Daker DK 4.5, 6, 10 kVA

image

Contents

1. There is no line voltage Line voltage is out of allowed UPS range The power supply cable is not correctly connected to mains socket The input circuit breaker has to be reset The mains socket is defective The UPS signals overloading Additional loads to the ones normally connected have involuntarily been connected on the output line e Check all the loads connected to the output The UPS doesn t operate in battery mode it shuts down or immediately signals it is close to the operating limit The UPS has operated with no mains voltage for a long time and has not been able to recharge the battery Recharge it for at least 6 hours by connecting the uninterruptible power supply to the mains The battery is flat due to not using the UPS for a long period Recharge it for at least 6 hours by connecting the uninterruptible power supply to the mains The battery has run down due to being used frequently to ambient conditions or to having exceeded its average service life it is necessary to change it The UPS doesn t deliver power to the output e Check that the loads are correctly connected to the output sockets 42 8 Technical features Daker DK 4 5 6 10 kVA Weights 52 Kg 52 Kg Dimensions L x Hx P in mm 440 x 176 x 680 440 x 176 x 680 Protection Electronic protection against overloading and short circuiting Shutdown on reaching operating limit and overheating Automatic shutdown due
2. and then press the enter key to save all of your changes Then the LCD will display figure AA to indicate completion of the setting changes To cancel your changes rather than save them press and hold the OFF key 27 for five seconds The LCD displays figure AA directly which indicates that your changes were canceled Z Press the Enter key Ghu F to save changes AA LINE E EF The UPS is locked 0 Turn Off the Utility Input breaker Your setting changes are now complete Connection The UPS has an RS232 serial communication interface that provide access through a processor to a range of data for the operation and the history of the UPS This function can be accessed through a WINDOWS interfacing program connecting a serial port of the PC to the interface socket that can be found on the back of the UPS using an RS232 cable 41 LI legrand 6 UPS communicator self diagnostic software From the website www ups legrand com it is possible to download free of charge a self diagnostic software running on WINDOWS 16 e 32 bit e Linux platforms This software can be used for the following functions Display of all the operation and diagnostic data in case of problems Setup of special functions Automatic shutdown of the local computer Windows and Linux operating systems Windows is a registered trademark of Microsoft Corporation 7 Possible malfunctioning The UPS always operates on batteries
3. battery battery 12V 12V 5Ah 5Ah Standards Electromagnetic compatibility Emission Immunity Conforms to EN 62040 2 Safety Conforms to EN 62040 1 Performance and features Conforms to EN 62040 3 NOTICE The batteries are considered hazardous waste and should be disposed of in accordance with current regulations 44 Daker DK 4 5 6 10 kVA Weights 25 Kg 25 Kg 26 Kg Dimensions L x Hx P in mm 440 x 88 x 680 440 x 88 x 680 440 x 132 x 680 Protection Electronic protection against overloading and short circuiting Shutdown on reaching operating limit and overheating Automatic shutdown due to protection triggering Ambient specifications Operating temperature range from 0 to 40 C Operating relative humidity range from 20 to 80 non condensing Degree of protection as per IEC529 IP21 Noise level at 1 meter lt 50dBA Electrical input specifications Rated input voltage 230V 380V Range of input voltage from 160 V to 280V 2 Rated input frequency 50 or 60 Hz 5Hz Maximum input current 25 Arms 33 Arms 54 3 Arms Number of input phases Single phase Waveform on output With battery operation sinusoidal Type of operation on line double conversion Electrical specifications on outpu Rated output voltage 230V 2 da ani 4 05kW 5 4 kW 9 kW RI e capacity on 4 5KVA 6 KWA 10 K
