Home
2080-SG001 - Literature Library
Contents
1. 4 2080 LC50 48AWB 28 20 2080 LC50 480WB 28 20 6 2080 LC50 480BB 28 20 3 PTO PWM 6 2080 LC50 480VB 28 20 3 PTO PWM 6 1 For Micro830 and Micro850 you need firmware revision 6 01 2 Maximum number of embedded HSC supported Publication 2080 SG001D EN P December 2013 or later to use PWM output Micro800 Programmable Controller Family Selection Guide 7 Micro800 Catalog Number Details 2080 LC 30 24 Q V B L Power Supply Bulletin Number AM 120 240V AC Base Unit B 24V DC LC10 Micro810 D 12V DC LC20 Micro820 LC30 Micro830 Output Type LC50 Micro850 B 24V DC Source Number of 0 ee DC Sink 10 12 16 20 24 48 Seay Input Type A 110V AC or 110 220V AC Q 24V AC DC D 12V DC 1 Available for Micro810 only Connected Components Connected Components Workbench is the programming and configuration Workbench Software Attribute Delivery software environment for the Micro800 controllers and our Connected Components products offering It simplifies setup and usage enabling applications ranging from simple Smart Relay up to Standalone Machine control Visit the website for the most up to date product information downloads and tools http ab rockwellautomation com Programmable Controllers Connected Co mponents Workbench Software Standard Edition Basic Download Connected
2. Power supply voltage range 20 4 26 4V DC Class 2 1 0 rating Input 120V AC 16 mA Input 24V DC 8 8 mA Input 24V DC 8 8 mA Output 2 A 240V AC Output 2 A 240V AC 2 A 24V DC Output 24V DC 1 A per point Surrounding air 2 A 24V DC temperature 30 C 24V DC 0 3 A per point Surrounding air temperature 65 C Insulation stripping length 7 mm 0 28 in Enclosure type rating Meets IP20 Pilot duty rating C300 R150 Isolation voltage 250V continuous Reinforced Insulation Type Output to Aux and Network Inputs to Outputs Type tested for 60 s 3250V DC Output to Aux and Network Inputs to Outputs 250V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 3250V DC Output to Aux and Network Inputs to Outputs 50V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC 1 0 to Aux and Network Inputs to Outputs 150V continuous Reinforced Insulation Type Input to Aux and Network Type tested for 60 s 1950V DC Input to Aux and Network 50V continuous Reinforced Insulation Type Input to Aux and Network Type tested for 60 s 720V DC Inputs to Aux and Network North American temp code 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiri publication 1770 4 1 Input Specifications Att
3. 25g Shock non operating IEC 60068 2 27 Test Ea Unpackaged Shock DIN mount 25 g PANEL mount 45 g Emissions CISPR 11 Group 1 Class A ESD immunity IEC 61000 4 2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10V m with 200 Hz 5096 Pulse 100 AM 1890 MHz 10V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV at 5 kHz on power ports 2 kV at 5 kHz on signal ports Surge transient immunity Publication 2080 SG001D EN P December 2013 IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on power ports 1 kV line line DM and 2 kV line earth CM on signal ports Micro800 Programmable Controller Selection Guide 23 Environmental Specifications Attribute Value IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Conducted RF immunity Certifications Certification when Value product if marked c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E322657 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified or U S and Canada See UL File 334470 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements N 61000 6 2 Industrial Immunity EN 61000 6 4
4. 40 Micro800 Programmable Controller Family Selection Guide Notes Publication 2080 SG001D EN P December 2013 Select Micro850 Expansion 1 0 The 2085 I O expansion modules provide superior functionality in a small sized low cost package A variety of digital and analog modules complement and extend the capabilities of Micro850 controllers by maximizing the flexibility of I O count and type Micro850 expansion I O modules include high density discrete and analog I O modules including a high accuracy RTD and Thermocouple module There are available solid state output modules which are recommended to reduce switching noise and for applications which require more switching cycles than relays Triac outputs are available for AC loads Sink and source transistor outputs are available for DC loads The following section provides the list of available Micro850 expansion I O modules and their specifications Micro850 Expansion 1 0 Modules Catalog Number Type Description 2085 1A8 Discrete 8 point 120V AC input 2085 IM8 Discrete 8 point 240V AC input 2085 0A8 Discrete 8 point 120 240V AC Triac Output 2085 1016 Discrete 16 point 12 24V DC Sink Source Input 2085 1032T Discrete 32 point 12 24V DC Sink Source Input 2085 0V16 Discrete 16 point 12 24V DC Sink Transistor Output 2085 0B16 Discrete 16 point 12 24V DC Source Transistor Output 2085 0W8 Discrete 8 point AC DC Relay Output 2085 0W16 Di
5. WA rower 9 OUT Micro850 DOOGOQOOOOOOUOUQUGUUE ET IS General Specifications 2080 LC50 24AWB 2080 LC50 240WB 2080 LC50 240VB 2080 LC50 240BB Attribute 2080 LC50 24AWB 2080 LC50 240BB Number of 1 0 24 14 inputs 10 outputs Dimensions HxWxD 90 x 158 x 80 mm 3 54 x 6 22 x 3 15 in Shipping weight approx 0 423 kg 0 933 Ib Publication 2080 SG001D EN P December 2013 Micro800 Programmable Controller Family Selection Guide 31 General Specifications 2080 LC50 24AWB 2080 LC50 240WB 2080 LC50 240VB 2080 LC50 240BB Attribute 2080 LC50 24AWB 2080 LC50 240WB 2080 LC50 240VB 2080 LC50 240BB Wire size Solid 0 2 mm2 24 AWG 2 5 mm 14 AWG rated 90 C 194 F insulation max Stranded 0 2 mm 24 AWG 2 5 mm 14 AWG Wiring category 2 on signal ports 2 on power ports 2 on communication ports Wire type Use copper conductors only Terminal screw torque 0 6 Nm 4 4 Ib in max using a 2 5 mm 0 10 in flat blade screwdriver Input circuit type 120V AC 24V DC sink source standard and high speed Output circuit type Relay 24V DC sink standard 24V DC source standard and high speed and high speed Power consumption 28W Power supply voltage range 20 4 26 4V DC Class 2 1 0 rating Input 120V AC 16 mA Output 2 A 240 V AC 24V DC Input 24V 8 8 mA Output 2 A 240 V AC 24V DC Input 24V 8 8 mA Output 24V DC Class 2 1
6. max screwdriver rated 90 C Publication 2080 SG001D EN P December 2013 56 Micro800 Programmable Controller Family Selection Guide 2080 RTD2 3 9 4 E B OO OU NE NC NC AO CHD CHO KC NC NC 080 TC2 1 23 4 8 foto cC NG NG NC AC CHD CIC NC NC NC Thermocouple and RTD 2080 TC2 2080 RTD2 Specifications 2080 RTD2 2080 TC2 Catalog Type Common mode Normal mode rejection ratio rejection ratio 2080 RTD2 2 channel non isolated RTD 100 dB 70 dB 50 60 Hz 50 60Hz 2080 TC2 2 channel non isolated Thermocouple Normal mode rejection ratio RTD types supported Thermocouple types supported Terminal screw torque 00 Q Platinum 385 70 dB 50 60 Hz 0 22 0 25 Nm 1 95 2 21 Ib in using a 2 5 mm 0 10 in flat blade screwdriver 200 Q Platinum 385 500 Q Platinum 385 1000 Platinum 385 100 Q Platinum 392 200 Q Platinum 392 500 Q Platinum 392 1000 Q Platinum 392 10 Q Copper 427 20 Q Nickel 672 604 Q Nickel lron 518 J K N T E R S B Thermocouple Operating Non operating Surrounding air max North American temperature temperature temp code 20 65 C 40 85 C 65 C 149 F T4 4 149 F 40 185 F Catalog Type Common mode rejection ratio 2080 RTD2 2 channel 100 dB non isolated RTD 50 60Hz 2080 TC2 2 channel non isolated Catalog Wire size 2080 RTD2 Solid 0 14 mm 26
7. Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions 1 See the Product Certification link at http www rockwellautomation com products certification for Declaration of Conformity Certificates and other certification details Publication 2080 SG001D EN P December 2013 24 Micro800 Programmable Controller Selection Guide Micro830 24 Point Controllers Allen Bradley General Specifications 24 point controllers Attribute 2080 LC30 240WB 2080 LC30 240VB 2080 LC30 240BB Input circuit type 24V DC sink source standard and high speed Output circuit type Relay 24V DC sink standard and 24V DC source standard and high speed high speed Event input interrupt Yes support 1 0 rating Input 24V DC 8 8 mA Input 24V DC 8 8 mA Output 2 A 240 V AC general use Output 24V DC Class 2 1 A per point Surrounding air temperature 30 C 24V DC Class 2 0 3 A per point Surrounding air temperature 65 C Isolation voltage 250V continuous Reinforced Insulation Type 50V continuous Reinforced Insulation Type 1 0 to Aux and Network Outputs to Aux and Network Inputs to Outputs Inputs to Outputs Type tested for 60 s 720V DC Inputs to Aux Type tested for 60 s
8. Outputs to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC Inputs to Aux and Network 3250V DC Outputs to Aux and Network Inputs to Outputs 50V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC 1 0 to Aux and Network Inputs to Outputs Publication 2080 SG001D EN P December 2013 Micro800 Programmable Controller Selection Guide Environmental Specifications Attribute Temperature operating Value IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 65 C 4 149 F 21 Temperature surrounding air max 65 C 149 F Temperature non operating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 non condensing Vibration IEC 60068 2 6 Test Fc Operating 2 g Q 10 500 Hz Shock operating IEC 60068 2 27 Test Ea Unpackaged Shock 25g Shock non operating IEC 60068 2 27 Test Ea Unpackaged Shock DIN mount 25 g PANEL mount 35 g Emissions CISPR 11 Group 1 Class A ESD immunity IEC 61000 4 2 6 kV contact discharges 8 kV air disc
