Product Data Sheet - Click 24 Fire and Security Maintenance

image

Contents

1. 20 3 10 1 Disable Zones and Inputs 4 ec nne nien rere ee re rH dps 20 3 10 2 Disable Outputs inicr nai 21 3 10 2 1 All Sounder Qutputs iure Pn RENT ER FE e rea HER 22 3 10 2 2 All Other Outputs ioo ren n e He RENE E acri 22 3 10 2 3 Selected O tputs 4 eene nonet men ire e t ee adenine 22 3 10 2 4 Fire Routing Output ace iie re e ie He den 22 Moorland House Nelson Park Cramlington Li 3 em Northumberland NE23 1WE amp LPCB Tel 44 0 1670 707 111 B F P A Y Fax 44 0 1670 707 222 1509001 British Fire Protection Systems Association ISO9001 www Advel co uk Email Sales Advel co uk 3 10 2 5 Fault Routing Outputs ccc ARSE AS ea tee LARA ee D RAR 22 3 10 3 gt Disable Controls teeth ba WO o ok es eee 22 3 10 4 Disable Delay Mode nnne trennen nennen nre 23 BAL SEM ADIN Gi M 24 Sel Enable Zone and pts iussi e HUI SERE ERO VO ERU e ES 24 3 1142 Enable Outputs iste eos encoding Deere meist ts 24 3 113 Enable Delay Mode onset aei tene onse deu 24 3 14 BEnable Change Time soe p ead p derbi aat 24 3 12 ln 25 3123 O ER 25 3 12 25 Test Display io eiat ecc ete e TR ERU ET Re EE cess eU p Pete EE 26 31237 Test BUZZ sarai ras 26 EE A OST 27 E A NON 27 3 13 1 Printer Communications Settings e 27 3132 Set p Printete asset e e a ete e tl bm tests 27 3 19 3 A ert eite ose 28 3134 JPrint Qutpu
2. 18 15 04 02 MON 15 APR 2002 If this panel is connected to a network ALL panels on the network will assume this new value Page 24 of 32 3 12 Testing Test Menu AONI HS DISPLAY BUZZE Press the buttons to highlight the required menu option and then press the Y button to select it 3 12 1 Test Zones The Test Zones function provides the means to implement a one person walk test in order to test specific call points or detectors in one or more zones When the Test Zones option is selected a pop up window is shown on the display to select whether the sounders will activate for about 10 seconds when an input device is activated For example WITHOUT SOUNDERS WITH SOUNDERS Press the AW buttons to scroll through and highlight the required option and then press the Y button to select it Note that the panel will have been programmed during commissioning to define which of the sounders are activated during a test The display then shows a list of the available Zones and their current test status For example 0 Zones in Test Zone Test State Location gt 0001 MH ASEMENT west 0002 BASEMENT EAST 0100 MAIN RECEPTION Press the AN buttons to scroll through and highlight the required zone and then press the Y button to change the Test State For example 1 Zone in Test Zone Test State Location 0001 EA EMENT WEST 0002 BASEMENT E
3. Inputs in Zone 001 Mode Lp Adrs State 1 001 0 Normal Disabled 002 0 Normal 1 Enabled 1 003 0 PRE ALARM 1 Enabled 004 0 Normal Press the 3 button to more information on the inputs including full device text type analogue value etc Press the AN buttons to scroll through and highlight the required input and then press the Y button to disable it Pressing the Y button when the input is already disabled will enable the input Press the Esc button to return 3 10 2 Disable Outputs The Disable Outputs Option enables the isolation of some or all of the outputs If disabled the outputs will not activate in the event of a fire alarm or other programmed event On selection of the Disable Outputs option a pop up window is shown for entry of the Level 2 password This is to prevent inadvertent disabling of outputs Please Enter Your Password Enter the password as normal Once a valid password has been entered a pop up window is shown on the display to select the type of outputs to disable ALL SOUNDER STYLE OUTPUTS ALL OTHER OUTPUTS SELECTED OUTPUTS FIRE ROUTING FAULT ROUTING Page 21 of 32 3 10 2 1 All Sounder Outputs Press the AV buttons to scroll through and highlight the ALL SOUNDER OUTPUTS Option and then press the Y button to disable them The display automatically reverts to the Main Disable Menu The Sounder Disabled Indicator will be illuminate
4. View Alarm Counter 0000000033 Page 19 of 32 In the above example the panel has entered the fire alarm condition 33 times since it was installed The panel increments the count by one each time it changes from the normal condition to indicate a fire alarm condition Whilst in the fire alarm condition and until it is reset further fire alarm events do not increment the counter Press the Esc button to return to the main view menu 3 9 9 View Network This Option can be used to obtain diagnostic information when a network is used to connect other panels or remote terminals The access level of all panels on the network can be checked from this display NETWORK Press 0 to Clear More gt Node Status 1 LOCAL Level 2 2 3 Level 1 4 Additional network diagnostics are available by selecting the More option For further information refer to the Ad Net network manual Document No 680 027 Pressing 0 allows the stored network status information to be cleared 3 9 10 View Logic This is a diagnostic aid to assist engineers when first commissioning a complex fire system 3 10 Disabling On selecting the Disable Menu the display shows four possible options For example Disable ZONE INPUTS OUTPUTS CONTROLS DELAY MODE Press the buttons to highlight the required menu option and then press the Y button to select it 3 10 1 Disable Zones and Inputs This option
5. button If there are still any zones in a test condition a pop up window with the following options FINISHED TEST KEEP ZONES IN TEST Selecting the FINISHED TEST option will cancel all zone tests The Test LED will then extinguish Alternatively it is possible to leave the Zone Test Function with one or more Zones still in Test by selecting the KEEP ZONES IN TEST option This will enable the inspection or use of other menu functions and return the display to the normal operating mode The Test LED will stay illuminated if this option is selected 3 12 2 Test Display The Test Display option checks the operation of all the Indicators and the Graphic Display All of the Indicators are turned on and the entire display is shown in reverse During this test it is possible to test the operation of the 4 V and 0 9 buttons When a button is pressed it is indicated on the display For example WED d Jide MaS de Press the Esc button to return to the Test Menu If no button is pressed for 1 minute the display will automatically revert to the normal operating display 3 12 3 Test Buzzer Test Menu ZONES DISPLAY BUZZER PRINTE When the Test Buzzer option is selected the internal buzzer will sound for about five seconds Page 26 of 32 3 12 4 Test Printer To invoke the printing of a test print sequence highlight the Test Print Option and press the Y button to confir
