RS8CH422 AK2 IO [w-AKC 55] User Manual
Contents
1. Operating temperature 4 F to 131 20 to 55 C 0 to 90 RH non condensing 4 F to 104 F 20 to 40 C 0 to 95 RH non condensing Storage Temperature 40 F to 158 F 40 to 70 C 0 to 95 RH non condensing AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 33 Code numbers for ordering Communications Module 08020061 Communications module type AK2 CM 101A Lonworks TP78 Digital Output Modules 080Z0011 8 DO type AK2 XM 204A with Euromate terminal blocks 080Z0026 8 DO type AK2 XM 204A without terminal blocks 080Z0018 8 DO type AK2 XM 204A with override with Euromate terminal blocks 080Z0031 8 DO type AK2 XM 204A with override without terminal blocks Combination Digital Output amp Universal Analog Input Modules 080Z0010 8 DO 8 Al type AK2 XM 205A with Euromate terminal blocks 080Z0025 8 DO 8Al type AK2 XM 205A without terminal blocks 080Z0017 8 DO 8Al type AK2 XM 205A with override with Euromate terminal blocks 080Z0030 8 DO 8Al type AK2 XM 205A with override without terminal blocks Universal Analog Input Modules 08020007 8AIl type AK2 XM 101A with standard terminal blocks 08020027 8 Al type AK2 XM 101A without terminal blocks Digital Input Modules High Voltage 08020013 8 DI type AK2 XM 102A with override with Euromate terminal blocks 08020029 8 DI type AK2 XM 102A with ov
2. me B LB Ir 5 VIDE NO DIV at YOL WODY n n SEEDS gg om ni asam B n ssuvism I zsnvism C zsnivism C ismivism C isnivism C wows m C xowsm C e E zu 200 520 a 5 3 i Im T LTL Ail walls N ES XK Ak P E N TVANYW JHL NI NAA AG SNOILVOLIO3dS JIGVO MOTIOS Ee Amd E YOMLIN NOT3HO3 Si aeda E E e 3dAl MMOMLAN i 404 SFINY 3AN38380 i NOLLO3NNOO G 3IHS i EX iS SI ll jJ D e AN COMV TEE cnc Mey V EE ATlddNS HIMOd 0 1 p oS i oc i QJ FGA SS oyy F RE I4 8 3 GI amp S 9 9 2 fel a Jo aS Uaua o9 SD gna ad HNO SEO DE rrr ooo O O ISNI Q31V2C 1 AYY08 SNOILY IN RS 8C H5 22 080R9208 06 05 1 AK2 Input Output Modules in AKC 55 Systems Make sure to follow all the steps in the instructions that follow 1 DD 222 Im B 2 4 IY 5 L F1 1 m POWER SET e ell 3 m STATUS 1 1 M STATUS2 W STATUS 3 wRESET mservied Dafi fa ADAP KOOL EF n AK2 CM 101A Hc Li E oll No 08020061 Lo uy RCO TP 78 Di Addressing Using the rotary ID switches shown at lower right in the illustration set the communication module s unique address from 001 099 Any number can be used as long as it is not used on any other communication module in the system Network connection Using 20 24 AWG shielded stranded twisted pair cable connect the c
3. ADAP KOOL AK2 Input Output Modules REFRIGERATION AND AIR CONDITIONING User manual Darfots Table of Contents Installing AK2 Modules Lunar hemme tuper ee iut na tede RR RR ane uden pp 3 6 Mois CHEER p 3 COmmUncahons P tS p 3 Povel p 3 Mountin p mods ae p 4 DIN rail MOUNU Go aise ccienssiseacesesieesz6decsscecandeeiaecnsdad stesiantes e er e E Re a Re efe etre pe ree be eer ERE RR LS p 4 Nfucavann utere eine dk Ei een i issih die nha p 4 Installaing a communications module srir siaaa enne enne nennen nne rrr enn pp 4 5 Cabling requirements TP78 1n AKC 55 Systems scssi tesiek ivot deer o res epe etr Co ce eeu eni ree svoctubesedesvndbeses p 4 Other transceiver types T p 4 AUI MM M p 6 Network connections M HH p 6 Power Connection 22 4 5 oe Fete epe e er ee Leben deus esee bae ta erect Haeo secet stage ped erke iksi p 6 Installers malanspecti n irpo Ur RE RE HHRERRE RE ORE Enor MA a E PE EO eere ree Eee Rb Lente o logus pp 6 7 Eror and status LED p 7 Installing an AK2 XM 204 digital output module sssseeeeeee nenne eene nnne nnns pp 8 9 Connecting RE p 8 Installer s fhinalanspection 2 ehe Der i Perte eene RE dea Era et pe tope ede ERE RE Re ebbe EH REESE be deg p 8 Installaing an AK2 XM 205A
4. Wow FUSED 5A SB 250VAC Status LEDs relay states and override switches There are eight status LEDs one for each output point A status LED represents the state of the point s relay and not necessarily the state of the device wired to that point If the LED is ON the relay is energized With the LED ON then a device wired through normally closed NC contacts is OFF because the normally closed contacts are open Refrigeration compressors for example are wired through normally closed NC contacts so that if power to the control system fails and all the relays are de energized the control circuits for the compressors will be closed and the compressors will run Override switches have logic in line with that of the status LEDs When an override switch is put in the ON position the corresponding relay is continuously energized the LED will come ON and any device wired through the normally closed NC contacts is forced OFF If the same point were to have a device wired through it s normally open NO contacts instead the LED would be ON and the device forced ON When an override switch is put in the OFF position the corresponding relay is continuously de energized the LED will be OFF and any device wired through the normally closed NC contacts is forced ON If the same point were to have a device wired through it s normally open NO contacts isntead the LED would be OFF and the device forced OFF AK2 Input Outp
5. the last real direction for valve travel will also be in the closed direction The hysteresis adjustment ensures that the valve train is always pre loaded in the same direction ensuring repeatability of valve posi tion Overdrive at init 0 to 31 Stepper motor valves do not usually include a feedback mechanism to determine the actual mechanical position of the valve Valve manufacturers however design their valves to be overdriven at complete closure without damage The Overdrive at init value gives the additional amount as a percent AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 24 Darfots age of Max steps that the valve should be driven closed whenever we initialize the valve Valve initial ization occurs automatically whenever the AKC 55 is reset whenever the AK2 XM 208A stepper motor EEPR control module is reset and whenever the associated refrigeration circuit defrosts Manual failsafe 0 to 100 Determines the position as a percentage of full open that the valve will default to should communications fail between the AKC 55 and the communications module for the AK2 XM 208A s lineup or between the communications module and the AK2 XM 208A Max phase current 0 to 1000 mA Limits the current and thus the power dissipation in the valve Take care to set the value to the valve manufacturer s specification The module resolves the programmed value to the nearest 10 mA Ma
