1. Power Models GOOCB10 and 600CB12 15 16 17 18 19 20 21 22 Also test fuse alarm relay contacts at CB F alarm terminals e Expect continuity 00 between Terminals C and NC e Expect an open circuit ee between Terminals C and NO Repeat Steps 13 and 14 to power up Side B A PWR and B PWR LEDs must both be green Make sure input power is off again before installing output wiring to this device For output wiring crimp dual hole lugs onto one end of 10 to 2 0 AWG copper output wires as required by NEC Work with one output wire at a time Insulate lug barrels with UL94 V O rated heat shrink tubing Clean the panel terminal and lugs with non abrasive non metallic pad If required lightly coat anti oxidant on lugs and output BATT and RTN terminals and then connect lugs to terminals as shown in Figure 10 NEC specifies only one lug and load at each output terminal Tighten nuts to no more than 50 in Ib 5 6 Nem max and then connect other end of output wire to load Install circuit breakers or fuses as shown in Figures 11 and 12 a Use screws provided with circuit breaker or fuse holder to attach cover to breaker or holder Use the cover removed previously for circuit breakers The fuse holder requires a cover b Insert a breaker in the load center frame Line is on top Breaker is upside down so ON toggle is up Or insert holder in load center frame Load is on top
2. ss c Fasten the cover to the load center using the screw previously removed with the cover in Step 1 d If applicable install fuse Figure 10 Output Lug Connections Telect Inc All Rights Reserved 136429 1 AO 07 14 10 1 509 926 6000 telect com Telect Dual Feed 600A Load Center Frame Power Models 600CB10 and 600CB12 2 Single Pole a a Breaker Ne se 7 N Rt p N yom SS Pad ki LINE gt 4 ne amp 1 P ooa a or and 4 A a s Double Pole ees A Breaker A A R Figure 11 Installing Circuit Breakers TPC Fuse SS Holder 7 pon Sa 1 ne TPC Fuse Figure 12 Installing Fuse Holders and Fuses 23 With the output loads devices fed by this load center disabled re enable fuses or breakers at primary distribution unit or battery 24 If applicable switch circuit breakers ON and then check voltage and polarity at loads Telect Inc All Rights Reserved 136429 1 AO 07 14 1 509 926 6000 telect com Telect Dual Feed 600A Load Center Frame Power Models 600CB10 and 600CB12 25 If possible either replace one of the functioning fuses with a blown fuse or switch OFF breaker e Fora load center with fuses or non mid trip circuit breakers the applicable ALM LED will turn red e Fora load center with mid trip breakers the applicable ALM LED will remain green 26 Check the CB F alarm terminals For a load center with fuses or non mid trip circuit breakers exp
3. 23 to 120 F 600A 75 C 167 F 49 to 55 C 120 to 131 F 550A 75 C 167 F 49 to 55 C 120 to 131 F 600A 90 C 194 F 9 Insulate the lug barrels with UL94 V O rated heat shrink tubing 10 Clean terminals and lugs with a non abrasive non mettalic pad 11 If required lightly coat anti oxidant on lugs and input BATT and RTN terminals and then connect lugs to input terminals as shown in Figure 8 Tighten lugs to 150 in lb 17 Nem max Side A Input RTN JAN i 4 Mi 6 2 Side A Input BATT R Figure 8 Input Lugs 12 Make sure the breaker or fuse holder positions are either empty off or contain dummy fuses phoney inoperative all plastic slugs Telect 13 Enable the fuse or breaker at primary distribution unit or battery rie 750A max to turn on Feed A to Side A of load center and then A PWRI check voltage and polarity at input connectors of the panel Verify the ALM following B PWR lt APWR LED on front of panel turns green ALM e BPWR LED turns red MOON MAX PER POLE INPUT 14 With A PWR LED green normal operation but with B PWR LED red A a B off or failure operation test A PWR relay and contact alarm terminal 24 e Expect continuity 00 between Terminals C and NC J e Expect an open circuit ee between Terminals C and NO Figure 9 LED Panel Telect Inc All Rights Reserved 136429 1 AO 07 14 9 1 509 926 6000 telect com lelect Dual Feed 600A Load Center Frame
