Home
60-839 Multi-Lingular Alpha Installation Manual Rev
Contents
1. 2000 2x16 LCD Alphanumeric Touchpad Document Number 466 1759 Rev B August 2000 Product Summary PT DD The Multilingual SuperBus 2000 2x16 LCD liquid crystal display Alphanumeric Touchpad lets you control all pro gramming and operation of the International Concord secu rity system The 2 line 16 character display provides messages to indi cate the current status of the system The touchpad includes police fire and auxiliary panic buttons that can be activated anytime A built in speaker provides alarm status and but ton press sounds This touchpad can be quickly connected and disconnected from the panel circuit board as described later in this docu ment If you plan on installing systems with no alphanu meric touchpads you may want to keep one of these touchpads with you for programming Installation Guidelines OOOO iy Q Mount the touchpad in an environmentally controlled area 4 C to 38 C or 40 F to 100 F Q When mounting the touchpad allow at least 41 4 inches on the left side for the Quick Guide slide out card LI Do not exceed the maximum available power See the panel installation instructions for maximum available power when using panel power for bus devices and hardwire devices Important If separate power supplies are necessary to accomo date bus devices and hardwire devices safety stan dards require that each power supply be prominently marked with adequate instructions for remo
2. must remove power from the panel before connecting the Programming Touchpad Cable to the panel Then use the procedure described earlier in this manual under Power Up and Bus Communication To connect a programming touchpad to an International Concord panel 1 With the panel powered up connect the cable onto a panel Programming Touchpad Header see Figure 5 Note If you connect the touchpad before the panel is pow ered up the panel will add the touchpad to system memory when power is applied You will then need to delete the touchpad from the panel memory before you disconnect it to prevent a bus failure See the panel installation instructions for more information 2 Enable the programming or service touchpad by pressing 8 installer or dealer code 0 2 While the service touchpad is active the touchpad will show a flashing star and trouble beeps will sound 5 beeps per minute 3 Enter programming mode by pressing L8 installer or dealer code 0 0 and program the panel using the panel installation instructions When programming is completed simply disconnect the programming touchpad E oo0o00000 JAVA ICAI OS CV M4 RS ee coool KZ RY AL SY RZ RLY JOS KZ OS a PROGRAMMING TOUCHPAD EE CABLE 60 858 9064A37 DSF Figure 5 Where to Connect a Programming Touchpad Testing z 4 CAUTION Contact
3. be installed on a wall or in an electrical gang box either single or dual gang To comply with safety standards the touchpad must be secured to the building structure before operation Installing the Mounting Plate 1 Separate the mounting plate from the touchpad by first removing the screw if necessary Then press in the tab at the bottom and swing the mounting plate away from the touchpad cover see Figure 1 2 For wall mount installations place the mounting plate on the wall Mark the wall at the break away tamper hole and the mounting holes see Figure 2 Be sure to leave a 44 inch clearance on the left side to allow for the Quick Guide slide out card Insert anchors into the wall at the marked locations where studs are not present 3 Looking at the back side of the mounting plate turn it so the tab is on the left see Figure 3 and position the Quick Guide slide card into the slots on the back of the mounting plate as shown Make sure the card 1s unfolded and the Zones section is facing you WALL MOUNTING HOLES 4 9064A33 DS4 BREAK AWAY TAMPER MOUNTING HOLE Figure 2 Marking the Mounting Holes Slide the card in the direction of the arrow until it snaps into the position shown Position the mounting plate in its normal mounting position tab at the bottom and fold the card toward you at all three scored lines The Zones section should be facing you an
4. ID 0 02 110185 The S digit SuperBus ID number is also located on a label on back of the touchpad 7 Press A or B to cycle through all bus device addresses until the touchpad appears 8 After verifying the touchpad device ID press repeat edly until the display shows SYSTEM PROGRAM MING 9 Press A or B until the display shows EXIT PRO GRAMMING READY then press The touchpad should show the date and time display Programming To progam options for the newly installed touchpad such as key beeps and display brightness see the panel installa tion instructions Connecting the Touchpad for System Programming Only For system programming of installations that don t include an alphanumeric touchpad as a permanent part of the sys tem you can temporarily connect the touchpad to the panel To do this you must first connect a Programming Touchpad Cable 60 858 to the touchpad wires see the installation instructions included with the cable Then connect the cable to the Programming Touchpad Header on the panel Note Be aware that the partition jumping feature is not available to users when a temporary programming touchpad is connected to the International Concord panel Programming Touchpad Header If you need to use partition jumping while the touch pad is connected to the Programming Touchpad Header you must add the touchpad to panel memory as if it were a permanent touchpad To do this you
5. Interactive Technologies Inc 2266 Second Street North North Saint Paul MN USA 55109 2900 T 651 777 2690 F 651 779 4890 1 800 777 1415 ICI Security Automation Fire Protection Access Control www ititechnologies com an nterlog i 64 company
