ME-AC-KNX-1-V2 User Manual

image

Contents

1. 6607 MNET without ack 6608 MNET transmission error 6608 MNET without response 6831 IR remote control transmission error reception error 6832 IR remote control transmission error transmission error 6840 Transmission error with the indoor outdoor unit reception error 6841 Transmission error with the indoor outdoor unit transmission error 6844 Error in inter connection cable in the indoor outdoor unit indoor unit number deactivated 5 min or more 6845 Error in inter connection cable in the indoor outdoor unit cabling error disconnection 6846 Initial timer deactivated In case you detect an error code not listed contact your nearest Mitsubishi Electric technical support service Intesis Software S L All rights reserved This information is subjectto change without notice IntesisBox is a registered trademark of Intesis Software SL n URL http www intesis com 25 25 ntes IS amp Email info intesis com software tel 34 938047134
2. Name Fan Mid2 1bit Function 1 Fan Middle2 Description Indicates or activates this Fan speed with a value of 1 Access type Read Write Data type ID 1 001 Object 29 Name Fan High 1bit Function 1 Fan High Description Indicates or activates this Fan speed with a value of 1 Access type Read Write Data type ID 1 001 Intesis Software S L All rights reserved n URL http www intesis com This information is subject to change without notice n tes IS amp Email info intesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 13 25 IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng Bit Object for Change of Vane Position in steps Object 30 Name Vane 1bit Function 1 To Horizontal O To Vertical Description With every write of 0 the vane position increases goes one step to vertical position Every write of 1 decreases the vane position goes one step to horizontal position Logical sequence is 0 Auto 1 Horizontal 2 Pos1 3 Pos2 4 Pos3 5 Vertical 6 Swing When going to vertical after Vertical position it goes to Swing and then goes round to Auto again When going to horizontal after Horizontal position it goes to Auto and then goes round to Swing again Access type _ Write only Data type ID 1 008 Bit Objects for Selection of Vane Position Only one from the seven objects will be act
3. Selects data type for Set Temperature object e When DPT Step is selected Set Temperature object works in Step logic O Decrease 1 Increase e When DPT UpDown is selected Set Temperature object works in Up Down logic 0 Up 1 Down Data type Enum 8bits DPT Step DPT UpDown Name After an AC command is received from KNX report Status through Description Selects which objects will send its status e Only related objects excluding the receiver e All related objects including the receiver Enum 8bits Yes No Name Show Scene bits Data type Description _ Show Hide Scene bit objects Enum 8bits Yes No Name Show I ncrease Decrease bits Data type Description _ Show Hide Increase Decrease bit objects Enum 8bits Yes No Name Enable Mode Fan Vane strings Data type Description _ Show Hide text type objects for Mode Fan and Vane Enum 8bits Yes No Intesis Software S L All rights reserved This information is subject to change without notice IntesisBox is a registered trademark of Intesis Software SL n URL http www intesis com Intes IS amp Email info intesis com software tel 34 938047134 User s manual r15 1 eng 21 25 IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng Name Mode Auto text Description Text description of Auto Mode to be shown in Mode Text communication objec
4. Scene5 1bit Function 1 Execute scene 5 Description Setting this object to 1 forces ME AC KNX 1 V2 to retrieve from eeprom the values for scene 5 and to setup Operation Mode Setpoint Temperature Fan speed and Vane position in the AC unit accordingly These values should have been saved previously using object Save Scene5 Access type Write only Data type ID 1 001 Intesis Software S L All rights reserved URL http www intesis com u This information is subject to change without notice n tes IS amp Email info intesis com tel IntesisBox is a registered trademark of Intesis Software SL ae 34 938047134 User s manual r15 1 eng 19 25 IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng 5 Parameters Name AC Unit type Description Indicates the type of AC indoor unit Select the model of your AC indoor unit from the list of models available Factory value is type MSZ FA Data type Enum 8bits MSZ FA Name Window minutes Description Minutes to wait before switching the AC unit OFF after receiving the indication of window open If 0 the AC unit will be switched off immediately While in OFF and with window open if it receives an order to switch ON the timer will be initialised and the AC unit will be switched OFF after the configured minutes 0 30 minutes Factory value is 0 D