6. Esc button at any time to cancel the log print Note The pop up window also allows selection of the Fire Alarm Counter On selection this is shown on the display but is not printed 3 13 8 Print Feed Paper Highlight the Feed Paper Option and press the Y button to confirm The display does not change but a command is sent to the printer to advance the paper Page 30 of 32 For easy reference cut out and frame mount on the wall next to the panel 3 Quick Reference Guide Mx4000 Series Controls amp Indications FIRE EN Sounder a Function 1 DO Fault a Sounder Fault O Function 2 Bosas B sounder Disable O Function 3 Silence O Test A System Fault Wion 4 Resound The panels may be fitted with separate zone fire indicators comprising of 20 50 100 or 200 red indicators these show the zones in a fire alarm condition In addition the panels may be fitted with separate indications showing the loaction of fire alarms in a pictorial display mimic diagram Graphic Display The graphical display provides detailed information of the source of fires faults and warnings It also shows menus for use when inspecting or programming the operation of the panel Under normal conditions the panel display shows the time date and status LEVEL 2 16 05 04 MAR 2002 NORMAL PANEL OPERATION Press Menu to View The following is a typica
7. Menu 3 10 2 4 Fire Routing Output Press the KW buttons to scroll through and highlight the FIRE ROUTING OUTPUTS Option and then press the Y button to disable it The display automatically reverts to the Main Disable Menu This feature disables the output connected to this panel only The Fire Routing Disabled Indicator will be illuminated 3 10 2 5 Fault Routing Output Press the MY buttons to scroll through and highlight the FAULT ROUTING OUTPUTS Option and then press the Y button to disable it The display automatically reverts to the Main Disable Menu This feature disables the output connected to this panel only 3 10 3 Disable Controls Disabling Controls will cancel Level 2 access and return the panel to Level 1 operation If the panel has an access key switch fitted use the key switch in preference to the menu option shown below Page 22 of 32 Disable ZONE INPUTS OUTPUTS CONTROLS DELAY MODE Press the buttons to highlight the Controls option and then press the Y button to select it The display then prompts for password entry Enter the password as normal When a valid password has been entered the control button functions and menu functions are disabled and the level 1 menu display will be shown CONTROLS DISABLED ENABLE CONTROLS VIEW The display will automatically revert to the normal operating display after a few seconds 3 10 4 Disable Delay Mode This operation w
8. Off Sounder B Enabled o 011 0 Off Relay 1 Enabled 0 004 0 Off Relay 2 The above example shows that the panel sounder circuits are disabled A symbol preceding the state e g Off indicates the device has been configured as an inverted output e g a fault relay that is designed to de energise when a fault occurs Press the AV buttons to scroll through the list of individual outputs within the selected zone Press the Esc button to return to previous views and the main display 3 7 Alarm Condition When the system registers a pre alarm or plant alarm condition the internal buzzer sounds intermittently and the display shows the cause of the fault in more detail An example of the display is shown below ZONE 0001 PRE ALARM BASEMENT WEST Location Text for First Zone ESTAURANT MULTI SENSOR Location Text and Type of Device 1 Zone In Alarm More gt o of Zones in Alarm To obtain more detailed information about the alarms press the 3 button The display then presents a list of all zones in an alarm condition Page 13 of 32 3 8 Menu Functions The following Menu Functions are available at Level 2 The display shows the primary Level 2 Menu as follows Level 2 Menu DISABLI PRINT ENABLE COMMISSION The following table gives a list of the Level 2 Menu Functions the sub functions available within each main function and a brief description for eac
9. Print the status of outputs Faults Print the fault conditions Disabled Print the disabled conditions Log Print the Event Log All Events of Fire Only Events Selectable Feed Paper Advance the paper in the printer Set up Configure the printer connection and automatic print options COMMISSION E Enter the Level 3 Commissioning and Panel Programming Functions Not required if a key switch is fitted for changing access levels Page 14 of 32 3 8 1 Using the Buttons to Navigate Menus Press the Menu button to bring up the display menu 3 8 1 1 Selecting Menu Options The Level 2 Menu is shown below Level 2 Menu IVIEW DISABLE ENABLE TEST PRINT COMMISSION Press the AW3 buttons to highlight the required menu option and then press the Y button to select it For example press the gt button followed by the y button to highlight the PRINT option as shown below and then press the Y button to select this option Level 2 Menu VIEW DISABLE ENABLE TEST PRINT COMMISSION Press the Esc button from within a menu option to return to the previous menu Press the Esc button from the Main Level 2 Menu shown above to return to the normal operating display If a button is not pressed for one minute 15 seconds if the panel is in a fire alarm condition the display will automatically revert to the normal operating display Pre
10. Sounder Disabled Yellow Indicates that the sounders have been disabled i e isolated System Fault Yellow Indicates the presence of a system fault Delayed Yellow Indicates that one or more output circuits are in a delayed operating condition Function 1 Red Fire Brigade Output Activated Or Spare function LED Function 2 Yellow Fire Brigade Output Disabled Or Spare function LED Function 3 Yellow Fire Brigade Output Fault Or Spare function LED Function 4 Yellow Fire Protection Equipment Warning Or Spare function LED Function 5 Red Fire Protection Output Activated Or Spare function LED The function LED Indicators are programmable and will have been configured and labelled accordingly during installation and commissioning of the system 2 3 Control Buttons Reset Only available with Press to reset the panel from a fire alarm condition Level 2 Access Mute Available in both Press to mute the internal buzzer Level 1 and Level 2 Silence Resound Only available with Press to silence the sounders Level 2 Access Al E Press again to re activate the sounders Evacuate Only available with Press to initiate a manual evacuation and sound the alarms Level 2 Access Page 6 of 32 2 4 Navigation Buttons Press to scroll through Menu Options Press to display more information Ay Press to scroll through menu Options Press to scroll through lists of zones or dev