6. but beeps contrast setting sound when buttons are pressed Touchpad display shows Check for correct bus wiring a flashing indicating a connections green and white wires at touchpad and panel terminals trouble condition and system doesn t respond to commands from touchpad Multilingual SuperBus 2000 2x16 LCD Alphanumeric Touchpad Adjusting Display Contrast O OOO Specifications r Compatibility International Concord Power Requirements 12 VDC nominal 8 15 4 VDC 115 mA maximum see Table 1 Temperature Range 40 F 4 C to LOO F 38 C Maximum Humidity 70 relative noncondensing Dimensions 5 127 mm x 4 5 114 mm x 1 25 mm Notices ee This Intruder Alarm System Accessory Security Grade 2 Environmental C Class II has been manufactured to comply with the following European directives i EMC Directive 89 336 EEC amending directive 92 31 EEC amp 93 68 EEC as per EN 50081 1992 EN 50130 04 1995 11 Low Voltage Directive Safety 73 23 EEC as per EN 60950 1997 A11 Changes or modifications not expressly approved by Interactive Technologies Inc can void the user s authority to operate the equipment 2000 Interactive Technologies Inc an Interlogix company Interlogix is a trademark of Interlogix Inc ITI and SuperBus are registered trademarks of Interactive Technologies Inc Concord and SnapCard are trademarks of Interactive Technologies Inc
7. d the folds should create a tab to slide the card in and out Align the mounting plate holes with the wall or gang box screw holes and secure the back plate using the screws provided Note Do not overtighten screws or the back plate may bind and prevent the touchpad from mounting properly For wall mount installations cut a hole in the wall in the wire access area of the mounting plate to pull the wiring cable through Multilingual SuperBus 2000 2x16 LCD Alphanumeric Touchpad SWING CARD OVER IN DIRECTION OF ARROW UNTIL CARD SNAPS INTO PLACE 9064A34 DSF Figure 3 Inserting the Quick Guide Slide Card into the Mounting Plate Wiring Wiring consists of connecting the touchpad to the panel ter minals Wiring the Touchpad to International Concord Panels 1 Remove power from the panel and disconnect the backup battery 2 Runa4 conductor 18 to 22 gauge wire from the panel to the touchpad location see Table 2 Multilingual SuperBus 2000 2x16 LCD Alphanumeric Touchpad Wiring 3 Connect the 4 conductor cable wires to the 12V A B and GND terminals on the back of the touchpad 4 Connect the touchpad wiring to the panel terminals as shown in Figure 4 GND BLACK BUS B WHITE BUS A GREEN 12V RED 12V A BUS B GND RED GREEN WHITE BLACK PANEL TERMINALS Figure 4 Wiring the Touchpad to Panel Terminals Attaching the Touch
8. pad to the Mounting Plate Align the tab at the top of the touchpad with the slot on the mounting plate and swing the touchpad down until you hear the latch on the mounting plate click into place Install the screw into the bottom of the touchpad Power Up and Bus Communication SS LULU After making all wiring connections from the touchpad to the panel you are ready to power up the panel and verify correct communication between the touchpad and the panel Upon power up the panel scans the bus for connected devices assigns a unit number to each bus device and auto matically learns the device ID number of each bus device To power up the panel and verify bus communication 1 Verify that all wiring between the panel and touchpad is correct 2 Connect the panel battery and restore AC power Alphanumeric touchpads briefly show SCANNING BUS DEVICES then display date and time Note Steps 3 through 10 are optional 3 At the touchpad enter program mode by pressing 8 installer dealer code default 5 4 8 2 1 0 0 The touchpad should display SYSTEM PROGRAM MING Press and the display shows SECURITY 5 Press A or 8 until the display shows ACCESSORY MODULES then press The display should read BUS DEVICES Testing 6 Press The display shows the lowest device address and its ID The following example shows what the International Concord device address display may look like UNIT
9. the central monitoring station before activating alarms to avoid dispatching local police and fire departments Test the touchpad by arming disarming the system activat ing the touchpad panics bypassing sensors and by turning chime and lights on off to verify correct operation Refer to the panel User s Manual for complete system operating instructions Multilingual SuperBus 2000 2x16 LCD Alphanumeric Touchpad Adjusting Display Contrast 00 The touchpad display contrast can be adjusted for easier viewing to help compensate for lighting conditions in the touchpad location The contrast adjustment lightens or dark ens the text To adjust display contrast 1 Enter configuration mode by pressing the D and 6 buttons together for at least two seconds The display shows DA nnn 2 Press and release the and 2 buttons together repeat edly until the desired contrast level is displayed 3 Press and the display briefly shows DONE then shows the time and date Troubleshooting Pe SDD 000 Table 3 describes what to do if the touchpad does not oper ate correctly Table 3 Troubleshooting Problem Action Solution Check for correct wiring con nections at touchpad and panel terminals Make sure panel battery is connected correctly and that AC power is present Touchpad doesn t power up no display and no beeps when buttons are pressed Touchpad display Check the touchpad display appears blank
10. ving all power from the unit LI Table 1 describes the power used by the touchpad Q Table 2 describes the maximum wire lengths allowed between the touchpad and the panel Q Up to 16 SuperBus 2000 devices can be connected to and addressed by an International Concord panel Q Language and bus device address settings are auto matic for International Concord systems Multilingual SuperBus 2000 2x16 LCD Alphanumeric Touchpad Multilingual SuperBus ITI Part No 60 839 Installation Instructions Table 1 Touchpad Power Usage Current mA Conditions 115 Maximum alarm current with the buzzer sounding and the keypad illuminated from a keypad press Maximum alarm current with the buzzer sounding or a keypad press but not both Typical operation 12 Standby current no AC power Table 2 Maximum Touchpad Wire Lengths Wire Gauge Unshielded or Shielded Max Touchpad Wire Length Between Touchpad and Panel 2 300 feet Tools and Equipment Needed 4 conductor 22 or 18 gauge wire Screwdriver 6 screws and anchors included Panhead screws for gang box installation OODD DN Saw or utility knife for cutting wallboard Installation OOOO OO O O O O O PRESS MOUNTING PLATE TAB REMOVE SCREW IF NECESSARY SWING MOUNTING PLATE AWAY FROM 9064a32 DSF TOUCHPAD COVER Figure 1 Separating the Touchpad from the Mounting Plate Installation OOOO ooo o ts The touchpad can