User`s manual - Xtreme Power Conversion
Contents
1. INPUT Capacity Voltage range Frequency Povver factor Harmonic distortion lt 3 at linear load 208VAC nominal 200 220 230 240VAC selectable 3 1 10596 15056 for 160 sec 2 cycles before switching bypass OUTPUT Rated voltage Crest factor Overload capacity Efficiency 97 ECO mode 91 online mode Sealed maintenance free lead acid BATTERY Battery type Battery quantity and size 20 12V 7AH 20 12V 9AH Terminal blocks or optional PDU 11 4 x 25 4 x 29 5 in PHYSICAL Input output Dimensions W x D x H Weight OPTIONAL Battery quantity and size 190 Ibs 223 Ibs EBP920 20 12V 9AH EBP940 40 12V 9AH EBP960 60 12V 9AH BATTERY PACKS Dimensions W x D x H 11 4 x 25 4 x 29 5 in Weight EBP920 254 Ibs EBP940 364 Ibs EBP960 474 Ibs 6 ft L6 30P Terminal blocks OPTIONAL PDU Input connection Receptacle options L6 30R L6 20R L6 15R 6 15 20R C19 32 104 F 0 40 C 0 9596 non condensing lt 50dBA ENVIRONMENT Temperature Humidity Audible noise Altitude APPROVALS 11 500 ft above sea level UL1778 cUL CE FCC Class A ROHS Depending on load level Xtreme Power Conversion Corporation Page 29 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Obtaining Service If the UPS requires Service 1 Use the TROUBLESHOOTING section in this manual to eliminate obvious causes 2 Verify there are
2. INPUT UPS LOAD I UPS output voltage M INPUT UPS LOAD A z UPS output frequency N INPUT UPS LOAD A UPS output load level O INPUT UPS LOAD gt 3 Bathory Battery voltage Xtreme Power Conversion Corporation Uninterruptible Power Supply Page 17 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply UPS inner temperature Viewing the UPS Default Settings e After the UPS completely starts up press the o function key to change the LCD display to figure Q1 Q1 Q2 Buzzer Off e Press the key to scroll through the UPS settings The LCD will display in sequence figure Q1 buzzer gt figure R Self test gt figure S Bypass Voltage Windows gt figure T Output Frequency Synchronization Window gt figure U Inverter Output Voltage gt figure V UPS Operation Mode gt figure W Output Volt age Micro Tune Value gt figure X UPS Id gt figure Y Parallel function status e Buzzer and Self test can only be changed in this mode while the UPS is on All other settings must be changed while the inverter is off in this mode See Changing the UPS Default Settings on page 22 e Default settings shown below Teuira Self test is not On Use the 2 key to toggle the setting and then save Xtreme Power Conversion Corporation Page 18 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply S T U Inverte
3. 254 Ibs 364 Ibs 474 Ibs Xtreme Power Conversion Corporation Page 39
4. e If there is a serious abnormal condition the UPS will lock itself in the OFF position as shown in figure AA and an abnormal message will appear on the LCD e After three seconds all messages will be locked except Bypass messages LED CJ2 and LCD ee If the Utility is abnormal after the UPS is locked the LED CJ 2 will be extinguished and the LCD will appear on the LCD e To release the UPS lock proceed as follows 1 Check the recorded error messages 2 Check the error messages in the Troubleshooting guide to help troubleshoot the problem For further help consult your local distributor 3 Press the Off key for five seconds A buzzer will sound twice 4 Turn Off the Utility Input breaker 5 Even if the UPS lock problem is solved now consult with your local distributor to make sure that the error condition is resolved Shut Off 1 Press the Off key for five seconds The Inverter output will be turned off and the output load will be supplied by the Bypass loop The LCD will display figure B 2 Turn Off the Utility and Bypass Input breakers 3 The UPS is now turned off completely Maintenance Bypass Mode 1 Maintenance Bypass Mode is for UPS maintenance only Only authorized technicians are allowed to perform the following procedures If there is any damage during unauthorized execution of these pro cedures your warranty will be void immediately Press the Off key for approximately five seconds Th
5. Check for proper battery connection then re charge the batteries for 8 hours to see whether the UPS provides backup power normally other wise consult your local distributor right away ErO5 bow amp If CB3 is tripped turn off the UPS completely and keep the CAM switch at position INV before pressing CB3 Then remove some uncritical load at the UPS output end If there is any damage to the insulation of the AC power cord please replace it with a new one Remove the short circuit at the EPO terminal Remove any objects blocking the ventilation Er14 Check that the cooling fans on the rear panel are working normally Make sure the UPS is operated normally If it is Er15 in CVCF mode you must turn off and turn on the UPS again Er16 Er27 All of the parameters except ID Number in a parallel UPS must be the same Er21 Disconnect and reconnect the RJ45 connector or set a UPS with ID 1 When the UPS is in CVCF mode it is prohibited Er24 from having bypass input You must turn off the UPS and bypass input and then restart the UPS Other error code Consult your local distributor for help If the backup power time is still too short after Er06 Er10 Er12 Er28 amp UPS fails to offer battery back up or its backup power time is shorter than calculated 8 hours of charging please contact your local distributor for battery replacement UPS locks itself and cannot be Restart UPS Consult your local dis
6. Siscoverheated En PS Output Overloading RE Fan Error EB Wrong Procedure to Enter Maintenance Mode 3 EtG Output Parameters Set Error in Parallel System in single unit a e TE ed or failure to find ID1 RD in Parallel System 36 fre CVC mode with Bypass input Ca Th PS at operated in nora rode in Pare Star 38 Erg Bypass Overload Time out and cut off output IE ee Control board and driver board settings do not match CI Other Error code The specified modes include Normal mode ECO mode CVCF mode etc Xtreme Povver Conversion Corporation Page 9 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Panel Explanations Front Panel 8 9 10 11 12 1 LCD 2 Green LED indicates that the UPS is able to run under redundancy mode a Solid green LED indicates that the utility input voltage is vvithin the acceptable vvindovv Flashing green LED indicates that the utility input voltage is outside the acceptable vvindovv Green LED indicates that Bypass Input is normal UPS ON Alarm Silence Go to previous page or change the setting of the UPS Confirm a changed setting Go to the next page UPS OFF Svvitch 10 Special functions log in out 11 UPS is working under ECO Economy mode 12 UPS Fault or Abnormal VOND P TT TT OE Normal si Tripa di 7 et RS 232 Port Terminal Resistor for Parallel function CAN Bus Conne