11. Y is shown or off is shown accordingly In the above option an external printer is selected with automatic printing of fires and alarms Setting the wide option will change the printing from the default 40 characters per line to 80 characters per line Note Only faults registered on this panel are printed Page 27 of 32 3 13 3 Print Inputs To print information on any input highlight the Inputs option and press the Y button to confirm The display will show the following Inputs First Zone KH Last Zone 98 Press to Start Print The display will prompt the zones in use on this panel For networked systems it is possible to select any zones used in the system Use the arrow A buttons to highlight the first and last zone number and use the number keys to change the zone number required Press the 3 key to start printing The display will show the following whilst information is sent to the printer and printed WORKING Press Esc to Stop After all information has been printed the display will automatically revert to the Print Menu Press the Esc key to stop printing if required The printout will show all input points for the zones selected Information printed includes Device Text Zone Number Loop and address current status and analogue value 3 13 4 Print Outputs To print information on any output highlight the Outputs option and press the Y button to confirm The displa
12. provides the means to disable a complete zone disable all input devices except call points or disable individual input devices On selecting this option the display shows a list of the current zones and their current disablement status For example O Zones with Inputs Disabled More Zone Mode Location 0001 Enabled BASEMENT WEST 0002 Enabled BASEMENT EAST 0008 Enabled GROUND FLOOR 0009 Enabled MAIN RECEPTION ARE Press the AY buttons to scroll through the available zones or key in a specific zone number Page 20 of 32 To disable the entire zone move over to the Mode column and highlight the existing mode Press the Y button and a pop up window appears showing the three possible options ALL INPUTS ALL EXCEPT CALL POINTS SELECTED INPUTS Press the AW buttons to scroll through and highlight the required option and then press the Y button to select it If ALL INPUTS is chosen the pop up window disappears and the State of the Zone is changed to ALL DISABLED If the ALL EXCEPT CALL POINTS is chosen the pop up window disappears and the State of the Zone is changed to PART DISABLED if there are actually call points in this zone or is changed to ALL DISABLED if there are no call points within this zone If SELECTED INPUTS is chosen the pop up window disappears and a list of the input devices within the selected zone is presented For example
13. 0V Normal Normal Too High Too Low Too High Too Low Aux Supply OmA 500mA Normal Too High 1 Loop Load OmA 500mA Normal Open Circuit Too High Short Circuit 1 Loop V Out 24V 32V Normal 1 Loop V In 24V 32V Normal L H Normal Programmable inputs Panel Switch Inputs Normal Normal Relay 1 Normal Relay 2 Normal Output 1 Normal Output 2 Normal Press the MW buttons to scroll through the panel internal circuits Press the Esc button to return to the main view menu The MX 4400 also displays Sounders C and D b Depends on the panel configuration installation and current operating condition i e fire alarm t Loop Load V Out and V In displayed for each loop driver 2 on MX 4200 4 on MX4400 Page 18 of 32 3 9 8 View Log After selecting to view the log option the display presents a pop up window to allow selection between a view of all of the event history a view of only the fire alarms that have occurred or a view of the fire alarm counter ALL EVENTS FIRE EVENTS ONLY ALARM COUNTER Press the AY buttons to highlight the required menu option and then press the Y button to select it The display then shows the appropriate list of events 3 9 8 1 Event Log The display will always show the most recent event to have occurred e g View Fire Events Ent
14. AST 0008 GROUND FLOOR 0009 MAIN RECEPTION ARE When one or more Zones are placed in a Test State the Test Indicator will be illuminated When an input device is activated i e break glass test on a call point or introducing test smoke into a smoke detector the bells will ring if selected and the display will indicate that a zone is registering a test condition by showing an exclamation mark on the display 2 Zones in Test zone Test State Location 0001 IN TEST I BASEMENT WEST 0002 BASEMENT EAST 0008 GROUND FLOOR 0009 MAIN RECEPTION ARE Page 25 of 32 When the activating test key is removed from the call point or the smoke clears from the detector chamber the panel will automatically reset and clear the test condition As an alternative to scrolling a specific zone number can be entered by using the button to move to the zone number column and then typing in the required number followed by the Y button If several consecutive zones are to be tested an alternative to selecting them all individually is to specify a range of zones as follows Move to the zone number column and highlighting the first zone to test then Press the Y button the display will then ask for the last zone to be tested Individual zones can then be toggled in or out of test by pressing the Y button To leave the Zone Test menu press the Esc
15. L Fault O Sounder Fault T Function 2 Mute L Disable O Sounder Disable L Function 3 p 068 Silence L Test O System Fault O Function 4 Resound Delayed Function 5 10 Evacuate LED Status Indicators Number and Letter Buttons Control Buttons 2 1 Graphical Display The graphical display provides detailed information of the source of fire alarms faults and warnings lt also shows menus for use when inspecting or programming the operation of the panel Under normal conditions the panel display shows the access level time date and status LEVEL 2 16 05 04 MAR 2002 NORMAL PANEL OPERATION Press Menu to View Page 5 of 32 2 2 LED Status Indicators The LED Status Indications show the basic operational state of the panel and whether the panel is in a fire alarm fault disabled or test condition Function Colour Description FIRE Red Indicates that the system has detected a fire alarm condition Fault Yellow Indicates that the system has detected a fault condition Disable Yellow Indicates that part of the system has been disable i e isolated Test Yellow Indicates that part of the system is in a test condition Power Green Indicates the presence of power Sounder Silenced Yellow Indicates that the sounders have been silenced Sounder Fault Yellow Indicates the presence of a fault in one or more sounder wiring circuits