9. and 2 kV line earth CM on signal ports 1 kV line earth CM on communication ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 8096 AM from 150 kHz 80 MHz Certifications Certification when product is marked 1 c UL us Micro800 Programmable Controller Family Selection Guide 35 Value UL Listed Industrial Control Equipment certified for US and Canada See UL File E322657 U Listed for Class I Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E334470 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab N 61000 6 2 Industrial Immuni E EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B Industrial Requirements ty European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emi ssions EtherNet IP ODVA conformance tested to EtherNet IP specifications KC 1 See the Product Certifica Korean Registration of Broadcastin compliant with Article 58 2 of Radio Waves Act ion link at http www rockwellautomati g and Communications Equipment Clause 3 on com products certification for Declaration of Conformity Certificates and other certification details Micro850
10. 14 1 5 mm 26 16 AWG Stranded 0 14 1 0 mm 26 18 AWG rated 90 C 194 F insulation max Non operating Surrounding air max temperature 65 C 149 F 40 185 F T4 North American temp code T4 Isolation voltage 500V AC North American temp code Publication 2080 SG001D EN P December 2013 58 Micro800 Programmable Controller Family Selection Guide AB Publication 2080 SG001D EN P December 2013 DeviceNet 2080 DNET20 Specifications 2080 DNET20 DeviceNet Communication Rate max 125 Kbps 420 m 1378 ft 250 Kbps 200 m 656 ft 500 Kbps 75 m 246 ft DeviceNet current 24V DC 300 mA Class 2 Wire size 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated 75 C 167 F or greater 1 2 mm 3 64 in insulation max Network protocol Backplane Power Number of nodes max power dissipation consumption 1 0 Slave Messaging 50mA Q24VDC 1 44W 20 nodes for I O operation Poll Command High Speed Counter 2080 MOT HSC Specifications 2080 MOT HSC Input Wire size Number of inputs Frequency max 250 kHz 50 Solid 1 Quadrature ABZ duty 0 14 1 5 mm 26 16 AWG differential input Stranded 0 14 1 0 mm 26 18 AWG rated 90 C 194 F insulation max Input impedance Pulse width All supply power Isolation voltage min and or current ratings 3580 Q 2 us Input
11. 2 PTO is supported on Micro830 catalog numbers ending in BB or VB only Publication 2080 SG001D EN P December 2013 20 Micro800 Programmable Controller Selection Guide Inputs and Outputs Micro830 Controllers Number and Type of Inputs Outputs Catalog Number Inputs Outputs PTO PWM HSC 120VAC 24V DC V AC Relay 24V Sink 24V Source SUPPOT Support 2080 LC30 100WB 6 4 2 2080 LC30 100VB 6 4 1 2 2080 LC30 16AWB 10 6 2080 LC30 160WB 10 6 2 2080 LC30 160VB 10 6 1 2 2080 LC30 240BB 14 10 2 4 2080 LC30 240VB 14 10 2 4 2080 LC30 240WB 14 10 4 2080 LC30 48AWB 28 20 2080 LC30 480BB 28 20 3 6 2080 LC30 480VB 28 20 3 6 2080 LC30 480WB 28 20 6 1 Maximum number of HSC supported Micro830 Controllers General Features Attribute 10 point 16 point 24 point 48 point Number of 1 0 2080 LC30 100WB 2080 LC30 100VB 2080 LC30 16AWB 2080 LC30 16QWB 2080 LC30 16QVB 10 6 inputs 4 outputs 16 10 inputs 6 outputs 2080 LC30 240WB 2080 LC30 24Q0VB 2080 LC30 240BB 2080 LC30 48AWB 2080 LC30 480WB 2080 LC30 480VB 2080 LC30 480BB 24 14 inputs 10 outputs 48 28 inputs 20 outputs Dimensions HxWxD 90 x 100 x 80 mm 3 54 x 3 94 x 3 15 in 90 x 100 x 80 mm 3 54 x 3 94 x 3 15 in 90 x 150 x 80 mm 3 54 x 5 91 x 3 15 in 90 x 230 x 80 mm 3 54 x 9 06 x 3 15 in Shipping weight approx 0 302 kg 0 666 Ib 0 302 kg 0 666 Ib 0 423 kg 0 93
12. 2 kV line earth CM on signal ports 1 kV line earth CM on communication ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Certifications Certification when product is marked 1 c UL us Micro800 Programmable Controller Family Selection Guide 39 Value UL Listed Industrial Control Equipment certified for US and Canada See UL File E322657 U Listed for Class I Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E334470 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions EtherNet IP ODVA conformance tested to EtherNet IP specifications KC 1 See the Product Certifica Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 ion link at http www rockwellautomation com products certification for Declaration of Conformity Certificates and other certification details Publication 2080 SG001D EN P December 2013
13. 48 Point Controllers 2080 1 C50 48Q0WB i MAC ID E wwsccemm 0123456789 M0 11 12 13 14 15 16 17 18 19 20 21 22 23 24 28 26 7 N mss as Sho123456789 10 19 12 13 14 15 16 17 18 19 our radiey 9 Allen Bradley ej General Specifications 2080 LC50 48AWB 2080 LC50 480WB 2080 LC50 480VB 2080 LC50 480BB 2080 LC50 48AWB 2080 LC50 480WB 2080 LC50 480VB 2080 LC50 480BB Attribute Number of 1 0 48 28 inputs 20 outputs Dimensions HxWxD 90 x 238 x 80 mm 3 54 x 9 37 x 3 15 in Shipping weight approx 0 725 kg 1 60 Ib Publication 2080 SG001D EN P December 2013 36 Micro800 Programmable Controller Family Selection Guide General Specifications 2080 LC50 48AWB 2080 LC50 480WB 2080 LC50 480VB 2080 LC50 480BB Attribute 2080 LC50 48AWB 2080 LC50 480WB 2080 LC50 480VB 2080 LC50 480BB Wire size Solid 0 2mm 24 AWG 2 5 mm 14 AWG rated 90 C 194 F insulation max Stranded 0 2 mm 24 AWG 2 5 mm 14 AWG Wiring category 2 on signal ports 2 on power ports 2 on communication ports Wire type Use copper conductors only Terminal screw torque 0 4 0 5 Nm 3 5 4 4 Ib in using a 0 6 x 3 5 mm flat blade screwdriver Input circuit type 120V AC 24V DC sink source standard and high speed Output circuit type Relay 24V DC sink standard 24V DC source standard and and high speed high speed Power consumption 33 W
14. 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 10V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B Immunity IEC 61000 4 4 2 kV 5 kHz on signal ports Surge Transient Immunity IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on power ports 2 kV line earth CM on shielded ports Conducted RF Immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Certifications All Micro800 Expansion 1 0 Modules Certification when Value product is marked 1 c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E322657 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E334470 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 See the Product Certification link athttp www rockwellautomation com products certification
15. 720V DC 1 0 to Aux and Network Inputs to Outputs and Network 3250V DC Outputs to Aux and Network nputs to Outputs Pilot duty rating C300 R150 2080 LC30 24QWB only Environmental Specifications Attribute Value Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 65 C 4 149 F Temperature surrounding 65 C 149 F air max Temperature non operating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 non condensing Publication 2080 SG001D EN P December 2013 Micro800 Programmable Controller Selection Guide 25 Environmental Specifications Attribute Vibration Value IEC 60068 2 6 Test Fc Operating 2 g 10 500 Hz Shock operating IEC 60068 2 27 Test Ea Unpackaged Shock 25g Shock non operating IEC 60068 2 27 Test Ea Unpackaged Shock DIN mount 25 g PANEL mount 35 g Emissions CISPR 11 Group 1 Class A ESD immunity IEC 61000 4 2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 8096 AM from 80 2000 MHz 10V m with 200 Hz
16. A per point surrounding air temperature 30 C 24 V DC Class 2 0 3 A per point surrounding air temperature 65 C Isolation voltage 250V continuous Reinforced nsulation Type Output to Aux and Network Inputs to Outputs Type tested for 60 s 3250V DC Output to Aux and Network nputs to Outputs 150V continuous Reinforced nsulation Type Input to Aux and Network Type tested for 60 s 1950V DC nput to Aux and Network 250V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 3250V DC Output to Aux and Network Inputs to Outputs 50V continuous Reinforced Insulation Type Input to Aux and Network Type tested for 60 s 720V DC Inputs to Aux and Network 50V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC 1 0 to Aux and Network Inputs to Outputs Pilot duty rating C300 R150 Insulation stripping length 7 mm 0 28 in Enclosure type rating Meets IP20 North American temp code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Publication 2080 SG001D EN P December 2013 32 Micro800 Programmable Controller Family Selection Guide Publication 2080 SG001D EN P December 2013 DC Input Specifications 208
17. Output 24V DC Input module 50V continuous Basic Insulation Type Inputs Outputs to Backplane Type tested for 60s 720V DC Inputs Outputs to Backplane Micro800 Accessories Micro810 LCD 2080 LCD Operating Temperature Temperature North American temperature surrounding air max nonoperating temp code 20 55 C 55 C 131 F 40 85 C 40 185 F T5 4 131 F Micro810 USB Adapter 2080 USBADAPTER USB cable Temperature Temperature Temperature North connector type operating surrounding air max non operating American temp code USB Type A B 20 55 C 55 C 131 F 40 85 C T5 Male Male 4 131 F 40 185 F Micro800 Programmable Controller Family Selection Guide 59 External Power Supply 2080 PS120 240VAC Attribute Value Dimensions HxWxD 90 x 45 x 80 mm 3 55 x 1 78 x 3 15 in Shipping weight 0 34 kg 0 75 Ib Supply voltage rangel 100V 120V AC 1A 200 240V AC 0 5A Supply frequency 47 63 Hz Supply power 24V DC 1 6A Inrush current max 24 A Q 132V for 10 ms 40 A 263V for 10 ms Power consumption Output power 38 4 W Q 100V AC 38 4 W 240V AC Power dissipation Input power 45 1 W 100V AC 44 0W 240V AC Isolation voltage 250V continuous Primary to Secondary Reinforced Insulation Type Type tested for 60s 2300V AC primary to secondary and 1480V AC primary to earth ground Output rati
