1. Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06 10 2010 Premler EX SExtinguishing Panel USER MANUAL FALSE ALARMS DATE TIME ZONE CAUSE IF KNOWN MAINTENANCE MAINTENANCE CATEGORY OF FURTHER SIGNED LOCATION OR ACTIVITIES IN VISIT NEEDED FINDINGS FALSE ALARM ACTION ALARM AREA YES NO REQUIRED Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06 10 2010 Premler EX SExtinguishing Panel USER MANUAL ALL OTHER EVENTS DATE TIME ZONE LOCATION DETAILS OF EVENT ACTION DATE INITIALS INCLUDING CAUSE IF KNOWN REQUIRED COMPLETED Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06 10 2010
2. 9 DISA BILEMEN d 10 To Programme an Input or Output as 10 LOG BOOK qe 11 MAINTENANCE WORK Hg E A RIT e ERAS SITE UE UMS RIS WEE a 11 FALSE ALARMS PE 12 ALL OTHER EVENTS 13 Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06 10 2010 Premler EX SExtinguishing Panel USER MANUAL INTRODUCTION The Premier EX 8 is a combined 2 zone 1 area extinguishing panel and 4 zone conventional fire alarm panel It has 2 zones dedicated to the extinguishing section These are known as crossed or co incidence zones Both circuits will need to be triggered in order to activate the extinguishing circuit This kind of operation also referred to as double knock It has 4 zones for fire detection referred to as peripheral zones or fire zones These will not trigger the extinguishing circuit The Extinguishing section is designed to BSEN12094 1 2003 The fire alarm section is designed to EN54 2 1998 A1 A2 The Power Supply section is designed to EN54 4 1998 A1 A2 This design allows the same panel to protect an extinguishing area and also monitor the rest of the site for a fire The panel has an integral Manual Release call point fitted to the front of the panel The panel has monitored inputs for field connections such as manual release emergency hold etc T
3. AUTO MANUAL Used to toggle between automatic amp manual only mode GAS RELEASE Used to view or alter Gas Release Counter COUNTER RELEASE Used to view or alter Release Duration Time Counter DURATION TIME RESET INHIBIT Used to view or alter Reset Inhibit Time Counter TIME 0 9 To enter access code amp timer values ENTER To confirm new timer setting CANCEL To Save an edited time and exit from the timer set up TERMINATE Used to terminate the release duration timer Bottle output Active Internal DURATION TIMER button Used during commissioning only Note that the controls can only be used after the keyswitch has been turned to the CONTROLS ENABLED ON position As the Premier EX8 is a combined Extinguishing amp fire alarm control panel it is possible that both the extinguishing section and the fire alarm section are in alarm at the same time If this occurs the reset Fire Panel button can be used to reset the Zone alarms leaving the extinguishing section active After the pre programmed Reset Inhibit delay the reset Extinguishing System button can then be used to reset the extinguishing section If the Extinguishing system has been through it s release cycle and the zones that triggered the release are still in alarm the reset fire panel button must be pressed first to reset the zones in alarm before the reset extinguishing system button can be pressed Issue 1 2 Approved Document No GL
4. the tone If there are any faults call an Engineer Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06 10 2010 Premler EX SExtinguishing Panel USER MANUAL DISABLEMENT The Premier EX8 allows any of the following to be disabled to aid commissioning and assist routine maintenance work e Crossed zones Peripheral Zones First stage sounders Second stage sounders amp Bottle output Disabled together First Stage Relay Second Stage Relay External Equipment Relay When an zone is disabled the panel will not respond to any fault or fire signals it receives from that input When an output is disabled the panel will not activate that output This might be used if the system requires routine maintenance and the customer needs the system to continue running but doesn t want spurious false alarms or fault signals The panel will respond in the usual manner to any events in any non disabled inputs To Programme an Input or Output as Disabled Any number of inputs or outputs can be disabled but it is good practice to only disable the minimum requirement at a time Insert and turn control key to enabled position Press DISABLE button and the GENERAL DISABLEMENT LED will come on flashing fast 4 flashes then off repeated Press SELECT button The GENERAL DISABLEMENT LED will light steady and the Crossed Zone 1 Disabled LED will flash 4 quick flashes amp off The panel is now in SELECT DISABLEMENT MODE
