1766-UM002 - Rockwell Automation
Contents
1. IP Address 192 168 1 35 Subnet Mask 255 255 255 0 Gateway Address MEAN Default Domain Name Primary Name Server TE WM Secondary Name Server zen um Protocol Control BOOTP Enable DHCP Enable Msg Connection Timeout x 1msj 15000 V SNMP Server Enable 7 SMTP Client Enable Msg Reply Timeout x 1mS 3000 HTTP Server Enable Inactivity Timeout x Min 30 Auto Negotiate Port Setting 10 100 Mbps Full Duplex Half Duplex User Provided Web Pages Starting Data File Number 50 Contact Location Cancel Ce Help RSLogix 500 RSLogix Micro version 8 10 or later also allows you to import an HTML file from your PC to specified ASCII files in the MicroLogix 1400 controller See page 36 for details HTML Pages Referencing Other Pages Servers following are some basic considerations when referencing other pages or servers e reference User Specified Pages in the MicroLogix 1400 controller by using the names zser1 htm through htm Publication 1766 UM002B EN P September 2015 34 Publication 1766 UM002B EN P September 2015 User Provided Pages to reference a page on the same controller specify a URL such as user2 htm e to reference a page on another processor specify a URL such as htip user2 htm where www xxx yyy zzz is the IP address of the controller e you can reference other WWW servers and display images from oth
2. Publication 1766 UM002B EN P September 2015 4 MicroLogix 1400 Embedded Web Server Connect the MicroLogix 1400 controller to the Network 1 Connect the module to the network 2 Obtain an IP address For more information see MicroLogix1400 Programmable Controllers User Manual 1766 UM001 Publication 1766 UM002B EN P September 2015 Connect the MicroLogix 1400 controller to the Ethernet network The RJ 45 connector is on the left hand side of the module 44592 By default the MicroLogix 1400 controller is BOOTP enabled If you connect the MicroLogix 1400 controller to a network that has a BOOTP server that server will assign an IP address to the MicroLogix 1400 controller and the LCD screen of the MicroLogix 1400 controller will display BOOTP IP address If your network does not have aBOOTP server use one of the methods described in the MicroLogix 1400 Programmable Controllers User Manual 1766 UM001 to assign an IP address to the MicroLogix 1400 controller MicroLogix 1400 Embedded Web Server 5 3 Access the Home page of In your web browser s Address box enter the IP address of the MicroLogix the web server 1400 controller The Home page is displayed Specify the IP address of the MicroLogix 1400 controller in the Address window of your web browser This is the controllers page J 9 E 1766 L32AWAA A 2 00 Microsoft Internet Explorer provided by Rockwe
3. TTS LII mm ii Allen Bradley MicroLogix 1400 Embedded Web Server Bulletin 1766 Controllers User Manual Rockwell Automation Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls publication SGI 1 1 available from your local Rockwell Automation sales office or online at http literature rockwellautomation com describes some important differences between solid state equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software de
4. Address a http 192 168 0 10 tcpcfg htm A MicroLogix 1400 Ethernet Configuration Microsoft Internet Explorer provided by Rockwell Automation Links M vid co MicroLogix 1400 Processor Ethernet Configuration TCP IP Configuration Ethernet Address MAC 00 00 BC 4F 00 0E P Address 010 Subnet Mask Gateway Address lame Server Secondary Name Server Default Domain Name Protocol Control Port Speed Port Duplex Auto Negotiate Status Ethernet Connection Current Connections Incoming Connections Outgoing Connections Connections Limit 192 168 0 10 255 255 255 0 0 0 0 0 0 0 0 0 0 0 0 0 Current 100 Mbps Full Duplex Enabled value 0 0 0 16 In 16 Out Simple Home Page Device Information Ethernet Configuration Diagnostic Information Memory Map User Provided Pages Internet Diagnostic Information This section gives you access to the various diagnostic information screens that are available Publication 1766 UM002B EN P September 2015 30 Simple Web Pages The diagnostic screens automatically refresh using a time which is configurable by the user and defaults to 15 seconds F MicroLogix 1400 Diagnostic Information Microsoft Internet Explorer provided by Rockwell Automation DER File Edt View Favorites Tools Help ay Qe Q x a JO search Favorites a Y LJ Address http 192 168 0 10 diags htm x Go links gt MicroLogix 1400 Pr
5. I Uy E O IO gt IO gt gt iO IND O I gt Es gt A O o In gt IO gt O 90 Simple Device Information Ethernet Configuration Diagnostic Information Memory Map User Provided Pages 2 Internet Each file contains a hyperlink that takes you to the specific Data Table Monitor page for that file When you click on a particular file the Data Table Publication 1766 UM002B EN P September 2015 32 Simple Web Pages Publication 1766 UM002B EN P September 2015 Monitor page appears displaying the contents of the data table file you selected MicroLogix 1400 Data Table Monitor Microsoft Internet Explorer provided by Rockwell Automation EDER File Edit View Favorites Tools Help au Qe 2 e JO search Sie Favortes B Ne x Address 48 http 192 168 0 10 module htm Do A MicroLoix 1400 Processor Data Table Monitor Address 0 1 2 B3 0 1023 31745 16415 N e e m px B3 10 64 32 16 B3 20 64 m e w 5 B3 30 B3 40 B3 50 B3 60 B3 70 B3 80 B3 90 B3 100 B3 110 B3 120 B3 130 B3 140 B3 150 B3 160 B3 170 B3 180 B3 190 B3 200 B3 210 B3 220 B3 230 4 0 0 0 0 al 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ojojojojojojojojojojojojojojojo jojojojojojojo mw ojojojojojojojojojojojojojojojo ojojojojojo o ow B3 240 ojo