18. Port No Yes Yes adds additional serial communications with 2080 SERIALISOL Modbus RTU and ASCII protocols isolated for increased noise immunity Digital Input Output Relay and No Yes Yes e 4 channel inputs outputs or combination Combination Modules modules 2080 104 2080 I040B4 2080 I040VA 2080 0B4 2080 0V4 2080 0W4I configurable as voltage and current inputs sink or source output e 4 channel relay outputs High Speed Counter No Yes Yes e Up to a minimum of 250 KHz differential line 2080 MOT HSC driver for improved noise immunity and additional dedicated 1 0 One Quadrature ABZ differential inputs alternately configurable for pulse internal pulse with external direction A up and B down input configurations and quadrature mode e User configurable minimum and maximum values preset and Z operation DeviceNet Scanner No Yes Yes e Scanner mode scan devices such as 2080 DNET20 CompactBlock LDX PowerFlex drives overloads and sensors Remote LCD No Yes No Operator interface for configuring such settings 2080 REMLCD as IP address on Micro820 controller e With RS232 and USB ports Non isolated Unipolar Analog No Yes Yes e adds up to 20 embedded analog 1 0 with 12 bit Input Output resolution with 48 point controllers 2080 IF2 2080 IF4 2080 OF2 e 2 channels for 2080 IF2 2080 OF2 e Achannels for 2080 IF4 Non isolated Thermocouple No Yes Yes e for temperature control when used with PID 2080 TC2 e 2channels for 2080 TC2 an
19. for Declaration of Conformity Certificates and other certification details Publication 2080 SG001D EN P December 2013 Select Micro800 Plug in Modules and Accessories D Aden Bradiey V 2080 MEMBAK RTC O uer amp radey C Allen Bradloy ay LLL ole KASEI 2000 TRIMPOT Micro800 plug in modules extend the functionality of embedded I O without increasing the footprint of the controller It improves performance by adding additional processing power or capabilities and adds additional communication functionality Micro820 Micro830 and Micro850 controllers support plug in modules Micro800 accessories consist of a Remote LCD compatible with Micro820 only an LCD with keypad compatible with Micro810 only a USB adapter compatible with Micro810 only and an expansion power supply Publication 2080 SG001D EN P December 2013 52 Micro800 Programmable Controller Family Selection Guide Micro800 Plug in Modules and Accessories Features and Compatibility Plug in Accessory Supported by Supported by Supported by Feature Micro810 Micro820 Micro830 Micro850 1 5 LCD and Keypad Yes No No backup module for Micro810 controllers 2080 LCD e configure Smart Relay Function Blocks Micro810 USB Adapter Yes No No USB programming access 2080 USBADAPTER External Power Supply Yes Yes Yes optional controller power supply 2080 PS120 240VAC RS232 485 Isolated Serial
20. instruction can vary greatly from program to program and from programming language to programming language Micro800 Communication Options Controller USB programming port Embedded Serial Port Serial Port Plug In Embedded Ethernet CIP Serial Modbus RTU ASCII Binary EtherNet IP Modbus TCP Micro810 Yes with adapter No Micro820 Yes with 2080 REMLCD Yes Master Slave Yes Yes Yes Micro830 Yes Yes Master Slave Yes No No Micro850 Yes Yes Master Slave Yes Yes Yes Micro800 Controllers Analog 1 0 and TC RTD Comparison Attribute Micro810 Micro820 Micro800 Micro850 with plug ins with expansion 1 0 Performance level LOW LOW MEDIUM HIGH Isolation to controller None None None Yes increased noise immunity Resolution and Nominal Accuracy Analog Input 10 bit 5 2 with calibration Analog l O 12 bit 5 2 with calibration Analog 0 12 bit 1 TC RTD 1 C CJC for TC 1 2 C Analog Input 14 bit input 0 1 Analog Output 12 bit output 0 133 current 0 425 voltage TC 0 5 3 0 C RTD 0 2 0 6 C Input update rate and filtering Update rate only dependent on program scan limited filtering Update rate only dependent on program scan limited filtering 200 ms ch 50 60 Hz filtering 8 ms all channels with or without 50 60 Hz filtering Recommended maximum shielded cable length 10m 100 m 1 These numbers are guideline
21. sink outputs 30V DC max 2 A surge 2 s min Publication 2080 SG001D EN P December 2013 54 Micro800 Programmable Controller Family Selection Guide Specifications 2080 104 2080 1040B4 2080 10404 2080 0B4 2080 0V4 Catalog Off state voltage Off state Power supply Mounting torque Status North American current voltage indicators temp code 2080 104 DC DC 0 2 Nm 4 yellow T4 5V DC max 1 5 mA max 1 48 Ib in 2080 I040B4 10 8V DC min 8 yellow AG 30V DC max 2080 1040V4 3 5V AC rms i 2080 0B4 2080 0V4 4 yellow Catalog Terminal base screw torque Isolation voltage Wire size 2080 104 0 22 0 25 Nm 50V continuous Basic Insulation Type Inputs to 0 2 2 5 mm 24 12 AWG solid or 1 95 2 21 Ib in Backplane stranded copper wire rated 90 C using a 2 5 mm 0 10 in Type tested for 60 s 720V DC Inputs to Backplane 194 F or greater insulation max 3 flat blade screwdriver 2080 I040B4 50V continuous Basic Insulation Type Inputs to P Outputs I Os to Backplane 2080 040V4 Type tested for 60 s 720V DC I Os to Backplane 2080 0B4 2080 0V4 Catalog Operating Non operating Surrounding Relative Vibration Shock Shock temperature temperature air max humidity operating non operating 2080 104 20 65 C 40 85 C 65 C 149 F 5 95 2g 10 500Hz 25g 25g 4 149 F 40 185 F noncondensing
22. 0 00 CPR 9 SR 6 e Microsoft Help Viewer 1 1 Note The Developer Edition requires an activation key See the FactoryTalk Activation help for additional information on activating Rockwell Automation software products Number and Types of Inputs Outputs Select a Micro810 Controller l ececooooeoeooo29 QD Allen Bradley As the smallest of the Micro800 family the Micro810 controller is available in a 12 point version with two 8 A and two 4 A outputs that eliminate the need for external relays The Micro810 features embedded smart relay function blocks that can be configured from a 1 5 LCD and keypad The function blocks include Delay OFF ON Timer Time of Day Time of Week and Time of Year for applications requiring a programmable timer and lighting control Programming can also be done through a program download via USB programming port using Connected Components Workbench Software To help you select a Micro810 controller consult the specifications for each catalog in the next section Catalog Number Power Inputs Outputs Analog In 0 10V 120V AC 240V AC 12 24V DC V AC Relay 24V DC SRC Shared with DC In 2080 LC10 120WB 24V DC 8 4 4 2080 LC10 12AWA 120 240VAC 8 4 2080 LC10 120BB 12 24V DC 8 4 4 2080 LC10 12DWD 12V DC 8 4 4 Publication 2080 SG001D EN P December 2013 10 Micro800 Programmable Controller Family Selection Guide Specifications Attribute 2
23. 0 LC50 240BB 2080 LC50 240VB 2080 LC50 240WB Attribute High Speed DC Input Standard DC Input Inputs 0 7 Inputs 8 and higher Number of Inputs 8 6 Voltage category 24V sink source Input group to backplane isolation Verified by one of the following dielectric tests 720V DC for 2 s 50V DC working voltage IEC Class 2 reinforced insulation On state voltage range 16 8 26 4V DC 65 C 149 F 16 8 30 0V DC 30 C 86 F 10 26 4V DC 65 C 149 F 10 30 0V DC 30 C 86 F Off state voltage max 5V DC Off state current max 1 5 mA On state current min 5 0 mA Q 16 8V DC min 1 8 mA Q 10V DC min On state current nom 7 6 mA 24V DC nom 6 15 mA 24V DC nom On state current max 12 0 mA 30V DC max 12 0 mA 30V DC max Nominal impedance 3kQ 3 74 KQ IEC input compatibility Type 3 Output Specifications Micro800 Programmable Controller Family Selection Guide AC Input Specifications 2080 LC50 24AWB 33 Attribute Value Number of inputs 14 On state voltage min 79V AC min On state voltage max 132V AC max On state current min 5 mA On state current max 16 mA Input frequency nom 50 60 Hz Input frequency min 47 Hz Input frequency max 63 Hz max Off state voltage max 20V AC Q 120V AC Off state current max 2 5 mA Q 120V AC Inrush current max 250 mA
24. 0 s 3250V DC 1 0 to Aux and Network Inputs to Outputs 50V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC 1 0 to Aux and Network Inputs to Outputs 250V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC Inputs to Aux and Network 3250V DC Outputs to Aux and Network Inputs to Outputs AC input filter setting 16 ms for all embedded inputs In Connected Components Workbench go to the Embedded 1 0 configuration window to re configure the filter setting for each input group 1 See the Micro810 User Manual publication 2080 UM001 for more Micro810 controller specifications Publication 2080 SG001D EN P December 2013 Environmental Attribute Temperature operating Micro800 Programmable Controller Family Selection Guide 11 Value IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 0 55 C 32 131 F Temperature surrounding air max 55 C 131 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Non operating Cold IEC 60068 2 2 Test Bb Unpackaged Non operating Dry Heat IEC 60068 2 14 Test Na Unpackaged Non operating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95
25. 080 LC10 12AWA 2080 LC10 120WB 2080 LC10 12DWD 2080 LC10 120BB Number of 0 8 Input 4 digital 4 analog digital configurable 4 Output Dimensions 91 x 75 x 59 mm HxWxD 3 58 x 2 95 x 2 32 in Supply voltage range 85 263V DC 20 4 26 4V DC 10 8V 13 2V DC 11 4V 26 4V DC Supply frequency range 47 63 Hz AC supply Voltage range 100 240V AC 50 60 Hz 24V DC Class 2 12V DC Class 2 12 24V DC Class 2 Power consumption oV A 3W 1 0 rating Input 120 240V AC Input 24V DC 8 mA Input 12V DC 8mA Input 24V DC 8 mA Output Relay 00 amp 01 8 A 240V AC B300 R300 General Use Relay 02 amp 03 4 A Q 240V AC C300 R150 General Use Output 24V DC 1A 25 C 24V DC 0 5A 55 C Operating temperature 0 55 C 32 131 F Shipping weight approx 0 203 kg 0 448 Ib Wire size 0 32 2 1 mm 22 14 AWG solid copper wire or 0 32 1 3 mm 22 16 AWG stranded copper wire rated 90 C 194 F insulation max Wiring category 2 on signal ports 2 on power ports Wiring torque 1 085 Nm 8 Ib in Wire type use Copper Conductors only Fuse type Rated 250V 3 15 A RADIAL Enclosure type rating Meets IP20 North American temp code T5 Insulation stripping length 7 mm 0 28 in Isolation voltage 250V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 6
