62 Zone Partially Controlled pattern dada 62 o A aucune its 63 MOTOR SCENE 63 AARAM OTO RA 63 Repor E aM O aen a o 64 Delete MOTO a EAR E EE EO EE 64 Reverse A A a maese Gees bederegkaeauade 64 FUNCHUON Sete Saa anaconda odds 64 Security EUnections IN Priority Ode ia 65 A e o E A EE AT 65 MORENO nana 65 PE Bunding LO 65 KEV BUNGIE doce do 65 PE Security ZONE Locas a iia 65 KEV Security Zone Lock coa i co 65 Wind PRE dad 66 WINO O 67 A O asauacoumeeceacess 69 E 70 A Po II cares E EA 70 Security TIME A A teed uaduetseuyviecaubesteneuedes 72 EOC Al Commana Mena iaa 72 Comtort Functions INM DIIOMEY Ol COR si a 74 COE OIE TAC OS COLE RAN TP O o E OEN 74 A E
45. Picture 68 Logs View Sensors log Picture 69 Logs View System log The Type filter There are four different actions that get logged System events that affect to the whole system Errors system events that is classified as an error Function events associated with the functions linked to zones Motors actuators events associated with motor actions System Hardware View Here a hierarchical overview of the system is presented For each box BuCo or Sub Controller you can see which Sensor boxes or motors that are connected Their IDs and other important information Xx ID O60E8C Name Tommy Type InteriorBlind Facade Facade 1 Security Zone Facade 1 Security Comfort Zone Facade 1 Comfort Picture 70 System Hardware View Showing the SubCos and the motors Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 59 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP PC Manual Control manual control of the system From almost any object in the Visual Configuration you can control the system by right clicking on the object and choosing from the options Facade sam Security Active Function Local PC Command Position Stop Has functions Me Ta Active Function Picture 71 PC Manual Control by right click on object If you want more precise co
46. This extra feature will enable users to take control of their blinds from their PC Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 47 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Views in the animeo IP Visual Configuration software Facades View If Facade Based approach was chosen or that the Configuration is Facade based then Facades view will be visible You can reach this view from the big tabs with blue icons on the 55 top bar In this view you will see all defined facades and in each fa ade there is a matrix where the motors are placed Solar shadings in each matrix cell will simulate the motor position Facade 1 Picture 55 Example of a facade in Facades View If you hover with the mouse over the solar shadings you will get a tooltip that shows different status such as motor name active function position and status etc You can double click on a facade to zoom in on just that facade in questions or use the magnifying button on the top right corner On the top Left corner you have a toggle button to activate PC Security Zone Lock which will send all solar shadings to Secure Position 0 until you toggle back to inactivate the lock Mastering the Zone options In Facade Based Configuration the way to create zones is very different compared to the zone creation in Group
47. This step in the software gives you some options Create a new facade when you want to define a facade and find the motors that are there Edit a facade when you want to change and modify an existing facade Configure unassigned motors motors which location is not known and hence is not placed inside a facade yet when you don t want to make all the facades at this moment Leave facade configuration when you are finished with the facades you want to make Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 25 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Please select an option below to configure the facades and to position the motors All motors have now been configured great You can now choose to Finish or to Edit a facade Facade options what to choose Depending on what configuration stage the commissioning is in different options are available Chose the option that best fits to want you want to accomplish Picture 20 Make New Configuration Facade Based option menu Select the Create a new Facade option and continue with the wizard Facade creation You are now in the first step of making a facade Give the facade a meaningful name and select which cardinal direction it faces Continue with the wizard why shouid I enter this informatio
48. While in Layout mode 0 select an item of choice and drag it into the Floor plan by holding left mouse button down while moving the mouse Move the item to where approximately it is in reality Once dropped they can be moved again Resize and rotate inserted items While in layout mode E when an item is selected it will get a frame with small dots in the corners Drag these corners with the mouse to resize the item To rotate an item you need to right click in the item with your mouse and there in the context menu that appears select rotate 45 Rotate several times until you reach the rotation you wanted mor Remove Rotate 45 Picture 105 Floor plan rotate item via context menu Remove items from the Floor plan If it happens that wrong items are placed into the Floor plan then select the item in question and press the Delete button on your keyboard or right click on the item with your mouse and select the Remove choice These items will go back to the Toolbars to the left Sometimes you need to refresh the filters in order to see them Highlight guides on the Floor plan When hovering with the mouse pointer above an item they will get highlighted If you hoover above a motor the remote that it is linked to will also get highlighted If you hoover above a remote the motors that it is linked to that remote will also get highlighted This is a good way to see the relations between the items Making remote bindings in the Floor p
49. Y A FLOR HRAL Y A FLOR LEVL Y A FLOR STRS Y A FLOR TPTN Y A GLAZ FULL Y A GRID COLS m Picture 102 Floor plan Import drawing options Press OK to finish the import process Navigating in the Floor plan Depending on the scale factor chosen you may need to navigate around in the Floor plan This can be done in several ways e Use the mouse s scroll wheel to zoom in or out e Focus on the Floor plan by selecting an unselected item on the Floor plan hold down the space key and at the same time hold down the left mouse button drag the mouse to navigate to a specific place This only works if the Floor plan is bigger than the screen meaning that you don t see the whole Floor plan Use the Zoom tool that you can find on the bottom right side Click on the handle to expand the tool then drag the square to a specific place and you will be navigated there Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 84 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Picture 103 Zoom tool zoom in part of floor plan drawing Items to insert into the Floor plan In Configuration mode there will be specific toolboxes visible when the Floor plans view is shown You can drag in Remotes and Motors into the Floor plan To help you distinguish between the differen
50. above ground In this case the start and stop must be adapted of course You can enter a negative value for start meaning that the time span will be delayed after the sunrise or before the sunset In order to cover both sunrise and sunset you need to add two sun functions And a third if you want have sun tracking during the day Custom Default The default function in animeo IP the function that is active when no other functions are active sends the solar shadings to position 0 However if this behavior is unwanted then use the Custom Default function Here you can set what should happen when the Custom default function goes active For example if you select Generic position there you can choose the Stop action that will leave the solar shadings at the position they are in A Custom Default function overrides the ordinary default function Custom Default H Function enabled Position Specific positon Y Generic position Position o _ Angle Lo E Picture 96 Function Settings Custom Default Settings 1 Enabled Per default the function is enabled but you can disable the function if necessary 2 Position Select if the solar shadings should go to a Specific position or a Generic position Service packages In animeo IP Visual Configuration software some extra features can be added if desired These features are divided into different Services The following Services are available Energy service package Cop
51. ade 1 Picture 76 Example of how PC Command Colors looks like Motor color Motors have been given a blue color indicating that it is a motor or that is selected Picture 77 Example of how the Motor color is used Zone Partially Controlled pattern Sometimes only some of the motors in a zone are controlled by PC Command or Local command When this happens a special pattern will be visible to indicate this Zone Partially Controlled state SecurityZone 1 l SecurityZone 2 Active Function Position Has functions e O Picture 78 Comfort Zones in Partially controlled state by a Local Command Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 62 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Picture 79 Security Zone in Partially controlled state by PC Command This pattern is visible in Groups View and Function List View Function Icon Icons are used to easily understand what function that is active or which functions a zone has There is one icon for each function The picture below is taken from the Icon legend toolbox shown in the Main View to the left Fire Alarm LA Major Error S PC Building Lock 3 Key Building Lock E PC Zone Lock 988 Key Zone Lock a Wind us Wind Direction Rain S Snow S a Frost Timer PC Com
52. al communication 1 Sensor bus 1RS485 bus 1Fire alarm input 1 Key Building Lock input 1 Major Error relay output Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 9 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Sub Controller SubCo Sub Controllers are used to extend the system in terms of number of motors sensors or switches the system can have The Sub Controller checks so that it has contact with the BuCo or it will command its solar shadings to Secure Position 0 in order to protect them or the end users The Sub Controller has the flowing inputs and outputs that are normally used 2 Ethernet ports for the animeo IP Bus backbone 1 Sensor bus 1RS485 Bus wep Note Separate data sheets and technical documentation are available for each product System restrictions For the time being a system is restricted to the following number of units For animeo IP RS485 The chart below explains the Number of SubCos used and number of motors that can be connected po x gt 2 200 400 600 800 1000 1200 1400 1600 1800 0O 400 500 700 1000 1200 1400 1600 1800 2000 In a system with 1000 motors the BuCo does not support any motors E gt 200 switches totally 200 Web remotes 5 Outside Sensor Boxes OSB or 5 Compact sensors 10 In
53. anual for animeo IP Ifyou are commissioning a big facade or floor by floor you can commission smaller parts of them and then later merge the parts to a complete facade though keep in mind Security Zone restrictions Facade 1 Picture 5 Example of a facade in Facade Based approach Group Based how to plan There are some general recommendations that should be considered before you divide the building into different groups zones A group should only have one cardinal direction Facade direction for easy sensor allocation The groups should be thought as a container with one set of Shared behavior or settings For each floor or area of the same functionality and behavior should be group SecurityZone Active Function Position Has functions O Picture 6 Example of a group in a Group Based approach Itis not recommended to make one Group Comfort Zone per room since it will create a lot of Comfort Zones with the same functionality a more complex performance demanding configuration without any benefits Instead this room configuration is made with Local Zones together with the Remotes Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 14 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP How to physically connect the Building Controller to your PC To config
54. asically the same as in the Virgin wizard Please read that section if there is anything you are not sure about Note You don t have to make a new discovery every time you extend the project select the Skip discovery checkbox in the Discovery view You only need to make a new discovery when units previously not connect or powered are added to the system A Note Sensors or Sensor boxes which are used in the Configuration are not possible to disable Y in the Extend Project Wizard Managing remotes and switches The animeo IP system is not dependent on remotes and the remote configuration may change over time That is why the Visual Configuration software has independent handling for remotes to provide an easy way to make changes to remotes during the system s lifetime Local Zones Remotes and switches create and control Local Zones LZ As soon as you bind a motor to a remote or switch a Local Zone is created You can think of the Local Zone as virtual zones for local Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 44 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP commands since they live outside or over the Security and Comfort Zones You can bind any motor to any remote independent of what Security Zone or Comfort Zone that particular motor resides in But the most common pra
55. ate another Security Zone make sure that the select mode is Motor mode options are found above the facade in blue green and red toolboxes Then click on each cell or motor that should belong to a certain Security Zone Once clicked the motor in each cell will be more visible and a green check box become visible to confirm that it has been checked for manipulation Once all motors in question have been checked then click on the Add button in the red Security Zone toolbox located above the facade to the right You will be asked to name the new Security Zone so give it a good name and click Ok Afterwards another questions pops up Since a Security Zone cannot be without a Comfort Zone a Comfort Zone will be automatically created Name the new Comfort Zone also with a good name and click on the Ok button Now you will have a new Security Zone inside the facade section Redo these steps until you have as many Security Zones as you need 2 Create Comfort Zones Comfort functions are placed inside a Comfort Zone so you need one or more of these Once all Security Zones are defined you go through each of them to see how the Comfort Zones should be defined The manner is the same as with defining Security Zones except this time you click on the Add button in the green Comfort Zone toolbox found above the facade at the top So click on each motor or cell that should have its own comfort function and when ready click on th
