Home

Zelio Logic 2 Programmable Smart Relays - Barr

image

Contents

1. E AABAA IAKA ARAE AAA avo aguia 11 JA dr LA Outeuhe 61 08 Molay BA ond QRO GA Relay SA 6 discrete I O 1 2 e inputs IH JL 2a 4 5 DT BAY ZTELDO Outputs OB Relay BA oF ta Functions pages 11 to 13 10 thew thew Led iban Modular smart relays have the following on the front panel Two retractable mounting feet Two power supply terminals Terminals for connection of the inputs Backlit LCD display with 4 lines of 18 characters Slot for memory cartridge or connection to a PC or communication interface 6 buttons for programming and parameter entry Terminals for connection of the outputs 2 3 4 ol 10 and 14 discrete I O 4 analog I O 1 z I O extension modules have the following on the front face I 1 Two retractable mounting feet 4 333999 2 Terminals for connection of the inputs Inputs IH IP 24VDC 4 3 Terminals for connection of the outputs 4 Aconnector for connection to the smart oS mm 5 ana Tao relay powered by the smart relay 5 Locating pegs 5 5 wipute Ascteg Outputs ctr GE Poelay BA OB D DD A EL 3 1 3 1 Characteristics Curves References Dimensions schemes pages 14 to 17 pages 18 and 19 pages 20 to 22 pages 23 to 27 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Functions Zelio Logic 2 Programmable Smart Relays Compact and modular
2. O a a m Zelio Soft 2 monitoring mode makes it possible to test the program executed by the smart relay i e O display the program on line O force inputs outputs control relays and current values of the function blocks O adjust the time O change from STOP mode to RUN mode and vice versa In simulation or monitoring mode the monitoring window allows the status of the smart relay I Os to be displayed within your application environment diagram or image Monitoring window Presentation description Characteristics Curves References Dimensions schemes pages 8 to 10 pages 14 to 17 pages 18 and 19 pages 20 to 22 pages 23 to 27 11 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Functions continued Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays Zelio Soft 2 programming software Definition Analog comparator a Control relay LCD backlighting 1 Output coil Functions Function Contact Fast counter Clock 1 Counter comparator 1 hae Summer Winter time switching or o Message Electrical scheme 21 HED eS Q 22 LADDER language enables a LADDER program to be written with elementary functions elementary function blocks and derived function blocks as well as with contacts coils and variables The contacts coils and variables can be annotated Text can
3. The firmware version of the smart relay must be V3 1 or above Modem communication interface Remote station The Modem communication interface allows messages telephone numbers and calling conditions to be stored When the calling conditions are met the messages as well as any values to be sent are date stamped and stored in the interface The Modem communication interface scales analog values to the physical values degree bar Pascal etc required by the user Modems Either GSM or analog PSTN type Modems can be used on both the Remote station and PC type Receiving devices when the PC is not fitted with an internal Modem GSM modem In order to exploit all the capabilities associated with Modem communication the Modem s must be fitted with DATA type SIM cards VOICE type SIM cards may be used but some functions will not be available See table on page 35 Zelio Logic Alarm alarm management software PC type Receiving device This software makes it possible to E receive classify and export alarm messages E read or remotely force the status of program elements inputs outputs control relays timing or counting values etc E send control instructions RUN STOP setting the time of the smart relay etc E send specific instructions modifying access rights recipients etc 1 Zelio Logic smart relays see pages 8 to 28 The communication interface Zelio Logic SR2 COMO1 comprises 1 Retractable mounti
4. with shielded cable sensor not isolated Control instructions not executed Protection Reverse polarity protection Smart relay type SRe eeceeB SRe eeeeFU Nominal value of inputs Voltage V 24 100 to 240 Current mA 4 4 0 6 Frequency Hz 47 to 63 Input switching limit values At state 1 Voltage V 2 14 2 19 Current mA a2 gt 0 17 At state 0 Voltage V lt 5 lt 40 Current mA lt 0 5 Input impedance at state 1 kQ 4 6 350 Configurable response time State Oto 1 50 60 Hz ms 50 State 1 to O 50 60 Hz ms 50 Isolation Between supply and inputs None Between inputs None Protection Reverse polarity protection Control instructions not executed Presentation description Functions Curves References Dimensions schemes pages 8 to 10 pages 11 to 13 pages 18 and 19 pages 20 to 22 pages 23 to 27 16 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Characteristics continued Smart relay type Operating limit values Contact type Thermal current Electrical durability for 500 000 operating cycles Minimum switching capacity Low power switching reliability of contact Maximum operating rate Mechanical life Rated impulse withstand voltage Uimp Response time Built in protection ansistor Smart relay type Operating limit values Load Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays SR2 eee SR3 B101 00e SR3 XT6
5. 2 wire RTU 19 200 bauds even parity address 1 Parameter entry Options Software workshop parameter Numberot wires 2 or 4 entry window Frame format RTU or ASCII Transmission speed 1200 2400 4800 9600 19 200 28 800 38 400 57 600 in bauds Parity None even odd Network address 1 to 247 LADDER programming 7 In LADDER mode the 4 data words 16 bits to be exchanged cannot be accessed by the application Transfers with the master are implicit and are effected in a way that is totally transparent Modbus exchanges Code Number of words Image of smart relay I O Read 4 03 Read Write 4 16 06 or 03 gt Status Read 1 gt 03 Function block diagram FBD programming 2 In FBD mode the 4 input data words 16 bits J1XT1 to J4XT1 and the 4 output data words 01XT1 to O4XT1 can be accessed by the application Dedicated function blocks make it possible to E break down a complete type input 16 bits into 16 separate bit type outputs o example break down a Modbus type input J1XT1 to J4XT1 and copy these status values to discrete outputs E make up a complete type output 16 bits from 16 separate bit type outputs O example transfer the status value of the discrete inputs or the status of a function to a Modbus type output 01XT1 to O4XT1 Modbus exchanges Code Number of words gt Read Write 4 16 06 or 03 cS Read 4 03 Read Write 4 16 06 or 03 gt gt Status Rea
6. This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com DIASED2051002EN US kh er sl oe ee T G
7. com 523083 523086 References SR2 COMO1 Sy SR2 CBLO7 Presentation functions pages 32 to 35 38 Zelio Logic 2 Programmable Smart Relays Modem communication interface Description Supply Reference voltage Communication interface 12 to 24 V SR2 COMO1 including cable SR2 CBLO7 1 Software Description Application Medium Reference Compatibility Zelio Logic Alarm PC CD ROM SR2 SFTO2 Microsoft Windows 98 NT4 2000 and XP Connection accessories Description Application Length Reference Connection SUB D9 SUB D9 1 8 SR1 CBLO3 cables connectors Between modem and PC Specific 0 5 SR2 CBLO7 Zelio SUB D9 2 connector Between communication interface cimo and modem 1 Can only be used with Zelio Soft 2 software version V3 1 or above 2 Spare part cable included with communication interface SR2 COMO1 Setting up Characteristics Dimensions Connections page 36 page 37 page 39 pages 40 and 41 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Weight kg 0 200 Weight kg 0 200 Weight kg 0 110 0 050 Dimensions Zelio Logic 2 Programmable Smart Relays Modem communication interface SR2 COMO1 2 x O4 Dual Dimensions VM inches 59 5 2 34 Presentation functions Setting up Characteristics References Connections pages 32 to 35 page 36 page 37 page 38 pages 40 and
8. pages 11 to 13 pages 14 to 17 pages 18 and 19 pages 20 to 22 26 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Schemes continuea Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays O ectio f sma SRe 0001B SRe eeeiFU SR3 B261B and SR3 B261FU SR2 B121B 24V SR2 6101FU 100 240 V 50 60 Hz N 11 12 13 14 15 16 1617 18 19 IAIBICIDIEIFIG 000000660 00000000000 O eee Bee BR 3 5A 4 e S B r 1 i x 12 240 V Ri or S 50 60 Hz T Ju A NU 12 24 V So l N A 12 240 V See 50 60 Hz 1 1 A quick blow fuse or circuit breaker 2 Fuse or circuit breaker 3 Inductive load 4 Q9 and QA 5A With discrete I O extension module SR3 BeeeB SR3 XTeeeB SR3 BeeeFU SR3 XTeeeFU 00000000 Smart SA I O extension Note QF and QG 5 A for SR3 XT141 8 Presentation description Functions Characteristics Curves References pages 8 to 10 pages 11 to 13 pages 14 to 17 pages 18 and 19 pages 20 to 22 27 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com 000005 Presentation i k PAR Unde ni Ea SR3 MBUO1BD Combination of smart relays with communication and I O extension modules 1 2 109458 jaye aputa F A r Anaig oi Dally E AM T Manu DM EEE 00000 Trata ee ee eee OF 1 Modular smart relay 10 or 26 I O 2 Modbus netw
