Home

PKC MKC

image

Contents

1. DIG 1 8 A DIG 2 9 e e DIG 3 10 e e Fig 8 AUXILIARY INPUT WIRING NOTES 11 1 This input is not isolated from measuring input double or reinforced insulation between instrument output and power supply must be assured by the external instrument 2 Don t run input wires together with power cables Fig 9 LOGIC INPUTS WIRING 3 Pay attention to the line resistance a high line resistance may cause measurement errors 8 NOTES 1 Do not run logic input wiring together with power cables 2 Use an external dry contact capable of switching 0 5 mA 5 V DC 3 The instrument needs 110 ms to recognize a contact status variation 4 The logic inputs NOT isolated by the measuring input double or reinforced insulation between instrument output and power supply must be assured by the external element D CURRENT TRANSFORMER INPUT 14 Current 15 transformer Load Fig 10 CURRENT TRANSFORMER INPUT WIRING This input allows you to measure and display the current running in the load driven by a time proportional control output during the ON and OFF periods of the output cycle time By this feature it is also available the Output failure detection function see page 66 NOTES 1 This input is not isolated from measuring input A double or reinforced insulation between instrument output and power supply must be assured by the exter
2. T C Ranges type 22 150 2550 F IEC 584 1 S 23 60 3200 IEC 584 1 24 60 3200 IEC 584 1 25 32 3300 IEC 584 1 G 26 0 4170 F D 27 0 4170 F 28 0 4170 Ni 29 0 2000 F NOTE for TC type B the accuracy is guaranteed for tempera ture higher than 500 950 F B RTD Resistance Temperature Detector Input for RTD Pt 100 3 wire connection C F selectable Measuring current 140 typical Line resistance automatic compensation up to 20 Q wire with no measurable error 105 STANDARD RANGES TABLE Input type Ranges RTD Pt 100 Q 15 200 850 IEC 571 30 330 1560 C LINEAR INPUTS Read out keyboard programmable between 1999 and 9999 Decimal point programmable in any position STANDARD RANGES TABLE Input type impedance 37 0 60 mV 38 12 60 31 0 20mA 32 4 20mA suu 33 0 5 V E gt 200 35 S gt 400 ka 36 2 10 V AUXILIARY INPUT Type NOT isolated linear input Function Programmable as remote set point input or bias on the local set point Read out keyboard programmable between 1999 and 9999 Temperature drift lt 300 ppm Sampling time 500 ms STANDARD RANGES TABLE Input type impedance Accuracy ELM 9 5 V gt 200 ka oF s 0 10 M gt 400
3. LII Ll Servo LII Ti high limit calcolated positioning L u by smart PLL LUL Lu LI Feedback RCG high limit calcolated Z ur calibration pr smart FLU T LAU L P F LII ET Groups Group u 7 default data loading 1 data loading When a run time parameter group is selected by keeping depressed for more than 8 seconds the MENU pushbutton the display will show Use the MENU pushbutton for horizontal scrolling gt Use the FUNC pushbutton for vertical scrolling Use the MAN pushbutton for going back to the previous display MKC PKC Cr Ce Ch Gi CA Sb iC CO GE on ao O O C N mk O CO Oo A C a Configuration Configuration Configuration Configuration Configuration Configuration Configuration Configuration Configuration Configuration Starting selection Safety code Default config Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 End Meas input Outputs Control out conf Aux cont out conf Digital conf Other conf r E F IL r GIH a Litre Litre ww m r prr f rik 8 L LVL f TL FK Loris F Pd IL r Lu D E Line Outi Split Ltr 1 s
4. 75 bRHh bAYL HIGH THRESHOLD USED WHEN ALARM 4 IS A BAND ALARM 76 LOW THRESHOLD USED WHEN ALARM 4 IS BAND 76 GONTROL ACTION 79 time group 4 CONTROL PARAMETER 78 EXTERNAL CONTROL OF AUTO MAN EXTERNAL CONTROL OF LOCAL REMOTE SETPOINT SELECTION 84 EXTERNAL CONTROL REVERSE DIRECT OUTPUT ACTION SELECTION 84 FEEDBACK POTENTIOMETER CALIBRATION ENABLING 93 Run time group 8 FEEDBACK POTENTIOMETER CALIBRATION 93 FEEDBACK HIGH LIMIT CALIBRATION 94 FEEDBACK LOW LIMIT CALIBRATION 93 OFD ALARM ACTION OFD ALARM CONFIGURATION RATE OF CHANGE FOR POSITIVE SETPOINT VARIATION RATE OF CHANGE FOR NEGATIVE SETPOINT VARIATION 83 I IE E n gt gt gt lt UJ fU 3 Mis See wooed t3 03 Q LC Ln in Ln 5 ae lt Run time Menu hidden SMART LIMIT VALUE 95 ALARM 1 HYSTERESIS ALARM 2 HYSTERESIS ALARM 3 HYSTERESIS uuu hee ALARM 4 HYSTERESIS HYSTERESIS INTEGRAL PRE LOAD MAIN CONTROL OUTPUT HIGH LIMIT MAIN
5. These instruments are capable to detect on the auxiliary input the sensor leads break condition When the sensor leads break condition is detected the instrument shows OPEn on the lower display NOTE the leads break condition can be detected only if the selected range has a zero elevation 4 20 mA or 1 5 V or 2 10 V 100 NOTES 1 The fault conditions on the auxiliary input will be displayed only if the relative indication has been selected see Display function at page 62 2 When a fault condition different from overrange or under range is detected on the auxiliary input the alarms the power output and the analog retransmissions operate as in presence of an underrange condition ERROR MESSAGES At the end of each configuration parameter group modifiction the instrument check the new parameters values At instrument start up in operative mode all the parameters are checked If an error is detected the instrument will show on the upper display the parameter family CnF x for configuration parameters GRP x for run time parameters CAL for calibration parameters where x is the number of the specific group where the error has been detected on the midle display the Err indication on the lower display for configuration or run time parameter it will show the mnemonic code of the group with the wrong parameter setting for calibration parameter it will show the mnemonic code of the
6. W To come back to the AUTO mode depress MAN push button for more then 1 sec or toggle the logic input The transfer from AUTO to MANUAL is bumpless this function is not provided if an output value has been selected at configuration parameter A UL C G04 The transfer from MANUAL to AUTO is bumpless or bumpless balanceless the bumpless feature is not provided if integral action is excluded If transfer from AUTO to MANUAL is performed during the first part of SMART algorithm TUNE when returning in AUTO the device will be forced automatically in the second part of the SMART algorithm ADAPTIVE At power up the device starts as configured at St Fn 06 configuration parameter NOTES 1 When auto manual control mode is selected by logic input at power up the instrument will start in accordance with the logic input status If the logic input status requires the manual mode the instrument will verify the St Fn C G06 parameter setting and if St Fn 06 is equal to Auto an or Cnd A the power output will be set to zero otherwise the power output will be set equal to the last value prior to power shut down 2 If the instrument is configured for one control output the control output is a servo motor type close or open loop and device starts up in manual mode the following action may occur 2 A The valve remains in the same position if St Fn C G06 an
7. ur g BAHL d p 9 _ 1 j E Lit n Ld D Ld 11 un Lt Lod 1 Li N as Lh Tn Lt i LS un 21 E Run time Group 4 control param o LI LI 1 k L Fiir Manual Reset of the alarms 1 70 L m Alarmi threshold 2 Lower threshold when AL1 is a band alarm 1 1 s Higher threshold when AL1 is a band alarm Li I 1 2 I threshold 7n Lower threshold when AL2 is a band alarm Li J Li 1 Ld Higher threshold when AL2 is a band alarm _ I3 C3 rs n _ L Alarm 3 threshold n Lower threshold when AL3 is a band alarm Li Higher threshold when AL3 is a band alarm 1 Alarm 4 threshold Lower threshold when AL4 is a band alarm higher threshold when AL4 is a band alarm OFD low alarm threshold OFD high alarm threshold Alarm 1 hysteresis Alarm 2 hysteresis Alarm 3 hysteresis Alarm 4 hysteresis Group 3 default data loading Proport band Hysteresis ON OFF control Integral time Derivative time Integral preload Relative gain of the secondary output Overlap dead band Control action Group 4 defaul
8. rSt Input contact used to reset acknowledge alarm Reset when logic level is 1 rE dr Input contact used for Reverse Direct control action selection Direct when logic level is 1 NOTE See also NOTE 2 of the d1 Fn Logic input 1 function C H01 parameter C H04 Logic input 2 contact status This parameter will be available only when d2 Fn C H03 is different from nonE Upper display CnF 5 Lower display d2 St Range CLSd The input is at logic level 1 when contact is closed OPEn The input is at logic level 1 when contact is open C H05 Logic input 3 function This parameter will be available only when input contact option is fitted Upper display CnF 5 Lower display d3 Fn Range nonE Input contact not used SP1 2 Input contact used for SP SP2 set point selection see note 2 SP3 4 Input contact used for SP3 SP4 set point selection see note 2 SP L r Input contact used for Local Remote set point selection Remote when logic level is 1 Au A Input contact used for Auto Manual selection Manual when logic level is 1 53 O LI Input contact used for output limiter activation Output limited when logic level is 1 Input contact used to stop input sampling Hold function Stop sampling when logic level is rSt Input contact used to reset acknowledge alarm Reset when logic level is 1 rE dr Input contact used fo
9. eeozlecteonie 170 1U0 XKC 001 04 99 B J USER MANUAL PKC MKC INDEX MOUNTING REQUIREMENTS OUTLINE AND CUT OUT DIMENSIONS CONNECTIONDIAGRAMS 4 PRELIMINARYHARDWARESETTINGS 17 SECURITY CODE SETTING 22 RUNTIME AND CONFIGURATIONMODE 25 General notes about graphic symbols Keyboard description CONFIGURATIONMODE RUNTIME MODE Display function Indicators Bargraph description OUT failure detection function O Direct access to the set point Manual function Serial link Lamp test SMART function Hold function Parameter protection RUNTIME PARAMETER MODIFICATION ERRORMESSAGES GENERALINFORMATIONS MAINTENANCE DEFAULTPARAMETER ALPHANUMERIC INDEX OF THE DISPLAYINDIGATHON A 2 b 1 MOUNTING REQUIREMENTS Screw bracket Gasket Select a location for instrument mounting where minimum vibrations are present and the ambient temperature is within 0 and 50 C 32 and 12232 The instrument can be mounted on a panel up to 15 mm thick with a cutout of 92 x 45 mm PKC or 92 x 92 MKC For outline and cutout dimensions refer to Fig 2 The surface texture of the panel must be better than 6 3 umm The instrument is shipped with rubber panel gasket 50 to 60 Sh To assure the IP65 and NEMA 4 protectio
10. C E L C F09 and C E H C F10 NOTE When the MAIN output is a servomotor type the instrument shows for this output the feedback position instead of the output in percent f Push FUNC push button again the lower display will show S followed by the SECONDARY control output value in the range 0 0 19 0 for feedback to 99 9 shows that the control output is gt 100 0 within the scale configured by SC E L C F15 and SC E H C F 16 NOTE When the secondary output is a servomotor type the instrument shows for this output the feedback position instead of the output in percent g Push FUNC push button again the lower display will show the value of the auxiliary input if configured Pushing FUNC push button again the display will come back to the control output value indication All the seven types of visualization are not bound to a time out unless OFD output failure detection is in not acknowledged alarm condition In this situation the instrument forces the indication described at point d and if a different indication is required it restores this indication after time out see t out 110 NOTES 1 The previous informations will be displayed only if the relative function has been previously configured 2 After parameter modification or monitoring the instrument comes back to the normal display mode wit
11. I J zn cy n L 1 1 a Li un E I F DL Lo Lt nT n N r3 Run time Group 7 Serial link param m LI Serial link protocol 1 type Serial link address Alarm 1 config Serial link baude rate Alarmi action Serial link byte format Alarmi Standby function Group 7 default data loading Alarm 2 type Alarm 2 configuration Alarm 2 action Alarm 2 Standby function Alarm 3 type Alarm 3 configuration Alarm 3 action Alarm 3 Standby function Alarm 4 type Alarm 4 configuration Alarm 4 action Alarm 4 Standby function OFD Alarm configuration OFD Alarm action Group 6 Default data loading r H r L Run time Run time Run time Group 8 Group dF Menu hidden Feedback poten Default param Smart limits calibration D ri _ xit li oO LITE e gt ba oL LII Ci Enabe mac LU Mn 8 j calcolate TEN os by smart loading M OL 0 nr Lift LII Eh servo LII J Max Pb low limit calcolated 117111 positioning ore by smart TL AL FORNA I un Ci Min Ti low limit calcolated I 1 1 calibration E ou by smart FOLL
12. r C13 high threshold used when the alarm 4 is a band alarm This parameter is available only when the alarm 4 is configured as band alarm A4 tP rF 13 bAnd Upper display Gr 3 Lower display bA4 h Range from 0 to 1000 digits NOTE The bA4 L and bA4 h values are algebraically added to the operative set point in order to obtain the band limits r C14 Output failure detection low alarm threshold This parameter is available only when the option is present and 110 is equal to or AC OF or SC On or SC OF Upper display Gr 3 Lower display A L Fd Range from 0 to Fd HS C 112 NOTES 1 The device is in alarm status when the current measured during the ON status of the load is lower than this threshold 2 The OFD output failure detection alarm threshold resolution values is equal to 0 1 A for range up to 25 A and 1 A for range up to 100 3 The hysteresis on this threshold values is fixed to 196 of fsv r C15 Output failure detection high alarm threshold This parameter is available only when the option is present and 110 is equal to or AC OF or SC On or SC OF Upper display Gr 3 Lower display A H Fd Range from 0 to Fd HS C 112 NOTES 1 The device is in alarm status when the current measured during the OFF status of the load leakage current is higher than this threshold 2 T
13. HSA2 1 HSA3 1 HSA4 1 Run time group 4 r dxx PARAMETER DEFAULT VALUE Pb 40 HYS 0 5 96 ti 4 00 mm ss td 1 00 mm ss IP 50 0 If only one control output is configured 0 0 If two control outputs without split range are configured r Gn OLAP Cn Ac ArW S tt S db OLL OLH r P C CY S OLL S OLH S r P SC CY rL rH Grd1 Grd2 tOL E A 1 00 0 rEV Run time group 5 r Exx PARAMETER DEFAULT VALUE 100 1 00m 5 0 0 100 0 Inf 15 s If relay output 25 If SSR output 0 0 100 0 Inf 15 If relay output 2 s If SSR output Initial range value Final range value Inf Inf Inf On E Lr On E rd On Run time group 6 r Fxx PARAMETER DEFAULT VALUE A1 tP Proc A1 Cn H A 1 A1 St OFF A2 tP Proc A2 Cn H A A2 Ac rEV A2 St OFF 5 A4 tP Proc A4 Cn H A A4 Ac rEV A4 St OFF Fd Cn A Fd Ac Run time group 7 r Gxx PARAMETER DEFAULT VALUE S L Pr bUS S L Ad S L bd 19 20 S L bF Run time group 8 The default calibration data are the complete potentiometer travel AFTER THE DEFAULT DATA LOADING OF THIS GROUP IT IS NECESSARY TO PERFORM THE PROPER CALIBRATION Run time group Hd r Lxx PARAMETER DEFAULT VALUE Pb Lo 1 0 Pb Hi 300 0 ti Lo 00 20 m
14. LOGIC INPUTS The instrument may be supplied with 3 logic inputs each one of them can be programmed as Set point selection SP SP2 Set point selection SP3 SP4 Local remote set point selection Auto manual selection 106 Output limiter activation Data Hold of the measured value Manual reset of the alarms acknowledge Reverse direct control action Input type Contact closure voltage free Active logic level Close or open programmable CURRENT TRANSFORMER INPUT FOR OUT FAILURE DETECTION The instruments equipped with this feature are capable by means of a CT to detect and signal a possible failure of the line driven by a control output programmed as a time propor tioning output see OUT failure detection Input range 50 mA AC Scaling programmable from 10 A to 100 A with 1 A step Resolution for full scale up to 25 A 0 1 A for full scale from 26 A to 100 A Minimum duration of the period ON or OFF to perform the measurement 120 ms SET POINTS This instrument allows to use up to 4 set points SP SP2 SP3 SP4 The set point selection is possible only by logic input Set point transfer The transfer between one set point to another or between two different set point values may be realized by a step transfer or by a ramp with two different programmable rates of change ramp up and ramp down Slope value 1 200 eng unit min or step Set points limiter
15. NOTES oF If option is not mounted or main control output is linear If option is mounted ALPHANUMERIC INDEX OF THE DISPLAY INDICATIONS RUN TIME PARAMETERS pr ACEr ono DDO Run time group 5 AUXILIARY CONTROL PARAMETER page 80 OUTPUT FAILURE DETECTION HIGH ALARM THRESHOLD ees 76 OUTPUT FAILURE DETECTION LOW ALARM THRESHOLD Run time group 6 ALARM SETTING ALARM 1 ACTION ALARM 1 CONFIGURAT ALARM 1 STANDBY FU ALARM 1 ALARM 2 ACTION ALARM 2 CONFIGURAT A A A A A LARM 2 STANDBY FU LARM 2 LARM 3 ACTION m 70 m ron p E F Fr Lin F5 m F p ALARM S TYPE u uuu u ALARM 4 ACTION ALARM 4 CONFIGURATION ALARM 4 STANDBY FUNCTION ALARM 4 TYPE ALARM 1 THRESHOLD ALARM 2 THRESHOLD ALARM 3 THRESHOLD ALARM 4 THRESHOLD Run time group 3 ALARM THRESHOLD AND HYSTERESIS VALUE ANTIRESET WINDUP HIGH THRESHOLD USED WHEN ALARM 1 IS A BAND ALARM iiciin 74 LOW THRESHOLD USED WHEN ALARM 1 ISA BAND ALARM cicanie 7 HIGH THRESHOLD USED WHEN ALARM 2 IS A BAND ALARM 74 LOW THRESHOLD USED WHEN ALARM 2 IS A BAND ALARM 74 HIGH THRESHOLD USED WHEN ALARM 3 IS A BAND ALARM cernes 75 LOW THRESHOLD USED WHEN ALARM 3 IS BAND ALARM
16. from 1999 to 9999 for linear input Input range 31 to 38 from 0 to 9999 for linear input with square root extraction from fi In L read out initial scale value C d05 to full range value for TC RTD input NOTES 1 Changing the value of this parameter the brG H bargraph full scale value 104 and rH set point high limit r E13 parameters will be realigned to it 2 The programmed input span in absolute value must be greater than 300 or 550 F for TC inputs 100 C or 200 F for RTD inputs 100 digits for linear inputs C d07 Main input offset adjustment Upper display CnF 1 Lower display OFSt Ranges from 500 to 500 NOTE the decimal point will be automatically positioned as selected for the main input Read out curve OFSt Adjusted curve Input C d08 Filter on the displayed value Upper display CnF 1 Lower display dS FL Ranges from 0 no filter to 8 seconds NOTE this is a first order digital filter applied to the read out of the main input C d09 Auxiliary input function Upper display CnF 1 Lower display A In F Range nonE Input not used rSP Input used as remote set point input bIAS Input used as bias for local set point NOTES 1 When auxiliary input option is not mounted the middle display will show not present 2 The parameter L r O C d16 will be forced to
17. or Ain or SECn Upper display Gr 3 Lower display AL2 Range in engineering units within the span limits for process alarm from 1000 to 1000 digits for deviation alarm from 0 096 to 100 0 for control output alarms NOTE The span limits are configured by In L C d05 and In H C d06 74 06 Low threshold used when the alarm 2 is a band alarm This parameter is available only when the alarm 2 is configured as band alarm A2 tP rF 05 Upper display Gr 3 Lower display bA2 L Range from 0 to 1000 digits 07 high threshold used when the alarm 2 is a band alarm This parameter is available only when the alarm 2 is configured as band alarm A2 tP rF 05 Upper display Gr 3 Lower display bA2 h Range from 0 to 1000 digits NOTE The bA2 L and bA2 h values are algebraically added to the operative set point in order to obtain the band limits r C08 Alarm 3 threshold This parameter is available when alarm 3 is configured as process deviation main power output or secondary power output alarm A3 tP rF 09 Proc or dEV or Ain or SECn Upper display Gr 3 Lower display AL3 Range in engineering units within the span limits for process alarm from 1000 to 1000 digits for deviation alarm from 0 0 to 100 0 for control output alarms NOTE The span limits are configu