7. Voltage Possible values are 200 208 220 230 or 240 VAC The inverter output voltage needs to match the input voltage for this system e Figure V indicates the operation modes of the UPS Possible values are Online Eco Economy mode fixed 50 Hz Output and fixed 60 Hz Output e Figure W indicates the adjustment of the Inverter Output voltage which may be set to 0 1 1 2 2 3 or 3 e Figure X indicates the position of the UPS when the UPS is in Parallel mode Possible positions are 1 2 3 and 4 The position must be 1 if the UPS is not in Parallel mode e Figure Y indicates the parallel function status P 01 indicates that the parallel function is disabled and P 02 indicates that the parallel function is enabled e After changing settings you must scroll to the SAVE screen figure Z and then press the enter o key to save all of your changes Then the LCD vvill display figure AA to indicate completion of the setting changes To cancel your changes rather than save them press and hold the OFF key 0 for five seconds The LCD displays figure AA directly which indicates that your changes were canceled Xtreme Power Conversion Corporation Page 20 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply AA The UPS is locked e Turn Off the Utility Input Breaker e Your setting changes are now complete e Restart the UPS Troubleshooting when the UPS is Off Due to Unknown Reasons
8. follows 2400 bps Data Length Pin Assignments The Pin Assignments of true RS 232 are as follows The connector is male Pin 3 RS 232 Rx Pin 2 RS 232 Tx Pin 5 Ground Xtreme Power Conversion Corporation Page 11 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Installation And Operation Carefully inspect the UPS for shipping damage before installation Retain the packing material for future use Unpacking Standard package contents Quick start guide User manual Upsilon 2000 software CD 4 Small Phillips head screws RS 232 cable Optional skirt assembly including 2 22 3 4 side skirt 2 11 5 front and rear skirt and 1 plastic skirt Selecting Installation Position Install the UPS in a proper environment to minimize the possibility of damage to the UPS and to extend the life of the UPS Please follow these requirements 1 Li Vt ad Keep at least 12 inches clearance from the rear panel of the UPS to the wall Keep at least 8 inches clearance from the rear panel of the External Battery Pack EBP to the wall Refer to the T90 EBP920 EBP940 EBP960 user manual for more details Do not block the air flow to the ventilation openings of the unit Ensure that the installation site is not excessively hot or moist Do not place the UPS in an environment near dust corrosive or salty material or flammable objects Do not expose the UPS to the outdoors Relative humidly non
9. reserves the right to contact the authorized service center directly to discuss repair costs and damage to the Connected Equipment to determine if it was caused by a Power Disturbance and the right to request that the service center forward the Connected Equipment or components of the Connected Equipment to XPC for inspection 5 Unless modified in writing signed by an officer of XPC and the Purchaser the terms of this policy are the com plete and exclusive agreement between the parties superseding all prior agreements oral or written and all other communications between the parties relating to the subject matter of this agreement No employee of XPC or any other party is authorized to make any representations beyond those made in this agreement con cerning the Load Protection Policy XPC Corporation 230 Yuma Street Denver CO 80223 1 800 582 4524 Xtreme Power Conversion Corporation Page 34 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Appendix A T90 EBP920 EBP940 EBP960 User Guide Important Safety Instructions Save These Instructions This manual contains important instructions that should be followed during installation and maintenance of the battery bank and batteries An Important Notice e This battery bank is connected to an UPS There will be over 240 DC voltage at the output terminals if the UPS or DC breaker is turned on e Do not try to repair the unit yourself contact your local supplier or you
10. Do not open the case as there are no serviceable parts inside Opening the case voids the warranty e Do not try to repair the unit yourself contact your local supplier Repairing the unit yourself voids the war ranty e Please make sure that the input voltage of the UPS matches the supply voltage e Use a certified input power cable with the correct plugs and sockets for the appropriate system voltage e To prevent any overheating of the UPS keep all ventilation openings free from obstruction and do not store things on top of the UPS Keep the UPS 30 cm away from the wall e Ensure that the UPS is installed within the proper environmental range 0 40 C and 0 90 non condens ing humidity e Do not install the UPS in direct sunlight Your warranty may be void if the batteries fail e Install the UPS indoors as it is not designed for installation outdoors e Dusty corrosive and salty environments can damage any UPS e Install the UPS away from objects that give off excessive heat and areas that are excessively wet e If liquids are spilled onto the UPS or foreign objects dropped into the unit the warranty will be null and void e The battery will discharge naturally if the system is unused for a long period of time e The UPS should be recharged every 2 3 months if unused If this is not done then the warranty will be null and void When installed and being used the batteries will be automatically recharged and kept in top condition e Do
11. OCIATED EQUIPMENT LOSS OF SOFTWARE COST OF CAPITAL COST OF ANY SUBSTITUTE EQUIPMENT FACILITIES OR SERVICES DOWNTIME THE CLAIMS OF THIRD PARTIES INCLUDING CUSTOMERS AND INJURY TO PROPERTY Submitting a Load Protection Policy Claim 1 Any claim under the Load Protection Policy must be made within 10 days of the date of alleged damage to the Connected Equipment 2 Call the XPC technical support department at 1 800 582 4524 and obtain a Load Protection Policy Returned Material Authorization RMA number Have information on all applicable insurance or other resources of re covery payment that is available to the Purchaser and the name of the power utility supplier for the location of the Connected Equipment XPC will forward to the Purchaser a Load Protection Policy claims form which Xtreme Power Conversion Corporation Page 33 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply must be completed and filed with XPC within 30 days Mark the Load Protection Policy RMA number on the Product the Purchaser is returning Pack the Product in its original packaging or similar packing materials if the original packaging has been discarded Enclose the completed Load Protection Policy claim form and a copy of the Purchas er s original sales receipt for the Product in the box Mark the RMA number clearly on the outside of the box Ship the Product one way shipping charges paid by the Purchaser to XPC Corporation 230 Yuma