5. be active in any moment If 1 is written in any of them the rest will be forced to zero If the AC unit changes of Operation Mode the corresponding object will be activated 1 and the rest will be forced to zero Object 19 Name Mode Auto 1bit Function 1 Mode Auto Activated Description Indicates or activates this Operation Mode with a value of 1 Access type Read Write Data type ID 1 001 Object 20 Name Mode Heat 1bit Function 1 Mode Heat Activated Description Indicates or activates this Operation Mode with a value of 1 Access type Read Write Data type ID 1 001 Object 21 Name Mode Dry 1bit Function 1 Mode Dry Activated Description Indicates or activates this Operation Mode with a value of 1 Access type Read Write Data type ID 1 001 Object 22 Name Mode Fan 1bit Function 1 Mode Ventilation Activated Description Indicates or activates this Operation Mode with a value of 1 Access type Read Write Data type ID 1 001 Object 23 Name Mode Cool 1bit Function 1 Mode Cold Activated Description Indicates or activates this Operation Mode with a value of 1 Access type Read Write Data type ID 1 001 Intesis Software S L All rights reserved z URL http www intesis com 12 25 This information is subject to change without notice n tes IS amp Email info intesis com Intesis
6. not required e Direct connection to the KNX EIB bus e Direct connection to the AC indoor unit e Fully KNX interoperable certified by KNX configuration from ETS e Multiple objects for control of different types bit byte characters e Control of the AC unit based in the ambient temperature read by the own AC unit or in the ambient temperature read by any KNX thermostat e Total Control and Monitoring of the AC unit from KNX including monitoring of AC unit s state of internal variables running hours counter for filter maintenance control and error indication and error code e AC unit can be controlled simultaneously by the IR remote control of the AC unit and by KNX e Up to 5 scenes can be saved and executed from KNX fixing the desired combination of Operation Mode Set Temperature Fan Speed and Vane Position in any moment by using a simple switching ETS3 Topology in ME AC KNX 1 V2 HR File Edit View Commissioning Diagnostics Extras Window Help Og m xX 2 c 7HhQ BRHO New Area 1 1 New Line W i 1 1 ME AC D r Slim Interface ER 0 On Off 1bit 1 On 0 OFF E 1 Mode 1byte O Aut 1 Heat 2 Dry 3 Fan 4 Coo C 2 Mode Text 14byte Maximum 14 characters EE 3 Fan 1byte O Aut 1 Low 2 Md1 3 Md2 4 High CE 4 Fan Text 14byte Maximum 14 characters E 5 Vane 1byte 0 Aut 1 Hor 5 Ver 6 Swing CI 6 Vane Text 14byte Maximum 14 characters EE 7 Set Tempera
7. of Intesis Software SL soft 34 938047134 IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng INDEX 1 Presentation tgiscieien ET 4 2 iSonlg edo pe a kedascadsendddlsdadae dada haatduibilents dude asdanedhaadedindiied beadadionuwedabdsans 5 3 Configuration and setup 0 cece eee enna heme e sheer 6 4 KNX communication Obj OCS ea dvs unco roter ere RR Peer Rte IRR Mesa Pa e COR Da Dae D 7 5 Parameters sectie usceceutos case nexu pues suat ERRANAK ARREA AE ENRERE ENKAR ANRA ARRAK AREA ANKER NEERA 20 6 Specificato MS miira aa RERA AE E E EEOAE DROPA AEA EEE OAA ENERE Aaa 24 7 AC Unit Types compatibility cicer ankeren i aa e i cect 24 8 Error Codes ueste iieiaei iiae dto P cursor adea aa dc d d dcn cans CC C i 25 O Intesis Software S L All rights reserved z URL http www intesis com 3 25 This information is subject to change without notice n tes IS amp Email info intesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 IntesisBox KNX Mitsubishi Electric A C User s manual r15 1 eng 1 Presentation ME AC KNX 1 V2 allows a complete and natural integration of Mitsubishi Electric air conditioners with KNX control systems Compatible with all models of Domestic and Mr Slim lines of air conditioners Main features e Reduced dimensions Installation even inside the A C indoor unit e Quick and non visible installation e External power