18. 49 SFUL OUTPUT SAFETY VALUE SAFn SMART FUNCTION eese 57 SERVOMOTOR TYPE SPRL OPERATIVE SETPOINT ALIGNEMENT START es 58 SPdS SETPOINT DISPLAY 59 SPLE SPLIT RANGE 41 Sr bH SERVO BEHAVIOR WHEN THE POWER OUTPUT IS LIMITED ccr u etes 59 7 ZJg oEuEcreontc Ero Electronic S r l Via E Mattei 21 28100 Novara ltaly Tel 39 0321481111 Fax 39 0321481112 eroelectronic ero eurotherm co uk BENELUX ERO Electronic Benelux SA NV Rue Val Notre Dame 384 MOHA 4520 WANZE Tel 085 274080 Fax 085 274081 ero electronic skynet be BRASIL ERO ELECTRONIC DO BRASIL Industria e Comercio Ltda Rua Garibaldi 659 Conj 202 90035 050 PORTO ALEGRE Tel 051 2214888 Fax 051 2214734 erobr nutecnet com br CHINA TIANJIN VEGA COMPANY Ltd TAIF Hebei District 300232 TIANJIN Tel 022 26273296 Fax 022 26273297 FRANCE ERO Electronic SARL Zac du Ch ne I 34 Rue du 35 me R giment d Aviation 69673 BRON CEDE Tel 0478267979 Fax 0478267800 GERMANY ERO Electronic GmbH Ottostrasse 1 65549 LIMBURG A D LAHN Tel 06431 95680 Fax 06431 57493 NETHERLAND ERO Electronic Nederland Ganieelan 4 2404 CH Alphen a d Rijn Tel 0172 420400 Fax 0172 420395 sales eroelectronic nl SOUTH AFRICA ERO Electronic S A Pty Ltd Agro House 1343 Spokeshave Avenue Stormill Ext 2 RO
19. NOTE The SF Cn Output safety condition C G07 has the priority on A I Sc auxiliary input safety condition C d15 C d16 Local remote set point operative mode This parameter is available only when auxiliary input is configured Upper display CnF 1 Lower display L r O fi Range ALG when the transfer from remote to local set point is performed the local set point value will be aligned to last remote set point value n ALG when the transfer from remote to local set point is performed the local set point value will not be changed The programmed ramps Grd1 r E14 and Grd2 r E15 may be activated NOTES 1 The selected local set point will be changed even if it is software protected 2 The parameter is forced to if A In F auxiliary input function C d09 is equal to blAS and 1 auxiliary input activation mode C d14 is equal to Cnd A General note on configuration group 1 Exiting from the configuration group 1 the instrument verifies automatically the programmed span for the linear input If it is wrong the device will show LAD 1 mre CONFIGURATION GROUP 2 C Exx OUTPUTS CONFIGURATION n C E01 OUT 1 function Upper display CnF 2 Lower display O1 Fn Range nonE Output not used Ain Time proportional main control output SECn Time proportional secondary control output ALr 1 Alarm 1 output Eun 1 Event 1 output C
20. Upper display Gr 5 Lower display S r P Ranges from 0 1 s to 25 0 s Above this value the display shows Inf meaning that no limit is imposed 82 NOTES 1 This parameter will be active even if device is configured for On OFF control 2 During the transfer from AUTO to MANUAL if this action is programmed as a not bumpless transfer the S r P function will be ignored and the output will step up to the value set by A UL C G04 parameter r E11 Secondary output cycle time This parameter is available when a time proportional secondary control output is configured Upper display Gr 5 Lower display SC CY Range from 1 to 200 s r E12 Set point low limit Upper display Gr 5 Lower display rL Range From fi In L C d05 to rH r E13 NOTES Whenever fi In L C d05 has been modified the following occurs 1 rL will be realigned to it 2 if the set point values are out of the new limits the set point automatically assumes the default value r E13 Set point high limit Upper display Gr 5 Lower display rH Range from rL r E12 to In H C d06 NOTES Whenever In H C d06 has been modified the following occurs 1 rH will be realigned to it 2 if the set point values are out of the new limits rH automatically assumes the default value 14 Rate of change for positive set point variations Upper display Gr 5 Lower display Grd1
21. or St Fn C G06 Cnd A or St Fn C G06 Cnd b and A UL C G04 2 B The valve will be moved to the value set in A UL if St Fn C G06 Cnd b and Ani UL C G04 is different from SERIAL LINK The device can be connected to a host computer by a serial link The host can put the device in LOCAL functions and parameters are controlled via keyboard or in REMOTE functions and parameters are controlled via serial link The REMOTE status is signalled by the REM LED This instrument allows to modify the operative and configura tion parameters via serial link The necessary conditions to implement this function are the following 1 the serial parameters see Run time group 7 should be properly configured 2 the device must be in the run time mode 3 when it is desired to modify configuration parameter the dip Switch V101 3 should be set to OFF configuration parameter enabled During configuration parameter downloading the device goes in open loop with all output in OFF state At the end of configuration procedure the device performs an automatic reset and then returns to close loop control LAMP TEST When it is desired to verify the display efficiency put the instrument in normal display mode and push W and MENU push buttons for more than5 s The instrument will turn ON with a 50 duty cycle all the LEDs of the display we define th
22. 0 0 nor nO 0 100 bEFr nor 4 20 mA No filter If option is not mounted If option is mounted 4 20 mA No filter Configuration group 3 C Fxx VALUE NOTES No decimal figure S SCL SC dP No decimal figure SC E L 0 SC E H 100 SC A C bEFr Configuration group 4 C Gxx PARAM VALUE NOTES S Fn Enb Cn tP Pld An F Enb A UL bu R A t t bufi St Fn Cnd b SF Cn Std SF UL 0 0 Configuration group 5 C Hxx PARAM VALUE NOTES d1 Fn 5 1 2 d1 St CLSd d2 Fn SP3 4 d2 St CLSd d3 Fn d3 St CLSd E1 Fn E1 St E2 Fn E2 St E3 Fn E3 St E4 Fn E4 St PARAM G brG O brG brG L brG H brG d SP AL SP dS Sr bH SS tr t out Fd Fn Fd HS fi In E CLSd CLSd Au A CLSd SP L r CLSd Configuration group 6 C Ixx VALUE DEv NOTES If option is not mounted or main control output is linear If option is mounted Fd Ou nonE TABLE 2 Configuration group 1 C dxx PARAM VALUE NOTES Ln Fr 60 Hz In t 18 TC K with F In d No decimal figure In S 91 Disabled fi In L 150 se In H 2500 F OFSt 0 dS FL 0 No filter A In F RSP Remote set point A In t 4 20 mA A In L 32 F A In H 1832 A LFL 0 No filter A LAA 1 nonE L r O n ALG PARAM O1 Fn O2 Fn O3 Fn O4 Fn S tP FEEd O5 Fn O5 rn O5 Lr O5 Hr O5 FL O6 Fn O6 rn O6 Lr fiAi
23. 32 screw terminals screw M3 for cables from 0 25 to 2 5 or from AWG 22 to AWG 14 with connections diagram and safety rear cover Dimensions according to DIN 43700 48 x 96 mm depth 128 mm for PKC model 96 x 96 mm depth 128 mm for MKC model Weight 500 g for PKC model 600 g for MKC model Power supply 100 V to 240 V AC 50 60 Hz 15 to 10 of the nominal value 24 V AC DC 10 of the nominal value 103 Power consumption 15 VA max for PKC model 16 VA max for MKC model Isolation voltage 2600 V rms according to IEC 1010 1 Display updating time 500 ms Sampling time 125 ms for linear inputs 250 ms for TC and RTD inputs Resolution 30000 counts Accuracy 0 2 f s v 1 digit 25 C ambient tempera ture NOTE for TC type B the accuracy is guaranteed for temperature higher than 500 C 950 F Common mode rejection 120 dB 50 60 Hz Normal mode rejection 60 dB 50 60 Hz Electromagnetic compatibility and safety requirements This instrument is marked CE Therefore it is conforming to council directives 89 336 reference harmonized standard EN 50081 1 and EN 50082 2 and to council directives 73 23 EEC and 93 68 EEC reference harmonized standard EN 61010 1 Installation category 1 Temperature drift CJ excluded lt 200 of span for mV and TC ranges 3 4 7 18 19 22 lt 300 ppm C of span for mA V lt 250 of span for TC r
24. C d14 Auxiliary input activation mode This parameter is available only when auxiliary input is configured Upper display CnF 1 Lower display Range The auxiliary input activation is controlled by external contact front key or serial link Cnd A The auxiliary input activation is controlled by its status The device works with local set point when auxiliary input is out of range while it works with remote set point or bias when it is within range NOTE The parameter local remote set point operative mode C d16 will be forced to n ALG if A In F auxiliary input function C d09 is equal to and 1 auxiliary input activation mode C d14 is equal to C d15 Auxiliary input safety condition This parameter is available only when auxiliary input is configured and A i Ani C d14 is equal to Upper display CnF 1 Lower display 1 5 Range nonE when the auxiliary input is out of range the instrument operates as in presence of the min or max auxiliary input value Cnd A when the auxiliary input is out of range the control output goes to safety value SF UL output safety value C G08 35 If servomotor open loop control drive is configured the Safety value SF UL C G08 has no effect and the instrument operates in accordance with SF Cn Output safety condition C G07 parameter setting
25. NOTE about the split range This function allows you to drive by the same control action two physical outputs two actuators with different bias and gain The relation between the Calculated Power Output and the resulting real outputs are shown below Real PWR First split Output output MAIN 100 Second split output Secondary 0 Calculated 100 PWR Output A C B D where for the first split output MAIN Bias 1 A Gain 1 100 B A For the second split output SECONDARY Bias 2 C Gain 2 100 D C FOR EXAMPLE Let s suppose that the first split output operates from 0 to Standard curve 33 3 of the calculated output while the second one operates from 33 3 to the 100 of the calculated output 42 Real PWR Output 100 First split nde output MAIN Standard curve y Second split output Secondary Calculated 0 100 PWR Output 33 3 Where A 0 B 33 3 D 100 We will set Bias 1 0 Gain 1 100 33 3 0 Bias 2 33 3 Gain 2 100 100 33 3 1 5 The bias and gain of the two split outputs are the following C bS C F03 is the Bias 1 applied to the main output AC Gn C F02 is the Gain 1 applied to the main output SC bS C F05 is the Bias 2 applied to the secondary output SC Gn C F04 is the Gain 2 applied to the secondary output C F02 Main control ou
26. Range from 1 to 200 digits per minute Above this value the display shows Inf and the transfer will be a step change r E15 Rate of change for negative set point variations Upper display Gr 5 Lower display Grd2 Range from 1 to 200 digits per minutes Above this value the display shows Inf and the transfer will be a step change r E16 Time out for the soft start This parameter is available when at least one output is configured as control output and no logic input is configured as Output limiter activator Upper display Gr 5 Lower display tOL Range from 1 to 540 min Above this value the display shows InF and the limiting action is always active NOTE The tOL can be alwais modified but the new value will be used only at the next device power up r E17 External control for AUTO MANUAL mode This parameter is available when one of the logic inputs is configured for Auto Manual selection Upper display Gr 5 Lower display Range On only OFF or serial link only 18 External control for local remote set point selection This parameter is available when one of the logic inputs is configured for Local Remote set point selection and 1 C d14 is equal to Upper display Gr 5 Lower display E Lr the Auto Manual selection is made by logic input the Auto Manual selection is made by Man key Range On the local remote set point selection is made by e
27. Relay energized or SSr 1 in alarm condition Reverse action Relay energized or SSr 1 in non alarm condition r F08 Alarm 2 stand by mask function This parameter is available only when OUT 2 is configured as alarm 2 output O2 Fn C E02 ALr 2 Upper display Gr 6 Lower display A2 St Range OFF Stand by function disabled On Stand by function enabled NOTES 1 If the alarm is programmed as band or deviation alarm this function masks the alarm condition after a set point change or at the instrument start up until process variable reaches the alarm threshold plus or minus hysteresis If the alarm is programmed as a process alarm or control output alarm this function masks the alarm condition at instrument start up until process variable reaches the alarm threshold plus or minus hysteresis 2 The change from On to OFF has immediate effect while the change from OFF to On has effect at the next start up or set point change r F09 Alarm 3 type This parameter is available only when OUT 3 is configured as alarm 3 output O3 Fn C E03 ALr 3 Upper display Gr 6 Lower display A3 tP Range Proc Alarm on process variable bAnd Band alarm on process variable dEV Deviation alarm on process variable Ain Alarm on Main control output value SECn Alarm on Secondary control output value NOTE When alarm type has been changed the alarm threshold will be forced to its default value and
28. The control output is conditioned to match a QUICK OPENING flow characteristic Eou The control output is conditioned to match an EQUAL PERCENTAGE flow characteristic For more details see also NOTE about output conditioning at page 43 C F13 Secondary control output in engineering unit This parameter will be available only when secondary control output is configured Upper display CnF 3 Lower display S SCL Range nO Scalable is not required YES Scalable is required NOTE This scaling allows to display the output value in engineering units instead of in percent 14 Secondary control output decimal point position This parameter will be available only when S SCL Second ary control output in engineering units C F13 is set to YES Upper display CnF 3 Lower display SC dP Range No decimal figure One decimal figure Two decimal figures C F15 Secondary control output initial scale value This parameter will be available only when S SCL Second ary control output in engineering units C F13 is set to YES Upper display CnF 3 Lower display SC E L Range from 199 to 999 16 Secondary control output full scale value This parameter will be available only when S SCL Second ary control output in engineering units C F13 is set to YES Upper display CnF 3 Lower display SC E H Range From 199 to 999 17 Secondary output auxiliary cond
29. The output is at logic level 1 when contact is closed OPEn The output is at logic level 1 when contact is open C H09 Event 2 function This parameter will be available only when OUT 2 is configured as event annunciator O2 Fn C E02 is equal to Eun 2 Upper display CnF 5 Lower display E2 Fn Range In E Error condition Over Under Open Shrt main input Logic level 1 when error occurs Cj Er Error condition on CJ measurement Logic level 1 when error occurs A In E Error condition Over Under Open on auxiliary input Logic level 1 when error occurs EA E Error condition on any measurement Logic level 1 when error occurs Au A Auto manual mode annunciator Logic level 1 when device is in manual mode SP L r Local Remote set point annunciator Logic level 1 when remote set point is used C H10 Event 2 contact status This parameter will be available only when OUT 2 is configured as event annunciator O2 Fn C E02 is equal to Eun 2 Upper display CnF 5 Lower display E2 St Range CLSd The output is at logic level 1 when contact is closed OPEn The output is at logic level 1 when contact is open C H11 Event 3 function This parameter will be available only when OUT 3 is configured as event annunciator O3 Fn C E03 is equal to Eun 3 Upper display CnF 5 Lower display E3 Fn Range In E Error condition Over Un
30. dead band keyboard programmable from 20 dead band to 50 overlap of the proportional band Output limiters For the main and or secondary control outputs it is possible to set output high limits output low limits output max rate of rise AUTO MANUAL mode selectable by front push button or logic input 108 OUTPUTS Control output updating time 125 ms when a linear input is selected 250 ms when a TC or RTD input is selected Action direct reverse programmable Output level limiter high and low limits for main control output high and low limits for secondary control output Out 1 and 2 Function singularly programmable as Control output Alarm output Event output Type Relay SSR or TRIAC Out 1 and 2 Relay Relay type SPDT Contact rating 3 A 250 V on resistive load Out 1 and 2 SSR Type not isolated voltage output Logic level 1 14V 20 mA max 24 V 1 mA Logic level 0 lt 0 5 V D C Out 1 and 2 TRIAC Switching mode isolated zero crossing type Rated current from 50 mA to 1 A Rated voltage from 24 V Hz Load type resistive load only Pt for external fuse 128 RMS Out 3 and 4 Function singularly programmable as Control output Alarm output Event output Servomotor drive Out 3 A out 4 V Type Relay Relay type SPST to 240 10 15 50 60 109 Contact rating 3 A 250 V on resistive load
31. instrument comes back to the normal display mode by MENU push button pressure or by the time out RUN TIME PARAMETER MODIFICATION By MENU push button it is possible to start the run time parameter modification by selecting desired run time parameter group During the run time parameter modification the upper display shows the selected parameter group the lower display shows the mnemonic code of the selected parameter while the central display shows the value or status assigned to the selected parameter The parameter monitoring and modification are subjected to a time out see t out 110 parameter after that the display returns in Normal display mode and the eventual modification on the last displayed parameter will be lost NOTES 1 In the following pages we will describe all the parameter of the instrument but it will show only the parameters related with the specific hardware and in accordance with the specific instrument configuration 2 If all the parameters of a group are not available the instrument will not display this group 3 For an easy consultation of the manual it is accompanied by a table with all the run time parameter visualization 71 Run time group 1 r Axx Set point VALUES LIP I SEPn r A01 Main set point Upper display Gr 1 Lower display SP Range from rL r E12 to rH r E13 r A02 Set point 2 This parameter is available only whe
32. it is advisable to linearize the ratio between flow rate and valve travel in order to obtain a better control of the process This instrument allows you to select an output linearization in accordance with the two most common valve flow characteris tics Quick opening Equal percentage PER CENT OF MAXIMUM FLOW EQUAL PERCENTAGE PER CENT OF RATED TRAVEL 7 Main control output in engineering unit This parameter will be available only when main control output is configured Upper display CnF 3 Lower display A SCL Range nO Scalable is not required YES Scalable is required NOTE This scaling allows you to display the output value in engineering units instead of in percent C F08 Main output decimal point position This parameter will be available only when A SCL Main control output in engineering units C F07 is set to YES Upper display CnF 3 Lower display AC dP Range No decimal figure One decimal figure Two decimal figures C F09 Main output initial scale value This parameter will be available only when SCL Main control output in engineering units C F07 is set to YES Upper display CnF 3 Lower display C E L Range from 199 to 999 C F10 Main output full scale value This parameter will be available only when SCL Main control output in engineering units C F07 is set to YES Up
