Home

OMNI-4000 hardware installation manual

image

Contents

1. X 60 Appendix A Glossary e cec te iaia n ee ie acc alii 60 Appendix B Troubleshooting ecce tiet t hene e A RE Ee deter eed e a et tun 62 Appendix C Communication troubleshooting guide ss 64 Introduction to OMNI 4000 communications is 64 Troubleshooting phase 1 create a site map 65 Troubleshooting phase 2 test the computer RS 485A Converter and OMNI Server 65 Troubleshooting phase 3 correct any communication wiring problems 67 Troubleshooting phase 4 run OMNI 4000 sisi 70 Appendix D Installation worksheets enne nnne ener enne enn 73 PB worksheets uit tede ete nde e he atit t endete d et ve es eR Duden eat 73 PB 2 Worksheets t anc ee E ee Ut egeat e ete E Pc 75 PE 3 Worksheets ee ede tea terere eere ERR dash neg gush een II Lenin Ure Shek RR sentant art 78 PB 4 Worksheets sr rare A ee eh vin ed ai 79 O ses in bep MR D RUMP MEN Sea ER MER II M E f Me 81 PB 6 worksheets xc niei de Hees epee dean cap ERO du Dane ee ree die es Pape e Rp Ree AA 83 WA OX GMT E 84 Chapter 1 Introducing OMNI 4000 There are several components to the OMNI 4000 system Personal computer OMNI 4000 software and modules see the OMNI 4000 user manual RS 485A Converter OMNI Server Power Blocks Other OMNI 4000 devices see the installation guide for the specific device Computer RS 485A OMNI Server OMNI 4000 Converter devices Runs the OMNI
2. If you are unsure of the potentiometer wiring for your actuator see Determining correct actuator feedback wiring on page 43 When routing the actuator feedback wires do not run them in or along the same conduit as AC power lines Follow the guidelines on page 9 If you are measuring AC power with a DMM note that if a limit switch opens the circuit the DMM measures voltage after the relay switch even if the relay is open 42 Phason Connecting equipment to Power Blocks Determining correct actuator feedback wiring After installing a new actuator or potentiometer or due to age related potentiometer wear the actuator might not move correctly Common symptoms include The actuator oscillating back and forth The actuator not traveling the full stroke during calibration The feedback potentiometer wiring must be properly connected to the control Determining the correct wiring can be difficult on some actuators or potentiometers Potentiometers have three wires positive negative and feedback FB If the feedback wire is not connected to the FB terminal on the control the actuator will not function properly Because the wires are often different colors and are not always labeled the same as above measuring the resistance between the wires is the best way to determine which wire is the feedback wire Follow the steps below to measure the resistance and determine the correct wiring Befo
3. Voltage selection switch set this switch to the correct voltage before installing the Power Block General purpose relay terminals RLY 1 to RLY 9 connect single stage on off equipment to these terminals You can configure these relays as heat cool duty cycle timed event curtain control or inlet actuator control gt Alarm relay terminal connect an external alarm system or alarm siren to this terminal Power terminal connect the incoming power 115 230 VAC 50 60 Hz to this terminal Temperature probe terminal TEMP connect the temperature probe to this terminal Actuator feedback terminals ACT1 ACT2 connect the actuator feedback from the actuators to these terminals Actuator present jumpers place the jumpers on the top two pins to enable or on the bottom two pins to disable actuator control for the corresponding actuator Pulse counter terminal if you are monitoring water usage connect a water meter with pulse output to this terminal Pulse counter jumper if you are monitoring water usage place the jumper on the top two pins to enable the pulse counter Power Block test board socket if you are using a Power Block test board plug it into this socket when testing For more information read Testing Power Blocks on page 56 Microboard socket the microboard not shown connects to this socket For more information read Microboard layout on page 34 BHAE el Ele Ee Lo 2007 10 1
4. DOOOOOOO0 ASSY 152203 e e 2 El S N YYYYMMDD NNN PULSE WO NNNNN FB FB ACTI ACT2 PRES UP JA ure POWER ACT 1FB ACT 2FB UP Gp PULSE INPUT Voltage selection witch set this switch to the correct voltage before installing the Power Block Variable stage fuses F1 F2 15 A 250 VAC ABC type ceramic fuses F1 is for variable stage 1 F2 for stage 2 Variable stage terminals VARI 1 VARI 2 connect variable speed fans to these terminals General purpose relay terminals RLY 1 to RLY 9 connect single stage on off equipment to these terminals You can configure these relays as heat cool duty cycle timed event curtain control or inlet actuator control Alarm relay terminal connect an external alarm system or alarm siren to this terminal Power terminal connect the incoming power 115 230 VAC 50 60 Hz to this terminal Temperature probe terminal TEMP connect the temperature probe to this terminal Actuator feedback terminals ACT1 2 connect the actuator feedback to these terminals Actuator present jumpers place the jumpers on the top two pins to enable or on the bottom two pins to disable actuator control for the corresponding actuator Pulse counter terminal if you are monitoring water usage connect a water meter with pulse output to this terminal Pulse counter jumper if
5. 2007 10 18 7 Chapter 1 Introducing OMNI 4000 Using power contactors to increase the capacity of relays Phason s 240 volt power contactors are heavy duty relays that allow you to increase the load handling capability of control relays Power contactors are ideal for secondary ventilation fans and electric heaters Phason s power contactor relays have the following electrical ratings Coil 10 2 mA at 240 VAC Contact 25 A at 240 VAC resistive 2 HP at 240 VAC 1 HP at 120 VAC motor power factor 0 4 1300 W at 120 VAC tungsten Phason offers three power contactor options Power contactor relay PC 240 includes power contactor relay and mounting hardware for easy mounting in an enclosure Power contactor kit 122 1 includes power contactor relay on off auto switch and label snubber filter reduces electrical noise and mounting hardware for easy mounting in an enclosure Power contactor unit 129 0 includes two power contactor relays two on off auto switches and two snubber filters mounted in a large enclosure The enclosure has room for two additional contactor relays or kits For more information about power contactors or other Phason accessories see your dealer or visit www phason ca Precautions guidelines and warnings See also Servicing and maintaining the controls on page 58 The OMNI Server and Power Blocks must be installed by a qualified electrician Before installing o
6. Enable and calibrate the actuator only after properly connecting it to the Power Block The actuator and Power Block must have power to calibrate If the actuator does not move check the actuator wiring If the actuator does not move through its full range off travel fully closed to fully open check the feedback wiring For more information read Determining correct actuator feedback wiring on page 43 To enable and calibrate actuators for PB 1 and PB 3 Power Blocks Calibrate the actuator by placing the Enable actuator control Disable actuator control ACTUATOR PRESENT jumper on the pins as h bel ACTUATOR ACTUATOR SONUS PRESENT PRESENT UP ERE UP OP The Power Block calibrates the actuator as H B J2 follows le 1 Open the inlets extend the actuator for eight seconds Relay 2 ON Relay 3 OFF 2 Close the inlets retract the actuator for eight seconds Relay 2 OFF Relay 3 ON 3 Open the inlets completely Relay 2 ON Relay 3 OFF 4 Close the inlets completely Relay 2 OFF Relay 3 ON To calibrate actuators for PB 2 4 5 Power Blocks Calibrate the actuator by placing the ACT PRESENT jumper on the pins as shown below Enable actuator control Disable actuator control ACT1 ACT2 TT ACTA ACT2Z PRESENT PRESENT UP UP 44 Phason Connecting equipment to Power Blocks The Power Block calibrates the actuator s as follows
7. Incoming power fuse F1 1 4 A 250 VAC slow blow glass Battery circuit fuse F2 1 A 250 VAC non time delay glass Battery backup terminal connect the 12 V backup battery to this terminal For more information read Connecting the backup battery on page 23 Power terminal connect the incoming power 115 230 VAC 50 60 Hz to this terminal For more information read Connecting the incoming power source on page 22 Ground plate screw connect a ground wire to this screw s le e ST e 9 Alarm relay terminals connect an external alarm system or alarm siren to these terminals For more information read Connecting alarm systems on page 21 2007 10 18 11 Chapter 2 Installing an OMNI Server Cover cable socket make sure the ribbon cable from the cover is properly connected to this socket 9 Computer communication socket TO_PC connect the RS 485 communication wiring to this socket For more information read Connecting the communications on page 13 The LED below the socket is a power indicator When the LED is lit the Server has power Communication channel sockets COM1 to COM8 connect the device Power Blocks and so on communication wiring to these sockets For more information read Connecting the communications on page 13 When the LED below a socket is lit that means the OMNI Server is communicating on that channel Transmit receive LEDs When the OMNI Server i
8. AC POWER TROUBLE Phas n AE WORKING OK LOGIN RELAY 11 ALARM VARI SPEED 1 VARI SPEED 2 RELAY 12 RELAY 2 RELAY 9 VS 2 START RELAY 1 RELAY 3 RELAY 4 ACT 1 OPEN RELAY 5 ACT 1 CLOSE RELAY 6 ACT 2 OPEN RELAY 7 ACT 2 CLOSE RELAY 8 VS 1 START WORKING ok e LOGIN gt RLY 4 NC NO ALARM gt IVs 1 eo gt RLYT ACTOPEN gt RLY 2 ACT CLOSE e 0 IRLY 3 VS 1 STAR lop m POWER BLOCK OMNI 4000 hardware installation manual 2007 Phason Inc All rights reserved Printed in Canada 20040204 2007 10 18 Power Block limited warranty This warranty applies only to the OMNI 4000 Power Block Power Block If you need warranty service return the product and original proof of purchase to your dealer Phason Inc Phason warrants the Power Block subject to the following terms and conditions This warranty is valid only to the original purchaser of the product for two yeats from the manufactuting date The manufacturing date is stated in the first eight digits of the serial number in the form year month day Phason hereby warrants that should the Power Block fail because of improper workmanship Phason will repair the unit effecting all necessary parts replacements without charge for either parts or labor Conditions Installation must be done according to our enclosed installation instructions The product must not have been pre
9. Actuator 2 must use relay 6 for open and relay 7 for close 2007 10 18 79 Appendixes Address Description Group OMNI label Function Description O Actuator 1 open Actuator 1 close Actuator 2 open Actuator 2 close Curtain 1 open Curtain 1 close Curtain 2 open Curtain 2 close Curtain 3 open Curtain 3 close Curtain 4 open Curtain 4 close Heat Cool Duty cycle or Timed event Actuator 1 must use relay 4 for open and relay 5 for close Actuator 2 must use relay 6 for open and relay 7 for close 80 Phason Appendix D Installation worksheets PB 5 worksheets Address Description Building Group PB label OMNI label Function Description O Actuator 1 open Actuator 1 close Actuator 2 open Actuator 2 close Curtain 1 open Curtain 1 close Curtain 2 open Curtain 2 close Heat Cool Duty cycle or Timed event Actuator 1 must use relay 4 for open and relay 5 for close Actuator 2 must use relay 6 for open and relay 7 for close Connected to System type 2007 10 18 81 Appendixes Address Description Building Group PB label OMNI label Function Description O Actuator 1 open Actuator 1 close Actuator 2 open Actuator 2 close Curtain 1 open Curtain 1 close Curtain 2 open Curtain 2 close Heat Cool Duty cycle or Timed event Actuator 1 must use relay 4 for open and relay 5 for cl
10. C C D D E a Each time you add a device test the login using Test Bench If adding a device slows down the login time by more than 30 seconds the device likely has communication problems Leave devices with communication problems disconnected for now and continue along the daisy chain until you have connected all properly communicating devices You can speed up the process by using two people with two way radios One person can check and connect the devices the other can test the logins 68 Phason Appendix C Communication troubleshooting guide Test Power Blocks for microboard problems 1 Remove the microboard from the Power Block with communication problems and set it aside fot now Connect a microboard to the Power Block Use one from a different Power Block that you know wotks Connect the Power Block to the daisy chain Test the communications using Test Bench Remember to look for the address of the current microboard not the original If the Power Block has no more communication problems the problem is the original microboard Order a replacement microboard If the Power Block still has communication problems the problem is likely the main bottom board Remove the microboard and reconnect the original one Reconnect the microboard you used in step 2 to its original Power Block Check Power Blocks for bottom board problems 1 Check the Power Block for enclosure damage or improper sealing Co