56. ation Click on the Select button to the right to open the sensor allocation dialog Allocate the wind sensors by double clicking or by drag and drop to the list to the right 2 Temperature threshold The temperature below which the frost function turns on On delay The time it must be frosty before the function turns on 4 Off delay The time after the frost disappears that the function turns off ad Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 71 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Security Timer This timer is used to send the solar shadings to secure position 0 during certain periods during the day You can have several different timers provided they don t conflict with each other if they do they will be shown red You can have up to 8 security timer functions in each Security Zone and in each of these you can have 24 timers Settings 1 Enabled Per default the function is enabled but you can disable the function if necessary 2 Add timer Click on the Add timer button to add a timer 3 Set time Drag the triangles with you mouse to change the start and stop time for each timer or enter the time manually in the textboxes to the right You can have a timer that is active from one day to the next 4 Delete Click on the red squares with the white
57. ays of choosing the firmware for upgrade and install e The system checks automatically while the Firmware Upgrade window is visible if there is any newer firmware In order for this feature to work the computer needs to be online e If you have the firmware in question stored locally you can click on the Select button to locate and load this file You will see immediately if the firmware version you chose is newer or older compared to the one existing in the system Click on the Start Upgrade button to initiate this process Wait and do nothing until the progress bar has disappeared If the system has Sub Controllers close the window and exit Commissioning mode and check the anomalies list to the left to see how the Sub Controller progress and when they are restarting When all Sub controllers are back online the system has been upgraded During Firmware Upgrade the system will be inactive in Maintenance Mode for a minute or two If asked choose Yes to leave Maintenance Mode ATTENTION Do NOT turn off power on any device during the upgrade process First the firmware will be sent to the BuCo Then it will be installed and the BuCo will restart After that the BuCo will check if the Sub Controllers needs to be upgraded and sends over the firmware The Sub Controllers will install the firmware and restart This procedure will take a while If power is cut during the upgrade the hardware could get in an invalid state and never work again Re
58. by Somfy SAS without prior notice Somfy Manual for animeo IP The Software its Documentation and its Content are protected by copyright and other intellectual property laws and by international treaties The Software is registered with the French Agency for the Protection of Programs APP located at 249 rue de Crim e 75019 Paris France under the Inter Deposit Digital Number IDDN FR 001 460028 000 S A 2011 000 31500 Somfy retains all ownership and or intellectual property rights and software licenses related to the Software its Documentation and its Content You acknowledge such ownerships intellectual property rights and software licenses and shall not take any action to jeopardize limit or interfere in any manner with such ownerships rights or licenses with respect to the Software its Documentation and its Content This license agreement do not grant or transfer You any title or ownership in the Software its Documentation and its Content Somfy can make amendments to the Documentation without prior notice 5 Entry into force Duration and Termination 5 1 Entry into force and Duration This license agreement is effective from the first date on which You install or purchase the Software until its termination This license agreement shall remain in force until You stop to use the Software or in case of termination according to article 5 2 5 2 Termination Any Party may terminate this license agreement with a written prior
59. ceccceseccceeeeeseccseseeeeceseeeeeceeseauaeeess Navigate folders emir E E EE Left part 2 the info and toolbox sidebar ccccooocccnnncononccnnnnnnnanocnnnnonanoconnnnonocnnnonnnnonnnnnonanioness Right part 3 The quick access tacna idas Bottom part 4 The Configuration Mode button ccccconccccnccnnnccnnnnnnnnnacononononaconnnononcnnnnnnanononnss Middle part 5 System content and Status iMfO cccccooocccnnconnnannnnnnnnnnaconnnonanaconnnonaronononanarononos THE Wel OMe CEM Cl a E Start Commissioning Make New Configuration cccccccsssecccesssececeeeceeeeesccessuseeeceecesseeceeseeseeeeas Commissioning enter connection details oooocccnconocnnnncnnnnnnnnnnonnnonaconnnnanononononnnonaronnonanonnnss Commissioning Project settings snm rta Commissioning End limits ON MOTOFS ccccccncccnonnccnncnnncnnnnnncnnnnonanonnnnnncnnnnnncnnnnoncrnonononnnonaronnonaninons COMMISSIONING Motors are powered cscseresessrcsescecsvssncusrsencustecacscsvacssncusrcenerencustencestenacssscasers Commissionine IL 2 MOTOTS moniraricniadion orienta Maxime eE callen ai iba rico SVE EE AAPP e PIE o o en eee ee COMmIissionine DISCOVE Pacino aro ed ONES SIO WMS TOS ritos Commissioning choose type of CONFIQUATION ccccccssseccccsseccceeesececseueceeceeseeceeseceteueceesenseeetas COMMISSIONING Group Based cscccccsseccsecccseccesceceeceeseneecaenceceuececee
60. cesseeeeneeeeeucesseacesseceetenees Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice 13 17 Somfy Manual for animeo IP COMMISSIONING Facade Based dias 25 Facade OPIO Scars 25 Facade cre OM di iaa 26 Facade den dias 26 Facade observation point of VIEW cccccsseccccessccccesececeeeccceceuscceceusecessunecesseuecessusecesseneceeseneeeeeeas 27 Motor location motor identification via Somfy s Visual Click finder cooooonccnconocnnnnnrnnnnnos 28 Facade motor identification Turn direction CHECK cooonnnccnnnnnnnnnnonnnnnnnnnnnnononnnnanonnnnnnnnnnnnnss 29 Facade motor identification Turn direction COLE CtiON ccccccssssssssseeecccecseaeesseeceecsauaeeeeeeeees 29 Facade s motor identification NAMING and Type occcccncccnncnnccnnnnnoncnnonnncnnnnnaronnonanononononononanonnonos 30 Commissioning Create more facades s sccssssesessoseveconssscuccssssestousvecuoussseneusscsscuessctenssseneousvesses 31 COMMISSIONING SENSO cistitis ios 31 Select Sensor DOKE a dica na adan 31 A A aualea E 32 Commissioning Switches and REMOtES ccssssessossvecsonssscnssssssesconssscuenssseneousestoussscuenssseneoussenses 32 DISCOVER REMOLES SWitchest ir ais 33 Discover Remotes Add MOS es spmaiecaerahedcaanunnee NA
61. controller is unreachable then find a backup of the configuration Note If you don t find a backup then try to use the Restore Configuration option Replace the BuCo hardware and plug it to the system and plug in the power cable to start it Connect to the BuCo via the animeo IP Visual Configuration software Enter the Configuration Mode Go to the File menu and choose Load Configuration find the backup configuration file Still in Configuration Mode click on the Upload button to activate the opened configuration Done Restore Configuration The animeo IP Visual Configuration auto saves the Configuration at certain points depending of what is done with the Configuration On top of this made changes that are not uploaded are saved every Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 92 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP 10 minutes You can use these Restore Configuration files as an undo functionality of something goes wrong Listed below are the different Restore Configuration files that you can use AutoSave The actual Configuration in the software saved every 10 minutes Use this file as an undo option UploadBackup A backup of the Configuration that is uploaded If something happens during upload use this file to restore Commissioning A backup of the latest
62. ctice is to create a Local Zone that is a copy of the Comfort Zone since you can drag and drop a Comfort Zone onto a remote to create this copy Local Commands and Priority When it comes to priority of functions a Local command comes between the Security functions and Comfort functions That means that Local commands see it as a local function will override for example sun but will not override wind To add remove or replace a Remote Switch To make changes to the configuration or system you need to be in Configuration Mode When you are in that mode the left sidebar will show the configuration toolboxes One of these boxes is the Remotes toolbox Picture 53 The Remotes Toolbox In this box you can see a list of all the existing remotes in the system At the top of the toolbox you have two option tabs one for physical remotes and one for Web remotes Below the tab is a toolbar with a row of buttons from left to right add replace and remove remote Simply click on a button when you want to do any of these things Add Remote Click on the plus button in the toolbar and the Remote wizard will pop up It is basically the same dialog as in the Virgin wizard Simply click on the remote or switch you want to add and it will be detected and shown in the list Select the remote and continue the wizard Add good names and info Continue the wizard when ready Replace Remote Select a remote that you want to replace if it got broken or so
63. dings are in 0 position and continue the wizard Click on the No button if you discover one or more solar shadings that are not in the 0 upper position and the wizard will help you to correct the error r Motor positioning made on facade Facade 1 Are all solar shadings on the facade in the upper 0 position Mo Previous Cancel Picture 25 Make New Configuration Find turn direction question Facade motor identification Turn direction correction Once again you will see the facade matrix But this time you select by clicking in the corresponding cells where solar shadings are down when they should be up Once you have selected all cells in question then click on the Change turn direction button and voila we have corrected the turn direction and the solar shadings will go to the 0 upper position Motor positioning made on facade Facade 1 Now we need to check if the turn direction of all motors on the facade is set correctly To do this you have to select all the motors that are NOT in the 0 position Change turn direction Previous Picture 26 Make New Configuration Change turn direction Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 29 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Now you should con
64. e Add button in the green Comfort toolbox You will see that the cells you have selected now have their own Comfort Zone Redo these steps until you have as many Comfort Zones as you need Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 37 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Picture 39 Facade for configuration with Comfort Zones Do steps 1 2 for each facade or facade sections that you have made For more information about how to edit zones go to the section Mastering the Zone options Configuration Part 2 Generic Settings Inanimeo IP a new settings concept has introduced Generic Settings These settings are centrally managed but can be used in any function in the system Currently there are two types of Generic Settings Solar Shading Positions and Time Periods The idea is to set one or some positions or Time Periods that the whole system uses Individual functions can subscribe to this generic setting Then when you need to change the position you do it once instead of going to every function affected Generic Solar Shading Positions In this window you manage all the generic positions that you want to use in the system both static positions and dynamic sun tracking positions You can also set for which facade this generic position is valid as an option Soi
65. e 58 A close up of the in zoomed Facade s toolbars Motor toolbar When one or several motors are selected the Motor toolbar buttons will be enabled or disabled The button behaviors are explained below Unassign If there is a motor or several that is in the wrong place in the fa ade then use this button to Unassign the motor from the fa ade The motors will enter to the Motors list toolbox as Unassigned motors Rename When one motor is selected you can change the motor name Replace When one motor is selected you can replace that motor with a new one The Replace button activates the Motor Replace wizard Replace is used when a motor has failures broken and needs to be replaced Swap If only two motors are selected they can be swapped The scenario could be that the two motors have been configured in the wrong place some mix up between two rooms for example Then use this Swap feature to make the motors take each other s place Comfort Zone toolbar When one or several motors are selected the Comfort Zone toolbar buttons will be enabled or disabled The button behaviors are explained below Add When one or several motors are selected you can add a Comfort Zone When the Add button is pressed then a new Comfort Zone will be created for the selected motors Rename When one or several motors in a Comfort Zone are selected the name of the Comfort Zone can be changed Delete If one or several motors are s
66. e animeo IP io Visual Configuration software Top part 1 the Menu and Navigation Bar In the menu and navigation bar you will find links to navigate through all views that exists in the system In the upper left corner you have the usual menu where you can access different features of the system Below in this menu you will get the title of the system you are connected to In the middle of the bar navigation folders will appear depending on the configuration you make Via these folders you will control what will be shown in the middle part of the main view Further to the right you will have two status lamps online and Fire Alarm that will light up when active In the upper right corner you have the usual Minimize Restore and Close buttons Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 16 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Navigate folders In the middle of the top bar three or more tabs will appear depending on the type of the current Via these tabs you can switch between different visualization of the system and its status For example you can switch between facades groups lists and Floor plans You simply click on them to switch tab and view Left part 2 the info and toolbox sidebar This sidebar has two facets one showing information when you are monitoring the sys