33. the bargraph is two parts the positive error is shown on the upper part while the negative error is shown on the lower part The last LED will flash if deviation is out of range OUT FAILURE DETECTION FUNCTION The device is capable to measure and display the current running in a load driven by a time proportional control output main or secondary programmable when the load is energized the leakage current flowing through the load when the load is de energized If the instrument has been correctly set it generates an alarm when the current running in the load when the load is energized is lower than the A L Fd r C14 parameter value It shows partial or total break down of the load the break down of the actuator or a power down due to a protection or a fuse intervention the leakage current when the load is de energized is higher than the A H Fd r C15 parameter value It shows a short circuit of the actuator The Display function paragraph describes how to show the two current values The fault condition is shown on the lower display by the Fd AL indication AL may be flashing or steady on in accordance with acknowledge condition and by the status of the assigned output If the ON or OFF period is lower than 120 ms the relative measurement couldn t be performed and the instrument will show flashing the last measured value 66 DIRECT ACCESS TO THE SET POINT
34. 36 Linear 37 Linear 38 Linear From From From From From From From From 0 to 4 to 0 to 1 to 0 to 2 to 0 to 12 to mV mV For these ranges it is possible to select a read out with one decimal figure but the instrument could not display a measure lower than 199 9 or higher than 999 9 and the input range will be limited by it NOTES 1 When a linear input is selected the instrument set automati cally the readout initial scale value C d05 equal to 0 and the readout final scale value C d06 equal to 4000 2 When input type has been changed the instrument automatically forces the fi In L C d05 SS th C 109 and brG L C 103 parameters to the new initial scale value the fi In H C d06 and brG H 104 parameter to the new final scale value and the fi In d C d03 parameter to no decimal figure C d03 Decimal point position Upper display CnF 1 Lower display fi In d Ranges decimal figure _ _ one decimal figure _ two decimal figures _ three decimal figures NOTES 1 For main input type 1 to 6 15 and 30 only the no decimal figure and one decimal figure are selectable the input range is limited within 199 9 and 999 9 and it acts as an input type changement 2 For main input type 7 to 14 and 16 to 29 this parameter is not available 3 For linear input types from 31 to 38 all positions are available C d04 Square root extractio
35. C G01 Enb and a secondary control output without split range is configured Upper display Gr Hd Lower display rG CL Range OFF Smart algorithm does not calculate r Gn r d06 value On Smart algorithm calculates r Gn r d06 value r L06 Hidden group default data loading Upper display Gr Hd Lower display dFLt Range OFF No loading data On loading data ERROR MESSAGES OVERRANGE UNDERRANGE AND SENSOR LEADS BREAK DETECTION ON THE MAIN INPUT The device is capable to detect a fault condition on the main input OVERRANGE or UNDERRANGE or SENSOR LEADS BREAK When the process variable exceeds the full scale value programmed by fi In t C d02 an OVERRANGE condition will be shown on the upper display as show in the following figure When the process variable is lower than the initial scale value programmed by fi In t C d02 an UNDERRANGE condition will be shown on the upper display as show in the following figure In presence of an main input out of range condition the control outputs operate as follows a When SF Cn C G07 is set to Std a 1 An OVERRANGE is detected and the device is set for one control output only the output will be forced to 0 if reverse action is programmed or to 100 if direct action is programmed the device has two control outputs the Main output is forced to 0 and Secondary outp
36. C G07 is set to Cnd b and an overrange an underrange condition is detected the servomotor is driven to its low limit position OUT 4 W will be maintained closed 3 When SF Cn C G07 is set to Cnd C the out of range condition acts on the control output as the complement of effect described at point a These instruments are capable to detect on the main input the sensor leads break condition When the sensor leads break condition is detected the instrument shows on the upper display Note On the linear input the leads break can be detected only for 4 20 mA 1 5 V 2 10 V 0 60 and 12 60 mV ranges In addition on RTD input a special test is provided to signal Shrt when input resistance is less than 12 Q Short circuit sensor detection When fault condition different from overrange or underrange is detected on the main input the alarms the power output and the analog retransmissions operate as in presence of an overrange condition ON THE AUXILIARY INPUT When remote set point signal exceeds the full scale value programmed by A In t C d10 an OVERRANGE condition will be shown on the lower display as shown in the following figure When the remote set point signal is lower than the initial scale value programmed by A In t C d10 UNDERRANGE condition will be shown on the lower display as show in the following figure
37. Cnd A When the instrument detects an overrange or underrange condition of the main input the 50 CONFIGURATION GROUP 5 DIGITAL INPUT OUTPUT CONFIGURATION r L rir inLiE C H01 Logic input 1 function Upper display CnF 5 Lower display d1 Fn Range Input contact not used SP1 2 Input contact used for SP SP2 set point selection See note 2 SP3 4 Input contact used for SP3 SP4 set point selection see note 2 SP L r Input contact used for Local Remote set point selection Remote when logic level is 1 Au A Input contact used for Auto Manual selection Manual when logic level is 1 O LIA Input contact used for output limiter activation Output limited when logic level is 1 Hold Input contact used to stop input sampling Hold function Stop sampling when logic level is rSt Input contact used to reset acknowledge alarm Reset when logic level is 1 rE dr Input contact used for Reverse Direct control action selection Direct when logic level is 1 NOTES 1 When logic input circuits are not mounted the middle display will show no Pr not present 2 When one logic input is set to SP 1 2 and no other logic input is set to SP 3 4 the relation between the logic level and the selected set point is the following Logic level 0 SP Logic level 1 SP2 When one logic input is set to SP 1 2 and a second logic input is set to
38. E02 OUT 2 function Upper display CnF 2 Lower display O2 Fn Range nonE Output not used Ain Time proportional main control output SECn Time proportional secondary control output ALr 2 Alarm 2 output Eun 2 Event 2 output C E03 OUT 3 function When the option is not mounted the middle display will show no Pr not present Upper display CnF 2 Lower display O3 Fn Range nonE Output not used Ain Time proportional main control output SECn Time proportional secondary control output ALr 3 Alarm 3 output Eun 3 Event 3 output fiC Sfi Servomotor control drive as main control output SC Sfi Servomotor control drive as secondary control output C E04 OUT 4 function Upper display CnF 2 Lower display O4 Fn Range nonE Output not used Ain Time proportional main control output SECn Time proportional secondary control output ALr 4 Alarm 4 output Eun 4 Event 4 output NOTES 1 When option is not mounted the middle display will show no Pr not present 2 When servomotor control drive is hardware selected see Output 3 and 4 selection at pag 20 the OUT 4 can be used only as servomotor drive C E05 Servomotor type This parameter will be available only when servomotor control drive is configured 2 O3 Fn 03 C S or SC SA Upper display CnF 2 Lower display SA tP Range CLSd Close loop type NOTE this selection is available only if feedback ci
39. SP 3 4 the relation between the logic levels and the selected set point is the following SP 3 4 SP 1 2 Set point level level selected 0 0 SP 0 1 SP2 1 0 SP3 1 1 5 4 When logic input is set to SP 3 4 and no other logic input is set to SP 1 2 the relation between the logic level and the selected set point is the following Logic level 0 SP Logic level 1 SP3 C H02 Logic input 1 contact status This parameter will be available only when d1 Fn C H01 is different from Upper display CnF 5 Lower display d1 St Range CLSd The input is at logic level 1 when contact is closed OPEn The input is at logic level 1 when contact is open C H03 Logic input 2 function This parameter will be available only when input contact option is fitted Upper display CnF 5 Lower display d2 Fn Range nonE Input contact not used SP1 2 Input contact used for SP SP2 set point selection see note 2 SP3 4 Input contact used for SP3 SP4 set point selection see note 2 SP L r Input contact used for Local Remote set point selection Remote when logic level is 1 Au A Input contact used for Auto Manual selection Manual when logic level is 1 O LI Input contact used for output limiter activation Output limited when logic level is 1 Hold Input contact used to stop input sampling Hold function Stop sampling when logic level is
40. The instrument will start in the same way it was prior to the power down configuration mode or run time mode If the instrument starts in configuration mode push the MENU pushbutton and go to the Configuration group 1 see page 30 If the instrument starts in run time mode by keeping depressed the MENU push button for more than 5 seconds the instrument will show Lut nant FII 1 NOTES 1 The upper display shows the selected parameter family 2 The middle display shows the selected action 3 The lower display shows the firmware version 4 If no push button is depressed for more than 10 s or 30 s according to CnF 6 t out time out selection 110 parameter setting the instrument returns automatically to the normal display mode 27 By A or push button it is possible to select between rinm LE monitor this selection allows you to monitor but not to modify the value assigned to the configuration parameters no gE modify this selection allows you to monitor and to modify the value assigned to the configuration parameters NOTES 1 During monitor mode the instrument continues to operate as in run time mode 2 When modify mode is started the instrument stops the control and sets control outputs to OFF turns OFF the bargraph displays MKC only sets analog retransmissions to the retransmitted initial scale value sets alarms in no alarm condition sets events
41. alarm status will be cleared rF10 Alarm3 configuration This parameter is available only when OUT 3 is configured as alarm output O3 Fn C E03 ALr 3 Upper display Gr 6 Lower display A3 Cn Range H A High alarm outside band with automatic reset Low alarm inside band with automatic reset H A Ac High alarm outside band with automatic reset and acknowledge 88 L A Ac Low alarm inside band with automatic reset and acknowledge H L High alarm outside band with manual reset L L Low alarm inside band with manual reset NOTE When alarm configuration has been changed the alarm status will be cleared r F11 Alarm 3 action This parameter is available only when OUT 3 is configured as alarm output O3 Fn C E03 ALr 3 Upper display Gr 6 Lower display A3 Ac Range dir direct action Relay energized or SSr 1 in alarm condition rEV Reverse action Relay energized or SSr 1 in non alarm condition r F12 Alarm 3 standby mask function This parameter is available only when OUT 3 is configured as alarm 3 output C E03 ALr 3 Upper display Gr 6 Lower display A3 St Range OFF Stand by function disabled Stand by function enabled NOTES 1 If the alarm is programmed as band or deviation alarm this function masks the alarm condition after a set point change or at the instrument start up until process variable reaches the a
42. allows you to monitor the current selected action only r d09 Group 4 default data loading Upper display Gr 4 Lower display dFLt Range OFF No loading data ON Loading data Run time group 5 r Exx AUXILIARY CONTROL PARAMETER reo LII r E01 Anti reset wind up This parameter is available when at least one control output is configured and Pb r d01 is different from 0 Upper display Gr 5 Lower display ArW Range from 1096 to 20096 of the input span r E02 Servo motor travel time This parameter is available when the open loop servomotor control drive output is configured O3 Fn C E03 is equal to AC SA or SC SA and SA tP C E05 are equal to OPEn Upper display Gr 5 Lower display Sf tt Range from 0 12 to 3 00 m ss r E03 Servo motor dead band This parameter is available when the servomotor control drive output is configured O3 Fn C E03 is equal to AC SA or SC SA Upper display Gr 5 Lower display S db Range from 1 to 50 04 Main control output low limit This parameter is available when one control output is configured as main output Upper display Gr 5 Lower display f OLL Range from 0 0 96 of the output span to OLH r E05 05 Main control output high limit This parameter is available when one control output is configured as main output Upper display Gr 5 Lower display OLH Range
43. and auxiliary input During measuring hold the instrument will continue to control the process using the last measured values and the following functions will be inhibited 1 Local set point to remote set point transfer and viceversa 2 Manual to auto mode transfer NOTE The auto to manual transfer is allowed The measure value on the upper display will be flash to indicate the hold status PARAMETER PROTECTION Moving from one run time parameter group to another the instrument will show at first the group number on the upper display the mnemonic code on the lower display and the security status on the middle display of the group The possible security status are Enb the parameters of this group are not protected and they may be modified inh the parameters of this group are ever protected and they cannot be modified the parameters of this group are software protected In this case using A and W push button set a value equal to the security code programmed during the Run time security code see page 23 and then push If the programmed value matches the security code the parameters of this group can be modified otherwise they remain protected ATTENTION One software key protects one or more run time parameter groups so that when the software key is inserted it is possible to modify the run time parameters of all groups The software protection will be automatically restored when the
44. disturbances which can affect the performance of the LOAD OPERATING er mA HF VOLTAGE For all the outputs the internal protection varistor assures a correct protection up to 0 5 A of inductive component lt 40 0 047 100 1 2 260 V AC lt 150 0 1 22 2 260 V same problem may occur when switch is used series 05 A 033 47 2 260 V with the internal contacts as shown in Fig 12 Anyway the cable involved in relay output wiring must be as far away as possible from input or communication cables C R LOAD Fig 12 EXTERNAL SWITCH IN SERIES WITH THE INTERNAL CONTACT In this case it is recommended to install an additional RC network across the external contact as show in Fig 12 2 VOLTAGE OUTPUTS FOR SSR DRIVE 24 Q OUT1 25 SOLID STATE RELAY 27 Q OUT 2 U 28 Q SOLID STATE RELAY Fig 13 SSR DRIVE OUTPUT WIRING Logic level 0 Vout lt 0 5 V DC Logic level 1 14 V 20 20 mA 24 V 20 1 mA Maximum current 20 mA NOTE This output is not isolated A double or reinforced insulation between instrument output and power supply must be assured by the external solid state relay E 3 TRIAC OUTPUTS Line
45. if A In F C d09 and 1 C d14 Cnd A 3 When bIAS is selected the instrument uses as operative Set point the sum of the local set point with the value measured by the auxiliary input scaled by A In L C D11 and A In H C d12 parameters C d10 Auxiliary input type This parameter will be skipped when the auxiliary input option is not mounted or A In F auxiliary input function C d09 is equal to nonE Upper display CnF 1 Lower display A In t Range 0 20 0 20 mA 4 20 4 20 0 5 0 5 V 1 5 1 5V 0 10 0 10 V 2 10 2 10 V C d11 Auxiliary input read out Initial scale value This parameter is available only when auxiliary input is configured Upper display CnF 1 Lower display A In L Range from 1999 to 9999 NOTE the decimal point will be automatically positioned as selected for the main input C d12 Auxiliary input read out full scale value This parameter is available only when auxiliary input is configured Upper display CnF 1 Lower display A In H Range from 1999 to 9999 NOTE the decimal point will be automatically positioned as selected for the main input C d13 Filter on auxiliary input This parameter is available only when auxiliary input is configured Upper display CnF 1 Lower display A I FL Ranges from 0 no filter to 8 seconds NOTE this is a first order digital filter applied to the measured value made by the auxiliary input
46. is able to reach the value programmed by this parameter using temporarily the valve position value as a feedback C G05 MANUAL to AUTO transfer type This parameter will be available only when at least one control output is configured and manual function is enabled An F C G03 Enb Upper display CnF 4 Lower display A t t Range Bumpless balance transfer bu b Bumpless balanceless transfer the operative set point is aligned to the measure value NOTES 1 The alignment is not performed if measure is in error condition or Remote Set point is selected 2 The selected local set point will be changed even if it is software protected 49 C G06 Device status at start up This parameter will be available only when at least one control output is configured and manual function is enabled AAn F C G03 Upper display 4 Lower display St Fn Range Auto starts always in auto mode an ltstarts always in manual mode with power output set to 0 Cnd A It starts in the same way it was left prior to power shut down if in manual mode the power output is set to 0 Cnd b It starts in the same way it was left prior to power shut down if in manual mode the power output will be equal to the last value prior to power shut down C G07 Condition for output safety value servomotor is driven to its high limit position This parameter will be available only when
47. it is possible to select which groups of them will be protected by the security code and in this case it is necessary to set the run time security code before to modify one or more parameters of a protected group The configuration security code protects all configuration parameters and it will be necessary to set the configuration security code before to start the configuration parameters modification For configuration parameters an hardware lock is also available Security code setting 1 Remove the instrument from its case 2 Set the internal dip switch V101 as follows 101 1 OFF V101 2 ON V101 3 OFF V101 4 OFF 3 Re insert the instrument 4 Switch on the instrument The display will show T3 upper display shows that the security code setting mode is selected while the lower display shows the firmware version 5 Push the FUNC pushbutton Run time security code The display will show Brun Note the middle display shows the current status of the run time security code 0 1 or On By and W push button set S run parameter as follows 0 No protection it is ever possible to modify all run time parameters 1 ever protected it is never possible to modify a run time parameter from 2 to 250 security code for run time parameter protection NOTES 1 the selected value of a security code cannot be displayed anymore and com