16. Number 680 014 Page 7 of 32 3 2 Changing from Access Level 1 to 2 If the panel has an access key switch fitted use the key in preference to the menu options shown below Press the MENU button The level 1 menu will be displayed as shown below CONTROLS DISABL ENABLE CONTROLS VIE To enable the controls ensure the Enable Controls option is highlighted and then press the Y button The display then requests entry of the Level 2 or 3 password as follows CONTROLS DISABLED Please Enter Your Password Enter the password using the number buttons and then press the Y button As each number is entered an asterix is shown on the display For example CONTROLS DISABLED Please Enter Your Password Kt If the password is correct the Level 2 Menu options will be shown If the password is incorrect the display briefly shows the following message CONTROLS DISABLED Please Enter Your Password Password Not Recognised If any of the control buttons Reset Silence Resound or Evacuate are pressed the display automatically prompts for the password Enter the password as above The function of the control button pressed is not initiated The button must be pressed again for the panel to action the required function 3 3 Changing from Access Level 2 to 1 If the panel has an access key switch fitted use the key switch Alternatively if passwords are use
17. Product Data Sheet User Manual User Manual MX 4100 MX 4200 MX 4400 Mx 4400 LE amp Mx 4800 Fire Alarm Control Panels Document Number 680 015 Revision 07 ELECTRONICOS LIMITED Contents 1 AR iaia 4 1 1 421114 EV CARO N RO OR ORE M OR 4 1 2 CAUTIONS and W AFNINOS siccacesssccesessesssceckectececsectanessoccacsusasvosacusdecsotendsSescavenss vguasdessessass chasessestscoessesaee 4 1 3 General Description siscssccescessccovascescecsonscuascccouvsnve Pee ERE PE EE soomestasessosscvaccoussvanocsossastwasoeanee sevssceasecoaseesace 4 2 CONTROLS AND INDICATIONS n nni 5 2 1 Graphical Display 5 2 2 LED Status IMdicators cies scensscsstesccssscesscsscvensesestassosssdesseseosenvesescesssuncbancssdsdessesstenssesessenvesastessuiacsescssaee 6 2 3 eiut content cvessccavesvceus cusssscourenoe seccssecsd ES FIORE RIE area 6 24 Eire 7 2 5 Number and Letter Buttons e eeeee eee eese ce sese nre zee sese nre riesi rene ezine nine ni sio nese sese toss toss setas estos seno 7 2 6 hiuc o y E E EE ES E E S 7 3 OPERATION 00 as 7 3 1 ACCESS O E E T T E A paiono ai 7 3 2 Changing from Access Level 1 to 2 e seseesseseeeesseesesoeseesoesesceseeeoeseeoenseeeesoeseeeorseeeeeseeeesoreereoesereerseseesee 8 3 3 Changing from Access Level 2 to 1 scssscsssrsssscsscceseccesccessccsesceess
18. buttons to highlight the required menu option and then press the Y button to select it 3 11 1 Enable Zones and Inputs Selecting this option will show a list of zones containing disabled input devices Either the complete zone or individual devices within the zone can then be enabled Display format is virtually identical to the Disable displays 3 11 2 Enable Outputs When this option is selected pop up menu appears asking if you want to enable ALL SOUNDER OUTPUTS ALL OTHER OUTPUTS ONLY SELECTED OUTPUTS the FIRE ROUTING OUTPUT or the FAULT ROUTING OUTPUT If ONLY SELECTED OUTPUTS is selected the display will list only zones containing outputs that have been disabled The individual outputs within the zone can then be enabled The display format is virtually identical to the Disable displays 3 11 3 Enable Delay Mode This option allows the re enabling of Investigation Delays 3 11 4 Enable Change Time Allows the clock time to be changed Note that a password must be entered before this can be changed Only level 2 passwords for users 1 5 are accepted For example E DATE 15525 15 04 02 MON 15 APR 2002 To change the settings use the AW buttons to highlight the required option Directly enter the new time or date using the number buttons As soon as a number button is pressed the display will clear the current setting and show the new value as it is entered For example E DATE
19. ction shows the Zones and Inputs that are currently in a Fire Alarm condition The operation of the panel and the information that can be shown is identical to the views available from the main operating display Refer to Section 3 4 for further information If there are no Zones or Inputs in a Fire Alarm condition the display automatically reverts to the Main View Menu 3 9 2 View Faults This function shows the Zones Inputs and Outputs that are currently in a Fault condition The operation of the panel and the information that can be shown is identical to the views available from the main operating display Refer to Section 3 5 for further information 3 9 3 View Alarms This function shows the Zones and Inputs that are currently in an Alarm condition These may occur if The Zone or Input is currently in a Fire Test condition and or Inputs that are configured to generate an alarm or pre alarm condition when operated are active The operation of the panel and the information that can be shown is identical to the views available from the main operating display 3 9 4 View Disabled This function shows only Inputs and Outputs that are currently in a Disabled condition The operation of the panel and the information that can be shown is identical to the views available from the main operating display Refer to Section 3 6 for further information If there are both Inputs and Outputs in a Disabled condition the display
20. d On networked systems this only disables the outputs connected to this panel 3 10 2 2 All Other Outputs Press the AY buttons to scroll through and highlight the ALL OTHER OUTPUTS Option and then press the Y button to disable them The display automatically reverts to the Main Disable Menu On networked systems this only disables the outputs connected to this panel This will disable all outputs other than sounder type outputs including the fire and fault routing outputs 3 10 2 3 Selected Outputs Press the MW buttons to scroll through and highlight the ONLY SELECTED OUTPUTS Option and then press the Y button to select it The display then shows a list of Zones containing outputs For example 2 Zones with Outputs Disabled More Zone Mode Location 0008 ENABLED GROUND FLOOR 0100 ENABLED MAIN RECEPTION Press the MW buttons to scroll through and highlight the required Zone and then press the gt button to view the outputs within this zone For example Outputs In Zone 0008 More Mode Lp Adrs State Enabled 1 032 0 Off SOUNDER Enabled 1 056 0 Off SOUNDER Enabled 2 011 1 On RELAY Enabled 3 026 1 Off RELAY Press the AN buttons to scroll through and highlight the required Output and then press the Y button to change the device mode The device mode will change from Enabled to Disabled and vice versa Press the Esc button to return to the Zone list and to the Main Disable
21. d cal up the Disablement menu and select Disable Controls see section 3 10 3 for details Page 8 of 32 3 4 Fire Alarm Condition When the system registers a fire alarm condition the Red Fire Indicator illuminates the internal buzzer sounds continuously and the display shows the zone in which the fire originated The sounders relays and other outputs will be turned on depending on the programming in the panel An example of the display is shown below FIRE STARTED IN ZONE 0001 BASEMENT WEST lt Location Text for First Zone KITCHEN lt CALL POINT gt lt Location Text and Type of Device Zone in Fire Last Fire in Z0001 lt No of Zones in Fire amp Last Zone ENT WEST Zone Description for Last Zone The upper part of the display shows the origin of the fire The lower part of the display shows the number of zones in a fire alarm condition and the last zone to enter the fire alarm condition This lower fire alarm status display is always present when the panel has registered a fire alarm condition If more than one fire alarm condition occurs the total number of zones in an alarm condition and the last zone in an alarm condition will be updated on the display If the sounders were silenced they will sound again whenever the fire spreads to a new zone FIRE STARTED IN ZONE 0001 More Alarms BASEMENT WEST Location Text for First Zone KITCHEN CALL POINT gt Location T