6. 1 080R9208 RS 8C H5 22 27 Denpi Specifications AK2 CM 101A communications module UL file number E166834 3 Input voltage 18 36 Vdc 24 Vac 20 PRESS Input power 50 W 60 VA CV I LAID i Input fusing 3 15 A SB 250 Vac h n drm n 7 4 Output voltage 18 36 Vdc in TT Output power capacity up to 45 W 200 00 IO module capacity up to 10 2 c i Power consumption 0 8 W 24 Vdc f 4 1 0 VA Q 24 Vdc I 1 POWER Im En i rJ Operating temperature mstarus2 4 F to 131 F 0 to 95 RH non condensing statusa IIE A42 1 Storage Temperature m RESET S e 6 E o o j of asewo Dag 40 F to 158 F 0 to 95 RH non condensing Ps op NECM 0j i u Compatible with 24 V battery backup systems 7 I mamo AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 28 Specifications AK2 XM 204A digital output module AK2 XM 205A combination digital output amp analog input module UL file number E166834 T g General purpose relays 8 form C Universal inputs 8 ESI r Relay rating 1 4 hp 120 240 Vac rie eee 5 A resistive Co EE ace 1l 24 Vdc or 240Vac u p i Device limit outputs 20A ri x Tis Relay fusing 5A 250 Vac Sensor excitation 5 or 12 Vdc 100 mA Excitation fusing auto reset 200 mA Power supply 18 36 Vdc 3 6 W supplied by communications module Power required to commu
7. A form is provided with each new module for this purpose You will need this information when configuring the host controller Inspection of the installed low voltage digital When a low voltage digital input module is ready for operation you should be able to observe input module the following 1 The module is securely mounted to DIN rail or to a flat surface 2 The module is connected to a communication module or to an existing lineup 3 Power has been reconnected to the communication module 4 The POWER LED is ON 5 The COMM ERROR LED is OFF 6 The status LEDs through 8 correctly reflect the operating status of the equipment being monitored AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 16 9 80 VAC POSITIVE 8 80 VOC 9 80 VAC NEGATIVE Do GND n 3 POWER Il rt T COMM ERROR rl n MT J 1 m2 m3 ma I HZ as Ze 1 apap koo ER ve AK2 XM 102A i ma No 08020028 e u DIGITAL Extension BDIL L pm INPUT R SS Is Me H YIT P N AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 17 Installing an AK2 XM 102A High Voltage Digital Input Module The AK2 XM 102A half width high voltage digital input module provides 8 digital inputs rated at 80 to 260 Vac Mounting Mount the module by connecting it to a communications module or to an existing line
8. Combination Digital Output and Universal Analog Input Module sssssssessssseneenennne e ennemi ennemi nennen neis pp 10 12 IBI ROI T p 10 Universal analo Tputs sen iier iet ror ene e RR d rep ere elei grab Jace Sasa Pesani Lese Ere eade bet Enn p 10 A inni cH p 10 Diy contact Inputs ae se p 11 Installers fnalmspecuonres aar p 12 Installing an AK2 XM 101A Universal Analog Input Module eeeee pp 14 15 LU iore pariet p 14 Compatible sensors x5 endete metn berti Red re BERE em b Ep t rane Eb senest p 14 4 20 mA MM PUts c M n p 14 Dry contact inputs iecore teer OR SE Ea O r RD GRE IE eU r ere HE ESATE Esa ais D ER In RE HIR ERR DESEE DINE p 14 Installer s hiialinspecti n eee ee peteret pe tope rep lbs tege epe r aE Er epe deese even E EdE eo erue DES i p 15 Installing an AK2 XM 101A Low Voltage Digital Input Module e pp 16 17 EEX plan atl OD M L p 16 Tnstall r stmalnspeehon sun ookesesokelseneeettdsrdankuubekekeaklldeestmieser p 16 Installing an AK2 XM 101A High Voltage Digital Input Module s pp 18 19 Plone p 18 Installers finabispectiOn a ee teet ent iet Gabba vete lero ete bene sepu vorerst se eee deles celer lee ees p 18 Installing an AK2 XM208A E
9. SR 40 F to 158 F 40 to 70 i 0 to 95 RH non condensing O AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 31 Darfots Specifications AK2 XM 102A digital input module high voltage ci UL file number E166834 Digital inputs 8 Input rating 95 260 Vac Power supply 18 36 Vdc 0 7W Pam i supplied by communica i tion module Gr Power required to communication module 0 8 W 24 Vdc 1 0 VA Q 24 Vac Operating temperature 4 F to 131 F 20 to 55 C rH COMMERROR I FEL 0 to 90 RH non condensing FI VG 4 F to 104 F 20 to 40 C Ll 7 0 to 95 RH non condensing m3 Pre en m POWER I p z d z Deku i c a Storage Temperature EA EP mel 40 F to 158 F 40 to 70 C Li AK2 XM 102A LER p s Mem p 0 to 95 RH non condensing DIGITAL Extension 8DIL INPUT AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 32 Dashes Specifications AK2 XM 208B bipolar stepper output module Bipolar stepper outputs 4 Input rating 95 260 Vac Power supply 18 36 Vdc 0 7 W supplied by communica tion module Power required to communication module 0 8 W 24 Vdc 1 0 VA 24 Vac Power supplied by module to operate valves 13 VA 12 or 24 Vdc brand dependent
10. VA AK2 XM 102B digital input module high voltage 8 digital inputs 80 260Vac 0 8 W 1 0 VA AK2 XM 208B Bipolar stepper output module 4 bipolar stepper outputs 0 8W 1 0 VA Stepper module requires a second separate 24 Vac power source Danfoss IOPS for valve drive power See installation section of this manual AK2 module names contain information about their use and size A module containing the letters CM is a communications module One containing the letters XM is an extension module The last grouping of 3 or 4 characters in the name specifies the exact type of module The first digit of the last group indicates the width of the module 1for a half width module and 2 for a full width module The remainder indicates the exact nature of the module Communications The AK2 CM 101A communications module is available with 3 types of Echelon transceiver TP78 EIA 485 and FTT The TP78 protocol is required for AKC 55 systems Each physically separate lineup of I O modules requires a communications module In locating the communications module remember that the total length of all cable runs from an AKC 55 including stubs is limited to 5000 feet A single communications module will support up to 9 I O modules Power supply Use only a galvanically isolated class 2 power supply It is recommended that one of the 24 Vac Danfoss IOPS supplies be used either the 30 VA or 56 VA version depending on the total VA demand of the exten
11. and an NC normally closed screw Wire each load to be controlled to the module using a numbered group of 3 terminal screws Connect each load to common and to either NO or NC contacts For each digital output on the combination module record the unique two digit address of the lineup s communi cation module the single digit location of the I O module 1 for the module next to the communication module 2 for the next one and so on up to 9 and the terminal number point number to which the controlled load is wired Also record a description of the point wired to the terminal e g compressor A1 A form is provided with each new I O module for this purpose You will need this information when configuring the host controller The module s 8 analog inputs connect to the terminals opposite the relay output terminals Each input can be either an analog or a dry contact digital input High and low voltage input modules are separately available for sensing the presence or absence of current flows e g compressor contactors Sensor types that can be used with this module are the same as for the AK2 XM 101A analog input module and will be found in the next section which covers that module Connect analog inputs as shown on the facing page Resistive sensors with two wires are connected like the temperature sensor shown at left and sensors requiring an excitation voltage are connected like the pressure transducer shown at right When con