26. 2080 I040B4 2080 I040V4 2080 0B4 2080 0V4 Specifications 2080 0WA4l Catalog Input Output Inrush current Backplan Output current Output current Output power resistive max e power resistive inductive 2080 OW4I 4 channel 120 mA Q 3 3V 3 3 VDC 2A Q 5 30V DC 1 0A steady state 250V A for 125V AC resistive loads relay output 120 mA Q 24V 38 mA 0 5 A Q 48V DC 5 28V DC 480V A for 240V AC resistive loads 0 22 A 125V DC 0 93 A steady state 60V A for 30V DC resistive loads 2A 125V AC 30V DC 24V A for 48V DC resistive loads 2 A 240V AC 0 5 A steady state 27 5V A for 125V DC resistive loads 48V DC 0 22 A steady state Q 125V DC 2 0 A steady state 15 A make Q 125V AC PF cos 0 204 2 0 A steady state 7 5 A make 240V AC PF cos 0 204 Publication 2080 SG001D EN P December 2013 Micro800 Programmable Controller Family Selection Guide 55 194 F insulation max Catalog Output power inductive break max Pilot duty Minimum load per Initial contact Output delay time rating point resistance of relay max max 2080 OW4l 180 VA for 125V AC inductive loads C300 R150 10 mA 30 MQ 10 ms ON or OFF 180 VA for 240V AC inductive loads 28 VA for 28 8V DC inductive loads 28 VA for 48V DC inductive loads 28 VA for 125V DC inductive loads Catalog Relay contact 0 35 power factor Volts max Amp
27. 24V AC DC sink source Power dissipation total 4 5 W 7W Power supply 24V DC Status indicators 16 yellow indicators 32 yellow indicators Isolation voltage 50V continuous Reinforced Insulation Type channel to system Type tested 720V DC for 60 s Enclosure type rating Meets IP20 North American temp code T4 Operating voltage range 10 30V DC Class 2 21 6 26 4V AC Class 2 See Derating Curve for 2085 1016 and Derating Curve for 2085 I032T on page 43 Off state voltage max 5V DC Micro800 Programmable Controller Family Selection Guide 2085 1016 and 2085 1032T DC Sink Source Input Modules 43 Attribute 2085 1016 2085 1032T Off state current max 1 5mA 1 2mA On state current min 1 8 mA 10V DC On state current nom 6 0 mA 24V DC 5 2 mA Q 24V DC On state current max 8 0 mA Q 30V DC 7 0 mA Q 30V DC Input impedance max 3 9 kQ 4 6 KQ IEC input compatibility Type 3 Type 1 1 Meets IEC Type 1 24V DC Input Specifications 2 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 3 RTB hold down screws should be tightened by hand They should not be tightened using a power tool Derating Curve for 2085 1016 Input voltage V 30 26 4 Temp 30 C 65 C heap Derating Curve for 2085 1032T Input voltage V Number L of input
28. 3 Ib 0 725 kg 1 60 Ib Operating temperature 20 65 C 4 149 F Wire size 0 14 2 5 mm 26 14 AWG solid copper wire or 0 14 1 5 mm 26 16 AWG stranded copper wire rated 90 C 194 F insulation max 0 2 2 5 mm 24 14 AWG solid copper wire or 0 2 2 5 mm 24 14 AWG stranded copper wire rated 90 C 194 F insulation max Wiring category 2 on signal ports 2 on power ports Wire type Use copper conductors only Terminal screw torque max 0 6 Nm 4 4 Ib in using a 2 5 mm 0 10 in flat blade screwdriver Power consumption 7 88W 12 32W 18 2 W Power supply voltage range 20 4 26 4V DC Class 2 Insulation stripping length 7 mm 0 28 in Enclosure type rating Meets IP20 North American temp code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Publication 2080 SG001D EN P December 2013 General Specifications Attribute Micro800 Programmable Controller Selection Guide 21 Micro830 Controllers 10 and 16 Point Controllers Qu ey m O00000900009 mw e o mm o mm o Q Allen Bradley Q Allen Bradtey mc MicroB30 amp 10 point controllers 2080 LC30 100WB 2080 LC30 100VB Input circuit type 12 24V sink source standard 24V sink source high speed Outpu
29. 50 Pulse 10096 AM 900 MHz 10V m with 200 Hz 5096 Pulse 100 AM 1890 MHz 10V m with 1 kHz sine wave 8096 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV at 5 kHz on power ports 2 kV at 5 kHz on signal ports Surge transient immunity IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on power ports 1 kV line line DM and 2 kV line earth CM on signal ports Conducted RF immunity Certifications Certification when product is marked 1 c UL us IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Value UL Listed Industrial Control Equipment certified for US and Canada See UL File E322657 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E334470 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 C Tick 1 See the Product Certificati Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions on link at http Awww rockwellautomation com products certification for Declaration of Conformity Certificates and other certification det
30. 820 Micro830 and Micro850 Catalogs Controller Catalogs Inputs Outputs Analog Out Analog In PTO PWM Embedded Family 120v 120 zwDC 12v Relay 2avoc zw PC DH Support d Ug AC 240v VAC DC Source DC Support AC Sink Micro810 2080 LC10 120WB 8 4 4 2080 LC10 12AWA 8 4 2080 LC10 120BB 8 4 4 2080 LC10 12DWD 8 4 4 Micro820 2080 LC20 200BB 2 7 4 1 PWM 2080 LC20 200WB 2 7 4 2080 LC20 20AWB 8 4 7 4 2080 LC20 200BBR 2 7 4 1 PWM 2080 LC20 200WBR E 2 22 4 B 2080 LC20 20AWBR 8 H 4 7 4 Micro830 2080 LC30 100WB 6 4 3 2 2080 LC30 100VB 6 S des 4 z 1 PTO PWM 2 2080 LC30 16AWB 10 6 2080 LC30 160WB 10 6 2 2080 LC30 16QVB 10 6 1 PTO PWM 2 2080 LC30 24QWB 14 10 4 2080 LC30 24QVB 14 10 2 PTO PWM 4 2080 LC30 240BB 14 10 2 PTO PWM 4 2080 LC30 48AWB 28 20 2080 LC30 480WB 28 20 6 2080 LC30 480VB 28 20 3 PTO PWM 6 2080 LC30 480BB 28 20 3 PTO PWM 6 Micro850 2080 LC50 24AWB 14 10 2080 LC50 240BB 14 10 2 PTO PWM 4 2080 LC50 24QVB 14 10 2 PTO PWM 4 2080 LC50 240WB 14 10
31. AWG min 2080 TC2 1 5 mm 16 AWG max Stranded 0 14 mm 26 AWG min 1 0 mm 18 AWG max rated 90 C 194 F insulation max 3i Allen Bradley Publication 2080 SG001D EN P December 2013 Trimpot Analog Input 2080 TRIMPOT6 Specifications 2080 TRIMPOT6 Numberof Mounting Operating Non operating Surrounding North inputs torque temperature temperature air max American temp code 6 channel 0 2 Nm 20 65 C 40 85 C 65 C 149 F T4 Trimpot 1 48 Ib in 4 149 F 40 185 F 2080 MEMBAK RT Backup Status SOCO RXO TXD 485 A S GNO RTS CTS Micro800 Programmable Controller Family Selection Guide 57 Memory Backup and High Accuracy RTC Plug In 2080 MEMBAK RTC Specifications 2080 MEMBAK RTC Mounting torque 0 2 Nm 1 48 Ib in Ib in using a 2 5 mm 0 10 in flat blade screwdriver Terminal Operating Non operating screw torque temperature temperature 0 22 0 25 Nm 20 65 C 40 85 C 1 85 2 21 4 149 F 40 185 F RS232 485 Serial Port Plug in 2080 SERIALISOL Specifications 2080 SERIALISOL Mounting torque 0 2 Nm 1 48 Ib in Operating temperature 20 65 C 4 149 F Terminal screw torque 0 22 0 25 Nm 1 95 2 21 Ib in using a 2 5 mm 0 10 in flat blade screwdriver 40 85 C Wire size Solid Surrounding air max 65 C 149 F 0
32. CISPR 11 Industrial Emissions 1 See the Product Certification link at http www rockwellautomation com products certification for Declaration of Conformity Certificates and other certification details For relay life chart see the Specifications section of the Micro830 and Micro850 User Manual publication 2080 UM002 Embedded Serial Port Cables Embedded Serial Port Cable Selection Chart Connectors Length Cat No Connectors Length Cat No 8 pin Mini DIN to 8 pin Mini DIN 0 5 m 1 5 ft 1781 CBL AMOQ 8 pin Mini DIN to 9 pin D Shell 0 5 m 1 5 ft 1761 CBL APoo 8 pin Mini DIN to 8 pin Mini DIN 2m 655ft 1761 cBL HMo2 8 pin Mini DIN to 9 pin D Shell 2m 6 5ft 1761 CBL PMoz2 8 pin Mini DIN to 6 pin RS 485 30 cm 1763 NCO01 series A terminal block 11 8 in 1 Series C or later for Class 1 Div 2 applications Publication 2080 SG001D EN P December 2013 Select a Micro850 Controller vceseocess D 5 9 e LJ J LJ LJ D o E DIXXXIELXE A Micro850 controller with a power supply plug in modules and four expansion 1 0 modules attached Micro850 controllers are suitable for applications that require more digital and analog I O or higher performance analog I O These controllers can support up to four expansion I O It comes in a 24 point and 48 point form factor with an embedded Ethernet port Micro850 controllers include e Expansion
33. Components Workbench Standard Edition for FREE at http ab rockwellautomation com Programmable Controllers Connected Components Workbench Software Packaging options Available on DVD orderable from Connected Components Workbench web page at http ab rockwellautomation com Programmable Controllers Connected Components Workbench Software Features e D FBD and ST editors user defined function blocks No activation needed Optional registration during installation for product updates and notices Publication 2080 SG001D EN P December 2013 Micro800 Programmable Controller Family Selection Guide Publication 2080 SG001D EN P December 2013 Developer Edition The Developer Edition offers the following additional programming features User defined Structures e You can combine different data types to create structures and then assign them to user defined variables e Structures are useful when you want a single variable to hold several related pieces of information For example you might want to define a structure to keep temperature ranges and alarm levels for a device rather than creating multiple variables Spy Lists You can define spy lists to monitor changes in variables and function block instances in Connected Components Workbench programs The Developer Edition installs the following additional software e Factorylalk Activation Manager v3 60 00 CPR 9 SR 6 e FactoryTalk Diagnostics v2 6