9. smart relays Zelio Soft 2 programming software Zelio Soft 2 software enables E programming in LADDER language or in function block diagram FBD language see pages 12 and 13 E simulation monitoring and supervision E uploading and downloading of programs m output of personalized files m automatic compiling of programs E on line help Coherence tests and application languages Zelio Soft 2 software monitors applications by means of its coherence test function An indicator turns red at the slightest input error The problem can be located by simply clicking the mouse Zelio Soft 2 software allows switching at any time to any of the 6 languages English French German Spanish Italian Portuguese and editing of the application file in the selected language Inputting messages for display on Zelio Logic 2 programmable smart relays Zelio Soft 2 software allows Text function blocks to be configured which can then be displayed on all smart relays which have a display Program testing 2 test modes are provided m Zelio Soft 2 simulation mode allows a program to be tested without a Zelio Logic 2 programmable smart relay i e enable discrete inputs display the status of outputs vary the voltage of the analog inputs enable the programming buttons simulate the application program in real time or in accelerated time dynamically display in red the various active elements of the program
10. status or the value of a program element to be modified from the Receiving device The operator initiates the call using the Receiving device PC or GSM telephone It is then possible to force the status of the discrete and or analog value of each of the 28 messages Remote dialogue using Zelio Soft 2 This function enables use of the Transfer Monitoring and Diagnostics modes available in Zelio Soft 2 via the Transmission network instead of the physical link cable SR2 USBO1 or SR2 CBLO1 between the product Remote station and the PC Receiving device It is then possible to m transfer a program created on a PC station to the Remote station m transfer a program installed on the Remote station to the PC station m modify from the PC the receiving device telephone numbers e mail addresses and the alert sending conditions E update the firmware in the smart relay and the Modem communication interface E display and modify discrete and analog values E perform diagnostics on the smart relay and on the Modem communication interface 1 Requires the use ofa GSM Modem on the Remote station side 2 Verify with the Transmission network operator that the e mail by SMS service is available Presentation Characteristics References Dimensions Connections pages 32 and 33 page 37 page 38 page 39 pages 40 and 41 34 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Functions continued Ze
11. 00 ABL 7RM1202 ABL 7RM2401 ABL 7RM24025 See page 45 SR1 CBLO3 SR2 MEMO SR2 MEMOZ SR2 A101BD SR2 A101FU SR2 A201BD SR2 A201FU SR2 B121B SR2 B121BD SR2 B121FU SR2 B121JD SR2 B122BD SR2 B201B SR2 B201BD SR2 B201FU SR2 B201JD SR2 B202BD SR2 CBLO1 SR2 CBLO6 SR2 CBLO7 SR2 COMO1 SR2 D101BD SR2 D101FU SR2 D201BD SR2 D201FU SR2 E121B SR2 E121BD SR2 E121FU SR2 E201B SR2 E201BD SR2 E201FU SR2 MANO1DE SR2 MANO1EN SR2 MANO1ES SR2 MANO1FR SR2 MANO1IT SR2 MANO1P0 SR2 PACK2BD SR2 PACK2FU SR2 PACKBD SR2 PACKFU SR2 SFTO1 SR2 SFTO2 SR2 USBO1 SR3 MBU01BD SR3 B101B SR3 B101BD SR3 B101FU SR3 B102BD SR3 B261B SR3 B261BD SR3 B261FU SR3 B261JD 1 SR3 B262BD SR3 PACK2BD SR3 PACK2FU SR3 PACKBD SR3 PACKFU SR3 XT101B SR3 XT101BD SR3 XT101FU 46 22 22 31 45 45 SR3 XT101JD SR3 XT141B SR3 XT141BD SR3 XT141FU SR3 XT141JD SR3 XT43BD 1 5 SR3 XT61B SR3 XT61BD SR3 XT61FU SR3 XT61JD VW3 A8 306TFO3 VW3 A8 306TF10 VW3 A8306R03 VW3 A8306R10 VW3 A8306R30 Zelio Logic 2 Programmable Smart Relays This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Find out more about Zelio Logic for your applications with the discovery packs m pack contains 1 product 1 connecting cable and 1 software CD m available in 24 Vdc or 100 240Vac Sch
12. 00 V single phase 240 V single phase Type of protection Thermal magnetic Fuse Thermal magnetic Fuse gG circuit breaker gG circuit breaker GB2 UL IEC C60N IEC GB2 UL IEC C60N IEC C60N UL C60N UL ABL 7RM1202 GB2 ee06 24580 1A GB2 ee05 24494 1A 24516 24516 ABL 7RM2401 GB2 ee06 24580 1A GB2 ee06 24580 1A 24516 24516 ABL 7RM24025 GB2 ee08 24582 3A GB2 ee08 24582 3A 24518 24518 GB2 CBee GB2 CDee GB2 DBee GB2 CSee 2 9 Pall 7 9 y oo a E lt Presentation References Dimensions Schemes page 42 page 45 page 45 page 45 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com References Power supplies dimensions Power supplies for d c control circuits Phaseo modular regulated power supplies Mains input voltage Output Nominal Nominal Auto protect Reference Weight RE 47 to 63 Hz voltage power current reset es V W A kg i 100 to 240 12 22 1 9 Auto ABL 7RM1202 0 180 Single phase wide kenge 24 30 1 3 Auto ABL 7RM2401 0 182 60 2 5 Auto ABL 7RM24025 0 255 ABL 7RM 1 For additional products please contact your local Schneider Electric representative Power supply ABL 7RMeeee Dual Dimensions VM I inches 100 3 93 0 3 54 Presentation Characteristics page 42 page 43 and 44 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Product Reference Index 170 XTS 041
13. 10e SR3 XT10100 V 5 10 150 24 to 250 NO 8 outputs 8 A 2 outputs 5 A SR3 B26100 SR3 XT14100 4 outputs 8 A 2 outputs 5 A Utilization DC 12 category A a DC 13 V 24 L R 10 ms A 0 6 AC 12 230 A 15 AC 15 V 230 A 0 9 At minimum voltage of 12 V mA 10 12V 10mA No load 10 At le operational current me 0 1 In millions of operating cycles ER 10 Conforming to IEC EN 60947 1 4 and IEC EN 60664 1 Trip 10 Reset E 5 Against short circuits EE None Against overvoltage None and overload SRe Bee2BD 19 2 to 30 Nominal voltage Nominal current Maximum current a CE Drop out voltage At state 1 V lt 2forl 0 5A Response time Trip ms lt 1 Reset ms lt i Built in protection Against overload and short circuits Yes Against overvoltage 7 Yes Against inversions of power supply FE Yes 1 If there is no volt free contact between the smart relay output and the load Analog outputs Output range V O to 10 Type of load Resistive Maximum load 10 Value of LSB 10 Conversion Resolution 10 bits Conversion time Smart relay cycle time Precision at 25 C 77 F 1 of the full scale value at 55 C 131 F E 1 of the full scale value Repeat accuracy at 55 C 131 F lt 1 Isolation Between analog channel E None and supply Cabling distance m ft 10 32 81 maximum with shielded cable Built in protection Reverse polarity protection Ye
14. 2 kV IEC EN 61000 4 6 10 V Mains interference IEC EN 61000 4 11 Presentation References Dimensions Schemes page 42 page 45 page 45 page 45 43 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Characteristics continued Power supplies selection Power supplies for d c control circuits Phaseo modular regulated power supplies Exceeding the nominal power only applicable to ABL 7RM1202 and ABL 7RM2401 The ambient temperature is a determining factor which limits the power that an electronic power supply can deliver continuously If the temperature around the electronic components is too high their life will be significantly reduced Conversely a power supply can deliver more than its nominal power if the ambient temperature remains well below the nominal operating temperature The maximum ambient temperature for Phaseo power supplies is 55 C 131 F Below this temperature uprating is possible up to 110 of the nominal power The graph below shows the power in relation to the nominal power that the power supply can deliver continuously according to the ambient temperature Power supply ABL 7RM24025 cannot exceed the nominal power of 60 W P Pn T T T t T T 0 32 40 104 55 131 Maximum operating temperature C F 1 ABL 7RM24025 2 ABL 7RM1202 and ABL 7RM2401 Upstream protection of power supplies Type of mains supply 1
15. 41 39 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Connections Zelio Logic 2 Programmable Smart Relays Modem communication interface SRe BeeiJD SRe BeeeBD et SR2 EoooBD a Input connections 1 DI rr OO 00000000 OO 12 24VDC ee o DO recon 2 _ COM Z ae 3 COM M l 4 STATUS Gil Iii WS ae ee MU re as as EEN Q1 Q2 Q3 Q4 4 tet Output connections 1 1 A quick blow fuse 2 Cable included with Modem communication interface SR2 COMO1 3 Cable for connection to the Transmission network included with analog PSTN modem 4 Antenna and cable included with GSM Modem SRe Beo1B SRe BeeeFU SR2 EcoeeeB et SR2 EoooFU T 24 Vor A 100 to 240 V 1 Input connections 1 1112131415 IG IBIC OO 00000000 12 24VDC E SR2 COMO1 COM Z REA ees STATUS mm _ D C oO Em P O OO 00 00 OO Analog PSTN or N So CE Co a GSM modem Lo fo Output connections 1 1 A quick blow fuse 2 Cable included with Modem communication interface SR2 COMO1 3 Cable for connection to the Transmission network included with analog PSTN modem 4 Antenna and cable included with GSM Modem Presentation functions Setting up Characteristics References Dimensions pages 32 to 35 page 36 page 37 page 38 page 39 40 This document provi
