Home

Online Pure Sinewave UPS Uninterruptible Power Supply System

image

Contents

1. 15 e 10 Backup time setting for outlets Parameter 3 Set up backup time on battery mode for general outlets 0 999 setting the backup time in minutes from 0 999 for general outlets on battery mode 0 When setting as 0 the backup time will be only 10 seconds 999 When setting as 999 the backup time setting will be disabled e 00 Exit setting 3 6 Operating Mode Description Operating mode LCD display Online mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at online mode ECO mode Energy saving mode When the input voltage is within voltage regulation range UPS will bypass voltage to output for energy saving Frequency When input frequency is within 40 Hz to Converter mode 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is sounding every 10 second 16 Standby mode UPS is powered off and no output supply power but still can charge batteries 3 7 Faults Reference Code Fault event F
2. H Battery Info a T ARA E RRA 7 E e m Programmable Mode Operation info Outlet Info 11 Display Function Backup time information Indicates the remaining backup time in pie chart Indicates the remaining backup time in numbers LLLI H hours M minute S second ault information 1 Indicates that the warning and fault occurs Indicates the warning and fault codes and the codes are listed in details in 3 5 section i Mute operation Indicates that the UPS alarm is disabled Output amp Battery voltage information CI LI ye Indicates the output voltage frequency or battery voltage LILLLI az Vac output voltage Vdc battery voltage Hz frequency OUTPUT Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 OVER LOAD Indicates overload SHORT Indicates the load or the UPS output is short circuit gr O mmable outlets information Indicates that programmable management outlets are working ode operation information Indicates the UPS connects to the mains r CU lt Indicates the battery is working Indicates the bypass circuit is working Indicates the ECO mode is enabled ECO Indicates the Inverter circuit is working Indicates the output is working Battery information Indicates the Battery level by 0 25 26 50 51 75 and 76 100 BATT FAULT
3. KR 19 1000RM KR 19 2000RM KR 19 3000RM Online Pure Sinewave UPS M POWER ALL Uninterruptible Power Supply System Table of Contents E dmportant Sareb Wa INGA 2 is Transport ls 2 1 2 Preparellol ita 2 io TINS all 0 EPA T LO DO STESSO 2 I4 Opera 0 ras 2 1 5 Maintenance service and faultS occcccccoconcncncncncncacaracararar arar nr arar r rar nr nennen nennen 3 2 Installadgon sanda SCLUD sessin aaia 4 Zl REAR panel Manara 4 2 2 Rack Mounted the UP Saa O 5 O Pass tantos duod E E A E E AS E E T 5 2 4 Battery replacement ura 7 2 5 Battery Kit assembly ODUON enrm e Vets readies ea etna 8 iaa 11 3 1 BULON 2 9 11 5 2 ESRB 11 Gsm say RR IT E UU T IUIS 13 3 4 LCD display wordings INGOX ccccccsecsscuseusecuscusecuscuseeuscusecususeeuecusecuseusecueausesues 13 A PES 13 3 6 Operating Mode DescriptlOn aida a 16 3S7 Faute Reference CO visa drain tice da eb Lain seva qa Lue eR E efr pd V b a bm VEN 17 3 8 Warming Indicator 17 E TWMOUD IESO O onnan 18 5 Storage and Mantena Ce sgreing a aaa dd 20 Oeo PECCAN Sian 21 1 Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety information and operating instruct
4. from the batteries e Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any other measures necessary when working with batteries remove wristwatches rings and other metal objects use only tools with insulated grips and handles When changing batteries install the same number and same type of batteries e Do not attempt to dispose of batteries by burning them This could cause battery explosion e Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic e Please replace the fuse only with the same type and amperage in order to avoid fire hazards e Do not dismantle the UPS system 2 Installation and setup NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged Please keep the original package in a safe place for future use NOTE There are two different types of online UPS standard and long run models Please refer to the following model table KR 19 DEM KR 19 Standard KR 19 KR 19 KR 19 3000RM KR 19 DM Long run KR4 19 3000RM L 2 1 Rear panel view KR 19 1000RM L KR 19 200
5. tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on Step 4 Cover the other side of plastic shell as one side of plastic shells below chart Then battery kit is assembly well 3 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on Step 4 Cover the other side of plastic shell as one side of plastic shells and insert one below chart Then battery kit is assembly well more dummy battery on the space 4 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on Step 4 Cover the other side of plastic shell as one side of plastic shells below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on Step 4 Cover the other side of plastic shell as one side of plastic shells below chart Then battery kit is assembly well 10 3 Operations 3 1 Button operation Turn on the UPS Press and hold ON Mute button for at least 2 seconds to turn on the UPS gt Mute the alarm When the UPS is on battery mode press and hold this button for at least 5 seconds to disable or enable the alarm system But it s not applied to the situations when w
6. 0RM L sich ds AI s eX IN KR 19 3000RM L x t Q O 8 90 Programmable outlets connect to non critical loads Output receptacles connect to mission critical loads AC input Input circuit breaker Network Fax Modem surge protection Emergency power off function connector EPO USB communication port RS 232 communication port SNMP intelligent slot 10 External battery connection only available for L model 11 Output circuit breaker eee Eure SY en 2 2 Rack Mounted the UPS This UPS can be mounted in the 19 rack chassis Please follow below steps to position this UPS Step 1 Step 2 Y ww nooo nee e E A i ME n 55 E ui i eoo j D t D u PONTE cece CUT nmm 2 3 Setup the UPS Step 1 Connect battery wires For safety consideration the UPS is shipped out from factory without connecting battery wires Before install the UPS please follow below steps to re connect battery wires first Step 1 Step 2 Step 3 Ert a reso Mal E Remove front panel Connect the AC input and Put the front panel back to re connect battery wires the unit Step 2 UPS input connection Plug the UPS into a two pole three wire grounded receptacle only Avoid using extension cords e For 200 208 220 230 240VAC models The power cord is supplied in the UPS pa
7. 2 3 4 11 12 13 and 41 on LCD display and alarm is continuously sounding Battery backup time is shorter than nominal value The UPS shut down automatically because short circuit occurs on the UPS output A UPS internal fault has occurred There are two possible results 1 The load is still supplied but directly from AC power via bypass 2 The load is no longer supplied by power Batteries are not fully charged Batteries defect 19 Check output wiring and if connected devices are in short circuit status Contact your dealer Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Contact your dealer to replace the battery 5 Storage and Maintenance Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this Case please contact your dealer Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 40 C 45 C Every 2 months 20 6 Spec
8. Indicates the battery is fault LOW BATT Indicates low battery level and low battery voltage Input amp Battery voltage information HH Vdc Indicates the input voltage or frequency or battery voltage morcm Vac Input voltage Vdc battery voltage Hz input frequency INPUT 12 12 3 3 Audible Alarm Sounding every 4 seconds Low Battery Sounding every second Overload Sounding twice every second Fault Bypass Mode Continuously sounding Sounding every 10 seconds 3 4 LCD display wordings index Abbreviation Display content Meaning I ENA DIS ESC HLS LLS BAT Enable Disable Escape Pr Pr uv 77123 High loss Low loss r oc 7 pe Pr Unum Battery Converter O Temperature O T U rm Pa er Pa ra oe XL TO mr m U Charger 3 5 UPS Setting There are three parameters to set up the Parameter 1 UPS Parameter 1 It s for program alternatives There are 10 programs to set up Refer to below table Parameter 2 and parameter 3 are the setting options or values for each program Parameter 2 Parameter 3 13 e 01 Output voltage setting Parameter 3 Output voltage For 200 208 220 230 240 VAC models you may choose the following output voltage 200 presents output voltage is 200Vac 208 presents output voltage is 208Vac 220 presents output voltage is 220Vac 230 presents output voltage is 230Vac 240 presents output voltag
9. Noise Level Less than 50dBA 1 Meter MANAGEMENT Smart RS 232 USB Supports Windows 2000 2003 XP Vista 2008 7 Linux Unix and MAC Optional SNMP Power management from SNMP manager and web browser Product specifications are subject to change without further notice
