digitalSTROM Installation Manual
Contents
1. a xr xr O lS O Room push button 1 Device push button 2 O Room push button 2 Push button Click Preset Room push button 1 1x click 1 Entire room 2x click 2 Reading 3x click 3 Relaxing 4x click 4 TV Room push button 2 1x click 11 Dining romantic 2x click 12 Dining light Device push buttons 1 1x click Associated standing lamp 2X 3X 4x Presets 2 4 click digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 96 132 Example 2 Fewer clicks due to one additional room push button Although the 4 presets in a room are enough for the residents they want to be able to call up each preset with a maximum of 2 clicks Therefore you are going to use a second room push button as in example 1 Presets 3 amp 4and 13 amp 14 however remain unused Example 3 Dimmed preset with one additional room push button Different lighting presets are called up in a bathroom with a room push button The resident wants to use dimmed lighting presets in the bathroom at night Therefore a second room push button is used to call up a dimmed lighting preset with only one click Room push button 1 Room push button 2 O Push button Click Preset Room push button 1 1x click 1 Mirror cabinet WC 2x click 2 Bath shower 3x click 3 Whole room light Room push button 2 1x click 11 Mirror cabinet dimmed 2x click 12 Bath shower dimmed 3x click 13 Whole room dimmed digitalSTROM Installation
2. Activate consumption event off Activates the sending of a consumption event message with the specified name e g TV off if the current consumption value falls below the configured threshold e g 230 W If the digitalSTROM Device is switched off by activities like Leaving home or Deep Off no consumption event will be notified k Rename device Opens a dialogue to rename a digitalSTROM Device 2 Rename Device x Device ID 00004456 Device Name Ceiling light Kitchen N 4 Close With Select previous device and Select next device you navigate directly to the next or previous digitalSTROM Device in the list Edit comment Opens the dialogue to edit a comment on the digitalSTROM Device Edit Comment x Comment for 00003754 Illuminant was replaced 24 08 2010 OK Cancel digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 82 132 Delete device Deletes the selected digitalSTROM Device from the device list Only applies to digitalSTROM Devices which are inactive grey Delete Device x Device Name Floorlamp Couch Device ID 000037b4 Are you sure you wantto delete this device Deleting the device will remove its configuration Therefore the device should only be deleted if itis permanently removed from this digitalSTROM installation If you want to connect the device again you might need to reregister the device manually within the power circuits tab Delete Cancel
3. During initial operation it is advisable to start the digitalSTROM Meters consecutively and to verify the successful registration of the connected terminal blocks The registration of all devices is completed when the status indicator light is continuously green for more than 1 minute and is no longer blinking yellow or blue The LED of the digitalSTROM Device continues blinking until all devices have automatically registered with one of the digitalSTROM Meters Configuring via push button or digitalSTROM Server The presets of a room can be configured by push button without requiring a digitalSTROM Server with a web based Configurator to do so Setup options are described in detail in the user manual in the section Setup If several digitalSTROM Meters are used in conjunction with a digitalSTROM Meter additional configurations can be made with the digitalSTROM Configurator Creating additional rooms or groups Allocating digitalSTROM Devices to other rooms or groups e g moving a standing lamp to another room Advanced settings for digitalSTROM Devices e g changing the push button function or operation mode of the power output Installation of digitalSTROM Server apps and executing system or firmware updates for digitalSTROM components Diagnostics and data evaluation Configuration tasks performed in the web based digitalSTROM Configurator are documented in detail in chapter 5 The push button function of
4. gt Rain No Rain Wind SE No Wind gt Hail No Hail gt Panic A Fire K Alarm 1 6 Alarm 2 H Alarm 3 i Alarm 4 The behaviour of selected higher level activities of digitalSTROM Devices is pre defined at the factory In the factory setting e g awnings are retracted during rain lights switched on in case of fire and shutters opened To change the behaviour of the digitalSTROM Device for a higher level activity open the main section Activities and choose the higher level activity in the selection list Usethe command Edit device properties in the device list to configure the selected device You will find information to configuring the device values for higher level activities in chapter 5 5 2 You will find additional information to default activities that digitalSTROM Devices have for higher level activities at http www aizo com downloads http www aizo com downloads C Data view C1 Data view tool bar In the data view tool bar you can see the valid commands for the displayed list items in the form of icons in addition to a title with information on the list content Devices in Room Living room 1281 12 Devices _ T wer u E g blink devices rename device eS In order to run a command for the list item you need to first select the item The selected item has a green background Frequently used commands are left aligned in the tool bar Less frequently used commands are rig
5. Device Settings x Device Name Blinds Living room Device ID O00716ba0 Position set Blade Angle 0 i Pi Close Example for digitalSTROM terminal block Shade Position The settings of the device value are interpreted by the digitalS TROM relay terminal block as position For this purpose the digitalSTROM relay terminal block must be calibrated appropriately after installation See also chapter 5 3 4 Use Stop to stop the motion of a shading system e g if Qoen or Close was previously used to travel to the end position Only for digitalSTROM relay terminal blocks Shade grey With Open the movement command to fully open the shutters or extend the awning can be started Only for digitalSTROM relay terminal blocks Shade grey With C ose the movement command to fully close the shutters or retract the awning can be started Only for digitalSTROM relay terminal blocks Shade grey Set blade angle The blade angle can be set by direct text input values between 0 100 or with a slider Only for digital STROM relay terminal block grey Shade Blind The blade angle must be calibrated appropriately after installation See also chapter 5 3 5 ill Test transmission quality Checks the transmission quality of the down and upstream communication to individual digital STROM Devices and shows the connection quality in a dialogue after test completion Transmission Quality x Device Name Doorbell De
6. The status bar shows the current software version of the digitalSTROM Configurator as well as information on executed commands or the operating condition of the digitalSTROM system 1 7 0 s35test01 Device Blinds Living room 00016ba0 was moved into zone Living room Commands The digitalSTROM system confirms successful implementation of the user s commands in the status bar Examples for this are Device ceiling light TV 000043e2 was moved to room living room Device desk lamp 0O0005A61 was deleted digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 38 132 Operating condition Information regarding the operating condition of the digitalSTROM systems is displayed in the status bar An example for this is Devices are updated Configuration is written Device 1 of 29 data set 10 of 19 This example displays the message while the devices are updating See also chapter 5 2 8 1 E Change update view The control elements Update wewand Advanced vew Basic veware used to update the data view and to show and hide additional main sections Refresh View Basic View F Language settings Use the drop down list to select the language for the menu navigation and dialogues in the digitalSTROM Configurator After changing the language setting the web based user interface is automatically re loaded in the selected language Deutsch English Francais Nederlands Turk
7. 230 V AC mains voltage Working on the electrical installation is only allowed if the system Is de energised Components must be installed and commissioned only by qualified personnel Local regulations must be complied with Distinctive feature of digital STROM A Ensure that the system is de energised by switching fuses to off before working on a digitalSTROM installation Reason Other than in conventional installations one has to note that in a digitalSTROM installation the digitalSTROM terminal blocks conduct mains voltage on the input side even if the consumers are switched off Switching off a consumer e g lamp with the push button does not de energise the terminal block digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 14 132 3 2 Preparatory works Before you start the actual work Check if all digitalSTROM components required for the assembly are available Visually inspect all devices for damage Replace damaged components and do not use them in the installation Follow the installation instructions for the individual digitalSTROM components These instructions are shipped with the digital STROM component They contain the required information and warnings for the correct use of digital STROM components Inform owners or occupants of the impending work Let them know which sections of the domestic installations will be affected by the interruption of power and how lon
8. 9 1 Faulty operating condition If you detect a faulty operating condition Check if the power supply of digitalSTROM Devices power circuit breaker is switched on Check if the electrical connections of digital STROM terminal blocks and digitalSTROM push button blocks are realised according to the installation instructions Make sure that connected consumers do not exceed the maximum permissible output Check if the connected consumers are supported by the operating mode of the digital STROM terminal block capacitive inductive load dimmable lamp etc Check if the installation of the digitalSTROM components in the distribution board corresponds to the installation instruction specifications maximum length and terminating resistors of the dS485 bus interconnections Check if digitalSTROM Filters are installed in front of the digitalSTROM Meter input Check the operating condition of the digital STROM Server and digitalSTROM Meter LED status indicator Check the configuration of the digitalSTROM Devices in the digital STROM Configurator 9 2 Ensuring reliable operation The steps described in the following section are meant to ensure the reliable operation of the digitalSTROM system The tests are performed consecutively for every power circuit Avoid any operations in the tested power circuit e g using push buttons during the following tests The described processes are excluded If you have removed any devices o
9. ale digitalSTROM digitalSTROM Installation Manua 2 132 Author aizo ag Copyright 2013 digitalSTROM com All rights and technical changes reserved at all times A1121D002V010EN 12 11 2013 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 3 132 Table of Contents 1 About the document 11 Forwhomis this document intended L2 What are the requirements for use L3 Installation manual as an online helo 14 Conventions L5 digitalSTROM glossary 16 digitalSTROM colour scheme About the system 21 How Is a digital STROM system constructed 22 Design and functionality Installation 3 1 Safetynotes 32 Preparatory works 33 Electrical installation in the distribution board 34 Installations in the rooms Initial operation 4 1 Starting the system 4 2 Configuring via push button or digital STROM Server 43 LED status indicator and restart 4 3 1 digitalSTROM Meter 4 3 2 digitalSTROM Server 44 Establishing a network connection 4 5 Login to the digitalSTROM Server 46 Remote access via the Internet Configuration 5 1 digitalSTROM Configurator user interface 5 2 Check basic server configuration 5 2 1 System overview 5 2 2 Configuring the network 5 2 3 Adjusting system settings 5 2 3 1 System 5 2 3 2 Location 5 2 3 3 Date and time system time 5 2 3 4 Apartment basis address 5 2 3 5 Setting presets 5 2 4 E mail settings 5 2 4 1 Mail server 5 2 5 Access authorisations 5
10. Net mask Address entry mask for the search of devices in a subnet Must be the same for all devices in a Subnet Gateway IP address of the device permitting communication with other networks DNS1 IP address of the 1st device for name resolution in the network Domain Name Server 1 DNS2 IP address of the 2nd device for name resolution in the network Domain Name Server 2 MAC Hardware address of the network adaptor Used for unique identification of the digitalSTROM Server cannot be changed Resetting the network settings Hold the LED push button at the housing front of the digital STROM Server depressed for 15 seconds to set the network configuration back to factory settings Please note that this will also reset the administrator password to factory settings See also chapter 5 2 6 digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 41 132 5 2 3 Adjusting system settings Check the system settings of the digitalSTROM Server and adjust them if necessary 5 2 3 1 System System Note the name must not contain any whitespaces and special characters except Name dSS Documentation Apply Enable access via SSH Iv Apply Name Network name of the digitalSTROM Server Sent as identifier during communication setup to UPnP enabled devices In factory settings the system name is set to the value dSS Enable access via SSH The digitalSTROM Server supports the SSH
11. The administrator Passwora is dssadmin To be able to modify the administrator password in the web based digital STROM Configurator user interface you need to enter the current password and the new password twice The password must not contain any spaces digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 48 132 Resetting the administrator password Hold the push button LED on the housing front of the digital STROM Server depressed for 15 seconds to set the administrator password back to factory settings Please note that this will also reset the network settings to factory settings See also chapter 5 2 2 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 49 132 5 2 7 System maintenance 5 2 7 1 Backing up and restoring system settings Backing up system settings Backup and restore settings In order to backup the system Settings given names and all App configurations the data can be downloaded using the backup button Note dSM and device data such as room setup or activity settings will not be stored Backup Restoring the data will overwrite all changes done on the system Select file to restore Browse Use Backupto save the current system settings in a backup file Once the system has created the backup file a browser dialogue opens allowing you to save the file e g on your laptop Select Save and choose the storage location of t
12. area of application it can be used as a direct trigger in a digitalSTROM Server app e g Event Responder Using the wall push button you can call up a variety of activities and use the same User Defined Actions as on your smartphone The joker black area of application can therefore be used to integrate consumers in a digital STROM system that cannot be covered by the available digitalSTROM colours although they should respond to higher level activities Typically these are devices that require a constant power supply during operation but are switched off during absence Furthermore the digitalSTROM push button block joker black can also be configured as a trigger for higher level activities such as Leaving home or Ringing See also chapter 5 3 2 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 9 132 2 About the system 2 1 How is a digitalSTROM system constructed The components of the digitalSTROM system To be able to use the existing power lines from the distribution board to the digitalSTROM Devices for communication purposes a digital STROM Meter is operated in each power circuit The digitalSTROM Meters like the power circuit breaker are installed into the distribution board Multiple digitalSTROM Meters max 62 units communicate via a standardised protocol dS485 bus interconnection The installation of a digitalSTROM Server enables connection to a higher level system buil
13. gt No Rain Wind Se No Wind gt Hail gt C No Hail gt Panic h Fire i Alarm 1 6 Alarm 2 H Alarm 3 i Alarm 4 These activities apply to all digitalSTROM Devices in the digitalSTROM installation independent of the application area e g light or shade digitalSTROM Devices triggering higher level activities can be installed in any room Higher level activities are triggered independent of the room Leaving home The actuation for 3 seconds of a push button configured as Leaving home push button triggers the activity Leaving home Most digitalSTROM Devices will be switched off The desired behaviour can be configured as necessary Coming home The brief actuation of a digitalSTROM push button configured as Coming home push button triggers the activity Coming home The actuation of any digitalSTROM push button will also trigger Coming home unless the Coming home push button was actuated upon returning Any digital STROM terminal block can be configured to either react to this activity or to ignore it For example you can switch on devices connected with a digitalSTROM inline adapter For this purpose the digital STROM inline adapter must be configured in the operating mode Saving See also chapter 5 3 2 Ringing The brief actuation of a digitalSTROM push button configured as Ringing push button triggers the activity Ringing Any digital STROM terminal block can be configure
14. list 1x click Specifies if Zx click applies to a connected device the devices in an area or the preset in the room 2X 3 4x click Visualises the used presets for 2x 3x 4x Click digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 74 132 Local priority for 1x click If local priority is active the digitalSTROM Devices switched on by the device or area push button will not be affected by presets being called up for the room Consequently they can only be switched off by using the corresponding device or area push button or by holding down 1s another push button of the corresponding colour e g yellow This functionality corresponds to the behaviour of the digitalSTROM line switch For the area push button local priority is active by default in factory settings You can deactivate local priority for the area push button as needed This might be useful if the presets called up in a room are meant to switch all digitalSTROM Devices belonging to an area The local priority setting for device and room push buttons cannot be changed Call up Coming home for absence If the higher level activity Leaving home is called up when the house is left e g through the Leaving home push button at the house entrance 1 click on any push button calls up the higher level activity Coming home This setting is active in the factory settings Deactivate the settings when e g the light push
15. usr share dss data configdirectory usr share dss data webrootdirectory usr share dss web webroot jslogdirectory Nar log dssijs savedpropsdirectory usr share dss data savedprops aC subsystems a spidermonkey j digestfile etc lighttpd user aC geodata 343 apartment aC zones aC dSMeters usr aC scripts The displayed system properties are not described here in detail but may be useful for problem analysis in the event of a support case The specifications are for information only and cannot be modified digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 56 132 5 3 Check and configure installation in power circuit A digitalSTROM Meter controls the communication between digitalSTROM Devices in each power circuit Check if the listed digitalSTROM Devices correspond with the information on your configuration sheets Assign unique names to the digitalSTROM Meters and associate them with previously noted dSM IDs This facilitates the later configuration of rooms and digitalSTROM Devices Add necessary information as comments to the selection list Configure the features of individual devices e g push button function Calibrate individual digital STROM Devices e g digitalSTROM relay terminal block Shade For the presentation in the Hardware main section a selection list containing all digital STROM Meters Is displayed in the upper half of the screen See al
16. 1 4 if the push button connected to the input shall be used for Open or Close See also chapter 5 3 1 For example you may operate two push buttons for light and a 2 way push button for shade at the same terminal block Pa a ete he ere ee ee ae LS 16 A 230 VAC dSM N L Push button 1 4 z B 2x serial rocker switch 2 conductor lighting terminal block bi l Uo e g Wago type 224 112 TF a ee Seem 10 mm 0 75 mm EE SW TKM200 digitalSTROM line switch Install the digitalSTROM line switches according to the installation instructions e g digitalSTROM line switch GE SDM200 for standing lamps O75 1 5 mm digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 23 132 digitalSTROM automation terminal blocks Install the digitalSTROM automation terminal blocks in accordance with the installation instructions e g digital STROM automation terminal block SW AKM200 for movement wind or rain sensors E imac ai cap mali ied hele cet A k me a Z230 VAC B JEM sensors 14 730 Zaire lighting eminal block ie type Woga 224 112 10 mm 075 mm m m tinned pigtail SW AKM200 The digitalSTROM automation terminal block is available in different designs 4 2 and 1 inputs and is conceived for connection of up to four sensors with 230 V switching output Ideally you would operate no more than twenty automation term
17. 12 11 2013 digitalSTROM com 5 Configuration 32 132 5 1 digitalSTROM Configurator user interface The digitalSTROM system can be quickly and conveniently configured and monitored with the web based user interface of the digitalSTROM Configurator The interface is very user friendly and is designed for easy and clearly structured navigation and intuitive operation General control elements digitalS TROM Configurator B1 b Bedroom a E S vig 4 E Living room Floor lamp Couch 4 Liont Presets Ceiling light Hall e Button Living room ite Ceiling light Dini 00004 39 000037b4 000044dd 00017 ca0 a B2 Fade off 00004437 wy Preset 1 Light on w Preset 2 Watch TV g Preset 3 Read g Preset 4 Relax g Area 1 on Dining table wa Shade Presets jLeaving Home B3 j Coming Home Door Bell 2013 08test03 Legend ANavigation main sections B Selection view B1 Tool bar B2 Tree list view B3 Higher level activities CData view C1 Tool bar C2 Tree list view C3 Embedded dialogue DStatus bar E Change update view F Language settings digitalSTROM Installation Manual iretox coria Ay dSS Documentation A vttps 192 168 8 133 L A A digitalSTROM Output Mode dimmed dimmed dimmed dimmed C2 A1121D002V010EN 12 11 2013 C1 input mode Device Area 1 Presets 2 4 Device CS The current settings can be saved for the selected preset
18. COS 5 thee haath ihe heated ete 31 digitalSTROM Installation Manual 132 132 ROOMS esi creates eos aaa A EES aeaa ia 89 Allocating deviceS ssssessessssserrrrsssrrrrrnrsseerne 101 CP CATING icerir enra N 100 SVS O a hane head ane Rdonteh ieee 9 COMMS ICOM lia doteri a a 9 DISEIDEITION DOF sikas 10 FUNCHONA owna aana a 11 Uporadabil I azaria a a a aa AARS 11 T Telegram Downstream COMMUNICATION ccceeeseeeeeeeeeeees 11 Upstream COMMUNICATION sssssseeeeesssererrnreseren 11 TEOUDIES NOONG miiia eieae eaa eae 127 A1121D002V010EN 12 11 2013 digitalSTROM com
19. Manual A1121D002V010EN 12 11 2013 digitalSTROM com 97 132 Example 4 Use area push button to switch specific lamps Configure the two digitalSTROM push button blocks as area push buttons to be able to directly switch selected digitalSTROM Devices in a room with only one click The ceiling light in the dining table area and the lamp above the lounge table can thus be switched directly However the area push buttons can still be used to call up presets for the room See also chapter 5 3 2 Device push button 1 ry O X Aw Kr B2 Qa Xa xr O _ O ie push button Device push button 2 O aki push button Push button Click Preset Area push button B1 1x click Area 1 On Dining table 2x click 2 Reading 3x click 3 Relaxing 4x click 4 TV Area push button B2 1x click Area 2 on Lounge table 2x click 2 Reading 3x click 3 Relaxing 4x click 4 TV Device push buttons 1x click Associated standing lamp 1 amp 2 2X 3X 4X Presets 2 4 click digital STROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 98 132 Local priority for 1x click Use the device setting Local priority for 1x click to determine how digital STROM Devices in an area react to presets called up for the room Refer to Local priority for 1x click in chapter 5 3 2 Additional presets with area push button B2 If the presets available at the area push buttons do not suffice for the room e g 2 4 you can configure the