4. Center Frame Power Models 600CB10 and 600CB12 ay D gt D 4 Plastic Load Strap Receptacle Holder Figure 2 Installing Load Straps 2 Turn over the load center and check the jumper settings on the alarm board located on the underside of the chassis Refer to Figures 3 and 4 The jumpers are set up for REC 4 non mid trip circuit breakers and fuses If you plan on using RLS 4 mid trip circuit breakers change the jumper setting as indicated Alarm Board Jumpers 6 Figure 3 Alarm Board Location bottom view of side A Telect Inc All Rights Reserved 136429 1 AO 07 14 5 1 509 926 6000 telect com Telect Dual Feed 600A Load Center Frame Power Models GOOCB10 and 600CB12 From the factory jumpers are set for REC 4 non mid trip circuit breakers and fuses a a a a g a a a ag a a REC 4 CBs RLS 4 Mid Trip CBs amp Fuses Figure 4 Alarm Board Jumper Settings 3 If you intend to install alarm wiring for load center and or bay alarms consider doing so now before installing the load center in the rack The alarm terminal is located near the top center of the load LEGEND center Refer to Figure 5 B PWR NO MINOR ACT NG NORMALLY CLOSED C COMMON l B PWR C MJR MNR REF NO NORMALLY OPEN a If you intend the alarm wires to exit at the back BEWE NG MAJOR AGT GBSGIRGUIT BREAKER r CB F NO MINORNO F _ FUSE of the rack don t forget to feed alarm wiring ACT ACTIVATE f th b k t th f
5. Circuit breakers for this load center are designed and manufactured by Airpax Corporation and Carling Industries to meet Telect s specifications Order circuit breakers only from Telect Telect Inc All Rights Reserved 136429 1 AO 07 14 3 1 509 926 6000 telect com Telect Dual Feed 600A Load Center Frame Power Models GOOCB10 and 600CB12 ALERT Only qualified technicians may install and maintain this product Verify all connections meet requirements specified in local electric codes or operating company guidelines before supplying power Protect this equipment with a fuse or breaker sufficient to interrupt power levels specified Install this product in locations accessible only to qualified personnel The panel weighs more than 35 Ibs 16 kg two persons may be required for handling and installing the Load Center Frame 1 4 Installation Instructions Please read these instructions carefully before beginning installation If assistance is required call Technical Support at 888 821 4856 or 509 921 6161 or e mail getinfo telect com e Teleci is not liable for shipping damage If damaged notify the carrier and call Telect s Customer Service Department at 800 551 4567 or 509 926 6000 for further recourse e Teleci recommends that you install load straps before installing the load center on the rack Also install load straps now for future add on loads e Inspect equipment after unpacking and compare it to the packin
6. NAKER EE dagan AA ag a NENEK PAKAN PANEN Ega ma PENGENE aga ea 6 Figure 6 Rack MOUNTING sasasi kana Kaka anak RE OR A KEKAH ia KAEN KE MR E 7 Figure 7 Ground Lug Connection ee Re AA Re RA ee ke ee ge ee ee Re ee 8 Roure 6 ne LUOS EE ER NR ER HE ER OE ER EE IG 9 Figure 9 LED Panel EER De Se Ee ee dee hb de DE ee tia n ek soe EE ee tienen eis 9 Figure 10 Output Lug Connections i sesse ee AA oa anaa anana gene Re gan aaa RA RA ee 10 Figure ti sIfnstallind Circuit Breakers is esse EE se sand OE eiiiai 11 Figure 12 Installing Fuse Holders and Fuses iss ese sesse ee ee ee ee ee ee Re ee ee Re ee ee Re ee ee ee 11 List of Tables Table 1 Circuit breakers fuses fuse holders and load strap kits sasarane aane aana Re 13 Table 2 Input power UGS EE tices ag ANAN a diate ds a NAN ANNA WG EN anes EA GEN WA Aa a naa Na ea gama dates 14 Table 3 Ground and circuit breaker output lUgs see AR Re Re ee aana ee 14 Telect Inc All Rights Reserved 136429 1 AO 07 14 ii 1 509 926 6000 telect com Telect Dual Feed 600A Load Center Frame Power Models 600CB10 and 600CB12 1 1 Overview Telect s dual feed 600A per feed load center frames provide high capacity 48V and 24V power protection for secondary power distribution and data and communications equipment Telect s load center frames are also ideal for primary distribution in small central offices and at remote sites Models 600C