48. manual mode annunciator Logic level 1 when device is in manual mode SP L r Local Remote set point annunciator Logic level 1 when remote set point is used C H14 Event 4 contact status This parameter will be available only when OUT 4 is configured as event annunciator O4 Fn C E04 is equal to Eun 4 Upper display CnF 5 Lower display E4 St Range CLSd The output is at logic level 1 when contact is closed OPEn The output is at logic level 1 when contact is open General notes on configuration group 5 1 Digitalinput function selection should be consistent with other configuration parameters otherwise this digitalinput will remain unused 2 Changing menu the device will check that the same function is not assigned to more than one digital input otherwise the display will show Upper display CnF 5 Middle display Err Lower display In Ot CONFIGURATION GROUP 6 C Ixx OTHERS CONFIGURATION PARAMETERS L rir DEH 101 Green bargraph function This parameter will be available for MKC models only Upper display CnF 6 Lower display G brG Range Pr Ur the green bargraph will show the process variable value DEV the green bargraph will show the deviation measured value minus set point 102 Orange bargraph function This parameter will be available for MKC models only Upper display CnF 6 Lower display O brG Range OP SP On bargraph is sh
49. rE type dan uation br Lud bargraph rra _ 21 Main Ir ri i Logic r i 1 Readout L 7117 1 JL control EE 225 Loar LACI 4 4 m 25 _ atstart _ contact _ alignement FEEd ALLN edits SEF n up status atstart up L E k i L F E 1 FEJ 1 21 Main F ition r 1111 1 ES dei L 11 2 eventi L 7177 0 Set point i function output in Function display _ _ main oe put ir _ _ _ Safety type LIF SE input mL eng units SFT value r Fit 2 _ 21 Main LL Servo Lr Filter LOZ ous LIT output T Output L Eventi L 7177 01 behaviour ie range decimal safety contact when power pay r point ecw value Z IFL status Z _ L output is oar value LIA position IL I limited Foe 1 I Outs _ 1 Main control _ r CE LIF Auxiliary L retransm _ output LTI L Threshold input initial initial scale function 1 function mre scale r the soft start A in ACE esent Eia 55EH outs _ 1 Main control r rc F LI C Auxiliary L TS output LMU L T E Time input full scale final scale contact dn inp Li 5 Hr value m readout EgbE
50. rL r E12 and rH r E13 parameters program mable CONTROL ACTIONS Algorithm PID SMART Types one control output digital or analog output one control output splitted on two outputs two control outputs NOTE the outputs can be freely selected among analog digital or servo outputs 107 Digital output types Relay SSR or TRIAC Digital output action type Proportional time Analog output types 20 mA Servomotor output Two relays with interlocked contact Servomotor output type Close loop Open loop with feedback for valve position indication only Open loop without feedback Proportional Band programmable from 0 5 to 999 0 of the input span Setting a PB equal to 0 the control action becomes ON OFF Hysteresis for ON OFF control action programmable from 0 196 to 10 0 of the input span Integral time programmable from 1 second to 20 minutes or excluded Derivative time programmable from 1 second to 10 minutes or excluded Integral pre load programmable for control output from 0 to 100 of the output range for two control outputs split range excluded from 100 to 100 of the output range Anti reset windup from 10 to 200 of the input span Main output cycle time from 1 second to 200 seconds Secondary output cycle time from 1 second to 200 seconds Relative secondary output gain keyboard programmable from 0 20 to 2 00 referred to the proportional band Overlap
51. symbol character wen k A During parameter modification it allows you to SA increase the value of the selected parameter During MANUAL mode it allows you to increase H the output value 53 lt v During parameter modification it allows you to decrease the value of the selected parameter During MANUAL mode it allows to decrease the output value RSP allows to toggle from Local set point to Remote set point or viceversa when depressed for more than 1 sec W MENU are used to start the lamp test function the command is accepted when push button are kept depressed for more than 5 s and device is in normal display mode A FUNC or W FUNC During parameter modification they allow you to increase decrease the value under modification with higher rate A MAN or W MAN During parameter modification they allow you to jump to the max or min programmable value NOTES 1 All the actions explained above which requires two or more push buttons must follow exactly the push button sequence shown 2 A 10 or 30 seconds time out see t out C 110 can be selected for parameter modification during run time mode If during parameter modification no push button is depressed for more than 10 30 seconds the instrument goes automatically to the normal display mode and the eventual modification of the last parameter will be lost CONFIGURATION MODE Switch on the instrument
52. this selection terminate the configuration modify mode the instrument preforms an automatic reset and restarts the run time mode Pushing A or W push button select the desired action and then push MENU push button RUN TIME MODE If V101 is correctly set see Operative mode and hardware lock at pag 22 and the configuration mode has been terminated the instrument will be in run time mode and in normal display mode see below During run time mode the instrument performs the loop control and manages all the instrument functions SMART ALARMS etc DISPLAY FUNCTION When device is powered and is operating in automatic mode the upper display shows the process variable the value will be flashing if device is in hold status and the middle display shows the set point value final or operative according to SP dS 107 parameter setting We define the above condition as normal display mode The lower display will show a at instrument start up the control output value the LED is lighted NOTES In accordance with the configured output type the control output can be displayed in the following ways a 1 If the device is configured with servomotor control drive only the feedback position value is displayed in the range 19 0 to 120 0 the display is blank if open loop servomotor without valve position indication has been programmed a 2 If the device is configured with one control out
53. 24 OUT 1 Load 23 Line 27 OUT 2 Load 26 Fig 14 TRIAC OUTPUT WIRING 12 Switching mode isolated zero crossing type Rated current from 50 mA to 1 A Rated voltage from 24 to 240 10 15 50 60Hz Load type resistive load only NOTES 1 2 3 4 5 To avoid electrical shock connect power line at the end of the wiring procedure For power connections use No 16 AWG or larger wires rated for at last 75 C Use copper conductors only Don t run input wires together with power cables This output is not fuse protected Please provide it externally using a fuse with 124 equal 10128 E 4 SERVOMOTOR OUTPUT Open the valve 29 Op Power Servo 30 line motor 31 Close the valve 12 l t lJ 133 13 1 8 5 88 l zu U 5 14 Close Shield Fig 15 SERVOMOTOR OUTPUT WIRING eter The two relay output must be interlocked see chapter E 5 ANALOG OUTPUTS Preliminary hardware setting paragraph Out 3 and 4 selection NOTES 1 Before connecting the instrument to the power line make sure OUT5 thatline voltage andthe load current are in accordance with the contact rating 3A 250V on resistive load 2 To avoid electric shock connect power line at the end of the wiring procedure 3 For servomotor conne
54. Alarm reset automatic or manual reset programmable on each alarm Alarm masking each alarm can be configured as masked alarm or standard alarm 110 This function allows you to delete false indication at instrument start up and after a set point change Process alarm Operative mode Minimum or maximum programmable Threshold programmable in engineering unit within the input range Hysteresis programmable in engineering units from 1 to 200 digits Band alarm Operative mode Inside or outside programmable Threshold two thresholds programmable Low from 0 to 1000 digits High from 0 to 1000 digits Hysteresis programmable in engineering units from 1 to 200 digits Deviation alarm Operative mode High or low programmable Threshold programmable from 1000 to 1000 digits Hysteresis programmable in engineering units from 1 to 200 digits Alarm on the main output value EVENTS It is possible to obtain an alarm condition when the main control All digital outputs are programmable as events output is lower or higher than a programmed value In this case they are used as input error annunciator or as Operative mode Minimum or maximum programmable instrument status indicator Threshold programmable from 0 1 to 100 0 of the output Event type Hysteresis programmable from 0 1 to 20 0 Error condition on the main input overrange underrange open or short circuit Alarm on the secondary out
55. CONTROL OUTPUT LOW LIMIT 81 MAIN CONTROL OUTPUT MAX RATE OF RISE M 81 MANUAL RESET ACKNOWLEDGE OF THE ALARMS MAIN OUTPUT CYCLE TIME DEAD BAND OVERLAP BETWEEN MAIN AND SECONDARY OUTPUT aaa 79 PROPORTIONAL BAND 78 MAX VALUE PROPORTIONAL BAND CALCULATED BY THE SMART ALGORITHM 96 MIN VALUE OF PROPORTIONAL BAND CALCULATED BY THE SMART ALGORITHM 96 POSITIONING OF SERVO AT HIGH LIMIT 94 POSITIONING OF SERVO AT LOW LIMIT 93 RELATIVE SECONDARY OUTPUT GAIN 79 Sq Sal Sa fX y tn tn in in in n r m tr tr x rz A 1 ani 525 5Adb 5ntt 5 5 5P3 SPY 551 RELATIVE GAIN OF THE SECONDARY OUTPUT CALCULATION BY SMART ALGORITHM SETPOINT HIGH LIMIT SETPOINT LOW LIMIT SERIAL LINK DEVICE ADDRESS SERIAL LINK BAUDE RATE SERIAL LINK BYTE FORMAT SERIAL INTERFACE PROTOCOL SECONDARY CONTROL OUTPUT HIGH LIMIT usse croce eiit 82 SECONDARY CONTROL OUTPUT EOW LIMIT recie erattu EE tne site eres 82 SECONDARY CONTROL OUTPUT MAX RATE OP RISE it n i conet SECONDARY OUTPUT CYCLE TIME SERVO MOTOR DEAD BAND SERVO MOTOR TRAVEL TIME Run time group 2 SMART ENABLE DISABLE SMRT ENABLED OR DISABLED MAIN SETPOINT SETPOINT 2 SETPOINT 3 SETPOINT 4 Run time group 7 SERIAL LINK PARAMETER Run time group 1
56. ETRANSMISSION MAIN CONTROL OUTPUT BIAS FULL SCALE VALUE UL eee eee 39 MAIN CONTROL OUTPUT CONDITIONING 43 G amp L OUT 6 RETRANSMISSION MAIN CONTROL OUTPUT DECIMAL POINT INITIAL SCALE VALUE POSITION 44 OUT 6 RANGE E MAIN OUTPUT FULL SCALE VALUE 44 MAIN INPUT OFFSET ADJUSTMENT 33 MAIN OUTPUT INITIAL SCALE VALUE 44 Bbhr Configuration group 6 MAIN CONTROL OUTPUT aaa OTHER CONFIGURATION PARAMETER 57 But Configuration group 2 ORANGE BARGRAPH FUNCTION OUTPUT CONFIGURATION eene 36 OUT 1 FUNCTION OUT FUNCTION ic oco SSEL SECONDARY CONTROL OUTPUT 55 INPUT THRESHOLD TO ENABLE THE IN ENG UNE Leisten rater 46 co trt notior qi eiua SCAC SECONDARY CONTROL OUTPUT AUXILIARY Str DEVICE STATUS AT START UP 5 CONDITIONING L L 46 Laub TIMEOUT SELECTION 222222222220 5265 SECONDARY CONTROL OUTPUT BIAS 42 EEn SECONDARY CONTROL OUTPUT CONDITIONING vsr centre 45 5 SECONDARY CONTROL OUTPUT DECIMAL POINT POSITION u usss 46 SCEH SECONDARY CONTROL OUTPUT FULL SCALE VALUE L uuu uuu uuu pe adis 46 SCEL SECONDARY CONTROL OUTPUT INITIAL SCALE VALUE nne 46 S 5n SECONDARY CONTROL OUTPUT GAIN 42 SFEn CONDITION FOR OUTPUT SAFETY VALUE
57. LURE DETECTION bhrb5H BARGRAPH FULL SCALE VALUE OUTPUT ASSIGNEMENT 61 BARGRAPH INITIAL SCALE VALUE FEEd VALVE POSITION INDICATION CONFIGURATION ONTROL OUTPUT Eb GREEN BARGRAPH FUNCTION 57 Configuration group 5 DIGITAL INPUTIOUTPUT En CONFIGURATION 5 d Fn LOGIC INPUT 1 FUNCTION 51 mP Configuration group 1 MAIN AUXILIARY INPUT d 5 LOGIC INPUT 1 CONTACT STATUS 52 CONFIGURATION tr teet 30 242421 21206214 oon LOCAL REMOTE SETPOINT OUT 3 FUNCTION 222 37 OPERATING MODE 2 44 4044 35 BUF OUT 4 FUNCTION 37 LINE 30 OSFL OUT5 FILTER ON THE MANUAL AUTO TRANSFER 48 RETRANSMITTED 39 DECIMAL POINT POSITION USER FUNCTION 38 READOUT FULL SCALE VALUE SH OUT 5 RETRANSMISSION READOUT INITIAL SCALE VALUE SCALE VALUE uu nn uu u nu n 38 SQUARE ROOT EXTRACTION OSL OUT 5 RETRANSMISSION FOR MAIN INPUT sossen INITIAL SCALE VALUE MAIN INPUT AND RANGE 05 OUT 5 RANGE MAIN CONTROL OUTPUT IN ENG UNIT G amp FL OUT 6 FILTER ON THE MANUAL FUNCTION f es RETRANSMITTED VALUE 40 MAIN CONTROL OUTPUT AUXILIARY OUT 6 FUNCTION aaa 39 CONDITIONING DEH OUT 6 R
58. Notes 1 The commons of the out 3 and 4 are connected together with the same rear terminal 2 When OUT 3 and 4 are used as independent relay outputs the addition of the two currents must not exceed 3 A Servomotor output Type Two relays with interlocked contact Out 3 and 4 Servomotor output type Close loop Open loop with feedback for valve position indication only Open loop without feedback Feedback potentiometer input from 100 O to 10 kO Servomotor travel time From 12 s to 3 minutes Servomotor dead band From 1 to 50 of the feedback span or of the valve travel time Analog outputs Out 5 and 6 Function Programmable as Control output Analog retransmission of the measured value Analog retransmission of the operative set point Output type Isolated output programmable as 0 20 mA 4 20 mA Scaling programmable from 1999 to 9999 Maximum load 600 Accuracy 0 1 when it is used as control output 0 05 96 when it is used as analog retransmission Note a too little range scaling can deteriorate the output accuracy Filter It is possible to apply a first order digital filter on the retransmitted value The time constant of the filter may be programmed within 0 and 85 ALARMS Alarm action direct or reverse function programmable Alarm functions each alarm can be configured as process alarm band alarm deviation alarm alarm on main or secondary control output value
59. ODEPOORT Tel 011 4742278 9 Fax 011 4749404 P O Box 43112 Industria 2042 ero sa kingsley co za SPAIN ERO ELECTRONIC IBERICA Calle La granja 74 Pol Ind Alcobendas MADRID Tel 091 6618194 Fax 091 6619093 U K ERO U K Unit 1 Cygnet Trading Estate Faraday Close Durrington Worthin WEST SUSSEX BN13 3RQ Tel 01903 693322 Fax 01903 693377 U S A AMERICAN ERO Electronic Corp BARRINGTON ILL 60010 Tel 0847 382 0881 Fax 0847 382 0240 U S A BARBER COLMAN Industrial Instruments Div O BOX 2940 Loves Park IL 31132 2940 Tel 0815 637 3000 Fax 0815 637 5341 jgsearle ad com display mode CO O oO N a O CO POs OO time 1 Set points n ro m w Lh n i Lh 7n H 1 n Ey Run time Group 2 Smart Main Set point Set point 2 Set point 3 Set point 4 Group 1 default data loading SMART enabled or disabled Run time Group 3 Alarms I1 11 w Ld 1 Lit F 1 Lo 1 ru m3 0 ur LOJI rr pM ur Z LOS Fono c pr 3 Fie ZE 2 7 BAJI r zl Lu o LEAN 5 at 7 D
60. On to OFF has immediate effect while the change from OFF to On has effect at the next start up or set point change r F05 Alarm 2 type This parameter is available only when OUT 2 is configured as alarm 2 output O2 Fn C E02 ALr 2 Upper display Gr 6 Lower display A2 tP Range Proc Alarm on process variable bAnd Band alarm on process variable dEV Deviation alarm on process variable Ain Alarm on Main control output value SECn Alarm on Secondary control output value NOTE When alarm type has been changed the alarm threshold will be forced to its default value and alarm status will be cleared 06 Alarm 2 configuration This parameter is available only when OUT 2 is configured as alarm 2 output O2 Fn C E02 ALr 2 Upper display Gr 6 Lower display A2 Cn Range High alarm outside band with automatic reset Low alarm inside band with automatic reset H A Ac High alarm outside band with automatic reset and acknowledge Low alarm inside band with automatic reset and acknowledge H L High alarm outside band with manual reset L L Low alarm inside band with manual reset NOTE When alarm configuration has been changed the alarm status will be cleared L A Ac 7 Alarm 2 action This parameter is available only when OUT 2 is configured as alarm 2 output O2 Fn C E02 ALr 2 Upper display Gr 6 Lower display A2 Ac Range dir direct action
61. SETPOINT VALUES DERIVATIVE TIME INTEGRAL TIME 78 VALUE INTEGRAL TIME VALUE CALCULATED BY THE SMART ALGORITHM 96 MIN VALUE OF INTEGRAL TIME VALUE CALCULATED BY THE SMART ALGORITHM 96 TIMEOUT FOR SOFT START CONFIGURATION PARAMETERS dfn LOGIC INPUT 2 FUNCTION 52 d2 amp St LOGIC INPUT 2 CONTACT STATUS 53 AUXILIARY INPUT ACTIVATION MODE daFr LOGIC INPUT FUNCTION iFL ON AUXILIARY INPUT VALUE amp 35 LOGIC INPUT CONTACT STATUS i5c AUXILIARY INPUT SAFETY CONDITION dSFL FILTER ON THE DISPLAYED VALUE inf AUXILIARY INPUT FUNCTION EVENT 1 FUNCTION inH AUXILIARY INPUT READ OUT E iS amp EVENT 1 CONTACT STATUS INITIAL SCALE VALUE EVENT 2 FUNCTION Aint AUXILIARY INPUT READ OUT E25 amp EVENT 2 CONTACT STATUS FUEL SGALE VALUE cies neither tcs 34 EVENT 3 FUNCTION Riak AUXILIARY INPUT 33 15 EVENT 3 CONTACT STATUS RE E n Configuration group 4 AUXILIARY CONTROL EVENT 4 FUNCTION n OUTPUT CONFIGURATION 47 EY4SE EVENT 4 CONTACT STATUS OUTPUT d FdFn OUTPUT FAILURE DETECTION FdHS PRIMARY CURRENT OF THE CURRENT brid RESOLUTION OF THE DEVIATION TRANSFORMER 60 BARGRAPH n Fd u OUTPUT FAI
62. TPUT 3 AND 4 SELECTION Output 3 and 4 can be set as 2 independent relay outputs 1 servomotor output with interlocked contact Set J204 see fig 21 and J205 see fig 20 according to the desired output type as shown in the following table J204 Fig 21 Output J 204 J205 Relay close open Servo open close NOTE when the servomotor close loop or the servomotor open loop with valve position indication outputs is required it will be necessary to set also V301 see IN CT Feedback selection paragraph IN CT FEEDBACK SELECTION This instrument can use the IN CT input or the Feedback input the two inputs are not contemporarily The current transformer input allows you to measure and display the current running in a load driven by a time propor tional control output during the ON and OFF periods of the output cycle time By this feature it is also available the Out failure detection function see page 66 The feedback input is used when the servomotor close loop or the servomotor open loop with valve position indication outputs is required To select the desired input type set V301 see fig 20 as detailed in the following table Input V301 1 V301 2 V301 3 V301 4 OFF ON ON Feedback OFF ON OFF ON OPTION CHECK This instrument can be supplied with many options Two integrated circuits KY101 and KY103 located as shown in fig 22 and inser
63. When the device is in AUTO mode and in Normal Display Mode it is possible to access directly to the selected set point modification SP SP2 SP3 or SP4 Pushing A or W for more than 2 s the set point will begin changing The new set point value becomes operative since no push button has been depressed at the end of 2 s time out The direct access to the set point is disabled if the run time group 1 is software protected or remote set point is used MANUAL FUNCTION The MANUAL mode function can be accessed only if configured by depressing the MAN push button for more than 1 sec or by acting on a logic input configured as Au A auto manual selection The command from keyboard is accepted and executed only if the instrument is in Normal Display Mode while the command from logic input is always accepted When in MANUAL mode the LED s MAN light up while the middle display shows followed by the main output values from 0 0 to 99 9 and the lower display shows S followed by the secondary output value from 0 0 to 99 9 When the device is configured with one control output only and this output is Servo the display will show the current valve position When the device has two control outputs and one of them is Servo during valve positioning the display will show the final position of the valve and not the current position The control output and or the feedback position can be modified by using