5. AGE RELAY ACTIVE RED Lights when the second stage relay is on 2 STAGERELAY TEST YELLOW Lights when the second stage relay is in test mode 2 STAGE RELAY DISABLED YELLOW Lights when the second stage relay is disabled MANL RELEASE NPUT ACTIVE RED A manual release call point connected to the remote input has been activated MAN RELEASE INPUT FAULT YELLOW Fault in wiring to Manual release call point MAN RELEASE INPUT DISABLED YELLOW Manual release call point circuit is disabled GASFRED NPUT ACTIVE RED The panel has received a signal from the cylinder to say the gas has been released GASHARED INPUT FAULT YELLOW There is a wiring fault to the bottle s sensor EMERG HOLD INPUTACTIVE YELLOW The emergency hold input has been activated EVERG HOLD NPUT FAULT YELLOW Fault in wiring to Emergency hold switch EMERG ABORT INPUT ACTIVE YELLOW The emergency abort input has been activated EMERG ABORT INPUT FAULT YELLOW Fault in wiring to Emergency abort switch AUTOMANUAL INPUT ACTIVE YELLOW The panel has been set to manual mode by a remote input AUTOMANUAL INPUT FAULT YELLOW Fault in wiring to Auto Manual switch PRESS SWITCH INPUT ACTIVE YELLOW The bottle s pressure switch output has been activated PRESS SWITCH INPUT FAULT YELLOW Fault in wiring to bottle s pressure switch BOTTLESCALESNPUT ACTIVE YELLOW The bottle s scales switch has been activated BOTTLESCALESNPUT FAULT YELLOW Fault in wiring to bottle s scales switch ACCESSLEVEL3 YELLOW Access leve
6. PREMIER EX8 EXTINGUISHING PANEL USER MANUAL Premier EX COMBINED FIRE amp EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 amp EN54 PARTS 2 amp 4 USER MANUAL Zeta Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06 10 2010 Premler EX SExtinguishing Panel USER MANUAL INDEX INDEX dec 2 INTRODUCTION RET 3 INDICATIONS amp CONTROLS iiion Guacamole 4 TCC ALVIS P 4 Controls E 6 PANEL OPBERATIDIN Sarees cate P Fa D eases eee ad Red eee 7 N rmal Operation serisine rsrs eorias ra es aE Eara EEEREN AEE EEES PERE 7 Fire Alarm Condition Peripheral 7 What to do in the event of fire EY ERU 7 Resetting from an alarm condition eiie qe eret teda tae trud tid ve po beoe oda 7 First Stasse Alarmas TET E TN 8 Second Stage Alar 8 Hold Abort a Second 8 rct P 8 Tc bene ces paces ns nae horns ve 9 ajo T
7. T MAN 132 Author NRPJ Date 06 10 2010 Framer EX Extinguishing Panel USER MANUAL PANEL OPERATION Normal Operation With the CONTROL Key in the OFF position and under normal conditions the system will be silent and the green POWER LED illuminated The system may either be in Automatic or Manual mode of operation This will be evident by the illumination of either the Automatic or Manual LED In Manual Mode the bottle output will not be activated automatically It must be started manually by pressing a manual release call point Fire Alarm Condition Peripheral Zones The Premier EX8 signals an alarm by the following Turn on the General Fire LED Turn on the Zonal Fire Indicator Turn on internal buzzer Start any sounders connected to the panel s sounder circuits Activate the fire relay What to do in the event of a fire 1 2 7 Follow the building evacuation procedure and check that everyone has left the building safely The building fire officer or suitably trained responsible person should CAREFULLY enter the building and locate the area of the alarm from the fire alarm panel Investigate to determine the cause of the alarm Look for the detector in the zone in alarm that signalled the fire The detector that signalled an alarm will have its RED ALARM LED on If a small fire is found a suitably trained person could tackle this with a suitable fire extinguisher If a larger fir
