Data Sheet DB GB IB IL 24 SEG-ELF - Digi-Key
Contents
1. 1000 1000 100 100 n 10 10 T E E 1 1 0 1 0 1 0 01 0 01 8 5 4 3 0 l A R 2 K Where t Typical tripping time in ms IL Load current in the segment circuit in A RL Load impedance in the segment circuit in Q Ig Current limit typical Value K Measured value on a hard short circuit Power Dissipation To keep the power dissipation to a minimum the control input must be in the idle state 0 V A constant supply to the control input of 24 V is not permitted This technical connection measure is the basis for the calculations below Formula to Calculate the Power Dissipation of the Electronics 500 kbaud Prot 0 23 W I x 0 06 Q Where Prot Total power dissipation of the module IL Load current in the segment circuit Formula to Calculate the Power Dissipation of the Electronics 2 Mbaud Prot 0 43 W I x 0 05 Q Where Prot Total power dissipation of the module IL Load current in the segment circuit Power dissipation of the housing Phou 0 6 W within the permissible operating temperature 5657_en_01 PHOENIX CONTACT 5 IB IL 24 SEG ELF Derating on 30 V I O Supply Uy Us Maximum permissible load current in the segment circuit llmax 2 5A at 25 C lt T lt 50 C llmax 2 0A at 50 C lt Ta lt 55 C Safety Equipment Overload short circuit in the segment circuit Surge voltage Polarity reversal Electrical lsolation Isolation of the Voltage Areas
2. IB IL 24 SEG ELF Behavior of the Electronic Fuse Function of the Fuse The fuse monitors the maximum nominal current in the segment circuit which must not exceed 2 5 A The terminal indicates the status of the fuse via the E LED and via the two input data bits If the fuse blows it remains in this state The blown fuse is indicated by E LED ON D LED Flashing at 2 Hz peripheral fault INO 0 and IN1 0 Message to the higher level control or computer system Peripheral fault PF Input bit Error message Resetting the Fuse There are three ways of resetting the fuse in an operational state 1 Failure deactivation and reactivation of the communications power at the bus terminal 2 24V pulse at the control input 3 Control signal from the application program via the bus system Resetting the Fuse Via the Control Input To reset the fuse via the control input connect an optional external button as shown in Figure 2 A The control input should only be supplied with 24 V to reset the fuse Set the control input to the idle state with O V or leave it open S T N OU G Q S Or Q 5657A004 Figure 2 Connection of a button for resetting the fuse Resetting the Fuse Via a Control Signal From the Application Program In order to reset the fuse from the application program send the Control_Device_Function service in the firmware
3. Yes see page 4 Protective elements in the power terminal or the bus terminal Protective elements in the power terminal or the bus terminal IEY To provide electrical isolation between the logic level and the I O area it is necessary to supply these areas via the bus terminal or via the permitted See also user manual bus terminal and a power terminal from separate power supply units Interconnection of the power supply units in the 24 V area is not Common Potentials The 24 V main voltage 24 V segment voltage and GND have the same potential FE is a separate potential area Separate Potentials in the System Consisting of Bus Terminal Power Terminal and I O Terminal Test Distance 5 V supply incoming remote bus 7 5 V supply bus logic 5 V supply outgoing remote bus 7 5 V supply bus logic 7 5 V supply bus logic 24 V supply I O 24 V supply I O functional earth ground Test Voltage 500 V AC 50 Hz 1 min 500 V AC 50 Hz 1 min 500 V AC 50 Hz 1 min 500 V AC 50 Hz 1 min Error Messages to the Higher Level Control or Computer System Short circuit overload in the segment circuit Yes IEY If a short circuit occurs in the segment circuit an error message is generated LEDs D and E on the terminal also flash to indicate the fault see Local Diagnostic Indicators on page 7 Falling below or exceeding the operating voltage Approvals CE UL CUL No Yes Yes 5657_en_01