6. 0 10 255 255 255 0 0 0 0 0 0 0 0 0 0 0 0 0 v SE Links Rockwell Automation Copyright 2008 Rockwell Automation Inc All Rights Reserved Any fields not configured remain blank Specifies Ethernet MAC address of the controller IP address for the controller Internet Subnet Mask subnet mask for the controller Default Gateway gateway address for the controller Primary Server Name Secondary Server Name Domain Name DNS server names if using DNS addressing domain name for the web server module if using DNS addressing Publication 1766 UM002B EN P September 2015 18 Monitor Diagnostics Network Status The Diagnostics gt Network Status page presents a summary of the status of communication activity on the Ethernet network This summary includes e Ethernet network configuration e packets sent and received over the Ethernet network e frames sent and received over the Ethernet network 1766 L32AWAA A 2 00 Microsoft Internet Explorer provided by Rockwell Automation BAE Fie Edit View Favorites Tools Help a Q Back x a Y 7 Search Sie Favorites Ir E E Address http 192 168 0 10 in A Allen Bradley TI PN PR Expand Minirnize Network Status Data Views Interface Counters Media Counters 8 Data Views NewData Rx 206086 Single Collisions User Provided Pages Tx Octets 319019 Mul
7. 1766 UM002A EN P November 2008 Copyright 2015 Rockwell Automation Inc All rights reserved Printed in the U S A
8. Yes please contact me via Return this form to Rockwell Automation Technical Communications 1 Allen Bradley Dr Mayfield Hts OH 44124 9705 Fax 440 646 3525 Email RADocumentComments ra rockwell com Publication CIG C0521D EN P July 2007 PLEASE FASTEN HERE DO NOT STAPLE Other Comments PLEASE FOLD HERE BUSINESS REPLY MAIL FIRST CLASS MAIL PERMIT NO 18235 CLEVELAND OH POSTAGE WILL BE PAID BY THE ADDRESSEE Rockwell Automation 1 ALLEN BRADLEY DR MAYFIELD HEIGHTS OH 44124 9705 NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES PLEASE REMOVE Notes Notes Notes Rockwell Automation Support www rockwellautomation com Rockwell Automation provides technical information on the Web to assist you in using its products At http support rockwellautomation com you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit http support rockwellautomation com Installation Assistance If you experience a problem with a hardware module within the first 24
9. as shown below Any data file property changes must be made offline and downloaded to the processor or later Use Data Views to Access Controller Data 13 Data File Properties General File 3 Type B Name BINARY Desc A T Elements n Last Attributes I Debug Skip When Deleting Unused Memory Scope Global Local oF Lao 2 v Protection Constant C Static None Memory Module Download Web View Disable LCD Edit Disable Publication 1766 UM002B EN P September 2015 14 Use Data Views to Access Controller Data Notes Publication 1766 UM002B EN P September 2015 Chapter 3 How to Use This Chapter Monitor Diagnostics This chapter describes the diagnostics presented on the user oriented diagnostic pages Topic Page Diagnostic Overview 16 Network Settings 17 Network Status 18 MicroLogix 1400 Controller The MicroLogix 1400 controller provides four diagnostic pages of Diagnostics user oriented diagnostics Topic Web page Overview of the current configuration of the MicroLogix 1400 controller Diagnostics Diagnostic Overview Summary of the network settings configured for the MicroLogix 1400 controller Diagnostics Network Settings Ethernet statistics Diagnostics Network Status Publication 1766 UM002B EN P September 2015 16 Monitor Diagnostics Diagnostic Overview E 1766 1 2 A 2 00 Microsoft
10. hours of installation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running United States 1 440 646 3434 Monday Friday 5pm EST Outside United Please contact your local Rockwell Automation representative for any States technical support issues New Product Satisfaction Return Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned United States Contact your distributor You must provide a Customer Support case number see phone number above to obtain one to your distributor in order to complete the return process Outside United Please contact your local Rockwell Automation representative for States return procedure Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation Vorstlaan Boulevard du Souverain 36 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1766 UM002B EN P September 2015 Supersedes Publication
11. s Search she Favorites amp E X LJ Address http 192 168 0 10 Gr Allen Bradley C PN VW PL oo Minimize Data views Y Views New Data View 9 Home Data Views File Name File Type of Element Access Group Apply Data Views Output 6 ees ES New Data View aaa Input 8 Administrator Y lt lt User 1 3 Status 5 Administrator lt lt User 2 Binary Administrator Wl lt lt User 3 m User 4 User 5 User 6 i6 Control Administrator lt lt User 7 User 8 Timer Administrator Y lt lt Counter Administrator lt lt Integer Administrator lt lt Diagnostics Diagnostic Overview Copyright 2008 Rockwell Automation Inc All Rights Reserved Network Settings Network Status Administrative Settings Server Settings User Management 2 http fuww rockwellautomation com MD Internet 3 Click Apply 4 to change an access group for the data table file you specified Publication 1766 UM002B EN P September 2015 Use Data Views to Access Controller Data 9 Monitor Data Views and Use the Data Views Data Views page to view existing data table files Data Table File Click the file name to view the data within a data table file Data View Page The Data Views page displays a list of the data table files their type and size in elements for a connected MicroLogix 1400 as shown in the following example Z 1766 1 2 A 2 0
12. the guest account New Data View File Name File Type i of Element Access Group Publication 1766 UM002B EN P September 2015 26 User Management Recover with Unknown Update the firmware using ControlFlash to initialize both user accounts and Password the access level of data view Publication 1766 UM002B EN P September 2015 Chapter 6 Simple Web Pages MicroLogix 1400 controllers can supply Simple Web Pages in environments where communications status is an issue These type of web pages only support HTML tags without graphic files You can only monitor Ethernet configurations and data tables with these type of web pages The following topics appear on the home page main menu as shown below e Module Information e Ethernet Configuration e Diagnostic Information e Data Table Memory Map e User Provided Pages a MicroLogix 1400 Simple Home Page Microsoft Internet Explorer provided by Rockwel EIER Fie Edit View Favorites Tools Help Qe M x a gt Search sie Favorites 37 E T LJ Address http f192 168 0 10 sindex htm v a Go Links r Rockwell Automation MicroLogix 1400 gt 22 021207 Ethernet Configuration Processor Diagnostic Information Data Table Memory Map amp User Provided Pages Default Home Pages Internet Publication 1766 UMO002B EN P September 2015 28 Simple Web Pages Publication 1766 UM002B EN P September 2015 Device Infor