12. and for operational settings Use the procedure that follows From the controller s Main Menu select Configuration From the Configuration Menu select Refrigeration From the Refrigeration Menu select the rack with the EEPR valve you want to configure From the Configure Rack Menu select the suction group The Evaporator configuration screen will appear note There may be many evaporators For the purposes of this explanation we have created a suction group with a single circuit The Evaporator configuration screen appears at left below EEPR configuration is an option under circuit type AKC 55 so leave that field as is and select gt Setup lt The screen at right will appear except that the cursor will be on the Fixture Type field Configure Rack amp Suction d Evaporators Number of Circuits 1 Dewpoint method Cale Dewpt Humidity sensor to use Inside RH 1 Name Type Circuit AAL EO r Fixture Typtesesasosenes Box Fixture Name User Def Enter user defined name Circuit Monitor box door No Num case box sensors Temperature control po Target 35 0 F 2 0 F Type of defrost None PG DN for more Configure the fixture and sensor information as for any other circuit using the procedures given in chapter 4 of the AKC 55 System User s Manual Then move the cursor to the Temperature control field and press EN
13. off It may blink initially until communication with the host controller is established If steady on seek support from Danfoss The status LEDs should remain are ON for each point whose output relay is energized and OFF for each point whose output relay is de energized nA UC P2 oO J ms Status LED red co rJ Fold Ik ui OBB Coeli CO a p Me E OT gavom mo GRIO WE QUIPUT VOLTAGE SELECT Secondary SET JUMPERS W3 amp W4 FOR 12 OR 24 VOLTS SEE DETAIL BELOW O O aw OOo 12v Primary Ve y oc GE ro om OE PIN JG Da cau SET JUMPERS Wi amp W2 il 5 n ca For iis OR 290 VILTS elg Ul SEE EE PEL 115 230Vac GND N L 600 300 mATYPE i 2000 O usv O O Unit shipped for 230 VAC supply I POWER SUPPLY CUPS Bipolar stepper output module AK2 XM 208B Part No 08020022 S6VA Part No 080Z0052 AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 21 Configuring a Danfoss controller for an AK2 XM 208A EEPR stepper motor output module After installation of the hardware host controller software must be configured for the type of valve to be controlled
14. the single digit location of the EEPR module 1 for the module next to the communication module 2 for the next one and so on up to 9 and the terminal number point number to which each EEPR valve s leads are wired Also record a description of the valve wired to the terminal e g circuit B 4 or meat cases system 22 You will need this infor mation when configuring the host controller for the new valve s Power to operate controlled EEPR stepper motors is provided through the AK2 XM 208B Connect 24 Vac from a separate external Danfoss IOPS power supply to the power terminals on the AK2 XM 208B module An external IOPS 56 VA can supply up to 16 valves using 4 AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 20 AK2 XM 208B modules Reconnect power to the communications module When all connections are made and after replacing the terminal blocks to the module if necessary reconnect power to the communications module The AK2 XM 208A is now ready to configure Inspection of the installed digital output module When physical installation of an AK2 SM 208B stepper EEPR control module is complete you should be able to observe the following 1 The module is securely mounted to DIN rail or to a flat surface The module is connected to a communication module or to an existing lineup Power has been reconnected to the communication module The POWER LED is ON The COMM LED is
15. 0 sec 0 Alco ESR 20 12V 800 50 sec 0 Alco ESR 20 24V 800 50sec 0 For Alco valves the Max steps value depends on the date code of the individual valve Valves manufactured before 2001 have 500 max steps Also consult Alco technical documentation for details EEE EE ee Manufacturers may change valve specifications without notice Always check the settings in the following tables against information provided with each new valve by its manufacturer or contact the manufacturer s application engineering depart ment for the information The fields in the EEPR Setup screen are as follows Max steps 0 to 10000 The number of steps that corresponds with 100 opening of the valve Step rate 0 to 500 sec The rate at which the valve motor must be driven Step hysteresis 0 to 127 When a gear driven valve is at any given position driving a number of steps to a new position reversing direction and then driving back the same number of steps the valve may not return to the position it started from This phenomenon occurs because of backlash in the gear train To compensate hysteresis is programmed and works like this When a valve is driven open to a target position the controller will over drive the valve by the hysteresis amount then drive back in the closing direction by the same hysteresis amount The effect is taht regardless of the net change in valve position either more open or more closed
16. 01A half width analog input module provides 8 analog inputs for sensors and dry contact digital inputs Excitation voltages for inputs are furnished at 5V and 12V Mount the module by connecting it to a communications module or to an existing lineup Mounting instructions are supplied with the module and are also given in the section of this manual about the communications module All safety precautions normally used when wiring control systems and high voltage equipment should be observed Disconnect power from the communications module before wiring any extension modules in its lineup The module s 8 analog inputs connect to the terminals on the top and bottom of the module enclosure Each input can be either an analog or a dry contact digital input High and low voltage input modules are separately available for sensing the presence or absence of current flows e g compressor contactors The following types of sensors can be connected to the module Sensor type Temperature sensor Temperature sensor Temperature sensor Dewpoint sensor Pressure transducer Pressure transducer Pressure transducer Current transducer Current transducer Humidity sensor with AKS 11 temperature sensor Indoor outdoor photo sensor Temperature sensor Temperature sensor Temperature sensor Temperature sensor Sensor range Remarks 58 to 212 F 94 to 320 F requires VRS 1 interface board 0 to 100 F 0 100 psig 0 200 psig 0 500 psig 0 2