7. kit to mount 600CB10 in a 23 rack 02117 02 746 Adapter kit for double pole input 600CB1X 2FA Load Connections Part Number Single pole 600CB1X 1PK Double pole 600CB1X 2PK 1 Two kits are required for dual feed inputs Triple pole 600CB1X 3PK 2 Required when using the GOOCB1X 3PK or 600CB1X 4PK 3 Holder kits contain fuse holder cover and fasteners Four pole 600CB1X 4PK 4 Load connection kits contain receptacle strap assembly and lug fasteners Telect Inc All Rights Reserved 136429 1 AO 07 14 13 1 509 926 6000 telect com Telect Dual Feed 600A Load Center Frame Power Models GOOCB10 and 600CB12 1 ALERT ALERT Only use components and crimping tools approved by agencies or certifying bodies recognized in your country or region such as Underwriter s Laboratories UL TUV etc Table 2 Input power lugs 400 MCM 500 MCM 750 MCM 777 7 MCM T amp B 54216 54218 Die code 76 Die code 87 Burndy YA322TC38 YA342TC38 YA392NT38 YA44L 2NT38 FX Die code 19 Die code 20 Die code 24 Die code L115 Panduit LCD400 38D 6 LCD500 38D 6 LCDN750 38D 6 Die code 76 Die code 87 Die code 106 Table 3 Ground and circuit breaker output lugs 1 4 in dual holes on 5 8 in centers uninsulated 8 AWG 6 AWG 4 AWG 2 AWG 2 0 AWG T amp B 542040410 54205 54206 54207 Die code 21 Die code 24 Die code 29 Die code 33 Burndy YA8CL 2TC14 YA6CL 2L YA4C 2L YA2CL 2TC14 YA26
8. B10 and 600CB12 are open frame chassis providing excellent heat dissipation and overhead access to the load centers BATT and RTN terminals vertical inputs Models 600CB10 and 600CB12 are white 2RU and fit racks with either EIA or WECO spacing Figure 1 600CB10 19 10 10 Position e Model 600CB10 contains 10 interrupter positions Load Center Frame on each side and fits a 19 in rack an adapter kit can be purchased separately to mount the 600CB10 in a 23 rack e Model 600CB12 has 12 interrupter positions on each side and fits a 23 in rack Both accommodate AIRPAX style LEL or Carling CA1 circuit breakers or fuses TPC TPW and TPS TLS in single through quad pole configurations Each circuit breaker or fuse pole position accommodates a bullet style plug in circuit breaker or fuse holder up to 100A With double pole circuit breakers or TPW fuses the maximum output load can be up to 200A With the triple pole circuit breakers the maximum load is 250A and with quad pole circuit breakers the maximum load is 400A Sides A and B are electrically isolated except for the alarm card which contains power fuse and bay status relays with dry Form C contacts The contacts are connected to wire wrap pins to switch on external power to visual audio external alarms The alarm card also controls the three dual color LEDs on the front panel All input output and alarm terminals are within the open frame chassis All BATT and RTN inputs outputs
9. Dual Feed 600A Load Center Frame Power 600CB10 and 600CB12 User Manual 600CB10 Front View 600CB10 C Rear View Telect Inc All Rights Reserved 136429 1 AO 0714 1 509 926 6000 telect com Telect Dual Feed 600A Load Center Frame Power Models GOOCB10 and 600CB12 Table of Contents AST OW ENVIS WW aas ee a EA a TAK AA a E ee I Ge a E a ag NE A ST a a b Ka aia EE Oe ie 1 1 2 Installation Guidelines cccceseesseeeeeeeececccecceccecccceeeeceaeausuauaaueuaeeaeessnseececececeeeeseneeeeeeeeenenea 2 1S Specificato S sisina ER OR NO ER EN cate 2 1 4 Installation Instructions esse ee Ee ee EE ee ee ee ee ee ER ee ee ee ee ee ee ee RE ee ee ee eke Re Re ee eek ee ee 4 1 5 Parts amp AccessONeS es ajaa Ee oe gra BA an KK AIK BIG de RE GENG SO IE a ee Ge a la a a ee EG DE ee Gee 13 1 GH MTEKCOMMECTIONS ss be ee Ab AE Sage NE a a Ge ee Eg ee NAN NE ie a Ge ee N 15 di Sos Borst es ha Ga a aaa an a aka mada na es aa gan dan pa anan ka a RR EE RE an 16 List of Figures Figure 1 600CB10 19 10 10 Position Load Center Frame sseeaaenee ee Re ee nenen eee 1 Figure 2 lt installing Load Staps sssrini ganean toe ede ge dad ese eel keep 5 Figure 3 Alarm Board Location bottom view of Side A ee ee anana eaaa eaaa aana nenen 5 Figure 4 Alarm Board Jumper Settings ii iese ee Re ke Re ee Re Re ee ee ke ee ee ee 6 Figure 5 Alarm Wiring RR aaa nemani eaaa nan d Bak aa ma E ENE