13. 0 Microsoft Internet Explorer provided by Rockwell Automation BEK Fie Edit View Favorites Tools Help au Oa A SB Address http 192 168 0 10 Eje gt A Rockwell Automation Data Views New Data View Data Views No File Name File Type Display of Element Access Group Data Views 1 v nistrato 1 o0 Output 6 Binary Administrator User Provided Pages 2 1i Input 8 Binary v Administrator D user 1 3 52 Status 66 Hexadecimal Administrator user 2 User 3 4 B3 Binary 1 Binary vj Administrator Bee c 5 T4 Timer i Administrator User 45 User 6 6 cs Counter 1 Administrator User 7 7 RE Control 1 Administrator User 8 r Cu TA 8 NZ Integer 1 Decimal v Administrator Diagnostic Overvir Network Settings Copyright 2008 Rockwell Automation Inc All Rights Reserved Network Status a Administrative Settir y a E ME Each file contains a hyperlink that takes you to the specific Data Views page for that file When you click a particular file the Data Views page appears displaying the contents of the data table file you selected Publication 1766 UM002B EN P September 2015 10 Use Data Views to Access Controller Data 1766 L32AWAA A 2 00 Microsoft Internet Explorer provided by Rockwell Automation DER Fie Edit View Favorites Tools Help Au M p gt Search Sie Favorites A E Address htt
14. 766 UM002B EN P September 2015 2 Table of Contents Notes Publication 1766 UM002B EN P September 2015 Chapter 1 How to Use This Chapter Typical Applications Browser Requirements MicroLogix 1400 Embedded Web Server Rockwell Automation offers enhanced MicroLogix 1400 controllers for your EtherNet IP control systems so you can monitor data remotely via web pages This chapter shows how you can use a MicroLogix 1400 controller in your control system Topic Page Typical Applications 3 Browser Requirements Connect the MicroLogix 1400 controller to the Network moj w Navigate the MicroLogix 1400 Controller With the MicroLogix 1400 controller you can access controller and control system data with different and remote access applications With a web browser you can easily monitor live MicroLogix 1400 controller data remotely With the MicroLogix 1400 controller you can access Simple web page view and custom designed User Provided page views Simple web pages use only HTML tags and are useful in limited communication environments where radio modems are used You can access the MicroLogix 1400 controllers only with Internet Explorer 6 0 Opera 9 23 FireFox 2 0 0 14 or Safari 3 0 4 or higher To access data view pages the browser requires Javascript and XML support The supported display sizes start from 640 x 480 Smaller display sizes also work but require scrolling to view the information
15. File Edit View Favorites Tools Help sax Y ix E Search 57 Favorites A i Address http 192 168 0 10 Allen Bradley Minimize a Home Data Views Device Name 1 User Provided Pages Device Description y Diagnostics 5 Device Location Administrative Settings Ethernet Address MAC F IP Address 1 4 Loginto the web server Many of the features of the MicroLogix 1400 controller require you to log in with appropriate access If you select a feature such as Data Views the MicroLogix 1400 controller prompts you to enter your user name and password The user name is either administrator or guest The password is ml1400 for administrator and guest for guest Default Access User Name administrator or guest case sensitive Password ml1400 for administrator guest for guest Enter Network Password qe This secure Web Site at 192 168 0 10 requires you to log on Please type the User Name and Password that you use for 1756 L32AWAA A 2 00 User Name administrator Password Save this password in your password list Cancel You can set up as many as 10 user accounts Each account can have read write or administrator access For more information see User Management Publication 1766 UM002B EN P September 2015 6 MicroLogix 1400 Embedded Web Server Security Warning Page For MicroLogix 1400 FRN 15 3 or later only To enhance web server security u
16. Input and Output file elements are output in decimal format Status defaults file elements are output in hexadecimal format with a leading Ox Integer file elements are output in decimal format Complex data types Timer Counter Control or other data types are output as a table with bits and important words specified Fixed display Float files are always output in floating point format C 96g formats format ASCII and STring files are always output as a null terminated text string Binary files are always output as two binary bytes Generating Custom Data Table Monitor Pages User Provided Pages 35 HTML Examples the following example shows an HTML code segment with a short description of what you would see on a web browser Examples HTML Code Web Browser Displays Input image word 0 lt ABDTR I 0 gt the value of the first word of the input image table in the default format of decimal with bold type Timer T4 0 IABDTR T4 0 the values of the timer in T4 0 in the default format of a table Timer T4 0 IABDTR T4 096d the values of the three words comprising timer T4 0 in decimal with bold type N24 0 to N24 3 lt ABDTR N24 0 4 gt the values of the four words in N24 0 through N24 3 in decimal with bold type S 21 to 5 723 lt ABDTR S 21 3 d gt the values of the three words in S 21 through 5 23 in decimal with bold type You can generate Custom Data Table Monitor pages with your text ed