12. Street Denver CO 80223 Attn LPP RMA 3 XPC will evaluate the Product to determine its level of functionality and will examine the Product for evidence of damage from a Power Disturbance If XPCs evaluation provides no evidence of damage from a Power Disturbance XPC will send to the Purchaser i a report summarizing the tests performed and ii a rejection of claim notice If the Product shows evidence of damage from a Power Disturbance XPC will request that all Con nected Equipment for which a Load Protection Policy claim has been submitted be sent for evaluation to either XPC or an authorized service center If it is determined that the Connected Equipment has been damaged by a Power Disturbance XPC will in its sole discretion issue payment to the Purchaser for either the cost of repair of the Connected Equipment or the Fair Market Value of the damaged Connected Equipment up to the dollar limits stated above XPC reserves the right to require the Purchaser to transfer title and deliver the Connected Equipment to XPC if it chooses to reimburse the Purchaser for the fair market value of the Connected Equipment XPCs maximum liability shall be reduced to reflect all such other payments or sources of recovery whether applied for or not 4 If XPC issues payment to the Purchaser to have the Connected Equipment repaired the repair must be per formed at a service center that is authorized by the manufacturer of the Connected Equipment XPC
13. T90 6kVA amp 10kVA Online UPS 6kVA 10kVA Models User amp Installation Manual www xpcc com 2015 Xtreme Power Conversion Corporation All rights reserved Rev 5 26 15 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Table of Contents Safety Instructions And Battery Care cccsscscscscsccccccccccccscscsccccccccscccscsces 4 SIGUIS EU ON essencial E AAS 4 BOEN C sateen aca E E E E 5 Productnr oduc DO Nceaeemetsammstesesmtaseigianmsimemesssebitaoit anem 6 GG ECO CPi POLIS ENC 5 erem S e E A E deca 6 Symbols on the LCD Display PAE teeceotsttmemttemtt uts tom acenatmastmomsstenttce taments ee 8 PP AION INIO iter ceca E A A A E 10 Se nee Ola eclale ah PO err E E E eT 11 Installation And Operation ssesessscesescecescecescecesoscesoscecoscessscesessesescesesseo 12 VC HNN aee E E A E E ties 12 Selecting Installation POSItoOn e essssesesssserssrresrrssessresrrssrrsrrssrrsrresresrerseesreseeeseeseeeseeseeeseeseeseerseeee 12 Terminal Block Explanatio usisero N EEA PEIE N E 12 Mipu OU POU ECON CURS NO asasinii AE E E E AEE 13 Start Upin Normal MOE ceiesiesniarisnsd eini EAE EREE A E S N site 14 Check Measured Values and Figures Detected by the UPS ssssssssessensseesseesseessressseessessserssereseee 16 Viewing the UPS Default SOTO GS encisscccviadacnrtaassstiosennocdsacedatsendtonssedaesasaeesinbsa diodes lt iasearidadsdaceanetaatanes 18 Changing the UPS BY F210 1h apes EEES etat ne ee ne ee S
14. ange from figure A to figure G for approximately 15 seconds e Press the UPS On switch again for about three seconds until the LCD display changes from figure G to figure H Then the UPS will be in self test mode The UPS may offer energy to the output in a minute and the LCD displays figure I In case of failure in pushing the UPS On switch for 15 seconds the UPS will auto matically turn off You must then repeat steps r Off which means the UPS pre start was successful Xtreme Power Conversion Corporation Page 15 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply H INPUT UPS LOAD u A A INPUT UPS LOAD ws A cS Check Measured Values and Figures Detected by the UPS e If you would like to check the measured values and figures detected by the UPS use the scroll up 2 and scroll down keys When you scroll down the LCD will display figure C Voltage from Utility Input gt figure 11 Voltage from Bypass Input gt figure J Frequency from Utility Input gt figure K Frequency from Bypass Input gt figure L UPS Output Voltage gt figure M UPS Output Frequency gt figure N UPS Output Load gt figure O UPS Battery Voltage gt figure P UPS Inner Temperature J INPUT UPS LOAD wy e im nn POU Frequency of Utility Input Xtreme Power Conversion Corporation Page 16 T90 GRVA amp LOkVA User s Manual INPUT UPS LOAD A L ET p Frequency of Bypass Input
15. condensation 30 90 Terminal Block Explanation T90 6kVA 8 10kVA MODELS OUTPUT INPUT a es sen fo nn GND L1 L2 Xtreme Power Conversion Corporation Page 12 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply L11 NOT USED all systems are single input N1 L12 G1 the terminals for utility input with single input connection G1 the terminal for UPS input ground N1 line 1 L1 input L12 line 2 L2 input G2 N22 L22 N21 L23 L21 the terminals for UPS output see below output options for configuration details G2 the terminal for UPS output ground Remarks 1 The maximum current for each terminal is 30 Amps for 6 kVA 50 Amps for 10 kVA 2 The UPS is always a Single Input configuration The Dual Input configuration is not used The AC source can be 208V or 240V landed to the L12 and N1 terminals 3 Use No 6 AWG 75 C minimum copper wire and 23 lb in Torque force when connecting to terminal block Input Output Configuration 208V input applications 208V input with a 208V output is the default for these systems 240V input applications If the input voltage is 240V the following steps must be performed to obtain a 240V output with a 240V input 1 The UPS inverter output voltage must also be programmed to 240V Refer to the Changing the UPS Default Settings section for more details OUTPUT INPUT a essen fo nn GND L1 L2 For any other output configurations needed please co
16. ction Port for Parallel System Optional Communication Slot 1 Optional Communication Slot 2 Cooling Fans nmw D Xtreme Power Conversion Corporation Page 10 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply External Battery Connector External Charger Connector Utility Input Breaker CB1 CAM Switch Maintenance Bypass Switch Input Output Terminal Block shown with cover removed Mounting Holes for External Charger Cabinet EPO Emergency Power Off Short to enable the function Thermal breaker for the protection of Load in abnormal condition CB3 T90 10K only Air Ventilation Hole POZZrDAT IO Communication Port The communication port on the UPS provides for RS 232 communication with the UPS software to remotely moni tor the power and UPS status You may use optional interface cards for Relay Dry Contact and SNMP These cards may be used simultaneously The software bundled with the UPS is compatible with many operating systems such as Windows 98 2000 ME NT and XP For other applications such as Novell NetWare Unix or Linux please contact your local distributor for a proper solution When the optional interface cards are used together with the onboard RS 232 port the EPO signals will get highest priority then the SNMP WEB card then the shutdown command at the relay card and then finally the onboard RS 232 port gets the lowest priority True RS 232 Interface Settings The RS 232 interface shall be set as