17. 5 0 50 or 0 75 A 0 100 0 150 or 0 200 A 10 95 RH 32 to 120 F 0 to 300 foot candles requires CTP KIT requires CTP KIT requires CTP KIT requires CTP KIT Connect analog inputs as shown on the facing page Resistive sensors with two wires are connected like the temperature sensor shown at left and sensors requiring an excitation voltage are connected like the pressure transducer shown at right When connecting a sensor with a 4 20mA output place a 250 ohm 1 4 watt precision resistor across the input terminals to be used When sensor cables have a required shield connect the shield to one of the two terminals labeled SHLD at the end of each half of the terminal strip Connect one side of a dry contact digital input pair to one of the terminals labeled A Al A2 etc and connect the other to one of the A A1 A2 etc terminals for excitation Remember to record that the input is a DI rather than an AI This information will be important when configuring the input at the host controller AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 14 Recording sensor information Inspection of the installed universal analog input module For each set of terminals on the universal analog input module record the unique two digit address of the lineup s communication module the single digit location of the I O module 1 for the module next to the communication module 2 for
18. EPR Stepper Motor Output Module sse pp 20 21 Configuring an AK2 XM208A EEPR Stepper Motor Output Module special requirements pp 22 25 Configuring AK2 I O Modules in an AKC 55 System important information for all modules p 26 What s different Board amp Pomt entries ettet tre teris tne xe ERR Ene Ep Ea E Pe Eee eror Torte a d p 26 Using AKC 55 Software with AK2 I O Modules sssssssssssseeeeee nennen nnne nnne nnns p 27 Specifications O AK2 MOGUIGS sui hermed er etat reete n trestemte pp 28 33 AK2 CM IOTA commu nications module reete toe Pere rete seede t ferte eret ee rabo Eee ER HERE MAR ERN p 28 AK2 XM 204A digital output module AK2 XM 205A combination AI DO module sess p 29 AK2 XM 101A Analog Input Module eese eene nnne nnne enne nnneenetnnn nennen teen nennen p 30 AK2 XM 102A low voltage digital input module esses nenne enne nennen en emen p 31 AK2 XM 102B high voltage digital input module sese meme ene p 32 AK2 XM 208B bipolar stepper output modules isisisi eeinetan enn enne kaeaea neti p 33 Code numbers ordering for AK2 modules ssssssssssssssssseeseseeenee nennen nennen snnt nnne p 34 AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 2 Installing AK2 Modules The AK2 series of I O modules form li
19. POLARITY CONNECT LEADS TO SIG AND GND y x 16 NO NC 2C NO NC 3C NO NC 40 NO NC NC Wire to normally closed load NO Wire to normally MAX OUTPUT RATINGS open load 1 4 HP 120 240VAC 5A RESISTIVE 24VDC OR 250VAC SC NO NC 6C NO NC 7C NO NC 8C NO NC pe de FUSED amp 5A SB 250VAC Shielded cable When sensor cables require a shield connect the shield to one of the two terminals labeled SHLD at the end of each half of the terminal strip Dry contact inputs Connect one side of a dry contact digital input pair to one of the terminals labeled A Al A2 etc and connect the other to one of the A A1 A2 etc terminals for excitation Remember to record that the input is a DI rather than an AI This information will be important when configuring the input at the host controller AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 11 Recording sensor For each analog on the combination module record the unique two digit address of the information lineup s communication module the single digit location of the I O module 1 for the module next to the communication module 2 for the next one and so on up to 9 and the terminal number point number to which the sensor is wired Also record a description of the sensor wired to the terminal e g suction pressure compressor A1 A form is provided on the rev
20. TER or left click A list box will open as shown at left below Move the cursor in the list box to EEPR and press ENTER or left click The screen will appear as at right below AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 22 Board amp Points Fixture Typ amp esee Box Fixture Name User Def Enter user defined name Circuit Monitor box door Num case box sensors N Temperature control REJ Target 35 0 F Type of defrost PG DN for more 11 02 46 Fixture Type sssrssessss Box Fixture Name User Def Enter user defined name Circuit Monitor box door No Num case box sensors 1 Temperature control BEER Target 25 0 F Type of defrost None PG DN for more Notice that once EEPR is selected the following Target line no longer shows a value often called a range or dead band since no dead band is required for a a modulating valve like a stepper EEPR Enter the target temperature Page down to the next page and specify defrost if any If there is an entry other than None you will have to select a condition Open Closed for the valve during defrost Configuration Return to the configuration menu select Board amp Points and choose the icon for variable outputs It is the fourth from left of the icons at the bottom of the screen The scre
21. been reconnected to the communication module The POWER LED is ON The COMM ERROR LED is OFF AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 15 Installing an AK2 XM 102A Low Voltage Digital Input Module The AK2 XM 102A half width low voltage digital input module provides 8 digital inputs rated at 9 to 80 Vac or Vdc Mounting Mount the module by connecting it to a communications module or to an existing lineup Mounting instructions are supplied with the module and are also given in the section of this manual about the communications module CAUTION All safety precautions normally used when wiring control systems and high voltage equipment should be observed Disconnect power from the communications module before wiring any extension modules in its lineup Digital inputs The module s 8 digital inputs connect to the terminals at the top and bottom of the module enclosure Connecting digital inputs Connect digital inputs as shown on the facing page Recording input For each set of terminals on the digital input module record the unique two digit address of the information lineup s communication module the single digit location of the I O module 1 for the module next to the communication module 2 for the next one and so on up to 9 and the terminal number point number to which the input is wired Also record a description of the input wired to the terminal e g oil fail A1
22. ded Belden 9841 AK2 Input Output Modules in AKC 55 Systenf464 9461 8768681 or equivalent 080R9208 RS 8C H5 22 4 EN j i MHOML3N JHL NO JNO ISVT IHL SI TInOON SNOILVOINYWWOO SIHL dl NMOHS SV SOLVNIAHAL AYOMLAN V SOV ld mel es OVA VZ JOON 1X3N OL LOANNOD I 5i pe anno z 16 ONnONO ANY OWA VZ j Gyros 3dON 1X3N OL 193NNOO Sy S31nQON NOISNV dX3 am JINON 02 JINON SNOLLVOINNNAOD