17. Internet Explorer provided by Rockwell Automation Ac File Q Back v ddress http 192 168 0 10 Allen Bradley Expand The Diagnostics Diagnostic Overview page presents a summary of the current configuration and overall status of the MicroLogix 1400 controller This summary includes e Ethernet link e Ethernet Connections DER ir Edit View Favorites Tools Help x a Search Favorites BS EB LJ Links gt Rockwell Automation EJ co 1766 L32AWAA A 2 00 Minimize Diagnostic Overview Network Settings Network Status Data Views Ethernet Link Data Views Port 5 New Data View repasa 100 Mbps User Provided Pages Port Duplex Full Duplex Diagnostics Enabled Auto Negotiate Status 1 Diagnostic Overvier Network Settings Network Status Ethernet Connections Administrative Setting Current Ethernet Connections 0 3 server Settings Incoming Ethernet Connections 0 LI SSA eno Outgoing Ethernet Connections 0 Ethernet Connections Limit 16 In 16 Out Seconds Between Refresh 15 Disable Refresh with 0 Internet This field Specifies Ethernet Link Port Speed whether the Ethernet port is operating at 10 Mbps or 100 Mbps Port Duplex whether the Ethernet port is operating at half duplex or full duplex Auto negotiate Status whether the port speed and duplex mode were determined via autonegotiation or whether they were manuall
18. This field Deferred Transmissions Monitor Diagnostics 19 Specifies Frames for which first transmission attempt is delayed because the medium is busy Late Collisions Number of times a collision is detected later than 512 bit times into the transmission of a packet Excessive Collisions Frames for which transmission fails due to excessive collisions MAC Transmit Errors Frames for which transmission fails due to an internal MAC sublayer transmit error Carrier Sense Errors Times that the carrier sense condition was lost or never asserted when attempting to transmit a frame MAG Receive Errors Frames for which reception on the Ethernet interface failed due to an internal MAC sublayer receive error CRC Errors Frames for which CRC error is detected Publication 1766 UM002B EN P September 2015 20 Monitor Diagnostics Notes Publication 1766 UM002B EN P September 2015 Chapter 4 Server Settings In The Field Web Home Page Administrative Settings Select Administrative Settings gt Server Settings to customize some of the server settings of the module as well as back up the file system on the web server module You can e customize server settings including web home page Customize Server Settings Select Administrative Settings gt Server Settings to customize the web home page A 1766 L32AWAA A 2 00 Microsoft Internet Explorer provided by Rockwell Automation FER Fil
19. Views 7 Change an Access Group 8 Monitor Data Views and Data Table File 9 Change Data Table Files 10 Disable Web View 12 Data views give you the ability to read controller data via a browser interface The MicroLogix 1400 controller provides web pages that let you configure a set of files a data view that can be read A data view consists of an HTML file and an XML file with data file information The HTML file is in a readable ASCII format It contains the File Name File Type of Element and Access Group Publication 1766 UM002B EN P September 2015 8 Use Data Views to Access Controller Data Change an Access Group Each data view contains a group of files that you want to monitor Each MicroLogix 1400 controller can support multiple data views One browser supports only one data view so if you want to look at many data views you need to run a corresponding number of browsers You change an access group from the Data Views New Data View page 1 From the Access Group pull down menu of the given data table file choose one of the following access group types e Administrator all access e Write read write access only e Read read access only 2 Choose Administrator Write or Read from the Access Group pull down menu to change a file s access group E 1766 1 2 A 2 00 Microsoft Internet Explorer provided by Rockwell Automation File Edit View Favorites Tools Help 5
20. able Display As Update Back Offset 15 14 13 12 11 10 N7 0 o o 0 0 0 0 2 Double click the data you want to change then the background color turns pink Data Views New Data View N7 Integer writable Display As Binary Offset 15 14 13 12 11 10 N7 0 0 0 0 0 0 3 Enter a value and either press Enter or click an area in the screen then a confirmation window appeats Data Views New Data View N7 0 14 was changed Do you want to change from 0 to 1 Publication 1766 UM002B EN P September 2015 12 Use Data Views to Access Controller Data Disable Web View Publication 1766 UM002B EN P September 2015 4 Click OK to change the value The following screen appears when the value is successfully saved into the server Data Change Result Microsoft Internet e JE Success to Change the New data If the following screen appears the value is not saved and the value returns to the original value Data Change Result 51 xj Access Denied Fail to Change the New data If you want to change the data in Decimal click the pull down menu to change the Display As to Decimal and follow the steps described The steps also apply to the String type Using RSLogix 500 RSLogix Micro V8 10 or higher you can disable individual data files from being viewed via any web browser by selecting the data file s properties page and checking the Web View Disable checkbox
21. because the input output and status files have fixed numbers When defining your custom tag consider the following Tag Item elements Description If not specified this defaults to one If it is less than one also defaults to one Each element is output using the same format whether specified with format or defaulted Any associated comment is displayed only for the first element format Legal values are b for binary d for decimal 0 for octal and x for hexadecimal The following file types allow the format to be specified e Input e Status e Output e Integer All other file types are displayed in an appropriate format Icomment Fixed display formats Data after the exclamation point and up to the closing gt is displayed in the Comment column of the monitor Float files are always output in floating point format C g format String files are always output as a null terminated text string Binary files are always output as four binary nibbles Complex data types Timer Counter Control or other data files are output as a table with bits and important words specified Importing User Page Files to the MicroLogix 1400 Controller Use RSLogix 500 RSLogix Micro to import user page files to the MicroLogix 1400 controller ASCII files 1 In the Project folder under the Data Files folder right click on the first of the block of four consecutive ASCII files where you will import the user