17. der the Load Protection Policy The following damage is not covered by this Policy 1 Restoration of lost data and reinstallation of software 2 Damage from a cause other than AC power line transients except for damage due to telephone line Local Area Network or CATV transients which is covered only if the Product offers such protection 3 DAMAGE CAUSED BY FAILURE TO PROVIDE A SUITABLE INSTALLATION ENVIRONMENT FOR THE PRODUCT INCLUDING BUT NOT LIMITED TO LACK OF A PROPER SAFETY GROUND Damage caused by the use of the Product for purposes other than those for which it was designed Damage caused by accidents or natural disasters including but not limited to fire flood and wind Damage caused by abuse misuse alteration modification or negligence Any labor costs or travel room and board expenses associated with the repair and or restoration of lost or damaged hardware software or data ONP S EXCEPT AS EXPRESSLY PROVIDED IN THIS POLICY XPC SHALL NOT BE LIABLE FOR ANY DAMAGES WHATSOEVER INCLUDING BUT NOT LIMITED TO DIRECT INDIRECT SPECIAL INCIDENTAL CONSEQUENTIAL OR MULTIPLE DAMAGES ARISING OUT OF THE USE OF THE PRODUCT OR DAMAGE TO THE CONNECTED EQUIPMENT REGARD LESS OF THE LEGAL THEORY ON WHICH SUCH CLAIM IS BASED EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE SUCH DAMAGES INCLUDE BUT ARE NOT LIMITED TO LOSS OF PROFITS LOSS OF SAVINGS OR REV ENUE LOSS OF USE OF THE PRODUCT OR THE CONNECTED EQUIPMENT OR ANY ASS
18. e LCD will display figure B and the UPS output will be in bypass mode Remove the cover of the CAM Switch Maintenance Bypass Switch then turn on the CAM Switch to Xtreme Power Conversion Corporation Page 21 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Bypass mode In the upper right hand corner of the LCD a sign will appear 4 Turn off the UPS Utility breaker You may proceed with UPS maintenance now 5 When you are done with UPS maintenance put the UPS back into normal working mode as explained previously Then return the CAM switch to INV mode replace the cover The UPS will switch back to inverter mode 6 The UPS will alert for ten seconds to warn that the procedure is abnormal and may damage the UPS due to uncertain utility status The UPS will switch back to Inverter mode immediately if you turn the CAM switch back to INV Xtreme Power Conversion Corporation Page 22 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Troubleshooting Guide Troubleshooting If the UPS malfunctions during first power up check the following a ls the input and output wiring correct b Is the input voltage of the utility within the input window of the UPS If problems still exist check the following error codes for possible solution Should the problem still persist please contact your local distributor for help Checkitems Solution Check the error code shown on the LCD
19. ee ee eee 20 Troubleshooting GUICEC cccceccscsceccccccscsccccccnceccccscscsccecccsceccscecscesccescece 23 HF ge 9 9 DOO INE een en ee ee E eee er eee ere ee eee 23 Communication Software sssssssssscsssosessssososesessosososeosssososesessosososeosseosos 24 Hawe SC U a A E unint dmemtstacstmoteconttacmenttcal 24 SOME US Ca ATO ecetacan masttgntaemtdassaoaitatatt antttaemtt ent mant btagsttaemeitt men nt 24 Optional Interface Cards ccscsccccccsceccccscscsccccccncsccccscsceccccscsceccscscscesesens 25 Relay VIA CON ACE AN eioen E EE A E 25 SNMP GG hates pence ce oe ppc sarge stada acer atacant ake caecccncepe palate item teu 25 interface Card ENS CAMO abe ccctartons nt eae eee eceeuacaedabese sauce esntadenuvsesaascadanccbenencanenodsdacnodeeadenentysaesgeuies 26 Replacing Batteries sessssessessessssessssososssessssessessssssosssesssssssesssssssessessssee 27 SpeciNCI CIONS esses cocaine AA TEERAA am 29 Xtreme Power Conversion Corporation Page 2 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply OOD GAINING SEVICE scccecesacsestasecesseunecaessdencnscuncuesnesnesssennaneseserecsaseaeeuasseesneines 30 Xtreme Power Conversion Limited Warranty cccscscscscsccccccccscscscsccceececs 31 Xtreme Power Conversion Load Protection POLicy ccsccscscessccscscsccececes 32 Appendix A T90 EBP920 EBP940 EBP960 User GuUICE ccscscscsceceeeees 35 Introduction To The Rear Pannell
20. ery or Batteries in an open fire The Battery May Explode CAUTION Do not open or mutilate the batteries The electrolyte from the batteries is toxic and harmful to the Skin and eyes CAUTION Risk of Electric Shock Battery Circuit is not isolated from AC hazardous Voltage may exist between battery terminals and ground Test before touching with bare hands CAUTION A Battery can present a Risk of Electrical Shock and High Short Circuit Current The Following Precau tion Should be Observed When Working on Batteries A Remove watches rings or other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not lay tools or metal parts on top of batteries Disconnect charging source prior to connecting or disconnecting battery terminals moO Xtreme Power Conversion Corporation Page 35 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Su Introduction To The Rear Panel Rear Panel Descriptions Page 36 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Installation And Operation Note The packing condition and the external outlook of the unit should be inspected carefully before installation Retain the packing material for future use Unpacking e Take the battery bank out of the PE foam e Remove the packing materials e Note The battery bank module is approx 120 kgs be cautious when unpacking and lifting the unit to avoid in
21. f repair or fair market value as determined by XPC during the period limits and up to the dollar limits stated as follows ao _ sxe ee This Load Protection Policy is not deemed first dollar coverage XPC s obligation is reduced by any amounts that the Purchaser is entitled to recover from other sources regarding the Connected Equipment including but not limited to insurance other warranty extended warranty or legal liability regardless of whether or not the Pur chaser makes a claim for recovery Eligibility for Coverage Under the Load Protection Policy 1 The Product must be registered on the XPC website www xpcc com within 10 days of purchase All re quired information must be provided and Purchaser should retain a copy for Purchaser s records When registering on the website Purchaser must list all connected equipment that is directly connected to the Xtreme Power Conversion Corporation Page 32 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply product Only those devices registered in that manner will be covered 2 All Connected Equipment must be UL or CSA approved 3 The Product must be plugged into a properly wired and grounded outlet Use of input surge devices ex tension cords adapters ground wires or electrical connections not manufactured by XPC voids the XPC Load Protection Policy No other surge protection device may be connected to the output sockets of the Product The installation mus