23. emperature 4 F to 1319 20 to 55 C 0 to 95 RH non condensing Storage Temperature 40 F to 158 F 40 to 70 C 0 to 95 RH non condensing Universal Inputs a Voltage Resolution 1mvV Accuracy 20 4 mV Q 0 4 Vdc Temp Coeff 0 4 mV C Accuracy 20 C 10 mV 4 10 Vdc Temp Coeff 1 4 mV C b Resistive Resolution 0 1Q Accuracy 1 2Q 10 400Q 0 4Q 400 1500Q 1 2Q 9 1500 23000 2 0Q 2300 25009 Temp Coeff 0 02Q C 10 1500Q 0 040 C 1500 23002 c Dry contact Contact cleansing current 120 mA for 0 1 msec Steady state current 10 mA Closed when contact resistance lt 200 Q d Ratiometric sensor AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 30 Denpi Specifications AK2 XM 102A digital input module low voltage UL file number E166834 E Low voltage digital inputs 8 d i Input rating 9 80 Vac or Vdc Power supply 18 36 Vdc 0 7 W oT iF supplied by communica 22228000 tion module El k Power required to communication module j 0 8 W 24 Vdc El cl rover I 1 0 VA Q 24 Vac m aa H j coMmeRROR NR Operating temperature EV 4 F to 131 F 20 to 55 C E iu m 0 to 90 RH non condensing z llis 8 16 4 F to 104 F 20 to 40 C Herm Deka Ve 0 to 95 RH non condensing pal of ser Ur qo Os 22 1 Storage Temperature NI bl
24. en that appears looks like the one at left below Enter the board amp point information module ad dress In the sample screen the address is 01 1 1 Yours will very likely be different Now select gt Setup lt and press ENTER and the screen at right below will appear Meet Lett Board Points Met Lett Board Points B Variable Outputs Stepper Setup Name Bd Pt Range Max Steps 4100 Boap r t co esecsemeres 200 Sec EEPR Circ l Max Steps gt Setup lt Step hysteresis 20 Overdrive at init 10 Manual failsafe 0 Max phase current EI Max holding current 20 gt Init Now SORT On s Bh ng HE pe The settings in the Stepper Setup screen are determined by the type of valve that is being configured and are given in the following tables Manual failsafe is explained in the text following the tables The sample has most of the data for a Danfoss valve taken from the first line of the table The table also contains information for other manufacturers valves AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 23 Step Overdrive Max phase Max holding Valve Type Max steps Step rate hysteresis at init current current Loo ob o Danfoss KVS 15 22 4100 300 sec 0 Danfoss KVS 28 35 5540 300 sec 0 eee ee HEEN eee Alco ESR 12 12V 500 or 800 50 sec 0 Alco ESR 12 24V 501 or 800 5
25. erride without terminal blocks Digital Input Modules Low Voltage 08020008 8 DI type AK2 XM 102B with override with standard terminal blocks 08020028 8 DI type AK2 XM 102B with override without terminal blocks Stepper Motor EEPR Valve Analog Output Module 08020022 8 bipolar EEPR AO type AK2 XM 208B Power Supplies 080Z0051 30 VA type IOPS 080Z0052 56 VA type IOPS AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 34 AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 35 ADAP KOOL Refrigeration Control Systems is a trademark of Danfoss A S www danfoss com Email ADAP KOOL Danfoss com Danfoss Inc Refrigeration amp Air Conditioning Division 7941 Corporate Drive Baltimore MD 21236 Tel 410 931 8250 Fax 410 931 8256 Direct Order Fax 410 931 0677 www acr danfoss com Danfoss shall not be responsible for any errors in catalogs brochures or other printed material Danfoss reserves the right to alter its products at any time without notice provided that alterations to products already on order shall not require material changes in specifications previously agreed upon by Danfoss and the Purchaser All trademarks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved Copyright 2002 2005 Danfoss Inc 080R9208 RS 8C H5 22
26. erse side of the form for the digital outputs for this purpose You will need this information when configuring the host controller Inspection of the installed combination module When a combination module is ready for operation you should be able to observe the following The module is securely mounted to DIN rail or to a flat surface The module is connected to a communication module or to an existing lineup Power has been reconnected to the communication module The POWER LED is ON The COMM ERROR LED is OFF The status LEDs reflect the status of the output relays The LED should be lit for each point whose relay is energized 7 The override LEDs reflect the status of the override switches The LED should be OFF for each switch in the center AUTO position The LED should be ON for each switch in the left OFF or right ON position ON tA 4 C2 b2 AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 12 AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 13 Installing an AK2 XM 101A Universal Analog Input Module Mounting CAUTION Universal Analog inputs Compatible sensors Sensor name AKS 11 AKS 12 THERM 3 DPS 100 AKS 32 100 AKS 32 200 AKS 32 500 CT 12 CT 13 CT 14 CT 15 EMHS3 PHOTO OD 1 ComTrol CTTS ECI TP 1 ECI TP 2 CPC 501 1121 Connecting analog inputs 4 20mA inputs Shielded cable Dry contact inputs The AK2 XM 1
27. le parts in the modules and when modules are in service the covers should always be in place Mount the module by connecting it to a communications module or to an existing lineup Mounting instructions are supplied with the module and are also given in the section of this manual about the communications module All safety precautions normally used when wiring control systems and high voltage equipment should be observed Disconnect power from the communications module before wiring any extension modules in its lineup Observe the cautions stated above Terminal blocks can be removed from the module for making connections Connections to the module are in groups of three as shown in the illustration Each group has a C common screw numbered from I to 8 an NO normally open screw and an NC normally closed screw Wire each load to the module using a numbered group of 3 terminal screws Connect each load to common and to either NO or NC contacts For each digital output module record the unique two digit address of the lineup s communi cation module the single digit location of the I O module 1 for the module next to the communication module 2 for the next one and so on up to 9 and the terminal number point number to which the controlled load is wired Also record a description of the point wired to the terminal e g compressor A1 A form is provided with each new I O module for this purpose You will need this informati
28. necting a sensor with a 4 20mA output place a 250 ohm 1 4 watt precision resistor across the input terminals to be used AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 10 TEMPERATURE SENSOR NO POLARITY AKS 11 CONNECT LEADS TO SIG AND GND PRESSURE TRANSDUCER AKS 32 BLACK GND WHITE SIG RED 12V 7 SHIELD SHLD ED TERMINAL SIG OUTDOOR RH SENSOR EMHS 4 TERMINAL GND TERMINAL 12V INDOOR RH WITH TEMP SENSOR 1 EMHS 3 QOUOD C 0000 00 00 Q0 0 000 0 O0 0 OO 0 0 0 0 D D C2 RH Ait At AZ AZ AGH A Ade Ad HAV AV shid shd ASt AS AG AB ATH AT AGH AB HAV SV shld sh ENG LE TEN cal H TERMINAL SIG V m f V TERMINAL 12V POWER OVERRIDE E TEMP T1 AND T2 NO POLARITY 1 CONNECT TO SIG AND GND m COMM ERROR OVR1 mi LJ sta OVR2 a u m2 m2 QVRS i Igea on OUTDOOR PHOTO WITH TEMP SENSOR EE J PHOTO OD 1 aid md OVR5 an PHOTO m5 m5 OVR6 VEE 12VAC OR DC wer ag EE over E VAC OR DE EXTERNALLY SUPPLIED ADARKODE PHOTO OUT SIG SIG pu 7 87 AK2 XM 205B ove il a m Jj PHOTO OUT GND GND cl s 8 No 08020030 OFF AUTO ON Lrj REAY OVERRIDE Extension 28 900 m TEMP BROWN AND WHITE LEADS NO