67. ease feel free to browse through the options below Make New Configuration Starting from scratch you have no idea where the motors are or how many facades you have click on the button below to start a wizard that will guide you Make New Configuration Load Configuration If you want to look at a project that you already have made or that you have received then click the button below to load that project Load Configuration Extend Configuration Did you forget something to be included in the configuration or have the users needs changed Has the project been expanded f so then click on the button below to start a wizard that will help you Extend Configuration Configuration Remotes Sensors IM Show this window on startup Picture 8 The Welcome Center view The blue rectangle at the top will suggest the next action that you might do with a shortcut to that action Use this Welcome Center whenever you want to change or add things to the configuration in the animeo IP system To start the commissioning of a new project just press the Make Project button or if you first want to check if you can connect to the animeo IP system press the Go to connect view button in the blue rectangle The Welcome Center will discover if the connected Building Controller is Virgin or not and then suggest what to do next Note A BuCo in Virgin state means that it has no configuration uploaded
68. eat importance that you have confirmed with the solar shading installers that the end limits of the motors to the solar shadings have been set Otherwise the solar shading can get damaged If you have received a confirmation that end limits have been set on all solar shadings you can tick the checkbox and continue the wizard which as you now means clicking the Next button A kali poz J i gt gt gt m Motor end limits secures that solar shadings do not get damaged Are you sure that end limits has been set on all motors i What does it mean in practise Usually when the solar shadings were installed on the facade the motor s end limits were also set End limits are defining the maximum position on how low or high the solar shading are allowed to go If the end limits are not set then the solar shading can be damaged ouch So be really sure and found out that the end limits has been set mee Picture 11 Make New Configuration End limits question Commissioning motors are powered The animeo IP system can discover motors but the motors need to be powered in order to be discoverable Make sure that all motors you want to discover are powered Tick the checkbox and continue the wizard Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 20 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS
69. ect the new Sub Controller Use the ID that you noted in step 1 Click Next to continue 9 Now click on the Upload button to active the replacement Sub Controller object mismatch If it happens that the new Sub controller will not control the same motors or sensors a special view in the Replace Sub Controller wizard will appear It will ask you for permission to remove those objects If this is not the case then check why not all motors or sensors were discovered maybe the bus plug is not properly connected If on the other hand this is a fact that the new Sub Controller will not control the same objects as the old one then tick the checkboxes and click the Next button Replace System Hardware Wizar ml gt Oops The Sub controller that you want to change differs from the old 060601 060601 Sun test 00 05 51 03 A9 23 100C 0 060602 060602 060603 060603 060605 060605 D605D7 0605D7 D604F7 0604F7 O605FF O605FF _ Remove these motors from the configuration Remove these sensors and all associated functions from configuration What do you mean with differs When replacing a Sub controller the new one must be able to communicate to exactely the same motors as the old one did Please check why the Sub controller cannot reach the motors above Note Sensors cannot be moved at all see the manual for more instructions Previous Cancel Picture 110 Replace Sub Controller wizard Replace a Sub Controller with a BuCo There
70. elected in a Comfort Zones that Comfort Zone can be deleted The motors in that Comfort Zones will be inherited by another Comfort Zone If several Comfort Zones exists then you have to select which one that will inherit the motors There must always be one Comfort Zone left in each Security Zone which is checked by the system Redefine If there is a need to expand a Comfort Zone merging motor s from another Comfort Zone select the Comfort Zone in questions or the motor s to be included and click the Redefine Button A dialog Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 50 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP will appear asking which Comfort Zone that should be the target zone Select the Comfort Zone that will take over inherits the motors and click on Select button to continue Security Zone toolbar When one or several motors are selected the Security Zone toolbar buttons will be enabled or disabled The button behaviors are explained below Add When one or several motors are selected you can add a Security Zone When the Add button is pressed then a new Security Zone will be created for the selected motors Rename When one or several motors in a Security Zone are selected the name of the Security Zone can be changed Redefine If there is a need to
71. elected will wink Ne move shortly down and up once Motors in the system Tommy 060 8 x Fl Name my The floor Facade GoSoft Direction Application Type InteriorBlind Y Position 44 Picture 81 The Motor Settings window Function Settings There are two different types of functions Comfort and Security functions Comfort functions have lower priority than Security functions Note For all timers used in this system the minute when the timer ends is included e g Ss setting a timer to end 10 30 it actually ends 10 30 59 Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 64 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Security Functions in priority order Fire Alarm If the Major Alarm input on the Building Controller is activated the solar shadings are locked to the 0 security position The Major Alarm input and hence functionality is often connected to the building s fire alarm system This function is always available Major Error If the Major error function is activated the solar shadings are locked to the 0 security position The Major error function gets active if any vital part of the system stops to work for example a broken sensor that is connected to a security functions This function is always available Major error can be caused by t
72. ertain direction Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 67 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP In practice this means that the usual wind speed threshold will be valid outside the protected angle The usual wind speed threshold can be set about 25 higher than the wind speed threshold for the protected angle Your sun protection will be used much more and still be protected from wind damage The wind direction function only reads from one wind direction sensor so at least one sensor must be allocated to have access to the wind direction function A wind Direction sensor should always be installed on the roof on the building where it can read wind from any direction The protected angle wind speed threshold cannot be set higher than the usual wind speed threshold same Security Zone They are mutually exclusive For interior Solar Shadings this function is ly Note that you cannot use both the Wind function and the Wind direction sensor in the not needed e Wind Direction Wind speed sensor used Wind speed 1 Sencorbox 1 Wind speed 2 Sensorbox 1 Wind direction sensor used Wind cirecton A i Speed threshold E m s On delay EM Off delay m Protected angle Wind direction No Tolerance J as i Protected speed threshold s m s
73. erved IDDN FR 001 460028 000 S A 2011 000 31500 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP We advise you to carefully study this manual to get the maximum out of the system This manual does not only contain information needed to install and run the program it also explains all functions and possibilities in detail animeo IP Visual Configuration software The software is the link between the system and the user From the software you make all settings of parameters e g wind and sun threshold and delays configuration of switches manual and locking commands The software also visualizes the status of all functions sensors and position of the solar shadings There is also a built in log that tracks all sensor values actions errors and changes of any parameter The software is developed for international usage so any unit e g wind m s km h kn and mph can be chosen and changed in runtime To make the usage of the software as user friendly as possible e g all sensors and zones can be given a specific name an alias The system will work even if the PC is not connected but you can of course not make any D settings or give any commands PC Requirements for the Visual Configuration Software Minimum Intel Pentium Dual Core 4 GB internal memory 1 GB free hard drive space True color graphic card 17 Widescreen moni
74. firm the turn directions again just as a precaution se y itioning made on facade Facade 1 Are all solar shadings on the facade in the upper 0 position Turndirections for this facade has been set Press next to continue Picture 28 Make New Configuration Turn direction set confirmation Continue the wizard after the turn direction has been set Facade s motor identification Naming and Type It is of major importance that you give each motor a good name This will help you later on when you are managing them for some reason A good name could be Motor 2 room 211 or M2 R211 F2 EF which could stand for Motor2 Room 211 Floor2 East Facade It is up to you to come up with the best way to name the motors Click on each cell in the facade matrix and enter the name Continue with the wizard when you have finished Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 30 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Motor type Screen v End product location Interior Cancel Picture 29 Make New Configuration Naming motors You can also set the type of solar shading application each motor drive which also is good to know when for example setting wind values for the wind function At the bottom right you can set solar s
75. for when the solar shadings are allowed to move Somfy s digital motors move so slow that it will never be noticed But the mechanical solution on a solar shading maybe require bigger movements to actual move then adjust this parameter to accomplish a real movement Minimum angle movement If you don t want the solar shadings to angle too much then use this setting to make a condition for when the solar shadings are allowed to angle Somfy s digital motors move so slow that it will never be noticed But the mechanical solution on a solar shading maybe require bigger movements to actual move then adjust this parameter to accomplish a real movement Position for unsupported products If there are solar shading types that does not support sun tracking inside the same Comfort Zone then set which position they should take when sun tracking is active Solar shading types that does not support sun tracking could be vertical venetian blinds or folding arm awnings Angle for unsupported products If there are solar shading types that does not support sun tracking inside the same Comfort Zone then set which angle they should take when sun tracking is active Solar shading types that does not support sun tracking could be vertical venetian blinds or louvers Default window height In order for the sun tracking to work properly the window height must be defined Enter the height of the window Default sun enter depth Specify how far the sun may enter in
76. gy optimal strategy decrease the Remote off Delay and increase the Disable and Reset Local Control time and vice versa to have a more occupant optimal strategy There is a fine balance between saving energy and to keep the occupants satisfied to not annoy them The risk of having a too aggressive user restriction could end in that the occupants demand to disable the sun function Case 3 Reuse function settings made The typical commissioning scenario is that most of whished functionality is the same throughout the building Once the different zones have been defined drag a function from the function library to a zone Do the settings required Now you can from the functions tree toolbox in the left right corner visible when in Configuration mode find the function and drag it to a another zone By doing this you will copy the settings made All you have to do is to secure that the correct sensor is allocated or do small changes Case 4 How do I undo something in the Configuration There is no ordinary undo functionality in animeo IP Visual Configuration software The undo that can be made is the differences between the Configuration on the BuCo and the Configuration on the PC Once you discover that you want to undo then go to the file menu and select Revert from Building Controller The Configuration will go back to the latest uploaded one Be aware that if you have done many changes since the last upload all of them will be lost Case 5 How
77. hading type and location for all the motors in the matrix if they are all the same The motor type will automatically be mixed if more than one solar shading type is selected in the cells Commissioning Create more facades Once all motors have been assigned to a certain facade you can create and define more facades When you have finished creating facades or the system notices that no motors are left to assign then you have two possibilities 1 Edita made facade change a name or the way it looks or reassign the motors that belong to that facade 2 Continue with the wizard selecting and assigning sensors remotes or switches Commissioning Sensors When you choose to continue with the wizard when all facades are done you will get to the Sensor step Continue the wizard to configure sensors or skip this step to continue further to remotes and switches You can always add sensors afterwards via the Extend wizard Select Sensor boxes When you choose to configure sensors you will get a list of Sensor boxes that the animeo IP system has discovered Select and name the Sensor boxes that you want to use Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 31 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Outside Sensorbox Sensorbox 1 Inside Sensorbox Sensorbox 2 00 26 18 5C F8 6D 52