11. Channel 3 First device Channel 3 Second device Channel 3 Last device 2007 10 18 13 Chapter 2 Installing an OMNI Server Communication cable requirements The following types of cable are acceptable Unshielded twisted pair UTP category 3 CAT3 or category 5 CAT5 Shielded twisted pair STP CAT3 or CAT5 Phason does not recommend other types of wire If you are using STP cable you must follow the specific instructions in Using shielded twisted pair STP cable below Using shielded twisted pair STP cable The advantage of using STP cable is that it can improve communications by reducing electromagnetic interference The drawback of STP cable is that it requires more care during installation If the shielding is connected incorrectly shielded cable can cause more problems than it solves How to install shielded cable When installing shielded cable you must connect the shielding to the building ground at one end only Phason recommends connecting the cable to the building ground near the computer or OMNI Server When connecting the devices along the communication channel daisy chain connect the shielding of the incoming cable to the shielding of the outgoing cable Do not connect the shielding to the device or to anything else At the last device on the daisy chain do not connect the shielding leave it unconnected The following diagram shows how to connect shielded cable Connect t
12. O ax 10 Olax assa to the OMNI Server 2007 10 18 19 Chapter 2 Installing an OMNI Server Connecting equipment to the OMNI Server This section contains the following Connecting temperature probes below Connecting alarm systems on page 21 Connecting the incoming power source on page 22 Connecting the backup battery on page 23 Connecting temperature probes The OMNI Server comes with a 30 foot probe for monitoring outdoor temperatures You can monitor temperatures in up to 5 additional areas by connecting additional probes All temperature probes cables can be extended up to 500 feet For more information read Extending probe cables on page 38 To connect temperature probes Follow the guidelines below and connect the temperature probe to the OMNI Server Do not run the probe cable in the same conduit as AC power cables Do not run the sensor cable beside AC power cables or near electrical equipment When crossing other cables ot power lines cross them at a 90 degree angle When connecting the outdoor temperature probe connect it to terminal AN1 For any additional probes connect to any of AN2 to AN6 e ANI EL 20 Phason Connecting equipment to the OMNI Server Connecting alarm systems An alarm system can be a siren an alarm panel or an auto dialer See your alarm siren s installation guide for installation instructions and in
13. 1 Open the inlets extend the actuator for eight seconds ACTI Relay 4 ON Relay 5 OFF ACT Relay 6 ON Relay 7 OFF 2 Close the inlets retract the actuator for eight seconds ACTI Relay 4 OFF Relay 5 ON ACT2 Relay 6 OFF Relay 7 ON 3 Open the inlets completely ACTI Relay 4 ON Relay 5 OFF ACT2 Relay 6 ON Relay 7 OFF 4 Close the inlets completely ACTI Relay 4 OFF Relay 5 ON ACT Relay 6 OFF Relay 7 ON Connecting curtain machines Curtains are usually controlled by equipment called curtain machines sometimes referred to as winches Curtains are opened and closed to let in more air or less air the idea being more air cools the building Each curtain machine you connect requires two relays one for opening the curtain and one for closing the curtain Use relays that are side by side pairs In other words relay 1 and 2 relay 3 and 4 ot other similar pair The first relay should be the open relay the second relay the close relay Powet Blocks PB 1 and PB 3 can control one curtain machine Power Blocks PB 2 and PB 4 can control up to four curtain machines Power Block PB 5 can control up to two curtain machines Power Block relay ratings 10 FLA at 115 230 208 VAC 1 3 HP at 115 VAC 1 2 HP at 230 VAC If you are connecting equipment that exceeds the relay ratings you must install a power contactor For more information read Using power contactors to incr
14. 4000 software Connects the Communicates with the Control equipment which provides an interface for OMNI Server to a OMNI 4000 devices and Collect data the OMNI 4000 devices serial port on the the computer computer OMNI Server The OMNI Server is the control center for the OMNI 4000 hardware The OMNI Server s eight communication channels transfer data between the computer and the OMNI 4000 hardware Each communication channel can communicate with up to 32 hardware devices for a total of 256 devices 8 x 32 256 The OMNI Server comes with a 30 foot temperature probe for monitoring outdoor temperatures There are five additional inputs for monitoring temperatures in other areas such as electrical rooms semen storage coolers and so on The OMNI Server comes with a backup battery and cable The battery keeps the OMNI Server operating during brief power failures The internal charger keeps the battery charged 2007 10 18 1 Chapter 1 Introducing OMNI 4000 OMNI Server features Eight communication channels a total of 256 device capacity Six temperature monitoring inputs Thirty foot temperature probe extendable to 500 feet Alarm relays one for power communication failure six for the temperature inputs Maintenance free backup battery and cable Rugged enclosure corrosion resistant water resistant and fire retardant CSA approval Two year limited warranty OMNI Server electrical rating
15. 4000 user manual Use the site map template at the end of the troubleshooting guide Fill in the template and use it as your site map There are two sheets provided if you need more make copies before you start Create a site map 1 At the OMNI Server select a communication channel COMI to COMS On the site map template print the communication channel number in the space provided 2 Follow the cable to the first device 3 On the template print the building name device type device address and group name in the space provided 4 Follow the cable to the next device Repeat steps 3 and 4 until you have finished printing the information for the last device on the channel 6 Repeat steps 1 to 5 for each communication channel that is in use has devices connected Troubleshooting phase 2 test the computer RS 485A Converter and OMNI Server Test the OMNI Server login When OMNI 4000 is running the TROUBLE light on the front cover of the OMNI Server should not be on If the light zs on there has been no communication between the OMNI Server and computer for at least 10 minutes It is possible the RS 485A Converter might not be working or plugged in or the computer s COM port is not working 1 Reset the OMNI Server and then restart the computer 2 After the computer is running start OMNI 4000 if it does not start automatically The OMNI Server should log in within a few seconds after OMNI 4000 starts 2007 10 1
16. 60 Hz to this terminal Actuator feedback terminal ACT1 connect the feedback from the actuator to this terminal Actuator present jumper J2 place the jumper on the top two pins to enable or on the bottom two pins to disable actuator control Temperature probe terminal TEMP connect the temperature probe to this terminal Pulse counter terminal PULSE if you are monitoring water usage connect a water meter with pulse output to this terminal Pulse counter jumper J3 if you are monitoring water usage place the jumper on the top two pins to enable the pulse counter This terminal is not used Microboard socket the microboard not shown connects to this socket For more information read Microboard layout on page 34 Power Block test board socket if you are using a Power Block test board plug it into this socket when testing For more information read Testing Power Blocks on page 56 Phason Power Block layout PB 4 interior layout 2 1 2 a a 5 E S D x a a Ed OR naa _ RLY 9 ALARM ASSY 152206 n S N o YYYYMMDD NNN PULSE WO NNNNN AUT PRACT PRES UP JA S H 1 2 PULSE INPUT gdoooogooog 9 o
17. a location for the Power Block Make sure you have enough cable and wire to reach all the equipment fans heaters misters curtains etc that you want to control 2 Remove the screws from the front cover and then gently lift it off 3 Mount the enclosure to a wall using the four screws provided with the control Insert the screws into the large holes in each corner of the box and tighten Connecting equipment to Power Blocks Follow these instructions when installing Power Blocks and connecting equipment to them Use the electrical knockouts for bringing wires or cables into or out of the Power Block enclosure Do not make additional holes in the enclosure this can damage the watertight seal or control components and void the warranty Refer to the installation worksheets starting on page 73 when installing and connecting equipment to Power Blocks 2007 10 18 35 Chapter 3 Installing Power Blocks Connecting temperature probes Power Block models PB 1 PB 3 and PB 6 come with 6 foot temperature probes Models PB 2 PB 4 and PB 5 come with 30 foot probes You can extend temperature probes cables up to 500 feet For more information read Extending probe cables on page 38 You can connect four probes to the Power Block and average them For more information read Using four zone averaging on page 39 When mounting probes for heat mat control on a PB 6 refer to Using temperature probes for heat mat control on page 37 A
18. jumper if you are monitoring water usage place the jumper on the top two pins to enable the pulse counter Power Block test board socket if you are using a Power Block test board plug it into this socket when testing For more information read Testing Power Blocks on page 56 Microboard socket the microboard not shown connects to this socket For more information read Microboard layout on page 34 Phason Power Block layout PB 6 interior layout I He En Em Ee e le E 2 S N YYYYMMDD NNN MOS NNNM S ASSY 152210 Voltage selection switch set this switch to the correct voltage before installing the Power Block Variable stage fuse F1 15 A 250 VAC slow blow ceramic fuse Variable stage terminal VARI 1 connect variable heating equipment such as heat mats to this terminal Alarm relay terminal connect an external alarm system or alarm siren to this terminal Power terminal connect the incoming power 115 230 VAC 50 60 Hz to this terminal Temperature probe terminal TEMP connect the temperature probe to this terminal Pulse counter terminal PULSE if you are monitoring water usage connect a water meter with pulse output to this termina
19. the surface of the control with your bare hands DO NOT direct a high pressure washer at the control Preventing moisture Moisture will not cause problems with the Power Block or other Phason controls and devices if you take proper care when installing them 1 After the first two weeks of operation remove the cover from the unit and check inside for moisture Be sure to switch off the power to the control before opening the cover 2 If there is moisture present wipe it out with a dry cloth and then check the cable entry points and rubber gasket for proper sealing 3 If the cable connectors are not sealing apply RTV or Silicon II non acetic acid sealant around the cable 58 Phason Servicing and maintaining the controls Some silicone sealants release acetic acid while curing This can cause corrosion and damage the control Let the silicone cure completely one to three days with the cover open and ensure no moisture enters the control Failure to do this might damage the control and void the warranty 4 Open and inspect the control again after two weeks to verify it is sealing properly Open and inspect the control for moisture once a year Proper care and maintenance will extend the life of the control 2007 10 18 59 Appendixes This section contains reference information that is useful when installing or troubleshooting the OMNI 4000 hardware Appendix A Glossary below Appendix B Trou