16. 9600 2100 on 5 5 V Current peak on power up Power dissipated 15 Micro breaks Permissible duration 1 ms repeated 20 times To be provided externally A 1 A fuse Supplied with 2 5 A fuse Type of connector ie Specific to Zelio Type of link Specific Zelio communication protocol Compatibility Only with Zelio Logic smart relays SRe Beeeee and SR2 Eeeeee version V3 1 and above Isolation of From the Com M connector By 1780 V opto coupler Com Z connector From the supply terminals By 1780 V opto coupler O Specific to Zelio RS 232 serial included with the communication interface Type of connector Type of link with SR2 CBLO7 Compatibility Analog PSTN modem AT commands GSM Modem AT commands Isolation of From the Modem By the cable SR2 CBLO7 Com M connector From the supply terminals By the cable SR2 CBLO7 E l IT Data saved Messages Up to 28 messages by the interface Telephone e mail details 1 to 10 recipients telephone numbers and or e mail addresses per message and recipient profiles Date and time Dating of messages to be sent Discrete and digital values Backup of values when the message activation condition is triggered Backup of data to be sent Flash memory Presentation Setting up References Dimensions Connections pages 32 and 33 page 36 page 38 page 39 pages 40 and 41 37 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp
17. Add and or subtract function COMPARE COMPARE Comparison of 2 analog values using the operands gt lt X 2 SPEED COUNT SPEED COUNT Fast counting up to 1 kHz MUL DIV Ea i Multiply and or divide function STATUS STATUS Access to smart relay status COM Sending of messages with communication interface see page 32 x RESET INIT INIT STEP STEP RESET IMIT IMIT STEF STEF Reinitializable step Initial step SFC step DIV OR 2 l CONV OR 2 l DIV AND 2 PT COMIDO 2 DIU AMO 2 DIW OF E Divergence to OR Convergence to OR Divergence to AND Ti CONV AND 2 FF COMI ANDE Convergence to AND Logic functions AND AHD AND function S300 NOR HOR NOT OR function 1 Function Block Diagram 2 Sequential Function Chart OR OR function Dei or HOR Exclusive OR function This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com NAND HAHO NOT AND function NOT HOT NOT function 13 Characteristics neral envir Product certifications Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays for communication Modem UL CSA GL pending C Tick Conformity with the low voltage directive Conforming to 73 23 EEC EN IEC 61131 2 open equipment Conformity with the EMC directive Degree of protection Conforming to 89 336 EEC Conforming to IEC EN 60529 EN IEC 61131 2 Zone B EN IE
18. C 61000 6 2 EN IEC 61000 6 3 7 and EN IEC 61000 6 4 Overvoltage category Degree of pollution Conforming to IEC EN 60664 1 IP 20 3 Conforming to IEC EN 61131 2 E 2 Ambient air temperature Operation 20 to 55 4 to 131 40 104 in an enclosure conforming to IEC 60068 2 1 around the device and IEC 60068 2 2 Storage C F 40 to 70 40 to 158 Maximum relative humidity 95 without condensation or dripping water Maximum operating altitude Operation m ft 2000 6562 Transport 3048 10 000 Mechanical resistance Resistance to electrostatic discharge Resistance to HF interference immunity Conducted and radiated emissions Screw terminals connection capacity Tightening using 3 5 screwdriver d Y e m e y a E P a g Te Number of control scheme lines Immunity to vibration IEC EN 60068 2 6 test Fc Immunity to mechanical shock ae IEC EN 60068 2 27 test Ea Immunity to electrostatic discharge Immunity to electromagnetic radiated fields Immunity to fast transients in bursts Immunity to shock waves IEC EN 61000 4 2 level 3 IEC EN 61000 4 3 level 3 IEC EN 61000 4 4 level 3 IEC EN 61000 4 5 Radio frequency in common mode IEC EN 61000 4 6 level 3 Voltage dips and breaks Immunity to damped oscillation waves Conforming to EN 55022 11 Group 1 Flexible cable with cable end Semi solid cable Solid cable Tightening
19. CK2BD 0 850 a connecting cable and Zelio Soft 2 programming software supplied on CD ROM Supply 100 to 240 V 12 An SR2 B121FU compact smart relay with display SR2 PACKFU 0 700 a connecting cable and Zelio Soft 2 programming software supplied on CD Rom 20 An SR2 B201FU compact smart relay with display SR2 PACK2FU 0 850 a connecting cable and Zelio Soft 2 programming software supplied on CD Rom 1 Programming on smart relay in LADDER language only Characteristics Curves Dimensions schemes pages 14 to 17 pages 18 and 19 pages 23 to 27 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com References 109442 eo 909990 a aru 7 a F Ee aoo Eu ar Pia A eis 7 ey a IL ti Wet ri n a SR3 B101BD 2990 Inpur ami Kib 109363 ta IH IL aa DE Qui Relay BA ya SR3 XT61BD em 7 J P aii niiit 109369 inpute 1H IR Pari EA E Relay 8A and OF 0G Relay yy a SE SR3 XT141BD a 534945 paj KTS SR3 XT43BD Zelio Logic 2 Programmable Smart Relays Modular smart relays Number Discrete Including Relay Transistor Clock Reference Weight of inputs 0 10 V outputs outputs 1 0 analog inputs kg Supply 12 V 26 16 6 10 0 Yes SR3 B261JD 7 0 400 Supply 24 V 10 6 4 4 0 Yes SR3 B101BD 0 250 6 4 0 4 Yes SR3 B102BD 0 220 26 16 6 10 2 0 Yes S
20. Catalog January a brand of Schneider Electric Zelio Logic 2 Programmable Smart Relays a ia ic O E Er pene 8 222 Telemecanique This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Modbus Telemecanique Zelio Twido and Phaseo are registered trademarks of Schneider Electric Other trademarks used herein are the property of their respec tive owners This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Contents Zelio Logic 2 Programmable Smart Relays selechon guide ernie a ne es ee ee eas aie EA a etn ee pages 4to7 Compact and modular smart relays m Presentation T me a e CR CR RR ee pages 8 and 9 E Descipion ss e o DOE US E rare ES A SR page 10 EE RUnelions a ui E Cn eyo pages 11 to 13 MChaALACleISUCS e aa ee eee eee pages 14 to 17 BG UNES TEA cer eae ai O ee ee a bai ORME A pages 18 and 19 ai Relerehices se cm eee ene pages 20 to 22 E Dimensions mounting a REA A ees page 23 EiSchemes a er TE ae cae a CT pages 24 to 27 Modbus network slave communication module aEPresentalions e RE CRE page 28 E Description characteristics sn o an RD da DL a page 29 EERUACIONS Mite ee nO te ee ree Tn a Rat ae Zs page 30 m References dimensions mounting 222200c seen ee page 31 Modem communication interface m Presentation description 0 cece ee ees pages 32 and 33 BM RUMCHONS zee oe acl ieee rar
21. E independently using the buttons on the smart relay m ona PC using Zelio Soft 2 software see page 14102 16 When using a PC programming can be performed either in LADDER language or in function block diagram FBD language see pages 12 and 13 Connection example 1 Modbus Master programmable controller for example Twido PLC 2 Zelio Logic 2 programmable smart relay 3 Modbus network slave communication module 4 T junction 5 Line end adaptors Function description m The Modbus network slave communication module is connected to a 2 wire or 4 wire Modbus network E The maximum length of the network is 1000 m 3281 ft 9600 bauds max AWG 26 E A maximum of 32 slaves can be connected to the Modbus network or a maximum of 247 slaves with repeaters E Line end adaptors must be fitted to both ends of the line 1 nF 10 V 120 Q 0 25 W in series E The line must be polarized 470 Q 0 25 W resistors 1 m The connection cable and its RJ45 male connectors must be shielded E The COMMON signal must be connected directly to the protective ground at one point on the bus 1 The polarization resistors must be managed by the master References Dimensions page 31 page 31 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Description characteristics Zelio Logic 2 Programmable Smart Relays Modbus network slave communic
22. N 61000 4 2 level 3 electrostatic discharge Resistance to HF interference immunity Conducted and radiated emissions Presentation page 28 electrostatic discharge Immunity to electromagnetic radiated fields Immunity to fast transients in bursts Immunity to shock waves Radio frequency in common mode Voltage dips and breaks Immunity to damped oscillation waves IEC EN 61000 4 3 level 3 IEC EN 61000 4 4 level 3 IEC EN 61000 4 5 IEC EN 61000 4 6 level 3 IEC EN 61000 4 11 IEC EN 61000 4 12 Conforming to EN 55022 11 Class B Group 1 Functions References Dimensions page 30 page 31 page 31 29 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com 510391 Functions Zelio Logic 2 Programmable Smart Relays Modbus network slave communication module Parameters can be entered either using Zelio Soft 2 software or directly using the buttons on the Zelio Logic 2 programmable smart relay SS l When the RUN instruction is given the Zelio Logic 2 programmable smart relay TT initializes the Modbus network slave communication module in a configuration previously defined in the basic program The Modbus network slave communication module has 4 parameters E number of UART wires and format of the frames on the Modbus network E transmission speed E parity E network address of the Modbus module The default parameter settings are as follows