78. hat section in the beginning of this manual you know now why you need to create Groups which will contain one Security Zone and one or many Comfort Zones plus motors Right click on the desktop of the main view or click on the New Group button to create a new group Give it a good name and click on the button ok and you will get a Group with a Security Zone in it red border Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 34 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP New Group Picture 35 Group Based view create New Group button Note When Facade Based commissioning is chosen you cannot make system Y changes via the Group View The buttons will not be visible in this case 2 Create Comfort Zones Motors and comfort functions are placed inside a Comfort Zone therefore you need one or more of these Select a Group by clicking on it and click on the Comfort Zone button or right click on the Group in question and select the menu choice Add Comfort Zone Give it a good name and click on the button ok and you will get a Comfort Zone in the Group green border SsecurityZone_3 Acta Funcion Postio Has functions Picture 36 The Add Comfort Zone menu option through right click 3 Assign Motors Now you can populate or
79. he following Sub Controller failure BuCo failure Network failure jo card failure Outside temperature sensor short circuit Out temp out of range Wind sensor 24hour time out Wind sensor short circuit Wind direction sensor short circuit Wind direction sensor out of range Rain sensor short circuit PC Building Lock This function gets active when the PC building Lock button is activated in the animeo IP Visual Configuration software the solar shadings are locked to the 0 security position This function is always available Use this function when a need to lock the whole building is necessary due to safety reasons Key Building Lock This function gets active when the Key building Lock input on the BuCo gets activated the solar shadings are locked to the 0 security position This function is always available Use this function when a need to lock the whole building is necessary due to safety reasons PC Security Zone Lock This function gets active when the PC Zone Lock choice is activated in the animeo IP Visual Configuration software the solar shadings are locked to the 0 security position This function is always available Use this function when a need to lock a Zone is necessary due to safety reasons Key Security Zone Lock This function gets active when the Key building Lock input on an Inside Sensor box gets activated the solar shadings are locked to the 0 security position This func
80. ick on the OK button Energy Service Package In the first version of animeo IP the Energy Service Package is included This package contains the functions Preserve and Get Heat Web Remotes Service Package When this service has been activated the Web Remotes functionality is unlocked and visible in the animeo IP Visual Configuration software Enter Configuration mode and look at the Remote toolbar to the left As you can see now there is a folder called WEB Click on that tab and you will get the same options as you have for physical remotes Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 81 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Create a Web remote Click on the plus icon to add a Web remote and then double click on the Web remote created in the list below to open the Remote Settings window Web Remotes gt tee ES Drag and drop items here WEB remote type Up stop and down Default gt Local command off delay Picture 98 Remote Settings Remotes toolbox with the Remote Settings window In this window you can see which motors are linked to the remote It is the same window as for physical remotes The main difference between physical and Web remotes virtual is that a WEB user owner needs to be set for each Web remote Create Web user
81. icking on it in the list Continue the wizard to add information about the selected remote in the list Give it a good name and fill in thoroughly all other information boxes This information will help you later a lot when you administrate the switches p 7 ES animeo IP Visual Configuration Make New Configuration Wizard commissioning has never been so easy o e 2 7 Please fill in the boxes below with descriptive information for this switch or remote This information will e help you later when you link motors to this remote Remote or switches For this system there is no difference between remotes or switches They are all treated the same You can always via the Remote toolbox ala manage your remotes and switches Picture 33 Make New Configuration Adding Remote information Continue with the wizard when you are ready Discover Remotes add more When you have added one remote to the system you can choose to add more remotes or continue the wizard to its final step Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 33 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Commissioning Finishing the Wizard upload Configuration to the BuCo You have reached the final step in the wizard All you have to do now is to simply click on the Upload
82. ing name Example Remotes Oftdelay 14200 Picture 63 General Settings window General E mails If service or errors appear in the animeo IP system these can be sent to notify personnel so appropriate actions can be taken The SMTP fields needed to be filled are the usual information that you can get from the IT department in the building or from the Building s Internet Service Provider ISP Enter the email addresses where the error and service reminders will be sent Enter the From address use one defined from the IT department or your own Enter the SMTP server connection which the emails will be sent from Also enter specific ports and authentication information if needed Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 55 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Unit settings Location Time General E mail Error email address Serice email address From address SMTP server Port M Authentication required Use _ e Picture 64 General Settings window Mail Network General network settings The BuCo can be set up to use a static IP address Fill in the network settings information provided by the IT department at site Proxy credentials The BuCo can be connected to a Proxy server that requires log in credentials
83. itions are when the outdoor temperature is lower than the threshold and the sun intensity is lower than the sun threshold the solar shadings can be programmed to take an appropriate position Normally this function is used outside occupancy hours You can have up to 8 of this function in a Comfort Zone Preserve Heat 2 Function enabled Temperature sensor used Temperature 1 Sensorbox 1 Sun sensor used Sun 2 Sensorbox 1 Temperature threshold 5 E Sun threshold 10 kdux On delay En Off delay EN Position Specific position Generic position io MON Angle lo i Time penod atan ci ie Everyday x Wholeday Specific time Start time 00 Picture 92 Function Settings Preserve Heat Settings 1 Enabled Per default the function is enabled but you can disable the function if necessary 2 Temperature sensor allocation Click on the Select button to the right to open the Sensor allocation dialog Allocate the temperature sensors by double clicking or by drag and drop to the list on the right 3 Sun sensor allocation Click on the Select button to the right to open the sensor allocation dialog Allocate the sun sensors by double clicking or by drag and drop to the list on the right 4 Temperature threshold The function goes active if the outside temperature drops below this Sun threshold The sun intensity must be less that this for the function to go active On delay De
84. ive without a Security Zone You can have several Comfort Zones in a Security Zone tis in the Comfort Zones the motors are placed Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 11 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Picture 3 Comfort Zones green inside Security Zones example on a building So when a Security Function goes active in a Security Zone that function overrides all active comfort functions in all Comfort Zones that exist in the Security Zone in question Local Zones LZ are used for manual control for remotes or switches in the building where the occupants can control the solar shadings as they wish Local Zones are o Independent and are not restricted within a Security Zone or Comfort Zone o Local Zones or local control will override active Comfort Functions for a certain time o Security Functions are not affected by local control and will always secure the building when necessary independently of whether Local Zones or Comfort Functions are active or not Picture 4 Local Zones yellow example on a building Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 12 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual f
85. l get to the Switch and Remote step Continue the wizard to configure them or skip this step to continue further to finish the wizard You can always add switches and remotes afterwards via the Add Remotes wizard Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 32 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Discover Remotes Switches Radio based one way remotes always need to be pressed in order to be discovered All you have to do is to press the Remote s button and it will pop up in the list As long as this wizard view is open the animeo IP system will discover new remotes or switches that you press The most recently discovered or pressed switch or remote will be placed at the top of the list r T E animeo IP Visual Configuration Make New Configuration Wizard commissioning has never been so easy lo e Y or remote you pressed on will jump to the top of the list Select the remote you want to configure and click on next button Listening Remote or switches For this system there is no difference between remotes or switches They are all treated the same You can always via the Remote toolbox manage your remotes and switches ma Picture 32 Make New Configuration Remote discovering Choose a remote you want to add to the configuration by cl
86. lace a Sub Controller with the BuCo see the Replace Sub Controller with Ss a BuCo section To replace the Sub controller follow the steps below 1 First locate the old Sub Controller and physically replace it with a new one Please keep track of boxes IDs or MAC address to easier identify them later on 2 Connect the Ethernet cable the motor bus and lastly the power cable Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 90 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP 3 Wait and see so that the Sub Controller starts and gets a heartbeat two green flashes every second 4 Go back to the PC and the animeo IP Visual configuration software and start the Replace Sub Controller Wizard You need to be in Configuration mode then go the top menu Tools gt Advanced gt Replace System Component gt Replace a Sub Controller 5 The wizard opens Now the system needs to discover the new Sub Controller Click on the Discover system button to start this procedure You may have to wait for a Sub Controller to connect yes it is the one you are replacing but the system does not know that yet 6 When the Discovery is finished click next to continue 7 Select the Sub Controller that you want to replace Use the ID that you noted in step 1 Click on the Next button to continue 8 Sel
87. lan While in Binding mode IB you can drag a remote to a motor or vice versa to create new links This action will trigger the Remote Settings window to appear You can use this window in the same manner as explained before in chapter Managing remotes Control motors from the Floor plan There are two ways to control selected items on the Floor plan Either you select one or many motors while pressing the Ctrl key and then right click with the mouse above one of them In the menu that appears you can select which action want to send Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 86 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Picture 106 Floor plans Context menu of an item when in Operation Mode Or after the selection having the PC Manual Command tool open and then control the motors by clicking on the buttons there Remember by controlling as above you will make PC Manual Commands which has higher priority than Local commands Remotes can also be handled as described above except that when you send action you will create a Local Command as if the remote itself was used While the motor moves an arrow will blink the direction and the actual motor position will be shown Navigating between floors plans When several Floor plans have been added the list box will contain them all C
88. lay before function turns on Off delay Delay before function goes off Position when active Normally 100 You can set any position You can also use the Generic Position feature 9 Active period Additionally you can set which days and time span this function should be active oS a i Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 76 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Sun The sun function is used to send the solar shadings to a specific position when there is sun When the sun intensity exceeds the On threshold the Solar Shadings will go down and when the sun intensity is lower than the Off threshold the solar shadings will be sent to 0 position The position the solar shadings will take when sun function is active is either a fixed predetermined position or a calculated position due to sun angle You can have up to 8 of this function in a Comfort Zone Function enabled Sun sensor used WEST Compact sensorbo Select On threshold 20 kw Off threshold 15 kim Regular position Specific position Generic position Positfion 100 Angle as Cc Sun tracking position Time period laos ate EVER cay x Whole day Specific time Twilight Start time 12 00 Av Dawn Dusk Stoo ti 0 505 Start before lo Minutes 2