8. set values for Operation Mode Setpoint Temperature Fan speed and Vane position in the AC unit Access type _ Read only Data type ID 5 Object 16 Name Time Counter 2byte Function 0 65535 hours Description This object indicates the AC indoor unit s operation time in hours Value is stored in ME AC KNX 1 V2 s eeprom This value can be used for maintenance control of AC indoor unit s filter as well as for monitoring AC unit s operation time Set to O for clearing its value after filter maintenance Access type Read Write Data type ID 7 001 Intesis Software S L All rights reserved n URL http www intesis com This information is subject to change without notice n tes IS amp Email info intesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 User s manual r15 1 eng IntesisBox amp KNX Mitsubishi Electric A C Object 17 Name Virtual Set Temperature 2bytes Function 31 169C or 30 199C or 28 172C depending on AC unit type see below Description This object is used to set the temperature setpoint from a external KNX control thermostat It is meant to be used only when ambient temperature is read from an external KNX sensor Value is used by ME AC KNX 1 V2 only when Virtual Temperature Control parameter is active set to Yes See Virtual Ambient Temperature communication object and Virtua
9. Box is a registered trademark of Intesis Software SL soft tel 34 938047134 IntesisBox amp KNX Mitsubishi Electric A C Bit Object for Increase Decrease of Fan Speed Object 24 Name Fan 1bit Function 1 Decrease 0 Increase Description With every write of 1 the fan speed decreases in one step Writing O increases the speed in one step When the maximum speed is reached it changes to automatic Access type Write only Data type ID 1 008 User s manual r15 1 eng Bit Objects for Selection of Fan Speed Only one from the five objects will be active in any moment If 1 is written in any of them the rest will be forced to zero If the AC unit changes of Fan Speed the corresponding object will be activated 1 and the rest will be forced to zero Object 25 Name Fan Auto 1bit Function 1 Fan in Auto Description Indicates or activates this Fan speed with a value of 1 Access type Read Write Data type ID 1 001 Object 26 Name Fan Low 1bit Function 1 Fan Low Description Indicates or activates this Fan speed with a value of 1 Access type Read Write Data type ID 1 001 Object 27 Name Fan Mid1 1bit Function 1 Fan Middle1 Description Indicates or activates this Fan speed with a value of 1 Access type Read Write Data type ID 1 001 Object 28
10. ata type Unsigned 8bits 0 30 Name Send object values to KNX on startup Description Indicates if ME AC KNX 1 V2 will send to KNX the object values indicating AC Unit status at power up when KNX bus is plugged to ME AC KNX 1 V2 Objects indicating AC Unit status are Mode Fan Speed Vane Position and Set Temperature Data type Enum 8bits Yes No Name When window closes go to last state Description Defines behaviour of AC unit once window is closed after AC unit has been switched OFF as a result of an open window timeout f this parameter is set to Yes last value that was written from KNX to object On Off will be sent to the AC unit If it is set to No the AC unit will be left in OFF state until a new ON request is received from KNX Data type Enum 8bits Yes No Name Virtual Temperature Control Description Meant to be enabled when communication objects Virtual Set Temperature and Virtual Ambient Temperature are used When enabled the following formula applies for calculation of Set Temperature sent to the AC unit Set Temperature Ambient Temperature Virtual Ambient Temperature Virtual Set Temperature When enabled Set Temperature object is meant not to be written and Ambient Temperature object is not present When disabled Virtual Set Temperature and Virtual Ambient Temperature objects are not present Data type Enum 8bits Yes No Intesis Software S L Al
11. gh 1108 Internal thermostat detector working 49C 1110 Outdoor unit fail 1300 Pressure low 1302 Pressure high High pressure probe working 63H 1503 Protection against freeze or battery high temperature 1504 Protection against freeze or battery high temperature 1504 Over heating protection 1509 High pressure error ball valve closed 1520 Super heating anomaly due to low temp of discharge TH4 2500 Erroneous operation of drain pump 2502 Erroneous operation of drain pump 2503 Drain sensor anomaly DS 4030 Serial transmission error 4100 Compressor pause due to excess of current initial block 4101 Compressor pause due to excess of current overload 4102 Phase detection opened 4103 Anti phase detection 4108 Phase opened in phase L2 or connector 51CM opened 4118 Error in the anti phase detector electronic board 4124 Connector 49L opened 4210 Cut due to over current of compressor 4220 Voltage anomaly 4230 Radiator panel temperature anomaly TH8 5101 Ambient temperature probe anomaly TH1 indoor unit 5102 Liquid probe anomaly TH2 5102 Cond Evap probe anomaly TH5 5104 Error detection in discharge temperature 5105 Outdoor probe error TH3 5106 Outdoor probe errorTH7 5107 Outdoor probe errorTH6 5110 Outdoor probe errorTH8 5202 Connector 63L opened 5300 Current probe error 6600 MNET duplicated address definition 6602 MNET Line transmission hardware error 6603 MNET BUS busy 6606 MNET Line transmission error 6607 MNET transmission error