23. O1 0 100 the smart relay length 3 m 9 8 ft Interface For USB port to be used with cable SR2 CBLO6 0 350 SR2 CBLO1 length 1 8 m 5 9 ft Description Application Reference Weight kg EEPROM For software incorporated inthe SR2MEMO1 0 010 memory cartridge smart relay version lt 2 4 no firmware of any version For firmware software SR2 MEMO2 0 010 incorporated in the smart relay version 2 3 0 Description Supply Reference Weight Modem 12 to 24 V communication interface See page 38 Input voltage Nominal Reference Weight output voltage kg 100 to 240 V 47 to 63 Hz 12 V or 24 V See page 45 Description Mounting Application Reference Weight capacity kg Dust and 1 or2 SR2 modules For mounting 14210 0 350 damp proof with 10 or 12 I O through a door enclosure or with split 1 SR2 module blanking plate with 20 I O arrangement or fitted with IP 55 1SR3 module dust and with 10 I O damp proof 1 I O extension module window with 6 10 or 14 I O hinged flap or 1 SR3 module with 26 I O 1 I O extension module 6 I O Mounting For mounting 14211 0 210 bracket and enclosure 14210 symmetrical through a door panel mounting rail Description Application Language Reference Weight kg User s manual For direct programming English SR2 MANO1EN 0 100 on the smart relay French SR2 MANO1FR 0 100 German SR2 MANO1DE 0 100 Spanish SR2 MANO1ES 0 100 Italian SR2 MANO1IT 0 100 Portu
24. R3 B261BD 0 400 16 6 0 10 Yes SR3 B262BD 0 300 Supply 24 V 10 6 0 4 0 Yes SR3 B101B 0 250 26 16 0 10 2 0 Yes SR3 B261B 0 400 Supply 100 240 V 10 6 0 4 0 Yes SR3 B101FU 0 250 26 16 0 10 2 0 Yes SR3 B261FU 0 400 Discrete I O extension modules 9 Number Discrete inputs Relay outputs Reference Weight of I O kg Supply 12 V for smart relay SR3 B261JD 6 4 2 SR3 XT61JD 0 125 10 6 4 SR3 XT101JD 0 200 14 8 6 SR3 XT141JD 0 220 Supply 24 V for smart relays SR3 BeeeBD 6 4 2 SR3 XT61BD 0 125 10 6 4 SR3 XT101BD 0 200 14 8 6 SR3 XT141BD 0 220 Supply 24 V for smart relays SR3 BeeeB 6 4 2 SR3 XT61B 0 125 10 6 4 SR3 XT101B 0 200 14 8 6 SR3 XT141B 0 220 Supply 100 240 V for smart relays SR3 BeeeFU 6 4 2 SR3 XT61FU 0 125 10 6 4 SR3 XT101FU 0 200 14 8 6 SR3 XT141FU 0 220 Supply 24 V Number Number Including Including Including Output Reference Weight of I O of inputs 0 10V 0 20mA Pt100 0 10V kg 4 2 4 2 max 2 max 1 max 2 SR3 XT43BD 7 5 0 110 For Supply Reference Weight use on voltage kg Modbus network slave 24V See page 31 0 300 Number Pack contents Reference Weight of I O kg Supply 24 V 10 An SR3 B101BD modular smart relay a connecting SR3 PACKBD 0 700 cable and Zelio Soft 2 programming software supplied on CD ROM 26 An SR3 B261BD modular smart relay a connecting SR3 PACK2BD 0 850 cable and Zelio Soft 2 programming software supplied on CD ROM Supply 100 to 240 V 10 An SR3 B101FU mod
25. are given on selecting the upstream protection devices which are often used with them and thus a comprehensive solution is provided that can be used in total safety These switch mode power supplies are totally electronic and regulated The use of electronics makes it possible to significantly improve the performance of these power supplies which offer E very compact size integrated overload short circuit overvoltage and undervoltage protection a very wide range of permissible input voltages without any adjustment a high degree of output voltage stability good performance considerably reduced weight a modular format allowing integration into panels Phaseo power supplies deliver a voltage which is precise to 3 whatever the load and whatever the type of mains supply within a range of 85 to 264 V for single phase Conforming to IEC standards and UL and CSA certified they are suitable for universal use The inclusion of overload and short circuit protection makes downstream protection unnecessary if discrimination is not required All the products are fitted with an output voltage adjustment potentiometer in order to be able to compensate for any line voltage drops in installations with long cable runs These power supplies are designed for direct mounting on 35 mm 1 38 and 75 mm 2 95 rails or on a mounting plate using the retractable mounting feet These power supplies are single phase and three references are avai
26. ation module The Modbus network slave communication module SR3 MBUO1BD comprises Two retractable mounting feet A Modbus network connection RJ45 shielded female connector A communication LED COM A Power on LED PWR A screw terminal block for the protective ground connection A spring clip for mounting on a 35 mm 1 38 mounting rail Two locating pegs Two locating pegs for clip on mounting ONO BON Product certifications UL CSA GL pending C TICK Conformity with the low voltage directive EN IEC 61131 2 open equipment Conforming to 73 23 EEC Conformity with the EMC directive Conforming to 89 336 EEC EN IEC 61131 2 Zone B EN IEC 61000 6 2 EN IEC 61000 6 3 and EN IEC 61000 6 4 Degree of protection Conforming to IP 20 IEC EN 60529 Overvoltage category Conforming to 3 IEC EN 60664 1 Degree of pollution Conforming to 2 IEC EN 61131 2 Ambient air temperature Operation C F 20 to 55 4 to 131 40 104 in an enclosure conforming to IEC 60068 2 1 and IEC around the device 60068 2 2 Storage C F 40 to 70 40 to 158 Maximum relative humidity 95 without condensation or dripping water Maximum Operation m ft 2000 6562 operating altitude Transport m ft 3048 10 000 Mechanical resistance Immunity to vibration IEC EN 60068 2 6 test Fc Immunity to IEC EN 60068 2 27 test Ea mechanical shock Resistance to Immunity to IEC E
27. be placed freely within the graphic m Control scheme input modes Zelio input mode enables users who have directly programmed the Zelio Logic 2 programmable smart relay to find the same user interface even when using the software for the first time Free input mode which is more intuitive is very user friendly and incorporates many additional features With LADDER programming language two alternative types of symbol can be used o LADDER symbols O electrical symbols Free input mode also allows the creation of mnemonics and notes associated with each line of the program Instant switching from one input mode to the other is possible at any time by simply clicking the mouse Up to 120 control scheme lines can be programmed with 5 contacts and 1 coil per program line E Functions O 16 time delay function blocks parameters of 11 different types can be set for each of these 1 10 second to 9999 hours 16 up down counter function blocks from 0 to 32767 1 fast counter 1 kHz 16 Text function blocks 16 analog comparator function blocks 8 clock function blocks each with 4 channels 28 control relays 8 counter comparators automatic Summer Winter time switching variety of functions coil latching Set Reset impulse relay contactor LCD screen with programmable backlighting 28 message blocks with communication interface see page 32 Oooo eaooaoeo oo oe LADDER language Notes corr
28. ber Discrete Including Relay Transistor Clock Reference Weight of inputs 0 10 V analog outputs outputs 1 0 inputs kg Supply 12 V 12 8 4 4 0 Yes SR2 B121JD 0 250 20 12 6 8 0 Yes SR2 B201JD 0 380 Supply 24 V 10 6 0 4 0 No SR2 A101BD 7 0 250 12 8 4 4 0 Yes SR2 B121BD 0 250 8 4 0 4 Yes SR2 B122BD 0 220 20 12 2 8 0 No SR2 A201BD 7 0 380 12 6 8 0 Yes SR2 B201BD 0 380 12 6 0 8 Yes SR2 B202BD 0 280 Supply 24 V 12 8 0 4 0 Yes SR2 B121B 0 250 20 12 0 8 0 Yes SR2 B201B 0 380 Supply 100 to 240 V 10 6 0 4 0 No SR2 A101FU 7 0 250 12 8 0 4 0 Yes SR2 B121FU 0 250 20 12 0 8 0 No SR2 A201FU 7 0 380 12 0 8 0 Yes SR2 B201FU 0 380 Number Discrete Including Relay Transistor Clock Reference Weight of inputs 0 10 V outputs outputs 1 0 analog inputs kg Supply 24 V 10 6 0 4 0 No SR2 D101BD 7 0 220 12 8 4 4 0 Yes SR2 E121BD 0 220 20 12 2 8 0 No SR2 D201BD 7 0 350 12 6 8 0 Yes SR2 E201BD 0 350 Supply 24 V 12 8 0 4 0 Yes SR2 E121B 0 220 20 12 0 8 0 Yes SR2 E201B 0 350 Supply 100 to 240 V 10 6 0 4 0 No SR2 D101FU 7 0 220 12 8 0 4 0 Yes SR2 E121FU 0 220 20 12 0 8 0 No SR2 D201FU 7 0 350 12 0 8 0 Yes SR2 E201FU 0 350 Number Pack contents Reference Weight of I O kg Supply 24 V 12 An SR2 B121BD compact smart relay with display SR2 PACKBD 0 700 a connecting cable and Zelio Soft 2 programming software supplied on CD ROM 20 An SR2 B201BD compact smart relay with display SR2 PA
29. cal resistance Vibration resistance Conforming to IEC EN 60068 2 6 test Fc 1mm 0 04 2 to 13 2 Hz 0 15 mm 0 01 13 2 to 57 6 Hz 2 gn 57 6 to 150 Hz Shock resistance Conforming to IEC EN 60068 2 27 test Ea Resistance to electrostatic discharge Conforming to IEC EN 61000 4 2 level 3 8 kV air 6 kV at the contacts Resistance to Immunity to radiated Conforming to IEC EN 61000 4 3 level 3 10 V per metre HF interference electromagnetic fields Immunity to fast transients in bursts Immunity to shock waves Conforming to IEC EN 61000 4 4 level 3 Conforming to IEC EN 61000 4 5 on common mode supply 1 kV serial mode supply 0 5 kV Immunity to damped oscillation waves Conforming to IEC EN 61000 4 12 on 1 kV supply 30 seconds 4 periods Conducted interference IEC EN 61000 4 6 10 kHz to 80 MHz level 3 10 V induced by radiated fields Connection to Flexible cable 1 conductor 0 14 to 1 5 AWG26 to AWG16 cable screw terminals with cable end 2 conductors 0 14 to 0 75 AWG26 to AWG18 cable tightened using Semi solid cable 1 conductor 0 14 to 2 5 AWG26 to AWG14 cable 3 5 screwdriver Solid cable 1 conductor 0 14 to 2 5 AWG26 to AWG14 cable 2 conductors 0 14 to 1 5 AWG26 to AWG16 cable Tightening torque Nm 0 6 y ST i C Interface type SR2 COM01 SR2 MODO1 SR2 MODO2 Nominal voltage 12 to 24 Voltage limits 10 to 28 8 10 to 30 0 0 10 32 Nominal current 12V 125 24 V 30 70 60 550