20. you are monitoring water usage place the jumper on the top two pins to enable the pulse counter Phason Power Block layout Power Block test board socket if you are using a Power Block test board plug it into this socket when testing For more information read Testing Power Blocks on page 56 Microboard socket the microboard not shown connects to this socket For more information read Microboard layout on page 34 Gita 2007 10 18 29 Chapter 3 Installing Power Blocks PB 3 interior layout gt eE Ele Elle Ee To 2 1 S N YYYYMMDD NNN WOA NNNNN ASSY 152204 S ACTUATOR PRESENT PULSE Pie PRE nuuuuuuuuu m a J3 RELAY RELAY RELAY wo 2 COMMONS Voltage selection switch set this switch to the correct voltage before installing the Power Block General purpose relay terminals RELAY 1 to RELAY 3 connect single stage on off equipment to these terminals You can configure these relays as heat cool duty cycle timed event curtain control or inlet actuator control Alarm relay terminal connect an external alarm system or alarm siren to this terminal Power terminal connect the incoming power 115 230 VAC 50
21. 1 3 6 cover and base WORKING OK LOGIN RLY 4 NC NO ALARM VS 1 led O RLY 1 ACT OPEN RLY 2 ACT CLOSE OD RLY 3 VS 1 START 6 O gt 2007 10 18 Chapter 3 Installing Power Blocks PB 2 4 5 cover and base WORKING OK RELAY 11 VARI SPEED 1 RELAY 12 RELAY 9 VS 2 START RELAY 3 RELAY 5 ACT 1 CLOSE RELAY 7 ACT 2 CLOSE LOGIN ALARM VARI SPEED 2 RELAY 2 RELAY 1 RELAY 4 ACT 1 OPEN RELAY 6 ACT 2 OPEN RELAY 8 VS 1 START Tm POWER BLOCK 4000 CO OOO 0 26 Phason Power Block layout PB 1 interior layout 2 1 S N YYYYMMDD NNN OE NANI S ASSY 152205 E ACTUATOR RES o A pocoocoooo zz m a Pepe RELAY RELAY 2 3 2 COMMON SB gt Voltage selection switch set this switch to the correct voltage before installing the Power Block Variable stage fuse F1 15 A 250 VAC ABC type ceramic fuse Variable stage terminal VARI 1 connect variable speed fans to this terminal General purpose relay terminals RELAY 1 to RELAY 3 connect single stage on off equipment to these terminals You can configure these relays as heat cool
22. 8 31 Chapter 3 Installing Power Blocks PB 5 interior layout gt BHAE ele le le 110 2 1 S N YYYYMMDD NNN WOE NNNNN ASSY 152209 1 9 gdoooogooodg O o O rom gt Sct age PAR HE S N oM ACT1 ACT2 N N PRES UP JA S H t 2 PULSE INPUT Voltage selection switch set this switch to the correct voltage before installing the Power Block General purpose relay terminals RLY 3 to RLY 7 connect single stage on off equipment to these terminals You can configure these relays as heat cool duty cycle timed event curtain control or inlet actuator control Alarm relay terminal connect an external alarm system or alarm siren to this terminal Power terminal connect the incoming power 115 230 VAC 50 60 Hz to this terminal Temperature probe terminal TEMP connect the temperature probe to this terminal Actuator feedback terminals ACT1 2 connect the actuator feedback to these terminals Actuator present jumpers place the jumpers on the top two pins to enable or on the bottom two pins to disable actuator control for the corresponding actuator Pulse counter terminal if you are monitoring water usage connect a water meter with pulse output to this terminal Pulse counter
23. 8 65 Appendixes Test the daisy chains A daisy chain is a continuous line of cable connecting the devices in series to a communication channel on the OMNI Server The daisy chain test verifies that all devices are properly connected to the communication channel The OMNI Server has eight communication channels labeled COM1 to COMB Active communication channels are channels that have devices installed on them For example if you have a Power Block connected to COMS then channel 8 is an active communication channel 66 Shut down OMNI 4000 On the OMNI Server unplug all except one of the connectors from the active channels Start Test Bench click Start Programs OMNI 4000 Diagnostics Test Bench A ias File Extended Functions General PB Controls NG Controls Omni Server Channels Computer Login Style System Information Automated Comm Port COM2 COM port used for the search Manual OmniServer Detected Status of the OMNI Server Available Ports COMI Clear Search Power Blocks 9 Number of Power Blocks logged in Nest Gen 12 Number of other OMNI 4000 devices logged in Manual Login TestBench32 Information Device List Load From File OMNI 4000 Load From OMNI Phason Inc Add Device Reset Server TB32 exe Version 2 0 0 2 Remove Device es i opyright jason Inc Save To File Save To OMNI 1995 2007 2007 Jun 11 08 43 05 Under Available Ports select the communication port that h
24. Be sure to align the pins correctly When the board is in place all variable and relay stages switch off uusnnopnudu nona oo0000000b0000000 oj UP TEST ANALOG _ PB 1 3 6 PB 2 4 5 H o fo El 3 E fel 2 R ACT ACT2 NN PRES UP JA lo PRESENT UP PULSE INPUT 56 Phason Finishing and testing the installation To test Power Blocks When you first connect the test board all stages are off Press the button to start at test 1 variable stages If the Power Block has no variable stage PB 3 4 5 the test starts at test 2 relay stages 1 Test 1 variable stages PB 1 2 6 Variable stage 1 runs at 100 for the three second de icing and then drops to 1 a Press the button Variable stage 1 goes to 50 b Press the button Variable stage 1 goes to 100 c Press the button Variable stage 1 turns off If there is only one variable stage PB 1 3 6 the test moves to test 2 If there are two variable stages PB 2 stage 2 runs at 100 for the three second de icing and then drops to 1 d Repeat steps a to c for variable stage 2 2 Test 2 relay stages PB 1 to 5 Relay 1 switches on a Press the button The relay switches off and the next relay switches on b Repeat step a until the last relay the alarm relay is on c Press the button The alarm relay swit
25. Replace damaged probes as soon as possible To connect temperature probes Follow the guidelines below and connect the temperature probe to the Power Block as shown in the appropriate diagram Polarity does not matter Do not run the probe cable in the same conduit as AC power cables Do not run the sensor cable beside AC power cables or near electrical equipment When crossing other cables or power lines cross them at a 90 degree angle PB 1 3 6 temperature terminal TEMP GND 36 Phason Connecting equipment to Power Blocks PB 2 4 5 temperature terminal HU UU TEMP C RR Using temperature probes for heat mat control For heat mats with internal temperature probes consult your dealer for the compatibility of the probes with the OMNI 4000 system For heat mats that do not have internal temperature probes mount the Phason temperature probe as close as possible to the heat mat The following diagram shows one possible mounting configuration Top view Side view heat mat temperature probe PVC tubing clamp PVC tubing gt pen divider 2007 10 18 37 Chapter 3 Installing Power Blocks Extending probe cables You can extend temperature probe cables to lengths of up to 500 feet Follow the guidelines below and on page 36 when extending cables Use two wire 18 AWG jacketed cable Phason recommends Belden 9408 Alph
26. Server and Power Blocks The manual does not explain the software or computer requirements For more information about the OMNI 4000 software see the OMNI 4000 user manual Styles Hint tip This is a hint or tip It contains helpful information that might make it easier for you to install or service the OMNI 4000 equipment Note This is a note It contains information that might help you better understand the OMNI 4000 equipment Caution This is a caution It contains important information that you must follow when installing or servicing the OMNI 4000 equipment Failure to follow this information can lead to damaged controls or equipment Warning This is a warning It contains important safety information that you must follow when installing or servicing the OMNI 4000 equipment Failure to follow this information can lead to damaged controls or equipment electrical shocks or severe injury vii Table of contents Chapter 1 Introducing OMNI 4000 sise 1 OMNI SerVel alli E E RE e ELA eo ea 1 OMNI Server features 1i tie A av ere nln edi agen 2 OMNI Server electrical ratings sise 2 Power BIOGKS ira a laine BN deg ee st PM 2 Power Block models and features 3 Power Block electrical ratings ceste rec i d a dea de a tee eee oneris 4 Power Block enclosure dimensions se 5 What you need to know before installing the OMNI enne nnne 6 Understanding power Surges and surge su
27. Understanding power surges and surge suppression on page 6 60 duty cycle terminal block voltage 2007 10 18 Appendix A Glossary A temperature based style of controlling heating or cooling elements using on durations and off durations Duty cycles are often used to control misters For cooling elements when the temperature is below the set point the cooling element is off When the temperature rises above the set point the element switches on for the on duration and then off for the off duration If at any time the temperature drops below the set point the duty cycle relay switches off and will not switch on again until the temperature rises above the set point For heating elements when the temperature is above the set point the heating element is off When the temperature drops below the set point the element switches on for the on duration and then off for the off duration If at any time the temperature rises above the set point the duty cycle relay switches off and will not switch on again until the temperature drops below the set point The part of a Power Block where you connect the wires for incoming power control elements and so on Electromotive force or potential difference usually expressed in volts 61 Appendixes Appendix B Troubleshooting If you are having trouble with communications read Appendix C Communication troubleshooting guide on page 64 I
28. Uure n 58 59 probes eee See temperature probes R S routing data Wires 9 RS 485A eine cin a Ree RR EASIER 19 sealing Rae RIDE See moisture SOtVICIDIQ camini 58 59 Shielded cable 4 44 14 15 single stage cooling heating elements 46 49 surge SUPPresSiON 6 2007 10 18 Appendixes T temperature probes averaglng ie cce LEE Ce Les 7 connecting to an OMNI Server 20 connecting to Power Blocks 36 37 extendirig rte 38 for heat Mats i iii 37 termination resistors 34 See also communications testing Power Blocks 56 57 three phase power 51 V variable heating 50 variable speed fans 49 50 85 Phason Inc 2 Terracon Place Winnipeg Manitoba Canada Phone 204 233 1400 E mail support phason ca 204 233 3252 Web site www phason ca R2J 4G7 Fax
29. a 5052 or an equivalent Extension cable is also available from Phason For more information contact your dealer or Phason Join the extension cable to the temperature probe cable as shown below If the unit operates erratically with the extended probe run the cable along a different path or shorten it gt mmuoo o 38 Slide three pieces of heat shrink tubing over the wires one for the red wire one for the black wire and one for both Strip the ends of the wires and then twist them together Solder the wires together using rosin core flux solder DO NOT use acid core solder Slide the heat shrink tubing over the solder joints Shrink the tubing using a heat gun Yout connection should look like this Phason Connecting equipment to Power Blocks Using four zone averaging Power Blocks can monitor the temperature in four different zones using four zone averaging The Power Block takes an average of the temperatures measured by the four probes and then operates according to the average temperature You must use four probes for averaging Using two three or more than four probes measures the temperature incorrectly To connect temperature probes for four zone averaging 1 Connect the four temperature probes as shown below Follow the guidelines in Extending probe cables on page 38 probe 1 probe 2 23 Connecting actuators Actuators are used for control elements that are no
30. as the OMNI Server connected Click Start Search The login starts and should take seconds rather than minutes The login is complete when the lights at the bottom of the window stop flashing red and green and instead stay red Verify that all devices on the daisy chain have logged in For a basic summary see the System Information section For detailed information about Power Blocks click the PB Controls tab For detailed information about other OMNI 4000 devices click the NG Controls tab If all devices log in repeat the test three times to check reliability To repeat the test click Clear Search on the General tab and then start at step 4 When you are finished testing the daisy chain close Test Bench Unplug the connector for the daisy chain you have been testing and then connect the next active channel Phason Appendix C Communication troubleshooting guide 10 Repeat steps 4 to 9 for each active communication channel When you are finished testing all active communication channels reconnect all the connectors Test the OMNI Server communication channels Repeat the daisy chain test using a daisy chain that you know is working properly Connect the daisy chain to a different communication channel each time you run the test until you have tested all eight channels If a test fails on a channel but passes on others the OMNI Server is failing at that specific channel Troubleshooting phase 3 correct any commu