89. lick on the list box and choose the Floor plan that you want to see by clicking with you left mouse button aT E AE MPAA Picture 107 Floor plan Navigating between floors Edit the Floor plan drawing While in Configuration mode to change the Floor plan drawing click on the edit button to the right of the Floor plan list box 2 The Floor plan drawing import dialog appears and you can change the drawing itself if you have an update or imported the wrong one You can change the floor it is supposed to be associated with Or you can change the Scale factor and color settings You can change all settings or just one and still keep the dragged item that resides on the current Floor plan drawing Click on the OK button to activate the changes or click on the close button to undo your changes Delete a Floor plan Deleting a Floor plan will erase the drawing from the configuration and all the items placed on the drawings Other settings made in that view will still be in the configuration such as motor and remotes and the bindings made with them Click on the Delete Floor plan button L and answer the message box that appears to force the delete action Tips amp Tricks Some of the functionality inside animeo IP Visual Configuration software is made to Ss overcome commonly encountered problems These problems are presented below as cases Case1 Customer asks for different sun function behaviors during the day There are ca
90. llow traffic going on that specific port You need to find out which port and which IP address the IT administrators will use e Using Somfy animeo IP Roam Anywhere is an easy way to access the BuCo from distance so that you don t have to be physically connected to the BuCo Ask the Support Team for more info Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 15 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Starting the animeo IP Visual Configuration software The Visual Configuration software for animeo IP is a software tool via which all the commissioning is done This graphical tool will guide you through the basic parts of the commissioning and will provide easy tools to bring up to the system The animeo IP Visual Configuration software is best used with big and multiple screens Some E of the views can be open simultaneously to get a better overview of the system The Main Window This wndow embodies all functionalities and features that you can manage in the animeo IP system The main window has five sections that will be described in detail below ings Tools Views Help Debug nm ey m x animeo IP Visual Configuration Test O System Info Comfort function Local Command PC Command Security function Icon legend Picture 7 The Main View of th
91. lowed to make any changes to a remote EJ Remotes Switches Remote name Facade 1 Up stop down Default x Local command off delay z A JECONOS Picture 54 The Remotes View where the Local Zones are created The view contains one big list of the motors to be controlled When the selected remote is new there will be no motors in the list instead blue arrows guide you to drag in motors or any zone to make the remote alive To the right of the view you can see all information about the remote that is selected In the drop down list box in the upper right corner you can see all the remotes in the system and choose one for inspection To add or remove Motors linked to a Remote You have to link motors to the remote and that can be done in several ways with drag and drop You can drag one or more motors from the motors list and drop them on the remote You can drag a remote and drop it on a motor in the motors list You can drag a whole facade from the facades view and drop it on a remote Then all motors in that facade will be controlled by that remote You can drag a remote and drop it on a facade Then all motors in that facade will be controlled by that remote You can drag and drop a Security Zone or Comfort Zone to a remote or vice versa from the Facade or Group tree list You can drag and drop a Security Zone or Comfort Zone to a remote or vice versa from the Facade zoom view or the Group view C
92. m functionality in particular Settings such as e Unit settings Measuring units shown in the software e Location and Time Set the Project and site location Set time e General Building name Remotes general off delay Change passwords e Network Proxy and emails settings Unit settings Set which units that should be presented The settings made are saved in the Visual Configuration Software and not in the Configuration Temperature Celsius C Fahrenheit F Lux flux Kilolux klux Centimeter cm Inches in J Picture 61 General Settings window Unit settings Location and Time These settings are important to be set correctly since many functions depend on them Location Select Country and then Region if available and lastly Location as close as possible to where the system is situated Longitude and latitude can be changed if better coordinates is at hand Suggested Time zone can also be changed Time There are two ways of setting system time Either you enter manually in the calendar presented and in the clock field and click on the Set button to active the new time Or use the time from the PC on which you are using animeo IP Visual Configuration software Click on the Set from PC button to activate the PC s time and clock settings Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 53 Somfy SAS capital 20 000 000 E
93. mand Local Command Get Heat Preserve Heat Sun C Custom default 7L Local cmd disabled 2 Picture 80 The Function Icons in animeo IP Motor Settings Here you get all information there is about a particular motor In the list at the top you can select the motor you want information from You can also when in Configuration Mode change the data for a motor Add a Motor Click on the button to add a motor to the system Doing this will start the Extend Wizard Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 63 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Replace a Motor Click on the double arrow button to replace a motor to the system Doing this will start the Replace Wizard gt Y Note that the motor selected in the list at the top will be the replaced one Delete a Motor Click on the button to delete a motor from the system Reverse Turn Direction Sometimes a motor is set so that it goes in the wrong direction For example when Solar Shadings are going down one of the solar shadings is going up In this case the Turn Direction is set wrongly To change the Turn Direction select the motor in question and click on the checkbox Remember to upload afterwards Note If you tick the Wink motor when selected checkbox the motor s
94. mething click on the arrows button in the toolbar and the Replace remote wizard will pop up It is basically the same dialog as in the Virgin wizard Simply press on the new remote or switch you want to put in and it will be detected and shown in the list Select the remote and continue the wizard Add good names and info Continue the wizard when ready When the wizard is finished all the motors from the old remote will have been transferred to the new remote Remove Remote Click on the X button in the toolbar a message box will pop up Answer the message box query by clicking the Yes button and the remote will be removed from the system Remember that all settings for that remote will be lost Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 45 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Note Changes made to the system will not take effect until they are uploaded to the building B controller To view the Remotes in the system From the Views menu option in the top bar or from the Welcome Center in the Remotes tab you can reach the Remote View where you can see all the remotes in the system You can also double click on a remote in the remote toolbox to open a view with the clicked remote selected Notice that it is only when you are in Configuration Mode that you are al
95. mfy SAS without prior notice Somfy Manual for animeo IP per quarter with different sun settings or having one sun function in the morning and another for the rest of the day For the Twilight feature read the section below Position Regular and Sun tracking For the Sun function there are two different positions types that can be chosen Regular position Sends the solar shadings to a certain predefined position and stays there the whole time when the Sun function is active You can set any position You can also use the Generic Position feature Settings 1 Specific or Generic position Choose to use an individual sun tracking settings for the Comfort Zone or subscribe to a Generic position that is globally defined Generic Solar Shading Position 2 Position The position solar shades in the Comfort Zone should take when the Sun function is active 3 Angle For venetian blinds enter the angle that they should take when the Sun function is active Regular position Specific positon Generic position Positon 100 to Angle as gt pS Sun tracking position Picture 94 Function Settings Sun Regular position Sun tracking position Calculates each minute the optimal solar shading position compared to the actual sun angle This way the solar shadings will follow the sun s rise and fall giving the occupants maximum natural light without glare The sun s azimuth is always used Arm 0 Sun tracking
96. n Remember that it is very important that all information about this facade is correct All added information about the facade and its floors will help you a lot in the end when you add functionality to the system Picture 21 Make New Configuration Create a Facade Facade definition It is in this step that you define how the facade matrix is built Enter how many floors the facade has Enter how many windows each floor has It is recommended that you define the facade as it looks even though not all openings or windows have solar shadings such as doors and entries Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 26 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Define how many floors the facade has Then define how many windows each floor has Don t forget to give each floor a descriptive name Number of windows 3 Number of windows 3 Number of windows 3 r St Why do I need to specify floors and windows The wizard will help you to find and position each motor The easiest way to do this is to create a matrix that represents the facade in question The wizard will later on use this matrix for you to easily click the motors in position Also the facade is shown in one of the main views in the software where you can see the status Picture 22 Make New C
97. n periods during the day You can have several different timers provided that they don t conflict with each other if they do they will be shown red You can have up to 8 Local Command Timer functions in each Security Zone and in each of these you can have 24 timers Settings 1 Enabled Per default the function is enabled but you can disable the function if necessary 2 Add timer Click on the Add timer button to add more timers Click on the red squares with the white x to delete a timer 3 Set time Drag the triangles with you mouse to change the start and stop time for each timer or enter the time manually in the textboxes to the right 4 Action Set which position the solar shadings should be in during the timer s active period You can choose from some standard positions You can also define new special positions 5 Delete Click on the red squares with the white x on the right hand side to delete a timer 6 Active period Additionally you can set for all timers added which days they should be active This is done via the list box located bottom left of the timers Comfort Timer 4 El Fundion enabled Timners E E 04 95 06 e J ie et orth fate Goto 100 0 7 07 00 to 18 00 f I f W oc 0 amp H amp 1 Action 18 00 to 0 7 00 Active period y a Pr q 4 7 j 1 Picture 90 Function Settings Comfort Timer Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR
98. n the navigation bar in the top center Picture 100 Floor plan the Tab icon and the Configuration toolbar Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 33 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Add a Floor plan drawing When Configuration mode is active you will see a toolbar with three buttons Add Edit and Delete Click on the add button to add a Floor plan In the dialog that appears you can do the following e Import file Import a Floor plan from a file dxf or dwg files are supported e You can also import pictures in the format jpeg or tif e Scale factor Choose the Scale factor If you enter 2 it will be double the size If you enter 0 5 it will be in half the size e Black and white Select if you want to view the imported Floor plan in black and white e Select an already defined Floor plan name or enter a new name Click OK to start the import process E 2 Add new Floor plan Import file IS ES Scale factor E stack and White Floorplan name cose Ha Picture 101 Floor plan Add floor plan drawing Usually a Floor plan has several information layers Select which layers that is of interest to import Select which layers to import W Y 0 Y KTI CONTROL Y DEFPOINTS Z A DOOR Y A EQPM
99. ntrol you can open the PC Manual Command located in the Quick Access Sleeves in the upper right corner First select and focus on an object a facade zone group motor or remote Then go to the PC Manual Command and to one of the following Switch between automatic auto mode or manual mode When automatic is active the auto button will be light up green inside This means that all functions can be active In manual mode only Security functions and PC Manual commands can be active When in PC Manual mode you can control the solar shadings via the up stop down buttons You can also use the slider located beside to send the solar shadings to a precise position PC Building Lock is reachable via the button in the upper right corner Click on this button to activate PC Building Lock which will lock the building whereupon only the Major Error and Fire functions can be active All other functions will not go active as long as this lock is on Picture 72 The PC Manual Command controls Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 60 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP System and function icons status colors and patterns used In animeo IP Visual Configuration certain predefined status colors are used to easier understand what the system does Read the sections below to