22. jury e Standard Package includes o User s Manual o DC connection cable o A pair of kits to fix DC connect cable o The casters cover kits atc yD C1 ES SA X1 Selecting Installation Position It is necessary to select a proper environment to install the unit in order to minimize the possibility of damage to the battery bank and extend the life of the batteries Please follow the instructions below 1 Keep at least 8 inches clearance from the rear panel of the battery bank from the wall or other obstruc tions 2 Do not block the air flow to the ventilation openings of the unit 3 Please ensure the installation site environmental conditions are in accordance with the battery bank work ing specifications to avoid overheat and excessive moisture 4 Donot place the battery bank in a dusty or corrosive environment or near any flammable objects 5 This battery bank is not designed for outdoor use Xtreme Power Conversion Corporation Page 37 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Installation of Casters Cover k E hi amp Push Here f Yh Di aa Installation Instructions b gt o gt d a ON OFF 2nd Battery Bank 1st Battery Bank UPS Xtreme Power Conversion Corporation Page 38 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Specifications anne T90 EBP920 T90 EBP940 T90 EBP960 Dimensions W x D x H Unit 11 4 x 25 4 x 29 5 in
23. l the batteries will be boosted to provide the DC voltage to the Inverter Internal Battery When AC abnormal it provide the backup power from the batteries Charger the battery charging device Inverter To convert the DC voltage to AC voltage Auto Bypass Loop When the UPS is overloaded or abnormal the UPS will Switch the UPS from inverter output to bypass output automatically UPS Output EMI Filter To eliminate the magnetic interference from the UPS Output and avoid the interfer ence caused by the output load and the UPS 10 Maintenance Bypass Switch Transfers system to maintenance bypass switch for maintenance Xtreme Power Conversion Corporation Page T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Symbols on the LCD Display Panel item symbol LINE Utility or Bypass Source Bypass Input Abnormal UPS fails to transfer to bypass Bypass Abnormal at ECO mode y UPS Shut off LINE OFF UPS Abnormal Lock LINE UPS LOAD E UPS Flow Display 4 Digit Measurement Display 14 UPS ON Switch or Alarm Silence UPS OFF Switch Previous Page or Setting Change Next Page Special Function Log In Out Enter or Reconfirm Xtreme Power Conversion Corporation Page 8 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply 23 UPS under ECO Mode 2 Oo Emergency Power Off 2 OS Battery Weak orDead r Output Short circuit S ert veer Overcurrent S 29 Em The uP
24. ly If no abnormal message appears then the pre startup of the UPS was successful and the charger begins to charge the batteries e Press the UPS On switch E for approximately three seconds The Buzzer sounds twice and the LCD display changes from figure B to figure C C E 2 Unies TT rT TE reui e The UPS is in self test mode again The LCD display will change from figure C to figure D and the UPS will remain in battery mode for approximately four seconds Then the display will change from figure E1 to figure F if the self test was successful test D Xtreme Power Conversion Corporation Page 14 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply E El INPUT UPS LOAD Testing a OK in self test E2 INPUT UPS LOAD Testingd Fail in self test F INPUT UPS LOAD u A i 208 VAC in Utility Input e Ifthe self test fails the LCD display will change from figure D to figure E2 Then an error code or error status will appear on the screen e Your start up operation of the UPS is complete now Make sure the UPS is connected to utility and charging at least 8 hours and the batteries are fully charged before connecting the device to be protected Start up in Battery Mode Cold Start e Make sure the UPS has at least one string 20 pcs of batteries e Push the UPS On switch once for approximately 5 seconds to wake the UPS The buzzer will sound twice The LCD display will ch
25. no circuit breakers tripped 3 Callyourdealerforassistance lfyoucannotreachyourdealer oriftheycannotresolvethe problem call Xtreme Power Conversion Corp Technical Support at 800 582 4524 Technical support inquiries can also be made at support xpcc com Please have the following information available BEFORE calling the Technical Support Department e Your name and address e The serial number of the unit e Where and when the unit was purchased e All of the model information about your UPS e Any information on the failure including LED s that may or may not be illuminated e Adescription of the protected equipment including model numbers if possible e A technician will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mate rial Authorization number RMA If you are returning the UPS to Xtreme Power for service please follow these procedures 1 Pack the UPS in its original packaging If the original packaging is no longer available ask the Technical Sup port Technician about obtaining a replacement set of packaging material It is important to pack the UPS properly in order to avoid damage in transit Never use Styrofoam beads for a packing material 2 Include a letter with your name address daytime phone number RMA number a copy of your original sales receipt and a brief description of the pr
26. not install the UPS in an environment with sparks smoke or hazardous gas e Make sure the UPS is completely turned off when transporting it It might cause electrical shock if the output is not cut completely e The UPS includes a Maintenance Bypass Switch Please follow the procedures strictly when switching on or off the Maintenance Bypass Switch e The UPS offers a CVCF Constant Voltage Constant Frequency setting function 1 For correct setting and wiring please contact with your local utility agent 2 Do not set it yourself or your warranty will be void e This UPS has been designed and constructed to protect your assets from the wide range of power aberra tions experienced on utility power lines today It is your insurance for a reliable clean and stable voltage supply It is worth taking care to install the system correctly and to have it maintained correctly by your local dealer e SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries e The UPS is intended for installation in a controlled environment e CAUTION A disconnect switch must be provided by others for the AC output circuit To reduce the risk of fire connect only to a circuit provided with branch circuit over current protection for 30 amperes for 6kVA See below for 10 kVA details rating in accordance with the National Electric Code ANSI NFPA 70 Xtreme Power Conversion Co