22. escesccsssscsesceesseseescessscsssscessoeses 8 3 4 Fire Alarm Conditi M 9 3 4 1 Detailed Fire Alarm Information enne nnne nennen nnne nenne 9 3 4 2 Investigation Delays ene ebore d cei oreet eee ee RE PLI ce e te ia toe DR esp vex ep ea ds 10 3 5 Fault COMditon e de 11 3 6 Disablement Condition nre ra HEY RARE andan Pocero EV HE SEEN sues veses 12 3 6 1 Disabled Inputs iaa caia ei ier eei rer e o ER P ERE 12 3 6 2 Disabled Outputs 5 nere rede e ER PER a 13 3 7 EA 13 3 8 MENA AAA arde Ouau Noan E reon Eeto b rE oo nt saroe K A SEES PEEPS Vaos 14 3 8 1 Using the Buttons to Navigate Menus enne enne rentrer nre 15 3 8 1 1 Selecting Menu Options enne enne enne nnne trennen nnne rne 15 3 8 1 2 Selecting Individual Zone Numbers e 15 3 9 VAC WAG et 16 3 9 1 Mewe bien 16 3 9 2 boo cr 16 3 9 3 A O 16 3 9 4 View big 16 3 9 5 Mae Tp o bt 16 3 9 6 View Outputs and Ad Dia ii 17 3 9 7 View Panel ici aa ias 18 3 9 8 View LOBA 19 IIEL EVM DOS onin ie PEDE 19 3 9 8 2 Alarm Counters sieni rir a noe HR ERE HER HE RE E REP REE 19 3 9 9 View Network Sine canine cee EPOR ET ERE REED IEEE KERN 20 39 10 View s Logie siis ie 20 ESI MEC
23. ext and Type of Device Zones in Fire Last Fire in 20005 o of Zones in Fire amp Last Zone ENT EAST Zone Description for Last Zone Press the MUTE button to silence the internal buzzer When the panel is enabled for Level 2 Access the following functions are available Press the SILENCE RESOUND button to silence the sounders Press the SILENCE RESOUND button again to re activate the sounders Press the RESET button to clear the alarm condition and restore the panel to normal operation Press the EVACUATE button to initiate a manual evacuation and to activate the sounders The display will show this fire alarm condition For example FIRE STARTED IN ZONE 0100 MAIN RECEPTION Location Text for First Zone Evacuation Key SWITCH gt Confirmation of Evacuation 1 Zone in Fire Last Fire in 20100 No of Zones in Fire amp Last Zone MAIN RECEPTION Zone Description for Last Zone 3 4 1 Detailed Fire Alarm Information Press the AW buttons to view a list of all zones in a fire alarm condition Zone FIRE LOCATION Scroll Y More 0001 BASEMENT WEST lt List of Zones in Alarm including 0005 BASEMENT EAST lt Zone No and location text If more detail regarding the source of any fires is required press the MW buttons to highlight the required zone in alarm and press the 3 button to show further informati
24. h function VIEW DISABLE ENABLE TEST PRINT Fires View Zones and Inputs that are reporting a fire alarm condition Faults View Zones and Inputs that are reporting a fault condition Alarms View Zones and Inputs that are reporting an alarm condition Disabled View Zones Inputs and Outputs that are disabled Inputs View the current state of Inputs Outputs View the current operational condition of all output circuits devices Log View the Event Log Alarm Counter Panel View the operational state voltage and current loading of the panel input and output circuits Network Zone Inputs View Network diagnostics Disable a complete zone or an individual input Outputs Disable sounder outputs or other devices Controls Cancel Level 2 access Delay Mode Zone Inputs Turn off the Stage 1 Stage 2 Investigation Delay Operation Enable a complete zone or an individual input Outputs Enable sounder outputs or other devices Delay Mode Turn on the Stage 1 Stage 2 Investigation Delay Operation Change Time Zones Allows authorised level 2 users to change time Configure one or more zones for walk test Display Test the Graphics Display Status Indicators and Keyboard Buzzer Test the Internal Buzzer Printer Inputs Test the connection to the Printer Print the status of inputs Ouputs
25. ices Press to confirm entry of numeric or letter information entry Press to confirm selection of a menu option Press to change some of the configuration options Number and Letter Buttons 2 5 ala Used to enter numbers or letters Esc Press to return to a previous menu Press to exit the menu functions and return to the normal display Press to show or return to Menu Functions 2 6 Buzzer The buzzer produces two different sounds to differentiate between fire alarm conditions and fault conditions Condition Operation Fire Alarm The buzzer operates with a continuous tone Fault The buzzer operates intermittently 3 Operation 3 1 Access Levels The panel operation is protected from inadvertent and erroneous misuse by means of three access levels These levels are as follows Level 1 Level 2 Level 3 Untrained user Authorised User Service and Maintenance Engineer e A Level 1 Untrained User can view the current operational condition of the system and may MUTE the internal buzzer A Level 2 Authorised User can view the operational condition of the system and may MUTE the internal buzzer In addition the EVACUATE SILENCE and RESET buttons are enabled and access to the Level 2 Menu functions is available A Level 3 User has access to program and configure the operation of the panel This is described in detail in the Installation and Commissioning Manual Part
26. ill be shown on the display If the internal buzzer was muted it will sound again when a new fault condition is registered When the fault condition is corrected the panel automatically clears the appropriate fault Status Indicators and Display information Press the MUTE button to silence the internal buzzer The display then shows the current time and date and service centre telephone number along with the indication of the fault FOR SERVICE CALL EVEL Panel access level 01234 567890 2 Service Call Number and Time Date 1 Zone In Fault No of Zones in FAULT To obtain more detailed information about the faults press the 3 button The display then presents a list of all of the zones in a fault condition with the first fault highlighted For example 2 Zones in Fault More gt lt Number of zones in fault ZONE LOCATION 1 BASEMENT lt Zone Location Text for each 100 RECEPTION lt zone Press the AN buttons to highlight the required fault and then press the gt button to show further information For example Faults in Zone 0001 More gt LP ADRS STATE 1 004 0 DEVICE MISSING lt Address fault condition Press the 3 button to show further information on device location type analogue digital values etc Press the ESC key to return to the previous display If no button is pressed within a minute the display automatically reverts to the mai