22. e Edit View Favorites Tools Help ay x a J Search Sie Favorites 2 6 Address http 192 168 0 10 Allen Bradley WW TE IV PN Expand Minimize Server Settings Data views Data Views Web Home Page O Default Home Page User Provided Pages Call Diagnostics Q user 1 Web Page Diagnostic Overvier simple Web Page Network Settings 5 Network Status Changes a Administrative Setting Server Settings User Management Copyright 2008 Rockwell Automation Inc All Rights Reserved gt Internet Take This Action Select a home page of MicroLogix 1400 controller If Default Home Page is selected the current web page is shown If User 1 Web Page is selected the first user provided page is shown For information see User Provided Pages on page 33 If Simple Web Page is selected the simple web page is shown For default home page enter the IP address in the URL address bar for example http 192 168 0 10 index htm Publication 1766 UM002B EN P September 2015 22 Administrative Settings Notes Publication 1766 UM002B EN P September 2015 Chapter 5 User Management How to Use This Chapter This chapter describes how to configure user access levels to different information on the module Topic Page User Accounts and Privilege Classes 24 Configure Access Limits for Web Pages 24 Create User Accou
23. er soutces without affecting your usage of data table memory except for the size of the HTTP reference Referencing Data Table Memory reference data table memory locations by placing custom tags into your HTML source which specify the data table location and optional formatting information Use the following format for the custom tag lt ABDTR file_type file_number file_element elements format gt The items surrounded by are sometimes optional The items surrounded by are always optional You must always specify the basic file reference Depending on which file is being referenced fi e_number ot file element may be defaulted If the fz e is I O or S the f e number does not need to be specified but the fz e element must be specified If the 7 e_type is not one of the three special files the f e_number must be specified and the z e_e ement may default to zero the input output and status files have fixed file numbers When defining your custom tag consider the following Tag Item Description elements If not specified this defaults to one If it is less than one it also defaults to one Each element is output using the same format whether specified with format or defaulted format Legal values are d for decimal and x for hexadecimal The following file types allow the format to be specified e Input e Timer e Output e Counter e Status e Control e Integer e Long Display format
24. ided Pages User 1 Server Settings User Management gt User Confirm User 2 Num Delete Edit Name Group Password Add a User User 3 1 Ba admin User 1D User 4 Er 2 est User 5 x Ba ou 1 Group User 6 Read v User 7 Password User 8 Diagnostics Confirm Password Diagnostic Overvi Network Settings Network Status a Administrative Settir Server Settings User Managemen Y lt a lt gt Internet In this field Do this User ID enter the user name for the account 20 characters maximum can contain these characters A Z a z 0 9 underscore _ and dash Group select Administrator Write or Read access for the user account Password enter the password for the account 10 characters maximum Confirm Password re enter the same password for the account IMPORTANT If you use Internet Explorer the number of characters allowed for a user ID or password depends on how many characters fit in the box Larger characters such as W take more room and reduce the total number of allowed characters A user account with a specific previlege can access the Data corresponding to the specific access level i e a user account with Read access level can not access the Data belonging to Write or Administrator acess group The following screen which shows only Read Access Group appears when you log in with
25. itor then download them to the MicroLogix 1400 controller using RSLogix 500 RSLogix Micro version 8 10 or later The first element of the file must contain a special tag as shown here lt ABCDM xx gt where xx is the automatic refresh rate in seconds 01 to 99 A value outside the range defaults to a snapshot display You can modify the refresh rate three different ways e enter the desired refresh rate and press the Change button e select the Default button for a 15 second refresh e disable the refresh by selecting the Disable button Referencing Data Table Memory the Data Table locations in the Custom Data Table Monitor are referenced by placing custom tags into the ASCII file of the processor The format of the custom tag is lt ABDTR file_type file_number file_element 4 elements format comment gt The items surrounded with are sometimes optional whereas the items surrounded by are always optional You must always specify the basic file reference Depending on which file is being referenced fi e_number ot file_element may be defaulted If the 7 e_type is Publication 1766 UM002B EN P September 2015 36 User Provided Pages Publication 1766 UM002B EN P September 2015 O or S the f e number does not need to be specified but the f e_e ement must be specified If the 7 e_type is not one of the three special files the 2 e_number must be specified and the fe_element may default to zero