8. The select button is used to highlight flash the section that needs to be disabled Press select button until the correct LED is flashing then press confirm The LED will now flash 4 quick flashes amp on to indicate that this section is disabled If more than one section needs to be disabled then press SELECT button again until the required zone is selected The previously disabled section will now have its disabled LED lit steady If the panel needs to be taken out of SELECT DISABLEMENT MODE eg to silence a fault on another part of the system turn the keyswitch off then back on again Once all the work has been done the zones need to be enabled again If the panel is not in SELECT DISABLEMENT MODE turn the keyswitch to controls enabled press DISABLE button Press the scroll button until the disabled section has been selected Press CONFIRM button to re enable Scroll to any other disabled section and enable in the same way When all sections are enabled again turn the keyswitch to off to return the system to normal NOTE During a Disabled condition sections of the fire alarm system will be inoperative Extra caution should be used in the disabled part of the premises Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06 10 2010 Premler EX SExtinguishing Panel USER MANUAL MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SIGNED
9. age relay output will be active To silence the sounder turn the keyswitch to ON position and press silence button The panel s internal tone and fire LEDs will remain active until the cause of the alarm has been removed and the panel has been reset A first stage alarm can be created manually by turning the keyswitch to the on position and pressing the 1 STAGE ALARM button A first stage alarm can be silenced amp reset when the panel is in automatic or manual mode Second Stage Alarm As soon as a FIRE is detected in the second Zone the second stage alarm is initiated The second stage sounder will be pulsed on for 1 second then off for 1 second This will be repeated as the timer counts down The two zone alarm LEDs will be illuminated as well as first stage alarm second stage alarm and Gas Imminent LEDs The second stage cannot be silenced and after a delay period Set by the the installer the extinguishing output will be initiated releasing the extinguishing agent and the second stage sounder will now be on constantly This will be followed by the GAS FIRED indication indicating that the extinguishing agent has been released Once the second stage alarm has been initiated it is advisable to evacuate and Seal the protected area prior to the release of the extinguishing agent Also the operation of the Yellow Manual Release call point will initiate the second stage alarm To do this lift the flap and push the op
10. ains fail or low mains LOW BATTERY YELLOW The batteries are below their final voltage amp should be replaced EARTH FAULT YELLOW Problem in system wiring At least one cable is shorting to earth EXT FAN DISABLE YELLOW The external equipment relay has been disabled SYSTEM FAULT YELLOW The CPU has crashed Or CPU reset has been pressed amp held REMOTE FAULT YELLOW The panel has received a fault input from external equipment REPEATER FAULT YELLOW The panel has lost communication with the repeater panel GEN S C FAULT YELLOW Indicated that a line fault is caused by a short circuit EXTNGUSHANT RELEASED RED The bottle output has been activated amp the gas released RELEASEMMNENT RED The panel has started the release timer and will activate bottle imminently HOLD ABOHT YELLOW An emergency hold OR emergency abort input has been activated MANUALRELEASE RED A manual release call point has been activated T STAGEALARM RED One of the crossed zones is in alarm ZUSTAGEALARM RED Both of the crossed zones are in alarm LOW PRESSURE YELLOW A drop in bottle pressure has been detected FLOODNGZONE FAULT YELLOW There is a fault relating to the flooding zone1 ie the extinguishing section of the panel MANUALMODE YELLOW The panel is in manual only mode ie will not be triggered by detectors AUTOVATICMODE GREEN The panel is in automatic or manual mode GENERAL YELLOW Lights when any section of the system is disabled GENERAL TEST YELLOW Lights