20. Room push button 1x short Factory setting push button block aN H eme ama fou Quit B L LE L Quit and save 1 x long 3 sec LED flashing According to Assembly Instructions newer device versions only or Light 2 x flashing short short long LED 2 x flashing Light 2 x flashing Cancel Automatically after 30 sec Example for the configuration of the push button function with click command on the local push button of a digitalSTROM push button block Light yellow Refer to the installation instructions for information on the configuration of additional digital STROM products digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 84 132 5 3 4Calibration of the motion time and direction of the digitalSTROM relay terminal block Shade The positioning of shading systems can not be directly controlled through the power output of the terminal block Instead it is controlled by the corresponding running time of the motor in the Shading system Therefore the shading system has to be calibrated after connection to the digitalSTROM relay terminal block During calibration the system moves to the end positions of the shading system whereby the direction of travel and the path time measurements are parametrised in the terminal block It is imperative for the parameters to be determined in order to ensure safe and faultless operation Calibration by digitalSTROM Configu
21. With C ose the movement command to fully close the shutters or retract the awning can be started Only for digitalSTROM relay terminal blocks Shade grey Set Blade Angle The blade angle can be set by direct text input values between 0 100 or with a slider Only for digital STROM relay terminal block grey Shade Blind The blade angle must be calibrated appropriately after installation See also chapter 5 3 5 Saving presets for the room area Save all device values for the selected preset with the command Save or use the command Save in other preset When the device values for a preset are saved the current device value at the device output is not changed Save settings to another preset x You are about to save your current settings to a different preset Please select the target from the list w Preset 2 Watch TV v Save Close With the command Re ect no values are saved instead the selected preset is called up once again Thus the room is in the previous state for the selected preset digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 114 132 Note on the configuration of areas To be able to serve a specific area the corresponding digitalSTROM push button must be configured as area push button in the Hardware main section See also chapter 5 3 2 Please also observe the note on local priority Further note that in factory settings digitalSTROM Devices are assigned to all areas I
22. a higher level activity is called up If a higher level activity is selected from the selection list of the main section Activities then the device value for this activity can also be changed saved in the digitalSTROM Device in this dialogue When the value is set the output is not directly changed Yet as necessary the value can be activated with the command Prevew reset at the output This way settings for the individual devices can be changed without calling up the activity in the entire installation The command Save saves all the settings displayed in the dialogue for the selected activity in the corresponding device The value does not necessarily need to be present at the output when saved so the Prevewdoes not necessarily have to be called up If the setting Do not change output is activated the setting of the device value for the higher level activity cannot be carried out F Device Properties Wind x Device Name Blinds Living room Device ID 00016ba0 Output Mode Settings Advanced Settings Blink when calling Wind Retain output when calling Wind Position 100 00 Up EN q stop Down Set Blade Angle 100 Preview N Vv Close Example dialogue for the setting of the device value for the higher level activity Wind for a digitalSTROM terminal block Shade grey digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 117 132 Advanced device properties BD Devic
23. button block Please take note that the dialogue for the device properties is structured differently for the digitalSTROM automation terminal blocks You will find the description later in this chapter Colour group Only available for digitalSTROM Devices of the application area joker black Choose the desired digitalSTROM colour for the operation of the selected digitalSTROM Device If a push button is intended to switch light the colour group is set to Light yellow The colour group of digitalSTROM relay terminal blocks is set based on the connected devices E g set the colour group to audio cyan if an audio system is switched with it In this way the digitalSTROM push button block joker can be used as the push button in the different colour areas digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 67 132 Light hd Light wW Shade Climate Ww Audio w Video Joker Refer to chapter 1 6 for instructions on the digitalSTROM colour scheme Furthermore in the colour group joker black higher level activities e g Ringing or Panic can also be triggered or digitalSTROM Server apps controlled with the connected push button For this see the description of Push button later in this chapter Qperating mode Operating mode of the power output for digitalSTROM Devices with power output and application area joker black The operating mode of the digitalSTROM Device jok
24. created and managed Create new group Name Lights ground floor Color Group Light w Save Cancel Edit user group Opens the dialogue to edit the selected group In order to be able to change the colour group of a group first all digitalSTROM Devices must be removed from the group Edit user group Name Lights ground floor Color Group 3 Cancel 8 Delete group Deletes the selected group In order to be able to delete a group first all digitalSTROM Devices must be removed from the group digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 120 132 5 6 2 Allocating a digitalSTROM Device to a group List of digitalSTROM Devices Apps Activities Rooms Groups System Hardware Help Groups Devices in group Shadow 2 FSS ce d 2 cia ef we rs All Devices Name dSID Output Mode Blinds Living room 00016ba0 00049022 Light w Shade w Video Blinds first floor R it Lights ground floor Y 1 selected row Use Drag amp Dropto allocate a digital STROM Device to a group Input mode Device Blinds first floor To do so select a digitalSTROM Device from the device list and with the left mouse button pressed drag it to the selected group in the selection list n order to move several digitalSTROM Devices at the same time select the digitalSTROM Devices with the mouse button while holding down Ctr or Shift For devices with a power output only the output
25. dss_backup_2013 01 14_145002 dss 1 14 2013 2 48PM DSS File it Local Disk C d dSSBackup d Perflogs do Program Files d Program Files d sources Temp d Users yy gt File name dss_backup_2013 01 14_145002 ds v All Files v Open Cancel Ex Firefox Dialogue Then use Restoreto start the recovery of the system settings from the selected backup file After completion the web based digital STROM Configurator is automatically reloaded in the browser 5 2 2 Restarting the digitalSTROM Server Reboot System dSS is running since Dec 20 07 23 System is up for 110 days 17 hours and 10 minutes Reboot The dSS application is running since Time of the last digitalSTROM application restart The system is running since Current operating time since the last digitalS TROM Server restart in days hours and minutes Select Restartto restart the digitalSTROM Server You cannot send any commands in the web based digital STROM Configurator during digitalSTROM Server restart After the restart the digitalSTROM Configurator is automatically re loaded Rebooting system Please wait while the system is rebooting The setup page will be automatically reloaded after the time elapses 65 seconds remaining digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 51 132 5 2 7 3 Formatting the SD card SD Card The dSS includes a micro SD card to store metering and loggi
26. for the transmission quality of the upstream communication is less than 80 Checking results The measured results can also be viewed in the protocol digitalSTROM Protocol of transmission quality Overview Testtransmuission quality of dewces Testtransmission quality for all devices on dSM 35041751e000001000000501 using 1 checks per device 7 Status Number of devices Stared tested Ended Summary Number of checks with errors Transmission quality digitalSTROM Installation Manual Number of tested devices Number of executed tests Number of tests wrth errors Average upstream quality Finished Thu Jan 17 16 34 43 CET 2013 Thu Jan 17 16 35 15 CET 2013 12 12 0 96 A1121D002V010EN 12 11 2013 digitalSTROM com 129 132 Removing sources of interference If an inadmissible number of transmission errors were detected the source of interference must be localised and isolated If you have connected many electronic devices using one or several connector strips you Should connect them first with a digital STROM Device Filter dS FD and repeat the test If the result improves considerably leave the digital STROM Device Filter dS FD in this location Otherwise continue the search For the identification of individual sources of interference switch them off separately and repeat the transmission quality test Considerably improves the result the corresponding consumer should remain connected to the d
27. installed in close vicinity The basis address which is configured in the digitalSTROM Server determines the address of the digitalSTROM Server and thus the increasing sequential numbering of the connected digitalSTROM Meters The Apartment Basis Address which is valid for the digitalSTROM installation must be configured once in the web based digitalSTROM Configurator on the digitalSTROM Server The numbering of the digitalSTROM Meters is then automatically transmitted to the connected digitalSTROM Meters The freely selectable address is between 0 62 The basis address the maximum number of connected digitalSTROM Meters must not exceed 62 This allows a maximum of 62 digitalSTROM power circuits digitalSTROM Meters located closely to each other to be operated in a building In a multi family residential building with several independent digital STROM installations it is therefore especially important to ensure that the address ranges do not overlap 5 2 3 5 Setting presets Activities configuration To protect the digitalStrom settings in your devices you can disable the activities configuration with the zone push button This setting is valid for the whole apartment J Configuration mode enabled Apply The programming mode short long click on the push button can be deactivated for the entire installation This prevents the settings from being adjusted by mistake or intentionally in publicly accessible areas The setup
28. is allocated to the group The push button input retains its previous function If the push button should control this group the device must be set in the device properties in the main section For devices without an output the push button output is allocated directly to the group See also chapter 5 3 2 Columns and columns The tool list of the device list in the main section Groups contains the same commands and columns as those in the device list in the main section Rooms See also chapter 5 3 2 However the device list also has the following command 8 Remove devices from group Removes the selected digitalSTROM Device from the group However the device list also has the following column Groups Group s to which the respective device is allocated can also be several The input mode that is also displayed indicates the group if the push button input of the device effectively controls a group digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 121 132 6 digitalSTROM Server apps digitalSTROM relies on open standards Manufacturers can easily equip digital STROM Devices with convenient applications New applications are continually being developed for digitalSTROM products With digital STROM you are benefiting from the technology of the future Not only can you extend its functionality by adding new rooms or devices you can also make use of new digitalSTROM Server apps on you
29. light living 1st floor F2 light kitchen 1st floor The proprietor of the apartment wants to control the ceiling light of the open kitchen and a section of the adjoining living area together in the same lighting preset Therefore you are going to shift the desired ceiling lights from the room living room to the room kitchen and rename this room kitchen with dining table Then you are going to adjust the lighting preset for this room accordingly See also chapter 5 5 2 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com digitalSTROM Installation Manual 91 132 AOS AOE DJOLE DOL dSF Filter dSM Meter GE TKM Push button GE KM Lighting GE KM Lighting dS485 Bus dSF Filter dSM Meter GE KM Lighting GE KM Lighting GE TKM Lighting Divide standard rooms into different rooms or merge devices from different circuits in one room SO SONS 2 8 e DOGC dSF Filter dSM Meter GE TKM Push button GE KM Lighting GE KM Lighting Q R dS485 Bus dSF Filter dSM Meter GE KM Lighting GE KM Lighting GE TKM Lighting 230 VAC 230 VAC 230 VAC 230 VAC A1121D002V010EN 12 11 2013 digitalSTROM com 92 132 5 4 2 Possible functions of the digitalSTROM push button block The digitalSTROM push button block can be operated with three different push button functions Push button Use Device push You can use the device push button to
30. relay terminal block determines the required parameters of the connected shading system digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 86 132 1 way 2 way Action push button push button Direction of movement Prepare E falv Start adjustment M Start configuration LIL Select E ay Select shade system First end position Move shutter blinds to the limit switch of the opened end position Move the awning to the limit switch of the extended end position Note The relay terminal block detects the end position by the change in the load current limit switch If in preset 2 the shading is already at the limit switch it will first have to be moved back by a few centimetres Second end position Move shutter blinds to the limit switch of the closed end position Move the awning to the limit switch of the retracted end position First end position Move shutter blinds to the limit switch of the opened end position Move the awning to the limit switch of the extended end position The calibra tion of the selected relay terminal block has now been successfully completed If you want to save the current positions in preset 2 Otherwise end adjustment 1 The 1 way push button changes the direction of travel after a long click 2 Depending on the installation of the digitalSTROM relay terminal block the direction of travel for the 2 way push button only matches
31. rising flank causes a switching sensor message for the On state Falling flank on Only the falling flank causes a switching sensor message for the On state Rising flank off Only the rising flank causes a switching sensor message for the Off state Falling flank off Only the falling flank causes a switching sensor message for the Off state Rising flank on off The rising flank causes the switching sensor message for the On and Off states in alternation Falling flank on off The falling flank causes the switching sensor message for the On and Off states in alternation digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 OdigitalSTROM com 71 132 Switching on delay The switching sensor messages for the On state are first sent off when the sensor signal for the minimal specified time duration is steadily present time entry in minutes and seconds Switching off delay The switching sensor messages for the Off state are first sent off when the sensor signal for the minimal specified time duration is steadily absent time entry in minutes and seconds In the factory settings the switching off delay is 1 minute in order to debounce sensors which switch frequently and so minimize the amount of switching sensor messages Therefore it is recommended to leave the switching delay set to at least 1 minute digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 OdigitalSTROM com 78 132 Py Edit
32. same colour group e g Shade grey Some application cases require the possibility to operate digitalSTROM Devices independent of the architectural floor plan or the power circuit Therefore sensors and push buttons which are allocated to a group trigger presets for all digital STROM Devices in the group Independent of which room the digitalSTROM Device is still allocated to thereby In the process the setting of the device values for the presets of the digital STROM Devices does indeed take place in reference to the preset in the room for more information refer to chapter 5 5 2 yet within a group the saved presets can also be called up by additional sensors Set the device values for the preset within a room in the main section Room Create the groups suitable for the application case you desire in the main section Group Use Drag amp Dropto allocate the digitalSTROM Devices to the created group Allocate at least one sensor to the digital STROM group e g a digitalSTROM push button block or a digitalSTROM automation terminal block Then the group can be operated via the allocated push button or sensor The devices in the rooms can continue to be operated as usual via the room push button Application example central push button for shading systems If you would like to e g operate all blinds on the south side of the building from an additional digital STROM push button e g a central push button at the entrance ins
33. second digitalSTROM area push button to call up additional presets e g 12 14 In this way you can position the presets for dining on the area push button B1 dining table and the presets for reading relaxation or watching TV on area push button B2 lounge table See also chapter 5 3 2 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 OdigitalSTROM com 99 132 Example 5 Combination between area and room push button You want to be able to switch dim two consumers connected separately via digital STROM line Switches simultaneously from each line switch e g connected standing lamps Configure for this purpose both digitalSTROM line switches as area push buttons for the same area e g Area 1 See also chapter 5 3 2 Area push button B1 l O D a Area push button B1 O Room push button 1 In this example both standing lamps are switched on off at the same time Push button Click Preset Room push button 1 Dining 2 Reading 3 TV 4 Whole room light Area push button Area 1 On Standing lamps 2 Reading 3 TV 1 2 3 4 1 2 3 4 4 Whole room light digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 100 132 5 4 4Creating and renaming digitalSTROM rooms digitalSTROM rooms selection list Apps Activities Rooms Syste Rooms lp Osi v3 ga Ea All Devices Bedroom Hallway Kitchen Living room The selection list shows existing rooms in a
34. sunset can be used in digitalSTROM Server apps e g to monitor meteorological data or to control shading systems digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 42 132 Use Select location on map to determine the coordinates on a map visually This allows you to pinpoint the coordinates within the selected locality or to determine the coordinates for a locality not listed in the Locality drop down list An already selected locality will not be changed hereby Enter an address directly into the search box or use the mouse to move the marker on the map Select your location x Search La a Karte Satellit ford i Wes ag f J gt pa West Ti GA A s Hampstead Wy oo Ww Ki i z l ilburn PX ERN A A LY Maida Hill E Bromley DN By Bow 4 i 3 t 7 x Fh i 2 i din to i e ja y i fite Ci i ee T mole y j g aise Sets ondo z Lean 7 tyde SN oY Ban Poplar 2 anary a d a lisle of Dogs K g Cs hehe l Fi Wr Greenwich Deptford ss New Crossa 4 Nica Greenwi west Kensington vo 4 s Battersea B Pa Ful a Chelsea hg Harbour b T s v Pm Sk oa Sateen PL Apply Cancel Selecting the country and locality will automatically adjust the time zone for the system time Unless country and locality are specified th
35. switch dim a consumer connected directly to button the power output of the digitalSTROM push button block With 2x 3x 4x click on the device push button you can also call up presets for the room Area push Use the area push button to directly switch dim selected digital STROM Devices button area with 1x click The other devices in the room are not affected by this With 2x 3x 4x click on the area push button you can also call up presets for the room Room push The room push button is generally used to call up presets for all digital STROM button Devices of the same colour group e g Light yellow which are added to the room The push button function is configured in the Hardware main section See also chapter 5 3 2 The push button function can also be configured by click commands on the local push button See also chapter 5 3 3 The following chapter 5 4 3 explains the use of the digitalSTROM push button block with dissimilar push button functions by using application examples digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 93 132 Areas ina room Device push button 1 7x zly as C Q Dining table L Xr Area B2 K rv Salon table Xa Rn o K re Kru e Living O room O Area push button B1 gt X Device push button 2 O Area push button B2 The area push button allows you to directly switch on all digitalSTROM Devices in an area with 1x click e g both c
36. switched to 0 off or 100 power on Dimmead The output power varies between 0 100 Use only for operation of dimmable loads Deactivated The digitalSTROM Device is not considered by the digitalSTROM Meter during the setup of presets and activities Use this setting if no load is connected to the terminal block digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 OdigitalSTROM com 73 132 Advanced properties a The Advanced Properties can be shown hidden by using the corresponding arrow Hide Advanced Properties a Push button Used presets Presets 2 4 default 1x Click Area 1 2x 3x 4x Click Presets 2 4 default Local priority for 1 click Call Coming Home when absent Used presets Determines which presets are used for the selected digitalSTROM push button block for 1x click 2x 3x 4X click For device push buttons the following presets are fixed Device preset 2 4 For area push buttons presets can be used as follows Area 1 preset 2 4 or preset 12 14 Area 2 preset 2 4 or preset 22 24 Area 3 preset 2 4 or preset 32 34 Area 4 preset 2 4 or preset 42 44 For room push buttons presets can be used as follows Preset 0 4 Preset 10 14 Preset 20 24 Preset 30 34 Preset 40 44 Presets 10 20 30 and 40 correspond in factory settings to preset 0 off For a quick overview of the current configuration the used presets are displayed in form of a
37. the Open Close push button after calibration Check the functionality of the push button while approaching the first end position and use the other Open Close push button as necessary For each additional step use the other applicable push button symbolised by After calibration the push buttons will match the effective direction of travel digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 87 132 5 3 5Turn time calibration for the digitalSTROM relay terminal block Shade Blinds are mechanically constructed to close the blades when they are lowered If the blinds are re opened the blades are first turned over before the entire blind is raised Due to this mechanical peculiarity the blades of many blinds can be controlled The digitalSTROM relay terminal block grey Shade can move the blades into the desired position Here the blade angle is not directly controlled by the terminal block power output Instead it is calculated on the basis of the turn time running time of the motor needed to open close the blades Therefore after connecting a shading system with blades the turn time must be calibrated During calibration the times for the complete opening and closing of the blades will be determined It is imperative for the parameters to be determined in order to ensure safe and faultless operation Calibration by digitalSTROM Configurator To perform the calibration in the web based digitalSTROM Configurat