4. 2 show that the Utility and Bypass inputs are normal The LCD will display OFF after few seconds 2 The UPS is in Bypass Mode now It will proceed to self test automatically If no abnormal message appears then the pre startup of the UPS was successful and the charger starts to charge the batteries 3 Press the UPS On Switch 5 for approximately three seconds The Buzzer sounds twice and the LCD display changes from previous status to RUN mode 4 The UPS is in self test mode again The LCD display will show TEST and the UPS will remain in battery mode for approximately four seconds 5 If the self test fails an error code or error status will appear on the screen 6 Your start up operation of the UPS is complete now Make sure the UPS is plugged into the wall receptacle for charging at least 8 hours and the batteries are fully charged before connecting the device to be protected Shutdown 7 Press the Off 9 key for five seconds The Inverter output will be turned off and the output load will be supplied by the Bypass loop 8 Turn Off the Input breakers 19 9 The UPS is now turned off completely 37 LI legrand 5 Installation Default data and special function execution Q1 buzzer On buzzer Off 0 Press the key to scroll through the UPS settings The LCD will display in sequence figure Q1 buzzer figure R1 Self test figure S1 Bypass Voltage Windows figure T Output Frequency Synchronization Wi
5. LI legrand Daker DK 4 5 6 10 kVA Manuel d installation Installation manual Part LEO5380AC 07 13 01 GF Index 1 Introduction 2 Conditions of use 3 LCD Panel 4 Rear panel 5 Installation 6 UPS communicator self diagnostic software 7 Possible malfunctioning 8 Technical features Daker DK 4 5 6 10 kVA 26 26 27 29 31 42 42 43 25 LI legrand 1 Introduction This manual contains information for users of the Daker DK 4 5 6 10 kVA models You are advised to read this handbook carefully before installing your uninterruptible power sup ply meticulously following the instructions given herein The UPS Daker DK is only been made for civil or industrial use it is not in conformity with the stan dards for electro medical equipment In case of problems with the UPS please read this manual before contacting technical support The Troubleshooting section can in fact help resolving most of the problems encountered while using the uninterruptible power supply 2 Conditions of use The UPS has been designed for the power supply of the data processing equipment The load applied must not exceed the one indicated on the rear label of your UPS The ON OFF button of your UPS does not electrically isolate the internal parts To isolate your UPS unplug it from the mains power socket Do not open the UPS container since there may be parts inside with dangerously high voltage even when the mains pl
6. WA 105 continuous Overload capacity 120 for 30 seconds 140 for 10 seconds Number of phases on output Single phase Three phase 45 LI legrand 8 Technical features Electrical specifications on output vvith battery operation Rated output voltage 230V 296 Output frequency 50 60 Hz 0 5 Active output capacity 4 05kW 5 AKW kW on non linear load Apparent output capacity ASKVA GRVA 10kW on non linear load Charging time to 90 of the load 4 hours 5 hours Standards Electromagnetic compatibility Emission Immunity Conforms to EN 62040 2 Safety Conforms to EN 62040 1 Performance and features NOTICE The batteries are considered hazardous waste and should be disposed of in accordance with current regulations 46 Conforms to EN 62040 3
7. ates that the utility input voltage is within the window Flashing green LED indicates that the utility input voltage is within the acceptable window Green LED indicates that Bypass Input is normal UPS ON Alarm Silence Go to previous page or change the setting of the UPS Confirm a changed setting Go to the next page UPS OFF Switch Special functions log in out UPS is working under ECO Economical mode UPS alarm LED 27 LI legrand Display LCD symbols 3 LCD Panel 1 LINE Utility or Bypass Source 17 Er10 Inverter Over current 2 LOW Battery Low 18 Er11 The UPS is overheated 3 Battery Abnormal 19 Er12 UPS Output Overloading 4 So UPS Overloading 20 Er14 Fan Error gt S Le neue al Er15 Lla tele ede TEJE 3 ramon ay Ere Omertrrcae 8 NAS Utility Input Abnormal 9 OFF UPS Shutoff 10 LINE OFF UPS Abnormal Lock 11 es UPS Flovv Chart 12 I 0000 SEE arko 14 EPO Emergency Power Off 15 Er05 Battery Weak or Dead 16 ErQ6 Output Short Circuit 28 4 Rear panel Daker DK 4 5 6 10 kVA 13 RS 232 Port 17 14 Emergenc