11. e Alarm Active Fault Test amp Disablement LEDs for most panel inputs amp outputs Some of these indications are not applicable for certain functions EG a fault on the 1 or 2 stage relays In such cases the LEDs are not present on the matrix See white outlines above For most functions more than one LED will light eg zone 1 fire amp COMMON ALARM The second stage sounder is pulsed and it s sounder active LED will also pulse in time with the actual sounder output The panel also has a 3 digit 7 segment display This is used to display the countdown timers during a second stage alarm Approved Document No GLT MAN 132 PAGE4 Issue 1 2 Author NRPJ Date 06 10 2010 Premler EX Extinguishing Panel USER MANUAL The Premier EX8 has the following LED indicators LED COLOUR FUNCTION MEANING POWER GREEN The panel is supplied with power either battery mains or both COMMON FIRE RED There is an alarm on the system Check which zone caused the alarm COMMON FAULT YELLOW There is a fault on the system Another LED s will be lit to indicate the specific fault BATTERY FAULT YELLOW There is a problem with the batteries Rectify or replace CHARGER FAULT YELLOW The panel is not charging the batteries usually m
12. e is found leave the building immediately and contact the fire brigade If no fire is found make a note of the detector that signalled fire and look for anything nearby that could be the cause of the activation eg cooking or use of a hot air gun etc Record findings in the fire alarm log book Resetting from an alarm condition After the relevant action has been taken the Premier EX8 fire alarm panel can be reset by the following 1 Press Start Stop sounder button This will silence the external sounders 2 Press Silence Fault Tone button This will silence the panel s internal buzzer 3 Press the Reset button This will return the panel to it s normal condition If the panel goes straight back into alarm then the cause of the alarm has not been cleared This could be a detector still exposed to smoke or a call point still in the active position Press Start Stop Sounder button followed by silence buzzer button on the panel then investigate for a call point or detector that still has its RED ALARM LED on Reset the call point or clear the smoke If the problem persists contact an engineer Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06 10 2010 Premler EX SExtinguishing Panel USER MANUAL First Stage Alarm On detection of a FIRE in either Zone 1 or Zone 2 the zone fire LED will be illuminated and the internal buzzer will be on The first stage LED and first stage sounder will be on The first st
13. erating element A second stage alarm can only be silenced amp reset when the panel is in manual mode Hold Abort a Second Stage Alarm If the hold input is activated during a second stage alarm the second stage sounder will now pulse on for 0 5 seconds then be off for 2 seconds and will repeat The counter will be reset to it s programmed value and the panel will restart it s programmed countdown when the input is released If an abort input is used the panel will abort the gas release and the panel will need to be reset Manual Mode In this mode operation Zone Fire and Fault alarms are still in operation and first amp second stage sounders will operate but the bottle output to the extinguishing agent will not operate Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06 10 2010 Premler EX SExtinguishing Panel USER MANUAL Reset To reset panel from an alarm condition press Start Stop Sounders Silence Buzzer then Reset If the panel enters the second stage alarm while in automatic mode the panel cannot be reset until the reset inhibit timer has finished it s countdown The panel can NOT be reset from a fault condition All faults are non latching so when a fault clears from the panel it will be automatically cleared from the display Faults The relevant LED will illuminate and the internal tone will sound Pressing the Silence buzzer button with the control key ON will silence
14. he panel has relay outputs for first amp second stage alarms fault amp gas fired The panel has remote inputs for Start Stop Sounders Silence amp Reset to allow the panel to be controlled remotely The panel has Open collector repeat outputs for most panel status indications eg 1 stage alarm 2 9 stage alarm Automatic mode Manual mode etc The panel has a connection for a serial repeater unit 4 wire The Premier EX8 can be in any of the following conditions Quiescent condition ie System Normal Fire condition ie a fire on one of the peripheral zones o The Premier EX8 will enter the fire condition within 1 second of a detector on a peripheral zone signalling an alarm Fault condition Disabled condition Test condition Pre activated condition o The Premier EX8 will enter the pre activated condition first stage alarm within 1 second of a detector on one of the crossed zone signalling an alarm Activated condition o The Premier EX8 will enter the activated second stage alarm condition within 1 second of the second crossed zone signalling an alarm Released condition o The Premier EX8 will enter the released condition bottle output activated within 1 second of establishing the activated condition OR after the delay configured in the bottle output timer WARNING Access to live components inside this fire alarm enclosure The key to open the door to gain internal access should be held by authorised perso