12. ion of the selected Fan speed Access type Read only Data type ID 16 001 Object 5 Name Vane 1byte Function 0 Aut 1 Hor 2 Pos2 3 Pos3 4 Pos4 5 Ver 6 Swin Description This object is used to monitor the Vane position in the AC unit Access type Read only Data type ID 5 Object 6 Name Vane Text 14 bytes Function 14 characters maximum Description This object is a text description of the selected Vane position Access type _ Read only Data type ID 16 001 Object 7 Name Set Temperature 2bytes Function 31 169C or 30 199C or 28 179C depending on AC unit type see below Description This object controls the temperature setpoint of the AC unit Value is meant to be written only when parameter is inactive set to No Virtual Temperature Control Access type Read Write Data type ID 9 001 Object 8 Name Ambient Temperature 2bytes Function 10 389C Description This object indicates the current ambient temperature measured by the AC indoor unit Access type _ Read only Data type ID 9 001 Object 9 Name Error 1bit Function 1 Operation Error Description This object when set to 1 indicates either an error in the AC unit or communication failure between AC unit and ME AC KNX 1 V2 Access type _ Read only Data type ID 1 001 Intesis Software S L All rights reser
13. iption Indicates or activates this Vane Position with a value of 1 Access type Read Write Data type ID 1 001 Object 36 Name Vane Swing 1bit Function 1 Vane in Swing Description Indicates or activates this Vane Position with a value of 1 Access type Read Write Data type ID 1 001 Object 37 Name Vane Auto Ibit Function 1 Vane en Auto Description Indicates or activates this Vane Position with a value of 1 Access type Read Write Data type ID 1 001 Intesis Software S L All rights reserved n URL http www intesis com This information is subject to change without notice n tes IS amp Email info intesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 User s manual r15 1 eng 15 25 IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng Bit Object to Change the Setpoint Temperature Object 38 Name Set Temperature 1bit Function 0 Increase 1 Decrease Description With every write of 1 the temperature setpoint decreases in one degree Every write of 0 increases one degree When the maximum or minimum permitted is reached it stops increasing or decreasing Value is meant to be written only when Virtual Temperature Control parameter is inactive set to No Access type Write only Data type ID 1 008 Intesis Software S L All rights reserved URL http www intesis co
14. ive in any moment If 1 is written in any of them the rest will be forced to O If the AC unit changes of Vane Position the corresponding object will be activated 1 and the rest will be forced to zero Object 31 Name Vane Horizontal 1bit Function 1 Vane Horizontal Description Indicates or activates this Vane Position with a value of 1 Access type Read Write Data type ID 1 001 Object 32 Name Vane Pos1 1bit Function 1 Vane in Pos1 Description Indicates or activates this Vane Position with a value of 1 Access type Read Write Data type ID 1 001 Object 33 Name Vane Pos2 1bit Function 1 Vane in Pos2 Description Indicates or activates this Vane Position with a value of 1 Access type Read Write Data type ID 1 001 Object 34 Name Vane Pos3 1bit Function 1 Vane in Pos3 Description Indicates or activates this Vane Position with a value of 1 Access type Read Write Data type ID 1 001 Intesis Software S L All rights reserved z URL http www intesis com 14 25 This information is subject to change without notice n tes IS amp Email info intesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 IntesisBox amp KNX Mitsubishi Electric A C Object 35 Name Vane Vertical 1bit Function 1 Vane Vertical Descr
15. ject s value is read from bus on startup Access type Write only Data type ID 1 009 Object 12 Name Device enable 1bit Function 0 Disabled 1 Enabled Description This object indicates wheter the ME AC KNX 1 V2 is enabled or disable Value is stored in ME AC KNX 1 V2 s eeprom If disabled the only active object of ME AC KNX 1 V2 will be this one the rest of objects will not be operative To enable again ME AC KNX 1 V2 just set this object to 1 Factory value for this object is 1 Enabled Access type Access type Read Write Data type ID 1 003 Object 13 Name Remote control enable 1bit Function 0 Disabled 1 Enabled Description This object is used to disable enable the AC indoor unit s remote control Value is stored in ME AC KNX 1 V2 s eeprom If enabled the AC unit can be controlled simultaneously by both the AC unit s remote control and KNX Factory value for this object is 1 Enabled Read Write Data type ID 1 003 Intesis Software S L All rights reserved This information is subject to change without notice IntesisBox is a registered trademark of Intesis Software SL n URL http www intesis com Intes IS amp Email infoQintesis com software tel 34 938047134 11 25 IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng Bit Objects for selection of Operation Mode Only one from the five objects will