10. Glad 00 a O Q RETURN B INPUT B 600A MAX GND cano Telect Inc All Rights Reserved 136429 1 AO 07 14 15 1 509 926 6000 telect com Telect Dual Feed 600A Load Center Frame Power 1 7 Drawings NOTES 1 Dimensions are in in mm 2 Breakers Fuses sold separately 3 Breaker Fuse line straps sold separately 4 Max lug width for input BATT and RTN is 50 mm 2 in 33 16 x1 14 in Stud Nut Lock Washer amp Flat Washer REAR VIEW ROTATED 0 625 15 9 14 20 x in Stud KEPS Nut amp Washer 1 A 2 SA 0 625 15 Te osas ee RINA BUS 14 20 x Ya in RTN A Input Terminal See Note 4 BATT A Input Terminal BATT A BUS T 0 73 18 5 1 TOP VIEW 600CB10 19 00 482 6 18 31 465 1 17 00 431 8 1 2 3 4 5 6 7 8 9 10 n 12 1 Telect Om 3 00 76 2 nou a Be 1 ji 0 50 12 7 FRONT VIEW Models 6 00CB10 and 600CB12 1 00 25 4 1 00 25 4 33 16 x1 14 in Stud Nut Lock Washer amp Flat Washer gt 1 3 47 88 1 14 20 x 1 in Stud KEPS Nut amp Washer 0 69 17 5 Max Lug Width i 1 RINBBUS 4 2 RTN B Input Terminal See Note 4 BATT B Input Terminal BATT B BUS 12 00 304 8 12 61 320 3 1 1 600CB12 23 00 584 2 22 31 566 7 21 00 533 4 2 3 4 8 6 7 8 9 10 W 12 1 i 1 25 31 8 1 75 44 5 Telect assumes no liability for the application or use of these products Neither does Telect conv
11. L2NT 14 Die code 49 Die code 7 Die code 8 Die code 10 Die code 13 Panduit LCD8 14A L LCD6 14A L LCD4 14A L LCD2 14A Q LCDN2 0 14A X Die code 21 Die code 24 Die code 29 Die code 33 Die code 45 Telect Inc All Rights Reserved 136429 1 AO 07 14 1 509 926 6000 telect com 14 Telect Dual Feed 600A Load Center Frame Power Models 600CB10 and 600CB12 1 6 Interconnections CGND CGND 6 INPUT A 600A MAX RETURNA 6 Tr OO oO 6 Tm O O 2 CAH 9 s Olin 7 el OROI i O 0 IS 9 OUTPUT A Oam OO n oO cme OLOR ame o Ge im 6 OQ Or Telect BAY ALM oie sewo AA samad IE B PWR ceFNG ALM ALARM PCB cere 100A MAX PER POLE pals ET Es A oa B 24 we elm e 99 e IT O 2 OOS 1 2 O O 4 vd O OUTPUT B mm 6 Om ORO 7 i O
12. and ground accommodate dual hole lugs Input and output terminals are studs and the ground terminals are bolt connections at the sides of the load center near the rear corners Only one ground connection is required Fuses fuse holders and circuit breakers are sold separately Also sold separately are single double triple and quad pole straps for the output of the breakers or fuses These copper straps bridge the output of the fuse holders or circuit breakers to the output studs See telect com to order breakers fuses fuse holders and load straps The 600CB10 C and 600CB12 C provide horizonal inputs and a cover The 600CB10 CL and 600CB12 CL also provide horizontal inputs a cover and single pole load straps pre installed into the panel The 600CB10 VL and 600CB12 VL provide vertical inputs as well as single pole load straps pre installed into the panel Telect Inc All Rights Reserved 136429 1 AO 07 14 1 1 509 926 6000 telect com Telect Dual Feed 600A Load Center Frame Power Models 600CB10 and 600CB12 1 2 Installation Guidelines Elevated Operating Ambient If installed in a closed or multi unit rack assembly the operating ambient temperature of the rack environment may be greater than the room ambient Therefore consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature Tma specified by the manufacturer Reduced Air Flow Installation of the e