15. l 3 selected GAS RELEASE COUNTER YELLOW Gas release counter is being displayed on 3 digit display RELEASE DURATION TIVE YELLOW Release duration time is being displayed on 3 digit display RESET NHBITTIVE YELLOW Reset inhibit time is being displayed on 3 digit display Author NRPJ Issue 1 2 Approved Document No GLT MAN 132 Date 06 10 2010 Premler EX SExtinguishing Panel USER MANUAL Controls The Premier EX8 has the following controls LABEL USE START STOP 1 Used to silence the sounders in an alarm or to manually start the FIRST STAGE SOUNDER STAGE sounders to evacuate building SILENCE BUZZER Used to silence the panel s internal buzzer in a fault or alarm condition RESET FIRE Used to reset the Fire detection section of the Control panel le Zones 1 to 6 PANEL RESET Used to Reset the extinguishing section of the Control panel EXTINGUISHING SYSTEM LED TEST To check that all indicator LEDs are working Use as part of the daily weekly fire alarm inspection DISABLE Used to access Disablement mode DISABLE Used to scroll to select which part of the system to disable SELECT DISABLE Used to confirm disablement of the highlighted part of the system CONFIRM TEST Used to access test mode TEST SELECT Used to scroll to select which part of the system to test TEST CONFIRM Used to confirm test mode of the highlighted part of the system
16. nnel only Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06 10 2010 Premier EX SExtinguishing Panel USER MANUAL INDICATIONS amp CONTROLS Indications Here is the fascia for the Premier EX8 panel FIRE FAULT TEST DISABLED GAS RELEASE COUNTER gt p POWER B au CMT GAS RELEASE COUNTER SEC 2 COMMON POWER EXT FAN RELEASE Lee te B Ed i M a DURATION SEC RESET INHIBIT Hue COS oa TIME MINUTES FIRE FAULT TEST DISABLED gt gt gt m gt e T e gt gt EXTINGUISHANT ME easey B RELEASE IMMINENT HOLD ABORT MANUAL RELEASE 1ST STAGE 2ND STAGE P B LOWPRESSURE FLOODING ZONE FAULT manuau MANUAL MODE AUTOMATIC MODE ii ACTIVE FAULT TEST DISABLED 1STSTAGESNDR N 2NDSTAGESNDREe BOTTLE OUTPUT p 18 RELAY gt I 2ND STAGE RELAY e oy NERAL CONTROLS GEI DISABLEMENT TEST ACTIVE ACTIVE FAULT MANRELEASEE GAS FRED 175175 j ABORT AUTO MANUAL PRESSURE SWITCH BOTTLESCALES DISABLED gt geta ALARM SYSTEMS by GLT Exports Ltd MADE IN THE UK TStSIAGE RESET SE LED SOUNDERS PANEL Es TEST Each function has its own indication LED There ar
17. when any section of the panel is in test mode CONTROLSACTIVE YELLOW Lights when controls enabled keyswitch is on ZONE 1 6ARE RED Lights when one of the detection zones is in alarm ZONE 1 6FAULT YELLOW Lights when one of the detection zones has a fault ZONE 1 6TEST YELLOW Lights when one of the detection zones is in test mode ZONE 1 6DGABLED YELLOW Lights when one of the detection zones is in disablement mode T STAGE SNDR RED Lights when the first stage sounder is on T STAGESNDRFAULT YELLOW Lights when the first stage sounder has a wiring fault T STAGESNDRTEST YELLOW Lights when the first stage sounder is in test mode T STAGE SNDR DISABLED YELLOW Lights when the first stage sounder is disabled 2 STAGE SNDRACTIVE RED Lights when the second stage sounder is on 2 STAGE SNDRFAULT YELLOW Lights when the second stage sounder has a wiring fault ZU STAGE SNDRTEST YELLOW Lights when the second stage sounder is in test mode 29 STAGE SNDRDSABLED YELLOW Lights when the second stage sounder is disabled BOTTLEOUTPUT ACTIVE RED Lights when the bottle output is on BOTTLEOUTPUT FAULT YELLOW Lights when the bottle output has a wiring fault BOTTLEOUTPUT DISABLED YELLOW Lights when the bottle output is disabled STAGE RELAY ACTIVE RED Lights when the first stage relay is on T STAGE RELAY TEST YELLOW Lights when the first stage relay is in test mode T STAGE RELAY DISABLED YELLOW Lights when the first stage relay is disabled 2 ST