38. the digitalSTROM push button block for devices sectors or rooms can also be configured via inching commands on the local push button See also chapter 5 3 3 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 25 132 4 3 LED status indicator and restart The digitalSTROM Meter and the digitalSTROM Server have an LED status indicator on the front of the housing The colour of the display optically signals the operating condition of the digitalSTROM Meter and digitalSTROM Server The operating condition of the digital STROM Meter can also be checked in the web based digitalSTROM Configurator The status of the LED status indicator and hardware errors are shown as icons in the main section Hardware in the digitalSTROM Meter selection list See also chapter 5 3 1 Events and error modes are indicated by the LED status indicator blinking once and changing its colour Different colours are associated with specific operating conditions See also chapters 4 3 1 and 4 3 2 Restarting and resetting via LED push button A membrane button LED push button which can be used to restart or reset the device is located under the LED status indicator Restarting the digitalSTROM Meter and digitalSTROM Server e In order to restart the digitalSTROM Meter or digitalSTROM Server the LED push button must be pressed continuously for 5 seconds After 5 seconds the colour of the LED status indicator for the digitalSTROM Server ch
39. 2 5 1 Release of applications 5 2 6 Changing the administrator password digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 OdigitalSTROM com Mm Hu aAwa uy A O 10 12 13 14 16 19 24 24 24 25 26 27 28 30 31 32 32 39 39 40 41 41 41 GREG 45 47 47 47 4 132 5 2 System maintenance 49 5 2 7 1 Backing up and restoring system settings 49 5 2 7 2 Restarting the digitalSTROM Server 50 5 2 7 3 Formatting the SD card 51 5 2 8 Check system updates 51 5 2 8 1 System update in the digitalSTROM Configurator online 51 5 2 8 2 Provide system update from USB flash drive offline 53 5 2 9 System properties 55 53 Check and configure installation in power circuit 56 5 3 1 Check and configure the digitalSTROM Meter functionality 56 5 3 2 Check and configure the digitalSTROM Device functionality 63 5 3 3 Configuring the push button function by click command on local push button 82 5 3 4 Calibration of the motion time and direction of the digitalSTROM relay terminal block Shade 84 5 3 5 Turn time calibration for the digitalSTROM relay terminal block Shade 87 5 4 Creating rooms and assigning devices 89 5 4 1 Application examples for rooms 90 5 4 2 Possible functions of the digitalSTROM push button block 92 5 4 3 Push button function application examples 94 5 4 4 Creating and renaming digitalSTROM rooms 100 5 4 5 Allocate digitalSTROM Devices to a room 101 55 Configuring activities and p
40. 21D002VO10EN 12 11 2013 digitalSTROM com 104 132 5 5 Configuring activities and presets The predefined device values of all digitalSTROM Devices in a room can be stored in an activity or preset and later called up later This allows e g realisation of different lighting presets in a room By using the digitalSTROM push button a single consumer is no longer switched but an entire preset is called up e g a lighting preset One activity allows calling up several presets e g lighting preset and shading simultaneously Activities however can only be called up with Special digitalSTROM Devices e g Leaving home push button for higher level activity Leaving home or in a digitalSTROM Server app At the same time digitalSTROM Devices selected by using an area push button can still be switched dimmed directly with Zx click Hence the functionality of a simple push button is extended to form a control unit for the whole room Please refer to the Operation section of the digitalSTROM user manual for the corresponding operating concept for digitalSTROM push buttons Call the activities presets and areas unique names Call up the activity preset area to be configured for a selected room Set the desired device values and special functions e g blinking of digitalS TROM Devices for the activity preset area and save the settings Repeat this process for all activities presets areas in this room Configure the acti
41. 8 Tool it 0 6 ere 37 User Interface cccccccceessssssseeeesssssseeeeeeeeesas 32 digitalSTROM inline adapter ZWS cccccccceee 23 digitalSTROM relay terminal block Shade Calibration running time direction of rotation 84 Calibration turn tiMe cccccccccccsssssseeeessssssseeeeees 87 digitalS TROM Apps IISTAN ING cccccccceeessstseeeeeeesssssteeeeeeessesseeeeeeeeseegs 122 UP Cate ccccccesesssssceeeeesesssseseeeeeessssseeeeeeeess 123 digitalSTROM Installation Manual 131 132 DOCUMEN ttt treated creates o E a EEE EEE 5 AS nline GMD sersssissnsisninonodniianus sninn ann 5 CONVENTIONS ss sssssssserrnrsssrrnrrnrssrrrnrnnnssrrrnnnnnsernnne 5 Requirements sssssssserrrnrsssrrrrrnnrsrerrrrnnnsserrnnnne 5 Target QGPOUP cc ccccccccecceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeneeeeess 5 E Error MESSageES sivinsiivescveieaecerecuneewendeecdveddeecdveddeeddeeds 27 Establishing a network connection eeessssseseeen 28 F FAA 130 G GOSSA tats E a tec a a a 6 E610 oc arei anaa Eao KAEN 118 Allocating deviceS sssssessessesserrrrsssrrrrrnrsseerne 120 O e E 119 H Hardware ee 56 Device properties ssssessssssssserrrnrssrrerrnnesee 66 75 digitalSTROM Devices sssssssrssssersrrrnrsssrrrernnesne 63 digital STROM Meter ccccccccccsssssseeeesssssseeeeees 56 Hardware error se ssssssssesrrrrsssserrnnrssererrnnrsserreenne 26 Shade device properties cccsccee
42. Blinds Device ID 00049022 Push button Blinds east Group Y Room push button Show Advanced Pt Area push button v Blinds east Group Cancel Example for a digitalSTROM push button block Shade grey which is assigned to the group Shade south side If a digitalSTROM Device with a push button input is assigned to a group e g digitalSTROM relay terminal block Shade grey the group will also be available in the properties dialogue but will not be automatically assigned This makes it possible for the push button connected to the digitalSTROM Device to be used as a central button for the group as necessary Refer to chapter 5 6 Information for digitalSTROM Devices of the colour group joker black Higher evel activities If the input of a digitalSTROM Device is configured for the joker application area black the connected push button can be used to trigger higher level activities To do so select the higher level activities Leaving home Ringing Panic or Alarm Then the push button completely sets up the corresponding digitalSTROM push button block e g as Panic push button Leaving Home Iv App button Leaving Home Door Bell Panic Alarm digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 70 132 App push button The push button can be used as an app push button to control digitalSTROM Server apps The app push button has no predefined functionality in f
43. DA lt neeneee 230 V AC digitalSTROM 10mm 0 75 mm l Tj 230 V AC The push button input is configured as room push button by default and controls the presets in the whole room The power output black strand may optionally be used to control a lamp in the room The lamp will then behave as if an additional digital STROM terminal block e g GE KM200 was used If the power output is not needed the strand has to be insulated digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 21 132 digitalSTROM push button block with 2 inputs Install the digitalSTROM push button block for 2 way operation according to the installation instructions e g digital STROM push button block GE TKM210 Shade grey with two push button inputs Two push buttons Serial rocker switch 230 V are connected to the independent inputs of the push button block Make sure the Open Close push button is connected correctly In case of awnings the push button should be connected to make sure that Open and Closed corresponds to the expected direction of travel of the shading The operating concept provides that the awning is extended with the Open push button up arrow If this is Supposed to happen when the Closed push button down arrow is pressed it has to be changed accordingly a E E A LS 16 A 230 VAC dSM Push button serial rocker switch 2 conductor lightin
44. Inactive digitalSTROM Devices and those physically removed from the installation stay registered in the digitalSTROM Meter e g seasonal decorative lighting Delete no longer used digitalSTROM Devices from the system Deleted digitalSTROM Devices have to be registered again if you want to use them later in the system For this purpose you select the corresponding digitalSTROM Meter in the Hardware main section and run the command Rereg ster all devices See also chapter 5 3 1 5 3 3 Configuring the push button function by click command on local push button The push button can also be configured by click commands on the local push button For this purpose you do not need a digitalSTROM Server or a digitalSTROM Meter and so can also be preconfigured The LED integrated in the housing of the digital STROM push button block visualises the operating condition during configuration For digitalSTROM push button blocks without LED you can connect a dimmable lamp for visualisation For this purpose the digitalSTROM push button block has to be equipped with a load output See also the following summary digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 83 132 Action Push button input LED display light Prepare Start Start configuration short short long LJILIL 4 fights dx lashing Dimmer configuration Es hmp Push button configuration Device push button ee e Area push button 4 4x flashing x
45. M Configurator for future configuration tasks However these tasks may only be performed with the pertinent product know how Installation manual as an online help This installation manual is integrated as online help into the web based user interface of the digitalSTROM Configurator in the Help main section As an online help the electronic format features additional functions such as full text search index etc and is constantly updated with the system updates You can download the latest version of the installation manual and also find additional useful support information at http www aizo com downl oads Conventions The following conventions are used in this installation manual Push buttons commands The names of push buttons commands are shown in bold and cursive fonts e g Call up Parameters Parameters are shown in inverted commas before and after cursive and bold e g Date Higher level activities The names of system functions are marked by the characters and and in bold e g Leaving home digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 6 132 1 5 digitalSTROM glossary Abbreviation Term Description digitalSTROM Device A device lamp push button washing machine etc which is connected to the 230 V mains and which can be controlled via digitalS TROM digital STROM Meter One digitalSTROM Meter is required for each power circuit It communicates
46. M Server Login to the digitalSTROM Server requires entering a user name and password in the login dialogue Depending on your browser settings a safety warning appears while a safe connection is being established to the digitalSTROM Server https Acknowledge the message with Continue loading this website to reach the dialogue Enter user name and password in the automatically opened dialogue box Login dialogue Authentication Required EJ P A username and password are being requested by https 7 192 168 8 118 The site says dSS11 User Name dssadmin Password eeeeeeee OK Cancel The factory settings for the digitalSTROM Server administrator password are User name dssadmin Password dssadmin The administrator password can be changed later in the web based digitalSTROM Configurator at any time See also chapter 5 2 6 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 31 132 4 6 Remote access via the Internet The digitalSTROM installation can also be conveniently operated via the Internet To do so the digitalSTROM Server must be connected with the personal mein digitalSTROM user account of the resident This is accomplished with the help of the digitalSTROM Server app mein digitalSTROM with the same name To connect the digitalSTROM Server with the mein digitalSTROM user account proceed as follows In the main section Apps check whether the digital STRO
47. M Server app mein digitalSTROM is installed on the digital STROM Server If itis not install it See also chapter 6 1 Open the digitalSTROM Server app mein digitalSTROM Follow the instruction steps within the digitalSTROM Server app to open a user account under www digitalstrom com and to connect the digitalSTROM Server with the mein digitalSTROM user account i Then the following functions are available to the user registered to digitalSTROM com in the area mein digital STROM Direct access to the digitalSTROM Configurator Issue a time restricted access authorisation to the digitalSTROM Configurator for third parties Sending of a temporarily active link Access to the weekly data backup automatically generated under the user account The backup contains the data and configurations in the connected digital STROM Server Acquisition configuration of applications free and at cost such as weather dependent Services After the digitalSTROM Server has been connected with the mein digitalSTROM user account the login information valid for the user account can also be used in the digital STROM App for Smartphones or tablets Thereby the communication between the digitalSTROM App and the connected digitalSTROM Server is automatically configured via the mein digitalSTROM user account Thus the digital STROM installation can be conveniently and centrally operated from anywhere digitalSTROM Installation Manual A1121D002VO10EN
48. Open Close for shade light The push button inputs 1 and 2 are used for the operation of a 2 way push button The Open Close push button is connected to push button input 1 Push button input 2 is automatically linked to push button input 1 The configuration of the 2 way push button is accomplished on push button input 1 The push button inputs 3 and 4 are used for the operation of a 2 way push button Here the Open Close push button is connected to push button input 3 Push button input 4 is automatically linked to push button input 3 The configuration of the 2 way push button is accomplished on push button input 3 Here the linked inputs 2 respectively 4 are not listed in the device list 2 way Close Off for shade light The push button inputs 1 and 2 are used for the operation of a 2 way push button Here the Close Off push button is connected to push button input 1 Push button input 2 is automatically linked to push button input 1 The configuration of the 2 way push button is accomplished on push button input 1 The push button inputs 3 and 4 are used for the operation of a 2 way push button Here the Close Off push button is connected to push button input 3 Push button input 4 is automatically linked to push button input 3 The configuration of the 2 way push button is accomplished on push button input 3 Here the linked inputs 2 or 4 respectively are not listed in the device list digitalSTROM Installation Ma
49. Preset 1 Light on Save 2 Refresh View Basic View E 33 132 A Navigation main sections Click on the particular main section tab to navigate between the main sections Use Advanced view and Basic vewin the lower right corner to toggle between the two views Advanced View Basic View In the advanced view additional main sections are shown in the navigation Default view Apps Activities Rooms Help Apps digitalSTROM Server apps For the installation and update of applications apps on the digitalSTROM Server Activities For the configuration of presets and activities Rooms For the administration of rooms and related digitalSTROM Devices Help For the use of the electronic online help Advanced view Apps Activities Rooms Groups System Hardware Help In the advanced view additional main sections are shown for navigation Groups For management of groups and corresponding digitalSTROM Devices System For the configuration of system settings such as network identification time date etc Hardware For the monitoring and configuration of digitalSTROM Devices in the electrical power circuits B Selection view B1 Tool bar selection view In the selection view tool bar you can see the title of the selected main section and the valid commands for the associated items in the form of icons Rooms j ou fra g g po A 29 E g add room rename room In order to run a command for the list ite
50. STROM Devices which can be configured for the activities or presets Please note that activity preset specific device settings may differ from the general device settings in the Hardware main section Embedded dialogue The embedded dialogue allows the device value of the digitalSTROM Device to be changed quickly and conveniently in the device list Inthe selection list choose the preset for which you want to change the device values Use Select next previous device or select the device directly from the list to set all devices in the room for the desired preset Use Saveor Save in other presetto save the current device values in the desired preset with one click digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 112 132 When a preset is selected the current device value of the first device in the device list is read and after a short time about 2 seconds is displayed in the embedded dialogue In the following please note the different labels and additional control elements for digital STROM Devices of the grey application area Shade Value 0 O Max Min y Example embedded dialogue for digitalSTROM terminal block Light yellow Value The current device value 0 100 can then be changed by using the slider or by entering the value directly In addition the device value can be changed by using ncrease value and Decrease value in 5 increments For the digit
51. Shade Device Properties Allows adjustment of the properties of digital STROM relay terminal blocks used for the control of motorised shutters blinds or awnings The values for Motion time open close and Motion time close open as well as the Direction of travel are detected during the calibration F Device Properties shade x Device Name Blinds Living room Device ID 00016ba0 Motion Time Open Close 30 00 S Motion Time Close Open 30 00 z Turn Time Fins 0 95 Direction of travel default v Protect calibration values Calibrate motion time and direction Start Calibrate turn time Start Reset Show Advanced Properties v Save Cancel The example shows the Shade device properties for the digitalSTROM relay terminal block Shutter GR KL200 grey Comment on the handling and interpretation of properties for different shading systems Shading system Motion commands Position in Off preset Shutters Usually operated via 2 way push button Motion time open close Motion time to lower shutter Motion time close open Motion time to raise shutter Shutters are used as screens or as weather and burglar protection In the factory settings of the digitalSTROM relay terminal block Shutters grey the shutters are closed shut in the Off preset Blinds Usually operated via 2 way push button Motion time open close Motion time to lower blind Motion time close open Motion time to raise blind Blinds are used as screens or as w
52. TROM Server app on the digitalSTROM Server 8 Terms of use Before the digitalSTROM Server app can be installed on the digitalSTROM Server the user has to agree to the aizo AG terms of use Disclaimer x Terms of Use March 21 2011 By using the website s made available under http dsapps aizo com hereinafter the Website or the Websites you are accepting these Terms of Use If you do not agree with anything in these Terms of Use you should not use the Websites The Websites are operated by aizo AG Brandstrasse 33 CH 8952 Schlieren hereinafter referred to as aizo or We Us etc You as the user of the Websites will be referred to hereinafter as You or the User Through the Website You will find applications You can download and use hereinafter referred to as dSS Extensions or dS Apps By downloading a dS App You declare to be bound by these Website Terms of Use Also by downloading a dS App You declare to be bound by the license terms applicable to the respective dS App w Except where explicitly stated otherwise the license applicable to the ds Apps is the Creative Commons License Attribution ShareAlike 2 5 Generic CC BY SA 2 5 The full text for this license is accessible here http creativecommons org licenses by sa 2 5ilegalcode 1 Copyright All intellectual property rights in relation to the Websites are reserved Rights in dS Apps are held by third par
53. TROM com 54 132 Insert the USB flash drive in the USB socket on the housing of the running digitalSTROM Server The system update will start automatically and is indicated by a blinking yellow blue LED It can take up to 2 minutes before the LED starts blinking Also the LED may briefly remain blue or yellow during the update If the LED shines green continuously for 2 minutes the update was completed successfully During a system update via USB flash drive any available firmware updates are automatically installed on the connected digitalSTROM Meters During a system update via USB flash drive all installed server apps are also automatically updated All newly available digital STROM Server apps are also included in a software update copied to the USB flash drive After the completed system update new digitalSTROM Server apps can be installed from the USB flash drive in the Apps main section See also chapter 6 2 Check for available firmware updates for digitalSTROM Meters in the system settings of the web based digitalSTROM Configurator after completed system update or the installation of additional digitalSTROM components Refer to chapter 5 2 8 1 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 OdigitalSTROM com 55 132 5 2 9System properties Property Tree 3434ss 3 amp 3 system j uptime 383 aversion aC Eventinterpreter aC security a language 4 host ajs 3 amp 3 config datadirectory
54. The area push button basically switches dims with Zx click digitalSTROM Devices belonging to the same area in a room All other devices in the room are not affected Area 2 as Area 1 Area 2 Area 3 Area 4 Use the drop down menu to select the desired area to be switched on with 2x click A maximum of 4 areas are available in each room If a digitalSTROM push button block is configured as area push button the main section Activities will show the associated preset e g Area 1 On If the preset for an area is saved e g Area 1 On the digitalSTROM Devices switched on at this time device value gt 0 will automatically make up the corresponding area See also chapter 5 5 2 With 2x 3x 4x click on the area push button additional presets can be called up for the room Room push button The room push button basically switches dims all digitalSTROM Devices belonging to a room With 1x 2x 3x and 4x click you can call up different presets for the room This corresponds to the factory settings of the digitalSTROM push button block digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 69 132 Information for digitalSTROM Devices with push button inputs in groups If a digitalSTROM push button block is allocated to a group the name of the group is automatically allocated in the properties dialogue and displayed with the group name and the addition Group 2 Device Properties x Device Name Button
55. The maximum current for the digitalSTROM Meter is 16 A digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 18 132 Installing and Install the 24 V DC power supply unit for the digitalSTROM connecting the power Server according to the installation instructions on the top hat supply unit option rail and connect it electrically The used power supply unit must have a rated voltage of 24 V DC 10 and a minimum current of 0 4 A Country Specific regulations must be complied with during assembly and wiring of the power supply unit 4 Installing and Install the digitalSTROM Server according to the installation connecting the instructions on the top hat rail and connect it electrically digital STROM Server option Make sure the 24 V DC supply to the digitalSTROM Server has the correct polarity 5 Connecting the Connect the Ethernet interface to a local network router Ethernet interface option 6 Connecting the dS485 Wire the bus interconnection between the digitalSTROM Meters bus cable according to the installation instructions If a digital STROM Server was installed connect the digitalSTROM Server with the bus cable according to the installation instructions Make sure the connection terminals for the bus interconnection have the correct polarity A twisted pair cable with a cross section of 0 8 mm is to be used for the dS485 bus interconnection A maximum of one digitalSTROM Server may be conn