16. l Temperature Control parameter Object s value is read from bus on startup Access type Write only Data type ID 9 001 Object 18 Name Virtual Ambient Temperature 2bytes Function 10 389C Description This object is used to indicate to the AC unit the present ambient temperature measured by an external KNX sensor Value is used by ME AC KNX 1 V2 only when Virtual Temperature Control parameter is active set to Yes See Virtual Set Temperature communication object and Virtual Temperature Control parameter Object s value is read from bus on startup Access type Write only Data type ID 9 001 Intesis Software S L All rights reserved a URL http www intesis com This information is subject to change without notice n tes IS amp Email infoQintesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 User s manual r15 1 eng 10 25 IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng Accessory Objects Object 11 Name Window 1bit Function 0 Open 1 Close Description Indicates to the AC unit the status of the room s window If opened after the minutes indicated in the parameter Minutes Window the AC unit will be switched off automatically The AC unit will remain OFF while the window is open If Minutes Window is 0 the AC unit will be switched off immediately Ob
17. l rights reserved This information is subject to change without notice IntesisBox is a registered trademark of Intesis Software SL n URL http www intesis com Intes IS amp Email info intesis com software tel 34 938047134 20 25 IntesisBox amp KNX Mitsubishi Electric A C Name Operating Mode Byte Object Type Description e When Enumeration is selected Mode object is shown and DPTHvacContrMode object is hidden e When DPT HvacControlling is selected DPTHvacContrMode object is shown and Mode object is hidden e When Both is selected both Mode and DPTHvacContrMode objects are shown Data type Enum 8bits Enumeration DPT HvacControlling Both Name Fanspeed Switching Object Type Description Selects data type for Fan Speed object e When DPT Step is selected Fan Speed object works in Step logic O Decrease 1 Increase e When DPT UpDown is selected Fan Speed object works in Up Down logic O Up 1 Down Data type Enum 8bits DPT Step DPT UpDown Data type Name Vane Switching Object Type Description Selects data type for Vane object e When DPT Step is selected Vane object works in Step logic O Decrease 1 Increase e When DPT UpDown is selected Vane object works in Up Down logic 0 Up 1 Down Data type Enum 8bits DPT Step DPT UpDown Name Set Temperature Switching Object Type Description
18. m u This information is subject to change without notice n tes IS amp Email info intesis com tel IntesisBox is a registered trademark of Intesis Software SL software 34 938047134 16 25 IntesisBox amp KNX Mitsubishi Electric A C Bit Object to save scenes Object 39 Name Save Scene1 1bit Function 1 Save Scene 1 Description Setting this object to 1 forces ME AC KNX 1 V2 to store in eeprom memory the current set values of Operation Mode Temperature Fan speed and Vane position for scene 1 Setpoint Access type Write only Data type ID 1 001 Object 40 Name Save Scene2 1bit Function 1 Save Scene 2 Description Setting this object to 1 forces ME AC KNX 1 V2 to store in eeprom memory the current set values of Operation Mode Temperature Fan speed and Vane position for scene 2 Setpoint Access type _ Write only Data type ID 1 001 Object 41 Name Save Scene3 1bit Function 1 Save Scene 3 Description Setting this object to 1 forces ME AC KNX 1 V2 to store in eeprom memory the current setup values of Operation Mode Setpoint Temperature Fan speed and Vane position for scene 3 Access type Write only Data type ID 1 001 Object 42 Name Save Scene4 1bit Function 1 Save Scene 4 Description Setting this object to 1 forces ME AC KNX 1 V2 to store in eeprom memory the current setup values of O