13. ble pole interrupters from 100 to 175A e 2 0 AWG min for triple pole interrupters e 4 0 AWG min for quad pole interrupters Circuit breakers e AIRPAX style LEL or Carling style CA1 Fuses and fuse holders e TFD fuse holders for single pole TLS or TPS fuses e TPC DC BBE 3 fuse holders for single pole TPC fuses e TPW fuse holders for double pole TPC fuses Alarms Specifications Alarm relay contacis 2A 30 VDC 0 6A 60 VDC Max alarm card power rating 24V 103 mA 2 47W 48V 128 mA 6 14W Alarm wire size 24 AWG typical 26 to 20 AWG Alarm terminals Wire wrap Dimensions Specifications 600CB10 width all models 19 in 483 mm 600CB12 width all models 23 in 584 mm Height 3 5 in 88 mm Depth 12 in 305 mm Dimensions Specifications Weight without packaging and accessories 600CB10 18 Ibs 8 2 kg 600CB12 22 Ibs 10 kg 600CB10 xL 21 Ibs 9 5 kg 6 00CB12 xL 25 Ibs 11 3 kg Weight shipping 600CB12 25 Ibs 11 kg 600CB12 30 Ibs 14 kg 600CB12 xL 28 Ibs 12 7 kg 6 00CB12 xL 33 Ibs 15 kg Operating temperature 10 C 14 F to 55 C 131 F Humidity 90 and non condensing Compliance Specifications UL Recognized NEBS Level 3 Telect suggests you avoid using different types of circuit breakers or fuses in the same load center Alarm contacts may vary among interrupter manufacturers and may incapacitate the alarm system
14. ect the following e An open circuit 0 between Terminals C and NC e Continuity 00 between Terminals C and NO 27 For a load center with mid trip breakers expect the following e Continuity 00 between Terminals C and NC e An open circuit Q between Terminals C and NO 28 Re install operable fuses or switch ON breakers before proceeding 29 Record circuit assignments in accordance with operating company procedures and guidelines 30 Lastly enable equipment loads one at a time to verify proper operation of loads Telect Inc All Rights Reserved 136429 1 AO 07 14 12 1 509 926 6000 telect com Telect Dual Feed 600A Load Center Frame Power Models 600CB10 and 600CB12 1 5 Parts amp Accessories The following tables list optional and replacement items for the load center For wire sizing and labeling please refer to Wire Sizing amp Label Convention Telect part number 117995 included with your load center Order parts and accessories online at telect com C ALERT ALERT Use only UL listed or UL recognized component secondary protection devices Steps for configuring a panel Single pole Part Number Multi pole Part 1 Choose vertical or horizontal input Breakers Breakers Number 2 Determine the guantity of load connections 30A 116671 125A 2 pole 134634 ee
15. ey any license under its patent rights or the patent rights of others This document and the products described herein are subject to change without notice Telect Inc All Rights Reserved 136429 1 AO 07 14 1 509 926 6000 telect com Telect Dual Feed 600A Load Center Frame Power Models 600CB10 and 600CB12 NOTES UNLESS OTHERWISE SPECIFIED 1 CONFORMS IN ACCORDANCE WITH ALL TELECT WORKMANSHIP STANDARDS 2 DIMENSIONS ARE IN INCHES 3 DIMENSIONS ARE FOR REFERENCE ONLY JA 24 LOAD STRAPS INCLUDED WITH Gooch CL ONLY 1 00 SPC 3 8 16 7 690 5 600CB12 CL SHOWN RETURN 1 00 SPC TYP 3 8 16 625 SPC LOAD 1 4 20 1 4 20 HEX BOLTS 0000000000 l00000000 000 FOR GROUNDING ooo BEK dd 625 SPC g 1 4 20 YAN LOAD STRAPS 625 WIDE 600CB12 CL Top View NOTES UNLESS OTHERWISE SPECIFIED 1 CONFORMS IN ACCORDANCE WITH ALL TELECT WORKMANSHIP STANDARDS 2 DIMENSIONS ARE IN INCHES 3 DIMENSIONS ARE FOR REFERENCE JAN 24 LOAD STRAPS INCLUDED WITH 600CB1 Bere EE 5 600CB12 VL SHOWN 4 TYP 8I8 16 LOAD SeeD 1 00 VERTICAL 625 SPC SPC D 1 4 20 1 4 20 HEX BOLTS FOR GROUNDING _ 625 SPC 1 4 20 YAN LOAD STRAPS 625WIDE 600CB12 VL Top View Telect Inc All Rights Reserved 136429 1 AO 07 14 17 1 509 926 6000 telect com elect Dual Feed 600A Load Center Frame Power Models GOOCB10 and 600CB12 This page intentionally lef