56. able Device ID 000044a7 Value 100 Max a Increase value 3 Decrease value Min q p Close Select next device Select previous device Example digitalSTROM terminal block for lighting digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 102 132 Value The current device value 0 100 can then be changed by using the slider or by entering the value directly In addition the device value can be changed by using ncrease value and Decrease value in 5 increments For the digitalSTROM relay terminal block Shade grey each actuation of ncrease value Decrease value will execute a small motion step Changing the device value in the dialogue will lead directly to a changed output value of the digitalSTROM Device Minwill set the current device value to 0 Maxwill set the current device value to 100 With Se ect previous device and Se ect next device you navigate directly to the next or previous digitalSTROM Device in the list Use this dialogue to test the connected digitalSTROM Devices or to set the device values of all digitalSTROM Devices in a room before saving them in an activity preset Please note the different label and additional control elements which are used in this dialogue for the digitalSTROM relay terminal blocks grey Shade e Device Settings x Device Name Blinds Living room Device ID 00016ba0 Position Set Blade Angle 0 i P Close Example fo
57. actory settings and can be used as needed See also chapter Controlling different devices with the touch of a button in the dSS Apps section of the user manual If the digitalSTROM push button block joker black input is configured for the joker black application area the push button is automatically used as app push button If one of the push buttons on the line switch GE SD200 is used as joker button and configured for the joker black application area the joker push button will also be automatically operated as app push button See the following description for the configuration of the push button function for the digitalSTROM push button block joker black and the line switch GE SDS200 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 OdigitalSTROM com 71 132 Function For digitalSTROM push button block joker black Determines the functionality of the push button inputs 1 and 3 for the digitalSTROM push button block joker black only for digitalSTROM push button block with 4 universal inputs If the push button inputs 1 or 3 respectively are configured as 2 way push buttons they will also determine the functions of push button inputs 2 or respectively 4 1 way The push button inputs 1 and 2 are operated as separate single push button inputs The push button inputs 3 and 4 are operated as separate single push button inputs Hereby all push button blocks are shown in the device list 2 way
58. alS TROM components The installation of firmware updates can be started manually by the user at any time with Install dSM Firmware update After a system update the default device values in the connected digitalSTROM Devices are updated for new activities During this process the presets affected by the update cannot be saved Therefore the user is informed of the update progress through messages in the status bar If the user attempts to save an affected preset in the digitalSTROM Configurator during the update the temporary restriction will also be pointed out by an additional dialogue 9 Update dSM Firmware Installs available updates on the digitalSTROM Meter The implementation of an Update does not affect the configuration of the installation 3 Release Information Opens a dialogue with detailed Release Information on the installed version of the digital STROM Server application firmware of the digitalSTROM Server digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 53 132 Release notes x Software Release Notes dSS V1 6 0 The Software Release Notes SRN describe software changes to existing Aizo products which can be updated by the customer u Document Number SRN 2012 07 Version v1 0 Affected Products Product digitalSTROM Server d5511 Software Description dSS Version Latest Version 1 6 0 Product digitalSTROM Meter dSM11 Software Description ARM Software Version L
59. alSTROM relay terminal block Shade grey each actuation of ncrease value Decrease value will execute a small motion step Changing the device value in the dialogue will lead directly to a changed output value of the digitalSTROM Device Minwill set the current device value to 0 Maxwill set the current device value to 100 With Select previous device and Select next device you navigate directly to the next or previous digitalSTROM Device in the list digitalSTROM relay terminal block Shade Please note the different label and additional control elements which are used in this dialogue for the digitalSTROM relay terminal block Shade Position 100 Up Stop Down Set Blade Angle 100 Example embedded dialogue for digital STROM relay terminal block Shade grey digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 113 132 Position The setting of the device value is interpreted by the digitalSTROM relay terminal block as position For this purpose the digitalSTROM relay terminal block must be calibrated appropriately after installation See also chapter 5 3 4 Use Stop to stop the motion of a shading system e g if Qoen or Close was previously used to travel to the end position Only for digitalSTROM relay terminal blocks Shade grey With Open the movement command to fully open the shutters or extend the awning can be started Only for digitalSTROM relay terminal blocks Shade grey
60. and a light push button is held for 3 s The activity Deep off can also be triggered at any time by 4 short clicks on the Off push button of the 2 way light push button e g on the 2 way line switch For example this allows you to completely turn off a TV which is connected to a digitalS TROM inline adapter digitalSTROM Devices switched off by the activity Deep off are switched on again if e Apush button of the same colour group is actuated in the room Does not apply to digitalSTROM Devices in colour group joker black e A corresponding preset or user defined action is called up by a digitalSTROM Server app e g using a timer switch a digitalSTROM push button joker configured as app push button or a responder via Event Responder Sleeping This activity can only be triggered by a digitalSTROM Server app e g timed events This activity is used to put all digitalSTROM capable devices in a room in a defined night time operating condition You can use it to switch off a WLAN router connected to a digitalS TROM inline adapter for example Waking up This activity can only be triggered by a digitalS TROM Server app e g timed events You can use it to switch the WLAN router on again in the morning for example digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 107 132 Higher level activities for the whole installation l Leaving Home Coming Home Door Bell gt Rain
61. and firmware updates in the web based digital STROM Configurator The digitalSTROM Server must be connected to the Internet online for this purpose digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 52 132 List of all available system updates Search for updates Updated list of all system updates made available online by digitalSTROM At the same time the digitalSTROM Server checks if updates are available for connected digitalSTROM Meters and presents available updates in an information box if needed 9 Update system Installs the available system updates and saves available firmware updates for digitalSTROM Meters in the digitalSTROM Server memory Afterwards the firmware updates for the connected digitalSTROM Meters are automatically installed Depending on the scope of the system updates the digitalSTROM Server will restart automatically after the update The web based user interface is briefly unavailable during this process As soon as the system is available again the browser will automatically reload the System Update section in the System main section Automatic firmware updates for digitalSTROM Meters are available from digitalSTROM Server version 1 6 0 For earlier versions the firmware update must be started manually after the system update However we generally recommend to check the firmware of connected digitalSTROM Meters after system updates and the installation of additional digit
62. anges to C blue Now you can release the LED push button to restart the digitalSTROM Server On the digitalS TROM Meter a successful restart is indicated after 5 seconds by a changing colour pattern Resetting the digitalSTROM Server n order to reset the digitalSTROM Server the LED push button must be pressed continuously for 15 seconds This will reset the administrator password the system name and the network settings to factory settings After 15 seconds the LED status indicator starts to blink in blue Now you can release the LED O push button to set the administrator password and the system name to factory settings and the network setting to DHCP digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 26 132 4 3 1 digitalSTROM Meter LED status indicator The LED status indicator colour indicates the operating condition of the digitalSTROM Meter Standard operation green C Initialising dS485 bus interconnection grey C Configuration error the digitalSTROM Meter must be replaced magenta Hardware error red Additional information during standard operation Simple brief blinking Events are indicated by the LED status indicator blinking once and changing its colour Colours are assigned to the different operating conditions Push button telegram received from a digital STROM Device black LED dark New digitalSTROM Device identified blue 2 digitalSTROM Device suc
63. atest Version 1 11 0 0 Software Description DSP Software Version Latest Version 1 2 2 0 installation Notes A software update needs to be executed in the digitalSTROM configurator within System System Close 5 2 8 2 Provide system update from USB flash drive offline If the digitalSTROM Server is not connected to the Internet available system updates may also be provided by a USB flash drive offline Use a browser to open the software update download site http www aizo com updates Download the available update in a compressed file ZIP format on your computer Unpack the file on your hard drive and copy the directory dss11 usb upgrade to the main directory root of the USB flash drive used for the system update At least 1 gigabyte free storage space must be available on the USB flash drive The digitalSTROM Server supports the Windows file system Therefore the data carrier need not be specially formatted or empty However the unpacked data must be available in the main directory root directory and not be saved in a sub folder PI EA Removable Device E Home Share View T amp gt Computer Removable Device E v amp r Favorites Name Date modified dSS11 usb upgrade 1 14 2013 3 15 PM d Libraries e Homegroup JE Computer i Local Disk C Removable Device E Ci Network item 1 item selected digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalS
64. ation is simple and quick It requires the installation of digitalSTROM Meters and an optional digitalS TROM Server in the distribution board These components form as it were the collective brain of the digitalS TROM installation The existing light switches are replaced with standard push buttons and equipped with digitalSTROM push button blocks The required digital STROM Devices e g digitalSTROM terminal block in ceiling light are installed in the supply lines to the consumers After installing the digitalSTROM push buttons and the digitalSTROM push button blocks the digitalSTROM installation is ready for operation Other digitalSTROM Devices may be added to installation at any time The basic configuration of the digitalSTROM installation and the configuration of presets e g lighting presets can be performed without a digitalSTROM Server Here the configuration is accomplished via click commands at the light push button The corresponding documentation to configure presets via click commands can be found in the Setup section of the digital STROM user manual A complete configuration of the digital STROM installation and the implementation of specific customer demands can be performed conveniently in the web based digitalSTROM Configurator The digitalSTROM Configurator is part of the optional digital STROM Server digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 13 132 3 1 Safety notes
65. be set before connecting the digitalSTROM relay terminal block 230 VAC dSM ere meerneeeemenese 8mm 0 75 1 5 mm l L E GRKL200 I LP LT Arep a Motor 230 V __ M y K1 AAN max L DO 0 5 Nm M The direction of rotation is taughtin The local push button is an OPTION When 3mm later and does not need to be taken into controlling the terminal block via digitalSTROM account during connection the push button is not required Control of a standard tubular motor for shutters via digitalSTROM relay terminal block digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 20 132 If the direction of rotation of the drive system does not match the Open and Closed direction of travel it can be changed during calibration of the digitalSTROM relay terminal block by using the web based digitalSTROM Configurator See also chapter 5 3 4 digitalSTROM push button block with 1 input Install the digitalSTROM push button block with 1 input according to the installation instructions e g digital STROM push button block GE TKM210 Lighting yellow with one push button input If a neutral conductor and sufficient space are available the digital STROM push button block is installed in the switch box Alternatively you can also install it in a junction box if a push button wire Is available 16A BdM PRAbd i
66. button in the exterior area should not automatically trigger Coming home during absence digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 OdigitalSTROM com 75 132 Ge Editing device properties For digitalSTROM automation terminal blocks SW AKM 210 Device Properties x Device Name Wind monitor Device ID 00094903 Sensor function Wind monitor v Input standard v A A Turn on delay 1 O y mmiss A Ar Turn off delay 1 0 y mmiss Cancel Example digitalSTROM automation terminal blocks for a connected wind monitor Due to the set function of the connected sensor pre defined switching sensor messages which can be used e g in the digitalSTROM Server app Event Responder to trigger other activities are sent off by the digitalSTROM automation terminal block The sensor messages for wind rain and smoke fire are processed as higher level activities within the entire digitalSTROM system See also chapter 5 5 2 Delay values can be defined for the sensor signal on order to debounce the quick acting signals The switching thresholds for the switching signal itself e g wind strength or amount of rain are set at the connected sensor When making these settings please refer to the product information of the sensor manufacturer Sensor function Specific function operating mode of the connected sensor on off App mode Available application possibility The switching sensor messages for co
67. can be controlled independent of the electrical power circuit and the architectural floor plan and be freely allocated For each electrical power circuit or respectively per digitalSTROM Meter up to 16 rooms can be covered Once the digitalSTROM Devices have been configured and allocated to a room e g reading corner or dining table you can save for this room specific activities presets e g lighting presets for reading or dining which can be called up with light push buttons Depending on the function of the digitalSTROM push button block presets can be called up for a device connected directly to the output device push button an area in a room area push button or for the whole room room push button Unless you have already renamed your digitalSTROM Devices in the Hardware main section you should allocate a unique name to each of them now based on the previously noted dSID This facilitates the subsequent configuration of digitalSTROM Devices and presets By default one room is created for each digital STROM Meter during installation This room should be renamed first and used as room with most digitalSTROM Devices digital STROM Devices later added physically to the system and registered are allocated by default to this room Create additional rooms and give them explanatory unique names Allocate digitalSTROM Devices to the created rooms by Drag amp Drop If all digital STROM Devices in the room belong to an already exis
68. ce ae 7 English v The following languages are available German English French Francais Dutch Nederlands Turkish Turkce digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 39 132 5 2 Check basic server configuration Following the initial digitalSTROM Server operation the basic configurations must be checked before you can start configuring the digitalSTROM Devices rooms presets and activities In Advanced view navigate to the main section System Check the network settings Check the system settings device names date and time etc Change the administrator password as necessary Check if system updates for the digitalSTROM Server or the digitalSTROM Meters are available and install them 5 2 System overview Apps Activities Rooms Groups System Hardware Help Menu Overview Overview m _ General information Registration Network Settings dS 11 image version s2013 0 test03 d S11 web setup version dss11 websetup 0 36 1 gitr744 f8e 7608 r1 system Settings dSS web module version dss web module 1 16 1 gitr1060 b163eff r1 Mail Settings Installed dSS package dss 1 21 0 gitr2623 58ee99e 11 89 Uptime 15 27 15 up 1 day 1 33 load average 0 15 0 28 0 33 Last login reboot system boot 3 0 17 Wed Apr 24 13 52 15 27 1 01 34 Password IP address 192 168 0 81 MAC A8 99 5C 00 03 17 Access Authorization System Maintenanc
69. cessfully registered cyan o Unable to register digitalSTROM Device red O Registration cycle of the digitalSTROM Device is concluded yellow Hardware error A hardware error is basically signalled by the colour red In addition additional information about the type of hardware error is determined by means of different blink frequencies and colours Critical temperature blinking red yellow Communication was deactivated The error message won t disappear before the temperature has dropped below the critical value The digitalSTROM Meter should be switched off to cool down and switched on again later The connected load should be checked Check the digitalSTROM Meter assembly if the error recurs See chapter 3 3 step 2 Hardware error 2 slow blinking red black LED dark A hardware or CPU error has been detected Turn the digital STROM Meter off and on again Replace the digitalSTROM Meter if the error recurs after restart Software updates System update 2 blinking red blue Do not switch the digitalSTROM Meter off digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 27 132 4 3 2 digitalSTROM Server LED status indicator The LED status indicator colour indicates the operating condition of the digital STROM Server C Standard operation green Hardware or software error red C Turn the digital STROM Server off and on again Replace the digitalSTROM Server if the err
70. cheme The application possibilities of digitalSTROM are very varied To make orientation easier for the planners electricians etc and to make their work as uncomplicated as possible the digitalSTROM Devices are classified into different colour groups Each colour group stands for a specific field of application This colour scheme is continued through to the housing colours of the digitalSTROM terminal blocks Colour Group Examples Yellow po Light Ceiling wall and floor standing lamps Grey shade Blinds shutters privacy protection Blue Air Condition Heating ventilation air conditioning Cyan a Audio Radio CD player Magenta ee Video TV projector DVD player Red ea Security Protection functions fire and burglar alarms Green bP Access Doorbell door opener Black ae Joker Can be used at will Comments on joker black The joker black area of application is a universal terminal block that allows digitalSTROM Devices to be reconfigured to any other digitalSTROM colour e g yellow for Light To make full use of the many possibilities of the digitalSTROM colour concept the colour group should always be adapted to the use of the connected consumer If a digitalSTROM Device is configured for the joker black area of application the digital STROM Device will only respond to higher level activities such as Leaving home or Deep Off If a digitalSTROM push button block joker black is configured for the joker black
71. cumentation on the configuration of presets via click commands Note on areas A digitalSTROM push button configured as area push button basically switches dims with 1x click digitalSTROM Devices belonging to the same area in a room All other devices in the room are not affected See also chapter 5 3 2 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 106 132 Higher level activities for the room li SILO IUU y i Deep off 4 Sleeping J Wake Up eee ad These activities apply to all digitalS TROM Devices assigned to the room Independent of the application area e g light or shade Standby The activity Standby can be triggered for a room when all lights are in the switched off state preset area or device off and a light push button is held for 2 s The activity Standby can also be triggered at any time by 3 short clicks on the Off push button of the 2 way light push button e g on the 2 way line switch Therefore even digitalSTROM Devices with other colours e g magenta for video can be switched off with all push buttons independent of the application area For example you can use the Wipe mode of the room push button to switch off the TV and put it into its own standby mode after turning off the room lighting See also chapter 5 3 2 Deep off The activity Deep off can be triggered for a room when all lights are in the switched off state preset area or device off
72. d to either react to this activity or to ignore it Normally a digitalSTROM terminal block can be set to blinking to also indicate the ringing visually Panic The actuation of a digitalSTROM push button configured as Panic push button issues the command Panic to all digitalSTROM Devices Each digitalSTROM terminal block can be configured so that it either responds to the activity or ignores it In the factory settings of the digitalSTROM terminal block for the activity Panic all lamps go on and the Shutters blinds are opened digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 108 132 Wind Am external wind monitor can protect e g a shade system from damage The wind monitor Signals that a defined wind speed has been exceeded However activities of digital STROM Devices which can trigger a higher level activity e g digitalSTROM automation terminal blocks for wind and rain are only processed within a group which the digitalSTROM Device Is allocated to Refer to the application examples in chapter 5 6 Rain An external rain monitor reports the onset of rain or hail to the digitalSTROM System With it e g shade systems can be retracted or skylights closed Hail Based on weather data external service providers generate weather warnings which prevent potential damage events Thus online weather services can report e g the onset of hail to the digital STROM System With it e g
73. digitalSTROM Meters b Define names of digitalSTROM Devices c Configure device properties for digitalSTROM Devices e g switch dim digitalSTROM terminal block d Define names of rooms e If required add rooms f Assign digitalSTROM Devices to rooms 5 Verifying basic configuration a Verify function in every room on site 6 Configuring presets a Define presets e g lighting presets by push button or digitalSTROM Server b Configure activities e g lamp blinks during Ringing 7 Additional functions of the digitalSTROM Server a Install and configure digitalSTROM Server apps b Point out digitalSTROM App for smartphones iPhone and Android smartphones to customers digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 125 132 8 Checking a Check presets b Check activities c Check function of apps d Check communication reliability Switch on all consumers in the power circuit for this purpose 9 Delivery to customer a Usecheck list in section Introduction of the digitalSTROM user manual digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 OdigitalSTROM com 126 132 8 Help Apps Activities Rooms Groups System Hardware Help digitalSTROM Manual Overview usage setup www aizo com downloads Install installation manual FAQ and support www aizo com support Overview operation settings You can find additional information on the ope