10. arnings or errors ON Mute Button occur Up key Press this button to display previous selection in UPS setting mode Switch to UPS self test mode Press and hold ON Mute button for 5 seconds to enter UPS self testing while in AC mode ECO mode or converter mode Turn off the UPS Press and hold this button at least 2 seconds to turn off the UPS in battery mode UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting OFF Enter Button by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to default display when pausing for 10 seconds Setting mode Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in standby mode or bypass mode Down key Press this button to display next selection in UPS setting mode Switch to bypass mode When the main power is normal press ON Mute Select ON Mute and Select buttons simultaneously for 5 seconds Then UPS Button will enter to bypass mode This action will be ineffective when the input voltage is out of acceptable range Select Button 3 2 LCD Panel Backup Time Info Fault Info Input amp Battery Mute Operation Voltage Info Output amp Battery Voltage Info
11. ault event Icon Bus start fail 0 X Bus over 0 0 0 01 x 1 02 x Invereroutputshortt 14 Bus under 03 x Battery voltage too high 2 rm 04 0 x 2 1 13 2 14 3 27 Bus unbalance 4 28 11 41 12 43 BATT FAULT Inverter soft start fail 11 Over temperature 440 Inverter voltage high 12 x Overload 43 3 8 Warning indicator Warning Low Battery Overload Battery is not connected Icon flashing Sounding every second H Over Charge Site wiring fault Sounding every second Sounding every second EPO enable Over temperature Charger failure Out of bypass voltage range Sounding every second Sounding every second E Sounding every second AL 17 4 Troubleshooting If the UPS system does not operate correctly please solve the problem by using the table below Symptom No indication and alarm even The AC input power is not Check if input power cord though the mains is normal connected well firmly connected to the mains The AC input is connected Plug AC input power cord to the UPS output to AC input correctly The icon Nanc the warning EPO function is activated set the circuit in closed code EP flashing on LCD position to disable EPO display and alarm is sounding Inca every second Line and neutral Rotate mains power socket conductors of UPS input by 180 and then connect are reversed to UPS system The icon Aand flashing
12. ckage e For 100 110 115 120 127VAC models The power cord is attached to the UPS The input plug is a NEMA 5 15P for 1K and 1KL models NEMA 5 20P for 2K and 2KL models Note For Low voltage models Check if the site wiring fault indicator lights up in LCD panel It will be illuminated when the UPS is plugged into an improperly wired utility power outlet Refer to Troubleshooting section Please also install a circuit breaker 40A between the mains and AC input in 3K model for safety operation Step 3 UPS output connection e For socket type outputs there two kinds of outputs programmable outlets and general outlets Please connect non critical devices to the programmable outlets and critical devices to the general outlets During power failure you may extend the backup time to critical devices by setting shorter backup time for non critical devices For terminal type input or outputs please follow below steps for the wiring configuration a Remove the small cover of the terminal block 5 b Suggest using AWG14 or 2 1mm power cords Suggest using AWG12 10 or 3 3mm4 5 3mm power cords for NEMA type c Upon completion of the wiring configuration please check whether the wires are securely affixed d Put the small cover back to the rear panel Step 4 Communication connection Communication port USB port RS 232 port Intelligent slot 7 To allow for unattended UPS shutdown start up and status monitoring connect the com
13. download and install monitoring software from the internet 1 Go to the website http www power software download com 2 Click ViewPower software icon and then choose your required OS to download the software 3 Follow the on screen instructions to install the software 4 When your computer restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock 2 4 Battery replacement NOTICE This UPS is equipped with internal batteries and user can replace the batteries without shutting down the UPS or connected loads hot swappable battery design Replacement is a safe procedure isolated from electrical hazards CAUTION Consider all warnings cautions and notes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the battery box by removing two screws on the front panel Step 4 Step 5 Step 6 Remove the top cover of battery After replacing the batteries Re connect the battery wires box and replace the inside put the battery box back to batteries original location and screw it tightly Put the front panel back to the unit 2 5 Battery kit assembly option NOTICE Please assemble battery kit first before installing it inside of UPS Please select correct battery kit procedure below to assemble it 2 battery kit Step 1 Remove adhesive