34. D EN P December 2013 Micro800 Programmable Controller Family Selection Guide Output Specifications 2085 0A8 Attribute 2085 0A8 Output signal delay Off to On 9 3 ms for 60 Hz 11 ms for 50 Hz On to Off 9 3 ms for 60 Hz 11 ms for 50 Hz Surge current max 5A 2085 OW8 and 2085 0W16 Relay Output Module Attribute 2085 0W8 2085 0W16 Number of outputs 8 relay 16 relay Dimensions HXWxD 28 x 90 x 87 mm 44 5 x 90 x 87 mm 1 10 x 3 54 x 3 42 in 1 75 x 3 54 x 3 42 in Shipping weight 140 g 4 93 oz 220 g 7 76 02 approx Wire size 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated 75 C 167 F or greater 1 2 mm 3 64 in insulation max Insulation strip length 10 mm 0 39 in Wiring category 2 on signal ports Wire type Copper Terminal screw 0 5 0 6 Nm orque max 44 5 3 Ib in 7 Bus current draw max 5V DC 120 mA 5V DC 160 mA 24V DC 50 mA 24V DC 100 mA Load current max 2A Power dissipation 2 72 W 5 14 W otal Relay contact 0 35 power factor Max Amperes Amperes Volt Amperes Volts Make Break Continuous Make Break 120VAC 15A 15A 20A 1800VA 180VA 240V AC 7 5A 0 75 A 24V DC 1 0A 10A 28V A 125VDC 022A Minimum load per 10 mA per point point Off state leakage max 1 5 mA Status indicators 8 yellow indicators 16 yellow indicators Isolation voltage 240V cont
35. I O support e upto six embedded High Speed Counter inputs Hsc e 100 kHz speed HSC available on 24V DC models e upto three embedded Pulse Train Outputs PTO for basic positioning e High speed input interrupts e Modbus RTU protocol serial port e Modbus TCP support e EtherNet IP support e CIP Serial support e Embedded USB programming and serial port RS232 485 e Embedded 10 100 Base T Ethernet port RJ45 e Plug in slots to customize according to needs To help you select a Micro850 controller see the following specifications 1 Embedded HSC is supported on all Micro850 catalog numbers except on 2080 LC50 xxAWB 2 PTO is supported on Micro850 catalog numbers ending in BB or VB Publication 2080 SG001D EN P December 2013 30 Micro800 Programmable Controller Family Selection Guide Micro850 Controllers Number and Types of Inputs and Outputs Catalog Number Inputs Outputs PTO HSC PWM Support 120V 24V Relay 24V 24V Support AC DC Sink Source VAC 2080 LC50 24AWB 14 10 2080 LC50 24QBB 14 10 2 4 2080 LC50 24QVB 14 10 2 4 2080 LC50 240WB 14 10 4 2080 LC50 48AWB 28 20 2080 LC50 480BB 28 20 3 6 2080 LC50 480VB 28 20 3 6 2080 LC50 480WB 28 20 6 1 Maximum number of HSC supported Micro850 24 Point Controllers IC CYOOOOO e e e llen Bradi j QD Allen Bradley OLUKONI QD Allen Bradley Allen Bradley Allen Bradley
36. Micro800 Programmable Controller Family Allen Bradley Bulletin 2080 Selection Guide THINK Rockwell SOLVE Allen Bradley Rockwell Software Automation Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls publication SGI 1 1 available from your local Rockwell Automation sales office or online at http rockwellautomation com literature describes some important differences between solid state equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software d
37. Otomasyon Ticaret A S Kar Plaza Ig Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90 216 5698400 www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 2080 SG001D EN P December 2013 Supersedes Publication 2080 SG001C EN P September 2012 Copyright 2013 Rockwell Automation Inc All rights reserved Printed in the U S A
38. Q 120V AC Inrush delay time constant max 22 ms IEC input compatibility Type 3 Attribute 2080 LC50 240WB 2080 LC50 24AWB 2080 LC50 240VB 2080 LC50 240BB Relay Output Hi Speed Output Standard Output Outputs 0 1 Outputs 2 and higher Number of outputs 10 2 8 Output voltage min 5V DC 5V AC 10 8V DC 10V DC Output voltage max 125V DC 265V AC 26 4V DC 26 4V DC Load current min 10 mA Load current Refer to Relay Contacts Ratings on page 33 A Q 30 C continuous max 100 mA high speed operation 1 0A Q 30 C 0 3 A 65 C standard operation A Q 65 C standard operation Surge current per point Refer to Relay Contacts Ratings on page 33 4 0 A for 10 ms every 1 s 30 C every 2 s 65 C Current per common max 5A Turn on time 10 ms 25 us 0 1 ms Turn off time max 1 ms 1 Applies for general purpose operation only does not apply for high speed operation Relay Contacts Ratings Maximum Volts Amperes Amperes Volt Amperes Continuous Make 120V AC 240V AC 75A 0 75 A 24V DC 10A 1 0A 28V A 125V DC 0 22 A Publication 2080 SG001D EN P December 2013 34 Micro800 Programmable Controller Family Selection Guide Publication 2080 SG001D EN P December 2013 For relay life chart see the Specifications section of the Micro830 and Micro850 User Manual publication 2080 UM002 Environmental Specifications Attribute Temperature operat
39. ails Publication 2080 SG001D EN P December 2013 26 Micro800 Programmable Controller Selection Guide Q Alien Bradiey 0123454 M vom o um vim I mnaznamsn N m 2 m m A omo ras NH o 22458759 10 19 42 t 14 tS TT ta ta our General Specifications 48 point controllers Q Allen Bradley Micro830 48 Point Controllers aoOOocOOOOOOOOOOCOOOorSaooOooOoOoO0O00900007 Q Allen Bradley LIOCCICGOOOU JOOOOOCIO MM OOOOOOOOOLDUUOCOQOUOUOUCM Q Allen Bradley 9 Allen Bradley Attribute 2080 LC30 48AWB 2080 LC30 480WB 2080 LC30 480VB 2080 LC30 480BB Input circuit type 120V AC 24V DC sink source standard and high speed Output circuit type Relay 24V DC sink standard and 24V DC source standard and high speed high speed Event input interrupt support Yes inputs 0 15 only 1 0 rating Input 120V AC 16 mA Output 2 A 240V AC general use Input 24V DC 8 8 mA Output 2 A 240V AC general use Input 24V DC 8 8 mA Output 24V DC 1 A per point Surrounding air temperature 30 C 24 V DC 0 3 A per point Surrounding air temperature 65 C Pilot duty rating C300 R150 Isolation voltage 250V continuous Reinforced Insulation Type Outputs to Aux and Network Inputs to Outputs Type tested for 60 s 3250V DC 1 0 to Aux and Network Inputs to Outputs 250V continuous Reinforced Insulation Type
40. alogging and recipe e Embedded 10 100 Base t Ethernet port RJ 45 e Support for Remote LCD module 2080 REMLCD for configuration e Embedded non isolated RS232 RS485 combo serial port e Modbus RTU protocol serial port e Modbus TCP support e EtherNet IP support e CIP Serial support To help you select a Micro820 controller consult the specifications for each catalog in the next section Publication 2080 SG001D EN P December 2013 14 Micro800 Programmable Controller Family Selection Guide Number and Types of Inputs Outputs for Micro820 Controllers Controller Catalogs Inputs Outputs Analog Out Analog In PWM Family 120V AC 120 240V 24V DC Relay 24v DC 2av Dc 10V DC 0 10V shared Support AC Source Sink with DC In Micro820 2080 LC20 200BB 12 7 4 1 2080 LC20 200WB 12 7 4 2080 LC20 20AWB 8 4 7 4 2080 LC20 200BBR 12 7 4 1 2080 LC20 200WBR 12 7 4 2080 LC20 20AWBR 8 4 7 4 Specifications General Specifications Attribute Number of 1 0 2080 LC20 20AWB R 12 inputs 8 outputs 2080 L 20 200BB R 2080 LC20 200WB R Dimension HXWxD 90 x 104 x 75 mm 3 54 x 4 09 x 2 95 in Shipping weight approx 0 38 kg 0 83 Ib Wire size Solid For fixed terminal blocks 2 5 mm 14 AWG rated 90 C 194 F insulation 0 14 mm 26 AWG Stranded Solid Solid and Stran
41. and Micro850 Programmable A more detailed description of how to install and use Controllers User Manual publication your Micro830 and Micro850 programmable 2080 UM002 controller Micro800 Plug in Modules User Manual Description of features installation wiring and publication 2080 UM004 specifications for the Micro800 plug in modules Micro800 Discrete and Analog Expansion O Description of features installation wiring and Modules User Manual publication specifications for the Micro800 expansion 1 0 2080 UM003 modules and accessories Industrial Automation Wiring and Grounding Provides general guidelines for installing a Rockwell Guidelines publication Automation industrial system 1770 4 1 Product Certifications website Provides declarations of conformity certificates and http www rockwellautomation com produ other certification details cts certification Publication 2080 SG001D EN P December 2013 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http www rockwellautomation com support you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect sup
42. d 2080 RTD2 Non isolated RTD No Yes Yes 2080 RTD2 Memory Module with RTC No No Yes backup project data and application code 2080 MEMBAK RTC high accuracy real time clock 6 Channel Trim Potentiometer No Yes Yes adds six analog presets for speed position and Analog Input temperature control 2080 TRIMPOT6 Publication 2080 SG001D EN P December 2013 Micro800 Programmable Controller Family Selection Guide 53 Micro800 Plug In Modules Digital Input Output Relay and Combination Plug Ins Specifications 2080 104 2080 1040B4 2080 1040V4 2080 0B4 2080 0V4 E Catalog Input Output On state voltage On state current as 7080 104 4 inputs DC DC 9 0V DC min 2 0 mA Q 9V DC min GD ten Brady 30V DC max 3 0 mA Q 24V DC nom 20804040V4 AC 5 0 mA max Pp ti 10 25V AC rms min AC s o a cu eoa on 30V AC rms max 2 0 mA 9V AC rms min e e ener on on 5 0 mA max 2080 I040B4 4 channel DC Input DC Input inputs source 9 0V DC min 2 0 mA SV DC min outputs combination 30V DC max 3 0 mA Q 24V DC nom AC Input 5 0 mA max 2080 1040V4 4 d ipit 10 25V AC rms min AC Input sane A outputs 30V AC rms max 2 0 mA 9V AC rms min combination Output 5 0 mA max 10V DC min Output 24V DC nom 5 0 mA 10V DC min 30V DC max 0 5 A max steady state 2 A surge 2 s min 2080 0B4 4 source outputs 10V DC min 5 0 mA 10V DC min 24V DC nom 0 5 A max steady state 2080 0V4 4