31. bleshooting on page 62 Appendix D Installation worksheets on page 73 Appendix A Glossary AC power actuator control elements inlet actuator inlets relay spikes 2007 10 18 Utility companies supply electrical power as alternating current which is referred to as AC power A device that has a mechanical arm that extends and retracts Actuators control elements that are not OFF or ON Instead they vary by a percentage For example inlets can be open various distances from 0 to 100 percent Typically linear actuators connect directly to the inlets or connect using cables and pulleys Inlets are usually located in ceilings or walls Inlet systems are often spring loaded to help close the inlets or counter weighted to help open the inlets For more information read Connecting actuators on page 39 Control elements are devices connected to the Power Blocks such as fans heaters actuatots and so on See actuator Inlets are shutter like devices mounted on a wall or ceiling that control airflow in a building A relay is an electromagnetic switch that is either on closed or off open Short term deviations or changes from a desired voltage level or signal These deviations can cause damage to electronic devices or cause them to malfunction Spikes are often caused by sudden excess power also known as power surges ot by drops in power knows as brown outs For more information read
32. cables or power lines cross them at a 90 degree angle If in doubt do not run any wire or cable that is not an AC power wire inside the same conduit or beside other AC power wires 2007 10 18 9 Chapter 2 Installing an OMNI Server Before installing the OMNI Server read the section What you need to know before installing the OMNI on page 6 OMNI Server layout OMNI Server exterior bottom and side Size A knockout hole is designed for size PG7 strain relief Size B knockout is designed for 3 4 inch conduit Size C knockout is designed for 1 inch conduit O ROLO ee O O O OO SES 2007 10 18 10 OMNI Server layout OMNI Server interior COM7 COM6 COM5 COM2 COM1 TO_PC O ETE ETN era era En E ETA ETA EE FROM PC FROM COM Qui 2 Woo 9NV SNY PNY ENV CNY LNY L1 L2 N 5 230 VAC 1 Voltage selection switch set this switch to the correct voltage before installing the OMNI Server For more information read Connecting the incoming power source on page 22
33. ches off and the test moves to test 3 3 Test 3 communications The alarm relay is on To skip test 3 press the button twice a Insert the loopback tester into the communication socket on the microboard b Press the button If the Login LED top right LED see page 25 lights the communication port works If the LED does not light the test fails 4 Finishing The tests are complete To repeat the tests press the button twice to start at test 1 a When finished remove the loopback tester and test board The control resets and resumes operation b Verify that all wires and connectors are properly connected and then fasten the cover to the Power Block 2007 10 18 57 Chapter 3 Installing Power Blocks Servicing and maintaining the controls Servicing and maintaining your Phason controls will extend the life of the controls and your equipment A Before installing or servicing Phason controls switch OFF the power at the source Maintaining actuators Because cables can stretch and equipment can come out of alignment similar to tires on your cat we recommend resetting the limit switches and calibrating your actuators at least once each year For more information read Enabling and calibrating actuators on page 44 Cleaning the controls Use caution when washing the room with a high pressure washer To clean the surface of the control wipe it with a damp cloth Do not use harsh or abrasive cleaners or rub
34. d all the closed on alarm CA connections together The alarm relays must be in parallel with each other so any device can trigger the alarm system when an alarm condition occurs If you are connecting the alarm system to a network of Power Blocks and your system uses a normally closed connection opens on alarm connect the system as shown in the normally closed diagram Join the alarm relays in a continuous loop The alarm relays must be in series with each other so any device can trigger the alarm system when an alarm condition occuts PB 1 3 6 alarm terminal common connection normally open connection closes on alarm normally closed connection opens on alarm PB 2 4 5 alarm terminal common connection normally open connection closes on alarm normally closed connection opens on alarm For the alarm system to sound or dial out during an alarm condition you must enable the alarms for each zone For more information read the OMNI 4000 user manual The ratings of the alarm system must not exceed the ratings of the Power Block s alarm relay Power Block alarm relay ratings 0 4 A at 125 VAC 2 A at 30 VDC resistive load 0 2 A at 125 VAC 1 A at 30 VDC inductive load 52 Phason Connecting equipment to Power Blocks To connect an alarm system to a PB 1 3 6 Normally open system closed on alarm Normally closed system open on alarm To c
35. duty cycle timed event curtain control or inlet actuator control Alarm relay terminal connect an external alarm system or alarm siren to this terminal Power terminal connect the incoming power 115 230 VAC 50 60 Hz to this terminal Actuator feedback terminal ACT1 connect the feedback from the actuator to this terminal Actuator present jumper J2 place the jumper on the top two pins to enable or on the bottom two pins to disable actuator control Temperature probe terminal TEMP connect the temperature probe to this terminal Pulse counter terminal PULSE if you are monitoring water usage connect a water meter with pulse output to this terminal Pulse counter jumper J3 if you are monitoring water usage place the jumper on the top two pins to enable the pulse counter Microboard socket the microboard not shown connects to this socket For more information read Microboard layout on page 34 Power Block test board socket if you are using a Power Block test board plug it into this socket when testing For more information read Testing Power Blocks on page 56 EE LI 2007 10 18 27 Chapter 3 Installing Power Blocks PB 2 interior layout MIE elle te JB 2 1 S N YYYYMMDD NNN AO MM ASSY 152204 22 ALARM COM N O N C
36. e the startup amperes inrush current of the connected devices do NOT and void the warranty 4 Phason Power Block enclosure dimensions 4 75 inches in 12 00 centimetres cm Enclosure A small PB 1 3 6 9 00 inches in 23 00 centimetres cm Enclosure B large PB 2 4 5 2007 10 18 Power Blocks Chapter 1 Introducing OMNI 4000 What you need to know before installing the OMNI Before installing your OMNI 4000 system you need to do some initial preparation 1 Read Understanding power surges and surge suppression below If you do not install external surge suppression devices you risk damage to the electronics inside your OMNI 4000 devices OMNI Server Power Block and so on which might cause them to fail Because it is not possible to completely protect the OMNI 4000 devices internally from the effects of power surges and other transients we highly recommend that you install external surge suppression devices For specific recommendations see your electrical contractor If you do not take these precautions you acknowledge your willingness to accept the risk of loss or injury 2 Using the Appendix D Installation worksheets on page 73 list all the equipment you want to control using the Power Blocks Install the equipment and make your electrical connections according to the sheet You can connect more than one piece of equipment to a single relay ot stage as long as the total current d
37. ease the capacity of relays on page 8 2007 10 18 45 Chapter 3 Installing Power Blocks To connect curtain machines Connect curtain machines to the Power Block as shown in the appropriate diagram PB 1 3 L1 L2 NEUTRAL PB 2 4 5 RLY1 RLY2 L1 L2 NEUTRAL Connecting single stage heating or cooling elements Heating or cooling elements include equipment such as electric heaters furnaces and single speed fans 46 Phason Connecting equipment to Power Blocks Power Block relay ratings 10 FLA at 115 230 208 VAC 1 3 HP at 115 VAC 1 2 HP at 230 VAC 360 W tungsten at 120 VAC If you are connecting equipment that exceeds the relay ratings you must install a power contactor For more information read Using power contactors to increase the capacity of relays on page 8 Gas furnaces using hot surface ignition or glow plug can draw more current than indicated on their nameplate and require power contactors For more information read your furnace dealer To connect single stage heating or cooling elements Connect single speed heating or cooling elements as shown in the appropriate diagram PB 1 3 gas furnace or brooder thermostat inputs Thermostat inputs NL L2 NEUTRAL PB 1 3 gas furnace or brooder power connections 2007 10 18 47 Chapter 3 Installing Power Blocks PB 1 3 a
38. evices with a five position communication connector connect the common reference to the E terminal DC powered devices with a four position connector Power Blocks PB 1 3 6 PB 2 4 5 PULSE PRES UP PULSE INPUT Common mistakes in communication wiring PULSE gt GND Not using the correct type of communication cable the communication cable must be twisted pair cable category 3 CAT3 or category 5 CAT5 You can use either unshielded twisted pair UTP or shielded twisted pair STP cable Phason does not recommend other types of wire For more information read Communication cable requirements on page 14 Not continuing the communication wiring properly all the devices on the communication channel must be connected in series in a daisy chain and the wire must be continued properly from one device to the next When continuing the communication wiring from one device to the next the wires must be connected as shown below Do not use branches ot T connections A wire goes into each position on the connector and then goes out to the next device 2007 10 18 17 Chapter 2 Installing an OMNI Server To 18 Not terminating the last device on the communication channel the last device on the communication channel must have the termination resistors in place or a termination module installed The termination resistors are located o
39. f you are having trouble with the OMNI 4000 software see the OMNI 4000 software manual ot the manual for the specific OMNI 4000 module If you are having trouble with the OMNI Server Power Blocks or equipment connected to them see if the situation is described in the following table and then follow the instructions to correct it Situation Power supply components blown out Burn marks on boards and components Motors and fans slow down or stop Variable speed fan not running Variable speed fan runs at maximum Possible cause Power surge brownout or power outage Brownout or power outage Circuit breaker off or tripped Fuse blown or missing 115 230 VAC switch in the wrong position Incorrect wiring Fuse blown or missing Incorrect settings No power to the fan Faulty fan Circuit breaker off or tripped Incorrect wiring Incorrect settings Possible solution Cannot do anything when it happens but could avoid the problem in future by providing proper voltage to the unit or by providing proper protection Cannot do anything o Reset the circuit breaker Check why the fuse was blown Repair any problems and then replace the fuse Switch off the power set the switch to the correct setting and then switch on the power Correct the wiring Check why the fuse was blown Repair any problems and then replace the fuse o Adjust the settings see the OMNI 4000 so
40. formation about the type of system normally open ot normally closed If you are connecting the alarm system to the alarm relays and your system uses a normally open connection closes on alarm connect the system as shown in the normally open diagram Join all the common connections together and all the closed on alarm NO connections together The alarm relays must be in parallel with each other so any device can trigger the alarm system when an alarm condition occurs If you are connecting the alarm system to the alarm relays and your system uses a normally closed connection opens on alarm connect the system as shown in the normally closed diagram Join the alarm relays in a continuous loop The alarm relays must be in series with each other so any device can trigger the alarm system when an alarm condition occuts OMNI Server alarm terminals normally open connection closes on alarm common connection normally closed connection opens on alarm OZ CI The RLY 1 to RLY 6 relays activate if there is a valid alarm condition as defined in OMNI 4000 If the server cannot communicate with the computer software the relays will NOT trigger For more information read the OMNI 4000 user manual The TROUBLE alarm relay activates when there is a total power fail AC power and backup battery or a loss of communication with the computer that is longer than five minutes The ratings of the alarm system must not exceed