14. e is 240Vac For 100 110 150 120 127 VAC models you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output voltage is 120Vac 127 presents output voltage is 127Vac e 02 Frequency Converter enable disable Parameter 2 amp 3 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Parameter 2 amp 3 Output frequency setting You may set the initial frequency on battery mode BAT 50 presents output frequency is 50Hz BAT 60 presents output frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz Parameter 3 Enable or disable ECO function You may choose the following two options ENA ECO mode enable DIS ECO mode disable Parameter 2 amp 3 Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key HLS High loss voltage in ECO mode in parameter 2 For 200 208 220 230 240 VAC models the setting range in parameter 3 is from 7V to 24V of the nominal voltage For 100 110 115 120 127 VAC models the setting range in parameter 3 is from 3V to 12V of the nominal voltage LLS Low loss voltage in ECO mode in parameter 2 Fo
15. ifications MODEL KR 19 1000RM L KR 19 2000RM L KR 19 3000RM L VA W 1000 VA 800 W 2000 VA 1600 W 3000 VA 2400 W INPUT 80 VAC 70 VAC 60 VAC 50 VAC 5 or 160 VAC 140 VAC 120 VAC 110 VAC 5 Voltage percentage 100 80 80 70 70 60 60 0 Range Low Line Comeback 85 VAC 75VAC 65 VAC 55VAC 5 or 170 VAC 150 VAC 130 VAC 120 VAC 5 High Line Transfer 150 VAC 5 or 300 VAC x 5 High Line Comeback 145 VAC x 5 or 290 VAC x 5 Frequency Range 45Hz 55 Hz or 56Hz 65 Hz Power Factor 0 99 normal voltage OUTPUT Output voltage AC Voltage Regulation Frequency Range Synchronized Range Frequency Range Batt Mode Current Crest Ratio CF Low Line Transfer 100 110 115 120 127 VAC or 200 208 220 230 240VAC 1 48 52 Hz or 58 62 Hz 50 Hz 0 2 Hz or 60Hz 0 2 Hz 3 1 max 2 Linear load Harmonic Distortion THDU 8 max Bat mode before shut down Transfer AC to DC Zero Time Inverter to Bypass 4 ms Typical Pure Sinewave EFFICIENCY 88 typical 90 peak BATTERY 3 5 Long run Depending on the capacity of external batteries Model Charging Current Current 8 0 A max Charging Voltage 41 1VDC 1 82 1VDC 1 82 1VDC 1 PHYSICAL Standard 480 x 438 x 88 600 x 438 x 88 600 x 438 x 88 iiis Net Weight kgs isi Net Weight kgs ENVIRONMENT 20 90 RH 0 40 C non condensing
16. ions carefully 1 1 Transportation Please transport the UPS system only in the original package to protect against shock and impact 1 2 Preparation e Condensation may occur if the UPS system is moved directly from cold to warm environment The UPS system must be absolutely dry before being installed Please allow at least two hours for the UPS system to acclimate the environment e Do not install the UPS system near water or in moist environments e Do not install the UPS system where it would be exposed to direct sunlight or near heater e Do not block ventilation holes in the UPS housing 1 3 Installation e Do not connect appliances or devices which would overload the UPS system e g laser printers to the UPS output sockets Place cables in such a way that no one can step on or trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the building wiring outlet shockproof outlet Please use only VDE tested CE marked power cables to connect the loads to the UPS system e When installing the equipment it should ensure that the sum of the leakage current of the UPS and the co
17. munication cable one end to the USB RS 232 port and the other to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS status through PC The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card When installing either SNMP or AS400 card in the UPS it will provide advanced communication and monitoring options PS USB port and RS 232 port can t work at the same time Step 5 Network connection Network Fax Phone surge port IN OUT Connect a single modem phone fax line into surge protected IN outlet on the back panel of the UPS unit Connect from OUT outlet to the equipment with another modem fax phone line cable Step 6 Disable and enable EPO function Keep the pin 1 and pin 2 closed for UPS normal operation To activate EPO function cut the wire between pin 1 and pin 2 Its in closed status for UPS normal operation Step 7 Turn on the UPS Press the ON Mute button on the front panel for two seconds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 8 Install software For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown You may insert provided CD into CD ROM to install the monitoring software If not please follow steps below to