74. ding automation the Internet or a local network Installing the digitalSTROM Server is optional In order to optimise the network conditions for digitalSTROM communication digital STROM Filters are installed for network conditioning digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 10 132 2 2 Design and functionality E Boa fe Pe fe r 7 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Connection to the RJ 45 network Typical connection pattern in the distribution board Minimally required components The smallest unit of a digitalSTROM system is composed of the following components e g for the Light group digitalSTROM Filter in the distribution board Function network conditioning digitalSTROM Meter in the distribution board Function communication and energy metering digitalSTROM push button block e g GE TKM210 in flush mounted box Function recording push button actuation digitalSTROM terminal block e g GE KM200 in ceiling diffuser Function illuminant switching or dimming Installation in the room Distribution board wTTTTTTIrTTTTrTtrr te E digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 11 132 Upgradability A digitalSTROM installation can be upgraded at will In addition to the use of additional digitalSTROM Meters with a digitalSTROM Server complex functionalities can also be realised Additional featur
75. e Logging System Update Property Tree In the main section System you can check and adapt the basic digitalSTROM Server configurations The overview shows general information on the digitalSTROM Server installation This information is not described here in detail but may be useful for problem analysis in the event of a support case digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 40 132 5 2 2 Configuring the network Select the operating mode of the network settings for the digitalSTROM Server Warning Changing settings on this page can make the dSS11 unreachable Static IP address configuration Please configure your network settings manually IP Address 192 168 0 81 Netmask 255 255 255 0 Gateway 192 168 0 1 DNS1 81 221 250 10 DNS2 81 221 252 10 MAC A8 99 5C 00 03 17 Apply Cancel Automatic IP setup with DHCP factory setting According to factory settings the digitalSTROM Server selects the IP address automatically by dynamic allocation DHCP In addition other settings such as net mask gateway etc are automatically set up with the connected router or Windows PC Static IP configuration All settings required for operation must be entered manually in the entry mask In case of manual network settings please note that a faulty configuration may render the digitalSTROM Servers inaccessible IP address Currently valid IP address of the digitalSTROM Server
76. e Properties Read Device Name TV light Device ID 00004c39 Output Mode dimmed Settings Advanced Settings LED mode auto off Transition Time standard slow 4 y Close LED mode Determines the display mode of the LED in the housing of the digital STROM Device This setting is only displayed if the selected digitalSTROM Device is equipped with an LED Auto The brightness of the LED corresponds to the current device value of the power output and is adjusted during dimming If the activity Deep Off is called up the LED goes dark If the output is deactivated the LED will glow weakly Off The LED stays permanently dark Transition time to call up Determines for the selected activity preset the speed of preset transitions for dimmed devices Default The device value for the activity preset will be reached within 400 ms Slow The device value for the activity preset will be reached within 60 ms i Rename device Opens the dialogue for renaming a digitalSTROM Device Rename Device x Device ID 00004456 ui Device Name Ceiling light Kitchen Clase With Select previous device and Select next device you navigate directly to the next or previous digitalSTROM Device in the list digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 118 132 5 6 Creating groups and allocating devices With groups digitalSTROM Devices can be operated within the
77. e and time 9 January 2013 11 38 CET Time zone Europe London agi Synchronize date and time over the network Date 09 01 2013 3 Time 19 01 00 x Apply Date and Time Current date and time settings on the digitalSTROM Server v 09 01 2013 E 17 20 00 A January 2013 rh S MTWMHTerF S 17 45 00 t a a oe 18 00 00 6 7 s g9 10 11 12 18 15 00 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 USS or Id only Today Use the calendar and the drop down menu to configure the date and the time manually digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 44 132 If the digital STROM Server is disconnected from the power supply the manually specified values for date and time remain stored in the battery powered clock 5 2 3 4 Apartment basis address Apartment base address The apartment base address defines the first address ofthe dSS or dSMs in a digitalSTROM installation The base address should only be changed if you discover problems that are related to a neighboring installation Base address 56 Apply Used range the addresses 56 58 are currently used by installed devices dSS dSM The possible range is 0 59 Basis address The unique identifier for the installation is allocated randomly at first start of the digitalSTROM Server and can be changed later The basis address assists as additional addressing in preventing overlapping effects of systems
78. e time zone has to be specified manually See also chapter 5 2 3 3 digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 43 132 5 2 3 3 Date and time system time Synchronising date and time with the network Date and time settings Current date and time 25 April 2013 15 26 CEST Time zone Europe Zurich Synchronize date and time over the network Additional NTP server optional Apply Time zone Standard time zone according to UTC GMT Use the drop down menu to select the time zone The time zone is automatically set if a country and a locality are chosen in the Location system setting See also chapter 5 2 3 2 Unless country and locality are specified in the Location system setting the time zone has to be Specified manually If the time zone is set correctly the changeover from daylight saving to standard time takes place automatically Synchronising date and time with the network synchronizer Automatic synchronisation of date and time with the configured NTP server factory setting A permanent Internet connection is required for this purpose Additional NTP server An additional NTP server can optionally be configured for the automatic synchronisation Without specification of an additional NTP server the values in the digitalSTROM Server are synchronised with the NTP sever from digitalSTROM Specifying date and time manually Date and time settings Current dat
79. eather and sometimes as burglar protection In addition to their position you can also control the angle of the blinds Blinds are also known as slat blinds In the factory settings of the digitalSTROM relay terminal block Blinds grey the blinds are closed shut in the Off preset Awning Usually operated via 1 way push buttons Motion time open close Motion time to retract awning Motion time close open Motion time to extend blinds Typically awnings are shading systems made of fabric For this reason they are usually retracted during bad weather or absence In the factory settings of the digitalSTROM relay terminal block Awning grey the awnings are retracted in the Off preset digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 79 132 Motion time open close Time the shading system needs to travel from the opened extended end position to the closed retracted end position Motion time close open Time the shading system needs to travel from the closed retracted end position to the opened extended end position Turn Time Blades Time a blind needs to open or close its blades Only active for blinds Direction of travel Determines the direction of travel of the connected motor The direction of travel for the motion commands Open Close can be reversed depending on the shading system or manufacturer Default Default direction of travel open close Reverse Reversed directi
80. ecte ej 5 Floor lamp Cg Ah 2 Leave Ho 00005852 switched Leaving Coming Home ee Doorbell 0000582c switched Door Bell a a ie erent a ea ne ae w cea Use Drag amp Dropto allocate digitalSTROM Devices to another room For this purpose you select a digitalSTROM Device in the device list and drag it while holding the left mouse button pressed to the desired room in the selection list n order to move several digitalSTROM Devices at the same time select the digitalSTROM Devices with the mouse button while holding down Ctr or Shift If you want to move all digitalSTROM Devices in a room to another one make sure you select all the digitalSTROM Devices before dragging them to the new room This allows the system to address the digitalSTROM Devices in the best possible way If aroom contains a new or as yet unknown digitalSTROM Device the symbol appears in the selection list behind the room name Columns and columns w Blink device Makes the selected digitalSTROM Device blink amp Edit device value Opens the dialogue to edit the current device value of the selected digitalSTROM Device The current device value is read from the digitalSTROM Device as the dialogue opens and displayed briefly for about 2 seconds in the dialogue Please note the different labels and additional control elements for digital STROM Devices of the grey application area Shade CB Device Settings x Device Name Ceiling light Dining t
81. ected to the RS485 bus interconnection Terminating resistors Make sure that the enclosed terminating resistors are connected at both ends of the bus interconnection The installation instructions and additional information can be downloaded at http www aizo com support digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 19 132 3 4 Installations in the rooms Install the digitalSTROM components in the rooms according to the installation instructions for electricians digitalSTROM terminal blocks switching dimming 150 W Install the digitalSTROM terminal blocks according to the installation instructions e g digitalSTROM terminal blocks GE KM200 for ceiling lights A dSM Ph i 230 VAC t digitalSTROM 8 mm 0 75 1 5 gt LED 230V AC a _ MOK i 7 0 5 Nm H o 1 E a a ae i SS _ max 3 mm 7 size I A local push button input 1 is available at the terminal block so you have a direct optional control point for lighting control in the room This input is configured as device push button by default which sets the local priority for local operation You must use stranded wire only in conjunction with cable end sleeves digitalSTROM relay terminal blocks Install the digitalSTROM relay terminal blocks according to the installation instructions e g digitalSTROM relay terminal block GE KM200 for shutters Please note that the limit switches at the drive should
82. eesssseeeeees 78 LE eaten sales AEO PAOA 126 FA E 126 Manual xieveracoscncceauataaceccacaanecuseuceeceadacaaseatacancantease 126 Initial operation se sssssssssserrrssensrrrnnrsnnrrrrnnrsserrrrnne 24 Configuration with push button ceeeeees 24 LED status indicator sssssseserrrresererrrrreserrrrrns 25 Restart and reset cccccccsssssseeeeessssssseeeeeeeseees 25 E S a EE E 24 Install digitalS TROM Server sssssssessssssesserrrsserreenn 18 PASE GUGM urasna nahana aana aan iaiia 12 Configuration sheet ssssserssssersrrrnrssserrernnesne 14 digitalSTROM Filter ssssssssssensssnsserrnrssserrernnssne 17 digitalSTROM Meter sssssssssrnrsssesrrrnrssserrernnesne 17 Distribution board ssssessssssssserrrreserrrrrrreserrrrn 16 dS485 bus interconnection s ssssseerrssssererreesne 18 Ethernet interface sssssssssssserrrrrsssrrrrrnrsssrren 18 Power supply Unit ssssseessessssserrrrssnrerrrnreserrrn 18 ROOS oa EEEE 19 Safety information sssssserreessesrrrrrrssrrrrrnrsseerne 13 Work StepS sssssssssssssserrrnrsserrrrnnnnsrernnnnnnsserrnnnne 16 A1121D002V010EN 12 11 2013 digitalSTROM com L LOOM CIA OGUE cresen 30 O Operating mode SWEERING ccstscatercdetrtstudpcateeedsdadyaadenstecsdadatptadeeeteent 67 pP Push button function Area PUSA DURON oiin inda 68 Device push button ssssserrssserrrrrrressern 68 71 72 ROOM PUSN DULLON sninn ta 68 70 R PROTOS
83. eiling lights in area B1 dining table The other digitalSTROM Devices remain unaffected A digitalSTROM Device belongs to an area if it was switched on device value gt 0 while the corresponding preset was saved e g Area 1 On For configuration of an area push button see chapter 5 3 2 For the setup of the presets Area n On see chapter 5 5 2 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 94 132 5 4 3Push button function application examples This chapter describes typical application examples for the application area Light yellow The application examples can be applied in principle to other application areas Legend of used icons Icon digitalSTROM component O O XK Ae Terminal block e g GE KM 200 O a Push button block e g GE TKM 210 Device push button e g line switch GE SDM 200 In the application examples the configuration of the digitalSTROM push button block and the used presets Is listed in tabular form The Off preset for the room push button is not presented explicitly every time for reasons of legibility digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 95 132 Example 1 Additional presets due to additional room push button More than 4 presets are intended for one room Therefore an additional room push button is used to call up the additional presets See also chapter 5 3 2 Device push button 1 lel S Aw
84. elected activity preset Rename Preset x New name for preset OK Cancel i Activate A command is transmitted to all digital STROM Devices to call up the current device value for the selected activity preset in the digitalSTROM Device 1 Reset selected acti vity Use this command to reset digitalSTROM Devices to the last issued device value unless it was changed retroactively e g by actuating a room push button As a consequence you can e g after calling up the activity Panic directly restore the lighting preset without activating presets or resetting dimmer values Li Display all available presets All available presets for the room are displayed In the factory settings of the digitalSTROM Configurator only those presets are displayed which can be activated for the room with the available push button configuration If other presets are to be called up e g with the digitalSTROM Server app Event Responder you can display them by using Display all available presets and rename or configure them as needed digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 110 132 Note on motion commands and presets for shading systems Comment on the Off preset and the position of various digitalSTROM relay terminal blocks for Shading systems Shading system Motion commands Position in Off preset Shutters Usually operated via 2 way push button Shutters are used as screens or as weather and burglar protectio
85. elements for digital STROM Devices of the grey application area Shade CY Device Settings x Device Name Ceiling light Dining table Device ID 000044a7 Value 100 Max Increase value q Decrease value Min N p Close Select next device Select previous device Example digitalSTROM terminal block for lighting Value The current device value 0 100 can then be changed by using the slider or by entering the value directly In addition the device value can be changed by using ncrease value and Decrease value in 5 increments For the digitalSTROM relay terminal block Shade grey each actuation of ncrease value Decrease value will execute a small motion step Changing the device value in the dialogue will lead directly to a changed output value of the digitalSTROM Device Minwill set the current device value to 0 Maxwill set the current device value to 100 With Select previous device and Select next device you navigate directly to the next or previous digitalSTROM Device in the list Use this dialogue to test the connected digitalSTROM Devices or to set the device values of all digitalSTROM Devices in a room before saving them in an activity preset digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 65 132 Please note the different labels and additional control elements which are used in this dialogue for the digitalSTROM relay terminal blocks grey Shade
86. ences telegrams per connected digitalSTROM Device Average value Average reception quality for telegrams sent upstream and downstream during the test digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 58 132 Min Minimum reception quality for telegrams sent upstream and downstream during the test Max Maximum reception quality for telegrams sent upstream and downstream during the test Lost queries Total number of telegrams for which no responding telegram was received Use the Wew report button to view the test results Transmission quality report x digitalS TROM 1 Protocol of transmission quality n Overview Testtransmission quality of devices Test transmission quality for all devices on dSM 3504175fe000001000000501 using 1 checks per device Status Finished Started Tue Jan 8 10 09 17 CET 2013 Ended Tue Jan 8 10 09 42 CET 2013 summary Number of tested devices 12 Number of executed tests 12 Number oftests with errors 0 Average upstream quality 96 a Close Use Download report to save the test results in HTML format on your computer Check device presence Checks the presence of digitalSTROM Devices registered in the digitalSTROM Meter This test is used to update the device list digital STROM Devices registered with the digital STROM Meter which are physically not present are displayed as inactive grey The digitalSTROM Meter automatically tests the dev
87. er can be selected independent of the co our group The operating mode of the power output is shown in the device list in the Output column See also chapter 5 3 2 Powersave ai Switch Powersave Wipe Switching The connected device is controlled via a digital STROM push button with the same colour group In Preset 1 4and for Area on it is switched on for Preset off Leaving home and Deep Off the connected device is switched off This operating mode is used e g if you connect a lamp to the digital STROM Device and operate it with the colour group light yellow via a room push button Saving The connected device shall be automatically switched off during absence or at night to save energy In case of Leaving home Sleeping and Deep Off the connected device will be switched off Coming home or Waking up will switch it on again In addition the power output switches on if Presets 1 40or Area on of the same colour group e g for light yellow are called up If the Off presets are called up the output remains unchanged The power output of the digital STROM Devices in the colour group joker do not respond to presets 1 4 or Area n On Saving can therefore be applied to devices with high standby consumption e g TV and audio equipment or devices in permanent operation e g network routers During absence these devices will be automatically disconnected from the power supply digitalSTROM Insta
88. eriod of time after the end of the motion time while the motor is still Supplied with power by the digitalSTROM relay terminal block This ensures that the end position is reached in case of increased motion time e g caused by cold weather or dirty guide rails Threshold of end switch recognition The digitalSTROM relay terminal block monitors the load current If the load current drops below this threshold the reaching of the end position is detected It drops once the shading system runs up on the integrated limit switch During standard operation the threshold must not be set to less than 116 mA in factory settings the threshold is 232 mA If the value is set to less than 58 mA limit switch recognition is deactivated and the digitalSTROM relay terminal block switches off the load after the defined motion time Number of steps for fine tuning adjustment Number of motion steps for fine tuning adjustment Open Close push button pressed for long before continuous travel is started Set the value at 0 if continuous travel is meant to start directly Motion time for fine tuning adjustment Duration of motion steps for fine tuning adjustment Used to determine the distance or angle for slat blinds of individual motions for fine tuning adjustment 3 Configure Consumption Event Opens the dialogue for the configuration of the consumption event message of the selected digitalSTROM Device Note This function is only available f
89. es like timer power measurement control by iPhone etc can be implemented Detailed information can be found in the Operation section of the digital STROM user manual Functionality During start up the digitalSTROM Meter automatically registers all digitalSTROM Devices installed in the associated power circuit This allows the immediate use of all components after installation 60 W 60 W rra OD Q 230 VAC dSF GE KM GE KM Filter Push button Terminal Terminal terminal block block block lf for example a push button connected to a digitalSTROM push button block is pushed the digitalSTROM terminal block sends a telegram on the upstream communication with information about the type of actuation number of clicks to the digitalSTROM Meter Power measurement 120 W 60 W 60 W dSF dSM GE TKM GE KM GE KM Filter Meter Push button Terminal Terminal terminal block block block The digitalSTROM Meter will then send a telegram on the downstream communication to all digitalSTROM Devices registered in the power circuit The telegram contains the command to output the device values for the called preset in the digitalSTROM Devices e g to switch the power output to a predefined dimmer value It also measures the current performance in the connected power circuit digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 3 12 132 Installation Install
90. evice power output The value is only displayed if the digitalSTROM Device is equipped with a power output Input mode Device area or preset operated with the push button Inpu Assignment and function of the push button input on the digital STROM push button block The value is only displayed if the digitalSTROM push button block is equipped with several push button inputs Room name Name of the room to which the digitalSTROM Device Is assigned Room ID Unique identifier of the room to which the digitalSTROM Device is assigned HW Info Hardware specifications of the digitalSTROM Device Firmware version Firmware version of the digitalSTROM Device Registered on Time of registration of the digitalSTROM Device in the digitalSTROM Meter Inactive since Time at which the digitalSTROM Device was deactivated time at which it was removed from the digitalSTROM power circuit Comment Recorded comment for the digitalSTROM Device digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 64 132 Commands w Blink devices Makes the selected digitalSTROM Device blink Edit device value Opens the dialogue to edit the current device value of the selected digitalSTROM Device The current device value is read from the digitalSTROM Device as the dialogue opens and displayed briefly for about 2 seconds in the dialogue Please note the different labels and additional control
91. f selected digitalSTROM Devices are not to be operated in one area they have to be removed from that area Two procedures can be used to configure an area Procedure 1 Define the area by saving the device value in the embedded dialogue digitalSTROM Devices with a value greater than 0 are automatically allocated to the corresponding area Therefore use the embedded dialogue to change save the device values in the selected preset e g Area 1 On Todoso switch on an area of the corresponding digitalSTROM Device or open the Shading system Switch off a device not corresponding to the area or completely close the shading system Repeat this procedure for all digitalSTROM Devices in the selected area which you would like to control and then save the preset for Area n On Procedure 2 Directly add remove devices by command Select preset Area n On Directly add remove the selected digitalSTROM Device to the selected area by using the Add to Area Remove from Area command The device value is not changed by this Refer to the commands Ealt Device Value and Add Remove Area in the following documentation digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 115 132 Commands w Blink devices Makes the selected digitalSTROM Device blink wf Add to area Adds the digital STROM Device selected in the list of devices to the area selected in the list of activities This command is only available