27. ill cancel the Investigation Delay mode Disable ZONE INPUTS OUTPUTS CONTROLS DELAY MODE Press the buttons to highlight the Delay Mode option and then press the Y button to select it If the delays are configured in the panel the display shows the following pop up window when the Disable Delay Mode Option is selected Note This delay function can only be configured using the PC Programming Tool NO DELAY USE INVESTIGATION DELAY Highlight the required option using the AW buttons and then press the gt button to confirm The display then reverts to the Disable Options Menu Select NO DELAY to disable the operation of the Stage 1 Stage 2 Investigation Function Select USE INVESTIGATION DELAYS to enable the operation of the Stage 1 Stage 2 Investigation Function If the investigation delays are in operation then the Delayed LED Indicator is illuminated When the investigation delays are disabled and turned off the Delayed LED Indicator is turned off Press Esc to cancel and make no change to the current operational setting If the delays are not configured in the panel the display briefly shows NOT CONFIGURED before returning to the Disable Menu Options Page 23 of 32 3 11 Enabling On selection of the Enable Menu Option the display shows the available Enable Functions Enable ZONE INPUTS OUTPUTS DELAY MODE CHANGE TIME Press the
28. is not acknowledged before the Stage 1 timer elapses the panel will enter a full alarm condition and will activate the sounders Pressing the 0 button acknowledges the alarm This extends the time allowed to investigate the source of the fire FIRE STARTED IN ZONE 0001 BASEMENT WEST Location Text for First Zone KITCHEN lt TEMPERATURE Location Text and Type of Device OUTPUT DELAY 120 s Delay Timer Stage 2 1 Zone in Fire Last Fire in Z0001 BASEMENT WEST The cause of the alarm can now be investigated If the alarm is a false alarm pressing the RESET button will clear the alarm condition This must be done before the Stage 2 timer has elapsed or the panel will enter a full alarm condition and will activate the sounders Note The EVACUATION button will terminate the investigation delays and activate all programmed sounders Page 10 of 32 3 5 Fault Condition When the system registers a fault condition the Yellow Fault Indicator is illuminated the internal buzzer sounds intermittently and the display shows the cause of the fault in more detail An example of the display is shown below ZONE 0001 DEVICE MISSING BASEMENT WEST Location Text for First Zone ESTAURANT MULTI SENSOR Location Text and Type of Device 1 Zone In Fault More gt o of Zones in FAULT If more than one fault condition occurs these w
29. ive Press the MW buttons to highlight the required zone and then press the gt button to view the location text assigned to the zone in full For example Press the 3 button again to view the inputs within the zone and their status For example Inputs in Zone 0001 More Mode Lp Adrs State Enabled 1 001 0 Normal Disabled 1 002 0 Normal Enabled 1 003 0 Normal Enabled 1 004 0 Normal The display shows the current disablement condition mode for each input as either enabled or disabled In addition the detection loop LP address ADRS and type of input are shown Press the AY buttons to scroll through the inputs Press the 3 button to show further information on device location type analogue digital values etc Press the ESC key to return If there are Outputs also disabled these will now be shown Page 12 of 32 3 6 2 Disabled Outputs The display presents a list of all of the zones in a disabled condition with the first disablement highlighted For example 2 Zones with Outputs Disabled More Zone Mode Location 0001 DISABLED BASEMENT WEST lt Zones with location text where 0100 DISABLED RECEPTION lt outputs are disabled Press the A buttons to highlight the required zone and then press the gt button to view the individual outputs and their disablement condition For example Outputs in Zone 0100 More gt Mode Lp Adrs State Disabled 0 001 0 Off Sounder A Disabled 0 001 1
30. l menu display Level 2 Menu ENABLE TEST COMMISSION Refer to the User Manual Document Number 680 014 for full operating instructions In the event of a fire alarm call TEL For Service amp Maintenance contact Navigation Buttons Press to scroll through Menu Options Press to display more information Press to scroll through menu Options Press to scroll through lists of zones or devices Press to confirm entry of numeric or letter information entry Press to confirm selection of a menu option Press to change some of the configuration options Number Buttons Pe Used to enter numbers or letters Press to return to a previous menu Press to exit the menu functions and return to the normal display Press to show or return to Level 1 or Level 2 Menu Functions Main User functions are VIEW TEST DISABLE amp ENABLE Control Buttons Reset Press to reset the panel from a latched condition Mute Press to mute the internal buzzer Silence Re sound Press to silence the bells Press again to re sound the bells Evacuate Press to initiate a manual evacuation and sound the alarms Level 2 Access is required for Reset Silence amp Evacuate buttons and for programming Menu functions Level 2 operation can be entered using a key switch if fitted or by entry of a pass code LED Status Indicators RED YELLOW Separate LED Indica
31. m The panel transmits 16 lines of test characters to the printer The information sent is echoed on the display When the test print is completed the display automatically reverts to the Test Options Menu Press the Esc button at any time to cancel the test print 3 13 Printing Print Menu INPUTS OUTPUTS FAULTS DISABL LOG FEED PAPER SETUP PRINT 3 13 1 Printer Communications Settings The information is sent to the printer in a serial form If an external printer is used ensure that the communications settings in the printer are set as follows Interface Type RS232 Baud Rate 9600 Parity None Data Bits 8 Stop Bits 1 3 13 2 Set up Printer To enable or set up the operating characteristics of the printer highlight the Set up Printer Option and press the Y button to confirm The display prompts for entry of the password to guard against inadvertent changes Enter the password as normal The display then shows a pop up window giving programming options as follows FIRES ALARMS FAULTS TESTS Y Y x x Printer Internal External Wide Y E The upper line of options determines whether the panel shall automatically print specific events as they occur The lower line of options determines whether a printer is connected and its type Use the 4 and V buttons to highlight the required option and change its setting Pressing the Y button turns the option on