64. ange 1 2 5 6 8 9 10 14 16 17 20 21 23 24 25 29 lt 350 of span TC ranges 11 12 13 26 27 28 lt 500 of span for RTD Operative temperature from 0 to 50 C 32 to 122 F Storage temperature 20 to 70 C 4 to 158 F Humidity from 20 to 85 RH non condensing INPUTS A THERMOCOUPLE Type J K T E N S B L U G D Ni Ni 18 Mo C F selectable External resistance 100 max maximum error 0 1 of span Cold junction automatic compensation from 0 to 50 C Cold junction accuracy 0 1 Input impedance gt 1 Calibration according to IEC 584 1 and DIN 43710 1977 104 Ranges L 1 100 900 C DIN 43710 1977 J 2 100 1000 IEC 584 1 3 100 1370 C 584 1 4 200 400 584 1 5 200 600 DIN 43710 1977 E 6 100 800 C IEC 584 1 7 100 1400 584 1 8 50 1760 584 1 9 50 1760 584 1 B 10 0 1820 584 1 G 11 0 2300 D 12 0 2300 13 0 2300 Ni 14 0 1100 16 150 1650 DIN 43710 1977 J 17 150 1830 F IEC 584 1 18 150 2500 584 1 19 330 750 F 584 1 20 330 1110 F DIN 43710 1977 21 150 1470 1 584 1
65. arameters exception made for Run rime group 8 r Hxx proceed as follows B 1 By MENU pushbutton select the Run time group dF r Ixx B 2 Push the FUNC pushbutton The middle and lower display will show dFLE B 3 By A or W pushbuttons select the On indication on the central display B 4 Push the FUNC pushbutton The central display will show nna and then it will show End The default parameter loading procedure of all run time parameters is terminated The following is list of the default run time parameters loaded during the above procedure Run time group 1 r Axx PARAMETER DEFAULT VALUE SP Set point low limit rL r E12 SP2 Set point low limit rL r E12 SP3 Set point low limit rL r E12 5 4 Set point low limit rL r E12 Run time group 3 r Cxx PARAMETER DEFAULT VALUE rSt OFF AL1 Initial range value for process alarm 0 for deviation alarm 0 0 for control output alarm 0 bA1 h 0 AL2 Initial range value for process alarm 0 for deviation alarm 0 0 for control output alarm bA2 L 0 bA2 h 0 AL3 Initial range value for process alarm 0 for deviation alarm 0 0 for control output alarm bA3 L 0 0 AL4 Initial range value for process alarm 0 for deviation alarm 0 0 for control output alarm bA4 L 0 bA4 h 0 A L Fd Initial scale value A H Fd Final scale value HSA1
66. at least one control Cnd b When the instrument detects an overrange or output is configured underrange condition of the main input the Upper display CnF 4 servomotor is driven to its low limit position Lower display SF Cn Cnd C When the instrument detects an overrange or Ranges underrange condition of the main input the When no output is configured as open loop servomotor action on servomotor is the complement of control SF Cn can be set as follows standard setting Std No safety value standard setting see chapter ERROR MESSAGES C G08 Output safety value Ov Un Safety value applied when the instrument This parameter will be available only when SF Cn C G07 is detect an overrange or underrange condition of equal to Ov Un OvEr or Undr or the parameter A I Sc the main input Auxiliary input safety condition C d15 is equal to Cnd A OvEr Safety value applied when the instrument Upper display CnF 4 detect an overrange condition of the main Lower display SF UL input Range Undr Safety value applied when the instrument from 0 0 to 100 0 if device is configured with one control detect an underrange condition of the main output input from 100 0 to 100 0 if device is configured with two control When the open loop servomotor control is configured outputs split range excluded SF Cn can be set as follows Std safety value standard setting see chapter ERROR MESSAGES
67. ay SS th Range for TC RTD ranges within the input range for linear input within In L Read out initial scale value C d05 and In H Read out full scale value C d06 NOTE At start up if the measured value is lower than threshold value the device maintains the output power limiting A OLL r E04 OLH r E05 S OLL r E08 and S OLH r E09 for a programmed time tOL rE 16 This function is called soft start This threshold value has no effect if tOL rE 16 InF or when one logic input is configured for output limiter activation 110 Time out selection SC On Set Fd Fn to SC On when the load under test Upper display CnF 6 is energized during the ON status of the second Lower display t out ary output relay energized or SSR output status Range t 10 10s time out 1 18 30 30s time out SC OF Set to SC OF when the load under test NOTE for more details see NOTE 2 at page 26 is energized during the OFF status of the second ary output relay de energized or SSR output status 0 NOTE When the option is not fitted the middle display will 111 Out failure detection show no Pr This parameter will be available only when the option is fitted and the main and or the secondary output is configured as time proportional control output Upper display CnF 6 Lower display Fd Fn 12 Current transformer full scale va
68. ay be enabled C G02 Control action type This parameter will be available only when at least one control output is configured Upper display CnF 4 Lower display Cn tP Range Pid The process is controlled by PID actions Pi The process is controlled by PI actions C G03 Manual function This parameter will be available only when at least one control output is configured Upper display CnF 4 Lower display An F 91 Manual function disabled Enb Manual function may be enabled C G04 Output value for AUTO to MAN transfer This parameter will be available only when at least one control output is configured and manual function is enabled An F C G03 Enb Upper display CnF 4 Lower display A UL Range from 0 0 to 100 0 of the output span if device is configured with only one control output from 100 0 to 100 0 of the output span if device is configured with two control outputs split range excluded Above the value 100 0 the display shows bufi meaning that the transfer from AUTO to MANUAL is bumpless the instrument set for MANUAL mode the same power output used in AUTO mode NOTES 1 When open loop servomotor control drive without valve position indication is configured this parameter is forced to bu and it cannot be modified 2 When open loop servomotor control drive with valve position indication is configured and the transfer from AUTO to MAN is required the instrument
69. bration enabling r H01 is equal to ON Upper display Gr 8 Lower display Fb HC Range OFF To skip calibration and hold the previous value select OFF and then push FUNC On memorize the current position as feedback high limit calibration select On and then push FUNC 94 This procedure is now completed and the calibration values are automatically checked If the calibrated feedback span is greater than 20 of the potentiometer input span the instrument memorizes the new values and comes back to the first display of the run time group 8 Otherwise the old calibration values will be retained and the display will show hr B Err FLAL It will be necessary to repeat the feedback potentiometer calibration procedure r H6 Group 8 default data loading Upper display Gr 8 Lower display dFLt Range OFF No loading data On loading data Run time group dF r Ixx DEFAULT RUN TIME PARAMETER LOADING rir LII IZ LL 101 Default run time parameter loading Default run time parameter loading of all run time parameters all groups exception made for group 8 Upper display Gr dF Lower display dFLt Range OFF No loading data On the run time parameters of all groups exception made for group 8 will be forced to their default values Run time group Hd r Lxx HIDDEN PARAMETERS SMART LIMITS 111 LI JD H NOTE This group is accessible from
70. c input is configured as alarm reset both actions of rSt parameter and of the logic input are active 02 Alarm 1 threshold This parameter is available when alarm 1 is configured as process deviation main power output or secondary power output alarm A1 tP rF 01 Proc or dEV or Ain or SECn Upper display Gr 3 Lower display AL1 Range in engineering units within the span limits for process alarm from 1000 to 1000 digits for deviation alarm from 0 0 to 100 0 for control output alarm NOTE The span limits are configured by fi In L C d05 and In H C d06 03 Low threshold used when the alarm 1 is a band alarm This parameter is available only when the alarm 1 is configured as band alarm A1 tP rF 01 bAnd Upper display Gr 3 Lower display bA1 L Range from 0 to 1000 digits r C04 high threshold used when the alarm 1 is a band alarm This parameter is available only when the alarm 1 is configured as band alarm A1 tP rF 01 bAnd Upper display Gr 3 Lower display bA1 h Range from 0 to 1000 digits NOTE The bA1 L and bA1 h values are algebraically added to the operative set point in order to obtain the band limits 05 Alarm 2 threshold This parameter is available when alarm 2 is configured as process deviation main power output or secondary power output alarm A2 tP rF 05 Proc or dEV
71. ctions use No 16 AWG or larger wires rated for at last 75 C Use copper conductors only Don t run input wires together with power cables For feedback potentiometer use shielded cable with the shield connected to the earth at one point only OUT 5 7 The relay outputs are protected by varistor against inductive load with inductive component up to 0 5 A Q Fig 16 A OUTPUT 5 WIRING Fig 16 B OUTPUT 6 WIRING NOTE 1 Do not run analog output wirings together with AC power cables 2 Out 5 and 6 are isolated outputs 3 The maximum load is equal to 600 F SERIAL INTERFACE RS 485 interface allows you to connect up to 30 devices with one remote master unit AA 5 22 T A R B B 5 u 21 R MES T Fig 17 RS 485 WIRING NOTES 1 The cable length must not exceed 1 5 km at 9600 BAUD 2 This serial interface is isolated 3 The following report describes the signal sense of the voltage appearing across the interconnection cable as defined by EIA for RS 485 a The A terminal of the generator shall be negative with respect to the B terminal for a binary 1 MARK or OFF state b A terminal of the generator shall be positive with respect to the B terminal for a binary 0 SPACE or ON 4 The EIA stan
72. dard establishes that by RS 485 interface it is possible to connect up to 30 devices with one remote master unit The serial interface of these instruments is based on High input impedance transceivers this solution allows you to connect up to 127 devices based on the same transceiver type with one remote master unit G POWER LINE WIRING N L2 32 e POWER LINE 100 V to 240 V A C 50 60Hz or 24 V AC DC 33 5 1 Line Neutral Fig 18 POWER LINE WIRING NOTES 1 Before connecting the instrument to the power line make sure that line voltage corresponds to the description on the identifi cation label 2 To avoid electrical shock connect power line at the end of the wiring procedure 3 For supply connections use No 16 AWG or larger wires rated for at least 75 C Use copper conductors only Don t run input wires together with power cables For 24 V DC the polarity is a not care condition The power supply input is fuse protected by a sub miniature fuse rated T 1 250 V When fuse is damaged it is advisable to verify the power supply circuit so that it is necessary to send back the instrument to your supplier 8 The safety requirements for Permanently Connected Equipment say a switch or circuit breaker shall be included in the building installation it shall be in close proximity to the equipment and within easy reach of the operator it shall be marked as the
73. der Open Shrt on main input Logic level 1 when error occurs Cj Er Error condition on CJ measurement Logic level 1 when error occurs Error condition Over Under Open on auxiliary input Logic level 1 when error occurs EA E Error condition on any measurement Logic level 1 when error occurs Au A Auto manual mode annunciator Logic level 1 when device is in manual mode SP L r Local Remote set point annunciator Logic level 1 when remote set point is used C H12 Event 3 contact status This parameter will be available only when OUT 3 is configured as event annunciator O3 Fn C E03 is equal to Eun 3 Upper display CnF 5 Lower display E3 St Range CLSd The output is at logic level 1 when contact is closed OPEn The output is at logic level 1 when contact is open C H13 Event 4 function This parameter will be available only when OUT 4 is configured as event annunciator O4 Fn C E04 is equal to Eun 4 Upper display CnF 5 Lower display E4 Fn Range fi In E Error condition Over Under Open Shrt on main input Logic level 1 when error occurs Cj Er Error condition on CJ measurement Logic level 1 when error occurs Error condition Over Under Open on auxiliary input Logic level 1 when error occurs EA E Error condition on any measurement Logic level 1 when error occurs Au A Auto
74. disconnecting device for the equipment NOTE a single switch or circuit breaker can drive more than one instrument 9 When a neutral line is present please connect it to the 32 terminal 4 5 6 PRELIMINARY HARDWARE SETTINGS How to remove the instrument from its case 1 Switch off the instrument 2 Push gently the lock A on the right 3 While the lock A is maintained out slide out the right side of the instrument see fig 19 a MENU Fung Fig 19 a B 4 Push gently the lock C the left MAIN INPUT SELECTION 5 While the lock C is maintained out slide out the instrument Set J103 see fig 20 according to the desired input type as see fig 19 b shown in the following table D J103 INPUT TYPE m 60mV 5V 10V 20 mA 1 2 open open close open open 3 4 open open close close open 5 6 open open open open close 7 8 open open open open close 5 7 close close open close open 6 8 close close open open open Fig 19 b 1357 1357 AUXILIARY INPUT SELECTION option 2 Set J102 see fig 20 according to the desired input type as aie J103 wm m shown in the following table RA J102 INPUT TYPE 5V 10V 20 mA 1 2 close open open 3 4 close close open 5 6 open open close 7 8 open open close 5 7 open close open 6 8 open open open D vo li Fig 20 OU
75. e 3 wires must be the same LINEAR INPUT Fig 6 mA mV AND V INPUTS WIRING NOTES 1 Don t run input wires together with power cables 2 Pay attention to the line resistance a high line resistance may cause measurement errors D 6 3 When shielded cable is used it should be grounded at one side only to avoid ground loop currents 4 The input impedance is equal to lt 5 Q for 20 mA input gt 1 MQ for 60 mV input gt 200 kQ for 5 V input gt 400 kQ for 10 V input A 4 2 3 AND 4 WIRE TRANSMITTER INPUT Shield Fig 7 A INPUTS WIRING FOR 2 WIRE TRANSMITTER 2 Shield Fig 7 INPUTS WIRING FOR 3 WIRE TRANSMITTER Fig 7 C INPUTS WIRING FOR 4 WIRE TRANSMITTER NOTES 1 Don t run input wires together with power cables 2 Pay attention to the line resistance a high line resistance may cause measurement errors 3 When shielded cable is used it should be grounded at one side only to avoid ground loop currents 4 The input impedance is lower than 5 20 mA input B AUXILIARY INPUT 4 When shielded cable is used it should be grounded at one side only to avoid ground loop currents 5 The input impedance is equal to lt 5 Q for 20 mA input gt 200 kQ for 5 V input gt 400 kQ for 10 V input C LOGIC INPUT
76. e derivative action is excluded r d05 Integral preload This parameter is available when at least one control output is configured and Pb r d01 is different from 0 Upper display Gr 4 Lower display IP Ranges from 0 0 to 100 0 of the output when device is configured with only one control output from 100 0 to 100 0 96 of the output when device is configured with two control outputs split range excluded 79 r d06 Relative secondary output gain This parameter is available when two control outputs are configured split range excluded and Pb r d01 is different from 0 Upper display Gr 4 Lower display r Gn Range from 0 20 to 2 00 r d07 Overlap dead band between main and secondary outputs This parameter is available when two control outputs are configured split range excluded and Pb r d01 is different from 0 Upper display Gr 4 Lower display OLAP Range from 20 to 50 NOTE A negative value means a dead band while a positive value means an overlap 408 Control action Upper display Gr 4 Lower display Cn Ac Range rEv reverse action dir direct action REVERSE ACTION DIRECT ACTION Input Input t Output Output t t NOTES 1 When device is configured with two control outputs split range excluded the control action is forced to reverse and it cannot be modify 2 When direct reverse selection is performed by a logic input this parameter
77. eset and restarts in the run time mode CONFIGURATION GROUP 1 C dxx MAIN AND AUXILIARY INPUT CONFIGURATION FL L rir LL I I mre Push the FUNC push button C d01 Line frequency Upper display CnF 1 Lower display Ln Fr Range 50 Hz 60 Hz C d02 Main input type and range Upper display CnF 1 Lower display In t Ranges 1 TC 6 3 4 TC 5 TC From 100 to From 100 to From 100 to From 200 to From 200 to 900 1000 1370 400 600 8088 30 6 7 8 9 10 TC 11 TC G or W 12 D or W3 13 TC C or W5 14 TC Ni Ni18 Mo 15 RTD Pt100 16 TC 17 TC 18 TC 19 TC 20 TC 21 TC 22 TC 23 TC 24 TC 25 26 G orW 27 D or W3 28 TC C or W5 29 TC Ni Ni18 Mo 30 RTD Pt100 2 2 4 lt From From From From From From From From From From From From From From From From From From From 100 to 100 to 50 to 50 to 0 to 0 to 0 to 0 to 0 to 200 to 150 to 150 to 150 to 330 to 330 to 150 to 150 to 60 to 60 to 32 to 0 to 0 to 0 to 0 to 330 to 800 1400 1760 1760 1820 2300 2300 2300 1100 1650 1830 2500 750 1110 1470 2550 3200 3200 3300 4170 4170 4170 2000 1560 08868 31 Linear 32 Linear 33 Linear 34 Linear 35 Linear
78. every group by keeping depress the MENU key for 8 secs r L01 Minimum value of proportional band calculated by SMART algorithm This parameter is available only when smart function is configured Sfi Fn C G01 Enb Upper display Gr Hd Lower display Pb Lo Range From 0 5 to Pb Hi r LO2 NOTE The resolution on Pb Lo value will be equal to 0 1 up to 10 096 and 1 up to 999 095 102 Maximum value of proportional band calculated by SMART algorithm This parameter is available only when smart function is configured S Fn C G01 Enb Upper display Gr Hd Lower display Pb Hi Range from Pb Lo r L01 to 999 0 NOTE The resolution on Pb Hi value will be equal to 0 1 up to 10 0 and 1 up to 999 0 r L03 Minimum value of integral time calculated by SMART algorithm This parameter is available only when smart function is configured SA Fn C G01 Enb Upper display Gr Hd Lower display ti Lo Range from 00 01 mm ss to ti Hi r LO4 104 Maximum value of integral time calculated by SMART algorithm This parameter is available only when smart function is configured Sfi Fn C G01 Enb Upper display Gr Hd Lower display ti Hi Range from ti Lo r L03 to 20 00 mm ss r L05 Relative gain of the secondary output calculated by SMART algorithm This parameter is available only when smart function is configured Sfi Fn
79. from fi OLL r E04 to 100 0 of the output span r E06 Main control output max rate of rise This parameter is available when one control output is configured as main output Upper display Gr 5 Lower display r P Ranges from 0 1 s to 25 0 s Above this value the display shows Inf meaning that no limit is imposed NOTES 1 This parameter will be active even if device is configured for On OFF control 2 During the transfert from AUTO to MANUAL if this action is programmed as a not bumpless transfer the ri r P function will be ignored and the output will step up to the value set by A UL C G04 parameter r E07 Main output cycle time This parameter is available when time proportional main control output is configured Upper display Gr 5 Lower display C CY Range from 1 to 200 s r E08 Secondary control output low limit This parameter is available when one control output is configured as secondary control output Upper display Gr 5 Lower display S OLL Range From 0 0 of the output span to S OLH r E09 r E09 Secondary control output high limit This parameter is available when one control output is configured as secondary control output Upper display Gr 5 Lower display S OLH Range from S OLL r E08 to 100 0 of the output span r E10 Secondary control output max rate of rise This parameter is available when one control output is configured as secondary control output