92. g terminal block e g Wage type 224 112 GR TKM210 10 mm 0 75 mm The input assignment for the digitalSTROM push button block with 4 universal inputs joker universal can be adapted without changing the wiring The assignment can be freely configured in the digitalSTROM Configurator at any time See also chapter 5 3 2 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 22 132 digital STROM push button block with 4 universal inputs joker universal Install the digitalSTROM push button block with 4 universal inputs according to the installation instructions only for digitalSTROM push button block SW TKM200 joker black with four push button inputs Up to four push buttons can be connected to the independent push button inputs of a joker digital STROM push button block and operated independently Every input is managed by the digitalSTROM system as an independent digitalSTROM push button block The dSID specified on the terminal block corresponds to the dSID of the first push button Push buttons 2 4 automatically receive the three following dSIDs The field of application for each connected digitalSTROM push button can be configured separately e g input 1 yellow Light input 2 grey Shade By combining two inputs each 2 way push buttons can also be configured on the digitalSTROM push button block with 4 universal inputs joker universal You can freely specify for the push button inputs
93. g the interruption is expected to last Each digitalSTROM component has an 8 digit number dSID nas N ATIG ec This number is attached to the back of the housing and ensures the unique JEZOV SOx max 1SOW identification of the digitalSTROM component Please note the dSID and the QiZO__GEKM200 location of the digitalSTROM component prior to installation 4A994816 A ry n 1 LS You can use these notes later to name the digitalSTROM Devices according to their function and location in the digitalSTROM Configurator To do so use the previously finished configuration sheets which are enclosed with the digitalSTROM installation manual or can be downloaded at http www aizo com downloads Installation location aizo AG Brandstrasse 33 8952 Schlieren HV UV Hans Muster Zurich Inst date 09 02 20xx me p O e fe C e a E r SSCS ooo p o s e dsF no Circuit SN comment 1o a a S O 2 o R a 3 S B a S O C Cr CO CXC a e o pa ozsa 1 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 15 132 digitalSTROMe dSM_ Room Device Type Function Addition location dSID_ Comment 1 ivng GETKM210 Dimming Pushbutton Doors 37D4_ Ceiling lamp 1_ ating GEKM 200 Dimming Ceilinglamp2 4816 1 jlivng GESDM 200 Switching Floorstandinglamp 3771 2 Corridor GETKM 200 Pushbutton a02 2 Corridor GE TKM 200 Pushbutton E234 2 Corridor GEKM 200 Dim
94. he backup file in the opening dialogue The file name must not be changed as part of this process Opening dss_backup_2013 01 14_145002 dss EJ You have chosen to open dss_backup_2013 01 14_145002 dss which isa dss File from https 192 168 8 118 50443 What should Firefox do with this file Open with Browse Save File Do this automatically for files like this from now on i OK Cancel Ex Firefox Dialogue Please note that the settings for the individual device values and network settings of the digitalSTROM Server are not included in the backup The backup includes only the system settings of the digitalSTROM Server Names of devices rooms activities digitalSTROM Meters System settings such as system name SSH access location and time zone Configuration of digitalSTROM Server apps The names of the digitalSTROM Meter and associated digitalSTROM terminal blocks 20 characters maximum are also stored in the digitalSTROM Meter If a digitalSTROM Server is replaced these names are automatically transferred to the digitalSTROM Meter digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 50 132 Restoring system settings Use Searchto select the backup file from which you want to restore the system settings File Upload EA B Local Disk dSSBackup v earch dSSBackuy o Organize v New folder i A Name i Date modified Tyt Computer _
95. hown or hidden as needed With Drag amp Drop you can move the columns shown to the left or right Simply click on the column header and drag the column while you hold the mouse button down The settings will not be saved and are deleted when you close the browser digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 37 132 C3 Embedded dialogue The dialogue for changing device values is embedded in the main section Activities in the device list This allows the user to quickly and conveniently navigate to the device values or to directly select a device without having to open additional dialogues Thus the current device values for the desired preset can be saved with just a few clicks See also chapter 5 5 2 Devices w re 1a be Name dSID Output Mode Input mode Value 0 Max TV light 00004c39 dimmed S Floor lamp Couch 000037b4 dimmed z Re Ceiling light Hallway 000044dd dimmed Device Sa Button Living room 00017ca0 Area 1 Presets 2 4 q Re Ceiling light Dining table 000044a7 dimmed Device Min 7 The current settings can be saved for the selected preset Preset 3 Read Save Save to another preset Tool advice f you place the mouse pointer over a control element without clicking it a tool advice is displayed explaining the function of the control element Devices in Room Living room 1281 we Ga S Nam Edit Device Values D amp Ceiling light Dini 000044a7 D Status bar
96. ht aligned digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 36 132 C2 Data list view In this view the applicable devices data for the selected item are shown in list form Name dSID Meter Name 5 Ceiling light Dini 000044a7 F1 Living room K Ceiling light Hall 000044dd F2 Bedroom Hall Blinds Living room 00016ba0 F1 Living room K a T 00015268 F1 Living room K A Button Living room 00017ca0 F1 Living room K E g list of all digitalS TROM Devices in a room Devices in grey are inactive and were not recognised physically by the digitalSTROM Meter e g because they were removed from the digitalSTROM installation Column menu You can freely configure the representation of the columns in the list as you desire Name dSID Meter Name Output lv ampadaire Sofa Sort Ascending yir Cy Ceiling light Dini z Sort Descending ving room K dimmed W Ceiling light Hall droom Hall dimmed Blinds Living root Columns Pi V Name g m 00015268 F1L 7 asID Si Button Living room 00017ca0 FIL C7 Meter Name 2 Button Blinds 00049022 FIL 7 Output Mode Floorlamp Couch 000037b4 FiL _ ad J Button Mode TV light 00004c39 F1L sd I Button Kitchen 00017ca3 F1L Button Input Button Dining table 00017ca1 F1L V Room Name App Button 00017ca2 F1L F Comment The columns can be sorted in ascending or descending alphabetical order Columns can be s
97. ice availability every 24 hours Checking device presence Checking device presence on dSM F1 Living room Kitchen 00000501 Cancel Use this command If you want to use previously inactive digitalSTROM Devices again in the digitalSTROM power circuit and want to update the presentation of inactive digitalSTROM Dewices in the list If you have physically removed digitalSTROM Devices from the digitalSTROM power circuit and want to delete them permanently from the system Only digital STROM Devices presented as inactive can be deleted digital STROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 59 132 Reregister all devices All digitalSTROM Devices physically connected to the digitalSTROM Meter are registered anew in the digitalSTROM Meter Use this command If you are restoring previously deleted digital STROM Devices in the installation If correctly connected digitalSTROM Devices are not listed in the digitalSTROM Configurator LL dentify device Shows the properties of the digital STROM Device on which a push button was last used push button block or housing push button The command dentify device allows you to easily check the dSID of installed digital STROM Devices and can be used to attribute names to those devices Q Identify Device xX Please press a pushbutton to show device properties dSM dSID HW Info Button Input Name Close ASM Na
98. if the selected digitalSTROM Device can be added to the selected area due to its configuration and type In particular this command facilitates the configuration of activities for the application area Shade since the shading systems no longer have to be moved to be added to the area F Remove from area Removes the digitalSTROM Device selected in the device list from the area selected in the activity list o Edit specitic device properties Opens the dialogue to change the device settings specific to the activity preset Default device properties BD Device Properties Read x Device Name TV light Device ID 00004c39 Output Mode dimmed Settings Advanced Settings Blink when calling Preset 3 M Retain output when calling Preset 3 J v Close Example of the device properties for a light preset for a digital STROM terminal block yellow Blink when activated The selected digitalSTROM Device blinks when the selected activity preset is activated Retain Outout The call for these activities presets is not responded to by selected digitalSTROM Devices Thereby the output value is not changed but the blinking is executed when desired digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 116 132 Information to configuring the device value for higher level activities As set in the factory digitalSTROM Devices have a pre set device value which is read out at the power output when
99. igitalSTROM power circuit by using a digitalSTROM Device Filter ds F D In case of devices operated for only a short period of time so their temporary interference is tolerable a digital STROM Device Filter dS FD can also be done without Attention digitalSTROM Devices cannot be operated after a digitalSTROM Device Filter dS FD If several devices are identified as sources of interference you may connect them together with a connector strip and a digitalSTROM Device Filter ds FD In this case you have to make sure that the maximum digitalSTROM Device Filter dS FD load is not exceeded digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 130 132 10 Frequently asked questions Please visit http www aizo com support or the websites of the respective product manufacturers There you can find useful support information and also a continuously updated list of Frequently Asked Questions FAQ digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 11 Index A PAC TIN CS terete cectcsrenicaces A 104 Editing device properties ccccceccssssseeeeeeeees 115 POF Ol OUD S srszannrauneauereess E 108 FOr the rOOM ccccssceeeeeesssssseeeeeeesssssseeeeeeessees 106 Higher level o cceccecsceeesssssssseeeesssssseeseeeeesseas 107 B Basic configurations ACCESS authorisations cccccecceessesstteeeeeeeeeseteees 47 Apartment basis AdCIreSS cccccccsssseeeeessseeeee
100. imply as apps within digitalS TROM digital STROM iPhone With this iPhone App you can access a digitalSTROM App installation in your apartment digital STROM Android With this Android App you can access a digitalSTROM App installation in your apartment digitalSTROMuser Contains information for users and electricians manual digitalSTROM Contains information for the electrician in the Installation manual Installation section in the digital STROM user manual Setup Simple changes that the user can make e g setting a lighting preset digitalSTROM Installation Manual A1121DO002VO10EN 12 11 2013 OdigitalSTROM com 7 132 Abbreviation Term Description Configuration Advanced settings that were made to a digitalSTROM installation Such settings are usually made by an electrician Activity A specific activity is triggered by pressing a button For example the activity TV dims the lights in the living room or the activity Dining switches on all the lights in the dining area Coming home Leaving Higher level activities built into each digitalS TROM installation allowing you to switch digitalSTROM Devices centrally on or off They are triggered by pressing the Leaving Home push button or the iPhone App A lighting preset is created by one or several lamps e g for the activity TV the reading lamp is dimmed by 50 the ceiling light is switched off and the standing lamp is Switched
101. inal block inputs per digitalSTROM Meter Thus with the digitalSTROM automation terminal block the status changes of sensor signals can be monitored and other digitalSTROM Devices or even the entire digital STROM installation correspondingly controlled See also chapter 5 3 2 digitalSTROM inline adapter ZWS The digitalSTROM inline adapter is used as a mobile relay switching contact and has a maximum switching capacity of 2300 W 700 VA capacitive inductive The digitalSTROM inline adapter can be used in any socket outlet within the digitalSTROM installation and thus also temporarily for connected devices e g for a standing lamp 3 digital STROM enabled products The digitalSTROM product range Is continually being extended Install additional products according to the associated installation instructions digitalSTROM Installation Manual A1121DO002VO10EN 12 11 2013 digitalSTROM com 4 2 24 132 Initial operation Starting the system After all digitalSTROM components have been installed in the rooms and the distribution board the digitalSTROM system can be energised When the digital STROM system is switched on for the first time all digitalSTROM Devices are registered in the digitalSTROM Meter Depending on the size of the installation this can take 5 10 minutes Check the LED status indicator on the digitalSTROM Server and the digitalSTROM Meter after switching on the power See also chapter 4 3
102. ions Application access Application Token Enable Access dS Android App Nexus S 517 5a E ds Android App GT P1000 c29bd ce E Apply Cancel digitalSTROM allows access of external applications to the digitalSTROM system e g via smartphone apps The authentication of an external application to the digital STROM Server requires either the administrator s user name and password or a unique access key token The token is automatically agreed between the external application and the digitalS TROM Server External applications supporting tokens are granted access to the digital STROM Server at any time after token release No user names or passwords will be saved in the external application as part of this process However the external application may ask for the user name and password during the first login to be able to perform the release directly In this case it is unnecessary for the digitalSTROM Configurator to allow access Use this list to allow or withdraw access for individual applications The list is used for central access authorisation management which may allow or prevent access to specific applications or the corresponding device 5 2 6Changing the administrator password Password Web interface admin password Note the password must not contain any whitespaces Current password New password Repeat new password Apply Cancel The administrator User name is dssadmin The user name cannot be modified
103. l barce s 2 2am 2 6 4455 242 sire oe oe Press Continue as soon as the blades are open and the blinds start moving up Press Stopto stop the moving blinds if necessary Calibration step 2 of 2 Calibration of fins turn time step 2 of 2 The determined turn time can now be fine tuned Open and close the blades using the on screen buttons and move from opened and closed position to the middle The turn time is adjusted correctly once the middle positions matches from both directions If the positions don t match the turn time must be adjusted and tested again Once the optimal value is set the calibration can be completed by clicking Finish Fins Turn Time 0 S Open Fins a Center Fins Close Fins y Finish Cancel tas crea 2o cam eet 2am eee eee oe oe To allow full visual concentration on the blade angle you can open or close the blades by using the arrow keys and Y on your computer keyboard Use the arrow keys and gt to approach the middle position Calibration using digitalSTROM push button without dSS The turn time can only be calibrated by using the web based digitalSTROM Configurator digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 89 132 5 4 Creating rooms and assigning devices The distribution of power circuits in existing electric installations often does not correspond to the architectural allocation of rooms Thanks to digitalSTROM digitalSTROM Devices
104. llation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 68 132 Wipe In case of a brief power failure many standard electronic devices drop into an integrated standby mode e g TV In the operating mode Wipe the power supply for the connected device is briefly interrupted for the Off presets or the activity Standby and the device is put into its own standby mode In case of Leaving home Sleeping and Deep Off the device will be completely cut off from the power supply Preset 1 4 Area onas well as Coming home and Waking up will switch the device on again By doing so the connected device will also be put in its own standby mode Thanks to the operating mode Wipe you can switch off devices e g TVs via digitalSTROM while leaving them in their own standby mode Push button Depending on the function of the digitalSTROM push button block presets can be called up for a device connected directly to the output device push button an area in a room area push button or for the whole room room push button Device push button hee Device push button Room push button Area push button Device push button The device push button basically switches dims with 1x click a device connected directly to the output With 2x 3x 4x click on the device push button additional presets can be called up for the room This corresponds to the factory settings of the digitalSTROM line switch Area push button
105. lphabetical order In the selection View you can see an object named All devices in first place This entry contains all active and inactive digital STROM Devices available in the installation Commands Blink all devices in room Makes all digitalSTROM Devices allocated to the selected room blink Om Create new room Opens the dialogue to name the newly created room Use a meaningful name for the room Create New Room x Name for new room OK Cancel kz Rename room Opens a dialogue to rename the selected room g Rename Room x New name for room Bathroom OK Cancel oO Remove selected room Deletes the selected room You can only delete a room if digitalSTROM Devices are no longer allocated to it and if it is not the last room configured in the corresponding digitalSTROM Meter digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 101 132 5 4 5 Allocate digitalSTROM Devices to a room List of digitalSTROM Devices Apps Activities Rooms Groups System Hardware Help Rooms Devices in All Rooms a BB fille FS ay All Devices Name dsID Output Mode Input mode Input Sd Wind monitor 00094903 Wind monitor Line 2 5 Motion detector 00094902 Motion detector Line 1 Tischfeuchte 0000f352 switched Device 2 way Bedroom Hallway Kitchen Living room 00004c39 dimmed 00015268 Powersave Device 0000380c dimmed Area 2 Presets 2 4 00003754 dimmed 1 device sel
106. m you need to first select the item The selected item has a green background digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 34 132 Frequently used commands are left aligned in the tool bar Less frequently used commands are right aligned B2 Tree list view In this view the items available for selection in the main section are presented in tree or list form eo All Devices Hallway I Kitchen Bedroom 4 Living room Hallway 4 amp Light Presets y a Kitchen Fade off p w Preset 1 Light on Living room Preset 2 Watch TV Preset 3 Read w Preset 4 Relax w Area 1 on Dining table we Shade Presets w Video Presets mm Standby Deep off Sleeping Wake Up E g tree and list form for rooms or presets In the selection view commands for the relevant item can also be called up in a context menu right mouse click Hallway a Pitas a Tv Kitchen Floo Living raam ee Ceil af Bunk Blin ga Create New Room Butt E2 Rename Room Butt P Delete Room Butt Apr Press the right mouse button while the pointer hovers over the desired item to open the context menu digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 35 132 B3 Higher level activities In this section of the selection list the higher level activities e g Leaving home Ringing etc are displayed El Leaving Home Coming Home Door Bell
107. me of the digitalSTROM Meter to which the digitalSTROM Device Is connected dSID Unique identifier of the digitalS TROM Device HW Info Hardware specifications of the digitalSTROM Device Push button input Input number only for digitalSTROM push button blocks with several inputs Name Name of the digitalSTROM Device The name of the digital STROM Device can be modified directly in the dialogue Use Saveto save the specified modified name After saving the dialogue is ready to display the next digitalSTROM Device digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 60 132 Edit system properties Opens the dialogue for editing the properties of the selected digitalSTROM Meter dSM Properties x dSM Name F2 Bedroom Hallway dSM ID 0000061d Lock newly registered devices Save Close Lock newly registered devices The locking of newly registered devices prevents impermissible digitalSTROM Devices from being registered in the digitalSTROM power circuit so activities or presets can be called up With this function an impermissible manipulation e g by adding a digitalSTROM push button block to an external power socket can be prevented The digitalSTROM installation does not respond to the inputs of locked digital STROM Devices The output of a locked digitalSTROM Device contains the included function Locked digitalSTROM Devices are displayed in the device list in red and corres
108. ming Push button Entrance A147 2 Corridor GE KM 200 Dimming Push button Atbathroom B659 3 Bedroom GE TKM 210 Dimming Push button Doors 5C58 Ceiling lamp 3 Bedroom GEKM 200 Dimming Dressngroom 5707 3 Bedroom GE SDM 200 Dimming Bedside lamp Mr 6868 so pm _ GE SDM 200 SDM 200 Pinmog f Bededo ime Ms lamp Ms we __ i e C o P S ee ee A Re GREG ee re ee es ee ee ee O digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 16 132 3 3 Electrical installation in the distribution board The following operations are performed in the distribution board Distribution board Work steps Supply to the rooms 1 Install digitalSTROM filter dSF for L1 L2 L3 uits with digitalSTROM 2 L1 L2 2 Install digitalSTROM meter dSM 3 Install digitalSTROM server power supply unit optional 4 Install digitalSTROM server dSS optional 5 Connect Ethernet interface optional 6 Create dS485 bus interconnection eeeeeoe aceseseeneeeeee dSF11 am dSF11 r 000000o0 Power in digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 17 132 Comments 1 Installing and Install the digitalSTROM Filters according to the installation connecting the instructions on the top hat rail and connect electrically with the digitalSTROM Filter mains sup
109. n In the factory settings of the digitalSTROM relay terminal block Shutters grey the shutters are closed shut in the Off preset Blinds Usually operated via 2 way push button Blinds are used as screens or as weather and sometimes as burglar protection In addition to their position you can also control the angle of the blinds Blinds are also known as slat blinds In the factory settings of the digitalS TROM relay terminal block Blinds grey the blinds are closed shut in the Off preset Awning Usually operated via 1 way push buttons Typically awnings are shading systems made of fabric For this reason they are usually retracted during bad weather or absence In the factory settings of the digitalSTROM relay terminal block Awning grey the awnings are retracted in the Off preset digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 111 132 5 5 2 Configuring digitalSTROM Devices for activities presets and areas List of digitalSTROM Devices Devices w re ta Name dSID TWiight oj Floor lamp Couch Ceiling light Hallway Sal Button Living room Ceiling light Dining table 00004c39 000037b4 000044dd 00017ca0 00004447 Output Mode dimmed dimmed dimmed dimmed Input mode Device Area 1 Presets 2 4 Device Value 0 Max Min Vv The current settings can be saved for the selected preset Preset 3 Read Save Save to another preset The device list only shows digital