27. ntact Xtreme Power Tech Support Please refer to the specifications of input current output current and recommended conductors listed below a ACinput and output minimum 75 C copper wire Maximum Input Input Breaker Size Input amp Output Terminal Torque a cy Section ane 6KVA 33A0 A AOA A AWGH8 8 17 17 7 141lb in Ib in 1ORVA 54 3 A AWG 6 23 Ib in b Battery input Model Maximum Current Conductor Section 6KVA AWG 10 LOKVA AWG 10 Xtreme Power Conversion Corporation Page 13 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Start Up in Normal Mode e Open the terminal block cover on the rear panel Before starting the installation make sure the wiring is connected properly e Make sure the utility input breaker and the UPS input breaker are in the Off position e Switch on the utility input breaker on the distribution panel and the UPS input breaker Then the UPS will start up Green LEDs and show that the Utility and Bypass inputs are normal UPS will display first figure A1 and then figure B oe Ge Utility EH db CEI A Parallel ID Mode eme lt p KVA RQ 3 a pass Step A1 INPUT UPS LOAD Utility mer J I Li i I fu I La Voltage Adjust Mn nn Mins Fault 4 Frequency Window ff B c Low 4 Buzzer Code Hil TII j Testing Battery Autonomy i N u B INPUT UPS LOAD J orr e The UPS is now in Bypass Mode It will proceed to self test automatical
28. oblem 3 Mark the RMA number on the outside of all packages Xtreme Power cannot accept any package without the RMA number marked on the outside of the boxes 4 Return the UPS by insured prepaid carrier to the address provided by the Technician 5 Refer to the Warranty statements in this manual for additional details on what is covered Xtreme Power Conversion Corporation Page 30 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Xtreme Power Conversion Limited Warranty Xtreme Power Conversion XPC Corporation warrants Xtreme Power Conversion equipment when properly ap plied and operated within specified conditions against faulty materials or workmanship for a period of three years for T90 Series products from the date of purchase XPC Corporation warrants internal batteries for a period of three years from the date of purchase For equipment sites within the United States and Canada this warranty covers repair or replacement at the sole discretion of XPC Corporation The customer is responsible for the costs of shipping the defective product to XPC Corporation XPC Corporation will pay for ground shipment of the re paired or replacement product This warranty applies only to the original purchaser If equipment provided by XPC Corporation is found to be Dead on Arrival DOA XPC Corporation will be respon sible for the costs of shipping product to and returning equipment from the customer in a timely manner as agreed
29. poration BE LIABLE FOR DIRECT INDIRECT SPECIAL INCI DENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF Xtreme Power Conversion EQUIPMENT including but not limited to any costs lost profits or revenue loss of equipment loss of use of equipment loss of software loss of data cost of substitutes or claims by third parties Purchaser s sole and exclusive remedy for breach of any warranty expressed or implied concerning Xtreme Power Conversion equipment and the only obligation of XPC Corporation under this warranty shall be the repair or replacement of defective equipment components or parts or at XPC Corporations sole discretion refund of the purchase price or substitution of an equivalent replacement product Xtreme Power Conversion Corporation Page 31 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Xtreme Power Conversion Load Protection Policy THIS POLICY IS NOT A WARRANTY REFER TO THE XPC CORPORATION INC LIMITED WARRANTY FOR INFORMATION CONCERNING THE WARRANTY FOR YOUR XPC PRODUCT THE LIMITATIONS AND CONDITIONS CONTAINED IN THIS POLICY DO NOT AFFECT THE TERMS OF THE XPC LIMITED WARRANTY Definitions 1 Product means a Standard 120 208 or 240 Volt power protection device that is used in the United States and Canada This policy does not include custom manufactured products 2 Power Disturbance means an AC power line transient telephone line or Local Area Network if appli cable
30. r output voltage set to 208V Selectable to 200 208 220 230 240V Please refer to the Output Configuration section of this manual V VV Output Voltage Adjustment 1 2 3 0 1 2 3 Xtreme Power Conversion Corporation Page 19 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply UPS position in parallel mode The parallel function is disabled e Press the scroll up 2 key to execute special functions The functions include buzzer ON as in figure Q1 buzzer OFF as in figure Q2 Alarm silence for UPS Warning and self test OFF as in figure R The UPS will execute the battery test for ten seconds If the self test is successful it will display figure E1 otherwise it will display figure E2 and an error message at the same time Changing the UPS Default Settings e Make sure the UPS is not On Press the On and scroll down keys simultaneously for approximately three seconds The buzzer will sound twice and the LCD will display figure Q1 indicating that the UPS is in setting mode e Except for Buzzer figures Q1 and Q2 and Self test figure R all of the other default settings may be changed by pressing the scroll up 2 key e Figure S indicates the bypass input acceptable window It can be 184 260 VAC or 195 260 VAC e Figure T indicates the bypass frequency window of the Inverter Output The acceptable setting values are 3 Hz and 1 Hz e Figure U indicates the acceptable Inverter Output
31. r warranty will be void e To eliminate any overheating of the battery bank keep all ventilation openings free from obstruction and do not place any foreign objects on top of the battery bank Keep the battery bank 20 cm away from the wall e Make sure the battery bank is installed within the proper environment as specified 0 40 C and 30 90 non condensing humidity e Do not install the battery bank under direct sunlight Your warranty will be void if the batteries fail due to overheating e This battery bank is designed for indoor use only e This battery bank is not designed for use in dusty corrosive and salty environment e The warranty for this battery bank will be void if water or other liquid is spilled or poured directly onto the battery bank Similarly we do not warrant any damage to the battery bank if foreign objects are deliber ately or accidentally inserted into the battery bank enclosure e The battery will discharge naturally if the system is unused for a period of time e lt should be recharged every 2 3 months if unused If this is not done then the warranty will be null and void During normal operation the batteries will be automatically remained in charged condition e Servicing of batteries should be performed or supervised by trained personnel with knowledge of batter ies and the required precautions e When replacing batteries replace with the same quantity type amp capacity CAUTION Do Not Dispose of Batt