30. d 1 gt 03 1 See page 12 2 See page 13 Presentation Characteristics References Dimensions page 28 page 29 page 31 page 31 30 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com 000007 References Zelio Logic 2 dimensions Programmable Smart Relays mounting Modbus network slave communication module Modbus network slave communication module pm For Reference Weight use with kg hia Modular smart relays SR3 MBU01BD 0 110 SR3 Bee1BD and SR3 Bee2BD 7 Connection accessories Description Reference Weight I kg T junctions Complete with 0 3 m 0 98 VW3 A8 306TF03 A ft cable 7 Complete with 1 m cable VW3 A8 306TF10 q SR3 MBU01BD Without cable 170 XTS 04100 Cables with Length 0 3 m 0 98 ft VW3 A8306R03 2 x RJ45 connectors Length 1 m 3 28 ft VW3 A8306R10 Length 3 m 9 8 ft VW3 A8306R30 1 Compatible with SR3 Bee2BD featuring hardware version H1 0 01 available since June 2005 Side view Rail mounting Screw mounting Dual Dimensions aches I 19 d0 MIO NA S B l fe Ble 00 lio o O IN j 19 d0 MIO EN A O ARE 1 73 0 59 Presentation Characteristics Functions page 28 page 29 page 30 31 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com 523083 Presentation SR2 COMO Functions setting up pages 34 to 35 32 C
31. d values 2 2 k2 0 5 W 10 k2 max 4 Shielded cables maximum length 10 m 32 81 ft 5 Analog inputs according to smart relay see table below Smart relays Analog inputs SR2 e12eeD IB to IE SR2 A201BD IB and IC SR2 D201BD IB and IC SR2 B2000D IB to IG SR2 E201BD IB to IG SR3 B10eBD IB to IE SR3 B2600D IB to IG SR3 BeeeJD SR3 XTeeeJD SR3 BeeeBD SR3 XTeeeBD Note QF and QG 5 A for SR3 XT1i416e 1 1 A quick blow fuse or circuit breaker 2 Ca Analog sensor Ta Analog transmitter 3 Recommended values 2 2 k2 0 5 W 10 k2 max 4 Shielded cables maximum length 10 m 32 81 ft Presentation description Functions Characteristics pages 8 to 10 pages 11 to 13 pages 14 to 17 Curves pages 18 and 19 References pages 20 to 22 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Schemes continued Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays SR3 BeeeBD SR3 XT43BD Connection alternatives 0 10V 0 20mA Pt100 2 0 0 1 0 0 2 0 1 0 1 0 1 1 Application example with 1 x 0 10 V input and 1 x Pt100 input O QB OV QC 1 Shielded cables maximum length 10 m 32 81 ft Application example with 1 x O 20 mA input and 1 x 0 10 V input 1 Shielded cables maximum length 10 m 32 81 ft Presentation description Functions Characteristics Curves References pages 8 to 10
32. ded by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Connections Zelio Logic 2 Programmable Smart Relays Modem communication interface For PCs without an internal Modem Analog PSTN Modem SR1 CBLOS 2 Analog PSTN Modem 1 Cable for connection to the Transmission network included with analog PSTN modem 2 To be ordered separately GSM Modem 12t024V Antenna GSM Modem 1 Cable included with the Modem length 50 cm 19 7 The cable length can be increased using SR1 CBLOS 1 8 m 5 9 ft 2 Antenna and cable included with GSM Modem Presentation functions Setting up Characteristics References Dimensions pages 32 to 35 page 36 page 37 page 38 page 39 41 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Presentation Power supplies Power supplies for d c control circuits Phaseo modular regulated power supplies The ABL 7RM range of power supplies is designed to provide the d c voltage necessary for the control circuits of automation system equipment Comprising 3 products this range meets the needs encountered in industrial commercial and residential applications These single phase modular electronic switch mode power supplies provide a quality of output current which is suitable for the loads supplied and compatible with the Zelio Logic 2 programmable smart relays range making them ideal partners Clear guidelines
33. een RR ein ict ae pages 34 and 35 MB S CUA SU pone ecg ees ac MO neo E ey ote tole eee eee page 36 mM Chalactenistics ca cro rier re te ae eae page 37 BE FCTCLCINGSSi Rm ms O ora SR DO en en meee nee Sonor cg ae page 38 BM DIMCMSIOMS ac cd RR en ae page 39 MB COnneCHONS scien ere ae ee cee ee een pages 40 and 41 Power supplies E Rresentanonn a cce Mes E my crevices De ad NR eer cei weat page 42 m Characteristics Selection ssa assina arara arara sda pages 43 and 44 m References dimensions mounting 00 cee eee eee ees page 45 G3 Telemecanique 3 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays ke CER LS qo antene TE ii a tine q 12V 24V nn 24V 12 and 20 10 12 and 20 12 and 20 8 4 and 12 6 6 0 8 4 12 2 and 12 6 8 0 and 12 0 100 240 V 10 12 and 20 6 0 8 0 and 12 0 20 20 20 1 FBD Function Block Diagram 4 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com 4 0 and 8 0 4 0 0 4 8 0 and 0 8 4 0 and 8 0 SR2 Beocoo FBD or LADDER SR2 Acecocoecee SR2 Acecococee LADDER only LADDER only SR2 Eocscocoe FBD or LADDER SR2 Deoooe SR2 Deecoo LADDER only LADDER only SR2 COM01 SR2 COMO1 SR2 COMO1 SR2 COMO1 for SR2 Band SR2 E for SR2 B a
34. esponds to the real state of the contact connected to the input of the smart relay i corresponds to the inverse state of the contact connected to the or input of the smart relay y i Standard coil az The coil is energized when the contacts to which it is connected are closed lt gt Latch coil Set The coil is energized when the contacts to which it is connected are closed EO lt It remains tripped when the contacts re open N lt Unlatch coil The coil is de energized when the contacts to which it is Reset R connected are closed It remains inactive when the contacts re open N lt Presentation description Characteristics Curves References Dimensions schemes pages 8 to 10 12 pages 14 to 17 pages 18 and 19 pages 20 to 22 pages 23 to 27 Telemecanique This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Functions continued T nci Definition Pre programmed functions Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays Zelio Soft 2 programming software FBD language allows graphical programming based on the use of predefined function blocks This language provides the use of 24 pre programmed functions for counting time delay timing definition of switching threshold example temperature regulation generation of impulses time programming multiplexing display etc Zel
35. grammable Smart Relays Compact and modular smart relays a c loads AC 12 1 3 0 2 5 24 V 2 0 48 V 1 5 110 V 10 230 V Millions of operating cycles 0 5 og 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 Current A AC 14 2 2 5 2 0 110 V i 230 V 1 0 48 V 24 V 0 5 Millions of operating cycles oe 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 Current A AC 15 3 Millions of operating cycles O ol 0 0 Current A 1 AC 12 switching resistive loads and photo coupler isolated solid state loads cos gt 0 9 2 AC 14 switching small electromagnetic loads lt 72 VA make cos 0 3 break cos 0 3 3 AC 15 switching electromagnetic loads gt 72 VA make cos 0 7 break cos 0 4 Presentation description Functions Characteristics References Dimensions schemes pages 8 to 10 pages 11 to 13 pages 14 to 17 pages 20 to 22 pages 23 to 27 19 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com 109440 109442 510345 References oe 90999999099209 iiag ar 04 SR2 A201BD a acid painy BA qi p SR2 E121BD SR2 PACK eeo0 Presentation description Functions pages 8 to 10 pages 11 to 13 20 Zelio Logic 2 Programmable Smart Relays Compact smart relays Num
36. guese SR2 MANO1P0 0 100 1 CD ROM comprising Zelio Soft 2 software an application library a self training manual installation instructions and a user s manual 2 Program loading using memory cartridge SR2 MEMO2 is incompatible with Modem communication interface SR2 COMO1 3 See pages 32 to 41 4 Products marketed under the Merlin Gerin brand Dimensions schemes pages 23 to 27 Characteristics Curves pages 14 to 17 pages 18 and 19 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Dimensions Zelio Logic 2 mounting Programmable Smart Relays Compact and modular smart relays SRe e10ee0e 10 I O SR2 012000 12 1 0 Mounting on 35 mm 7 rail Screw mounting retractable lugs Dual Dimensions VM inches SR2 e200eee 20 I O SR3 B26eee 26 I O Mounting on 35 mm 1_ rail SR3 XT43BD 4 I O SR3 XT61 e 6 I O SR3 XT101ee and SR3 XT141 ee 10 and 14 I O Mounting on 35 mm Trail Screw mounting retractable lugs SR3 a G XT43BD 35 5 1 39 5 0 98 XT6100 35 5 1 39 25 0 98 XT10100 72 2 83 60 2 36 XT14100 72 2 83 O 2 36 14210 14211 Cut out a 104 5 4 11 104 5 4 11 101 5 3 99 101 5 3 99 55 2 16 55 2 16 105 234 96 l l 57 57 io o a 2 24 Presentation description Functions Characteris
37. haracteristics page 37 Zelio Logic 2 Programmable Smart Relays Modem communication interface The communication products in the Zelio Logic 2 range are primarily designed for monitoring or remote control of machines or installations which operate without personnel Examples E monitoring of lift pumps livestock premises ventilation food level etc refrigeration units car washes E alert in the event of failure of industrial or domestic heating boilers E remote control of lighting car parks warehouses E remote control and monitoring of escalators in large stores in the transport sector E refuse compact or full alert The communication range comprises E a communication interface connected between a smart relay and a Modem m GSM 1 or analog PSTN 2 Modems m Zelio Logic Alarm software Communication interface A E GSM a 5 E m vf Analog 8 or a d he x PSTN o Analog PSTN or 3 Modem GSM modem a OO 00000 Zelio Logic 2 m programmable smart relay q J J o 1 mo 9 The system comprises m a Remote station machine or installation to be monitored 1 control is achieved using a smart relay with clock from the Zelio Logic SRe Beeeee or SR2 Ee eeee 2 range via its inputs and outputs The smart relay is connected via a communication interface 3 to a GSM 7 type Modem 4 or when a telephone line is available nearby to an ana