19. m the values for scene 2 and to setup Operation Mode Setpoint Temperature Fan speed and Vane position in the AC unit accordingly These values should have been saved previously using object Save Scene2 Access type Write only Data type ID 1 001 Object 46 Name Execute Scene3 1bit Function 1 2 Execute scene 3 Description Setting this object to 1 forces ME AC KNX 1 V2 to retrieve from eeprom the values for scene 3 and to setup Operation Mode Setpoint Temperature Fan speed and Vane position in the AC unit accordingly These values should have been saved previously using object Save Scene3 Access type Write only Data type ID 1 001 Object 47 Name Execute Scene4 1bit Function 1 Execute scene 4 Description Setting this object to 1 forces ME AC KNX 1 V2 to retrieve from eeprom the values for scene 4 and to setup Operation Mode Setpoint Temperature Fan speed and Vane position in the AC unit accordingly These values should have been saved previously using object Save Scene4 Access type Write only Data type ID 1 001 Intesis Software S L All rights reserved z URL http www intesis com 18 25 This information is subject to change without notice n tes IS amp Email info intesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 IntesisBox amp KNX Mitsubishi Electric A C Object 48 Name Execute
20. n Mode in the AC unit Access type Read Write Data type ID 20 105 Object 50 Name Mode Cool Heat 1bit Function 0 2Cool 1 Heat Description This object is used to monitor the Operation Mode in the AC unit Writing a O sets the Operation Mode to Cool Writing 1 sets the Operation Mode to Heat Setting the Operation Mode to Heat through Mode object or DPTHvacContrMode object sets this object to 1 Setting the Operation Mode to any other but Heat sets this object to 0 Access type Read Write Data type ID 1 100 Object 2 Name Mode Text 14 bytes Function 14 characters maximum Description This object is a text description of the selected Operation Mode Access type Read only Data type ID 16 001 Object 3 Name Fan 1byte Function 0 Aut 1 Low 2 Md1 3 Md2 4 High Description This object is used to monitor the Fan speed in the AC unit Access type Read only Data type ID 5 Intesis Software S L All rights reserved z URL http www intesis com 7 25 This information is subject to change without notice n tes IS amp Email info intesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 IntesisBox amp KNX Mitsubishi Electric A C Object 4 Name Fan Text 14 bytes Function 14 characters maximum Description This object is a text descript
21. nfo intesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 IntesisBox amp KNX Mitsubishi Electric A C Name Fan High text Description Text description of Fan Speed High to be shown in Fan Text communication object Data type String 14bytes Name Vane Horizontal text Description Text description of Vane Horizontal position to be shown in Vane Text communication object Data type String 14bytes Name Vane Position 1 text Description Text description of Vane Position 1 to be shown in Vane Text communication object Data type String 14bytes Name Vane Position 2 text Description Text description of Vane Position 2 to be shown in Vane Text communication object Data type String 14bytes Name Vane Position 3 text Description Text description of Vane Position 3 to be shown in Vane Text communication object Data type String 14bytes Name Vane Vertical text Description Text description of Vane Vertical Position to be shown in Vane Text communication object Data type String 14bytes Name Vane Swing text Description Text description of Vane in Swing to be shown in Vane Text communication object Data type String 14bytes Name Vane Auto text Description Text description of Vane in Auto to be shown in Vane Text communication object Data type S
22. onnector the one in the largest uncovered part into the socket CN92 or CN105 of the AC unit s control board Fix the ME AC KNX 1 V2 inside or outside the AC indoor unit depending on your needs remember that ME AC KNX 1 V2 must be also connected to the KNX bus Close the AC indoor unit s front cover again IMPORTANT Do not modify the length of the cable supplied with the interface it may affect to the correct operation of the interface Connection of the interface to the KNX bus Disconnect power of the KNX bus Connect the interface to the KNX TP 1 EIB bus using the KNX standard connector red grey of the interface respect polarity Reconnect power of the KNX bus Connections diagram CN105 for Domestic line CN92 for Mr Slim line Consult user manual to identify to which line belongs depending on AC model number CN105 1 or T CN92 1 4 ion cabl Internal Connection cable l supplied with the i l 58 mm wov sjsagupmmm xw QXO8SISe u control 200 mm 2 board interface AC indoor unit KNX TP 1 EIB bus Intesis Software S L All rights reserved URL http www intesis com 5 25 n This information is subject to change without notice ntes IS amp Email info intesis com tel IntesisBox is a registered trademark of Intesis Software SL soft 34 938047134 IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng 3 Configura