32. rent loads without a need to upgrade the power rating e The multi functional LCD LED panel displays various states of the UPS The LED display shows the UPS working status utility status and abnormal status The LCD display shows input output voltage frequency load status inner cabinet temperature and abnormal phenomena e To protect the unit from overloading it automatically switches to bypass mode in 160 seconds at 100 105 load or 40ms if loading is at 105 150 of rating In case of overloading at 150 of rating it switches to bypass mode immediately It will automatically switch back to inverter mode once the overload condi tion ceases e Should the output become short circuited the UPS cuts the output automatically until the short circuit situation is removed manually e Should the unit become overheated the internal thermal switch will detect the heat and switch to bypass mode and vice versa e The fully digitalized control circuit built into the UPS allows upgrading the functionality of the UPS as well as reaching a high level of protection of the UPS Powerful communication capability enhances its ability for remote control and monitoring e Maintenance free sealed batteries minimize after sales service e The maintenance bypass switch provides an easy and safe troubleshooting or maintenance function when the utility is normal e Providing four different working modes Normal ECO CF50 and CF60 it may be used in a wide variet
33. rporation Page 4 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply A Ratings of output branch circuit 10 kVA tower Output No Output rating 8 P I over current protection No 1 L23 N22 10 kVA 208 V No 2 L21 N22 10 kVA 240 V e CAUTION To reduce the risk of fire connect the UPS input to a circuit provided with branch circuit over current protection for 40A for 6kVA and 60A for 10kVA rating in accordance with the National Electric Code ANSI NFPA 70 e Install the UPS so that it is not likely to be contacted by people e The maximum ambient operating temperature is 40 C or equivalent e Units are considered acceptable for use in a maximum ambient 40 C e Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions e When replacing batteries replace with the same type and number of batteries or battery packs e CAUTION Risk of fire hazard UPS can be used with four Battery Cabinets e CAUTION RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE DISPOSE OF USED BAT TERIES ACCORDING TO THE INSTRUCTIONS e CAUTION Do not dispose of batteries in a fire The batteries may explode e CAUTION Do not open or mutilate batteries Released electrolyte is harmful to the skin and eyes It may be toxic e CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed
34. sicvsscectavecxeacvotecaavsataangecdanserxoeredacaduassecsonisaxedaveastaneastoddonsqasemenseassane 36 installation INGO DOT AOU re tar iaio tease ienne AET EAE 37 Selecting Installation FO SHIN o mttaestemtsmmsmmmeluemamanoteetmeneneeatmaenanttueimen 37 Installation of Casters COVER ccc sac cssucesmexeansasndchecuepanansdchinewzeanoomenauanoncedinesaueaunedeeatebasmenacteesseaneenatededs 38 installation UE UC O DES xe ecierenscsctancnec cans sundaniesacansinnaeeepedeasnaetecuedaaeycececinedaneancoacestasdoneraneeasacnieauenontevers 38 SOCI AU ONG A E E A E E E temen im EN E E temes temia 39 Xtreme Power Conversion Corporation Page 3 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Safety Instructions And Battery Care Safety Instructions e For Parallel System installation please refer to T90 6kVA 8 10kVA Parallel System Installation Guide e Due to small leakage currents generated by the EMI filter in the UPS it is necessary to double check that the ground wire of the UPS is properly grounded before connecting the UPS to the AC mains e To ensure safety in all applications where a UPS is hard wired to the electrical supply ensure that the sys tem is installed by a qualified electrical contractor e The UPS has its own internal energy source battery Should the battery be switched on when no AC power is available there could be voltage at the output terminals e Make sure that the AC utility outlet is correctly grounded e
35. spike or surge 3 Connected Equipment properly connected electronic equipment 4 Fair Market Value of damaged Connected Equipment as determined by XPC shall be the lower of a the average price the same or similar items are being sold for on eBay b the price list of Orion Blue Book or if such price list is no longer published a published or announced price list reasonably selected by XPC c the lowest price the same or similar items can be purchased for in the United States or d the total amount of all payment s you have or are entitled to receive from insurance other warranties extended warranties a legal liability claim or from other sources or persons for the damaged Connected Equipment 5 Purchaser means the person or entity that originally purchased the Product from an authorized reseller or distributor of XPC Products The Purchaser of this Product is protected for the term of the XPC Limited Warranty against certain losses caused by a Power Disturbance for properly connected electronic equipment referred to as the Connected Equipment subject to certain terms and conditions provided below This policy applies only to the original purchaser of the Product If the Product is transferred or sold to another person or entity this policy is void Load Protection Policy Dollar and Period Limits For purchasers that meet the qualifications and conditions set forth in this policy XPC will provide reimbursement cost o
36. t comply with all applicable electrical and safety codes set forth pursuant to the NEC 4 The Product must have undeniable physical evidence of a Power Disturbance that directly and proximately caused the damage 5 The Connected Equipment must have been damaged by a Power Disturbance on a properly installed grounded and National Electric Code NEC code compliant 120 208 240 Volt AC power line in the United States or Canada by a Power Disturbance on standard telephone land line or PBX telephone equip ment line that is properly installed and connected to an RJ11 port on the Product or by a Power Distur bance on a standard Local Area Network connection that is properly installed and connected to an RJ45 port on the Product and d is directly plugged into and properly connected to the Product in its original condition which was properly operated when a Power Disturbance passed through the Product and i exhausts the protection capacity of the Product or ii damages the Product 6 The Load Protection Policy does not apply if the Product has been operated in a failure mode or not in compliance with XPC operating instructions in the Product user s manual or if the Connected Equipment has not been operated in compliance with the instructions and manuals of its manufacturer vendor 7 This policy is null and void if XPC determines in its sole discretion that the Product has been tampered with or altered in any way What is Not Covered Un