100. of a new project Save Configuration when you want to save a commissioning configuration locally on file Load Configuration when you want to open a saved commissioned configuration Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 93 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Configuration Report View Print when you want to print a report about the configuration Connect to Building Controller when you want to connect to another system Disconnect from Building Controller when you want to leave a system Upload to Building Controller when you want to send Configuration changes made to the Building Controller that you are connected to Revert From Building Controller when you want to undo the latest changes made to go back to the configuration that the Building controller has Restore Configuration when you want to use the inbuilt backup due to some system issues Exit when you want to close the animeo IP Visual configuration software e Edit gt Delete when you want to remove selected objects Properties when you want to see the selected object s properties e Settings gt Generic Solar Shading Positions here you manage the general solar shading positions Generic Time Periods here you manage the general time periods Licenses here
101. omfy SAS without prior notice Somfy Manual for animeo IP r Configure each motor enter information about them Exclude motors that does not belong to the configuration _ Exclude motor from configuration Use sms Seni llas Type Application Floor _ Facade sae Yes 060237 060237 Screen Internal Alias r Yes 060265 060265 Screen Internal Facade Floor Room Type Application E Wink motors when selected What is motor state and why should I enter extra motor information When a motor is discovered it gets in a state called Unassigned The motor is in the configuration but it has no owner Zone group The motor gets Assigned when it is placed in a facade zone group If the discovered motor does not belong to the project configuration it n eds to be Excluded Picture 19 Make New Configuration Motor configuration Previous Next Cancel These properties can of course be changed afterwards in the Motor view Continue the wizard when you are ready jump to Sensor Box Configuration If it turns out that some motor should be excluded from the configuration for example if it should only be under locally wired control then tick the Exclude motor from configuration checkbox to exclude that motor from the configuration Commissioning Facade Based Read through the instructions and make sure that you understand the concept Continue the wizard Facade options
102. on of any applicable laws and regulations 8 Audit Upon 10 days written notice Somfy may audit Your use of the Software You agree to cooperate with Somfy s audit and provide Somfy with reasonable assistance and access information Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 97 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice
103. onfiguration Define a Facade Continue the wizard when you have finished defining the facade Facade observation point of view Since you know that you can do Facade Based commissioning facade by facade floor by floor or even room by room the method that helps you find the motors needs to know if you are standing inside or outside looking at the building Choose the correct point of view position Read through the instructions on how to use the motor finding method at the bottom Continue with the wizard animeo IP Visual Configuration Make New Configuration Wizard commissioning has never been so easy Where are you Standing Are you looking at the facade from the outside or from the inside 0 Looking from ne i JE Do motor assignment for this facade later Choose this option if you only want to define the facade matrix and not assign motors to it for the moment Why is this important When creating Facades you will use Somfy s Visual Click Finder method to locate the motors This method needs to know your point of view so that the window order left to right is correct Cancel Picture 23 Make New Configuration Facade Based Point of view question There is a third option called Do motor assignment for this facade later The purpose of this choice is that you may want to define facades but without identify the motors at this stage If this is the case then choose this option before continuing
104. oning made on facade Facade 1 Previous gt Cancel Picture 24 Make New Configuration Find motor position All in all there should be around seven cycles or more depending on the size of the facade Continue the wizard when you have been confirmed that all motors on the facade have been found If you feel that you missed selecting a cell or that you are making too many cycles then you can restart the process by clicking on the round arrow button on the upper left side of the wizard You can also print a version of the facade with the numbers written so that someone can help you if you cannot see the solar shadings move or if you have to go outside yourself to check the solar shadings Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 28 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Facade motor identification Turn direction check In this next step the system wants to know if all motors turned in the correct direction The system has sent all the motors to 0 position All you have to do is to check the solar shadings on the facade in question to confirm that they are in their upper 0 position If the turn direction has been wrongly set then the solar shading will be in its 100 lower position So click on the Yes button if all solar sha
105. opyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 46 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP When you have dragged and dropped the Remote Settings view will pop up Here you can see all the motors or motor owners that the remote will be able to control what we call in animeo IP a Local zone Now drag and drop as described above to make your remotes active Remember to save your configuration to file and then upload your changes to the BuCo when you are ready To remove motors or zones from a remote you simply first select e g a motor in the list Then click on the red X button to the right of the motor This will remove that motor from the remote Settings for a Remote You can make two important settings for a remote Select remote type Depending on what kind of possibilities the users will have and what kind of remote is used you can select different ergonomic profiles Set local command off delay In the general settings view there is a global off delay setting for remotes default but here you can set a specific time delay for a remote in question The Local Command off delay is the time span that the user s command will be active before the system takes over again Virtual Remote Service There is an option to add virtual remotes e g web remotes to an animeo IP system
106. or allocation dialog Allocate the temperature sensors by double clicking or by drag and drop to the list on the right 3 Sun sensor allocation Click on the Select button to the right to open the sensor allocation dialog Allocate the sun sensors by double clicking or by drag and drop to the list on the right Temperature threshold The function goes active if the room temperature drops below this Sun threshold The sun intensity must be greater that this for the function to go active On delay Delay before function turns on Off delay Delay before function goes off Position when active Normally 0 You can set any position You can also use the Generic Position feature 9 Active period Additionally you can set which days and time span this function should be active O eae Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 75 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Preserve Heat This function is used to make use of the solar shadings to increase the insulation factor for the window openings This will reduce heat from dissipating throughout the window during cold and gray days lowering heating costs This scenario occurs when it is quite cold and dark outside You have to know a bit about the window glass performance to set this function properly The functions cond
107. or animeo IP Zones how you should plan to maximize the usage of the different zones A Security Zones is intended to protect the solar shadings and the building from different conditions The behavior set up with functions for a Security Zone should reflect the solar shading types that will be controlled by the Security Zone Also other aspects need to be addressed such as Facade s cardinal direction Facade direction Different floors with different needs Interior or exterior Mounting Wind aspects Basically you need a Security Zone for each different behavior required that needs some special settings due to security considerations Comfort Zones on the other hand are purely for occupant comfort and energy saving functions Therefore other aspects need to be addressed before deciding how the Comfort Zones should be distributed inside the Security Zone Aspects such as Different floors with different needs Different rooms with different needs Different solar shading types Basically you need a Comfort Zone for each different behavior that needs some special settings due to comfort considerations It is possible that each motor has its own Comfort Zone but then you have to make comfort function settings for each motor Facade Based Configuration or Group Based Configuration In animeo IP there are two ways to commission and visualize a building Facade Based or Group Based The recommended way is Facade Based but
108. place It happens that things get broken In this system you can easily replace a system component such as BuCo Sub controllers remotes and motors via the Replace System Hardware Wizard While in Configuration mode under the main menu Tools gt Advanced gt Replace System Component choose which component you want to replace Replace a Motor ATTENTION First replace the broken motor physically Connect all the wires and set the end limits The Replace System Hardware Wizard opens and shows a list of motors Select the motor that you want to replace Click on the Next button to continue the wizard Now the system needs to discover the new motor Click on the Discover system button to start this procedure Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 89 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Found 5 motors 1 new O unsssigned Picture 108 Discovered motors information The Discover should now show that it found a new motor Click in the Next button to continue If this is not the case then make sure that all cables to the motor are attached and that it is powered Next a list of newly discovered motors will be shown Select the new motor that will replace the old one in the configuration Click on the Next button Then finally click on the Finish but
109. position When active go to Custom sun tracking Generic sun tracking Maximum allowed position 100 ES Maximum allowed angle EN E Minimum position movement 1 de Minimum angle movement Position for unsupported products fy Angle tor unsupported products lo x Default window height 150 cm Default sun enter depth 50 cm Picture 95 Function Settings Sun Sun tracking position Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 78 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Settings 1 Custom or Generic sun tracking Choose to use an individual sun tracking settings for the Comfort Zone or subscribe to a Generic sun tracking that is globally defined Generic Solar Shading Position Maximum allowed position This is the maximum allowed bottom position that the solar shades are allowed to take Change this setting if you don t want the solar shadings to go all the way down Maximum allowed angle For solar shadings with angle feature such as Venetian blinds this is the maximum allowed angle that the solar shades are allowed to take Change this setting if you don t want the solar shadings to go tilt all the way down Minimum position movement If you don t want the solar shadings to move too much then use this setting to make a condition
110. r Picture 37 Example of defined facade in Main View There are two important steps that should be done before you add functions to this configuration 1 Define more Security Zones As you are familiar with the zone concept in animeo IP since you have read that section in the beginning of this manual you know by now why you need to create Security Zones and one or many Comfort Zones When facades or facade sections were made in the Virgin Wizard they were provided automatically with one big Security Zone and one big Comfort Zone What you now need to do is to subdivide these into smaller zones to be better able to provide special function behavior or meet other needs of the occupants or customer So in the main window you will see all facade sections see figure 9 Double click on a facade or click on the magnifying button at the right top corner to access a facade s inner parts Now you will see a grey matrix with one red and one green frame around all the cells Inside each cell are the motors that were found and assigned in the Virgin Wizard Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 36 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Select mode Motor Comfort zone D Security zone Picture 38 A facade zoomed in for configuration If you want to cre
111. r motors manually from the PC Shortcuts to important system status windows Zoom and pan feature if you have many objects zoomed in and want to pan around Bottom part 4 The Configuration Mode button In order to be able to make or change the Configuration the system needs to be in Configuration Mode There are two ways to enter this mode via the Settings menu or via this button at the bottom of the Main Window When you press this button you will be asked to enter a user name and password to confirm that you have the authority to change a configuration To exit from Configuration Mode just click on the button again Middle part 5 System content and status info It is in this area that the system s different objects will be shown depending on what folders you select in the top bar Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 17 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP The Welcome Center When you start the Visual Configuration software for the first time you will be greeted by the Welcome Center This is your base from where you will get suggestions of what to do Here you will also find short cuts to all the wizards in the system as well as other useful resources All is well the system is working fine Tf you want to change something in the configuration pl