29. neups with each lineup having a single user addressed communications module and up to nine self addressing I O modules of any assortment These lineups become groups of nodes on an AKC 55 based supermarket control and monitoring system The modules are physically linked by means of connectors at each end of each module The connector holds the modules together and makes the electrical connections between them All power and network connections are made through the module connectors with only the communications module in each lineup having a power cable and a network cable to the system s I O network Fuses Each module has a black cover with an identification label There are fuses in the communica tions modules and in modules that have digital outputs The fuses are reached by removing the module cover Except for the fuses there are no user adjustments or user serviceable parts in the modules and when modules are in service the covers should always be in place The types of AK2 I O modules are the following Module name Description Inputs and outputs provided Power AK2 CM 101A communications module AK2 XM 204A digital output module 8 relay outputs 3 0 W 3 7 VA AK2 XM 205A universal analog input amp digital output module 8 relay outputs 8 universal inputs 3 9 W 4 8 VA AK2 XM 101A universal input module 8 universal analog inputs 1 3 W 1 5 VA AK2 XM 102A digital input module low voltage 8 digital inputs 9 80Vac or Vdc 1 W 1 25
30. nications module 3 9 W 24 Vdc 4 8 VA 24 Vac 4 Iss SU Operating temperature 4 F to 1319 20 to 55 C 9 0 to 9596 RH non condensing Storage Temperature 40 F to 158 F 40 to 70 C 9 0 to 95 RH non condensing Universal Inputs a Voltage Resolution 1 mV Accuracy 20 4 mV 0 4 Vdc Temp Coeff 0 4 mV C Accuracy 20 C 10 mV 4 10 Vdc Temp Coeff 1 4 mV C b Resistive Resolution 0 1Q Accuracy 1 2Q 10 4000 10 40 400 1500Q 1 2Q 1500 23000 2 0Q 2300 25000 Temp Coeff 0 020 C 10 1500Q 0 040Q 1500 23000 c Dry contact Contact cleansing current 120 mA for 0 1 msec Steady state current 10 mA Closed when contact resistance lt 200Q d Ratiometric sensor AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 29 Done Specifications AK2 XM 101A analog input module mi lt G V G 2 1 J 2oooo000000Q0Q0 dr hl M TI re n e Li NW POWER r L q ig m COMM ERROR pl In LE 7 7 ADAP KOOU EE Lj B AK2 XM 101A aru Lj Ex No 08020027 H Lm Extension 8Al Un m 7 C i se tj La ON UL file number E166834 Universal inputs 8 Sensor excitation 5 or 12 Vdc 100 mA Excitation fusing auto reset 200 mA Power supply 18 36 Vdc 1 1 W supplied by communication module Power required to communication module 1 3 W 24 Vdc 1 5 VA 24 Vac Operating t
31. nnected to a communication module 3 Power has been reconnected to the communication module 4 The POWER LED is ON 5 The COMM ERROR LED is OFF 6 The status LEDs through 8 correctly reflect the operating status of the equipment being monitored AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 18 POSITIVE 80 260 VAC NEGATIVE 80 260 VAC 0000 0 0 0 HL POWER r COMM ERROR mi m2 3 ADAP KOOL Oy 7 AK2 XM 102B ma No 080Z0020 j 4 DIGITAL Extension BDIH INPUT AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 19 Compatible valves Disconnect power from the lineup Mounting CAUTION Connecting leads from EEPR valves Recording board and point information Connecting 24 Vac valve power Installing an AK2 XM 208A EEPR stepper motor output module The AK2 XM 208A EEPR stepper motor output module provides 4 bipolar outputs for control of stepper motor EEPR valves supplied by Danfoss and certain other manufacturers see table below This module is compatible with Danfoss AK2 SC 255 and AKC 55 system controllers The AK2 XM 208A EEPR stepper moter output module can be supplied in two 1 without terminal blocks 2 with Phoenix type terminal blocks Electrical data is found in the specifi cations toward the end of this manual The AK2 XM 208A ou
32. ommunications module to one of the I O network terminal blocks on the host AKC 55 rack controller A communica tions module can also be connected in a daisy chain to the network terminals of another node on the AKC 55 s I O network There is no need to observe any particular polarity with the A and B wires when making network connections Connect the shield to the terminals marked shield at both ends of every TP78 communica tions cable If the communications module is the last unit on the cable run place a network terminator across its A and B terminals Network terminators are supplied with an AKC 55 across each set of NETWORK terminals If you are rebuilding an I O run you should find a terminator across the A B terminals of the last node on the network Power connection With main power to the communications module interrupted connect the 24V terminals and ground of the power supply to the three corresponding terminals of the communications module Make sure to use a supply with a VA rating adequate for the modules being con nected Module power ratings are given on page 3 Wiring of the communications module is now complete Inspection of the installed Communication module When a communication module is ready for operation you should be able to observe the following proceding clockwise around the module from the power terminal strip Power connections have been made 2 Address switches have been set to a valid unique addre
33. on when configuring the host controller When all connections are made and after replacing the terminal block if necessary reconnect power to the communications module When a digital output module is ready for operation you should be able to observe the following The module is securely mounted to DIN rail or to a flat surface The module is connected to a communication module or to an existing lineup Power has been reconnected to the communication module The POWER LED is ON The COMM ERROR LED is OFF The status LEDs are ON for each point whose output relay is energized and OFF for each point whose output relay is de energized 7 The override LEDs reflect the status of the override switches The LED should be OFF for each switch in the center AUTO position The LED should be ON for each switch in the left OFF or right ON position AAKQRN AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 8 RELAY m POWER OVERRIDE r4 a m COMM ERROR OVRI n mi mi OVR2 ral az m2 owns m3 m3 OVR4 m4 m OVR5 m5 ms Don fit OVRS m6 m6 OVR7 1 ADAP KOOIS F IM seer AK2 XM 205B OVRE ER m8 m8 No 08020030 OFF AUTO ON by I j RELAY OVERRIDE Extension BAIBDO CT I l rn 5 NC Wire to normally closed load NO Wire to normally MAX OUTPUT RATINGS open load 1 4 HP 120 240VAC 5A RESISTIVE 24VDC OR 250VAC