32. n display Page 11 of 32 3 6 Disablement Condition If any zones input devices or output devices have been disabled the DISABLE Indicator is illuminated In addition the SOUNDER DISABLE Indicator is illuminated if one or more sounder circuits or devices have been disabled The display indicates the presence of zone disablement conditions in the lower half of the display as follows LEVEL 2 16 05 04 MAR 2002 1 Zone With Disablements More gt When the disablement conditions are removed the appropriate indications are cleared from the display and from the Indicators When all disablement conditions are removed the DISABLE Indicator is also turned off To obtain more detailed information about the disablement conditions press the gt button The display will then present the disablement conditions in the following sequence Zone Individual Inputs Outputs 3 6 1 Disabled Inputs The display presents a list of all of the zones in a disabled condition with the first disablement highlighted For example 2 Zones with Inputs Disabled More ZONE MODE LOCATION 0001 PART DISABLED BASEMENT WEST Zone disablement condition and 0002 ALL DISABLED BASEMENT EAST location text The display shows the status as ALL DISABLED if every input device within the zone has been disabled and shows the status as PART DISABLED if there is at least one input device within the zone still act
33. ndard for clarification and to ensure that the installation is compliant with the requirements of EN54 1 3 General Description This manual covers the use and operation of the Mx 4100 Mx 4200 Mx 4400 and Mx 4800 Fire Alarm Control Panels Refer to the Installation and Commissioning Manual Document No 680 014 for details of how to install and program the panel The Mx 4100 is a Single Loop Analogue Addressable Fire Alarm Control Panel The Mx 4200 is a Multiple Loop Analogue Addressable Fire Alarm Control Panel with provision for up to two loops The Mx 4400 is a Multiple Loop Analogue Addressable Fire Alarm Control Panel with provision for up to four loops The Mx 4800 is a Multiple Loop Analogue Addressable Fire Alarm Control Panel with provision for up to eight loops All four panels are designed for use with the Apollo Discovery Explorer XP95 Series 90 and Hochiki ESP ranges of fire detection equipment Page 4 of 32 2 Controls and Indications The Mx 4100 Mx 4200 Mx 4400 and Mx 4800 are provided with indications and control functions as shown in the diagram below and described in the following text The Mx 4800 has two such display elements one for loops 1 4 and the other for loops 5 8 Normal operator level indications controls and user programming can all be achieved using either display Graphic Liquid Navigation Crystal Display Buttons EN FIRE Sounder Silenced Aa Function 1 Reset
34. on For example Page 9 of 32 FIRES IN ZONE 001 More gt LP ADRS DEVICE LOCATION 1 001 0 KITCHEN List of devices within the Zone that are in Alarm 2 Zones in Fire Last Fire in Z0005 No of Zones in Fire amp Last Zone EMENT EAST zone Description for Last Zone This shows that the device at address 1 on the loop initiated the fire in Zone 1 If there are more Zone 1 devices in alarm these will be shown in the list Press the MY buttons to scroll through the devices Press the button or the Esc button to return to the previous display If no button is pressed within 15 seconds the display automatically reverts to the main display 3 4 2 Investigation Delays The Investigation Delay Function can be disabled or enabled as required by ENS4 2 Refer to Section 3 10 4 If the Investigation Delay Function Stage 1 Stage 2 Investigation Delay is enabled a fire alarm is registered at the panel but does not immediately activate the sounders On registering the alarm the display shows FIRE STARTED IN ZONE 0001 BASEMENT WEST Location Text for First Zone KITCHEN lt TEMPERATURE Location Text and Type of Device OUTPUT DELAY 30 s Press 0 to extend Delay Timer Stage 1 1 Zone in Fire Last Fire in Z0001 BASEMENT WEST The Output Delay Timer shows the amount of time left for investigation If the alarm
35. on for all Outputs Outputs More gt Zone Mode Location 0008 ENABLED GROUND FLOOR 0100 ENABLED MAIN RECEPTION Press the MW buttons to highlight the required zone and then press the gt button to view the individual outputs For example Outputs In Zone 0008 More Mode Lp Adrs State Enabled 1 032 0 Off SOUNDER Enabled 1 056 0 Off SOUNDER Enabled 2 011 1 On RELAY Enabled 3 026 1 Off RELAY A symbol preceding the state e g On indicates the device has been configured as an inverted output e g a fault relay that is designed to de energise when a fault occurs Page 17 of 32 3 9 7 View Panel The View Panel Option provides a diagnostic readout of the operational condition and readings for the internal panel electronic circuits When the option is selected the display shows a list of the circuits For example Panel Circuits ITEM DESCRIPTION 01 0 Sounder A 01 1 Sounder B 02 0 Sounder A Load 02 1 Sounder B Load VALUE STATE 5 6V Normal 5 6V Normal OmA Normal OmA Normal The following table lists the internal panel circuits and indicates the values that can be displayed Sounder A Sounder B Normal Open Circuit Short Circuit Sounder A Load Sounder B Load OmA 1000mA Normal Too High Battery OV 30V Normal Too High Too Low Charger Earth Monitor OV 30V OV 3
36. presents the inputs first followed by the outputs If there are no Inputs or Outputs in a Disabled condition the display does not change and continues to show the Main View Menu 3 9 5 View Inputs This function shows the current operational condition for all Zones and Individual Inputs The display presents a list of all of the zones containing input devices with the first zone highlighted For example Page 16 of 32 Inputs Zone Mode Location 0001 Enabled BASEMENT WEST 0002 ALL DISABLE BASEMENT EAST 0008 Enabled GROUND FLOOR 0009 Enabled MAIN RECEPTION ARE Press the MY buttons to highlight the required zone and then press the gt button to view the full location text Press the 3 button again to view the inputs within the zone and their status For example Inputs in Zone 0008 lt More gt Mode Lp Adrs State Enabled 1 001 0 Normal Disabled 1 002 0 Normal Enabled 1 003 0 Normal Enabled 1 004 0 Normal The display shows the current disablement condition mode for each input as either enabled or disabled In addition the detection loop Lp address Adrs and input state are shown Press the AW buttons to scroll through the inputs Press the gt button to show further information on device location type analogue digital values etc Press the Esc button to return to previous view 3 9 6 View Outputs This function shows the current operational conditi