43. dable controllers are designed for applications that require more digital and analog I O or higher performance analog I O They can support up to four expansion I O Micro850 controllers include additional communication connection options through an embedded 10 100 Base T Ethernet port Several Micro830 and Micro850 controllers support basic positioning through embedded pulse train outputs PTO These controllers also allow you to configure up to six high speed counters HSC and choose from nine HSC operation modes HSC is supported on all Micro830 and Micro850 catalogs except on 2080 LCxx xxAWB PTO is only supported on Micro830 and Micro850 catalog numbers that end in BB or VB This selection guide serves to help you identify the right controller plug ins expansion I O and accessories based on your requirements 2 Select a Micro810 3 controller go to page 9 Select a Micro800 controller go to page 3 controller go to page 19 Select a Micro820 Select Micro800 controller go to page plug ins and Select Micro850 accessories expansion I O Select a Micro830 aot oae ath go to page 41 Select a Micro850 controller go to page 29 Publication 2080 SG001D EN P December 2013 Micro800 Programmable Controller Family Selection Guide 3 Micro800 Controllers Comparison Features Attribute Micro810 Micro820 Micro830 Micro850 12 point 20 poin
44. ded 0 14 mm 26 AWG For removable terminal blocks 0 2 mm 24 AWG 2 5 mm 14 AWG For RS232 RS485 serial port 0 14 mm 26 AWG 1 5 mm 16 AWG 1 5 mm 16 AWG max rated 90 C 194 F insulation max rated 90 C 2 2 194 F insulation max Stranded 0 14 mm 26 AWG 1 0 mm4 18 AWG Wiring category 2 on signal ports 2 on power ports 2 on communication ports Wire type Use copper conductors or shielded cables Publication 2080 SG001D EN P December 2013 General Specifications Attribute Micro800 Programmable Controller Family Selection Guide 15 2080 LC20 20AWBIR 2080 LC20 200BB R 2080 LC20 200WB R Terminal screw torque For removable and fixed terminal blocks 0 5 0 6 Nm 4 4 5 3 Ib in using a 0 6 x 3 5 mm flat blade screwdriver Note Use a handheld screwdriver to hold down the screws at the side For RS232 RS485 serial port 0 22 0 25 Nm 1 95 2 21 Ib in using 0 4 x 2 5 x 80 mm 2 component grip with non slip grip screwdriver Input circuit type 24V DC sink source standard for 2080 LC20 200WB R 2080 LC20 200BB R 120V AC for 2080 LC20 20AWB R for Inputs 4 11 only Output circuit type Relay 24V DC source Relay standard and high speed Power input 24V DC Power consumption 5 62 W without plug ins max 8 5 W with plug ins max Power dissipation 6W Power supply voltage ra
45. eres Amperes Volt Amperes Continuous Make Break Make Break 2080 OW4l 120V AC 15A 15A 20A 1800V A 180V A 240V AC 75A 0 75 A 24V DC 1 0A 1 0A 28V A 125V DC 0 22 A Catalog Operating Non operating Surrounding Relative Shock Shock temperature temperature air max humidity operating non operating 2080 OW4l ER 65 C 40 85 C 65 C 149 F 5 95 2gQ10 500Hz 10g DIN rail 149 F 40 185 F noncondensing mounting 25 g Panel mounting 35g Analog Input and Output Plug ins 338 Allen Bradley Specifications 2080 IF2 2080 IF4 2080 OF2 Catalog Number of Voltage Current Power Input impedance Voltage inputs range range consumption resistive load 2080 OF2 outputs vo slco alvo es 2080 IF2 2 inputs unipolar 0 10V 0 20mA 60 mA Q 2100 k for voltage non isolated 3 3V mode A COM COM cow cow A 250 Q for current 2080 IFA 4 inputs unipolar mode non isolated 2080 0F2 2 outputs unipolar 60 mA Q 24V 1 KQ min non isolated Catalog Current Mounting Terminal screw Wire size Operating Non operating Surrounding North resistive torque torque temp temp air max American load temp code 2080 IF2 0 2 Nm 0 22 0 25 Nm Solid 20 65 C 40 85 C 65 C 149 F T4 1 48 Ib in 1 95 2 21 0 14 mm 26 AWG min 4 149 F 40 185 F 2080 IFA Ip in 1 5 mm 16 AWG max using a 2 5 mm Stranded 2000 962 a S 0 10 in 0 14 mp 26 AWG min flat blade 1 0 mm 18 AWG
46. escribed in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations Identifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss IMPORTANT Identifies information that is critical for successful application and understanding of the product ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you identify a hazard avoid a hazard and recognize the consequence SHOCK HAZARD Labels may be on or inside the equipment such as a drive or motor to alert people that dangerous voltage may be present BURN HAZARD Labels may be on or inside the equipment such as a drive or motor to alert people that surfaces may reach dangerous temperatures alae ta Allen Bradley Rockwell Automation Micro800 Micro810 Micro820 Micro830 Micro850 Connected Components Workbench FactoryTalk PowerFlex CompactBlock and TechConnect are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Select a Micro800 Controller Micr
47. harges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 8096 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10V m with 200 Hz 5096 Pulse 100 AM 1890 MHz 10V m with 1 kHz sine wave 8096 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV 5 kHz on power ports 2 kV 5 kHz on signal ports Surge transient immunity IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on power ports 1 kV line line DM and 2 kV line earth CM on signal ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Publication 2080 SG001D EN P December 2013 28 Micro800 Programmable Controller Selection Guide Certifications Certification when product is marked 1 c UL us Value UL Listed Industrial Control Equipment certified for US and Canada See UL File E322657 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E334470 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 C Tick Australian Radiocommunications Act compliant with AS NZS
48. ing Value IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 65 C 4 149 F Temperature surrounding air max 65 C 149 F Temperature non operating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 non condensing Vibration IEC 60068 2 6 Test Fc Operating 2 g 10 500 Hz Shock operating IEC 60068 2 27 Test Ea Unpackaged Shock 25g Shock non operating IEC 60068 2 27 Test Ea Unpackaged Shock DIN mount 25 g PANEL mount 35 g Emissions CISPR 11 Group 1 Class A ESD immunity IEC 61000 4 2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 10096 AM 900 MHz 10V m with 200 Hz 5096 Pulse 100 AM 1890 MHz 10V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV 5 kHz on power ports 2 kV 5 kHz on signal ports 1 kV 5 kHz on communication ports Surge transient immunity IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on AC power ports 1 kV line line DM
49. inuous Reinforced Insu Type tested 3250V DC for 60 s ation Type channel to system Pilot duty rating C300 R150 Enclosure type rating Meets IP20 North American temp code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 2 RTB hold down screws should be tightened by hand They should not be tightened using a power tool Micro800 Programmable Controller Family Selection Guide 47 Analog Expansion 1 0 2085 IF4 2085 IF8 2085 OF4 Analog Input and Output Modules Attribute 2085 IF4 2085 OF4 2085 IF8 Number of 0 4 8 Dimensions HxWxD 28 x 90 x 87 mm 44 5 x 90 x 87 mm 1 1 x 3 54 x 3 42 in 1 75 x 3 54 x 3 42 in Shipping weight 140 g 4 93 oz 220 g 7 76 oz approx Bus current draw max 5V DC 100 mA 5V DC 160 mA 5V DC 110 mA 24V DC 50 mA 24V DC 120 mA 24V DC 50 mA Wire size 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated 75 C 167 F or greater 1 2 mm 3 64 in insulation max Wiring category 2 on signal ports Wire type Shielded Terminal screw torque 0 5 0 6 Nm 4 4 5 3 Ib in Power dissipation total 1 7 W 37W 1 75 W Enclosure type rating Meets IP20 Status indicators 1 green health indicator 1 green health indicator 1 green health indicator 8 red error indicators Isolat
50. ion voltage 50V continuous Reinforced Insulation Type channel to system and channel to channel Type tested 720V DC for 60 s North American temp T4 code 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 2 RTB hold down screws should be tightened by hand They should not be tightened using a power tool Input Specifications 2085 IF4 and 2085 IF8 Attribute 2085 IF4 2085 IF8 Number of inputs 4 8 Resolution 14 bits 13 bits plus sign bit Voltage 1 28 mV cnt unipolar 1 28 mV cnt bipolar Current 1 28 uA cnt Data format Left justified 16 bit 2s complement Conversion type SAR Update rate lt 2 ms per enabled channel without 50 Hz 60 Hz rejection 8 ms for all channel 8 ms with 50 Hz 60 Hz rejection Step response time up to 6396 4 60 ms without 50Hz 60 Hz rejection depends on number of enabled channel and filter setting 600 ms with 50 Hz 60 Hz rejection 4 20 mA default Input current terminal user configurable 0 20 mA Input voltage terminal user 10V configurable 0 10V Publication 2080 SG001D EN P December 2013 48 X Micro800 Programmable Controller Family Selection Guide Input Specifications 2085 IF4 and 2085 IF8 Attribute 2085 IF4 2085 IF8 Input impedance Voltage terminal gt 1 MQ Current terminal lt 100 Q Absolu
51. ith 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV Q 5 kHz on power ports 2 kV Q 5 kHz on signal ports 1 kV Q 5 kHz on communication ports Surge transient immunity IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on power ports 1 kV line line DM and 2 kV line earth CM on signal ports 1 kV line earth CM on communication ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Micro800 Programmable Controller Family Selection Guide 17 Certifications Certification when Value product is marked c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E322657 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E334470 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions EtherNet IP ODVA conformance tested to EtherNet IP specifications KC Korean Registration of Broadcasting and Communications Equipment co