34. put board amp point screen Mestere Board amp Points T Sensor Inputs Name Bcast Bd Pt Type Inside Temp No 01 1 1 PT1000 Disch Press C No 02 1 1 AKS32 500 Dropleg Temp C No 02 1 2 PT1000 Inlet Temp C No 02 1 3 PT1000 Suction Temp CA No 02 1 4 PT1000 Suction Pres CA No 02 1 5 AKS32 200 Oil Press CAL No 02 1 6 AKS32 200 Outside Temp No PT1000 SORT On PG DN for more a M M To make an entry in the board amp point screen you will need the address information you recorded while installing the individual I O modules On the Board amp Points screen enter for each point the two digit communications module address first A hyphen automatically appears Then enter the single digit position number for the extension module then the two digit point number The point number can be entered as 01 or as 1 but the entry will always display as in the screen shown above Either three character configuration or four character board amp point numbers will be accepted by the AKC 55 because traditional IO boards require three character addresses as detailed in chapter 4 of the AKC 55 System User Manual and AK2 points require the four character addresses described here If any other number of characters is entered the entry will be rejected and zeros will appear AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 Using AKC 55 Software 26 AK2 Input Output Modules in AKC 55 Systems 06 05
35. red tabs to release them and lock the module in place Screw mounting When mounting on a flat surface with screws mount the communications module first using the screw slots Then connect the first extension module and secure it is advisable to connect the modules first then position the entire lineup of modules and mark the screw holes After drilling the holes mount with panhead screws or bolts Installing a communications module Cabling requirements A communications module has one of three types of transceiver TP78 EIA 485 or FTT The AKC 55 I O network uses the TP78 protocol In an AKC 55 system communications modules with TP78 transceivers code number 08020061 are required No other type of communications module will function Use 20 to 24 AWG stranded twisted shielded Belden 9841 9464 9461 8762 8761 or equivalent Place a terminator across the network terminals on the last communications module on any cable run from the AKC 55 Use the drawing on the facing page for reference while wiring to an AKC 55 system Other transceiver types The communications module when not used with AKC 55 systems is available with two other transceiver types Those types and their cabling requirements are FTT transceiver Code number 08020062 Use 16 AWG stranded twisted Belden 85102 or equivalent Do not use shielded cable with this transceiver EIA 485 transceiver Code number 08020063 Use 20 to 24 AWG stranded twisted shiel
36. sible cause 1 Automatic address No working modules found assignment failed Module limit exceeded 2 Unable to retrieve self Software error in one or more identification record I O modules from one or more modules 3 Upper memory buffer Maximum number of input boundary exceeded points 80 exceeded 1 2 3 Host communication Host AKC 55 is offline timeout Every hour the communications module performs a check with all the extension modules in its lineup During this check less than 1 4 second the ERROR LED on the communications module will light This is normal and does not indicate any malfunction Installing an AK2 XM 204 digital output module AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 7 Fuses Mounting CAUTION Connecting loads Recording digital output information Inspection of the installed digital output module The AK2 XM 204 digital output module provides 8 fused digital outputs each output can be wired to normally open NO or normally closed NC relay contacts This module is available with or without override switches and can be supplied in three terminal block variations 1 without terminal blocks 2 with Phoenix type terminal blocks and 3 with Euromate type terminal blocks Electrical data is found in the specifications toward the end of this manual Fuses are reached by removing the module cover Except for the fuses there are no user adjustments or user serviceab
37. sion modules in the lineup Part numbers for ordering IOPS power supplies are given on the last page of this manual In selecting a power supply be certain to check the total power requirements in VA using the table above When a Danfoss IOPS is used it can be located up to 50 feet from the communications module it is powering AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 3 Use 16 or 18 AWG wire when connecting power to the communications module Fuses Fuses are reached by removing the module cover Except for the fuses there are no user adjustments or user serviceable parts in the modules and when modules are in service the covers should always be in place Mounting modules All AK2 modules offer two mounting options DIN rail mounting and screw mounting All of the modules in a lineup must be mounted in the same way DIN rail mounting For DIN rail mounting first mount the rail with a minimum of 2 1 4 inches clearanceon each side Open the first module s red tabs by using a small screwdriver as shown in the drawings below until the tabs snap open Then position the module by slipping it over the rail hold it in place and press the red tabs The module will be securely mounted To mount the second and subsequent modules on a DIN rail open the red tabs as shown below Position the new module so that the connectors are engaged and gently push the module toward the rail until it is seated Then press the
38. ss from 001 to 099 3 Connection has been made to an I O network terminal of an AKC 55 at the NETWORK terminals or to the network terminals of another node on the AKC 55 s I O network AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 6 4 If this module is the last node on an I O cable run make sure that it is terminated by using one of the terminators supplied with the AKC 55 The terminator should be placed across the A and B terminals at the network connection on the communication module 5 If functioning is normal the first five status LED states shown below under Error LED OFF will occur in order The module will go through these states any time power is interrupted and reapplied Software configuration of I O points is done from the AKC 55 or a PC and is covered in the section titled Configuration Error and Status LEDs The Error and Status LEDs indicate the following conditions when there is power to a commu nications module on the I O network and a lineup of I O modules is connected Error LED OFF Status LEDs ON Meaning 1 briefly Powering up 2 Local bus initialized waiting for host acknowledgement 3 Connection to host established Receiving configuration 1 2 3 briefly Communications module configured 1 blinking 2 3 on Running all modules operational Error LED blinking I blinking 2 3 on Running one or more modules offline Error LED ON Status LEDs ON Description Pos