4. PHOENIX CONTACT 6 IB IL 24 SEG ELF Local Diagnostic Indicators and Terminal Point Assignment Figure 1 IB IL 24 SEG ELF with the appropriate connector 5657A003 Local Diagnostic Indicators Des Color Meaning D Green Diagnostics ON Bus active Flashing 0 5 Hz Communications power present bus not active 2 Hz Communications power present peripheral fault 4Hz Communications power present local bus error OFF Communications power not present bus not active E Red Fuse in segment circuit Us OFF Fuse OK ON Fuse has blown I A blown fuse is indicated by both diagnostic indicators The red E LED is on and the green D LED flashes at 2 Hz Function Identification Black 2 Mbaud white stripe in the vicinity of the D LED Terminal Point Assignment A The terminal points are only provided for measurement purposes and for connecting a manual reset button for the electronic fuse Terminal Assignment Point 1 1 Connection of a manual reset button for the fuse control input 2 1 Connection of a manual reset button for the fuse 24 V 1 2 2 2 Measuring points for the main voltage Um 1 3 2 3 Measuring points for GND of supply voltages 1 4 2 4 Measuring points for functional earth ground FE 5657_en_01 PHOENIX CONTACT 7
5. This service can be used to send control commands to one or more INTERBUS devices For example the service may be used to acknowledge a peripheral fault triggered by the electronic fuse and to reset it For more detailed information on firmware services please refer to the Firmware Services and Error Messages user manual IBS SYS FW G4 UM E Order No 2745185 5657_en_01 PHOENIX CONTACT 8 IB IL 24 SEG ELF Internal Circuit Diagram Local bus UL 24 V Uy Figure 3 ELF at ah i s Cssssse ro Q 24 V Us 5657B005 Internal wiring of the terminal points Protocol chip bus logic including voltage conditioning LED with details of the display designation D or E see page 7 Optocoupler Electronic fuse Electrically isolated area Programming Data Configuration Data INTERBUS ID code BEnex 190gec Length code C2hex Input address area 2 bits Output address area 0 bits Parameter channel PCP 0 bits Register length bus 2 bits Other symbols used are explained in the IB IL SYS PRO UM E user manual or in the Inline system manual for your bus system Other Bus Systems IR For the programming data configuration data of other bus systems please refer to the corresponding electronic device data sheet GSD EDS Process Data As
6. DGD OGD OO GD Lionas OGD OO IB IL 24 SEG ELLF Inline Segment Terminal With Electronic Fuse INSPIRING INNOVATIONS AUTOMATIONWORX Data Sheet PHOENIX CONTACT 01 2006 Description Features The terminal is designed for use within an Inline station The segment terminal is used to create a partial circuit segment circuit within the main circuit It is not used to supply power and therefore has no elements for protection against polarity reversal and surge voltage This terminal has an LED for bus diagnostics and occupies two input data bits which are used to indicate the status of the electronic fuse Automatic creation of a segment circuit in the main circuit Protection of the segment circuit using an electronic fuse with short circuit current limitation Diagnostic indicators Mapping the status of the electronic fuse in the input data Resetting the fuse via the bus system or manually using an optional external button manual for your bus system This data sheet is only valid in association with the IB IL SYS PRO UM E user manual or the Inline system The product versions differ in the scope of supply and the transmission speed see Ordering Data on page 2 The function is identical Differing technical data is indicated For greater clarity the order designation IB IL 24 SEG ELF is used throughout this document q m Make sure you always use the latest documentation It can be downloa
7. N PWR IN IB IL SCN PWR IN CP Type IB IL SYS PRO UME IL SYS INST UM E Order No 2727462 2727637 Order No 2743048 2698737 Pcs Pkt 10 10 Pcs Pkt 1 5657_en_01 PHOENIX CONTACT 2 IB IL 24 SEG ELF Technical Data General Data Housing dimensions width x height x depth Weight without connectors Weight with connectors Operating mode Permissible temperature operation Permissible temperature storage transport Permissible humidity operation 12 2 mm x 120 mm x 71 5 mm 44 g approximately without connectors 59 g approximately with connectors Process data mode with 2 bits 25 C to 55 C 25 C to 85 C 75 on average 85 occasionally IEY In the range from 25 C to 55 C appropriate measures against increased humidity gt 85 must be taken Permissible humidity storage transport 75 on average 85 occasionally IEY For a short period slight condensation may appear on the outside of the housing if for example the terminal is brought into a closed room from a vehicle Permissible air pressure operation Permissible air pressure storage transport Degree of protection Protection class Transmission Speed IB IL 24 SEG ELF IB IL 24 SEG ELF PAC IB IL 24 SEG ELF 2MBD IB IL 24 SEG ELF 2MBD PAC Interface Local bus Power Consumption 500 kbaud Communications power Current consumption from the local bus Power consumption fro