26. jojojo jojojojojojojojojojojojojojojojojojo ojojojojojojojojojo ojojojojojojo jojojojojojojo o ojojojojojojojojojojojojojojojojojojojojojojo o ojojojojojojojojojojojojojojojojojojojojojojojo mw B3 250 Display format Decimal Refresh data every 15 seconds Default Disable Change Parameters Simple Home Page Device Information Ethernet Configuration Diagnostic Information Memory User Provided Pages Internet The available and default display formats depend on the data type of the file You can change the Display format and Refresh data every xx seconds fields by entering data in the text boxes and clicking the Change Parameters button To change the refresh data function back to the default of 15 seconds click the Default field To disable the refresh data function click the Disable button Chapter User Provided Pages You can use a text editor to generate up to 8 user provided web pages Each page is stored in four consecutive ASCII files of the MicroLogix 1400 controller The channel configuration feature of RSLogix 500 RSLogix Micro version 8 10 or later allows you to select the starting file number and the number of user pages to be stored as shown in the following example Channel Configuration General Channel 0 Channel 1 Channel 2 Driver Hardware Address Me ork Cink ID
27. lication 1766 UM002B EN P September 2015 40 Index Notes Publication 1766 UM002B EN P September 2015 How Are We Doing Your comments on our technical publications will help us serve you better in the future Thank you for taking the time to provide us feedback You can complete this form and mail or fax it back to us or email us at RADocumentComments ra rockwell com Pub Title Type MicroLogix 1400 Embedded Web Server Cat No Bulletin 1766 Controllers Pub No 1766 UM002A EN P Pub Date November 2008 Part No Please complete the sections below Where applicable rank the feature 1 needs improvement 2 satisfactory and 3 outstanding Overall Usefulness 1 2 9 How can we make this publication more useful for you 2 3 Can we add more information to help you Completeness all necessary information procedure step illustration feature is provided MN example guideline other explanation definition Technical Accuracy 1 2 3 Can we be more accurate all provided information is correct text illustration Clarity 1 2 3 How can we make things clearer all provided information is easy to understand Other Comments You can add additional comments on the back of this form Your Name Would you like us to contact you regarding your comments there is no need to contact me Your Title Function Location Phone Yes please call me Yes please email me at
28. mation The device information page displays a table with information about the Micrologix 1400 controller The specific information displayed includes the controller model series revision and mode of the controller A MicroLogix 1400 Processor Information Microsoft Internet Explorer provided by Rockwell Automation DER Fie Edit View Favorites Tools Help a Qe c x a JO search Favorites 2 BE z Ly Address http 192 168 0 10 madule htm Do Er MicroLogix 1400 Processor Device Information Device Name 1766 L32AWAA 2 00 Device Description MicroLogix 1400 Processor Device Location Ethernet Address MAC 00 00 BC 4F 00 0E IP Address 192 168 0 10 OS Revision Series A FRN 2 0 HTML File Revision 1 7 Current Time RTC is disabled CPU Mode Remote Program Contacts Simple Home Page Device Information Ethernet Configuration Diagnostic Information Memory Map User Provided Pages Internet Ethernet Configuration This page displays a table with information about the current Ethernet configuration parameters Included are the module s IP address the subnet mask gateway address the Ethernet hardware address and whether BOOTP is Simple Web Pages 29 enabled Also included are the name server secondary name server and the default domain name parameters if configured ER File Edit View Favorites Tools Help Ar Qs c2 x a JO search Sie Favorites v
29. nts 25 Recover with Unknown Password 26 By assigning user accounts with different access levels you can manage which users have access to view network configuration or have access to view and change data views Several pages on the MicroLogix 1400 controller such as diagnostics pages and data views pages have default access protection Before accessing these pages you must authenticate your access by entering a user name and password The module displays the log in box when you access these web pages IMPORTANT Once authenticated you do not have to re enter a user name or password when accessing subsequent pages You must close your browser to log out The default user name is administrator with password ml1400 or guest with password guest IMPORTANT It is strongly recommended that you change the password for the default Administrator account For MicroLogix 1400 FRN 15 3 or later the password ml1400 will no longer be accepted when changing or after changing the password for the default Administrator account Publication 1766 UM002B EN P September 2015 24 User Management User Accounts and Privilege Classes Configure Access Limits for Web Pages Publication 1766 UM002B EN P September 2015 The MicroLogix 1400 controller supports multiple user accounts each with a user name and password Each user account is configured for one of these access levels e Administrator all access e Write read wri
30. ocessor Diagnostic Information Rx Octets 174376 Single Collisions Tx Octets 231429 Multiple Collisions Rx Packets li 1313 Deferred Transmissions Tx Packets 1057 Late Collisions Command Sent Excessive Collisions Command Received MAC Transmit Errors Replies Sent MAC Receive Errors Replies Received Carrier Sense Errors Replies Sent with error CRC Errors Replies Received with error 0 0 0 0 0 0 0 0 0 Refresh counters every 15 seconds Change Default J Disable Simple Home Page Device Information Ethernet Configuration Diagnostic Information Memory Map User Provided Pages Internet Publication 1766 UM002B EN P September 2015 Simple Web Pages 31 Data Table Memory Map The Data Table Memory Map page displays a list of the data table files their type and size in elements for a connected MicroLogix 1400 controller To view memory maps login with a Read access group user account A MicroLogix 1400 Data Table Memory Map Microsoft Internet Explorer provided by Rockwell Automation DER Fie Edit View Favorites Tools Help Ar Qe Q x a JO search 57 Favortes B E Address http J192 168 0 10 module htm Do uns MicroLogix 1400 Processor Data Table Memory Map File Elements File Type 256 Binary 256 ASCII 256 ASC 256 ASC 256 ASCII 256 ASC 256 ASCII 256 ASCII 256 ASC 256 ASC