16. g list Immediately report any shipping damage defects or missing parts to Telect at 800 551 4567 Keep all documentation that comes with your shipment 1 Assign interrupter positions and install load straps for those positions before installing the load center in a rack as follows a Choose interrupter positions for breakers or fuses You may mix interrupter ratings and single and multi pole interrupters in the same load center Telect recommends not mixing fuses with circuit breakers e Avoid mixing non mid trip and mid trip breakers e Avoid mixing TLS TPS with TPC fuses TLS and TPS fuses are compatible but made by different manufacturers e Do not use multiple single pole breakers or fuses with multi pole load straps b Record interrupter position s and amperage of each intended interrupter e To mitigate heat build up caused by heavy loads gt 100A plan a space on one side those interrupters c Remove bottom screw holding circuit breaker cover to selected interrupter positions Refer to Figure 2 e Retain screw and cover if you intend to use circuit breakers e Retain screw but discard cover if you intend to use fuses e Remove corresponding screw in plastic load strap support e Slip receptacle s of load strap into plastic load strap receptacle holder and fasten with screw removed in the previous step Telect Inc All Rights Reserved 136429 1 AO 07 14 4 1 509 926 6000 telect com Telect Dual Feed 600A Load
17. ing washers for Two pairs of 3 8 16 studs on 1 in centers per terminal max lug dual hole compression lugs width of 1 94 in 49 2 mm per pair Torque nut using 9 16 in or 15 mm wrench to 150 in Ib 17 Nem max Input wire size 1 AWG to 750 MCM Grounding Specifications Earth GND terminal bolts with washers for dual hole compression Two pair of 1 4 20 threaded holes on 5 8 in centers Torque bolts lug using 7 16 in or 12 mm wrench to 50 in lb 5 5 Nem max Ground wire size 2 AWG min for any input interrupt device 400A or more Telect Inc All Rights Reserved 136429 1 AO 07 14 2 1 509 926 6000 telect com Telect Dual Feed 600A Load Center Frame Power Models 600CB10 and 600CB12 Outputs Specifications Max output circuit breaker or fuse holder Single pole 100A Double pole 175A Max output load continuous Single pole 80A Double pole 140A Minimum short circuit interrupt rating 5000A Max total output load 550A per side Output terminal studs with KEPS nuts and washers for dual hole 1 4 20 studs on 5 8 in centers max lug width of 0 625 in 15 8 compression lugs mm for a BATT terminal and 0 70 17 7 mm for a RTN terminal Torque bolts using 7 16 in or 12 mm wrench to a 50 in Ib 5 5 Nem max Output wire size e 10 AWG min for a 25A single pole interrupter to 2 AWG min for a 100A single pole interrupter e 2 AWG min for dou
18. quipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised Mechanical Loading Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading Circuit Overloading Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on overcurrent protection and supply wiring Appropriate consideration of equipment nameplate ratings should be used when addressing this concern Reliable Earthing Reliable earthing of rack mounted equipment should be maintained Particular attention should be given to supply connections other than direct connections to the branch circuit e g use of power strips Disconnect Device A readily available disconnect device shall be incorporated in the building installation wiring 1 3 Specifications Inputs Specifications Voltage range nominal voltage 21 6V to 30V nominal 24 VDC AOV to 60V nominal 48 VDC Max input load rating 600A per side at max operating ambient of 49 C 120 F Short circuit withstand rating 5000A Nominal power loss at full load Less than 75W per side 28 800W full load per side 600A x 48V Percentage of full power dissipation at nominal voltage Less than 1 Max input interrupt device 750A Input terminal studs with nuts flat washers and spr