23. peration Mode Setpoint Temperature Fan speed and Vane position for scene 4 Access type Write only Data type ID 1 001 Object 43 Name Save Scene5 1bit Function 1 Save Scene 5 Description Setting this object to 1 forces ME AC KNX 1 V2 to store in eeprom memory the current setup values of Operation Mode Setpoint Temperature Fan speed and Vane position for scene 5 Access type Write only Data type ID 1 001 Intesis Software S L All rights reserved n URL http www intesis com This information is subject to change without notice n tes IS amp Email info intesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 User s manual r15 1 eng IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng Bit Object to execute scenes Object 44 Name Execute Scene1 1bit Function 1 Execute scene 1 Description Setting this object to 1 forces ME AC KNX 1 V2 to retrieve from eeprom the values for scene 1 and to setup Operation Mode Setpoint Temperature Fan speed and Vane position in the AC unit accordingly These values should have been saved previously using object Save Scenel Access type _ Write only Data type ID 1 001 Object 45 Name Execute Scene2 1bit Function 1 2 Execute scene 2 Description Setting this object to 1 forces ME AC KNX 1 V2 to retrieve from eepro
24. s ntesisBox KNX ME AC KNX 1 V2 v0 8 Interface for integration of Mitsubishi Electric air conditioners into KNX TP 1 EIB control systems Compatible with Domestic and Mr Slim line air conditioners commercialised by Mitsubishi Electric Application s Program Version 0 8 U i gt ser s Manual KNX r15 1 eng Order Code ME AC KNX 1 V2 Issue Date 2012 07 01 IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng Intesis Software S L All Rights Reserved Information in this document is subject to change without notice The software described in this document is furnished under a license agreement or nondisclosure agreement The software may be used only in accordance with the terms of those agreements No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or any means electronic or mechanical including photocopying and recording for any purpose other than the purchaser s personal use without the written permission of Intesis Software S L Intesis Software S L Mila Fontanals 1 bis 08700 Igualada Spain TRADEMARKS All trademarks and tradenames used in this document are acknowledged to be the copyright of their respective holders Intesis Software S L All rights reserved URL http www intesis com 2 25 n This information is subject to change without notice n tes IS amp Email info intesis com tel IntesisBox is a registered trademark
25. t Data type String 14bytes Name Mode Heat text Description Text description of Heat Mode to be shown in Mode Text communication object Data type String 14bytes Name Mode Dry text Description Text description of Dry Mode to be shown in Mode Text communication object Data type String 14bytes Name Mode Fan text Description Text description of Fan Mode to be shown in Mode Text communication object Data type String 14bytes Name Mode Cool text Description Text description of Cool Mode to be shown in Mode Text communication object Data type String 14bytes Name Fan Auto text Description Text description of Fan Speed Auto to be shown in Fan Text communication object Data type String 14bytes Name Fan Low text Description Text description of Fan Speed Low to be shown in Fan Text communication object Data type String 14bytes Name Fan Mid 1 text Description Text description of Fan Speed Mid 1 to be shown in Fan Text communication object Data type String 14bytes Name Fan Mid 2 text Description Text description of Fan Speed Mid 2 to be shown in Fan Text communication object Data type String 14bytes Intesis Software S L All rights reserved z URL http www intesis com 22 25 This information is subject to change without notice n tes IS amp Email i
26. tion and setup This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS ETS database for this device can be donwloaded from http www intesis com down eib ME AC KNX 1 V2 zip Please consult the README txt file located inside the downloaded zip file to find instructions on how to install the database IMPORTANT Do not forget to select the correct model of AC indoor unit connected to the interface this is in Parameters of the device in ETS Intesis Software S L All rights reserved n URL http www intesis com 6 25 This information is subject to change without notice n tes IS amp Email info intesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng 4 KNX communication objects Main Objects Object 0 Name On Off 1bit Function 1 On O Off Description This object is used to Start On and Stop Off the AC unit Access type Read Write Data type ID 1 001 Object 1 Name Mode 1byte Function O Aut 1 Heat 2 Dry 3 Fan 4 Cool Description This object is used to monitor the Operation Mode in the AC unit Access type Read only Data type ID 5 Object 49 Name HVAC Mode 1byte Function O Aut 1 Heat 3 Cool 9 Fan 14 Dr Description This object is used to monitor the Operatio