38. ied with 24 V via the smart relay at the same voltage 1 LCD Liquid Crystal Display Curves References Dimensions schemes pages 18 and 19 pages 20 to 22 pages 23 to 27 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com 534941 534944 Presentation continued VEMORT ig SR2 MEMO1 SR2 MEMOZ SR2 COMO1 Communication interface Functions pages 11 to 13 Characteristics pages 14 to 17 Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays Memory cartridges The Zelio Logic 2 programmable smart relays can be fitted with a backup memory cartridge which enables copying of the program into another smart relay for loading and updating of on board software and firmware 7 building of identical equipment remote transmission of updates These memory cartridges also enable a backup copy of the program to be saved prior to replacing the product When they are used with a smart relay without display or buttons the copy of the program contained in the cartridge is automatically transferred into the smart relay On power up Modem communication interface The communication products in the Zelio Logic 2 range include m a Modem communication interface connected between a smart relay and a Modem see pages 32 to 41 m analog PSTN 2 or GSM 3 Modems m Zelio Logic Alarm software They are designed for monitoring or remote cont
39. independently using the buttons on the smart relay ladder language O ona PC using Zelio Soft 2 software When using a PC programming can be performed either in LADDER language or in function block diagram FBD language see pages 12 and 13 Backlighting of the LCD display 7 is set by either using the 6 programming buttons on the smart relay or by using Zelio Soft 2 software example flashing in the event of a malfunction The autonomous operating time of the clock assured by a lithium battery is 10 years Data backup preset values and current values is provided by an EEPROM Flash memory 10 years Compact smart relays Compact smart relays meet requirements for simple automation systems The number of inputs outputs can be m 12 or 20 I O supplied with 12 V or 24 V E 10 12 or 20 I O supplied with 24 V or 100 240 V Modular smart relays and extensions The number of inputs outputs for modular smart relays can be E 26 I O supplied with 12 V m 10 or 26 I O supplied with 24 V 24 V or 100 to 240 V To improve performance and flexibility Zelio Logic 2 modular smart relays can be fitted with I O extension modules with from 10 to 40 I O E discrete I O extension modules with 6 10 or 14 I O supplied via the smart relay at the same voltage E analog I O extension modules with 4 I O supplied with 24 V via the smart relay at the same voltage E network communication module suppl
40. io Logic 2 programmable smart relays provide a high processing capacity up to 200 function blocks including 24 pre programmed functions F TIMER AC TIMER Aa Timer Function A C ON delay and OFF delay TIMER EH Timer Function BH adjustable pulsed signal TIMER BW JLL TIMER Ev Timer Function BW pulse on rising falling edge f ax TIMER Li far TIMER Li Pulse generator ON delay OFF delay BOOLEAN BOOLEAN Allows logic equations to be created between connected inputs UP DOWN COUNT UF DORH COUNT Up down counter with external preset GAIN GAIN Allows conversion of an analog value by change of scale and of set fl 4 BISTABLE i EIS TABLE Impulse relay function CAM CAM Cam programmer PRESET H METER PRESET H METER Hour counter hour minute preset TRIGGER TRIGGER Defines an activation zone with hysteresis SET RESET ER Bistable latching Priority assigned either to SET or RESET function PRESET COUNT PRESET COUNT Up down counter 1 20 TIME PROG DEPOOD TIME PROG Time programmer weekly and annual Tel MUX MUX Multiplexing functions on 2 analog values WAL MMi l Zone comparison Min lt Value lt Max DISPLAY DIS PL Display of digital and analog data date time messages for Human Machine interface ARCHIVE A ba COMP IN ZONE ARCHIVE Storage of 2 values simultaneously SFC functions 2 GRAFCET tn ADD SUB
41. lable m ABL 7RM2401 24 V 1 3 A E ABL 7RM24025 24 V 2 5 A m ABL 7RM1202 12 V 1 9 A ABL 7RM2401 ABL 7RM24025 ABL 7RM1202 1 2 3 OO O 0000 Input Output 100 240V N 24V LN E aE OO 0000 Inpu Output t 100 240V 24V ABL 7RM 1 2 5 mm 14 AWG screw terminals for connection of the incoming a c supply voltage 2 Output voltage adjustment potentiometer 3 2 5 mm 14 AWG screw terminals for connection of the output voltage 4 LED indicating presence of the d c output voltage 5 Retractable mounting feet Characteristics References Dimensions Schemes pages 43 and 44 page 45 page 45 page 45 42 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Characteristics Power supplies Power supplies for d c control circuits Phaseo modular regulated power supplies Power supply type ABL 7RM1202 ABL 7RM2401 ABL 7RM24025 Certifications UL CSA TUV Conforming to standards Safety IEC EN 60950 1 IEC EN 61131 2 A11 IEC EN 60950 1 EMC IEC EN 61000 6 2 IEC EN 61000 6 1 IEC EN 61000 6 3 LED indication no Input voltage Nominal values V 100 to 240 Permissible values V 85 to 264 Permissible frequencies Hz 47 to 63 Efficiency at nominal load gt 80 gt 84 Current consumption z 0 5 100 V 0 3 240 V 0 6 100 V 0 4 240 V 1 2 120 V 0 7 240 V Current at switch on AO OZO O oO O s Power facto
42. lio Logic 2 Programmable Smart Relays Modem communication interface Function Remote station device Analog PSTN GSM Modem Modem Type of SIM card DATA DATA VOICE VOICE DATA N VOICE N Send alert receive instruction with GSM telephone Send alert receive instruction with PC running Zelio Logic Alarm software 1 Transfer program Update firmware Monitoring Send alert to e mail address HI Functions available Functions not available Note Instructions cannot be transmitted by e mail 1 When using a GSM Modem on the PC side the SIM card must have a DATA number Presentation Characteristics References Dimensions Connections pages 32 and 33 page 37 page 38 page 39 pages 40 and 41 35 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Setting up Zelio Logic 2 Programmable Smart Relays Modem communication interface Setting up of the installation or the machine to be monitored involves 2 steps Connection for programming the smart relay and the interface Communication interface Smart relay SR2 COMO PC BARR RRRRERER RED 1 Interface cable marked COM Z 2 Cable SR2 USBO1 or SR2 CBLO1 After having powered up the smart relay and the interface the application program can be transferred in order to simultaneously m load the automation system program into the smart relay E load the alert conditions messages and telephone nu
43. log PSTN modem 2 E the GSM 5 or analog 5 TRANSMISSION NETWORK provided by different telecommunication operators E a monitoring or control Receiving device which may be one of the following o aPC 7 fitted with an analog PSTN or GSM Modem 8 O ora GSM telephone 9 Note the majority of Modems built into PCs can be used Various combinations are possible between the types of Modem used on the Remote station and the type of Receiving device PC Modems or GSM telephone The type of architecture selected will therefore depend mainly on E whether or not an analog PSTN telephone line is available E whether or not it is necessary to send SMS messages see page 35 1 Global System Mobile 2 Public Switched Telephone Network References Dimensions Connections page 38 page 39 pages 40 and 41 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Presentation continued Zelio Logic 2 description Programmable Smart Relays Modem communication interface 10N continued Smart relay Remote station The smart relay as on an independent machine or installation is used for control 7 It contains the application program created using Zelio Soft 2 software The smart relay may be selected from the various models in the Zelio Logic 2 range m for all supply voltages E with 10 12 20 or 26 I O up to 40 I O with discrete extension module E with or without display E with clock
44. mbers e mail addresses into the interface This operation can also be carried out remotely using Transfer mode after having made the operating connections described below A Program loading using memory cartridges SR2 MEMO1 or SR2 MEMO2 is incompatible with Modem communication interface SR2 COMO01 Operating connections Analog PSTN modem Communication interface Smart relay SR2 COMO1 Modem 1 Interface cable marked COM Z 2 Cable SR2 CBLO7 included with the interface GSM Modem Communication interface Smart relay SR2 COMO GSM Modem 1 Interface cable marked COM Z 2 Cable SR2 CBLOY7 included with the interface 3 SUB D 9 SUB D 15 cable included with the Modem 4 Antenna and cable included with the Modem Presentation Characteristics References Dimensions Connections pages 32 and 33 page 37 page 38 page 39 pages 40 and 41 36 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Characteristics Zelio Logic 2 Programmable Smart Relays Modem communication interface Product certifications Environment category C UL CSA C Tick Degree of protection IP 20 Ambient air Operation 20 to 55 4 to 131 conforming to IEC EN 60068 2 1 and 60068 2 2 temperature Storage C F 25 to 70 13 to 158 conforming to IEC EN 61131 2 Maximum relative humidity 95 without condensation or dripping water Maximum operating altitude m ft 2000 6562 Mechani