80. guration has been changed the alarm status will be cleared r F15 Alarm 4 action This parameter is available only when OUT 4 is configured as alarm 4 output O4 Fn C E04 ALr 4 Upper display Gr 6 Lower display A4 Ac Range direct action Relay energized or SSr 1 alarm condition Reverse action Relay energized or SSr 1 in non alarm condition r F16 Alarm 4 stand by mask function This parameter is available only when OUT 4 is configured as alarm 4 output O4 Fn C E04 ALr 4 Upper display Gr 6 Lower display A4 St Range OFF Stand by function disabled On Stand by function enabled NOTES 1 If the alarm is programmed as band or deviation alarm this function masks the alarm condition after a set point change or at the instrument start up until process variable reaches the alarm threshold plus or minus hysteresis If the alarm is programmed as a process alarm or control output alarm this function masks the alarm condition at instrument start up until process variable reaches the alarm threshold plus or minus hysteresis 2 The change from On to OFF has immediate effect while the change from OFF to On has effect at the next start up or set point change r F17 OFD Output Failure Detection alarm configuration This parameter is available only when OFD option is configured Fd Fn C 111 equal to AC On or AC OF or SC On or 5 Upper disp
81. h on the lower display the indication previously selected INDICATORS Lit when process variable is in Celsius degree F Lit when process variable is in Fahrenheit degree ST Flashing when the first step of SMART algorithm is activated Lit when the second step of SMART algorithm is activated Lit when the lower display shows the output power value MAN Lit when device is in manual mode REM Lit when device is controlled by serial link RSP Lit when Remote Set point is used SPX Lit when an auxiliary Set point SP2 SP3 or Sp4 is used Flashing when a temporary set point from serial link is used 64 Lit when OUT 1 is used as control output and it is in ON condition or when Event 1 is at logic level 1 or when alarm 1 is in alarm state and acknowledged Flashes when alarm 1 is in alarm state and it is not acknowledged Lit when OUT 2 is used as control output and it is in ON condition or when Event 2 is at logic level 1 or when alarm 2 is in alarm state and acknowledged Flashes when alarm 2 is in alarm state and it is not acknowledged Lit when OUT 3 is used as control output and it is in ON condition or when servomotor output increases or when Event 3 is at logic level 1 or when alarm 3 is in alarm state and acknowledged Flashes when alarm 3 is in alarm state and it is not acknowledged Lit when OUT 4 is used as control output and it is in ON condition or when servomotor output decreases or when Eve
82. h MENU pushbutton again The central display will show nna Lung and then the display will show r1 3 7 The default parameter loading procedure of all configuration parameters is terminated The following is a list of the default configuration parameters loaded during the above procedure TABLE 1 Configuration group 1 C dxx PARAM VALUE NOTES Ln Fr 50 Hz In t 3 TC K with G In d No decimal figure In S 915 Disabled fi In L 100 C fi In H 1370 C OFSt 0 dS FL 0 No filter A In F RSP Remote set point A In t 4 20 mA A In L 0 C A In H 1000 C A LFL 0 No filter A LAA 1 nonE L r O fi n ALG Configuration group 2 C Exx PARAM VALUE NOTES O1 Fn Ain If servo motor drive is not mounted ALr 1 If servo motor drive or linear output is mounted O2 Fn ALr 2 O3 Fn nonE If option is not mounted C S If servo control motor drive is mounted ALr 3 If option is mounted O4 Fn nonE If option is not mounted ALr 4 If option is mounted S tP CLSd If feedback circuitry is mounted OPEn If feedback circuitry is not mounted FEEd no Fb O5 Fn nonE If option is not mounted RAin If option is mounted O5 rn O5 Lr O5 Hr O5 FL O6 Fn O6 rn O6 Lr O6 Hr O6 FL PARAM C Gn C bS SC Gn SC bS C Cn SCL C dP C E L C E H fiC A C 5 4 20 0 1000 0 nonE PV rt 4 20 0 1000 0 dls 2 00 50 0 2 00
83. he OFD output failure detection alarm threshold resolution values is equal to 0 1 A for range up to 25 A and 1 A for range up to 100A 3 The hysteresis on this threshold values is fixed to 1 of fsv r C16 Alarm 1 hysteresis This parameter is available only when Out 1 is configured as alarm output O1 Fn C E01 ALr 1 Upper display Gr 3 Lower display HSA1 Range from 1 to 200 digits r C17 Alarm 2 hysteresis This parameter is available only when Out 2 is configured as alarm output O2 Fn C E02 ALr 2 Upper display Gr 3 Lower display HSA2 Range from 1 to 200 digits r C18 Alarm 3 hysteresis This parameter is available only when Out 3 is configured as alarm output O3 Fn C E03 ALr 3 Upper display Gr 3 Lower display Range from 1 to 200 digits r C19 Alarm 4 hysteresis This parameter is available only when Out 4 is configured as alarm output O4 Fn C E04 ALr 4 Upper display Gr 3 Lower display HSA4 Range from 1 to 200 digits r C20 Group 3 default data loading Upper display Gr 3 Lower display dFLt Range OFF No loading data ON Loading data Run time group 4 r dxx CONTROL PARAMETERS Lt uy 1 r NOTE when SMART function is activated all the parameters calculated by SMART Pb Ti Td and rCG can not be modified r d01 Proportional band This parameter is available when at least one control output is co
84. he display will show Lua The modify mode is started This display allows you to load the default configuration parameter For more details see chapter Default parameter see Appendix A 4 By or W push button select the OFF indication and push the MENU push button The display will show O I LTH in This is the starting display of the first group of configuration parameters NOTES 1 In the following pages we will describe all the parameters of the instrument but the instrument will show only the parameters related with the specific hardware and in accordance with the specific instrument configuration i e setting OUT 3 different from servo all the parameters related with servomotor output will be skipped 2 During configuration parameters modify mode the upper display shows the selected parameter group the lower display shows the mnemonic code of the selected parameter while the central display shows the value or status assigned to the selected parameter 3 For an easy consultation of this manual a table with all the parameter visualizations is enclosed When it is desired to exit from configuration modify mode proceed as follows a Push MENU push button until the Configuration group END is displayed b Pushing A or W push button select the YES indication c Push MENU push button The instrument terminates the configuration modify mode it preforms an automatic r
85. ing back to the S run parameter the display will show On when S run is different from 0 or 1 0 when S run is equal to 0 1 when S run is equal to 1 When the security code is forgotten a new value can be set 2 When S run is different from 0 or 1 the run time default and the run time hidden groups are ever protected by security code Run time groups protected by security code The display will show this parameter it is possible to set if the run time group 1 will be protected or not by the run time security code By A and WY push button set Gri parameter as follows nO No protection it is always possible to modify run time group 1 parameters Yes the run time group 1 parameter modification will be protected by security code Push the FUNC push button the instrument memorizes the new setting and goes to the next parameter Ln I m m NOTE the above described selection be repeated for all groups of the run time mode Configuration security code The display will show 1 JEFE 5EnF Note the middle display shows the actual status of the configuration security code 0 1 or On By A and push button set S CnF parameter as follows 0 No protection it is ever possible to modify all configuration parameters 1 ever protected it is never possible to modify a configuration parameter from 2 to 250 security code for configuration paramete
86. ing to be careful for not damage the electronic components 4 To clean external plastic or rubber parts use only cloth moistened with Ethyl Alcohol or denatured C H OH Isopropil Alcohol pure or denatured CH CHOH or Water H O 5 Verify that there are no loose terminals 6 Before re inserting the instrument in its case be sure that it is perfectly dry 7 re insert the instrument and turn it ON DEFAULT PARAMETERS DEFAULT RUN TIME PARAMETERS A complete and consistent set of run time parameters is memorized in the instrument These data are the typical values loaded in the instrument prior to shipment from factory This instrument allows you to load the default value of a single run time parameter group or to load all the run time parameters exception made for Run time group 8 r Hxx A When it is desired to load the default parameter of a single group proceed as follows A 1 By MENU pushbutton select the desired run time parameter group A 2 By FUNC pushbutton select the last parameter of the selected group The middle and lower display will show or W pushbuttons select the On indication on the central display A 4 Push the FUNC pushbutton The central display will show 5 I eno The default parameter loading procedure for the selected group is terminated When it is desired to load the default value of all the run time p
87. is function LAMP TEST No time out is applied to the LAMP TEST When it is desired to come back to the normal display mode push any push button During the LAMP TEST the instrument continues to control the process SMART FUNCTION It is used to automatically optimize the control action To enable the SMART function proceed as follows 1 push the MENU push button until Gr 2 run time parameter group is shown 2 push the FUNC push button until Sfirt parameter is shown 3 push A or and set the On indication on the middle display 4 push the FUNC push button The ST LED will turn on or flashing according to the selected algorithm When the smart function is enabled it is possible to display but not to modify the control parameters To disable the SMART function proceed as follows 1 push the MENU push button until Gr 2 run time parameter group is shown 2 push the FUNC push button until Sfrt parameter is shown 3 push A or and set the OFF indication on the middle display 4 push the FUNC push button The ST LED will turn off The instrument maintains the current set of control parameters and it enables parameter modification NOTES 1 When ON OFF control is programmed Pb 0 the SMART function is disabled 2 The SMART enabling disabling can be protected by safety key HOLD FUNCTION By means an logic input it is possible to stop the inputs sampling keeping frozen the last measure values main
88. itioning This parameter will be available only when secondary control output is configured and SC Cn Secondary control output conditioning C F12 is different from nor Upper display CnF 3 Lower display SC A C Range bEFr The functions listed at Note are calculated 47 before to apply the action selected by SC Cn Secondary control output conditioning C F12 parameter AFtr The functions listed at Note are calculated after to apply the action selected by SC Cn Secondary control output conditioning C F12 parameter General note on configuration group 3 Exiting from the configuration group 3 the instrument automati cally tests the SPLt parameter Split range C F01 When SPLt parameter is enabled Enb the instrument performs the following actions 1 If AR UL parameter Output value for AUTO to MAN transfer C G04 is lower than 0 it will be forced to 2 Ifthe SF UL parameter Output safety value C G08 is lower than zero it will be forced to zero 3 Ifthe IP parameter Integral pre load r d05 is lower than zero it will be forced to 50 0 CONFIGURATION GROUP 4 C Gxx AUXILIARY CONTROL CONFIGURATION C G01 Smart function This parameter will be available only when at least one control output is configured Upper display CnF 4 Lower display S Fn 15 Smart function disabled Enb Smart function m
89. larm threshold plus or minus hysteresis If the alarm is programmed as a process alarm or control output alarm this function masks the alarm condition at instrument start up until process variable reaches the alarm threshold plus or minus hysteresis 2 The change from On to OFF has immediate effect while the change from OFF to On has effect at the next start up or set point change r F13 Alarm 4 type This parameter is available only when OUT 4 is configured as alarm 4 output O4 Fn C E04 ALr 4 Upper display Gr 6 Lower display A4 tP Range Proc Alarm on process variable bAnd Band alarm on process variable dEV Deviation alarm on process variable RAin Alarm on Main control output value Alarm on Secondary control output value NOTE When alarm type has been changed the alarm threshold will be forced to its default value and alarm status will be cleared r F14 Alarm 4 configuration This parameter is available only when OUT 4 is configured as alarm 4 output O4 Fn C E04 ALr 4 Upper display Gr 6 Lower display A4 Cn Range H A High alarm outside band with automatic reset L A Low alarm inside band with automatic reset H A Ac High alarm outside band with automatic reset and acknowledge L A Ac Low alarm inside band with automatic reset and acknowledge H L High alarm outside band with manual reset L L Low alarm inside band with manual reset NOTE When alarm confi
90. lay 6 Lower display Fd Cn Range A Alarm with automatic reset A Ac Alarm with automatic reset and acknowledge L Alarm with manual reset NOTE When alarm configuration has been changed the alarm status will be cleared 18 Output Failure Detection alarm action This parameter is available only when one output is configured as alarm annunciator Fd Fn 111 equal to AC On AC OF or SC On or SC OF and Fd Ou C 113 is different from Upper display Gr 6 Lower display Fd Ac Range direct action Relay energized SSr 1 in alarm condition Reverse action Relay energized or SSr 1 in non alarm condition 9 NOTE When output is in OR condition with an alarm an event output the Fd Ac parameter can only be monitored but not modified and it assumes the same action defined by Alarm Action or Event Logic Level for the alarm or the event r F19 Group 6 default data loading Upper display Gr 6 Lower display dFLt Range OFF No loading data ON Loading data Run time group 7 SERIAL LINK PARAMETER r_ 3 LIT I r G01 Serial interface protocol Upper display Gr 7 Lower display S L Pr Range OFF No serial interface bUS Modbus jbUS Jbus NOTE When serial interface circuit is not mounted the middle display will show no Pr r G02 Serial link device add
91. lue Range nonE Function not provided This parameter will be available only when 111 is C On Set to C On when the load under different from nonE test is energized during the ON status of the Upper display CnF 6 main output relay energized or SSR output Lower display Fd HS status 1 Range From 10 Ato 100A C OF Set Fd Fn to AC OF when the load under test is energized during the OFF status of the main output relay de energized or SSR output status 0 60 C H3 Out failure detection output assignment This parameter will be available only when Fd Fn C 111 is different from nonE Upper display CnF 6 Lower display Fd Ou Range The Out failure detection alarm is signalled only on display OUt 1 The Out failure detection alarm is signalled on OUT 1 OUt 2 The Out failure detection alarm is signalled on OUT 2 OUt 3 The Out failure detection alarm is signalled on OUT 3 OUt 4 The Out failure detection alarm is signalled on OUT 4 NOTE Out failure detection alarm annunciator cannot be assigned to an output just configured as control output CONFIGURATION GROUP END C Lxx END CONFIGURATION This group will be displayed only when configuration modify mode is enabled Upper display ConF Lower display End Range nO with this selection the instrument comes back to the first display of the configuration modify mode YES
92. m configuration has been changed the alarm bAnd Band alarm on process variable status will be cleared dEV Deviation alarm on process variable fiAin Alarm on Main control output value SECn Alarm on Secondary control output value NOTE When alarm type has been changed the alarm threshold will be forced to its default value and alarm status will be cleared r F03 Alarm 1 action This parameter is available only when OUT 1 is configured as alarm 1 output O1 Fn 01 ALr 1 Upper display Gr 6 Lower display 1 Range direct action Relay energized or SSr 1 alarm condition Reverse action Relay energized or SSr 1 in non alarm condition 04 Alarm 1 stand by mask function This parameter is available only when OUT 1 is configured as alarm 1 output O1 Fn C E01 ALr 1 Upper display Gr 6 Lower display A1 St Range OFF Stand by function disabled On Stand by function enabled NOTES 1 If the alarm is programmed as band or deviation alarm this function masks the alarm condition after a set point change or at the instrument start up until process variable reaches the alarm threshold plus or minus hysteresis If the alarm is programmed as a process alarm or control output alarm this function masks the alarm condition at instrument start up until process variable reaches the alarm threshold plus or minus hysteresis 86 2 The change from
93. m ss ti Hi 20 00 mm ss rG CL OFF DEFAULT CONFIGURATION PARAMETERS A complete and consistent set of configuration parameters is memorized in the instrument These data are the typical values loaded in the instrument prior to shipment from factory When it is desired to load the default value of all the configura tion parameters proceed as follows If the instrument starts in configuration mode push the MENU pushbutton If the instrument starts in run time mode by keeping depressed the MENU push button for more than 5 seconds the instrument will show rm m LUMI RUD NOTE If no push button is depressed for more than 10 s or 30 S according to CnF 6 t out time out selection C 110 parameter setting the instrument returns automatically to the normal display mode By A or W push button select odF NOTES 1 When modify mode is started the instrument stops the control and Sets control outputs to OFF turned OFF the bargraph displays MKC only sets analog retransmissions to the retransmitted initial scale value sets alarms in no alarm condition sets events to OFF disables the serial link the time out will be removed 2 When the modify mode is disabled by V101 SW3 the A or W push button pressure has no effect Push MENU pushbutton again and select the Default configuration group C Cxx By A or Y push button select the desired configuration parameter set tb 1 or tb 2 Pus
94. mart Logic L L1 Green frequency function range function input 1 bargraph Lar D En SPLE 5AFn With the instrument normal display mode J r r by keeping depressed the MENU pushbutton for more than 5 seconds the instrument will show r Main DCU EE Logic FCE LI input LACE 2 LAV L T Lo inputi Orange type function output n contact bon nar rr function n Int gain status Lior L Lar LF Man Lard Bargraph L i L L L L sz i L 1 Bargrap un MANUAL r initial scale point function output input 2 A function value 4 position ADE bias E _ function Lor ri worn nr Ecl rn Dr LL I I Square I _ 1 Second Output CE i Lr root LATS Como T L 1117 121 Bargraph extraction function output AUTO contact full scale toe for main moc EFP gain OZN MAN ASE ts status value FI input LIBRE transfert Lir Lut FL FEJ _ 1 21 Second F LI MAN _ _ i Readout UAL t Resolution Lar me LAFE Servo L T auto LT Logie Lore scale 21 2 output transfert _ deviation imb value bF P SLi 5 bias