41. ftware manual Switch on the power o Replace the equipment o Reset the circuit breaker Correct the wiring o Adjust the settings see the OMNI 4000 software manual Relay not operating load 62 Incorrect wiring Fuse blown or missing Correct the wiring Check why the fuse was blown Repair any problems and then replace the fuse Phason Situation 2007 10 18 Possible cause Incorrect relay configuration cool for heater or heat for fan Incorrect settings No power to the load Faulty equipment Circuit breaker off or tripped Blown relay Appendix B Troubleshooting Possible solution Change the configuration see the OMNI 4000 software manual o Adjust the settings see the OMNI 4000 software manual Switch on the power o Replace the equipment o Reset the circuit breaker Solve the problem that caused the relay to blow and then replace the circuit board or use a different relay 63 Appendixes Appendix C Communication troubleshooting guide Introduction to OMNI 4000 communications All OMNI 4000 devices such as Power Blocks Feed Level Sensors and so on communicate with the computer along communication channels A communication channel is a continuous line of cable connecting all devices in series in other words a daisy chain Each device connects to the communication channel as shown below A wire goes into eac
42. h position on the connector and then goes out to the next device The last device on a communication channel must have the termination resistors in place or a termination module installed For the location of the termination resistors see the device s installation guide The OMNI Server is the control center for the OMNI 4000 hardware The OMNI Server s eight communication channels transfer data between the computer and the devices Each communication channel can communicate with up to 32 devices for a total of 256 8 x 32 256 Computer RS 485A Converter OMNI Server OMNI 4000 devices Runs the OMNI 4000 software Connects the OMNI Communicates with the Control equipment which provides an interface for Server to a serial port OMNI 4000 devices and Collect data the OMNI 4000 devices on the computer the computer y Phes n ini ern Ti POWER BLOCK ein communication channel 64 Phason Appendix C Communication troubleshooting guide Troubleshooting phase 1 create a site map A site map shows the layout of the OMNI 4000 devices on your communication system The site map should list the device type and address the physical location the building name for example and the group name It is also important to note the sequence of the devices on each communication channel Print a Site Structure Report Use the report to help identify the device addresses and locations For more information read the OMNI
43. hason reserves the right to improve or alter the OMNI Server without notice Service and technical support Phason will be happy to answer all technical questions that will help you use your OMNI 4000 system Before contacting Phason collect the following information A description of the problem A description of what you were doing before the problem occurred The model s and serial number s of the devices Any messages displayed by the OMNI 4000 software My dealer s name How to contact my dealer Street PO Box City State Province Zip Postal Phone Fax E mail Web site 2 Terracon Place Phone 204 233 1400 Winnipeg Manitoba Fax 204 233 3252 Canada E mail support phason ca R2J 4G7 Web site www phason ca Phason controls are designed and manufactured to provide reliable performance but they are not guaranteed to be 100 percent free of defects Even reliable products can experience occasional failures and the user should recognize this possibility If Phason products are used in a life support ventilation system where failure could result in loss or injury the user should provide adequate back up ventilation supplementary natural ventilation or an independent failure alarm system The user s lack of such precautions acknowledges their willingness to accept the risk of such loss or injury About this manual The OMNI 4000 installation guide explains how to install the OMNI
44. he manufacturing date The manufacturing date is stated in the first eight digits of the serial number in the form year month day Phason hereby warrants that should the OMNI Server fail because of improper workmanship Phason will repair the unit effecting all necessary parts replacements without charge for either parts or labor Conditions Installation must be done according to our enclosed installation instructions The product must not have been previously altered modified or repaired by anyone other than Phason The product must not have been involved in an accident misused abused or operated or installed contrary to the instructions in our user and or installation manuals Phason s opinion about these items is final The person requesting warranty service must be the original purchaser of the unit and provide proof of purchase upon request All transportation charges for products submitted for warranty must be paid by the purchaser Except to the extent prohibited by applicable law no other warranties whether expressed or implied including warranties of merchantability and fitness for a particular purpose shall apply to the OMNI Server Any implied warranties are excluded Phason is not lable for consequential damages caused by the OMNI Server Phason does not assume or authorize any representatives or other people to assume any obligations or liabilities other than those specifically stated in this warranty P
45. he Properties window displays 6 Beside Bits per second select 115200 and then click OK The main Hyper Terminal window displays 7 Type your name If the window displays the characters you typed the daisy chain is wired correctly If the window does not display the characters there is a problem with the wiring closer to the OMNI Server Unplug the loopback tester and connect it to the next connector closer to the OMNI Server Repeat step 7 until you find the wiring problem Test for problems communicating with the devices 1 If there is a loopback at one of the connections unplug it 2 Connect the last device on the daisy chain Make sure the two termination resistors are installed For more information read the installation guide for the specific device 3 Unplug the daisy chain from the OMNI Server 4 Measure the resistance at the OMNI Server end of the cable The measurement from A to B ot C to D should be 120 to 160 ohms Ifthe resistance is higher there might be corrosion or poor connections at the devices Ifthe resistance is loner there might be more than one device with termination resistors 5 Connect the daisy chain to the OMNI Server 6 Connect the devices one at a time starting with the device closest to the OMNI Server Make sure the wiring is consistent at each connector A wire goes into and then goes Wire colors each position on out to the next the connector device A A B B x
46. he cabling for each channel as shown 14 Phason Connecting the communications First device Last device OMNI Server Connect the shielding from Do not connect y the incoming to the shielding Chnneetihe the outgoing C cable shielding to the building ground Installing the communication wiring Before installing the communication wiring read a the following Connector types below Consistent wiring on page 16 Common reference wiring on page 16 Common mistakes in communication wiring on page 17 Connector types There are three possible connector types on Phason devices The four positions A B C D are common to all models Some models have five positions and include E for common reference wiring The six position connectors that include position 1 are included on the RS 485A and OMNI Alarm Manager OAM only The proper connector alignment is shown below qoagv 102 amp v 3 d 9 8 V 1 2007 10 18 15 Chapter 2 Installing an OMNI Server Consistent wiring Using consistent wiring helps eliminate communication connection errors and makes troubleshooting much easier Use the wite colors shown below when connecting all devices to the communication system Wire function RS 485A OMNI Server First device All remaining devices alarm signalO white green 1 white green 1 white green communication blue A blue A b
47. he group the old device belonged to so that the group represents the new device 4 Verify that OMNI 4000 can communicate with the new device A good way to do this is to check the approptiate tab in the Settings Manager or check the viewet if one is available for that type of device For more information about any of the above steps see the OMNI 4000 user manual or the manual for the specific module Check the Site Structure Report 1 Print a Site Structure Report 2 Compare the report to your site map In particular check the number of devices if the report shows more devices than exists there are obsolete device addresses in the system For more information about any of the above steps see the OMNI 4000 user manual Back up your configuration and settings After correcting any problems back up your configuration and settings using the Backup and Restore Utility For more information read OMNI 4000 user manual 70 Phason Appendix C Communication troubleshooting guide channel channel channel channel channel EK Building Device type Device address Group name Position on channel SLOSASAL S lin P eed finisher I OWAI DOLL OA Lint Marar ODSILII SH Lint SY W Z5 ES LV Lagoon E 2007 10 18 71 Appendixes channel channel channel channel channel ME aa CCI CE EAS EAS EAS CCI CE EAS DE 72 Phason Appendix D Installation worksheets Appendix D Installation workshee
48. ing Group Pod OMNI label Function Description Cooling variable speed fan Cooling variable speed fan O Actuator 1 open Actuator 1 close Actuator 2 open Actuator 2 close Curtain 1 open Curtain 1 close Curtain 2 open Curtain 2 close Curtain 3 open Curtain 3 close Curtain 4 open Curtain 4 close Heat Cool Duty cycle or Timed event Actuator 1 must use relay 4 for open and relay 5 for close Actuator 2 must use relay 6 for open and relay 7 for close pf Neraly open LI Normally closed L 2007 10 18 75 Appendixes Address Description Building Group PB label OMNI label Function Description Cooling variable speed fan Cooling variable speed fan O Actuator 1 open Actuator 1 close Actuator 2 open Actuator 2 close Curtain 1 open Curtain 1 close Curtain 2 open Curtain 2 close Curtain 3 open Curtain 3 close Curtain 4 open Curtain 4 close Heat Cool Duty cycle or Timed event Actuator 1 must use relay 4 for open and relay 5 for close Actuator 2 must use relay 6 for open and relay 7 for close pf Normaily open LI Normally closed L 76 Phason Appendix D Installation worksheets Address Description Building Group PB label OMNI label Function Description Cooling variable speed fan Cooling variable speed fan O Actuator 1 open Actuator 1 cl
49. itched on or off The strength of the transients can be over 1000 volts and can vary with the type of equipment and wiring as well as several other factors Visible symptoms of electrical noise include erratic control operation cycling inlets communication problems and more However the affects of electrical noise are not always visible Over time electrical noise can cause electronic circuits relay contacts and power contactors to deteriorate Phason highly recommends installing filters on aX inductive loads Installing filters helps extend the life of equipment Filters help prevent electrical noise problems by absorbing the transient energy Even if you do not have visible symptoms of electrical noise filters help keep controls operating reliably and can extend the life of the controls and equipment connected to them Phason s snubber filters part number 127 0 are intended for use with solenoids timer relays DC motors furnaces and other equipment connected to the control s relays You can also use the filters with loads connected to power contactors Install a filter in parallel with the load as shown in the following example Od CONTROL L2 NEUTRAL Some power contactors include snubber filters For more information read Using power contactors to increase the capacity of relays on page 8 For more information about snubber filters or other Phason accessories see your dealer or visit www phason ca