37. to with the customer once the customer has requested and received a Return Material Authorization RMA number DOA equipment is defined as equipment that does not properly function according to user documenta tion when initially received and connected in conjunction with proper procedures as shown in the user documen tation or via support provided by XPC Corporation personnel or authorized agents This warranty shall be void if a the equipment is repaired or modified by anyone other than XPC Corporation or a XPC Corporation approved third party b the equipment is damaged by the customer is improperly used or stored is subjected to an adverse operating environment or is operated outside the limits of its electrical specifi cations or c the equipment has been used or stored in a manner contrary to the equipment s operating manual intended use or other written instructions Any technical advice furnished by XPC Corporation or a XPC Corpora tion authorized representative before or after delivery with regard to the use or application of Xtreme Power Con version equipment is furnished on the basis that it represents XPC Corporations best judgment under the situation and circumstances but it is used at the recipient s sole risk EXCEPT AS STATED ABOVE XPC Corporation DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE EXCEPT AS STATED ABOVE IN NO EVENT WILL XPC Cor
38. tributor for turned off help Xtreme Power Conversion Corporation Page 23 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Communication Software Hardware Setup 1 Connect the male connector of the RS 232 cable to the UPS communication port 2 Connect the female connector of the RS 232 cable to a dedicated RS 232 port of the attached computer Software Installation e For local monitoring refer to the supplied Upsilon CD e For remote monitoring refer to the optional NetAgent CD that comes with Web SNMP card Xtreme Power Conversion Corporation Page 24 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Optional Interface Cards Relay Dry Contact Card Pin assignments of 10 pin terminal i 2z 3 ajs 6 7js 9j10 Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Pin 7 Pin 8 Pin 9 Pin 10 SNMP Card UPS on Bypass mode Utility Abnormal Utility Normal Inverter On Battery Low Battery Bad or Abnormal UPS Alarm Common Shutdown UPS positive signal Shutdown UPS negative signal The shutdown function will be activated after 6 25 VDC is applied between pin 9 and pin 10 for 5 sec onds The capacity of each relay contact is 40 VDC 25mA Installation Position slot 1 CHA CN7 or slot 2 CHB CN8 Flexible signal output for N C Normal close or N O Normal open contact by shorting pins 1 2 or pins 2 3 from JP1 5 The shutdown function will be enabled 1 min
39. ute after blackout occurs if pins 1 2 of both CN1 and CN6 are shorted Otherwise the shutdown function can be enabled only by pins 9 10 of CN3 if pins 2 3 of both CN1 and CN6 are shorted Net Agent II Internal Card For installation please refer to the card s user Manual Position slot 2 CHB Xtreme Power Conversion Corporation Page 25 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Interface Card Installation Xtreme Power Conversion Corporation Page 26 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Replacing Batteries To be performed by qualified personnel only 1 Unscrew the bottom of the front panel as indicated in Step 1 below 2 Remove the front panel as indicated in Step 2 T90 6K shown above 3 Remove the screw of the battery pack fastener as shown in Step 3 4 Remove the fastener as shown in Step 4 5 Unplug the hot swappable battery connectors as shown in Step 5 Xtreme Power Conversion Corporation Page 27 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply 6 Rotate the battery pack handle 90 degrees as shown in Step 6 7 Remove the battery packs from the UPS as shown in Step 7 Xtreme Power Conversion Corporation Page 28 T90 GRVA amp LOkVA User s Manual Specifications MODEL NUMBER Uninterruptible Power Supply T90 10K 6kVA 5 4kW 10kVA 9kW 160 280VAC 45 65Hz auto sensing Up to 0 99 at linear load
40. when working on batteries 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Wear rubber gloves and boots 4 Do not lay tools or metal parts on top of batteries 5 Disconnect charging source prior to connecting or disconnecting battery terminals 6 Determine if battery is inadvertently grounded If inadvertently grounded remove source from ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit Battery Care If the UPS is unused for an extended period of time it must be stored in a moderate climate The batteries should be charged for twelve hours every three months by plugging the UPS power cord into a wall receptacle and turn ing on the input breaker on the front panel Repeat this procedure every two months under a high temperature environment Xtreme Power Conversion Corporation Page 5 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Product Introduction General Characteristics e True online architecture continuously supplies your critical device with stable regulated transient free pure sine wave AC power e 20kHz PWM sine vvave topology yields excellent overall performance The high crest factor of the inverter handles all high inrush cur
41. y of applications e The DC start function ensures the start up of the UPS during power outages e A revolutionary battery management circuit analyzes battery discharging status to adjust the battery cut off point and extend battery life e The intelligent temperature controlled fan may not only extend the life of the fan but also reduce noise because of sudden fan spin This helps keep your office quiet and comfortable e When the UPS is out of order you can read the possible reason directly from the LCD screen which re duces unnecessary repairs e When the UPS is operated in CF50 or CF60 mode the recommended load connected shall be 75 of rated capacity if the input voltage is 176 280VAC and 50 of rated capacity if the input voltage is 160 280 VAC Xtreme Power Conversion Corporation Page 6 T90 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Single input System Block e OS En Do es gr an 3 9 10 2 1 Sed EMI CAM i is I Filter Switch cans Utility Input PFC Inverter Static Switch Boost Battery UPS Utility Input to provide the AC source to the UPS rectifier circuit and charger UPS Utility Input Breaker to protect the UPS Rectifier circuit from over current EMI Filter on UPS Utility Input to eliminate the magnetic interference from AC Source or UPS Utility Input Rectifier and Booster When Utility is normal they will converts the AC to DC and correct input power factor When Utility is abnorma
Download Pdf Manuals
Related Search
Related Contents
Philips DVD+RW DW4S4J10C - RCC Italy Untitled - Crosley Radio "user manual" ABTASTGERÄT Bedienungsanleitung DT099G Report -- Xiaojie Liang(xili1100) EURODESK SX3242FX/SX2442FX Titan Lighting TN-5504 Installation Guide iR3045/iR3045N iR3035/iR3035N iR3025/iR3025N Guida Copyright © All rights reserved.