110. nding of e mails E mail address Sender address used by digitalSTROM Server apps to send messages e g dss11EGBadenerstrasse3c gmail com Mail server name Name of the mail server SMTP used to send outgoing mails e g smtp gmail com Outgoing mail server requires authentication Please note that authentication via user name and password is usually mandatory on a mail server SMTP to send e mails User name User for authentication with mail server SMTP e g dss11EGBadenerstrasse3c gmail com Password Password for authentication with mail server SMTP e g EgBstr 3c digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 46 132 Use secure SMTP SSL via port 465 The transmission of data is encrypted with SSL Secure Socket Layer For this purpose a communication port reserved for encrypted data transfers port 465 TCP is used Use secure data transmission TLS va port 25 The transmission of data is encrypted with TLS Transport Layer Security For this purpose the default port for outgoing mail port 25 SMTP is used Please note that safe communication requires corresponding firewall settings Depending on settings port 25 or port 465 must be configured accordingly Your e mail provider can give you information on procedures supported by the mail server Verify server certificate Determines if the certificate will be checked during mail server c
111. ng data Formatting the card will delete metering and logging data but not the system settings itis recommented to format the card if errors were detected SD card status OK Format SD card For digitalSTROM Servers without additional SD card e g dSS11 1GB the system setting SD card Is not available Status of the SD card Shows the current state of the SD card The status of the SD card is automatically checked during each digitalSTROM Server restart Use Formatto format the card after repeated errors or to delete metering and log data irretrievably System settings remain unchanged 5 2 8Check system updates You can check for and install available system updates and firmware updates in the web based digitalSTROM Configurator The digitalSTROM Server must be connected with the Internet to enable the automated search for available updates If the digital STROM Server is not connected to the Internet available system updates may also be provided by a USB flash drive See also chapter 5 2 8 2 Check for and install available updates after commissioning or later installation of additional digitalSTROM Meters Make sure to back up your settings prior to a system update See also chapter 5 2 8 1 The installation of updates ensures that the latest version of all digitalSTROM components is in operation 5 2 8 1 System update in the digitalSTROM Configurator online You can check for and install available system updates
112. ntact open and contact closed are sent off Dawn dusk For use with a dawn dusk sensor Switching sensor messages Lightand Dark Movement sensor For use with movement sensors Switching sensor messages Vo movement and Movement With the digitalSTROM Server app Movement sensor a multitude of application possibilities can be easily realised Smoke detector For use with smoke detectors Switching sensor messages No smoke and Smoke Triggers the higher level activity Fire digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 76 132 Wind monitor For use with wind monitors Switching sensor messages No wind and Wind Triggers the higher level activity Wind Rain monitor For use with rain monitors Switching sensor messages No rain and Rain Triggers the higher level activity Rain Sunlight For use with rain monitors Switching sensor messages Light and Dark Thermostat For use with a thermostat Switching sensor messages Temperature exceeded and Temperature fallen below Input Determines the interpretation of a sensor signal Standard The rising flank causes a switching sensor message for the On state The falling flank causes a switching sensor message for the Off state Inverted The rising flank causes a switching sensor message for the Off state The falling flank causes a switching sensor message for the On state Rising flank on Only the
113. nual A1121D002VO10EN 12 11 2013 OdigitalSTROM com 72 132 Function For digitalSTROM line switch GE SDS200 Determines for digital STROM line switch GE SDS200 the functionality of the 2 push buttons on the housing which can be pushed together or individually 1 way Both push buttons are operated as one joint single push button in the application area Light yellow Here the line switch is listed as a single device in the device list 2 way Both push buttons are operated as 2 way push button for the application area Light yellow Here one push button is used as On push button the other as Off push button In this case dimming functions for example can be realised even more easily Here the line switch is listed as a single device in the device list 1 way joker push button One push button is used as 1 way push button in the application area Light yellow Here the configuration is performed in the list of devices at the line switch GE SDS200 The configuration of the joker push button is performed at the line switch with the hardware data SW SDS200 shown additionally in the device list The application area of the joker push button can be chosen as needed Output Determines the operating mode of the power output of the digital STROM terminal block The setting is only shown in the dialogue if the selected digitalSTROM terminal block is equipped with a power output Switched The output is
114. of presets through the web based digitalSTROM Configurator however is always possible Refer to chapter Setup of lighting preset with the light push button in the Setup section of the user manual for details on the programming mode digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 45 132 5 2 4E mail settings 5 2 4 1 Mail server Mail Server Configuration of the server settings for outgoing e mails The mail server can be used by digitalSTROM Apps to sent e mails E Mail Address me mail server com Mail Server Name mail server com F Outgoing mail server requires authentication User me mail server com Password eecccceccese Use Secure SMTP Port 465 Use secure data transmission TLS Verify server certificate Check Connection Send Testmail Apply Cancel To avoid having to store confidential third party access data on the digitalSTROM system it is recommended to set up a separate email account for each digitalSTROM installation The account can be set up with a free provider e g gmail and exclusively used for sending e mail from the digital STROM Server The corresponding server settings and required access data are provided by your e mail provider A 2 way authentication 2 step verification for logging on to a mail server as it is offered as an optional setting by e g Google is not supported by the digitalSTROM Server Server settings for the se
115. ommunication Server certificates confirm the association of a server with a person or company and are used as basis for encrypted SSL TLS connections Use Check connection to check the accessibility of the configured mail server However no authentication will be performed and no test e mails sent Success x Connection test successful Show details v OK Use Send Testmail to verify authentication and encryption If the test is completed successfully a test mail will be sent to the configured e mail address sender In case of an error the mail server error message will be displayed in a dialogue Error x Mail delivery failed service unavailable Hide details msmtp envelope from address dssl11EGBadenerstrasse3c gmail com not accepted by the server msmip server message 530 5 7 0 Must issue a STARTTLS command first k26sm1003387 1wbo msmitp could not send mail using account specified on command linehost smtp gmail com port 25 timeout off protocol smip domain localhost auth none user dssl1EGBadenerstrasse3c gmail com password not set bd OK Example Option Use secure data transmission TLS via port 25 inactive whereas the mail server demands an encrypted transmission TLS After successful testing the settings must be saved by clicking on Apply digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 47 132 5 2 5Access authorisations 5 2 5 1 Release of applicat
116. on Address in each digital STROM chip terminal block 96 bit The same concept as a Mac address Power circuit All wall sockets switches lights and electrical devices which are wired behind a fuse or a circuit breaker CB Often there is one power circuit per room in your apartment Downstream Communication from the digitalSTROM Meter to the communication digitalSTROM terminal blocks Upstream Communication from the digitalSTROM terminal blocks communication to the digitalSTROM Meter dS485 protocol Protocol between dSS and dSM based on RS TIA485 Shutters Shutters are used as screens or as weather and burglar protection In the factory settings of the digital STROM relay terminal block Shutters grey the shutters are closed Shut in the Off preset Blinds Blinds are used as screens or as weather and sometimes as burglar protection In addition to their position you can also control the angle of the blades Blinds are also known as slat blinds In the factory settings of the digitalSTROM relay terminal block Blinds grey the blinds are closed shut in the Off preset Awning Typically awnings are shading systems made of fabric During bad weather or absence they are usually retracted In the factory settings of the digitalSTROM relay terminal block Awning grey the awnings are retracted in the Off preset digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 8 132 1 6 digitalSTROM colour s
117. on of travel close open Protect calibration values Protects parameters against being overwritten by the calibration Calibration can only be initiated in the web based digitalSTROM Configurator or via inching commands if the protection is lifted This setting prevents the unintentional overwriting of calibration data during the setup of new presets Calibrate motion time and direction Determines the motion time and direction of travel for the shading system connected to the digital STROM relay terminal block See also chapter 5 3 4 Calibrate Turn Time Determines the turn time for the blades of the blinds connected to the digitalSTROM relay terminal block See also chapter 5 3 5 Advanced properties a The Advanced Properties can be shown hidden by using the corresponding arrow Hide Advanced Properties a Motion when blinking 990 ms Reverse time on direction change 500 ms Follow up time at end position 2000 ms Threshold of end switch recognition 0 mA Number of steps for fine tuning adjustment 8 Motion time for fine tuning adjustment 200 ms Motion time when blinking Blinking is indicated by a short motion of the shading system Motion time for the blinking motion Reverse time on direction change Duration of the motion break caused by a direct reversal of direction digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 80 132 Follow up time at end position Maximum p
118. or DSP Software Version Software version of the digitalSTROM Meter signal processor HW Version Hardware version of the digitalSTROM Meter Commands Blink Meter LED Makes the LED status indicator on the housing front of the selected digitalSTROM Meter blink alll Test Transmission Quality Checks the transmission quality of the down and upstream communication to all active digitalSTROM Devices connected to a digitalSTROM Meter and shows the connection quality ina dialogue after test completion To test the worst case all possible consumers TVs computers in the corresponding power circuit should be switched on Use this command To check the communication reliability of newly installed and configured digitalSTROM components To analyse problems which you suspect to relate to the transmission quality alll Test Transmission Quality x dSM Name F1 Living room Kitchen dSM ID 00000501 Number of active Devices 12 Number of test messages per device 1 Progress 0 Average Min Max Upstream Communication 0 0 0 Downstream Communication 0 0 0 Lost Messages 0 Start Close ASM Name Name of the digitalSTROM Meter whose transmission quality is being tested ASM ID Unique identifier of the digital STROM Meter whose transmission quality is being tested Number of Devices Number of digitalSTROM Devices connected to the digitalSTROM Meter Number of queries per device Number of test sequ
119. or recurs after restart C Initialising dS485 bus interconnection grey If the LED stays grey after restart a hardware error has occurred and the digital STROM Server must be replaced C System start yellow 2 System update Blinking blue yellow Do not switch off the digitalSTROM Server during a system update Error messages blink The colour of the LED status indicator is interrupted by a single blink to indicate an error message The colour of the interruption blinking indicates the error message in the digital STROM Server SD No other digitalSTROM Meters were found magenta a No physical network connection LAN available cyan digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 28 132 4 4 Establishing a network connection The digitalSTROM Server supports the Universal Plug and Play Standard UPnP This standard was developed by different device manufacturers to simplify the network configuration for devices as much as possible Connect the digitalSTROM Server to a network router with a typical RJ 45 network cable Recognise the digitalSTROM Server in the network Open the web based digitalSTROM Configurator in the browser Connecting to a network LAN To integrate the digital STROM Server 1 in a network LAN you have to connect the digital STROM Server using a standard RJ 45 network cable 2 with a DHCP capable network router 3 In order to acce
120. or the digitalSTROM relay terminal block SW KL and the digitalSTROM inline adapter SW ZWS 3 Configure Consumption Event Device Name TV Device ID 00015268 Current Consumption 4 W Refresh itis recommended to set the threshold value to 50 of the maximal consumption Iv Activate consumption event Turn On Name TV Turn On Send event if consumption of 230 W overrun Iv Activate consumption event Turn Off Name TV Turn Off Send event if consumption of 230 W underrun Save Cancel If the consumption of the connected device exceeds or falls below this defined threshold corresponding consumption event messages will be sent off The threshold should be set to 50 of the maximum consumption of the connected devices The minimum threshold is 20 W The messages can be used to control other activities e g to trigger an activity in the digitalS TROM Server app Event Responder digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 81 132 Current Consumption Current consumption value of the connected device in Watt Use Update to update the display of the current consumption value Use Agp yto set the thresholds automatically to 50 of the current consumption value recommended threshold Activate consumption event on Activates the sending of a consumption event message with the specified name e g TV on if the current consumption value exceeds the configured threshold e g 230 W
121. or use the command Edit shade device properties Len in the Hardware main section Device Properties shade x Device Name Blinds Living room Device ID 00016ba0 Motion Time Open Close 30 00 S Motion Time Close Open 30 00 S Turn Time Fins 0 95 z Direction of travel default w Protect calibration values Calibrate motion time and direction Start Calibrate turn time Start Reset Show Advanced Properties v Save Cancel Use Start to calibrate turn time to start a support sequence for the manual determination of the blade turn time The calibration takes 2 steps In the first step the turn time is roughly measured In the second step the user can visually check the complete opening and closure as well as a middle position of the blades change them if necessary and finally confirm them You can always use Resetto return the turn time to the factory settings of 3 seconds digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 88 132 Calibration step 1 of 2 Calibration of fins turn time step 1 of 2 The blind will move to the required position for calibrating the turn time first Once this position is reached press the arrow button up until the blades are completely closed and the blinds were raised slightly The approximate turn time will be calculated using the number of steps Press the Next button to continue with fine tuning the turn time Number of Steps 0 Stop Continue Cance
122. ply Position the digitalSTROM Filter correspondingly close to the digitalSTROM Meter The cable length of the electrical connection between the digitalSTROM Filter and the digitalSTROM Meter must be kept as short as possible If additional digitalSTROM Meters are installed in other sub distribution units digital STROM Filters must necessarily also be installed Fasten the screws of the unused connection terminals on the digitalSTROM Filter while doing so The digitalSTROM Filter must be installed on the primary side of the digitalSTROM Meter If the filter is located on the secondary side communication in the digital STROM power circuit will be impaired 2 Installing and Install the digitalSTROM Meter according to the installation connecting the Instructions digitalSTROM Meter Distances The arrangement of digitalSTROM Meters must include a distance of 0 5 TE after every third digitalSTROM Meter If the digitalSTROM Meters are mounted horizontally the distance must be kept after each device Heat dissipation at high load and increased ambient temperature will be improved by this O STE O STE Vertical installation Horizontal installation Connection Disconnect the connections on the output side from the power circuit breaker and connect the digitalSTROM Meter according to the installation instructions The digitalSTROM Meter is connected in series with the power circuit breaker
123. pondingly marked The lock can be deactivated in the context menu of the device list To open the context menu click the right mouse button while the locked digitalSTROM Device is selected Devices oS wl amp 2 Bm SG Name dSID Output Mode c Floorlamp Couch PESA EE Ceiling light Kitchen a Blink Ceiling light Dining table Edit Device Values TV light all Test Transmission Quality Panic Update Device Status Table lamp e TV z gt Edit Device Properties ve Blinds Living room z A Button Living room Button Dining table aas c Rename Device App Button plies Edit 7 t Button Kitchen tCommen 2 Button Blinds Sy Unlock Device EZ Rename dsM Opens the dialogue to rename the selected digitalSTROM Meter The name of the digitalSTROM Meter should preferably contain the room designation to ensure a clear allocation to specific rooms e g for energy visualisation digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 61 132 Rename dSM x Meter ID 00000501 Ve Meter name F1 Living room Kitchen p Close L Vew communication Presentation of the communication log files for the communication between the selected digitalSTROM Meter and the digitalS TROM Devices registered therein oF oF a View protocol for device update Opens the protocol for the update of the device which is automatically executed for digitalSTROM Meters in connection with a firmware
124. protocol secure shell and enables safe login and encrypted data transfer with SSH clients SSH access is inactive in factory settings and is mainly used by digitalSTROM developers User and password for the SSH connection are always identical with the administrator password for the web based digitalSTROM Configurator See also chapter 5 2 6 5 2 3 2 Location Location Country United Kingdom i Locality London v Coordinates 51 50853 N 0 12574 W Sunrise Sunset 09 03 34 17 11 06 CET The time zone under Date and time will automatically be set depending on the locality selected in the list Selectlocation on map Apply Country Use the drop down list to select the country where the digitalSTROM installation is used Locality Use the drop down list to select the locality where the digitalSTROM installation is used The list only provides localities for selection in the chosen country If your locality is not listed choose the nearest locality Coordinates Coordinates are automatically chosen according to the selected country and locality If needed they can be accurately defined by choosing Select location on map Sunrise sunset The times for sunrise and sunset are automatically determined for the selected coordinates and the current system time astronomic clock These times are also available when the digital STROM Server is not connected to the Internet The specifications for coordinates and sunrise
125. r app The displayed apps can be directly opened by a double click on the icon 3 Uninstall app Removes the digitalSTROM Server app permanently from the digitalSTROM Server deinstallation Installing Apps Activities Rooms Groups System Hardware Help Menu Install Use Refetch list from server C Insi Disclaimer Install anne Update http Avww aizo co ale Version 0 9 3 r1 This app automatically turns off lights after a predefined amount of time Mobile Remote Control http www dss11 de mre doku Ay Version 0 9 23b r1 This app enables control of a digitalSTROM installation via a mobile phone ci Update l st from server Refreshes the list of available digitalSTROM Server apps For digitalSTROM Servers with web access Update list from USB flash drive Refreshes the list of available digitalSTROM Server apps from a USB flash drive For digitalSTROM Servers without web access In order to install digitalSTROM Server apps from a USB flash drive the corresponding software update must first be installed on the flash drive After connecting the flash drive you need to wait for the automatically started system update See also chapter 5 2 8 2 The command is only available if a USB flash drive containing a system update is connected to the digitalSTROM Server housing digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 123 132 Cd Install app Installs the selected digitalS
126. r digitalSTROM terminal blockShade Position The setting of the device value is interpreted by the digitalSTROM relay terminal block as position For this purpose the digitalSTROM relay terminal block must be calibrated appropriately after installation See also chapter 5 3 4 Use Stopto stop the motion of a shading system e g if Qoen or Close was previously used to travel to the end position Only for digitalSTROM relay terminal blocks Shade grey With Open the movement command to fully open the shutters or extend the awning can be started Only for digitalSTROM relay terminal blocks Shade grey With C ose the movement command to fully close the shutters or retract the awning can be started Only for digitalSTROM relay terminal blocks Shade grey Set Blade Angle The blade angle can be set by direct text input values between 0 100 or with a s der Only for digital STROM relay terminal block grey shade blind The blade angle must be calibrated appropriately after installation See also chapter 5 3 5 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 103 132 5 Rename device Opens a dialogue to rename a digitalSTROM Device Rename Device x Device ID 00004456 Device Name Ceiling light Kitchen N P Close With Select previous device and Select next device you navigate directly to the next or previous digitalSTROM Device in the list f Edit comment Opens a dialogue to edi
127. r personal digitalSTROM Server The existing digitalSTROM system can for instance be enlarged by integrating an additional timer or a presence simulator Installing new applications apps or updating already installed applications can be completed quickly and easily in the Apps applications main section Applications are downloaded and installed directly from the digitalSTROM App server Get an overview of already installed digitalSTROM Server apps Check the availability of new digitalSTROM Server apps on the digitalSTROM App server Install or remove digitalSTROM Server apps at will Check the availability of updates for already installed digitalSTROM Server apps Functional description of available digitalSTROM Server apps You will find an overview of the available digital STROM Server apps under http www digitalstrom com system anwendungen digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 6 1 6 2 122 132 Apps Activities Rooms Groups System Hardware Help Menu Use Use i Install Update A cis te Ls w Presence Si User Define Event Respo Energy Graph Timers In the factory settings of the digitalSTROM Server the most important digitalSTROM Server apps are already pre installed These digitalSTROM Server apps cannot be uninstalled and are automatically updated during system updates See also chapter 5 2 8 Open app Opens the selected digitalSTROM Serve