18. nnected devices does not exceed 3 5mA 1 4 Operation e Do not disconnect the mains cable on the UPS system or the building wiring outlet shockproof socket outlet during operations since this would cancel the protective earthing of the UPS system and of all connected loads e The UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet e In order to fully disconnect the UPS system first press the OFF Enter button to disconnect the mains Prevent no fluids or other foreign objects from inside of the UPS system 1 5 Maintenance service and faults e The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel Caution risk of electric shock Even after the unit is disconnected from the mains building wiring outlet components inside the UPS system are still connected to the battery and electrically live and dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away
19. on LCD display and alarm is sounding every second The icon ZiNand flashing The external or internal Check if all batteries are on LCD display and alarm is battery is incorrectly connected well sounding every second connected Fault code is shown as 27 and the Battery voltage is too high Contact your dealer BATT FAULT or the charger is fault icon is lighting on LCD display and alarm is continuously sounding Fault code is shown as 28 and the Battery voltage is too low Contact your dealer BATT FAULT or the charger is fault icon is lighting on LCD display and alarm is continuously sounding The icon A and OVER LoAd UPS is overload ip aa loads from tna podeis UPS is overloaded Devices Remove excess loads from connected to the UPS are UPS output fed directly by the electrical network via the Bypass After repetitive overloads Remove excess loads from the UPS is locked in the UPS output first Then shut Bypass mode Connected down the UPS and restart devices are fed directly by it the mains Fault code is shown as 43 and The The UPS shut down Remove excess loads from OVER LOAD automatically because of UPS output and restart it overload at the UPS output icon is lighting on LCD display and alarm is continuously sounding 18 Symptom Fault code is shown as 14 and the icon is lighting on LCD display and alarm is continuously sounding Fault code is shown as 1
20. r 200 208 220 230 240 VAC models the setting range in parameter 3 is from 7V to 24V of the nominal voltage For 100 110 115 120 127 VAC models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage e 06 Bypass enable disable when UPS is off Parameter 3 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Parameter 2 amp 3 Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key HLS Bypass high voltage point For 200 208 220 230 240 VAC models 230 264 setting the high voltage point in parameter 3 from 230Vac to 264Vac For 100 110 115 120 127 VAC models 120 132 setting the high voltage point in parameter 3 from 120Vac to 132Vac LLS Bypass low voltage point For 200 208 220 230 240 VAC models 170 220 setting the low voltage point in parameter 3 from 170Vac to 220Vac For 100 110 115 120 127 VAC models 85 115 setting the low voltage point in parameter 3 from 85Vac to 115Vac e 08 Programmable outlets enable disable Parameter 3 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programmable outlets disable Parameter 3 Set up backup time limits for programmable outlets 0 999 setting the backup time limits in minutes from 0 999 for programmable outlets which connect to non critical devices on battery mode

Download Pdf Manuals

image

Related Search

Related Contents

Manuel d`utilisation  Kramer Electronics VS-3232V video switch  Genius Traveler 7000    Fraisier Bulletin technique  amoladora recta axial die grinder cod. 79901  GSM/GPRS/GPS Vehicle Tracker TK103A/B User Manual  Haz clic aquí para ver el panfleto de instrucciones, las  Everpure CGS-22 User's Manual  model wp-4 wp4-50 kp-4 ro-4m  

Copyright © All rights reserved.
Failed to retrieve file