52. lection Guide Certifications Certification when Value product is marked 1 c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E322657 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E334470 CE European Union 2004 108 EC EMC Directive compliant with EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B EN 61131 2 Programmable Controllers Clause 11 C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions 1 See the Product Certification link at http www rockwellautomation com products certification for Declaration of Conformity Certificates and other certification details For relay life chart see the Specifications section of the Micro8 10 User Manual publication 2080 UMO001 Publication 2080 SG001D EN P December 2013 Select a Micro820 Controller 2080 L020 200BB Ethernet Address E4 90 69 9D 0F 51 As one of the smaller controllers in the Micro800 family the Micro820 controller comes as a 20 point form factor with six catalogs available for selection The Micro820 controller is designed for smaller standalone machines and remote automation projects It has the following features e Two plug in module slots e microSD card slot for project backup and restore dat
53. mpliant with Article 58 2 of Radio Waves Act Clause 3 1 See the Product Certification link at http www rockwellautomation com products certification for Declaration of Conformity Certificates and other certification details For more information see the Micro820 Programmable Controllers User Manual publication 2080 UM005 Publication 2080 SG001D EN P December 2013 18 Micro800 Programmable Controller Family Selection Guide Notes Publication 2080 SG001D EN P December 2013 Select a Micro830 Controller The Micro830 controller allows integration of as many as five plug in modules The plug in modules enable machine builders to personalize the controllers to increase functionality Most models offer removable terminal blocks and simplified communication via serial port The controllers include upto six embedded High Speed Counter inputs Hsc 100 KHz speed HSC available on 24V DC models upto three embedded Pulse Train Outputs PTO for basic positioning High speed input interrupts e Modbus RTU protocol serial port e CIP Serial to allow tighter integration with Panel View Component Embedded USB programming and serial port RS232 RS485 Plug in slots to customize according to needs To help you select a Micro830 controller check out the specifications for each catalog in the next section 1 Embedded HSC is supported on all Micro830 catalog numbers except on 2080 LC30 xxAWB
54. nge 20 4 26 4 V DC Class 2 Auxiliary power supply output for 10V thermistor 1 0 rating Input 120V AC 16 mA Input 24V DC 8 8 mA Output 2 A 240 V AC Output 24V DC 1 Aperpoint 2A 24V DC Surrounding air temperature 30 C 24V DC 0 3 A per point Surrounding air temperature 65 C Input 24V DC 8 8 mA Output 2 A 240 V AC 2A 24V DC Isolation voltage 250V continuous Reinforced 50V continuous Reinforced 250V continuous Reinforced nsulation Type Output to Aux and Insulation Type I O to Aux and Insulation Type Output to Aux and Network Inputs to Outputs Network Inputs to Outputs Network Inputs to Outputs 150V continuous Reinforced Type tested for 60 s 720 50V continuous Reinforced nsulation Type Input to Aux and V DC 1 0 to Aux and Network nsulation Type Input to Aux and Network Inputs to Outputs Network Type tested for 60 s 3250 V DC Type tested for 60 s 720 V DC Output to Aux and Network Inputs nputs to Aux and Network 3250 0 Outputs V DC Outputs to Aux and Network Type tested for 60 s 1950 V DC nputs to Outputs nput to Aux and Network Pilot duty rating C300 R150 C300 R150 Insulation stripping length e 7 mm for the removable and fixed terminal blocks e 5mm for the RS232 RS485 serial port Enclosure type rating Meets IP20 North American temp code T4 1 Use this Conductor Category information for planning conductor
55. ngs 24V DC 1 6 A 38 4 W max 1 Any fluctuation in voltage source must be within 85V 264V Do not connect the adapter to a power source that has fluctuations outside of this range 2 When setting up a Micro800 system verify that total power consumption of the controller plug in and expansion 1 0 does not exceed the output power capacity of the power supply used Remote LCD 2080 REMLCD Attribute Dimensions HxWxD Value 97 x 130 x 35 5 mm 3 82 x 5 12 x 1 40 in Display type 192 x 64 pixel monochrome Display size 48 x 106 5 mm 1 89 x 4 19 in Backlight 25000 hrs 25 C LED tricolor backlight RGB Operator input Tactile keys function keys arrow keys ESC and OK keys Programming port USB to serial converter for programming the controller Input supply voltage 12V 24V DC 10 Input supply current max 90 mA 12V and 60 mA Q 24V Power consumption max 1 5W Weight approx 405 g 0 89 Ib includes packaging weight Wire size Single wire gauge 0 14 1 5 mm 26 16 AWG rated 90 C 194 F Dual wire gauge 0 14 0 75 mm 26 18 AWG rated 90 C 194 F Wire type Copper Wiring category 3 on power ports 3 on communication port Enclosure type ratings Meets IP65 when front panel mounted North American temp code T4 1 Use this conductor category information Publication 2080 SG001D EN P Decembe
56. non condensing Vibration IEC 60068 2 6 Test Fc Operating 2 g Q 10 500 Hz Shock operating IEC 60068 2 27 Test Ea Unpackaged Shock 30g Shock nonoperating IEC 60068 2 27 Test Ea Unpackaged Shock 30 g DIN Rail Mounted 30 g Panel Mounted Emissions CISPR 11 Group 1 Class A ESD immunity IEC 61000 4 2 4 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 8096 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV 5 kHz on power ports 2 kV 5 kHz on signal ports Surge transient immunity IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on power ports 1 kV line line DM and 2 kV line earth CM on signal ports 2 kV line earth CM on shielded ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 8096 AM from 150 kHz 80 MHz Voltage variation IEC 61000 4 11 6096 dip for 5 and 50 periods on AC supply ports 30 dip for 0 5 period at 0 and 180 on AC supply ports 10096 dip for 0 5 period at 0 and 180 on AC supply ports 10 fluctuations for 15 min on AC supply ports 9596 interruptions for 250 periods on AC supply ports Publication 2080 SG001D EN P December 2013 12 Micro800 Programmable Controller Family Se
57. o800 controllers are designed for low cost standalone machines These economical small size PLCs are available in different form factors based on the number of I O points embedded in the base with a range of features intended to address different requirements The Micro800 family shares programming environment accessories and plug ins that allow machine builders to personalize the controller for specific capabilities Micro810 controllers function as a smart relay with high current relay outputs but with the programming capabilities of a micro PLC The Micro810 controllers come in a 12 point form factor Micro820 controllers are specifically designed for smaller standalone machines and remote automation projects It has embedded Ethernet and serial ports and a microSD slot for datalogging and recipe management These controllers come as 20 point form factors that can accommodate up to two plug in modules It also supports the Micro800 Remote LCD 2080 REMLCD module to allow easier configuration of such settings as IP address and functions as a simple IP65 text display Publication 2080 SG001D EN P December 2013 2 Micro800 Programmable Controller Family Selection Guide Choose a Micro800 Controller Micro830 controllers are designed for standalone machine control applications They have flexible communications and I O capabilities with up to five plug ins They come as a 10 16 24 or 48 point form factors Micro850 expan
58. onductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 2 RTB hold down screws should be tightened by hand They should not be tightened using a power tool 2085 1A8 2085 IM8 2085 0A8 AC Input Output Modules Attribute 2085 IA8 2085 0A8 Number of inputs 8 Dimensions HxWxD 28 x 90 x 87 mm 1 10 x 3 54 x 3 42 in Shipping weight approx 140 g 4 93 oz Bus current draw max 5V DC 150 mA 5V DC 180 mA Wire size 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated 75 C 167 F or greater 1 2 mm 3 64 in insulation max Insulation stripping length 10 mm 0 39 in Wiring category 2 on signal ports Wire type Copper Terminal screw torque max 0 5 0 6 Nm 4 4 5 3 Ib in Input output circuit type 120V AC input 240V AC input 120V 240V AC output Power supply 120V AC 240V AC 120V 240V AC Power dissipation total 2 36 W 2 34W 5 19W Enclosure type rating Meets IP20 Micro800 Programmable Controller Family Selection Guide 2085 1A8 2085 IM8 2085 0A8 AC Input Output Modules Attribute Status indicators 2085 IA8 2085 IM8 2085 0A8 8 yellow indicators 45 Isolation voltage 150V continuous Reinforced Insulation Type channel to system Type tested 1950V DC for 60 s channel to system Type tested 3250V DC for 60 s 240V continuous Reinforced Insulation Type N
59. orth American temp code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines p blication 1770 4 1 2 RTB hold down screws should be tightened by hand They should not be tightened using a power tool Input Specifications 2005 IA8 and 2085 IM8 Attribute 2085 IA8 2085 IM8 Number of Inputs 8 Voltage category 120V AC 240V AC Operating voltage range 74 120V AC 159 240V AC Off state voltage max 20V AC 40V AC Off state current max 25mA On state current min 5 0 mA Q 74V AC 4 0 mA Q 159V AC On state current max 12 5 mA Q 120V AC 7 0 mA Q 240V AC Input impedance max 22 2 KQ Inrush current max 450 mA Input filter time 20 ms Off to On On to Off IEC type compliance Type 3 Output Specifications 2085 0A8 Attribute 2085 0A8 Number of Inputs 8 Voltage category 120V 230V AC Operating voltage range 120 240V AC Output voltage min 85V AC Output voltage max 240V AC Off state current max 25mA On state current min 10 mA per output On state current max 0 5 A per output On state current per module max 4A Off state voltage drop max 1 5V AC 0 5 A 2 5V AC 10 mA Fusing Not protected A suitable rating fuse is recommended to protect outputs Publication 2080 SG001D EN P December 2013 46 Publication 2080 SG001