27. tring 14bytes Intesis Software S L All rights reserved This information is subject to change without notice IntesisBox is a registered trademark of Intesis Software SL URL Intesis http www intesis com info intesis com 34 938047134 software User s manual r15 1 eng 23 25 IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng 6 Specifications Dimensions 59 X 36 X 21 mm Weight 429 KNX current consumption 5 mA Operating Temperature 25 859C Stock Temperature 40 859C Isolation voltage 4000 V 7 AC Unit Types compatibility A list of Mitsubishi indoor unit model references compatible with ME AC KNX 1 V2 and their available features can be found in http www intesis com pdf IntesisBox ME AC xxx 1 AC Compatibility pdf Intesis Software S L All rights reserved z URL http www intesis com 24 25 This information is subject to change without notice n tes IS amp Email info intesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng 8 Error Codes Code Description In Hexadecimal 8000 No active error 8001 Communication error with the AC unit 1102 Discharge Temperature hi
28. ture 2byte C CI 8 Ambient Temperature 2byte 10 38 C ER 9 Error 1bit 1 Error in AC Unit E 10 Error Code 2byte AC Unit Error Code EE 11 Window 1bit 1 Closed 0 Window Open E 12 Device Enable 1bit 1 Enabled O Disabled E 13 Remote Control Enable 1bit 1 Enabled 0 Disablec EE 14 SavejExec Scene 1byte O Scenel 4 SceneS CE 15 Current Scene 1byte O Scene1 4 SceneS ER 16 Time Counter 2byte Hours Intesis Software S L All rights reserved URL http www intesis com 4 25 ma This information is subjectto change without notice ntes IS Email info intesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 IntesisBox amp KNX Mitsubishi Electric A C User s manual r15 1 eng 2 Connection The interface comes with a cable 3 meters long for direct connection to the internal control board of the AC indoor unit Connection of the interface to the AC indoor unit Disconnect mains power from the AC unit Open the front cover of the indoor unit in order to have access to the internal control board In the control board locate the socket connector marked as CN92 in Mr Slim models or CN105 in the rest of models Using the cable that comes with the interface insert one of its connectors the one installed in the shortest uncovered part into the socket of the ME AC KNX 1 V2 marked as AC Unit and the other c
29. ved n URL http www intesis com This information is subject to change without notice n tes IS amp Email info intesis com IntesisBox is a registered trademark of Intesis Software SL soft tel 34 938047134 User s manual r15 1 eng IntesisBox amp KNX Mitsubishi Electric A C Object 10 Name Error Code 2bytes Function AC Unit Error Code Description This object indicates the Error Code of the AC unit Note that a value of 8000h means no error 8001h means communication error between ME AC KNX 1 V2 and the AC Unit Consult further error codes in the list below Access type Read only Data type ID 7 Object 14 Name Save Execute Scene 1byte Function For Save 128 Scenel 129 Scene2 130 Scene3 131 Scene4 132 Scene5 For Execute O Scenel 1 Scene2 2 Scene3 3 Scene4 4 Scene5 Description This object is used to store execute a scene a scene is a given combination of set values for Operation Mode Setpoint Temperature Fan speed and Vane position in the AC unit The current combination of these values are stored in ME AC KNX 1 V2 s eeprom when saving and retrieved from memory and set in the AC unit when executing Access type _ Write only Data type ID 5 Object 15 Name Current Scene 1byte Function O Scenel 1 Scene2 2 Scene3 3 Scene4 4 Scene5 Description This object is used to monitor the active scene a scene a is given combination of

Download Pdf Manuals

image

Related Search

Related Contents

SW-817 _KINYO_A_三國語說明書_110301  Service Manual, Milano Single Head Coffee Brewer  Consulter l`Appel d`offres  Weslo 10.0i User's Manual  Philips 1906C User's Manual  handbuch für batteriebetriebene, bewässerungs-steuergeräte  IMPORTANT SAFETY INSTRUCTIONS SAVE THESE    自転車による製品事故を防ごう!!  地球環境とソニー ソニーは、あらゆる生命の生存基盤である地球  