8. cable connection 30 Daker DK 4 5 6 10 kVA 5 Installation Check for the following standard package contents User Manual e RS 232 communication cable Tower Rack Accessories Kit as below 3 100 53 54 56 57 3 100 58 59 S3 TE 1 la E 1 ao S M3 ee mail 3 100 53 54 56 57 x8 x8 x6 310058 x7 31 LI legrand Tower configuration setup 5 Installation Step 1 var Optional 32 Daker DK 4 5 6 10 kVA UPS battery cabinet Step 1 33 LI legrand 5 Installation Configuration rack 19 aa UE Ge an as an Gi ua na ua un 23 ag dd 2G AO AO DI GF AG AG AA ag yi y La 34 Daker DK 4 5 6 10 kVA ua UE ua ua ua ua SD ua va ua ua 7a xa SH un un um an an Gh aa un ua un IS AO dA dA dA an Step 5 Step 6 35 LI legrand 5 Installation On the rear of the uninterruptible power supply are the following connections Output sockets and input connector 17 or 18 connect to these connectors the power cable and the output cables included Socket for connecting computer serial interface RS232 9 female pins 4 required when using the diagnostic and shutdown management software Presetting for the connecti
9. ndow figure U Inverter Output Voltage figure V1 UPS Operation Mode figure W Output Voltage Micro Tune Value figure X UPS Id gt figure Y Parallel function status RI E Self test disable N O N R2 E Self test anable J LI n S1 Bypass Voltage is adjusted to narrow range EA r o S2 Bypass Voltage is adjusted to wide range EN T Frequency Window is 3 Hz en Ez HE 38 Daker DK 4 5 6 10 kVA U inverter output voltage nao nao E v1 The UPS is operating in normal mode 25 o pa v2 The UPS is operating in Eco mode mm m gt V3 The UPS is operating in CVCF 50 Hz mode 7 m La ZI v4 The UPS is operating in CVCF 60 Hz mode E m on E Ww Output Voltage Adjustment 3 to 3 X UPS position in parallel mode Y The parallel function is disabled 39 LI legrand 5 Installation Press the scroll up key to execute special functions The functions include buzzer ON as in figure Q1 buzzer OFF as in figure Q2 Alarm silence for UPS Warning and self test OFF as in figure R1 or self test ON as in figure R2 The UPS will execute the battery test for ten seconds If the self test is successful it will display figure E1 otherwise it will display figure E2 and an error message at the same time UPS Default Settings and their alternatives Make sure the UPS is not On Press the On and sc
10. on of additional batteries 16 3 100 53 54 56 57 Cable section table a AC input and output minimum 75 C copper wire 3 100 53 56 25A AWG 10 4 mm 17 7 11 lb in 3 100 54 57 33A AWG 8 6 mm 17 7 11 Ib in 3 100 58 59 54 3 A AWG 6 10 mm 23 Ib in b Entr e Batterie 3 100 53 56 19A AWG 10 4 mm 3 100 54 57 25A AWG 10 4 mm 3 100 58 59 41A AWG 10 4 mm Daker DK 4 5 6 10 kVA VVARNING For safety reasons it is advised not to modify the cables supplied it is also necessary to make sure that the mains socket the uninterruptible power supply is connected to is fitted with a safe connection to the earth system and appropriate protection in accordance with current regulations WARNING The mains supply socket or the disconnection device must be installed nearby the equipment and must be easily accessible Proceed to the installation as follows 1 Position the uninterruptible power supply so that the vents are not obstructed 2 Connect the input connector 17 or 18 the power cable and the output cables to the appropriate connectors 17 or 18 3 Connect the loads to the output cables ensuring that the switches of the various users are off 4 Connect the power supply plug to a power socket with suitable voltage and current Start 1 Switch on the power breaker 19 of the distribution panel Then the UPS will start up Green LEDs A71 and 4