37. ry 0076 Number of Highlighted Event Time Date Node Lp Addr Zone 10 54 23 I 1 001 0 001 Time Origin and Zone 14 03 02 FIRE ALARM Date Event and Analogue Value BASEMENT Zone Text Description ROOM 10 Device Location Description In the above example the latest fire occurred Event No 76 at 10 54 am on March 14 2002 This fire alarm originated at the device at address 001 Addr on Loop 1 Lp on Panel No 1 Panel The device was in Zone 001 The analogue value registered by the device 64 has also been recorded The lower two lines show the zone and device location texts descriptions for ease of identification Press the AY buttons to scroll through the fire alarm events logged in the system Press the A button to show more recent events and press the Y button to show earlier events To view the details for a specific Log Entry Number it is possible to select the record by typing in the required number using the number keys The number entered is echoed at the upper right of the display For example View Fire Events Echo of number entered These four lines are blank and reverse highlighted until the number entered is confirmed Press the Y button to confirm The display will then display the required record Press the Esc button to return to the main view menu 3 9 8 2 Alarm Counter Alarm Counter The Panel records the number of times that the fire alarm condition has occurred at the panel
38. splay will show the following depending on the disabled conditions present If there are zones with inputs disabled 2 Zone s with Inputs Disabled First Zone KH Last Zone 99 Press to Start Print If there are zones with outputs disabled 1 Zone s with Outputs Disabled First Zone E Last Zone e 98 Press gt to Start Print The panel analyses the network and the display will prompt the zones in a disabled condition Use the arrow A buttons to highlight the first and last zone number and use the number keys to change the zone number as required Press the 3 key to start printing The printout will show the location and state of all input and output points in a disabled condition for the zones selected The display always present the zones with inputs disabled first if any exist After printing the inputs the display will present the information on disabled outputs if any exist Note If there aren t any disabled conditions present then selecting this menu option will no effect Page 29 of 32 3 13 7 Print Log To print information from the History Log highlight the Print Log Option and press the Y button to confirm A pop up window will be shown asking if all events or just fires should be printed Highlight the required option using the AN buttons and press the Y button to confirm When the Log Print is completed the display automatically reverts to the Print Options Menu Press the
39. ss the Menu button to return directly to the Level 2 Menu display previously shown 3 8 1 2 Selecting Individual Zone Numbers When the display is showing a list of Zone Numbers it is possible to select a specific zone number by using the number keys For example if the display is showing a list of zones Inputs Zone Mode Location 0001 ARES ASEMENT WEST 0002 Enabled BASEMENT EAST 0008 Enabled GROUND FLOOR 0009 Enabled MAIN RECEPTION ARE To select a particular Zone move to the zone number column The existing zone number will then be highlighted Enter the required Zone Number using the number buttons for example 12 Inputs Zone Mode Location 12 nabled BASEMENT WEST 0002 Enabled BASEMENT EAST 0008 Enabled GROUND FLOOR 0009 Enabled MAIN RECEPTION ARE Finally press the Y button to confirm The display will then show a new list of Zones with the selected Zone highlighted at the top of the list If the number is entered incorrectly press the Esc button Page 15 of 32 3 9 Viewing View Menu FIRES FAULTS ALARMS DISABLE INPUTS OUTPUTS PANEL NETWOR Note that Fires Faults Alarms and Disablements are all normally shown without having to select the view menu If however you wish to manually View any of these they can be selected from this menu as required 3 9 1 View Fires This fun
40. tors show the presence of a fire alarm condition and if configured that the fire brigade has been called Indicate other system operating conditions including Fault Test and Disablement conditions Indicates the presence of power to the system if flashing indicates that the panel is running on battery standby power Page 31 of 32 This page is intentionally left blank Page 32 of 32
41. ts ta ete st ese e e deiner 28 B30 Prnt Eaults25525s55 stabat e a bo bla E e ata harte 29 3 13 6 Print Disabled ineo eve e eed m o age det 29 E Grid E E 30 JJ3 8 Print Eeed Raper soc os eie ive d ooi iuda tie 30 User Manual 1 Introduction 1 1 Standards The Mx 4100 Mx 4200 Mx 4400 Mx4400 LE and Mx 4800 Fire Alarm Control Panels conform to the following standards BS EN54 2 1998 Control and Indicating Equipment BS EN54 4 1998 Power Supply Equipment BS EN60950 2000 Safety of information technology equipment BS EN50130 4 1996 Product Family Standard Electromagnetic Compatibility Directive 89 336 EEC and the amending directive 92 23 EEC Low Voltage Directive 73 23 EEC 1 2 Cautions and Warnings Before commencing with installation or operation of the panel please read this manual carefully If you are unclear on any point DO NOT proceed Contact the manufacturer or supplier for clarification and guidance y Only Trained service personnel should undertake the Installation Programming and maintenance of this equipment o This product has been designed to comply with the requirements of the Low Voltage Safety and the EMC Directives Failure to follow the installation instructions may compromise its adherence to these standards This Fire Alarm Control Panel is compliant with the requirements of ENS4 parts 2 and 4 1998 Where appropriate reference is made in this manual to the relevant sections of the ENS4 sta
42. y will show the following Outputs First Zone EH Last Zone 98 Press to Start Print The display will prompt the zones in use on this panel For networked systems it is possible to select any zones used in the system Use the arrow A buttons to highlight the first and last zone number and use the number keys to change the zone number required Press the 3 key to start printing The printout will show all output points for the zones selected Information printed includes Device Text Zone Number Loop and address current status and analogue value Page 28 of 32 3 13 5 Print Faults To print information on any faults highlight the Faults option and press the Y button to confirm The display will show the following 2 Zones in Fault First Zone EH Last Zone 99 Press to Start Print The panel analyses the network and the display will prompt the zones in a fault condition Use the arrow A buttons to highlight the first and last zone number and use the number keys to change the zone number as required Press the 3 key to start printing The printout will show the location and state of all input and output points in a fault condition for the zones selected Note If there aren t any fault conditions present then selecting this menu option will no effect 3 13 6 Print Disabled To print information on any disablement highlight the Disabled option and press the Y button to confirm The di