95. n ALr 1 ALr 2 nonE AC SA ALr 3 nonE Alr 4 CLSd OPEn no Fb nonE AAin 4 20 32 1832 0 nonE PV rt 4 20 32 Configuration group 2 C Exx VALUE NOTES If servo motor drive is not mounted If servo motor drive or linear output are mounted If option is not mounted If servo control motor drive is mounted If option is mounted If option is not mounted If option is mounted If feedback circuitry is mounted If feedback circuitry is not mounted If option is not mounted If option is mounted 4 20 mA F oF No filter If option is not mounted If option is mounted 4 20 mA F O6 Hr 1832 SP Configuration group 4 C Gxx O6 FL 0 No filter PARAM VALUE NOTES S Fn Enb Configuration group 3 C Fxx Cn tP Pld PARAM VALUE NOTES An F Enb SPLt dis Af UL buf RC Gn 2 00 f A t t bufi RC bS 50 0 St Fn Cnd b SC Gn 2 00 SF Cn Std SC bS 0 0 SF UL 0 0 RC Cn SCL nO Configuration group 5 C Hxx RC dP No decimal figure PARAM VALUE NOTES C E L 0 d1 Fn 5 1 2 100 d1 St CLSd bEFr d2 Fn SP3 4 d2 St CLSd S SCL nO d3 Fn fi St SC dP No decimal figure d3 St CLSd SCEL 0 E1 Fn fi In E SC E H 100 E1 St CLSd SC A C bEFr E2 Fn REA E E2 St CLSd E3 Fn Au A E3 St CLSd 4 E4 St PARAM G brG O brG brG L brG H brG d SP AL SP dS Sr bH SS tr t out Fd Fn Fd HS Fd Ou SP L r CLSd Configuration group 6 C Ixx VALUE DEv
96. n insert the panel gasket between the instrument and the panel as shown in fig 1 While holding the instrument against the panel proceed as follows 1 insert the gasket in the instrument case 2 insert the instrument in the panel cutout 3 pushing the instrument against the panel 4 insert the mounting brackets as shown in fig 1 5 with a screwdriver turn the screws with a torque between 0 3 and 0 4 Nm Fig 1 1 Gasket Panel Screw bracket Panel OUTLINE AND CUT OUT DIMENSIONS 15 max 1 5 K IN e geo tt nnnnnnn tag U UUU g 00 4539 i UU I g m OW N 60 nn nnnnnnn K E tf c r a m UU UUUUUUU y JU UUUUUUU 0 y 128 16 Fig 2 A OUTLINE AND CUT OUT DIMENSIONS FOR PKC MODEL 2 000000000000000000000 000000000000000000000 Fig 2 OUTLINE AND CUT OUT DIMENSIONS FOR MKC MODEL CONNECTION DIAGRAMS Connections are to be made with the instrument housing m installed i
97. n for main input Upper display CnF 1 Lower display fi In S Ranges 915 square root extraction disabled Enb square root extraction enabled NOTES 1 This parameter is available only for main input type 31 to 38 2 When the square root extraction is enabled the In L read out initial scale value C d05 In H read out full scale value C d06 brG L bargraph initial scale value C 103 brG H bargraph full scale value C 104 and SS th threshold to enable the soft start C 109 parameter values must be positive or equal to zero Enabling the square root extraction the instrument verify the actual value of the fi In L fi In H brG L brG H and SS th parameters and force to zero the eventual negative values C d05 Read out initial scale value Upper display CnF 1 Lower display fi In L Ranges from 1999 to 9999 for linear input Input range 31 to 38 from 0 to 9999 for linear input with square root extraction from initial range value to fi In H read out full scale value C d06 for TC RTD input NOTE Changing the value of this parameter the brG L bargraph initial scale value C I03 and rL set point low limit r E12 parameters will be realigned to it If a linear input is selected also the SS th threshold for soft start 109 will be realigned to it C d06 Read out full scale value Upper display CnF 1 Lower display In H Ranges
98. n its proper location 2 3 nc 23 12 a Ec ABH 8 25 0 J ne 26 15 J s a 27 6 Ja MES 25 A MEASURING INPUTS ab NOTE external component like barriers etc connected between sensor and input terminals may cause E318 7 errors in measurement due to excessive and or not balanced 5s E line resistance or possible leakage currents og az ERS s cpas 8 E ae C C z GI 114 B B 2 MER s sl 8322 J 3j J Fig 3 REAR TERMINAL BLOCK 9 A 1 TC INPUT gt L shield Fig 4 THERMOCOUPLE INPUT WIRING NOTES 1 2 3 Don t run input wires together with power cables For TC wiring use proper compensating cable preferable shielded When a shielded cable is used it should be connected at one point only 5 A 2 RTD INPUT RTD RTD 3 7 gt wo a gt wo zk Fig 5 RTD INPUT WIRING NOTES 1 Don t run input wires together with power cables 2 Pay attention to the line resistance a high line resistance may cause measurement errors 3 When shielded cable is used it should be grounded at one side only to avoid ground loop currents 4 The resistance of th
99. n one of the logic inputs is configured for SP SP2 selection Upper display Gr 1 Lower display SP2 Range from rL r E12 to rH r E13 r A03 Set point 3 This parameter is available only when one of the logic inputs is configured for SP3 SP4 selection Upper display Gr 1 Lower display SP3 Range from rL r E12 to rH r E13 r A04 Set point 4 This parameter is available only when one of the logic inputs is configured for SP SP2 selection and another one for SP3 SP4 selection Upper display Gr 1 Lower display SP4 Range from rL r E12 to rH r E13 r A05 Group 1 default data loading Upper display Gr 1 Lower display dFLt Range OFF No loading data ON Loading data Run time group 2 r bxx SMART ENABLE DISABLE _ d 5BnrE r b01 SMRT This parameter is available when at least one control output is configured and SMART function is enabled Sfi Fn C G01 Enb Upper display Gr 2 Lower display Sfrt Range OFF SMART algorithm is deactivated ON SMART algorithm is activated Set On or OFF to activate deactivate the SMART algorithm Run time group 3 r Cxx ALARM THRESHOLD AND HYSTERESIS VALUE r C01 Manual reset of the alarms Upper display Gr 3 Lower display rSt Range ON OFF Change to ON and then depress FUNC key to reset acknowledge the alarm condition NOTES 1 The reset acknowledge function is always enabled 2 When one of the logi
100. nal element 2 Do not run current transformer input wiring together with AC power cables 3 The minimum active period to perform this measurement is equal to 120 ms 4 The input impedance is equal to 20 Q 1 RELAY OUTPUTS The contact rating of all outputs is equal to 3A 250V AC on j NC resistive load 23 The number of operations is 1 x 105 at specified rating OUT 1 Sr WARNING When OUT 3 and 4 are used as independent relay E outputs the addition of the two currents must not exceed 3 A NO 25 NOTES 1 To avoid electrical shock connect power line at the end of the wiring procedure 26 NC 2 For power connections use No 16 AWG or larger wires rated for at last 75 C 3 Use copper conductors only OUT 2 27 4 Don t run input wires together with power cables All relay contacts are protected by varistor against inductive load ogl NO _ with inductive component to 0 5 OUT The following recommendations avoid serious problems which 29 occur when using relay output for driving inductive loads OUT 3 lt q zg C OUT l NO OUT4 Fig 11 RELAY OUTPUTS WIRING INDUCTIVE LOADS The value of capacitor C and resistor R are shown in the High voltage transients may occur switching inductive loads following table Through the internal contacts these transients may introduce
101. ndition or Remote Set point is selected 107 Set point display type Upper display CnF 6 Lower display SP dS Range Fn SP When device is in normal display mode and it is performing a set point ramp the middle display will show the final set point value OP SP When device is in normal display mode and it is performing a set point ramp the middle display will show the operative set point value NOTE This selection has effect only when local set points are used 108 Servomotor behaviour when the output power is limited This parameter will be available only when the close loop servomotor control drive is configured Upper display CnF 6 Lower display Sr bH Range bAL When the PID output reaches the specific output limits Main control output low limit r E04 or Main control output high limit r E05 or Secondary control output low limit r E08 or Secondary control output high limit r E09 the instrument will reach the respective limit and than it will maintain the output relay in open condition 59 n bAL When PID value is higher than Main control output high limit r E05 or Secondary control output high limit r E09 the OUT 3 A relay contact is ever closed When PID value is lower than Main control output low limit r E04 or Secondary control output low limit r E08 the OUT 4 W relay contact is ever closed 109 Input threshold to enable the soft start Upper display CnF 6 Lower displ
102. nfigured Upper display Gr 4 Lower display Pb Range from 0 5 to 999 0 of the input span Set 0 0 for On OFF control action NOTES 1 The Pb resolution will be equal to 0 1 up to 10 0 and 1 up to 999 0 2 When device is working with SMART algorithm the Pb value will be limited as selected by parameters Pb Hi r L02 and Pb Lo r L01 r d02 Hysteresis for ON OFF control This parameter is available when Pb r d01 0 On OFF control action Upper display Gr 4 Lower display HYS Range from 0 1 to 10 0 of the input span r d03 Integral time This parameter is available when at least one control output is configured and Pb r d01 is different from 0 Upper display Gr 4 Lower display ti Range from 00 01 to 20 00 mm ss Above this value the display blanks and the integral action is excluded NOTE When device is working with SMART algorithm the ti value will be limited as selected by ti Hi r LO4 and ti Lo 7 03 r d04 Derivative time This parameter is available when at least one control output is configured Cn tP C G02 is equal to Pid and Pb r d01 is different from 0 Upper display Gr 4 Lower display td Range From 00 00 to 10 00 mm ss NOTES 1 When device is working with SMART algorithm and Cn tP C G02 is equal to Pid the td value will be made equal to a quarter of ti value 2 When Cn tP C G02 is equal to Pi th
103. nt 4 is at logic level 1 or when alarm 4 is in alarm state and acknowledged Flashes when alarm 4 is in alarm state and it is not acknowledged BARGRAPH DESCRIPTION On MKC model only two 33 LED s bargraphs are available On the right bargraph with orange LED s it is possible to show the operative set point scaled as configured by brG L C 103 and brG H 104 The SP LED located on the base of the bargraph is lighted the power output value The LED located on the top of the bargraph is lit When the device has two process outputs the central LED which is a two color LED become green It divides the bargraph into two parts the MAIN process output is shown on the upper part while the SECONDARY process output is shown on the lower part If a process output is a servomotor type the bargraph will show the valve position instead of the power output the first or last LED s is flashing when the feedback position is out of range 0 100 On the left bargraph with green LED s it is possible to show the process variable scaled as configured by brG L C 103 and brG H 104 The PV LED located on the base of the bargraph is lit The deviation error PV SP with resolution configured at brG d C 105 The DEV LED located on the top of the bargraph is lit When the deviation error indication is selected the central LED which is a two color LED become orange It devides
104. onfigured as PV rt or SP rt Upper display CnF 2 Lower display O5 Hr Range From 1999 to 9999 NOTE Decimal point is positioned as previously selected at CnF 1 fi In d C d03 11 OUT 5 filter on the retransmitted value This parameter will be available only when OUT 5 is configured as process variable retransmission O5 Fn C E07 is equal to PV rt Upper display CnF 2 Lower display O5 FL Range From 0 no filter to 8 seconds NOTE this is a first order digital filter applied to the retransmit ted output value C E12 OUT 6 function Upper display CnF 2 Lower display O6 Fn Range nonE Output not used Ain Main control output linear SECn Secondary control output linear PV rt Process variable retransmission SP rt Operative set point retransmission NOTE When the option circuitry is not mounted the middle display will show no Pr not present C E13 OUT 6 range This parameter will be available only when Out 6 is configured O6 Fn C E12 different from nonE Upper display CnF 2 Lower display O6 rn Range 0 20 20 20 mA 4 20 4 20 mA 4 OUT 6 retransmission initial scale value This parameter will be available only when Out 6 function C E12 is configured as PV rt or SP rt Upper display CnF 2 Lower display O6 Lr Range From 1999 to 9999 NOTE Decimal point is positioned as previously selected at CnF 1 fi In d C d03 C E15 OUT 6 retransmi
105. oup 2 also the following actions are automatically performed A The A UL parameter Output value for auto to manual transfer C G04 will be forced to bumpless if 1 its value is lt 0 and only one control output is configured 2 servomotor open loop without feedback is configured B The parameter SF Cn Condition for output safety value C G07 will be forced to standard Std if it is not complied with configured control output type The parameter SF UL Output safety value C G08 will be forced to 0 if only one control output is configured and its value is 0 D The parameter Fd Fn Out failure detection current measurement C I11 will be forced to if it is assigned to a control output different from a time proportional output E The parameter Fd Ou Out failure detection output assignment C 113 will be forced to it is assigned to an output configured as control output F The parameter IP Integral pre load r d05 will be forced to 50 0 if only one control output is configured and its value is lt 0 CONFIGURATION GROUP 3 C Fxx CONTROL CONFIGURATION Lad Ir Ler C F01 Split range This parameter will be available only when two control outputs are configured Upper display CnF 3 Lower display SPLt Range dlS Split range feature is not required Enb Split range feature is required
106. own the operative set point value P Out On bargraph is shown the process output value 103 Bargraph initial scale value This parameter will be available only for MKC models when G brG C 101 is equal to Pr Ur and or O brG C 102 is equal to OP SP Upper display CnF 6 Lower display brG L Range From fi In L Read out initial scale value C d05 to In H Read out full scale value C d06 104 Bargraph full scale value This parameter will be available only for MKC models when G brG C 101 is equal to Pr Ur and or O brG C 102 is equal to OP SP Upper display CnF 6 Lower display brG H Range From fi In L Read out initial scale value C d05 to R In H Read out full scale value C d06 105 Resolution of the deviation bargraph This parameter will be available only for MKC models when G brG C 101 is equal to DEV Upper display CnF 6 Lower display brG d Range 1 2 5 10 20 or 50 Digits per segment 106 Operative set point alignments at start up Upper display CnF 6 Lower display SP AL Range ALG At start up the operative set point is aligned to measure value and then it will reach the selected set point with the programmed ramp Grd1 r E14 and Grd2 r E15 n ALG At start up the operative set point is equal to the selected set point NOTE The ALG selection has no effect when the measure is in error co
107. per display CnF 3 Lower display C E H Range from 199 to 999 C F11 Main output auxiliary conditioning This parameter will be available only when main control output is configured and C Cn Main control output conditioning C F06 is different from nor Upper display CnF 3 Lower display Range bEFr The functions listed at Note are calculated before to apply the action selected by C Cn Main control output conditioning C F06 parameter 45 The functions listed at Note are calculated after to apply the action selected by C Cn Main control output conditioning C F06 parameter Note Main control output limiters for more details see r E04 and r E05 parameters Main control output max rate of rise see 06 Control output display value for more details see Display function paragraph at pag 62 and C F07 C F08 C F09 and C F10 parameters Threshold for alarm on control output value for more details see r F01 r F05 r F09 and r F13 parameters The control output value displayed by bargraph C F12 Secondary control output conditioning This parameter will be available only when secondary control output is configured Upper display CnF 3 Lower display SC Cn Range nor The control output is calculated by the PID C PL The control output is complemented 100 PID calculated value Ouic
108. put linear or time proportional the control output value is displayed in the range 0 to 100 a 3 if the device is configured with two control outputs the value of the MAIN output is shown on the two most significant digits while the value of the SECONDARY output is shown on the two less significant digits The decimal point between the two values will be flashing NOTE the graphic symbol specific control output is gt 100 Whenever one of the two outputs is a servomotor type the instrument shows for this output the feedback position instead of the output in percent shows that the b push the FUNC push button the lower display will show A followed by the current consumed by the load under test when the load is in ON condition see also OUT failure detection c Push FUNC push button again the lower display will show b followed by the leakage current running in the load under test when the load is in OFF condition see also OUT failure detection d Push FUNC push button again the lower display will show Fd followed by the OUT failure detection alarm status OF no alarm AL flashing alarm AL steady acknowledged alarm Push FUNC push button again the lower display will show fi followed by the MAIN control output value in the range 0 0 19 0 for feedback to 99 9 shows that the control output is gt 100 0 or within the scale configured by
109. put value Error condition on the auxiliary input It is possible to obtain an alarm condition when the secondary Error condition on both inputs control output is lower or higher than a programmed value Auto Man mode annunciator Operative mode Minimum or maximum programmable Local remote set point annunciator Threshold programmable from 0 1 to 100 0 of the output Hysteresis programmable from 0 1 to 20 0 AUXILIARY POWER SUPPLY Type 24 V DC 20 not isolated Max current 25 mA GENERE SERIAL INTERFACE Types RS 485 isolated Protocol type MODBUS JBUS Baud rate programmable from 600 to 19200 BAUD Byte format 8 bit Parity even odd or none programmable Stop bit one Address from 1 to 255 Output voltage levels according to EIA standard NOTE The EIA standard establishes that by RS 485 interface it is possible to connect up to 30 devices with one remote master unit The serial interface of these instruments is based on High input impedance transceivers this solution allows you to connect up to 127 devices based on the same transceiver type with one remote master unit 112 MAINTENANCE 1 REMOVE POWER FROM THE POWER SUPPLY TERMI NALS AND FROM RELAY OUTPUT TERMINALS 2 Remove the instrument from case 3 Using a vacuum cleaner or a compressed air jet max 3 kg cm remove all deposit of dust and dirt which may be present on the louvres and on the internal circuits try
110. r protection NOTE the selected value of a security code cannot be displayed anymore and coming back on the S CnF parameter the display will show On when S CnF is different from 0 or 1 0 when S CnF is equal to 0 1 when S CnF is equal to 1 When the security code is forgotten a new value can be set RUN TIME AND CONFIGURATION MODES Keyboard description The hardware selection described in Operative mode and MENU is used to select a parameter group hardware lock paragraph allows you to start one of the two following operative modes FUNC J when the instrument is in normal display mode it run time mode changes the indication on the lower display see configuration mode display function 1 During parameter modification it allows you to At power up the instrument starts in the same mode it was memorize the new value of the selected parameter prior to the power OFF and go to the next parameter increasing order MAN when the instrument is in normal display mode General note about graphic symbols used for mnemonic pushing MAN push button for more than 1 s it is code visualization possible to enable or disable the manual function The instrument displays some characters with special symbols During parameter modification it allows you to The following table shows the correspondence between the scroll back the parameters and groups without symbols and the characters memorizing the new setting