11. roll down keys simultaneously for approximately three seconds The buzzer will sound twice and the LCD will display figure Q1 indicating that the UPS is in setting mode To scroll through the options press the key to go DOWN and to scroll up Except for Buzzer figures Q1 and Q2 and Self test figures R1 and R2 all of the other default settings may be changed by pressing the scroll up key Figures S1 and S2 indicate the bypass input acceptable window It can be 184 260 VAC or 195 260 VAC Figure T indicates the bypass frequency window of the Inverter Output The acceptable setting values are 3 Hz and 1 Hz Figure U indicates the acceptable Inverter Output Voltage Possible values are 200 208 220 230 or 240 VAC Figures V1 V2 V3 and V4 indicate the operation modes of the UPS Possible values are Online Eco Economical mode fixed 50 Hz Output and fixed 60 Hz Output Figure W indicates the adjustment of the Inverter Output which may be set to 0 1 1 2 2 3 Or 3 Figure X indicates the position of the UPS when the UPS is in Parallel mode Possible positions are 1 2 3 and 4 The position must be 1 if the UPS is not in Parallel mode Figure Y indicates the parallel function status P 01 indicates that the parallel function is disabled and P 02 indicates that the parallel function is enabled 40 Daker DK 4 5 6 10 kVA After changing settings you must scroll to the save screen figure Z
12. to protection triggering Ambient specifications Operating temperature range from 0 to 40 C Operating relative humidity range from 20 to 80 non condensing Degree of protection as per IEC529 IP21 Noise level at 1 meter lt 50 dBA Electrical input specifications Rated input voltage 230V Range of input voltage from 160 V to 280 V Rated input frequency 50 or 60 Hz 5Hz Maximum input current 25 Arms 33 Arms Number of input phases Single phase Waveform on output With battery operation sinusoidal Type of operation on line double conversion Electrical specifications on output Rated output voltage 230V 296 Active output capacity on nominal load 4050W 5 4KW Apparent output capacity on nominal load 4 5KVA 6KVA 105 continuous Overload capacity 120 for 30 seconds 140 for 10 seconds Number of phases on output Single phase 43 LI legrand 8 Technical features Electrical specifications on output vvith battery operation Rated output voltage 230V 296 Output frequency 50 60 Hz 0 5 Active output capacity on non linear load 4 05kW 5 4kW Apparent output capacity on non linear load 4 5kVA 6kVA Battery operation Operating time 6 min 4 min Charging time to 90 of the load 4 hours n 20 n 20 maintenance free maintenance free Technical data and number of batteries sealed lead sealed lead
13. ug is disconnected there are no parts inside that the user can repair The front control panel is provided for manual operations Do not press on the panel with sharp or pointed objects The UPS Daker DK has been designed to work in closed clean rooms where there are no inflam mable liquids or corrosive substances and where it is not too damp Do not place near equipments that generate strong electro magnetic fields and or near equi pments that are sensible to electro magnetic fields engines floppy disks speakers adapters monitors video etc Do not pour any liquid on the UPS or inside the UPS Do not place the UPS in humid environment or near liquid such as water chemical solution Do not expose the UPS to the direct sunlight or any heat sorces Keep the ventilation slits clean to dissipate the heat of the UPS Use grounded power cable to connect the UPS to the mains supply Do not plug laser printers into the UPS because of their high start up current Do not plug house electric equipments such as hair dryer air conditioner and refrigerator into the UPS outlets 26 Daker DK 4 5 6 10 kVA 3 LCD Panel w N Oo NAM SF 9 10 11 12 1 3 4 2 11 12 e e dos OA ue ups 1040 CI Chez GD VIVO gt Function legrand LCD panel Green LED indicates that the UPS is able to run under redundancy mode Solid green LED indic
14. y Povver Off EPO Dry Contact 18 Signal inputs 19 15 Communication Card Options Slot 20 16 External Battery Connector O 310056 310057 Il 3 100 53 y 310054 a 51 i E si il E me 14 le 310058 i 310059 15 17 18 AC utility power connection AC Outlets power connection Utility Input circuit breaker Cooling Fans 29 LI legrand Interface Settings 3 100 53 54 55 56 57 AAA A Ll O O O O O O OUTPUT INPUT G2 N22 L21 G1 NI L12 GROUND L21 N22 UPS OUTPUT G2 OUTPUT EAI RTH L12 N1 UTILITY Gi INPUT E GROUND INPUT ARTH 3100 58 5 Eee gt eee ote G2 N22 L21 UTILITY BYPASS G1 N1 L12 L11 INPUT DIM ONLY L11 N1 clamps not used in this version _TBI TB2 4 Rear panel 3 100 59 2 OO OO TB1 OUTPUT G1 G2 L21 TB2 N1 INPUT L12 N1 clamps for connection to the UPS input line 3 100 58 R S T N1 clamps for connection to the UPS input line 3 100 59 G1 clamp for UPS input ground cable connection L21 N22 clamps for UPS output connection G2 clamp for UPS output ground