31. om Tag Error A12 0 Value OK MB A12 0 2 Value OK MB gt A12 0 10 Value ER MBJ gt Binary Test A12 096b Value No Custom Tag Error A12 096B Value Custom Tag Error A12 096b 5 Value No Custom Tag Error Done Internet Publication 1766 UM002B EN P September 2015 38 User Provided Pages Notes Publication 1766 UM002B EN P September 2015 A access group creating 8 access levels classes 24 access limits configuring 24 administrative settings 27 Administrator access 24 authentication 24 browser requirements 3 change data table files 70 configure server settings 27 configuring access limits 24 user accounts 25 connecting 4 creating access group 8 D data table memory map 37 data views monitoring 9 overview 7 device information 28 diagnostic information 29 Diagnostic Overview 16 diagnostics diagnostic overview 16 Ethernet statistics 18 network settings 17 disable web view 72 E Ethernet configuration 28 G generating custom data table monitor pages 35 Index H HTML pages 33 installing 4 IP address 4 MicroLogix 1100 Controller Diagnostics 75 monitor diagnostics 15 navigating 6 password 23 26 Read access 24 recovering 26 requirements browser 3 server settings 27 simple web pages 27 T typical applications 3 U user accounts classes 24 creating 25 user management 23 user provided pages 33 W write access 5 Pub
32. or Diagnostics Administrative Settings User Management Simple Web Pages User Provided Pages Table of Contents Chapter 1 Howto Use This Chapter ER Seren 3 Typical Applications o arcae odes ets ersehen 3 Browset Requirements suisse as Basen ua 3 Connect the MicroLogix 1400 controller to the Network 4 Navigate the MicroLogix 1400 Controller 6 Chapter 2 How to Use This Chapters pi Up tn 7 Overview GF Data VIEWS rcu quce EA AAA AA 7 Chane arr Access Group ea sera ele bas 8 Data VIEW PAGERS paa 9 Change Data Table Files nee ee 10 How to Change a Data File 10 Disable se ire ad hoher 12 Chapter 3 How to Use This Chapter za ta ee o 15 MicroLogix 1400 Controller Diagnostics 15 Network a ROT 18 Chapter 4 Server SCHIEN P EM UE 21 C stomize Server SERIO eee padece a d S 21 Chapter 5 How to Use This Chapter wen Frac cite e hoo dcin ere cts 23 User Accounts and Privilege 1 24 Configure Access Limits tor Web Pages Br eese RA 24 Recover with Unknown Password 26 Chapter 6 Device Taformation A ee 28 Ethernet Configurations essen 28 Diagnostic Information ae ae ea 29 Data Table Memory Map a ae Era O 31 Chapter 7 Pages AR 33 Generating Custom Data Table Monitor Pages 35 Index Publication 1
33. p 192 168 0 10 Rockwell Automation Data Views New Data View 00 Output Display As Binary 11 Data Views New Data View User Provided Pages User 1 A User 2 User 3 User 4 User 5 User 6 User 7 User 8 Diagnostics Diagnostic Overwi gt Copyright 2008 Rockwell Automation Inc All Rights Reserved The available and default display formats depend on the data type of the file Click Back to display the previous page To refresh the data view click Update Change Data Table Files The data in the Data File Types such as Binary Integer Long Float and String can be changed The Binary Integer and Long types support all the Display formats You can edit Binary types by bit and the Octal Decimal and Hexadecimal types by element A user account with either Write or Administrator access level can change the Data Table Files When you click N7 in Data Views Data Writable appears beside a Data File Type Integer here as shown below Data Views New Data View 7 Integer writable Display As v Update Back Offset 0 1 2 3 4 5 6 7 8 9 How to Change a Data File Type In the steps that follow a Binary type is assumed Publication 1766 UM002B EN P September 2015 Use Data Views to Access Controller Data 11 1 Change Display As to Binary then the following screen appears Data Views New Data View 7 Integer writ
34. page HTML file 2 Click on Properties 3 Click on Import HTML 4 Use the browser to locate the user page HTML file you want to import 5 Double click on the file to select it 6 Click OK 7 Repeat this process for each user page file User Provided Pages 37 8 When all user page files have been imported go online with your MicroLogix 1400 controller processor 9 Select the User Provided Pages link to view the User Provided Pages menu as shown in the following example A MicroLogix 1400 User Provided Pages Microsoft Internet Explorer provided by Rockwell Automation DER Fie Edit View Favorites Tools Help 7 Qs x a search Favorites a LJ Address http 192 168 0 10 module htm Io Links gt Hr MicroLogix 1400 Processor User Provided Pages Pages User Provided Page 1 User Provided Page 2 User Provided Page 3 User Provided Page 4 Simple Home Page Device Information Ethernet Configuration Diagnostic Information Memory Map User Provided Pages Internet Click on the User Provided Page RX to display that specific page ASCII Test Microsoft Internet Explorer provided by Rockwell Automation File Edit View Favorites Tools Help Qe e x a search Sie Favorites B a M m Address 48 http 192 168 0 10 module htm ASCII Test file type and file number Test A Value No Custom Tag Error A 0 Value No Cust