128. r terminal blocks from the power circuit check the device presence before testing See also chapter 5 3 1 At least one digitalSTROM terminal block must be registered in and physically connected with the power circuit Switching on all electrical devices Switch on all consumers in the tested power circuit worst case to test the transmission quality with the highest impact from potential sources of interference These include for instance Chargers for telephones MP3 players etc PCs laptops monitors printers routers TV sets radios amplifiers Fluorescent lights low voltage lamps ESL dimmers Vacuum cleaners digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com Testing the transmission quality 128 132 Select in the Hardware main section the corresponding digitalSTROM Meter and run the command Jest transmission quality For a meaningful result you should use the value of 5 for Number of queries from device Start the test dM Name F2 Bedroom Hallway dSM ID OO00061d Number of active Devices Number oftest messages per device Progress Upstream Communication Downstream Communication Lost Messages Average Max 100 Close Sources of interference should be identified and isolated by using a digital STROM Device Filter dS FD lf over 10 of queries number of devices number of queries is equal to 100 are lost Ifthe mean value
129. ration and configuration of digitalSTROM components at http www aizo com downloads Installation manual The present digital STROM installation manual is integrated as an online help in the installation on the digitalSTROM Server It can be opened in the web based digitalSTROM Configurator in the main section He p As an online help the electronic format features additional functions such as full text search index etc and is constantly updated with the system updates You can download the latest version of the installation manual and also find additional useful Support information at http www aizo com downloads Contents Table of contents in tree structure for navigation in document Index directory of keywords Most important terms of reference Search Searching text in the document Favourites Electronic bookmarks for direct navigation to frequently visited pages FAQ and support Find frequently asked questions FAQ or support information at http www aizo com support or on the websites of corresponding product manufacturers User manual You can download the digitalSTROM user manual at htto www aizo com downloads digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 127 132 9 Troubleshooting Please also visit the website http www aizo com support or the websites of the respective product manufacturers There you will find additional useful support information for troubleshooting
130. rator To perform the calibration in the web based digitalSTROM Configurator use the command Edit shade device properties Fs in the Hardware main section Device Properties shade x Device Name Blinds Living room Device ID 00016ba0 Motion Time Open Close 30 00 S Motion Time Close Open 30 00 z Turn Time Fins 0 95 S Direction of travel default v Protect calibration values Calibrate motion time and direction Star Calibrate turn time Start Reset Show Advanced Properties v Save Cancel Use Start to calibrate motion time and direction to start a sequence whereby the terminal block determines the required parameters of the driven shading system independently Calibration is performed in 3 steps At each step the user can visually check and confirm the shading system end position digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 85 132 The individual steps depend on the type of shading system shutters blinds awnings Follow the corresponding instructions The corresponding dialogues for the digitalSTROM relay terminal block Shutter GR KL200 grey serve as example here Please note that the direction of travel of the connected shading system Is not yet known prior to calibration Therefore the push buttons for the motion commands in the dialogues are shown as left right arrows instead of Open Close You need to first test the direction of travel using the arrows before you can follow the
131. resets 104 5 5 1 Renaming calling up and setting up digitalSTROM activities 105 5 5 2 Configuring digitalSTROM Devices for activities presets and areas 111 5 6 Creating groups and allocating devices 118 5 6 1 Creating and renaming digitalSTROM groups 119 5 6 2 Allocating a digitalSTROM Device to a group 120 6 digitalSTROM Server apps 121 6 1 Use 122 62 Installing 122 6 3 Updating 123 7 Installation checklist 124 8 Help 126 9 Troubleshooting 127 91 Faulty operating condition 127 92 Ensuring reliable operation 127 10 Frequently asked questions 130 11 Index 131 digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 5 132 1 About the document 1 1 1 2 1 3 1 4 For whom is this document intended This document is intended for use by people who are Installing and commissioning digitalSTROM components Configuring digitalSTROM systems in the web based digital STROM Configurator Using the web based digitalSTROM Configurator for analysis monitoring or troubleshooting What are the requirements for use It is assumed that the reader of this document already has extensive knowledge of digitalSTROM products Electricians must have the necessary technical knowledge and qualifications required for carrying out work to the electrical installations The prerequisite for this is the digitalSTROM basic training Technically interested users may utilise the web based digitalSTRO
132. s 44 Backing up restoring the system n 49 DAE Silage meee renee E erer sere ee 43 Formatting the SD Card ccccccccesssssssteeeeeeeees 51 POC AION a E 41 Mail Server ee 45 NEONO a crenece treet ererere eet re eee 40 PAS SON e asi oe ce art E a eeaeceate 47 eee ee ee ee ee ee ee 39 Setting presets 0 0 eeeeesceeeeessssseeeeeesesssseeeeeees 44 System and firmware UPdAateS eeeeeeeteeeeees 51 SYSTEM properties ccccceeeessssseeeeesesssseeeeeeees 55 SVS UCT FSS EAL Ernia 50 SYSTEM Settings cceeeeeseeeeeeessssssseeeeeeessssseeeeeeees 41 C Colour schemMe sssssssserrrssssserrrrrsserrrrrnresnrrrrrnrsseenne 8 Comment on joker ss ssssssssserrnrssssrrrnrsssrrerrnnssennn 8 D Device properties ssssssssrrrrsssrrerrrrrssrrerrnnnsee 66 75 digitalSTROM Apps ssssssssssssssssrrrsssesrrrnnrsserrrrnnssne 121 Opening sssssssseerrrsssesrrrrnrsserrrrnnrsserrnrrnrnsserreenne 122 digitalSTROM Configurator ssssssssssrrrrsssesrrrressne 32 Advanced ViE W ssssssesssssseserrrrrsserrrrnrrsserrrrnnreseenn 33 ColuMN MENU ssssssssserrrrssesrrrrnrsserrrrrnnnnernennnenne 36 Context MENU ssssssessssssssrrrnseessreernrrnnnnnnnnerrrrrennnna 34 Data VIEW uo ccccccceecssssseeeeeessssseseeeeeeesssssseeeeeeeeesegs 35 Navigation ssssssesrrsssesrrrrrrsserrrrnnrsnerrnrnnrsserrrenne 33 Selection VI W sssssserrssssesrrrrrsserrrrrnrssnrrrrrnrsseenne 33 Stats Dai aoaaa E 37 3
133. shade systems can be retracted or skylights closed in good time Fire An external smoke detector reports that a smoke development has been detected to the digitalSTROM System With it the activity Fire on the Panic or Leaving home push button can be set back 1 click Alarm 1 4 The higher level activities Alarm 1 4 are freely available and can be used e g to indicate a Specific event as an alarm with the digitalSTROM Server app You will find information to additional application possibilities of higher level activities and configuring the digitalSTROM automation terminal block in chapter 5 3 2 Higher level activities for groups In the factory settings higher level activities are processed within the entire digitalSTROM installation However activities of digitalSTROM Devices which can trigger a higher level activity e g digitalSTROM automation terminal blocks for wind and rain are only processed within a group which is allocated to the digitalSTROM Device Refer to the application examples in chapter 5 6 The available activities are extended all the time digital STROM Devices have a behaviour for selected higher level activities that is preset at the factory E g awnings are retracted during rain lights switched on in case of fire and shutters are opened digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 109 132 Commands a Rename Opens a dialogue to rename the s
134. so chapter 5 3 1 The lower half of the screen contains the data view with the digitalSTROM Devices registered in the selected digitalSTROM Meter Use the device list to rename configure and test digitalSTROM Devices See also chapter 5 3 2 5 3 1 Check and configure the digitalSTROM Meter functionality digitalSTROM Meter selection list Apps Activities Rooms Groups System Hardware Help Meters fo wl G BQ fe Status Name dSM dSID Number of Devices Lock new Devices F1 Living room Kitchen 00000501 13 enabled i F2 Bedroom Hallway 00000610 9 disabled Columns Status digitalSTROM Meter operating condition The status corresponds to the LED status indicator on the housing Additional information on the operating condition is shown as tool advice in case of errors Additional information is not displayed during standard operation See also chapter 4 3 1 Name Name of the digitalSTROM Meter ASM dS D Unique identifier of the digital STROM Meter Number of Devices Number of digital STROM Devices connected to the digitalSTROM Meter Lock new Devices Status of the locking for newly registered devices activated deactivated Power W Total energy consumption of the digitalSTROM Devices connected to the digitalSTROM Meter in Watts digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 57 132 ARM Software Version Software version of the digitalSTROM Meter microprocess
135. specified sequences Calibration step 1 of 3 Calibration step 1 of 3 Use the arrow buttons below to move the metal shade to the upmost position In case your metal shade was already in the upmost position before calibration was started you will have to move it a couple of centimeters down and then up to ensure the correct end position Please press Continue to automatically lower the metal shade q Stop P Cancel Calibration step 2 of 3 Calibration step 2 of 3 The metal shade is now moving to the lowest position Various parameters are calculated during that time Please press Continue as soon as the metal shade reaches the lowest position it will then move up again The calibration needs to be canceled and restarted in case the lowest position was not reached Stop Continue Cancel Calibration step 3 of 3 Calibration step 3 of 3 The metal shade is now moving to the upmost position Various parameters are calculated during that time Please click Finish when the upmost position is reached The calibration needs to be restarted in case the upmost position was not reached Stop Finish Calibration using digitalSTROM push button without dSS A sequence of motion commands must be called up to calibrate a digitalSTROM relay terminal block by using inching commands The shading system must reach its end position in one Specified driving sequence as part of this process Hereby the digitalSTROM
136. ss the digitalSTROM Server with your computer laptop 4 you must also connect your computer laptop with the router using a standard RJ 45 network cable 5 You may also use a wireless network 6 to be able to move freely around the house during configuration and testing of the digitalSTROM installation Depending on network installation and configuration you can integrate the digitalSTROM Server into the Internet 7 in this way Please note that the router settings may need adjusting For external browser access you need to set up port forwarding for the incoming port 443 https For external access by the digitalSTROM smartphones App you need to set up port forwarding for the incoming port 8080 http Refer to the manufacturer s support documentation for any questions related to router settings For network LAN integration you should use a RJ 45 network cable without shielding The cable shielding might come into contact with an electrical conductor in the distribution board which is connected to mains power and thus could lead to defects or place persons at risk digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 29 132 Locating the digitalSTROM Server in the network Refer to the chapter Accessing digitalSTROM with my computer in the Setup section of the user manual digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 30 132 4 5 Login to the digitalSTRO
137. t a comment on the digitalSTROM Device Edit Comment x Comment for 000037b4 Illuminant was replaced 24 08 2010 OK Cancel Delete device Deletes the selected digital STROM Device from the device list Only applies to digitalSTROM Devices which are inactive grey Delete Device x Device Name Floor lamp Couch Device ID 000037b4 Are you sure you want to delete this device Deleting the device will remove its configuration Therefore the device should only be deleted if itis permanently removed from this digitalSTROM installation If you want to connect the device again you might need to reregister the device manually within the power circuits tab Delete Cancel Inactive digitalSTROM Devices and those physically removed from the installation stay registered in the digitalSTROM Meter e g seasonal decorative lighting Delete no longer used digitalSTROM Devices from the system If a digitalSTROM Device is still shown as active after it has been electrically disconnected from the installation active devices are black inactive devices are grey in the device list the display can be refreshed by using Check device presence Deleted digitalSTROM Devices have to be registered again if you want to use them later in the system For this purpose you select the corresponding digitalSTROM Meter in the Hardware main section and run the command ARereg ster al devices See also chapter 5 3 1 digitalSTROM Installation Manual A11
138. tead of operating the blinds only through the push button in the room use a group for the colour group Shade grey To do so the digitalSTROM push button central push button and the corresponding digital STROM relay terminal block Shade grey must be allocated to the same group Application example wind monitor for awnings Use one group for the colour group Shade grey if all awnings on a building should be retracted as soon as a specific wind speed is exceeded By default the higher level activity Wind is called up within the entire installation whereby in addition to the awnings the blinds are also automatically retracted However if you only want to protect the awnings with the wind monitor create a group for this e g awnings and allocate awnings and wind monitors to this group This way only the awnings in the group respond to the activity Wind digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 119 132 5 6 1 Creating and renaming digitalSTROM groups Selection list Groups ts ta To All Devices Light w Shade w Video gt Blinds first floor gt Lights ground floor The colour groups available in the digitalSTROM system are displayed in the upper section of the selection list In the lower section of the selection list the groups created by the user are displayed Commands 8 Create new group Opens the dialogue to create a new group A maximum 8 groups can be
139. ting room of another power circuit all terminal blocks should be moved together via Drag amp Dropto the other room The digitalSTROM push button block is configured in the Hardware main section See also chapter 5 3 2 The digitalSTROM push button block can also be configured by click commands on the local push button See also chapter 5 3 3 If digitalSTROM Devices from different power circuits or digitalSTROM Meters are combined to form one room this room will take up one of the possible 16 rooms on both digitalSTROM Meters digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 90 132 5 4 1 Application examples for rooms Dividing a power circuit up in several rooms and allocating digitalSTROM Devices On the ground floor digitalSTROM capable ceiling lights in the two bedrooms are all installed in the same power circuit e g Light Sleeping GF However the ceiling lights in individual bedrooms are to be controlled differently Therefore you are going to rename the default room parents room and create an additional room which you are going to call children s room Then you will shift the corresponding digitalSTROM Devices from the parents room to the children s room See also chapter 5 4 5 Allocating digitalSTROM Devices from different power circuits to one room The digitalSTROM capable ceiling lights of an open eat in kitchen are installed in different power circuits e g F1
140. ty developers and not by aizo Use of other content on the Websites i e other than dS Apps including but notlimited ta imanes diaarams and texts other than for the limited nurnose of visiting the Wenhsites Accept Close 6 3 Updating Apps Activities Rooms Groups System Hardwere Help Menu Update i Use 2 Check for new updates Update Selected Se Update All install SS Update Search for updates Searches for updates for already installed digitalSTROM Server apps install update Installs the selected update on the digitalSTROM Server nstall all updates Installs all available updates on the digitalSTROM Server During system updates via USB flash drive all installed digitalSTROM Apps will be updated See also chapter 5 2 8 2 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 124 132 7 Installation checklist 1 Installing digitalSTROM components in electrical power distribution board a Install digitalSTROM Filter dSF b Install digitalSTROM Meter dSM Install digitalSTROM Server dSS option d Connect digitalSTROM Server to network e Connect dS485 bus interconnection 2 Installing digitalSTROM Devices in rooms 3 Initial operation a Initial operation of digitalSTROM Meter dSM b Initial operation of digitalSTROM Server dSS option c Check and install available system updates 4 Configuring via digitalSTROM Server a Define names of
141. update The protocol contains detailed information regarding the status of the devices installed in the digitalSTROM power circuit their firmware version and the time of the last status change After the update has ended successfully all devices should have the status Update The protocol is of considerable benefit in detailed troubleshooting or for support requests The protocol can be downloaded as an HTML file as necessary Device update status report x digitalS TROM Status of device configuration update yi Overview Device Update Task Update device configuration data tables Progress Device update completed Summary Total number of devices 24 Number of devices with updated configuration 15 Number of devices that cannot be updated q Number of inactive devices 0 Number of devices with communication errors 0 Detailed Results Device Meter Device Name Firmware Configuration Status Last Status Change dSID dSID Version ID Download Repor Close digitalSTROM Installation Manual A1121D002V010EN 12 11 2013 digitalSTROM com 62 132 Delete device Deletes the selected digital STROM Device from the device list Only applies to digitalSTROM Devices which are inactive grey Delete Device x Device Name Floorlamp Couch Device ID 000037b4 Are you sure you wantto delete this device Deleting the device will remove its configuration Therefore the device should only be deleted if itis permanently remo
142. ved from this digitalSTROM installation If you want to connect the device again you might need to reregister the device manually within the power circuits tab Delete Cancel Inactive digitalSTROM Devices and those physically removed from the installation stay registered in the digitalSTROM Meter e g seasonal decorative lighting Delete digitalSTROM Devices that are no longer used from the system digitalSTROM Devices which were deleted and later re integrated into the system can be registered again in the Hardware main section with Reregister All Devices See also chapter 5 3 1 digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 63 132 5 3 2 Check and configure the digitalSTROM Device functionality digitalSTROM Device list Devices we F alll 8 GF Fy Met Z wo Name dSID Output Mode Input mode Input 5 Wind monitor 00094903 Wind monitor Line 2 Standard 5 Motion detector 00094902 Motion detector Line 1 Standard Bedside table 0000380c dimmed Area 2 Presets 2 4 3 Leave Home 00005852 switched Leaving Coming Home Doorbell 0000582c switched Door Bell 2 Ceiling light Bedroom 000043fe dimmed Presets 0 4 Button2 Hallway 0000448e disabled Presets 0 4 2 Button 1 Hallway 00005812 disabled Area 1 Presets 2 4 Ceiling light Hallway 000044dd dimmed Device Columns Name Name of the digitalSTROM Device Unique identifier of the digitalSTROM Device Output Operating mode of the digitalSTROM D
143. vice ID 0000582c Upstream Communication 98 Downstream Communication 100 Close digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 66 132 Use this command if you have a technical problem with a digitalSTROM Device e g if it behaves erratically amp Update device status Checks the status of the selected digitalSTROM Device and updates the device list accordingly If the selected digitalSTROM Device is registered in the digitalSTROM Meter but physically unavailable it is shown as inactive grey If the digital STROM Device is physically available it is shown as active black This function allows the testing of individual devices Use Check device presence to test all digitalSTROM Devices connected to a digital STROM Meter See also chapter 5 3 1 4 Edit device properties Device Properties x Device Name Button Living room Device ID 00017ca0 Color Group W Shade Iv Push button Room push button Y Button Function 2 way Down v Show Advanced Properties v Save Cancel The dialogue allows editing the properties of the selected digitalSTROM Device The depicted example shows the device properties of a digital STROM push button block joker whereby a 2 way push button with which the shutters of a room can be closed is attached to inputs 1 and 2 See also chapter 3 4 Chapter 5 4 3 contains corresponding application examples explaining possible configurations of the digital STROM push
144. vities presets areas for the next room Configure higher level activities such as Ringing Panic etc digitalSTROM Installation Manual A1121D002VO10EN 12 11 2013 digitalSTROM com 105 132 5 5 1 Renaming calling up and setting up digitalSTROM activities Selection list digitalSTROM activities Presets CJ Bedroom J Hallway C Kitchen a j Living room 4 Light Presets g Off Fade off w Preset 1 Lighton w Preset 2 Watch TV wy Preset 3 Read g Preset 4 Relax w Area 1 on Dining table ww Shade Presets W Video Presets t Standby a Deep off 4 Sleeping Wake Up we 3 g Coming Home 3 Door Bell gt Rain No Rain Wind SE No Wind Hail gt C No Hail 11 gt Panic dh Fire i Alarm 1 Alarm 2 i Alarm 3 ff Alarm 4 X m s m Sample presets for lighting The selection list shows the created rooms and configurable presets and areas as well as the activities for the room or the whole installation Presets for areas e g Area 1 On and additional presets e g preset 12 14 are only listed if they were used accordingly in the configuration of the push button function See also chapter 5 4 2 The switch conditions and device values for activities presets and areas can be set to suit the wishes of the end user Presets can also be configured by click commands at the light switch Refer to the Setup section of the digitalSTROM user manual for the corresponding do
145. with the digitalSTROM Devices e g digitalSTROM terminal blocks via 230 V and measures the energy and performance in this power circuit digitalSTROM Server Connects the digitalSTROM installation to a home network and extends the functionality of this system digitalSTROM filter Conditions the 230 V grid for digitalS TROM communication digitalSTROM Device Makes it possible to filter any interference from non Filter digitalSTROM ready consumers in such a way so that these devices can be used without interfering with digital STROM communication digitalSTROM terminal Terminal block with an integrated digitalSTROM chip Its block function is dimming and switching digitalSTROM push Similar to the digitalS TROM terminal block its main button block function is to send signals from a push button to the digitalSTROM Meter digitalSTROM line switch digitalSTROM dimmer on a 230 V cable for table and standard lamps digitalSTROM Software on the digitalSTROM Server for configuring a Configurator digitalSTROM installation It is accessed via a web browser dSS dSF dS FD digitalSTROM Server The web based digitalSTROM Configurator serves as Software user interface with the server software This software is Open Source digitalSTROM Server app Downloadable additional functions available on the digitalSTROM Server e g stairwell lighting presence Simulation etc These additional functions are sometimes referred to s