45. nd SR2 E SR2 MEM02 A incompatible with SR2 COMO1 SR2 SFTO1 SR2 PACKeBD SR2 PACKeFU see page 20 see page 20 ABL 7RM1202 ABL 7RM24000 20 SSS EU Es Ler TO enie p eee ee os eeove o ge acoceoneoeorrr qa uh a i oitir Se o ES Tam SR3 B261JD SR3 BeeeBD SR3 BeeiB SR3 BeelFU 1 FBD Function Block Diagram This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Selection guide Zelio Logic 2 Programmable Smart Relays Extensions and interfaces SR3 XTeeeJD SR3 XTeeeBD SR3 XTeeeB SR3 XTeeeFU This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Ea This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com 109446 109458 000003 26 Presentation 20 029990000 Fee TT Ti 2 13 4 15 00 ele E2 Cl j boa TP E 00000 Curtsuta Atop EA ad grado pt re SR2 B121BD Modular smart relay and extension module combination 1 2 T LALLILLELLILLTIEILE L 9006008 a p J 7 m d TILLE Serer o 8868 dA o 65866 GOA 00 00 0000 soos j kdi r wy BA si 1 i fia 1 Modular smart relay 10 or 26 I O 2 Discrete I O 6 10 or 14 I O or analog I O 4 I O extension module 1 2 3 ee sseses um 0 0 0 ee co co oe cp ee oo 1 Modular smart relay 10 or 26 I O 2 Network communication module 3 Disc
46. neider Electric Head office Schneider Electric North American Operation Division 1415 South Roselle Road Palatine IL 60064 TEL 847 397 2600 http Awww us telemecanique com http www us schneider electric com ART 808501 The efficiency of Telemecanique branded solutions Used in combination Telemecanique products provide quality solutions meeting all your Automation amp Control applications requirements Networks amp Communication PELL Tepe oe Intaria es amp VO J A Na Detection Power supplies Motor control Mounting systems A worldwide presence Constantly available More than 5 000 points of sale in 130 countries m You can be sure to find the range of products that are right for you and which complies fully with the standards in the country where they are used Technical assistance wherever you are m Our technicians are at your disposal to assist you in finding the optimum solution for your particular needs m Schneider Electric provides you with all necessary technical assistance throughout the world Simply Smart Owing to changes in standards and equipment the characteristics given in the text and images in this document are not binding us until they have been confirmed with us Production Schneider Electric Industries Photos Schneider Electric Industries Printed by s5 a DIASED2051002EN US O 2007 Schneider Electric All Rights Reserved January 2007 a
47. ng feet 2 A 12 to 24 V supply terminal block 3 A slot for connection to the Modem or the PC 4 An interface status LED indicator 5 A connection cable to the smart relay 6 A spring clip for mounting on a 35 mm mounting rail Functions setting up Characteristics References Dimensions Connections pages 34 to 35 page 37 page 38 page 39 pages 40 and 41 33 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Functions Zelio Logic 2 Programmable Smart Relays Modem communication interface Sending of alerts This function makes it possible to send an alert to a Receiving device When the calling condition is met a message is sent to one or several telephone numbers or e mail addresses Types of message m alert message to a PC with Modem and Zelio Logic Alarm software E SMS message 7 to a GSM telephone E e mail via SMS 1 2 One or all of the solutions can be selected simultaneously The Remote station to be monitored initiates the call The telephone line is only used while the alert message is being transmitted Up to 28 messages can be used These messages consist of m a 160 character text which may contain a discrete and or analog value counting values analog input voltages that can be scaled etc E 1 to 10 recipient telephone numbers e mail addresses pe Condes fit gorii the Enio th O Tirin ACTIVE ta AC THE Receipt of instruction This function allows the
48. ork slave communication module 1 2 3 ee ARGOS Te do de io a eeeeo t E eo eo ee ee oe om 00 00 1 Modular smart relay 10 or 26 I O 2 Network communication module 3 I O extension module discrete 6 10 or 14 I O or analog 4 I O A The order shown above must be observed when using a Modbus network slave communication module and a discrete or analog I O extension module An I O extension module cannot be fitted before the Modbus network slave communication module Characteristics Functions page 29 page 30 28 Zelio Logic 2 Programmable Smart Relays Modbus network slave communication module The Modbus protocol is of the master slave type Two exchange methods are possible E request reply the request from the master is addressed to a specific slave The master waits for the reply to be returned by the slave polled E distribution the master distributes a request to all the slave stations on the bus These stations execute the instruction without sending a reply Zelio Logic modular smart relays are connected to the Modbus network via the Modbus network slave communication module This module is a slave that is not electrically isolated The Modbus network slave communication module must be connected to an SR3 BeeeBD modular smart relay with a 24 V supply only no other voltages are available Configuration The Modbus network slave communication module can be configured
49. r 0 6 LED indication Green LED Nominal output voltage 12 24 A Nominal output current 1 9 1 3 2 5 Precision Output voltage Adjustable from 100 to 120 Line and load regulation o 4 3 Residual ripple interference mV 200 250 200 Micro breaks Holding time ms gt 10 for max and Ue min Protection Against short circuits Permanent Thermal protection Against overcurrent cold state lt 1 7In iin ii AA I Against overvoltage V lt 10 5 lt 19 Connections Input mm 1 x 2 5 14 AWG or 2 x 1 5 416 AWG screw terminals AWG Output 1 x 2 5 14 AWG or 2 x 1 5 16 AWG screw terminals AWG Environment Storage temperature C F 25 to 70 13 to 158 40 to 70 40 to 158 Operating temperature C F 20 to 55 4 to 131 Maximum relative humidity 95 Degree of protection IP20 Vibration IEC EN 61131 2 IEC EN 60068 2 6 test Fc Operating position Vertical Connections Series No Parallel Yes same references Dielectric strength Input output 3000 Vac 50 Hz 1 min Protection class no Class II without PE conforming to VDE 0106 1 Input fuse incorporated Yes not interchangeable Emissions Conducted radiated IEC EN 61000 6 3 EN 55011 EN 55022 CI B Immunity Electrostatic discharge IEC EN 61000 6 2 generic standard IEC EN 61000 4 2 4 kV contact 8 kV air Electromagnetic IEC EN 61000 4 3 level 3 10 V m Conducted interference IEC EN 61000 4 4 level 3
50. rete I O 6 10 or 14 I O or analog I O 4 I O extension module A The order shown above must be observed when using a Modbus network slave communication module and a discrete or analog I O extension module An I O extension module cannot be fitted before the Modbus network slave communication module Functions Characteristics pages 11to 13 pages 14 to 17 8 Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays Zelio Logic 2 programmable smart relays are designed for use in small automation systems They are used in both the industrial and commercial sectors m For industry O automation of small finishing production assembly or packaging machines O decentralized automation of ancillary equipment of large and medium sized machines textile plastics materials processing sectors etc o automation systems for agricultural machinery irrigation pumping greenhouses etc E For the commercial building sectors O automation of barriers roller shutters access control O automation of lighting systems O automation of compressors and air conditioning systems Their compact size and ease of setting up make them a competitive alternative to solutions based on cabled logic or specific cards m Programming Simple programming ensured by the universal nature of the languages meets all the requirements of automation specialists and also the needs of the electrician Programming can be performed O
51. rol of machines or installations which operate without personnel The Modem communication interface supplied with 12 to 24 V enables messages telephone numbers and calling conditions to be stored 1 Use memory cartridge SR2 MEMO2 only for software and firmware versions V3 0 or higher Use SR2 MEMO for any software versions earlier then V3 0 of the Zelio Logic 2 software The SR2 MEMO cannot update firmware of any version 2 Public Subscriber Telephone Network 3 Global System Mobile Curves References Dimensions schemes pages 18 and 19 pages 20 to 22 pages 23 to 27 9 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Description With display 10 12 and 20 I O Ra E Ls Anglo of 24700 24 Inputs 11 14 MVOC Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays Without display 10 12 and 20 I O Compact smart relays have the following on L the front face 1 Two retractable mounting feet oe 20909990 Two power supply terminals ana aes Terminals for connection of the inputs Backlit LCD display with 4 lines of 18 characters Slot for memory cartridge or connection to a PC or communication interface 6 buttons for programming and parameter entry Terminals for connection of the outputs Input TM wv 2 3 4 ED EEE a Ee ol iparba 01 04 Aslay BA er Se Se a With display 10 and 26 I O M