112. re in Layout Mode you also have the possibility to merge facades This feature is very practical if you have done commissioning floor by floor or even room by room and you want to merge these facade sections into one big facade for better supervising since it will reflect the way the facade looks in reality Select any facade section that you want to merge and drag it over another facade section When the facade sections intersect a merge guides appear Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 4 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP i mA me t ne ai fii SS j EII A AA A y IA AAA A SS ae n ae i 6 ks Picture 48 Merge of facade Help guides visible These merge guides become active highlighted depending on which direction you are intersecting the other fa ade section The merge guide will tell you how the new merged facade will grow and also how the sections will be placed relative to each other If the facade sections have the same number of floors or windows you can only merge left and right or top and bottom When the facade sections differ in floors or windows for example if you are trying to merge a big section to a smaller section or vice versa the diagonal guides are also activated You can see on the guide how the two facade parts will be merged Note You
113. s Start doing this by clicking on the user icon in the middle on the right to show the Web users window Username Password Real name Sam sam Type in new user here Picture 99 Remote Settings Web users window It is here that you manage the user accounts for Web remotes You can do four things Import user list Open an excel file with three columns or a comma separated csv file and the Web users list will be populated accordingly Add user By clicking the on the last entry where it says Type in a new user here Enter the username real name and password and hit the Enter key to create and add a user account Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 32 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Remove user Select one or several users in the user account list and then click on the remove user button at the top right Doing this will remove the user not the remote Edit user Select any column on a user in the account list to edit the entry Note Several users can be assigned to the same Web remote One user can have several 0 Web remotes Close the window when you have added the users you want Select Web remote ergonomics You can select the type of WEB remote At this time there are three possibilities Up Stop and Down
114. ses where you need one sun function for each season of the year which is the case in Norway or that during sun rise and sun set different sun values are needed to avoid glare In these Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 87 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP cases use several sun functions and set the Time Period feature to manage when each of the sun functions are allowed to be active These settings can be made for all Comfort Functions Case 2 Create good energy optimal scenarios as the ones in animeo IB There are different ways to limit the end users ability to control their blinds The best scenario is to have a mix of limits and possibilities for the end user To save maximum energy the solar shadings should be in the optimal position as much as possible Often this position is not the preferred position by the end user The parameters listed below should be used as a palette to create the best energy mode for the customer e Use the Remote Off Delay Remember to use the Generic Settings feature e Use the Local Command Timer s Disable Local Control and Reset Local Control feature Medium energy saving example Set the Remote off Delay to 4 hours Disable Local Control from 18 00 to 07 00 Reset the Local control at 09 00 12 00 and 15 00 To have a more ener
115. side Sensor Boxes ISB Totally max 100 sensors from all sensor boxes For a system using animeo IP RS485 technology it is recommended to connect maximum 200 motors per Sub controller It is also recommended to not connect switches on the same bus line as motors Sensor Bus Each Sensor Bus can have up to 1 Outside Sensor box and two Inside Sensor boxes connected It is recommended to not connect more than 10 Sensor boxes to a system Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 10 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP The RS485 bus Each RS485 bus can have up to 200 motors or remotes connected It is recommended to not mix motors and switches on the same RS485 bus If this still is the case then the nr of motors is decreased to 100 and 30 switches Zones how they work In animeo IP there are three types of zones Security Zones Comfort Zones and Local Zones Let s start with Security and Comfort Zones Security Zones SZ and Comfort Zones CZ are related as parent and child A Security Zone is the highest type of zone tis in the Security Zone that Security Functions act Picture 2 Security Zone red example on a building Comfort Zones are created inside a Security Zone tis in the Comfort Zone that Comfort Functions act A Comfort Zone cannot l
116. speed threshold The wind speed value that will trigger on the protected angle chosen Example In the example shown in the picture above the normal wind speed threshold is set to 12 m s But if the wind is blowing from the North which is the protected angle in this case 8 m s is enough to trigger the function The angle span set is north 45 which is wind coming in from 337 5 and 22 5 When it snows some Solar Shadings have to be locked in their secure position For interior Solar Shadings this function is not needed lt gt Snow Hy Rain sensor used Rain 1 Sensorbox 1 Temperature sensor used Temperature 1 Sensorbox 1 Temperature threshold E G On delay EN Off delay EM Picture 85 Function Settings Snow Settings 1 Rain sensor allocation Click on the Select button to the right to open the sensor allocation dialog Allocate the wind sensors by double clicking or by drag and drop to the list to the right 2 Temperature sensor allocation Click on the Select button to the right to open the Sensor allocation dialog Allocate the wind sensors by double clicking or by drag and drop to the list to the right 3 Temperature threshold Choose from which temperature the function should be active 4 On delay The time it must snow before the function goes active Copyright O 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 69 Somfy SAS capital 20 000
117. t Sensor box then continue the wizard and Upload the Configuration For each function that listened to the old Sub Controller s sensor box needs to have its sensors reallocated to this new one When all sensors have been replaced in the affected functions upload the changes by pressing the Upload button Now add the motor bus to the new Sub controller Start the Replace Sub Controller Wizard You need to be in Configuration mode then go the top menu Tools gt Advanced gt Replace System Component gt Replace a Sub Controller The wizard opens Now the system needs to discover the new Sub Controller Click on the Discover system button to start this procedure You may have to wait for a Sub Controller to connect yes it is the one you are replacing but the system does not know that yet When the Discovery is finished click next to continue Select the Sub Controller that you want to replace Use the ID that you noted in step 1 Click on the Next button to continue Select the new Sub Controller Use the ID that you noted in step 1 Click Next to continue Tick the checkboxes to remove the old sensors and click on the Next button Now click on the Upload button to active the replacement Done Replace a Building Controller To replace a Building Controller follow the steps below 1 A O SA Make or find a backup of the existing Configuration Go to the file menu and Save the configuration If the Building
118. t items there are some filters to be used Filter on OF Picture 104 Floor plan Configure toolboxes Filter on Choose to filter the two toolboxes Remotes and Motors on specific configuration definitions such as Floor Room Direction or Type Secondly choose a value to filter on For example if filtering on Floor and Floor 1 then only the remotes and motors belonging to that floor will be shown Filter on selected remotes If you have several remotes and many motors on a floor you may need to filter even deeper This filter will only show the motors linked to the selected remote in question In order for this to work the remote bindings must have been made prior to this 1 Note You can have selected remotes in both the list and on the floor plan Keeping track SS of this will help you to avoid confusion Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 85 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Show only unplaced motors When you drag motors into the Floor plan you are mainly interested in the motors that are not placed on the Floor plan This filter will enable so that you only see the unplaced motors those that still need to be dragged into the Floor plan Remember to upload the new settings to the BuCo when you finished configuring Insert items by drag and drop
119. te to the next slide Commissioning enter connection details First the Visual configuration software needs to know which Building controller BuCo that should be commissioned This is done by entering the IP number or host name of the building controller in question When connected directly from your PC to the BuCo using one of the IP Bus Ethernet ports the default host name is buco animeoip com or the IP number 10 1 10 1 Enter this name or numbers in the first textbox unless it is already filled with one of these values The default port number on the BuCo is 10000 so enter that number in the port number text box Then click on the Connect button The wizard will check if it can reach the BuCo on the IP number that you have given You will get a green arrow and a message if you succeed in connecting Click on the Next button to continue r To be able to make a configuration you need to be connected to a building controller Enter the IP address or name and the port number of the building controller you want connect to for configuration Enter connection details Host name or IP number 192 168 1 54 Port number 10000 Default 10000 Connect What do you mean with access With this tool you can connect to different building controllers The tool needs to know exactly which one you want to connect to The only way to do this is to give the tool an IP number such as 10 1 10 1 and a port number such as 80
120. tem and one providing a toolbox when you are in Configuration Mode Information faceted In the first upper box there is an Internet based weather forecast getting data according to the projects location stated in the commissioning phase This feature requires that the system be connected to the Internet In the second box there is a System Info list that presents different statuses of the system In the third box there is a legend about the system colors used In the fourth box there is another legend briefly explaining the different icons used in the system Configuration faceted In the first upper box a tree view of the system s different facades or groups is shown In this tree you can navigate and create zones to which you later can add functions The second box contains the system s remotes and the functionality to manage them In the third box all the system s motors are shown From this box or list you can drag and drop motors to Comfort Zones In the last box you have all the available functions that exist in the system Read more about how to configure the system via the configuration faceted sidebar in chapter X Right part 3 The quick access tabs The three tabs visible on the right side of the main window open containers of features that you maybe want to have quick access to Click on the tabs to reveal them The three tabs have the following purposes PC manual command when you want to control certain zones o
121. tion dialog Allocate the wind sensors by double clicking or by drag and drop to the list to the right If more than one sensor is chosen the sensor with the highest wind speed value will be read from At least one sensor must be allocated 2 Wind speed threshold The wind speed needed to activate the wind function 3 On delay The time the wind speed must exceed the wind speed threshold before activating wind function 4 Off delay The time the wind speed must be less than the threshold before deactivating the wind function Examples of settings wind speed parameters The following examples are just proposals contact the end product supplier to get advice Solar shading type Recommended wind speed On delay Off Delay m s Km h Mph Facade awning Screen 7 25 15 1 sec 5 15 min External venetian blind 12 43 26 1 sec 5 15 min Folding arm awning 6 22 13 1 sec 5 15 min Rolling shutter 15 54 33 1 sec 5 15 min Wind direction If you have a wind direction sensor installed you have access to this smart function The standard Wind function act irrespective of the wind direction it leads to the following fact if the wind comes from say the west and exceeds the wind speed threshold your sun protection on east facade will be locked in secure position which is probably not necessary With the wind direction function you can set a specific protected angle with its own wind speed threshold that should be extra sensitive if the wind blows from a c
122. tion is always available Use this function when a need to lock a Zone is necessary due to safety reasons Settings Select which Key switch that should control this function The values ON or Off is shown to indicate in which status the switch or key lock is in Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 65 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP it Key Security Zone Lock Key switch input used Switch 1 Sensorbox 2 Picture 82 Function Settings Key Security Zone Lock Wind Speed The wind function is used to ensure that the Solar Shadings will not be damaged by wind When the wind speed exceeds the wind threshold the Solar Shadings will be locked in the secured position 0 For interior Solar Shadings this function is not needed Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice 66 Somfy Manual for animeo IP Wind i Wind speed sensor used ADD Y pe Wind speed 1 Sensorbox 1 Wind speed threshold 7 m s On delay 2 Off delay EN Picture 83 Function Settings Wind Settings 1 Wind sensor allocation Click on the Select button to the right to open the Sensor alloca