50. l Pulse counter jumper J3 if you are monitoring water usage place the jumper on the top two pins to enable the pulse counter Microboard socket the microboard not shown connects to this socket For more information read Microboard layout on page 34 2007 10 18 33 Chapter 3 Installing Power Blocks Microboard layout i e Le le 34 Power Block Vit Hi yyyy mm dd ASSY 152202 S N YYYYMMDD NNN WO NNNNN S H 1 Connection pins these pins plug into the microboard socket on the Power Block Termination resistors lf there are any devices on the communication channel after this one remove these two resistors Communication socket connect the communication wiring to this socket For more information read Connecting the communications on page 13 Address label write down this address Each Power Block has a unique address and you will need to know which address belongs to which Power Block for the software Version label if you need to contact Phason Customer Support you might need to provide the information from this label Phason Mounting Power Blocks Mounting Power Blocks Follow these guidelines when mounting Power Blocks Mount the Power Block on a sheltered vertical surface Mount the Power Block with the electrical knockouts facing down Mount the Power Block away from sources of moisture and heat To mount Power Blocks 1 Select
51. l ratings See Power Block or OMNI Server extending temperature probes 38 F feedback potentiometer 40 2007 10 18 fill TS eti ta foi data eoa faeit iti tata du 7 40 four zone averaging eee 7 G 1 gas TUINACES 2 ia 46 49 hot surface ignition 47 incoming power See also three phase power connecting to a Power Block 54 55 connecting to an OMNI Server 22 23 L M layout See OMNI Server or Power Block loopback tester See testing Power Blocks maintaining the controls 58 59 microboard inet epi 34 MOISE nn et 58 59 mounting 9 See OMNI Server or Power Block N O normally open closed See alarm systems OMNI Server features esce A 2 layQUE I eed ede 10 12 mounting s ssaa ede eate cde rn 12 PAlINGS si icit ee ede i e Ne 2 OMNI Server communications 13 19 P potentiometer See feedback potentiometer power See incoming power or three phase power features ueneno eeu 3 layout iine hte exe 25 34 MOUNTING ee etre pe ra 35 FANS EN 4 TESTING sete ne ee 56 57 power contactors ccccccccococcncnnncncncnoninanananananas 8 84 OMNI 4000 hardware installation manual P continued power supplies DC 40 power SUrges ii aie 6 preventing MOISt
52. largest amount of stroke that is feasible with the actuator The stroke is the distance the actuator arm extends or retracts DC powered actuators filters and power supplies If you are connecting DC powered actuators you must connect snubber filters to absorb the transient energy the motors generate Installing the filters helps extend the life of Power Block relays For more information read Reducing electrical noise using filters on page 7 Phason offers two models of DC actuator power supplies Both models are CSA approved and include snubber filters DC power supply 124 0 includes 18 and 18 VDC fused outputs and a snubber filter all mounted in an enclosute DC power supply 124 1 includes 18 and 18 VDC fused outputs and a snubber filter all mounted in a large enclosure The enclosure has room for two power contactor kits PC 240 or 122 1 36 V DC powered actuator positions more slowly and accurately with an 18 V power supply but has less thrust For more information about power supplies or other Phason accessories see your dealet ot visit www phason ca Power Block relay ratings 10 FLA at 115 230 208 VAC 1 3 HP at 115 VAC 1 2 HP at 230 VAC If you are connecting an actuator that exceeds the relay ratings you must install a power contactor For more information read Using power contactors to increase the capacity of relays on page 8 40 Phason Connecting equipment to Power Blocks To con
53. ll other single stage heating or cooling elements E BETA L1 L2 NEUTRAL PB 2 4 5 gas furnace or brooder thermostat inputs Thermostat inputs Le L2 NEUTRAL PB 2 4 5 gas furnace or brooder power connections A Li L2 NEUTRAL 48 Phason Connecting equipment to Power Blocks PB 2 4 5 all other single stage heating or cooling elements Connecting variable speed fans The variable stages are for controlling shaded pole permanent split capacitor or universal motors only If you are using three phase power connect the Power Block and the fan motor to the same phase For more information read Using three phase power on page 51 The ratings of the fan motor must not exceed the ratings of the Power Block s variable stages Power Block variable stage ratings 10 FLA at 115 230 VAC Variable stage fuses 15 A 250 VAC ABC type ceramic To connect variable speed fans Connect variable speed fans as shown in the following diagrams PB 1 L2 NEUTRAL 2007 10 18 49 Chapter 3 Installing Power Blocks PB 2 L1 L2 NEUTRAL Connecting variable heat elements You can connect vatiable heat elements such as heat mats and heat lamps to a PB 6 If you are using three phase power connect the PB 6 and the load to the same phase For more informa
54. lue communication white blue B white blue B white blue communication orange C orange C orange communication white orange D white orange D white orange common referenceO green E green E green O Only for OMNI systems with an OMNI Alarm Manager Not available on all models Common reference wiring Common reference wiring helps eliminate communication problems The common reference wire normally connects to position E on the communication connector For devices such as Power Blocks that have four position connectors it is a good idea to leave the communication cable one foot longer than is needed for connecting to the terminals A B C and D You can then use the extra length of wite to connect to a reference point on the circuit board in place of the E terminal From the RS 485A to the OMNI Server For systems with an OMNI Alarm Manager follow the instructions in the OAM installation guide For systems without an OMNI Alarm Manager connect the wire from the E on the RS 485A to one of the COM REF terminals on the OMNI Server Hl A gt mz 16 Phason Connecting the communications From the OMNI Server to each device For each communication channel connect a wire from the COM REF terminal on the OMNI Server to the following terminal on each device Follow the same guidelines for continuing the wiring properly as you would for communication wires D
55. n the circuit board of all OMNI devices You must remove the termination resistors from all devices except the last one on the channel The termination resistors on OMNI Power Blocks are in sockets on the Micro Board and can be removed and replaced if necessary Termination resistors on all other devices must be removed using wire cuttets For the location of the termination resistors on Power Blocks see Microboard layout on page 34 For other OMNI devices see the installation guide for the particular device If you remove the termination resistors from the last device by mistake you will have to install a Termination Module on that device The Termination Module connects to the communication socket on the last device For information contact your dealer or Phason Customer Support Running the communication cable in the same conduit as or beside AC power cables routing communication cable in the same conduit as or beside AC power cables can cause electrical interference and communication failures Follow the guidelines below when routing communication cable Do not run the cable in the same conduit as AC power cables Do not run the cable beside AC power cables or near electrical equipment When crossing other cables or power lines cross them at a 90 degree angle For more information read Routing data wires on page 9 connect the communication and common reference wiring Connect all the devices on each communication chan
56. nect actuators to PB 1 and PB 3 Power Blocks Refer to your actuator s installation guide for information about its power supply requirements Connect the actuator to the Power Block as shown below Use ACT1 for feedback RELAY 2 for open and RELAY 3 for close AC powered actuators L2 NEUTRAL DC powered actuators If you are unsure of the potentiometer wiring for your actuator see Determining correct actuator feedback wiring on page 43 When routing the actuator feedback wires do not run them in or along the same conduit as AC power lines Follow the guidelines on page 9 If you are measuring AC power with a DMM note that if a limit switch opens the circuit the DMM measures voltage after the relay switch even if the relay is open 2007 10 18 41 Chapter 3 Installing Power Blocks To connect actuators to PB 2 PB 4 and PB 5 Power Blocks Refer to your actuator s installation guide for information about its power supply requirements Connect the actuator s to the Power Block as shown below For Actuator 1 use ACT 1 FB for feedback RLY 4 for open and RLY 5 for close For Actuator 2 use ACT 2 FB for feedback RLY 6 for open and RLY 7 for close AC powered actuators L2 NEUTRAL DC powered actuators
57. nel in series For example A on the OMNI Server to A on the first device to A on the second device and so on Use the wires specified in Consistent wiring on page 16 As you go to each device remove the termination resistors from each device except for the last one on the communication channel The last device must have the termination resistors in place Connect the TO PC connector on the OMNI Server to the connector on the RS 485A Converter Phason Connecting the communications Connecting the RS 485A Converter After connecting the communication and common reference wiring to all OMNI devices the OMNI Server and the RS 485A Converter connect the RS 485A to the computer 1 Attach the adhesive mount to the side of the RS 485A 2 Fasten the communication cable to the RS 485A using the tie at least 1 wtap Make sure the bend in the wire is at least one inch in diametet 3 Connect one end of the extension cable to the RS 485A and the other end to your computer s serial port 4 Connect the AC adapter to the RS 485A Use only the E20013 adapter provided with the RS 485A Converter Other adapters can damage the converter and void the warranty If the RS 485A Converter requires warranty service return the adapter along with the converter 5 Plug the AC adapter into a 115 VAC outlet to the computer s E20013 to a 115 VAC serial port AC outlet adapter O pwr
58. nication wiring problems The tests in this section require a loopback tester Loopback testers are available from your dealer or Phason zn T 301040 Daisy chain loopback tester L AH If a tester is not available you can create a temporary loopback by inserting wires into the connectors as shown to the right Be careful not to damage the connectors Loopback tests help verify the integrity of the communication line During the tests the computer sends out information along the communication cable The information bounces back when it gets to the loopback connector The computer compares the information it receives back if it is the same as the information sent out then both the send TX and receive RX lines are intact Verify the daisy chain is wired correctly 1 Unplug all devices from the daisy chain 2 Atthe end of the chain farthest from the OMNI Server connect a loopback connectot 3 Start the Windows utility Hyper Terminal usually Start Programs Accessoties Communications Hyper Terminal You might see a window display asking if you want to make Hyper Terminal your default Telnet program Click No to continue Hyper Terminal s Connection Description window displays 4 Beside Name type something and then click OK The Connect To window displays 2007 10 18 67 Appendixes 5 Beside Connect Using select the COM port the OMNI Server is connected to and then click OK T
59. onnect an alarm system to a PB 2 4 5 Normally open system closed on alarm 2007 10 18 53 Chapter 3 Installing Power Blocks Normally closed system open on alarm BN ALARM Connecting the incoming power source You can connect the Power Block to 115 or 230 VAC 60 Hz powet Connect the Power Blocks to the OMNI Server before connecting the power source For more information read the Connecting the communications on page 13 Before connecting the power set the voltage selection switch to the correct voltage If you are using three phase power make sure the control power and the variable speed fans are connected to the same phase For more information read Using three phase power on page 51 Before connecting the incoming power switch OFF the power at the source Do not switch ON the power until you have finished all wiring and verified all equipment is properly connected and free of obstructions 54 Phason Finishing and testing the installation To connect the incoming power source 1 Set the voltage select switch to the correct voltage setting 2 Connect the incoming power source as shown below L2 NEUTRAL Finishing and testing the installation After you have finished connecting all equipment wiring and cables to the Power Blocks verify the wires are connected properly If you filled in the installation worksheets use