39. the next one and so on up to 9 and the terminal number point number to which the sensor is wired Also record a description of the sensor e g suction pressure compressor A1 A form is providedwith each new module for this purpose You will need this information when configuring the host controller TEMPERATURE SENSOR NO POLARITY AKS 11 CONNECT LEADS TO SIG AND GND PRESSURE TRANSDUCER AKS 32 BLACK GND WHITE SIG RED 12V SHIELD SHLD m POWER COMM ERROR Zhu ADAP KOOL AK2 XM 101A No 08020027 Extension 8AI Ale Al AZt A2 ABE Ab Ade Ab HAN SV shid shid ooooo00000 ZI M A OUTDOOR RH SENSOR EMHS 4 TERMINAL GND TERMINAL SIG TERMINAL 12V INDOOR RH WITH TEMP SENSOR EMHS 3 RH G TERMINAL GND H TERMINAL SIG V TERMINAL 12V TEMP T1 AND T2 NO POLARITY CONNECT TO SIG AND GND OUTDOOR PHOTO WITH TEMP SENSOR PHOTO OD 1 PHOTO 12VAC OR DC 12VAC OR DC EXTERNALLY SUPPLIED PHOTO OUT SIG SIG PHOTO OUT GND GND TEMP BROWN AND WHITE LEADS NO POLARITY CONNECT LEADS TO SIG AND GND When a universal analog input module is ready for operation you should be able to observe the following Und WN Ke The module is securely mounted to DIN rail or to a flat surface The module is connected to a communication module or to an existing lineup Power has
40. tput module is compatible with the following stepper moter EEPR valves Danfoss Alco Sporlan KVS 15 22 ESR 12 12V CDS 8 12V KVS 28 35 ESR 12 24V CDS9 12V ESR 20 12V CDS 16 17 12V ESR 20 24V Before installing any new module disconnect power from the lineup s communication module Do not reconnect power until by following these instructions the installation including the final inspection has been completed Mount the AK2 XM 208A module by connecting it to a communications module or to an existing lineup Mounting instructions are supplied with the module and are also given in the earlier section of this manual about the communications module All safety precautions normally used when wiring control systems and high voltage equipment should be observed Disconnect power from the communications module before wiring any extension modules in its lineup Observe the cautions stated above There are connectors for four valves on each module Terminal blocks can be removed for making easy connection of wire leads from valves Each compatible EEPR valve has four leads red white black and either green or blue Remove the terminal block from an unused valve position on the module Loosen the connec tor screws Now connect the valve leads to the terminal block in accordance with the key printed on the module housing For each EEPR control module record the unique two digit address of the lineup s communi cation module
41. up Mounting instructions are supplied with the module and are also given in the section of this manual about the communications module CAUTION All safety precautions normally used when wiring control systems and high voltage equipment should be observed Disconnect power from the communications module before wiring any extension modules in its lineup Digital inputs The module s 8 digital inputs connect to the terminals on the top and bottom of the module enclosure Connecting Digital inputs Connect digital inputs as shown on the facing page Recording input For each set of terminals on the digital input module record the unique two digit address of the information lineup s communication module the single digit location of the I O module 1 for the module next to the communication module 2 for the next one and so on up to 9 and the terminal number point number to which the input is wired Also record a description of the input wired to the terminal e g compressor A1 A form is provided with each new module for this purpose You will need this information when configuring the host controller Inspection of the installed Low voltage digital When a high voltage digital input module is ready for operation you should be able to observe input module the following 1 The module is securely mounted to DIN rail or to a flat surface 2 Connection has been made to a communication module or to another module that is already co
42. ut Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 9 Mounting CAUTION Digital outputs Connecting loads Recording digital input information Universal analog inputs Compatible sensors Connecting analog inputs 4 20mA inputs Installing an AK2 XM 205A Combination Digital Output and Universal Analog Input Module The AK2 XM 205A combination digital output and analog input module provides 8 fused digital outputs and 8 universal analog inputs Each output load can be wired through normally open NO or normally closed NC relay contacts This module is available with or without override switches and with two types of terminals both of which can be seen in the illustration that follows Excitation voltages for inputs are furnished at 5V and 12V Mount the module by connecting it to a communications module or to an existing lineup Mounting instructions are supplied with the module and are also given in the section of this manual about the communications module All safety precautions normally used when wiring control systems and high voltage equipment should be observed Disconnect power from the communications module before wiring any extension modules in its lineup Loads are connected as described in the previous section for digital output modules Connec tions to the module are in groups of three as shown in the illustration Each group has a C common screw numbered from to 8 an NO normally open screw
43. x holding current 0 to 70 The percentage of Max phase current required by some stepper valves to hold the valve at its most recently achieved position The module resolves the programmed value to the nearest 10 Valve in defrost List box Closed Open the position the valve should maintain during defrost AK2 Input Output Modules in AKC 55 Systems 06 05 1 080R9208 RS 8C H5 22 25 Configuration The AK2 XM 208A requires Board amp Points configuration as an analog output board in accordance with the information in the following section under What s different Configuring other AK2 I O Modules in an AKC 55 System Configuration of points on AK2 modules is almost exactly the same as for other points in an AKC 55 system Consult chapter 4 of the AKC 55 System User s Manual What s different There is one difference in configuration When entering the board and point information for an AK2 point there are five characters to enter That is why you recorded for each point a the communications module address 2 digits from 01 to 99 the leftmost switch is not used and remains set to zero b the I O module position 1 digit from 1 to 9 c the point number 1 digits from 1 to 8 note that on combination modules there are two sets of points digital outputs and universal analog inputs each set numbered from I to 8 one set is entered in the digital output board amp point screen and the other in the sensor in