111. r Reverse Direct control action selection Direct when logic level is 1 NOTE See also NOTE 2 of the d1 Fn Logic input 1 function C H01 parameter Hold C H06 Logic input 3 contact status This parameter will be available only when d3 Fn C H05 is different from nonE Upper display CnF 5 Lower display d3 St Range CLSd The input is at logic level 1 when contact is closed OPEn The input is at logic level 1 when contact is open C H07 Event 1 function This parameter will be available only when OUT 1 is configured as event annunciator O1 Fn C E01 is equal to Eun 1 Upper display CnF 5 Lower display E1 Fn Range fi In E Error condition Over Under Open Shrt on main input Logic level 1 when error occurs Cj Er Error condition on CJ measurement Logic level 1 when error occurs A In E Error condition Over Under Open on auxiliary input Logic level 1 when error occurs EA E Error condition on any measurement Logic level 1 when error occurs Au A Auto manual mode annunciator Logic level 1 when device is in manual mode SP L r Local Remote set point annunciator Logic level 1 when remote set point is used C H08 Event 1 contact status This parameter will be available only when OUT 1 is configured as event annunciator O1 Fn C E01 is equal to Eun 1 Upper display CnF 5 Lower display E1 St Range CLSd
112. rcuitry is mounted and selected OPEn Open loop type C E06 Valve position indication This parameter will be displayed only when open loop servomotor control drive output is confi gured Upper display CnF 2 Lower display FEEd Range Fb no Fb The valve position is not measured NOTE If the feedback option is not mounted this parameter will be forced to no Fb no feedback C E07 OUT 5 function Upper display CnF 2 Lower display O5 Fn Range nonE Output not used Ain Main control output linear SECn Secondary control output linear PV rt Process variable retransmission SP rt Operative set point retransmission NOTE When the option circuitry is not mounted the middle display will show not present The valve position is measured and displayed C E08 OUT 5 range This parameter will be available only when Out 5 is configured O5 Fn C E07 different from nonE Upper display CnF 2 Lower display O5 rn Range 0 20 0 20 mA 4 20 4 20 mA 09 OUT 5 retransmission initial scale value This parameter will be available only when Out 5 function C E07 is configured as PV rt or SP rt Upper display CnF 2 Lower display O5 Lr Range From 1999 to 9999 NOTE Decimal point is positioned as previously selected at CnF 1 In d C d03 C E10 OUT 5 retransmission full scale value This parameter will be available only when Out 5 function C E07 is c
113. red by In L C d05 and In H C d06 09 Low threshold used when the alarm 3 is a band alarm This parameter is available only when the alarm 3 is configured as band alarm A3 tP 09 Upper display Gr 3 Lower display bA3 L Range from 0 to 1000 digits 10 high threshold used when the alarm 3 is a band alarm This parameter is available only when the alarm 3 is configured as band alarm A3 tP rF 09 Upper display Gr 3 Lower display bA3 h Range from 0 to 1000 digits NOTE The bA3 L and bA3 h values are algebraically added to the operative set point in order to obtain the band limits r C11 Alarm 4 threshold This parameter is available when alarm 4 is configured as process deviation main power output or secondary power output alarm A4 tP rF 13 Proc or dEV or Ain or SECn Upper display Gr 3 Lower display 14 Range in engineering units within the span limits for process alarm from 1000 to 1000 digits for deviation alarm from 0 0 to 100 0 for control output alarms NOTE The span limits are configured by fi In L C d05 and R In H C d06 r C12 Low threshold used when the alarm 4 is band alarm This parameter is available only when the alarm 4 is configured as band alarm A4 tP rF 13 bAnd Upper display Gr 3 Lower display bA4 L Range from 0 to 1000 digits
114. ress This parameter is available only when S L Pr r G01 is different from OFF Upper display Gr 7 Lower display S L Ad Range from 1 to 255 r G03 Serial link baud rate This parameter is available only when S L Pr r GO1 is different from OFF Upper display Gr 7 Lower display S L bd Range from 600 to 19200 baud 19200 baud is shown on display as 19 20 r G04 Serial link byte format This parameter is available only when S L Pr r GO1 is different from OFF Upper display Gr 7 Lower display S L bF Range 8 8 bits without parity 8E 8bits even parity 80 8bits odd parity r G05 Group 7 default data loading Upper display Gr 7 Lower display dFLt Range OFF No loading data ON Loading data Run time group 8 r Hxx FEEDBACK POTENTIOMETER CALIBRATION re H ur O rni LL NOTE The run time group 8 will be displayed only if the instrument is in MANUAL mode r H01 Feedback potentiometer calibration enabling This parameter is available only when close loop servomotor output or open loop servomotor output with valve position indication is configured Upper display Gr 8 Lower display En CL Range OFF this selection disables the feedback potentiom eter calibration and the instrument will come back to the first display of the run time group 8 this selection starts the feedback potentiometer calibration NOTE No time out will be applied during feedback potentiome
115. ssion full scale value This parameter will be available only when Out 6 function C E12 is configured PV rt or SP rt Upper display CnF 2 Lower display O6 Hr Range From 1999 to 9999 NOTE Decimal point is positioned as previously selected at CnF 1 In d C d03 C E16 OUT 6 filter on the retransmitted value This parameter will be available only when OUT 6 is configured as process variable retransmission O6 Fn C E12 is equal to PV rt Upper display CnF 2 Lower display O6 FL Range From 0 no filter to 8 seconds NOTE this is a first order digital filter applied to the retransmit ted output value General note on configuration group 2 I Exiting from the configuration group 2 the instrument verifies automatically the congruence of all parameters If a wrong setting is detected the device will show r Ln Err Fili WLI The group 2 parameter passes the congruence test when 1 Only one of the 6 outputs is configured as main output 2 Only of the 6 outputs is configured as secondary output 3 If only one control output is configured it should be the main control output Ain 4 The servomotor must be close loop type if it is one of two control outputs NOTE The instrument may be used as an indicator so that this test is satisfied even if no output is configured as control output II Exiting from the configuration gr
116. status Laut Readout p _ Outs I _ 1 Main control r 07 5 NN scale on the auxiliary function para value for merc retransm P or conditioning Eur Eu ailure detec ITAL aux input HZL value Carn EF 2 Secondary Primary L 1 tullscale Control LO Eventa LO Current output contact of the current SEL n conditioning 5 99 transtormer roe 1 rors _ E Secondary Out failure LAr 1 Fiteron L oute L ir control L rir LAID me alias output inpu rer ron i R IFL mp fbr SSCL NES F di assignement I Auxiliary I 2 Qut 6 _ 21 Secondary LT input LIN L LV control output Eri Event 4 _ _ _ _ _ decimal point _ contact mode value S Position E HSE status F Auxiliary l Out6 Secondary input LINL retransm Er control output safety E full scale initial scale Eg condition PIE I value SLEL readout p Oute I 21 Secondar Li remote L Control output set point on the final scale operatin ceo retransm L Spe value GEEH readout a n 3 Secondary control o
117. t data loading time Group 5 Aux control param 2 L Li J E dE LII 2 Li fs 2 ae ru ni pou dE LII rm 4 cy Ln t od Lr 2 SOLA E Lr 2 EL ED Ld 1 j C od L Cr a Th Anti reset windup Servo motor travel time Servo motor dead band Main control output low limit Main control output high limit Main output max rate of rise Main output cycle time Second control output low limit Second control output high limit Second control output max rate of rise Second control output cycle time Set point low limit Set point high limit Rate of change positive Set point variac Rate of change negative Set point variac Time out for soft start External control for AUTO MAN mode External control for local remote set point External control for reverse direct selection Group 5 default data loading LI Run time Group 6 Alarm setting _ LI 21 Lh 5 Fx dE LII EL ti jt GTA pr LI FT ut poemas 4 LI LI nar TI hoe Li Pu ry n n Pu un I1 m m 1 P
118. ted in a socket give you the possibility to verify if your instrument is equipped with the desired option When KY101 is present the auxiliary input and the digital inputs are present When KY103 is present the auxiliary power supply option is present Fig 22 ON_ DIP 1234 V101 Operative mode and Hardware lock 1 By V101 see fig 22 it is possible to select one of the following operative modes a run time mode without configuration mode b run time and configuration modes c security code setting mode Set V101 according to the following table Modes V101 1 V101 2 V101 3 V101 4 a OFF ON ON ON b OFF ON OFF ON OFF ON OFF OFF 2 When run time mode is selected mode a or b V101 3 allows you to activate deactivate the hardware lock for configuration parameters If V101 3 is ON the lock is activated If V101 3 is OFF the lock is deactivated When the lock is activated no one of the configuration parameter can be modifyed 3 All the others switch combinations are reserved SECURITY CODE SETTING MODE General notes The instrument parameters are divided in two families and each family is divided in groups The first family encompasses all the run time parameters The second family comprises all the configuration parameters A specific security code enables the parameter modification of each family For run time parameters
119. ter calibration procedure r H02 Servomotor low limit positioning This parameter is available only when feedback potentiometer calibration enabling r H01 is equal to On Upper display Gr 8 Lower display POS L Range 0 0 to 100 0 The middle display will show the valve position as a percentage of the full input span By A and 7 push button it is possible to modify the valve position When the desired initial position has been reached push the FUNC push button r H03 Feedback low limit calibration This parameter is available only when feedback potentiometer calibration enabling r HO1 is equal to On Upper display Gr 8 Lower display Fb LC Range OFF To skip calibration and hold the previous value select OFF and then push FUNC To memorize the current position as feedback low limit calibration select and then push FUNC On r H04 Servomotor high limit positioning This parameter is available only when feedback potentiometer calibration enabling r H01 is equal to On Upper display Gr 8 Lower display POS H Range 0 0 to 100 0 The middle display will show the valve position as a percentage of the full input span and WY push button it is possible to modify the valve position When the desired final position has been reached push the FUNC push button r H05 Feedback high limit calibration This parameter is available only when feedback potentiometer cali
120. to OFF disables the serial link the time out will be removed 3 When the modify mode is disabled by V101 V101 3 the A or W push button pressure has no effect MONITOR MODE During the run time mode it is possible to monitor but not modify all configuration parameters When it is desired to verify the instrument configuration proceed as follows 1 A or push button select the monitor mode 2 Push the MENU push button the display will show F Li Lm 1 it shows that configuration group 1 is selected and it encompass all the input parameters The configuration parameter Monitor mode follows the Modify mode sequence NOTES 1 During monitor mode the instrument continues to operate as in run time mode 2 During monitor mode if no push button is depressed for more than 10 s or 30 s according to t out C 110 parameter setting the instrument returns automatically to the normal display mode 28 MODIFY MODE 1 By A or W push button select the modify mode 2 Push the MENU push button If a security code is applied to the configuration parameter the instrument will show L LIT II 3 By A and 7 push button set a value equal to the security code assigned to the configuration mode see Configuration security code at page 24 If the code is different from the security code the instrument automatically returns to the first configuration display otherwise t
121. tput gain This parameter will be available only when the split range is enabled SPLt C F01 Enb Upper display CnF 3 Lower display C Gn Range from 0 50 to 5 00 C F03 Main control output bias This parameter will be available only when the split range is enabled SPLt C F01 Enb Upper display CnF 3 Lower display C bS Range from 100 0 to 100 0 96 of the output span C F04 Secondary control output gain This parameter will be available only when the split range is enabled SPLt C F01 Enb Upper display CnF 3 Lower display SC Gn Range from 0 50 to 5 00 C F05 Secondary control output bias This parameter will be available only when the split range is enabled SPLt C F01 Enb Upper display CnF 3 Lower display SC bS Range from 100 0 to 100 0 96 of the output span C F06 Main control output conditioning This parameter will be available only when main control output is configured Upper display CnF 3 Lower display C Cn Range nor The control output is calculated by the PID C PL The control output is complemented 100 PID calculated value Ouic The control output is conditioned to match a QUICK OPENING flow characteristic Eou The control output is conditioned to match EQUAL PERCENTAGE flow characteristic NOTE about output conditioning Sometimes non linear valves are used where a linear valve is suitable In these cases
122. ut calibration error In Ct current transformer input calibration error FEEd electrical feedback input calibration error 05 AA output 5 mA calibration error 06 AA output 6 mA calibration error When one of these errors is detected contact your supplier Other errors The instrument is also capable to detect the following errors E 100 Error during data saving in FRAM E 110 Error in FRAM handling E 500 Error during auto zero measurement E 501 Error during zero integrator measurement E 502 Error during reference junction measurement NOTE this error may be generated by an ambient temperature higher than 70 158 F or lower than 20 4 F When one of these errors is detected contact your supplier 102 Two errors related with the preliminary hardware setting are detectable 3 wrong position of the V301 dip switch 8 wrong position of the V101 dip switch When one of these error is detected the display blanks and the error code is shown on most significant digit of the upper display Remake V101 or V301 setting GENERAL INFORMATIONS GENERAL SPECIFICATIONS Case Polycarbonate black color self extinguishing degree V 0 according to UL 94 Front protection designed and tested for IP 65 and NEMA 4X for indoor locations when panel gasket is installed Test were performed in accordance with IEC 529 70 1 and NEMA 250 1991 STD Installation panel mounting Rear terminal block
123. ut is forced to 100 a 2 An UNDERRANGE is detected and the device is set for one output only the output is forced to 100 if reverse action is programmed or to 0 if direct action is programmed the device has two control outputs the Main output is forced to 100 and Secondary output is forced 00 b With SF Cn C G07 set to Ov Un when an overrange or an underrange condition is detected the power output is forced to the safety value SF UL C G08 c When SF Cn C G07 is set to OvEr c 1 if an overrange condition is detected the power output is forced to the safety value SF UL C G08 c 2 if an underrange condition is detected the instrument will operate as described at point a 2 d When SF Cn C G07 is set to d 1 if an underrange condition is detected the power output is forced to the safety value SF UL C G08 d 2 if an overrange condition is detected the instrument will operate as described at point a 1 NOTE IN ALL CASES ABOVE DESCRIBED THE OUTPUTS WILL BE FURTHER INFLUENCED BY OUTPUT CONDITION ING When servomotor open loop is configured the Condition for output safety value SF Cn C G07 acts as described below 1 When SF Cn C G07 is set to Cnd A and an overrange or an underrange condition is detected the servomotor is driven to its high limit position OUT 3 A will be maintained closed 2 With SF Cn
124. utput auxiliary ALL conditioning 5 2 4 ELOELECTROMC 170 APP XKC 000 04 99
125. wrong calibration parameter The device resets automatically after a time out of 6 s 20 s if serial link is enabled Configuration and run time parameter errors When one of this error is detected following the procedures described for standard parameter modification reach the group with the wrong parameter setting and correct it every keystroke restarts the time out The time out is disabled when modify configuration parameters mode is enabled When the error is corrected push MENU until the device resets if in run mode or end the modify configuration parameters mode following the normal procedure Repeat the above described procedure if another error is shown 101 Feedback potentiometer adjustment error If this error is detected span less than 20 of complete potentiometer travel push any key to load default calibration parameters Then remake the calibration following the normal procedure see Gr 8 Calibration parameter errors The instrument will show on the lower display one of the following indications fi l te main termocouple input calibration error 1 could junction compensation error main RTD input calibration error mA input calibration error 1 5 main 5V input calibration error 1 10 main 10 V input calibration error auxiliary mA input calibration error 1 5 5V input calibration error 1 10 auxiliary 10 V inp
126. xternal contact only OFF the local remote selection is made by RSP push button or serial link only r E19 External control for reverse direct output action selection This parameter is available when one of the logic inputs is configured for direct reverse output action selection Upper display Gr 5 Lower display E rd Range On the reverse direct selection is made by external contact only OFF the reverse direct selection is made by Cn Ac r d08 parameter or serial link only r E20 Group 5 default data loading Upper display Gr 5 Lower display dFLt Range OFF No loading data ON Loading data Run time group 6 r Fxx r F02 Alarm 1 configuration ALARM SETTING This parameter is available only when OUT 1 is configured as alarm 1 output O1 Fn C E01 ALr 1 ur oF Upper display Gr 6 Lower display A1 Cn nrri Range High alarm outside band with automatic ree reset L A Low alarm inside band with automatic reset H A Ac High alarm outside band with automatic r F01 Alarm 1 type reset and acknowledge This parameter is available only when OUT 1 is configured as L A Ac Low alarm inside band with automatic reset alarm 1 output O1 Fn 01 ALr 1 and acknowledge Upper display Gr 6 H L High alarm outside band with manual reset Lower display A1 tP L L Low alarm inside band with manual reset Range Proc Alarm on process variable NOTE When alar

Download Pdf Manuals

image

Related Search

Related Contents

klicken - Schmidtmeister  Fisher DCS-TS750 User's Manual  Bushnell 18-0833 Binoculars User Manual  Philips KEY019  8 page user manual in PDF  JVC CA-MD70R User's Manual  Liste ateliers  DUAL-CD-SPIELER  RX-F31S  MANUEL D`INSTRUCTIONS  

Copyright © All rights reserved.
Failed to retrieve file