123. to BuCo button and the configuration you have made will be sent to the BuCo Building Controller that you are connected to E e B animeo IP Visual Configuration Make New Configuration Wizard commissioning has never been so easy me Sa Virgin wizard completed the configuration will be uploaded to the BuCo when you press the upload button Upload to Buco Upload what does it mean In order for your configuration to take effect you need to upload it to the Building Controlier BuCo Press the Upload button to do so Previous Cancel Picture 34 Make New Configuration Finished Upload the Configuration to the BuCo When the upload is finished and successful you can end the wizard by clicking the Finish button Great now you have made the animeo IP system s backbone Let s bring it to life with functions Configuration Configuration Part 1 Group Based So the configuration you made so far if you did all the steps in the Virgin Wizard has discovered motors sensors and switches Click on the Bind motors button in the Welcome Center or close the latter to reach the main window You are now automatically in Configuration Mode directly after finishing the Virgin Wizard There are three important steps that must be done before you add functions to this configuration 1 Create Groups As you are familiar with the zone concept in animeo IP since you have read t
124. to the room without creating glare Twilight The twilight feature is used to detect when sunrise or sunset is occurring When using this feature some special conditions need to be known and thought about Think of this feature as a sun function with a special timer The sun sensor value time and facade or motor direction all must be valid before this feature gets active Set the sensor On threshold to a low value so that the sun rise or sun set is captured by the function The system uses the official sunset and sunrise meaning when the sun is starting to come above the horizon and vice versa E g the sun rise function goes active when the sun has an angle of 0 8 degrees below the horizon It is recommended to use the twilight sunrise feature only with fixed position Because sun tracking starts only when there is a positive angle so if sun tracking is chosen together with twilight sunrise then there will be a gap before the function gets active since the sun tracking will not be activated until the sun is above the horizon Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 79 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Keeping the 30 min delay will make sure that we cover the actual twilight event Be innovative when it comes to skyscrapers where windows several hundreds of feet
125. ton Replace a Remote The Replace System Hardware Wizard opens and shows a list of remotes Select the remote that you want to replace Click on the Next button to continue the wizard Now the system needs to discover the new remote Press on one of the remote s button to activate it in the system Select the new remote in question and then click on the Next button a Replace System Hardware Wizard Now in the list below are all the remotes or switches discoverd by the system Press on a button the switch or remote you pressed on will jump to the top of the list Select the remote you want to configure and click on next button Remote ID oa Type Button Time Configured 119960 SmartSwitch3 Auto Discovered 6 1 2012 2 58 59 PM False 1B2A36 SmartSwitch3 Auto Discovered 6 1 2012 2 54 37 PM True Listening Remote or switches For this system there is no difference between remotes or switches They are all treated the same You can always via the Remote toolbox manage your remotes and switches Previous Next Cancel Picture 109 Replace Remote wizard Click on the Upload button to update the configuration and after upload click on Finish button to exit the wizard Replace a Sub Controller Note If a Sensor box is connected to the Sub Controller and at least one of the sensors y are used then got to the Replace Sub Controller with Sensor section Note You can rep
126. tor 1280x768 resolution Mouse and Keyboard Windows 7 32bit Recommended Intel Core i3 or better 4 GB internal memory 1 GB free hard drive space True color graphic card one or multiple 24 monitor 1920x1080 resolution or more Mouse and Keyboard Windows 7 64bit software should be dedicated to animeo IP only No other programs should run on the PC to lj To ensure the functionality of the system the PC running the animeo IP Visual Configuration fulfill the warranty terms How to read this manual The manual is made in such way that you quickly can start a commissioning while reading the manual It will present parts of the animeo IP Visual Configuration software in the order as they come up when commissioning from scratch First we go through some basic concepts that need to be understood and things that need to be planned before you start the animeo IP Visual configuration software l Here and there you will find the picture to the left in the manual SE This indicates tip and trick information that can be useful When you will find this picture to the left in the manual it indicates very important information Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 7 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Before Commissioning Understanding animeo IP There
127. ts and what kind of sensors will be used Each sensor can also be given a name Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 Q Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP In the wizard there is a special remote section where the user can discover Remotes or Switches hereafter only called Remotes since they are basically the same The user pushes a button ona remote and that remote will appear in a list The user may assign the remote some descriptive data in order to make it easier to bind to motors in a later stage 30 ee ale pee pa dy me px P A ae mimi P As a Al BE mH TE O ci io sOmfy dape 7 Ibs ae A A A Ml ae A O xt ie sOmfy Presented below are the different boxes in the animeo IP topology The BuCo is the hub and the decision taking unit in the animeo IP system It is to this device that the animeo IP Visual Configuration software communicates with From the BuCo a backbone network TCP IP can be made in order to extend the system covering larger areas and increasing the number of devices that could be included The extension is made with Sub controllers The BuCo has the flowing inputs and outputs that are normally used 2 Ethernet ports for the animeo IP Bus backbone 1 Ethernet port for extern
128. ure the animeo IP system you need to have some sort of physical connection to the Building Controller s Ethernet ports e The easiest way is to simply take an Ethernet cable and plug it in to a free IP Bus Ethernet port on the BuCo and the other end into your PC Make sure that your PC can get its IP number dynamically addressed DHCP because it will get one from the BuCo Do not connect the IP bus to an IT Network The BuCo has its own DHCP server and will y create conflicts when connected to another network e Connect the LAN port to a router and your PC to the router In this case the router will decide which IP number the BuCo will get Look in the external software tools provided for an easy BuCo IP identification e Ilfthe BuCo s LAN port is connected to the buildings network then the IT administrators needs to know the BuCo s MAC address which you can see in the Hardware view in Visual Configuration software The IT administrator needs to set up rules in their router so that when the BuCo s MAC address is presented in the network it should be mapped to a specific IP number in their internal network You need to get that IP number and you need to access to their network with your computer e n order to reach the BuCo from the Internet the IT administrators must first to the above then they need to re route traffic requesting to a certain port in their public Internet IP number The firewall settings should be set so that they a
129. uros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Note The BuCo needs to reboot before the settings are changed The system will be inactive Y in Maintenance Mode for a minute or two If asked choose Yes to leave Maintenance Mode Note If the BuCo is connected to Internet or to a network with NTP Network Time Protocol then the Set time feature will be overridden Location Select the nearest location of this project Coon Region Location Barda So Asia Baku x juni 2042 tH on to JE 7 14 20 21 28 5 Cancel Picture 62 General Settings window Location Time General Building name Change the name of the system if it is incorrect Remotes Off delay This is the general default setting that Remotes can subscribe to All Remotes that is set to listen to this setting will change its off delay when changed This is an easy and quick way to manage the Remotes off delay Passwords As a user the password can be changed which is needed to access the system and making changes on the Configuration Click on the Change button to show the Password settings dialog Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 54 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Build
130. x on the right hand side to delete a timer Security Timer El Fundion enabled Hmers 17 y 13 t 20 00 to 07 00 Picture 88 Function Settings Security Timer Solar shadings blocked during lunch and night Local Command Timer Use this timer to disable local control or reset local control This function could be used for example during Lunch and none working hours to ensure that the most energy efficient function is active You can also use the reset feature to get a more coherent and nicer looking facade You can have several different timers provided that they don t conflict with each other if they do they will be shown red You can have up to 8 Local Command Timer functions in each Security Zone and in each of these you can have 24 timers Settings 1 Enabled Per default the function is enabled but you can disable the function if necessary 2 Add timer Click on the Add timer button to add a timer 3 Action Choose between Disable local control and Reset local control depending on what you want to achieve Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 72 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP 4 Set time Drag the triangles with you mouse to change the start and stop time for each timer or enter the time manually in the textboxes to the right
131. y functions have higher priority than Comfort functions for example a wind function overrides a sun function Add functions To reach the available functions or to be able to edit the configuration at all you need to be in Configuration Mode To enter this mode you simply click on the Configuration Mode button centered at the bottom of the main window The rest of the commissioning is done via the view presented here You are automatically in Configuration Mode after finishing the Virgin Wizard When you are in Configuration Mode the left sidebar with the toolboxes is visible At the bottom there you have all functions that are available in the animeo IP system Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 39 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP A Custom Default Picture 42 The Functions library in the Functions toolbox Simply drag and drop a function you want to a zone This can be done to either a zone in the middle of the main window or to the zone tree toolbox in the left upper corner Once you have dropped a function by releasing the mouse button the Function Settings will appear showing settings for that particular function Security functions red orange can only be dropped to a Security Zone Comfort functions green can only be dropped to a Comfort Zone Make
132. you manage the licenses that the configuration should have General Settings here you will find settings that are related to the project as a whole such as location units building name passwords etc Enter or Exit Configuration Mode when you want to edit the configuration you must be in this mode e Tools gt Reset Local Command when you want to override all Local Commands setting the system to Auto mode Disable local control when you temporarily want to block Local Commands Make new Configuration when you will do a new commissioning Extend Configuration when you want to add hardware to the configuration Advanced gt o Replace System Component gt Replace a Motor when you want to exchange a motor Replace a Remote when you want exchange a remote Replace a Sub controller when you want to replace a Sub Controller Replace a BuCo when you want to replace a Building Controller o Firmware upgrade when you want to make a software update to the animeo IP system e Views gt Welcome Center the window from where you can easily access different parts of the animeo IP Visual configuration software Sensors View where you can see the status of all the sensors in the system Functions View where you can see the status of all the functions in the system Remote View where you can see and manage all the remotes within the system Copyright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001
133. yright 2003 2012 SOMFY SAS All rights reserved IDDN FR 001 460028 000 S A 2011 000 31500 80 Somfy SAS capital 20 000 000 Euros RCS Bonneville 303 970 230 Changes can be done by Somfy SAS without prior notice Somfy Manual for animeo IP Web remotes service Floor plans service Each Services are activated via a dedicated license key enables certain time period In order to acquire a license the following steps should be followed 1 Connect to the BuCo in question 2 Enter Configuration mode 3 Goto the License View by the main menu gt Settings gt Licenses License View Ed BuCo ID oz2413 Owner s m O O Description Service Expires Key Floorplans 2013 05 24 7MLG N302 HLWJ SNES KISY D6WK JU Renew Delete Web switches 2013 05 24 CTBE JYYM ABKN 7LDO 34XL RCIA KQ Renew Delete Energy package 2013 05 24 LQVF LAJS VMIY Z2P8 D2A4 OR3P RQ Renew Delete Picture 97 License View Manage licenses 4 Copy the number in the text field BuCo ID and send this number to your Somfy Sales person 5 When you have received a license key open the License View again 6 Click on the Import license button in the upper right corner if you have received a license file Or follow step 7 7 Click on the Activate button appearing to the right of the Service you want to activate This will open the Activate License View 8 Enter the expiration date and the license key that you have received 9 Cl