52. s Presentation description Functions Curves References Dimensions schemes pages 8 to 10 pages 11 to 13 pages 18 and 19 pages 20 to 22 pages 23 to 27 17 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Curves Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays d c loads DC 12 1 3 0 2 5 2 0 1 5 1 0 0 5 Millions ot operating cycles 0 0 0 05 1 1 5 2 Current A DC 13 2 1 4 L R 10 ms 48 V 1 2 L R 10 ms 24 V 1 0 L R 60 ms 48 V l I oe L R 60 ms 24 V 0 6 0 4 Millions of operating cycles 0 2 0 05 4 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 Current A 1 DC 12 switching resistive loads and photo coupler isolated solid state loads L R lt 1 ms 2 DC 13 switching electromagnets L R lt 2 x Ue x le in ms Ue rated operational voltage le rated operational current with a protection diode on the load DC 12 curves must be used with a coefficient of 0 9 applied to the number in millions of operating cycles Presentation description Functions Characteristics References Dimensions schemes pages 8 to 10 pages 11 to 13 pages 14to 17 pages 20 to 22 pages 23 to 27 18 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Curves continued Zelio Logic 2 Pro
53. sions schemes pages 23 to 27 References pages 20 to 22 Curves pages 18 and 19 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Characteristics continued PF Smart relay type Primary Nominal voltage Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays SR2 SR2 SR2 SR2 SR3 SR3 SR3 SR3 eieiBD B122BD e201BD B202BD B101BD B102BD B261BD B262BD Voltage limits Nominal input current Including ripple Without extensions 24 19 2 to 30 70 With extensions 100 160 300 180 Power dissipated Without extensions 3 6 3 4 6 5 With extensions 2 Po fo Micro breaks Permissible duration lt 1 repeated 20 times Protection Against reverse polarity op Smart relay type SR2 e121B SR2 e201B SR3 B101B SR3 B261B Primary Nominal voltage V 24 Voltage limits V 20 4 to 28 8 Nominal frequency Hz 50 60 Nominal input current Without extensions 145 233 160 280 With extensions a 280 415 Power dissipated Without extensions VA 4 To ta 75 With extensions VA 7 5 10 Micro breaks Permissible duration ms lt 10 repeated 20 times rms insulation voltage V 1780 50 60 Hz Smart relay type SR2 6101FU SR2 6121FU SR2 e201FU SR3 B101FU SR3 B261FU Primary Nominal voltage V 100 to 240 Voltage limits V Nominal input current Without extensions 80 30 100 50 80 30 100 50 With extensions mo 80 40 80 60 Power dissipated Without ex
54. solation Between supply and inputs E None Between inputs None Maximum counting frequency a 1 Protection Reverse polarity protection Control instructions not executed analog inputs Smart relay type SRe eeeeJD SRe eeeeBD Input range V O to10 or Oto 12 Oto 10 or Oto 24 Input impedance kQ 14 12 Maximum non destructive voltage 14 4 30 Value of LSB 39 mV 4 mA Input type Common mode Conversion Resolution Ed 8 bits Conversion time Smart relay cycle time Precision at 25 C 77 F 5 at 55 C 131 F 6 2 Repeat accuracy at 55 C 131 F 2 Isolation Between analog channel amp supply None Cabling distance m 10 maximum with shielded cable sensor not isolated Protection Control instructions not executed Analog inputs Application Assignable inputs Reverse polarity protection o 10 V 0 20 mA Pt100 Input range Input impedance Maximum non destructive value IH and IJ IH and IJ IJ 0 to 10 Vdc O to 20 mA 25 to 125 C 13 to 257 F 246 E and Pt 30 V 30 mA 9 8 mV 20 uA 0 15 C 32 F Value of LSB Input type Pt100 probe IEC 751 3 wire Conversion Resolution 10 bits Conversion time Smart relay cycle time Precision at 25 C 77 F Eos Css at 55 C 131 F E 15 C 35 F Repeat accuracy at 25 C 77 F lt 0 3 C 32 F Isolation Between analog chan amp supply None Cabling distance m ft 10 32 81 maximum
55. tensions 7 12 With extensions VA 12 17 Micro breaks Permissible duration ms 10 rms insulation voltage V 1780 Smart relay type SRe eeeeJD SRe eeeeBD V 12 24 Nominal value of inputs Voltage Current mA 4 Input switching limit values At state 1 Voltage V 25 6 215 At state 0 Voltage lt 2 4 lt 5 Current mA lt 0 9 lt 0 75 Input impedance at state 1 kQ 7 4 Conforming to IEC EN 61131 2 Type 1 Sensor compatibility 3 wire Yes PNP 2 wire No Input type Resistive Isolation Between supply and inputs None Between inputs None Maximum counting frequency kHz 1 Protection Reverse polarity protection Control instructions not executed Presentation description pages 8 to 10 Functions pages 11 to 13 Dimensions schemes pages 23 to 27 Curves References pages 18 and 19 pages 20 to 22 15 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Characteristics continued discrete inputs Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays Smart relay type SRe eeeeJD SRe eeeeBD Nominal value of inputs Voltage V 12 24 Current mA 4 Input switching limit values At state 1 Voltage gt 15 Current mA 20 5 21 2 At state 0 Voltage V lt 5 Current mA lt 0 2 lt 0 5 Input impedance at state 1 kQ 14 12 Conforming to IEC EN 61131 2 Type 1 Sensor compatibility 3 wire Yes PNP 2 wire No Input type Resistive I
56. tics Curves References pages 8 to 10 pages 11 to 13 pages 14 to 17 pages 18 and 19 pages 20 to 22 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Schemes Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays SRe eee1BD SRe eeeiJD SR2 Bee2BD and SR3 Bee2BD SR3 B261eD SR2 eeeeBD 24V SR2 B121JD 12V 11 12 13 14 IB IC ID IE O 11121314 IBICIDIE 00000000 l OO 00000000 Oo QQ 29 99 09 Gi Ceo DO 0 60 00 Q2 Q 4 I 5 A 4 Q1 Q2 Q3 3 L i l 12 240 V E A 50 60 Hz Ny 12 24 V T PO e O Teo N 12 240 V E 50 60 Hz or pers 3 od A E aa isu 12 24 V 1 1 A quick blow fuse or circuit breaker 2 Fuse or circuit breaker 3 Inductive load 4 Q9 and QA 5 A Discrete input used for 3 wire sensors 1 BN OO 00000000 1 1 A quick blow fuse or circuit breaker Presentation description Functions Characteristics Curves References pages 8 to 10 pages 11 to 13 pages 14 to 17 pages 18 and 19 pages 20 to 22 24 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com Schemes continued Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays Analog inputs 1 1 A quick blow fuse or circuit breaker 2 Ca Analog sensor Ta Analog transmitter 3 Recommende
57. torque With LADDER programming IEC EN 61000 4 11 IEC EN 61000 4 12 Class B 1 1 conductor 0 25 to 2 5 cable AWG 24 to AWG 14 2 conductors 0 25 to 0 75 cable AWG 24 to AWG 18 1 conductor 0 2 to 2 5 cable AWG 25 to AWG 14 1 conductor 0 2 to 2 5 cable AWG 25 to AWG 14 2 conductors 0 2 to 1 5 cable AWG 24 to AWG 16 0 5 4 4 N m Ibf in 120 Number of function blocks Cycle time Response time With FBD programming Up to 200 10 to 50 20 minimum Back up time in the event of power failure Day time Program and settings 10 years lithium battery at 25 C 77 F 10 years EEPROM memory cartridge Program memory checking On each power up Clock drift 12 min year O to 55 C 32 to 131 F 6 sec month at 25 C 77 F and calibration Timer block accuracy 1 2 cycle time Smart relay type SR2 B121JD SR2 B201JD SR3 B261JD Primary Nominal voltage V 12 Voltage limits Including ripple V 10 4 to 14 4 Nominal input current Without extensions 120 200 250 With extensions 400 Power dissipated Without extensions 15 25 3 With extensions W 5 Micro breaks Permissible duration ms lt 1 repeated 20 times Protection Against reverse polarity Presentation description pages 8 to 10 14 Functions pages 11 to 13 1 Except for the configuration SR3 BeeeBD SR3 MBU01BD SR3 XT43BD class A class B work in progress Dimen
58. ular smart relay a connecting SR3 PACKFU 0 700 cable and Zelio Soft 2 programming software supplied on CD Rom 26 An SR3 B261FU modular smart relay a connecting SR3 PACK2FU 0 850 cable and Zelio Soft 2 programming software supplied on CD Rom 1 Can only be used with Zelio Soft 2 software version 2 V3 1 2 Including 8 outputs at maximum current of 8 A and 2 outputs at maximum current of 5 A 3 Power supply to the I O extension and communication modules is via the modular smart relay 4 See page 26 5 Can only be used in FBD language 6 See pages 28 to 31 Note The smart relay and its associated extensions must have an identical voltage 21 This document provided by Barr Thorp Electric Co Inc 800 473 9123 www barr thorp com 534944 523109 DF563990 References 510352 m EENEN SR2 SFTO1 SR2 USBO1 MEMORY a SR2 MEMO1 SR2 MEMOZ Presentation description pages 8 to 10 Functions pages 11 to 13 Zelio Logic 2 Programmable Smart Relays Compact and modular smart relays Separate components Description Application Reference Weight kg Programming software For PC supplied on CD ROM 1 SR2 SFTO1 0 200 Zelio Soft 2 multilingual compatible with Microsoft Windows 98 NT 2000 XP and ME Connecting cable Between the PC SUB D 9 pin SR2 CBLO1 0 150 connector and the smart relay length 3 m 9 8 ft Between the PC USB connector amp SR2 USB