19. rie aha ne Soha per populated fuse 40A 116672 150A pore 134635 OF circul rea er position 50A 116673 175A 2 pole 135921 3 Choose multi pole connections if required 60A 118160 200A 3 pole 134636 4 Select circuit breakers or fuses aT as EE EE e If fuses choose TPC or TFD holders salad e If circuit breakers or fuse holders select BoA 119192 230A epoi 1 194698 quantity equal to number of load connections A 118163 400A pola 143962 P 2 h e Select circuit breaker or fuse amperage values 100A 118159 eam 600CB0S REK Panel Part Number Fuses TPC TPS TLS 600A Dual feed 10 10 load center frame 600CB10 25A 125441 130476 N A vertical inputs 30A 125442 130478 N A 600A Dual feed 10 10 load center frame 600CB10 C 40A 125443 130482 N A hoirzontal inputs 50A 125444 130484 N A 600A Dual feed 10 10 load center frame 600CB10 VL h 60A 125445 130486 N A vertical loaded 70A N A 130488 N A 600A Dual feed 10 10 load center frame 600CB10 CL 75A 125446 N A N A horizontal loaded 600A Dual feed 12 12 load center frame 600CB12 50A N A N A 140640 vertical inputs 90A 1254477 N A 140641 600A Dual feed 12 12 load center frame 600CB12 C 1004 125448 N A 140642 horizontal inputs 125A 125449 N A 140644 600A Dual feed 12 12 load center frame 600CB12 VL TPC fuse holder 129347 vertical loaded TFD fuse holder for TPS TLS fuses 129816 600A Dual feed 12 12 load center frame 600CB12 CL Fuse holder cover 600CBXX CFK horizontal loaded Adapter
20. ry or region such as Underwriter s Laboratories UL TUV etc 5 Use an approved crimping tool to attach approved dual hole compression lug onto suitable grounding wire Size of ground depends on input interruption device 6 If required lightly coat anti oxidant on lug and grounding surface on side of panel Connect the lug using 1 4 20 bolts flat washers and split washer provided as shown in Figure 7 Tighten the bolt to 50 in lb 5 5 Nem z 5 ebi r A w gif at Figure 7 Ground Lug Connection WARNING Before connecting input power cables make sure input power to the panel is turned off 7 Make sure input power is off before connecting this panel s input cables to PDU or battery 8 For input wiring crimp dual hole compression lugs onto 1 AWG to 750 MCM copper wires The choice of input wiring depends on the following criteria e Input interrupt device rating affects size of input wiring e Ambient operating temperature affects the type of input wire insulation Use the table on the following page to choose the correct temperature rated input wires For further information consult the National Electrical Code NEC Telect Inc All Rights Reserved 136429 1 AO 07 14 8 1 509 926 6000 telect com lelect Dual Feed 600A Load Center Frame Power Models 600CB10 and 600CB12 Ambient Operating Temperature Range Max Current Rating Per Side Min Cable Insulation Temperature Rating 5 to 49 C
21. t blank Telect Inc All Rights Reserved 136429 1 AO 07 14 18 1 509 926 6000 telect com Telect
22. t f th k b f wir CB F C MINOR C REF REFERENCE rom the back to the front of the rack before wire CENG SE NG wrapping the alarm pins A PWR NO MAJOR NO APWRC MAJOR C b It is possible to use a short manual wire wrap A PWR NC MAJOR NC tool to install alarm wiring after securing the load center to the rack If you intend to use a power or larger manual wire wrap tool you must install FRONT OF LOAD CENTER alarm wiring now Figure 5 Alarm Wiring Telect Inc All Rights Reserved 136429 1 AO 07 14 6 1 509 926 6000 telect com Telect Dual Feed 600A Load Center Frame Power Models 600CB10 and 600CB12 4 Locate an unused rack position and mount the load center using at least two sets of fasteners per side as shown in Figure 6 Mount the panel as high as possible on the rack leaving at least 1RU of access space above the load center Tighten screws to 35 in Ib 4 29 Nem Telect recommends using a seismic rack for best rigidity k j Me 4 ey od j A X A w 8 ER WS Figure 6 Rack Mounting WARNING Failure to properly ground this equipment can create hazardous conditions to installation personnel and to the equipment Telect Inc All Rights Reserved 136429 1 AO 07 14 7 1 509 926 6000 telect com lelect Dual Feed 600A Load Center Frame Power Models GOOCB10 and 600CB12 ALERT Only use components and crimping tools approved by agencies or certifying bodies recognized in your count