60. or layouts la eo Ae le ea AL DR rer ERE duets 30 PB 4 interior layout 31 PB 5 Interior IAYOUT 25H nr oriali i nilo 32 PB 6 interior layout 33 Microboard YOU ICE 34 Mounting Power BIoCKS n irrita ta ge ip eR RR Ua ela a ER Lau ee Eu eR dau ER Run PER 35 Connecting equipment to Power Blocks sisi 35 Connecting temperature probes issues 36 Extending probe Cables e a e ok PER ERE pani HE red Pr AXE DPA sauder e Rue pex RATIS 38 Using four zone averaging occorre vasa re rper ri bone venere aaepe ca 39 Gonnecting act atots 1 2 pee Pie te ni RU REGES EPOR S Ee Hae OL ERE REP iii 39 Determining correct actuator feedback wiring ooooccccnnoncccnnnocinonanonnnonanannnn nano nnnr naar n enne 43 Enabling and calibrating actuators nennen nnne nennen nns 44 Connecting curtain machines issues 45 Connecting single stage heating or cooling elements 46 Connecting variable speed fans sen 49 Connecting variable heat elements ss 50 Using thiree phase DOME Euh e tad dde Wat t denter e te PA RE e deter t teats Mente eed 51 Connecting alarm Systetmis e edite n eed Li eee aded e e legate cated 51 Connecting the incoming power SQUICE i 54 Finishing and testing the installation 55 Testing Power BlocKS u dt me en eco dee Mete es ode aere adel ee NIV 56 Servicing and maintaining the controls sisi 58 y eerwepilTem c
61. ose Actuator 2 must use relay 6 for open and relay 7 for close 82 Phason Appendix D Installation worksheets PB 6 worksheets Description Building Group VARI 1 VHS1 Heating Phason a O Heat mat 1K O Connected to System type Normally open O Normally closed O Address Description Building Group VARI 1 VHS1 Heating Phason a O Heat mat 1K O Connected to System type Normally open L Normally closed L 2007 10 18 83 index A AC actuators n See actuators Actuator Position SEnsor 40 actuator power supplies 40 actuators calibrating iaioa ea 44 45 58 connectirig sisi 39 42 feedback Ice 40 maintaining See calibrating alarm systems connecting to a Power Block 51 54 connecting to an OMNI Server 21 22 B C backup battery 23 24 Calibrating actuators 44 45 58 CICANING E 58 communications 13 19 connecting curtain machines 45 46 single stage cooling heating elements 46 49 variable speed fanS n 49 contactors See power contactors curtains machines 45 46 D data WINES insect dieit ai 9 DC actuators See actuators DC power supplies 40 E electrical noise 7 electrica
62. ose Actuator 2 open Actuator 2 close Curtain 1 open Curtain 1 close Curtain 2 open Curtain 2 close Curtain 3 open Curtain 3 close Curtain 4 open Curtain 4 close Heat Cool Duty cycle or Timed event Actuator 1 must use relay 4 for open and relay 5 for close Actuator 2 must use relay 6 for open and relay 7 for close pf Normaity open LI Normally closed L 2007 10 18 77 Appendixes PB 3 worksheets Address Description 78 Building Group PB label OMNI label Function Description O Actuator 1 open Actuator 1 close Curtain 1 open Curtain 1 close Heat Cool Duty cycle or Timed event Actuator 1 must use relay 4 for open and relay 5 for close Address Description Building PB label OMNI label Function Description O Actuator 1 open Actuator 1 close Curtain 1 open Curtain 1 close Heat Cool Duty cycle or Timed event Actuator 1 must use relay 4 for open and relay 5 for close Phason Appendix D Installation worksheets PB 4 worksheets Address Description Group OMNI label Function Description O Actuator 1 open Actuator 1 close Actuator 2 open Actuator 2 close Curtain 1 open Curtain 1 close Curtain 2 open Curtain 2 close Curtain 3 open Curtain 3 close Curtain 4 open Curtain 4 close Heat Cool Duty cycle or Timed event Actuator 1 must use relay 4 for open and relay 5 for close
63. ppression 6 Reducing electrical noise using filters ii 7 Using power contactors to increase the Capacity of relays sss 8 Precautions guidelines and warnings ss 8 Chapter 2 Installing an OMNI Server 10 OMNI Server aout het eH tte teer nm tt ur reed ed bea dcbet nde cenfeo Et ates 10 OMNI Server exterior bottom and side sis 10 OMNI Server interior 2 ot aiite Tee Le eet lei 11 Mounting the OMNI Server vico ede d e eed a tee fee a e tn PER Erates 12 Connecting the communications siennes 13 Communication cable requirements sisi 14 Installing the communication wiring ss 15 Connecting the RS 485A Converter ntun nn nnna 19 Connecting equipment to the OMNI Server iii 20 Connecting temperature probes isa 20 Connecting alarm systems utile IE pue Er Ue e Pee e e editus 21 Connecting the incoming power source issues 22 Connecting the backup battery sise 23 Finishing the Installation ete E REED LO Ee Reo EO io 24 Chapter 3 Installing Power Blocks cc re e ern Ete te Seb Pent n age I Phat ner Ore Dau RES ER Rem URS 25 Power Block layout 8 n dt e ette e cte e ets 25 PB 1 9 6 cover and Ds ser rn tena atten tet Me dete ta dai Doe e een bob rt tetes bat 25 PB 2 4 5 cover and base ipe eie raza 26 PE 1 interior layout a use e ple b t e ede be ee t d e aede ex aaa 27 PB 2 interior layout d T 28 PBE S interi
64. r servicing the OMNI equipment switch OFF the incoming power at the source Install the OMNI Server Power Blocks and all equipment connected to them according to local electrical codes 8 Phason What you need to know before installing the OMNI Mount the enclosures on a sheltered vertical surface with the electrical knockouts facing down Use a screwdriver to tighten the screws in the enclosures Do not use a drill or over tighten the screws this can crack the enclosures and ruin the watertight seal Use the electrical knockouts for bringing wires or cables into or out of the enclosures Use watertight strain reliefs or conduit connectors at all cable entry points Do not make additional holes in the enclosures this can damage the watertight seal or control components and void the warranty Routing data wires Routing data wires in the same conduit as or beside AC power cables can cause electrical interference erratic readings and or improper control Data wires include all of the following Temperature probe and humidity sensor cables Actuator feedback potentiometer wires Data communication wires including RS 232 RS 485 Any cable or wire that does not provide AC power Guidelines for routing data wires Do not run the wires in the same conduit as AC power cables Do not run the wires beside AC power cables or near electrical equipment When crossing other
65. raw does not exceed the relay or stage s limit For more information read Power Block electrical ratings on page 4 Understanding power surges and surge suppression Power surges can be caused by external influences outside the barn for example lightning or utility distribution problems or they can be caused internally inside the barn for example starting and stopping inductive loads such as motors One of the most common causes of power surges is lightning When lightning strikes the ground it produces an enormously powerful electromagnetic field This field affects nearby power lines which transmit a surge to any device connected to it such as lights computers or environmental controls like Power Blocks Lightning does not have to actually strike a power line to transmit a surge Surge suppression devices offer some protection from power surges Because it is not possible to internally protect this product completely from the effects of power surges and other transients Phason highly recommend that you install external surge suppression devices For specific recommendations see your electrical contractor If you do not take these precautions you acknowledge your willingness to accept the risk of loss or injury 6 Phason What you need to know before installing the OMNI Reducing electrical noise using filters Electrical noise is caused by high voltage transients created when inductive loads such as power contactors are sw
66. re checking the potentiometer wires verify that the power wires are properly connected Test the actuator movement using the test card For more information read 1 Manually move the actuator away from the end of its stroke by at least a quarter of its total stroke 2 Disconnect all three potentiometer wires from the control 3 Number the wires 1 2 and 3 in any order 4 Set your ohmmeter to measure the potentiometer s maximum resistance normally 20 000 Q 5 Measure and record the resistance between wires 1 and 2 Q 6 Measure and record the resistance between wires 1 and 3 Q 7 Measure and record the resistance between wires 2 and 3 Q 8 The pair of wires with the highest measured value are the positive and negative wires Connect the wires to the positive and negative actuator terminals on the control At this time do not be concerned with which wite you connect to which terminal 9 Connect the remaining wire to the feedback terminal 10 Test the actuator to see if the control moves it properly If the actuator moves in the opposite direction than it is supposed to switch the positive and negative wires on the control 2007 10 18 43 Chapter 3 Installing Power Blocks Enabling and calibrating actuators After connecting an actuator to a Power Block you need to enable and calibrate the actuator Placing the actuator present jumper on the correct pins enables actuator control and starts the calibration procedute
67. re to protect it A marine battery storage container is an ideal enclosure The battery circuit has a fuse If the fuse is blown or missing the Server will not maintain the charge in the battery and the battery will not operate the Server during a power failure For more information read OMNI Server interior on page 11 2007 10 18 23 Chapter 2 Installing an OMNI Server To connect the backup battery Connect the backup battery to the OMNI Server as shown below UU LE BAT black negative red positive Finishing the installation After you have finished connecting all equipment wiring and cables to the OMNI Server verify the wires ate connected properly and then close the cover 1 di 2 Make sure all the wires are properly connected to the correct terminals Make sure all connectors are properly connected to their sockets For more information read OMNI Server interior on page 11 Make sure the voltage selection switch is in the correct setting Switch on the power to the OMNI Server and then make sure al equipment is functioning properly Close the covet Insert the four screws into the cover and then tighten them A Do not over tighten the screws Do not use power screwdrivers or drills 4 Phason Chapter 3 Installing Power Blocks Before installing the Power Blocks read the section What you need to know before installing the OMNI on page 6 Power Block layout PB
68. rrosion caused by exposure to the barn atmosphere can cause the bottom board to fail If the enclosure has damage or does not seal properly replace the entire Power Block Keep the microboard from the new Power Block for future use Instead connect the original microboard Test the communications using Test Bench If the Power Block still has communication problems remove the original microboard and then connect the new one Discard the original microboard Checking other OMNI 4000 devices All other OMNI 4000 devices LEM OWM OWS FLS MLS have only one circuit board For the FLS and MLS power and communications are in the control units If you have one of these devices and the wiring is OK and there is power to the board but Test Bench cannot find it replace the circuit board using a kit 2007 10 18 69 Appendixes Troubleshooting phase 4 run OMNI 4000 Remove obsolete device addresses 1 Start OMNI 4000 2 Open the Configuration Manager and then click the Buildings tab 3 Remove obsolete device addresses under Available select a device and then press DELETE 4 Repeat step 3 until you have removed all obsolete addresses Configure the new addresses If you replace a device that has communication problems or you replace the microboard in a Power Block the address of the device changes When the address changes you need to 1 Add the new device to OMNI 4000 2 Assign the device to a building 3 Edit t
69. s Input power 115 230 VAC 50 60 Hz Incoming power fuse F2 1 A 250 VAC non time delay glass Backup battery 12 V 7 2 Ah gel cell Battery circuit fuse F1 1 4 A 250 VAC slow blow glass Alarm relay 0 4 A at 125 VAC 2 A at 30 VDC resistive load 0 2 A at 125 VAC 1 A at 30 VDC inductive load Power Blocks Power Blocks can control virtually any type of load from variable and single speed fans to feed augers to lights No matter what your ventilation or control strategy is there is a Power Block that suits your needs Power Blocks work with the ventilation module of the OMNI 4000 system to control equipment according to your programmed settings If the computer or communications fail the Power Blocks continue to operate according to the last settings received from the OMNI 4000 software When communication is restored the software sends updated settings to the Power Blocks 2 Phason Power Blocks Power Block models and features There are six models of Power Blocks Model Enclosure size Temperature probeQ Variable stages Relay stages 6 foot 30 foot 6 foot 30 foot 30 foot 6 foot For more information about enclosure sizes see Power Block enclosure dimensions on page 5 All temperature probes can be extended up to 500 feet using extension cable For more information see Extending probe cables on page 38 The variable stage on a PB 6 is for heat mat control In addition to the features in