8. ded at www download phoenixcontact com A conversion table is available on the Internet at www download phoenixcontact com general 7000_en_00 pdf IE This data sheet is valid for all products listed under Ordering Data on page 2 5657_en_01 PHOENIX CONTACT GmbH amp Co KG 32823 Blomberg Germany 1 Phone 49 52 35 30 0 Fax 49 52 35 34 12 00 www phoenixcontact com www phoenixcontact com salesnetwork IB IL 24 SEG ELF Ordering Data Terminals Description Segment terminal with electronic fuse with connector and labeling field Transmission speed 500 kbaud Segment terminal with electronic fuse Transmission speed 500 kbaud Segment terminal with electronic fuse with connector and labeling field Transmission speed 2 Mbaud Segment terminal with electronic fuse Transmission speed 2 Mbaud Type IB IL 24 SEG ELF PAC IB IL 24 SEG ELF IB IL 24 SEG ELF 2MBD PAC IB IL 24 SEG ELF 2MBD Order No 2861409 2727789 2863847 2861182 Pcs Pkt 1 IRs One of the connectors listed below is needed for the complete fitting of the IB IL 24 SEG ELF and IB IL 24 SEG ELF 2MBD terminals Accessories Description Connector black w o color print Connector black with color print Documentation Description Configuring and Installing the INTERBUS Inline Product Range user manual Automation Terminals of the Inline Product Range user manual Type IB IL SC
9. m the local bus Main voltage Um Nominal current consumption at Um Power Consumption 2 Mbaud Communications power Current consumption from the local bus Power consumption from the local bus Main voltage Um Nominal current consumption at Um 80 kPa to 106 kPa up to 2000 m above sea level 70 kPa to 106 kPa up to 3000 m above sea level IP20 according to IEC 60529 Class 3 according to VDE 0106 IEC 60536 500 kbaud 500 kbaud 2 Mbaud 2 Mbaud Through data routing 7 5V 30 mA maximum 0 23 W maximum 24 V DC nominal value 2 5 A nominal value 7 5 V 60 mA maximum 0 45 W maximum 24 V DC nominal value 2 5 A nominal value Supply of the Module Electronics and the I O Through the Bus Terminal Power Terminal UL Um Connection method Through potential routing The main voltage Uy is supplied by the bus terminal or by a power terminal The segment voltage Ug is provided automatically at the IB IL 24 SEG ELF terminal and protected by the internal electronic fuse Connections for a supply voltage are not provided on the segment terminal The terminal points are only provided for measurement purposes and for connecting a button for resetting the blown fuse 5657_en_01 PHOENIX CONTACT 3 IB IL 24 SEG ELF Digital Control Input Number 1 Nominal voltage Uin 24V DC Nominal current at Uy 5 mA Definition of switching thresholds Low level lt 5V High level 15 Vi Permissible cable leng
10. signment of IN Process Data IEY For the assignment of the illustrated byte bit view to your INTERBUS control or computer system please refer to the DB GB IBS SYS ADDRESS data sheet Order No 9000990 IEY The IN process data only maps the status of the electronic fuse Bit view Bit 1 0 Assignment Fuse OK 1 1 Fuse has blown 010 PHOENIX CONTACT 01 2006 5657_en_01 PHOENIX CONTACT 9
11. th to the external button Segment Circuit Protection 30 m to ensure conformance with EMC directive 89 336 EEC Nominal voltage 24V DC Permissible range 19 2 V DC to 30 V DC Nominal current 2 5A Voltage drop at nominal current 05V Short circuit current limiting Minimum 2 8A Maximum 8A Behavior after error Latch function i e remains switched off Closing resistor 60 MQ Tripping time in the event of a short circuit 100 ms IEY The fuse is tripped by a thermal overload protection The tripping time depends on the ambient temperature and the level of the short circuit current The data entered here applies for an ambient temperature of 25 C The power supply unit must be able to provide a short circuit current of at least 8 A Behavior When Ground Connection Interrupted Leakage current when switched on ON communications power present 2 mA maximum Output current when switched off 200 pA OFF communications power not present Output voltage when switched off 1V 5657_en_01 PHOENIX CONTACT 4 IB IL 24 SEG ELF Time Current Characteristic A and Time Resistance Characteristic B on Ohmic Overload Ambient Operating Temperature T 25 C A lc B