35. pon logging in to the MicroLogix 1400 Web Server page with the default administrator account and default password a warning displays to notify the user to change the default password Aten sradey 1766 L32BXB B 15 03 Automation O Do not prompt me until next controller power up i i You navigate the web server s web pages by using the navigation panel on the avigate the MicroLogix 8 pages by using g P 1400 Controller left of the screen There are also tabs across the top you can click to navigate the folders containing documents Tabs across the top match the documents within a folder as shown in the left navigation panel 1766 L32AWAA A 2 00 Microsoft Internet Explorer provided by Rockwell Autom File Edit View Favorites Tools Help Q HAG Dr deem 2 5 Click folders to open and close additional levels of information 1766 13 Device Name Device Description MicroLog Click a document to display a A m th dd FF FF web page showing specific gt Ethernet Address MAC FF FF FF information IP Address 192 168 OS Revision Series A HTML File Revision L7 Publication 1766 UM002B EN P September 2015 How to Use This Chapter Overview of Data Views Chapter 2 Use Data Views to Access Controller Data The MicroLogix 1400 controller provides access to the controller data table files This chapter shows you how to set up views of data table files Topic Page Overview of Data
36. scribed in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations Identifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss IMPORTANT Identifies information that is critical for successful application and understanding of the product Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you identify a hazard avoid a hazard and recognize the consequence ATTENTION TU avai Labels may be on or inside the equipment such as a drive or motor to alert people that dangerous voltage may be present AMET Labels may be on or inside the equipment such as a drive or motor to alert people that surfaces may reach dangerous temperatures lala la Rockwell Automation Allen Bradley SLC 5 02 SLC 5 03 PLC 5 MicroLogix SLC 500 RSLogix RSLinx RSLogix 500 RSLogix Micro and TechConnect are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies MicroLogix 1400 Embedded Web Server Use Data Views to Access Controller Data Monit
37. te access only e Read read access only The access level determines which web pages the user can access You configure access limits for individual web pages Each page in the MicroLogix 1400 controller has one of these protection levels e Administrator e Write e Read The protection levels are hierarchical Administrator users can access Read protected pages These pre defined pages those web pages that come with the MicroLogix 1400 controller in the MicroLogix 1400 controller have these default access levels You can change the Data View access group if needed with administrator privilege Web Page Default Protection Level Home page no protection Diagnostics pages Read protection Data Views Read protection New Data View Administrator protection Server Setting page Administrator protection User Management page Administrator protection User Management 25 Create User Accounts You need Administrator access to create and modify user accounts You can create as many as 10 individual accounts You manage accounts from the Administrative Settings User Management Edit Users page A 1766 1 2 A 2 00 Microsoft Internet Explorer provided by Rockwell Automation File Edit View Favorites Tools Help a Qe 5 gt a Search sie Favorites vut 2 m Address http 192 168 0 10 v SE Links gt Allen Bradley ASSUM U New Data View ca User Prov
38. tiple Collisions Diagnostics Rx Packets 1633 Deferred Transm Diagnostic Overviev Tx Packet 1315 Late Collisi eee Braces ate Collisions Olfen Command Sent Excessive Collisions a Administrative Setting Command Received MAC Transmit Errors Server Settings Replies Sent Carrier Sense Errors 5 User Management Replies Received MAC Receive Errors Replies Sent with error CRC Errors Replies Received with error Replies Timed Out Seconds Between Refresh 15 Disable Refresh with 0 Internet This field Specifies Interface Counters Rx Octets Octets received on the Ethernet interface Tx Octets Octets sent on the Ethernet interface Rx Packets Packets received on the Ethernet interface Tx Packets Packets sent on the Ethernet interface Command Sent Command sent on the Ethernet interface Command Received Replies Sent Command received on the Ethernet interface Replies sent on the Ethernet interface Replies Received Replies received on the Ethernet interface Replies Sent with error Outbound packets that contain errors Replies Received with error Inbound packets that contain errors Replies Timed Out No reply within a specified time period Media Counters Single Collisions Successfully transmitted frames which experienced exactly one collision Multiple Collisions Publication 1766 UM002B EN P September 2015 Successfully transmitted frames which experienced more than one collision
39. y configured Ethernet Connections Current Ethernet Connections current number of active connections Incoming Ethernet Connections current number of incoming connections Outgoing Ethernet Connections current number of outgoing ethernet connections Ethernet Connection Limit Publication 1766 UM002B EN P September 2015 maximum number of Ethernet incoming outgoing connections Network Settings This field Network Interface Ethernet Address MAC IP Address Monitor Diagnostics 17 The Diagnostics gt Network Settings page presents a summary of the current Ethernet configuration for MicroLogix 1400 This summary includes e Ethernet address details E 1766 1 2 A 2 00 Microsoft Internet Explorer provided by Rockwell Automation File Edit View Favorites Q Back Tools Help Address E http if192 168 0 10 x a Search Sie Favorites 223 E y Allen Bradley Expand Minimize Home Data Views 9 Data Views I New Data View Cal User Provided Pages Diagnostics El Diagnostic Overviev 8 Network Settings 3 Network Status Administrative Setting 5 server Settings User Management 1766 L32AWAA A 2 00 Diagnostic Overview Network Settings Network Status Network Interface Ethernet Address MAC IP Address Subnet Mask Default Gateway Primary Name Server Secondary Name Server Default Domain Name FF FF FF FF FF FF 192 168
Download Pdf Manuals
Related Search
Related Contents
B142 GAS QUIKSERT® TURBINE FLOW SENSOR Manual de instalação e instruções de uso American Power Conversion NS 600 User's Manual flash depliant bon der - Communauté de communes du Langeadois User`s Manual Quick Guide MANUEL D`INSTRUCTIONS - TA Triumph Optio 33L Panduit RJ12 Copyright © All rights reserved.