70. s sending information the FROM PC LED is lit When it is receiving information the FROM COM LED is lit Common reference terminal connect the common reference wiring from the RS 485A Converter to one of these terminals For more information read Connecting the communications on page 13 e Rie Outdoor temperature probe terminal AN1 connect the temperature probe for monitoring outdoor temperatures to this terminal For more information read Connecting temperature probes on page 20 Additional temperature probe terminals AN2 to AN6 connect temperature probes for monitoring additional areas to these terminals For more information read Connecting temperature probes on page 20 Mounting the OMNI Server Follow these guidelines when mounting the OMNI Servet Mount the OMNI Server on a sheltered vertical surface Mount the OMNI Server with the electrical knockouts facing down Mount the OMNI Server away from sources of moisture and heat To mount the OMNI Server 1 Select a location for the OMNI Server 2 Remove the screws from the front cover and then swing it open 3 Mount the enclosure to a wall using the four screws provided with the control Insert the screws into the large holes in each corner of the box and tighten 12 Phason Connecting the communications Connecting the communications If you are installing an OMNI Alarm Manager OAM in the OMNI Server follow the additional ins
71. t OFF or ON Instead they vary by a percentage For example inlets can be opened various distances from 0 percent to 100 percent Typically linear actuators are connected directly to the inlets or by cables and pulleys Inlets are generally located in the ceiling or walls Inlet systems are usually spring loaded to aid in closing the inlet or counter weighted to aid in opening the inlets Each actuator you connect requires two relays one for opening and one for closing Power Blocks PB 1 3 can control one actuator Power Blocks PB 2 4 5 can control up to two actuators 2007 10 18 39 Chapter 3 Installing Power Blocks Feedback potentiometers Each actuator you connect must have a feedback potentiometer The feedback potentiometer which you connect to the Power Block s corresponding feedback terminal lets the control know how far the actuator s arm is extended Most linear actuators are available with potentiometer feedback and internal adjustable limit switches A 10 000 ohm 10 turn feedback potentiometer is preferred but the internal feedback potentiometer can range between 1000 and 20 000 ohms Potentiometers outside of this range will affect the precision to which your Power Block can control the actuator If your actuator does not have a feedback potentiometer Phason offers an Actuator Position Sensor APS 1 For more information contact your dealer or Phason A system operates more precisely when using the
72. the ratings of the alarm relay s OMNI Server alarm relay ratings 0 4 A at 125 VAC 2 A at 30 VDC resistive load 0 2 A at 125 VAC 1 A at 30 VDC inductive load 2007 10 18 21 Chapter 2 Installing an OMNI Server To connect an alarm system to an OMNI Server Normally open system closed on alarm Connecting the incoming power source You can connect the OMNI Server to 115 or 230 VAC 50 60 Hz power Connect the communication and common reference wiring before connecting the power source For more information read the Connecting the communications on page 13 Before connecting the power set the voltage selection switch to the correct voltage Before connecting the incoming power switch OFF the power at the source Do not switch ON the power until you have finished all wiring 22 Phason Connecting equipment to the OMNI Server To connect the incoming power source 1 Set the voltage select switch to the correct voltage setting 2 Connect the incoming power source as shown below L1 L2 N 115 230 VAC L1 L2 N Connecting the backup battery The OMNI Server comes with a maintenance free 12 V rechargeable battery and cable The battery keeps the OMNI Server operating during brief power failures There is an internal trickle charger on the OMNI Server that keeps the battery charged Store the battery close to the server in a vented enclosu
73. the table all Power Blocks have the following 2007 10 18 Alarm relay Pulse input for water meter monitoring Status LEDs Power failure memory protection Overload protection fuse for variable stages Rugged enclosure corrosion resistant water resistant and fire retardant CSA approval Two year limited warranty Chapter 1 Introducing OMNI 4000 Power Block electrical ratings The ratings below are for all Power Blocks Some models do not have variable stages others do not have relay stages For a list of Power Block models and their features see Power Blocks on page 2 Input power 115 230 208 VAC 60 Hz Variable stages 10 FLA at 115 230 VAC Fuses 15 A 250 VAC ABC type ceramic Relay stages DO 10 FLA at 115 230 208 VAC 1 3 HP at 115 VAC 1 2 HP at 230 VAC 360 W tungsten at 120 VAC Alarm relay 0 4 A at 125 VAC 2A at 30 VDC resistive load 0 2 Aat 125 VAC 1 A at 30 VDC inductive load O You can connect two or more pieces of equipment to a variable stage or relay as long as they are the same type for example two fans and the total current draw does not exceed the limit of the variable stage or relay Q If you are connecting a load that exceeds the ratings of the relay you must install a power contactor For more information read Using power contactors to increase the capacity of relays on page 8 exceed the relay s current rating Failure to do this can overload the Power Block Make sur
74. them to verify that you have connected all the wires and cables to the proper locations 1 Make sure all equipment is properly installed and connected to the correct locations 2 Switch on the incoming powet at the source 3 Verify the wiring is correct and the equipment functions properly For more information read Testing Power Blocks on page 56 4 Fasten the cover to the Power Block using the four cover screws A Do not over tighten the screws Do not use power screwdrivers or drills 2007 10 18 55 Chapter 3 Installing Power Blocks Testing Power Blocks The Power Block test board part number 170042 that comes with the OMNI Server allows you to quickly test Power Blocks to make sure they are wired correctly The test verifies the variable stages relays and communications port are operating properly 5 Additional test boards are available from your dealer or Phason The last part of the test requires a loopback tester Loopback testers are available from your dealer or Phason If a tester is not available you can make a temporary one as shown to the right Label all wires before removing them from the communication connector To connect the test board 1 Remove the cover from the Power Block 2 Connect the test board as shown below JA for PB 2 4 5 or TEST for PB 1 3 6 You do not have to switch off the power off while connecting or disconnecting the test board The button faces the inside of the control
75. tion read Using three phase power on page 51 The ratings of the equipment must not exceed the ratings of the PB 6 s variable stages Power Block variable stage ratings 10 FLA at 115 230 VAC Variable stage fuse 15 A 250 VAC ABC type ceramic To connect variable heat elements Connect vatiable heat elements as shown in the following diagram PB 6 50 Phason Connecting equipment to Power Blocks Using three phase power If you are connecting the Power Block to a three phase system make sure to connect the control power and the variable heating or cooling equipment to the same phase The Power Block must be powered from the same phases that supply the equipment If the control power and the variable stages are wired to different phases the equipment will operate erratically Correct three phase wiring 208 VAC Connecting alarm systems An alarm system can be a siren an alarm panel or an auto dialer See your alarm siren s installation guide for installation instructions and information about the type of system normally open ot normally closed 2007 10 18 51 Chapter 3 Installing Power Blocks If you are connecting the alarm system to a network of Power Blocks and your system uses a normally open connection closes on alarm connect the system as shown in the normally open diagram Join all the common connections together an
76. tructions in the OAM installation guide when connecting the communications All OMNI 4000 devices including Power Blocks Local Environment Monitors Feed Level Sensors and more communicate with the computer along communication channels A communication channel is a continuous line of cable connecting all devices in the series in other words a daisy chain Each device connects to the communication channel as shown below A wire goes into and then goes each position on out to the next the connector device The last device on a communication channel must have the termination resistors in place or a termination module installed For the location of the termination resistors on Power Blocks see Microboard layout on page 34 For other OMNI devices see the installation guide for the particular device The OMNI Server is the control center for the OMNI 4000 hardware The OMNI Server s eight communication channels transfer data between the computer and the devices Each communication channel can communicate with up to 32 devices for a total of 256 8 x 32 256 The following diagram is a simplified overview of the OMNI 4000 system Communication channel up to 8 channels 32 devices per channel Channel 1 Channel 1 First Second device device device OMNI Server Channel 1 l Last Channel 2 Channel 2 Channel 2 First Second Last device device device
77. ts There ate two or three copies of each worksheet If you need additional worksheets make copies before filling them in or download additional worksheets from www phason ca PB 1 worksheets below PB 2 worksheets on page 75 PB 3 worksheets on page 78 PB 4 worksheets on page 79 PB 5 worksheets on page 81 PB 6 wotksheets on page 83 PB 1 worksheets Address Description Building Group PB label OMNI label Function O Description Cooling variable speed fan O Actuator 1 open Actuator 1 close Curtain 1 open Curtain 1 close Heat Cool Duty cycle or Timed event Actuator 1 must use relay 4 for open and relay 5 for close 2007 10 18 73 Appendixes 74 Address Description Building Group PB label OMNI label Function Description Cooling variable speed fan O Actuator 1 open Actuator 1 close Curtain 1 open Curtain 1 close Heat Cool Duty cycle or Timed event Actuator 1 must use relay 4 for open and relay 5 for close Address Description Building PB label OMNI label Function Description Cooling variable speed fan O Actuator 1 open Actuator 1 close Curtain 1 open Curtain 1 close Heat Cool Duty cycle or Timed event Actuator 1 must use relay 4 for open and relay 5 for close Phason Appendix D Installation worksheets PB 2 worksheets Address Description Build
78. viously altered modified or repaired by anyone other than Phason The product must not have been involved in an accident misused abused or operated or installed contrary to the instructions in our user and or installation manuals Phason s opinion about these items is final The person requesting warranty service must be the original purchaser of the unit and provide proof of purchase upon request All transportation charges for products submitted for warranty must be paid by the purchaser Except to the extent prohibited by applicable law no other warranties whether expressed or implied including warranties of merchantability and fitness for a particular purpose shall apply to the Power Block Any implied warranties are excluded Phason is not liable for consequential damages caused by the Power Block Phason does not assume or authorize any representatives or other people to assume any obligations or liabilities other than those specifically stated in this warranty Phason reserves the right to improve or alter the Power Block without notice OMNI Server limited warranty This warranty applies only to the OMNI 4000 OMNI Server OMNI Server If you need warranty service return the product and original proof of purchase to your dealer Phason Inc Phason warrants the OMNI Server subject to the following terms and conditions This warranty is valid only to the original purchaser of the product for two years from t

Download Pdf Manuals

image

Related Search

Related Contents

Owner`s Manual Manual de usuario TC-L47WT50 TC  取扱説明書 - 五輪工業所  Generac 1654-0 Portable Generator User Manual  User`s manual Reception terminal - Alcatel  Eglo BORGO 1  

Copyright © All rights reserved.
Failed to retrieve file