60. ponents Workbench 1 See Number and Types of Inputs Outputs for Micro810 Micro820 Micro830 and Micro850 Catalogs on page 6 2 For Micro820 and Micro830 controllers the number of maximum digital 1 0 assumes 8 point digital 1 0 plug ins for example 2080 I040B4 are used on all available plug in slots For Micro850 controllers the maximum number of digital 1 0 supported between the base plug ins and expansion 1 0 is 132 3 Including reading and writing 1 0 program execution and communications overhead Publication 2080 SG001D EN P December 2013 4 Micro800 Programmable Controller Family Selection Guide Micro800 Controller Programming Comparison with Connected Components Workbench Attribute Micro810 Micro820 Micro830 Micro830 Micro830 Micro850 Micro850 12 point 20 point 10 16 point 24 point 48 point 24 point 48 point Program steps 2K 10K 4K 10K 10K 10K 10K Data bytes 2 KB 20 KB 8 KB 20 KB 20 KB 20 KB 20 KB IEC 61131 3 languages Ladder diagram function block diagram structured text User defined function blocks Yes Floating point 32 bit and 64 bit PID Loop Control Yes number limited only by memory Embedded serial port protocols None Modbus RTU Master Slave ASCII Binary CIP Serial 1 Estimated Program and Data size are typical program steps and variables are created dynamically 1 Program Step 12 data bytes The number of bytes per
61. port programs For more information contact your local distributor or Rockwell Automation representative or visit http www rockwellautomation com support Installation Assistance If you experience a problem within the first 24 hours of installation review the information that is contained in this manual You can contact Customer Support for initial help in getting your product up and running United States or Canada 1 440 646 3434 Outside United States or Use the Worldwide Locator at http www rockwellautomation com support americas phone en html or contact Canada your local Rockwell Automation representative New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures United States Contact your distributor You must provide a Customer Support case number call the phone number above to obtain one to your distributor to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Rockwell
62. r 2013 60 Micro800 Programmable Controller Family Selection Guide For More Information Visit the Micro800 website at http ab rockwellautomation com Programmable Controllers Micro800 to learn more about Micro800 products and download Connected Component Workbench software and Micro800 firmware updates If you would like a manual you can download a free electronic version from the Internet http rockwellautomation com literature purchase a printed manual by contacting your local Allen Bradley distributor or Rockwell Automation representative You can also visit the following websites for additional technical information Sample Code Library http samplecode rockwellautomation com idc groups public docume nts webassets sc home page hcst Technical Forums http www rockwellautomation com forums Connected Component Accelerator Toolkit http www rockwellautomation com components connected ccat html Additional Resources These documents contain additional information concerning related Rockwell Automation products Resource Description Micro810 Programmable Controllers User A more detailed description of how to install and use Manual publication 2080 UM001 your Micro810 programmable controller Micro820 Programmable Controllers User A more detailed description of how to install and use Manual publication 2080 UM005 your Micro820 programmable controllers Micro830
63. ribute T4 ng and Grounding Guidelines 2080 LC50 48AWB 2080 LC50 480WB 2080 LC50 480VB 2080 LC50 480BB Number of Inputs 120V AC Input High Speed DC Input Standard DC Input Inputs 0 11 Inputs 12 and higher 28 12 16 Input group to backplane isolation Verified by the following dielectric tests 1950V AC for 2 s 150V working voltage IEC Class 2 reinforced insulation Verified by the following dielectric tests 720V DC for 2 s 50V DC working voltage IEC Class 2 reinforced insulation Voltage category 110V AC 24V DC sink source Operating voltage range 132V 60Hz AC max 16 8 26 4V DC 65 C 149 F 16 8 30 0V DC 30 C 86 F 10 26 4V DC 65 C 149 F 10 30 0V DC 30 C 86 F Publication 2080 SG001D EN P December 2013 Input Specifications Micro800 Programmable Controller Family Selection Guide 37 Attribute 2080 LC50 48AWB 2080 LC50 480WB 2080 LC50 480VB 2080 LC50 480BB 120V AC Input High Speed DC Input Standard DC Input Inputs 0 11 Inputs 12 and higher Off state voltage max 20V AC 5V DC Off state current max 1 5mA 1 5mA On state current min 5 mA Q 79V AC 5 0 mA 16 8V DC 1 8 mA Q 10V DC On state current nom 12 mA Q 120V AC 7 6 mA Q 24V DC 6 15 mA Q 24V DC On state current max 16 mA Q 132V AC 12 0 mA Q 30V DC Nominal impedance 12 kQ 50 Hz 3kQ 3 74 kQ 10 kQ 60 Hz IEC input compatibility Type 3 Inr
64. rounding Guidelines publica 2 RTB hold down screws should be ti ion 1770 4 1 ghtened by hand They should not be tightened using a power tool Environment Specifications Environment Specifications for All Micro850 Expansion 1 0 Modules Attribute Temperature operating Value IEC60068 2 1 Test Ad Operating Cold IEC60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 65 C 4 149 F Temperature nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Temperature surrounding air max 65 C 149 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 2 g 10 500 Hz Publication 2080 SG001D EN P December 2013 50 Micro800 Programmable Controller Family Selection Guide Environment Specifications for All Micro850 Expansion 1 0 Modules Attribute Value Shock operating IEC 60068 2 27 Test Ea Unpackaged Shock 25g Shock nonoperating IEC 60068 2 27 Test Ea Unpackaged Shock 25 g for DIN Rail Mounting 35 g for Panel Mounting Emissions CISPR 11 Group 1 Class A ESD Immunity IEC 61000 4 2 6 kV contact discharges 8 kV air discharges Radiated RF Immunity IEC
65. routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Publication 2080 SG001D EN P December 2013 16 X Micro800 Programmable Controller Family Selection Guide Publication 2080 SG001D EN P December 2013 Environmental Specifications Attribute Temperature operating Value IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 65 C 4 149 F Temperature 65 C 149 F surrounding air max Temperature EC 60068 2 1 Test Ab Unpackaged Nonoperating Cold nonoperating EC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat EC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity EC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 non condensing Vibration EC 60068 2 6 Test Fc Operating 2 g Q 10 500 Hz Shock operating EC 60068 2 27 Test Ea Unpackaged Shock 25g Shock non operating EC 60068 2 27 Test Ea Unpackaged Shock DIN mount 25 g PANEL mount 45 g Emissions CISPR 11 Group 1 Class A ESD immunity IEC 61000 4 2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 10V m w
66. s 18 24 32 45301 2085 0V16 Sink and 2085 0B16 Source DC Output Module Attribute 2085 0V16 2085 0B16 Number of outputs 16 sinking 16 sourcing Operating voltage range 10 30V DC On state voltage min 10V DC On state voltage nom 24V DC On state voltage max 30V DC On state current max 0 5 A Q 30V DC per output 8A per module 44 5 x 90 x 87 mm 1 75 x 3 54 x 3 42 in Dimensions HxWxD Publication 2080 SG001D EN P December 2013 44 Micro800 Programmable Controller Family Selection Guide Publication 2080 SG001D EN P December 2013 2085 0V16 Sink and 2085 0B16 Source DC Output Module Attribute 2085 0V16 2085 0B16 Shipping weight approx 220 g 7 76 oz Bus current draw max 200 mA Q 5V DC Wire size 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated 75 C 167 F or greater 1 2 mm 3 64 in insulation max Wiring category 2 on signal ports Terminal screw torque max 0 5 0 6 Nm 4 4 5 3 Ib in Output circuit type 24V DC sink 24V DC source Power dissipation total 5W Power supply 24V DC Class 2 Status indicators 16 Yellow channel indicators Isolation voltage 50V continuous Reinforced Insulation Type channel to system Type tested 720V AC for 60 s Enclosure type rating Meets IP20 North American temp code T4 1 Use this Conductor Category information for planning c
67. s only Maximum cable length is dependent on the application and other and so on Publication 2080 SG001D EN P December 2013 actors such as cable type installation required accuracy sensor Micro800 Programmable Controller Family Selection Guide 5 Micro800 Power Requirements Controller Module Power Requirement Micro810 12 point 3 W 5V A for AC module with or without LCD Micro820 20 point 5 62 W without plug ins max Micro830 and Micro850 without plug in expansion 1 0 10 16 poin 5W 24 point 8W 48 point 11W Plug in modules each 1 44 W Expansion 1 0 2085 l016 0 85 W system bus power consumption 2085 0327 0 95W 2085 1A8 075W 2085 IM8 075W 2085 0A8 0 90W 2085 0B16 1 00W 2085 0Vi6 1 00W 2085 OW8 1 80W 2085 OW16 3 20W 2085 IF4 170W 2085 IF8 175W 2085 OF4 370W 2085 IRT4 200W 1 When setting up a Micro800 system verify that total power consumption of the controller plug in and expansion 1 0 does not exceed the output power capacity of the power supply used See External Power Supply 2080 PS120 240VAC on page 59 for power supply specifications 2 Micro820 controllers require a maximum of 8 5 W with plug ins Publication 2080 SG001D EN P December 2013 6 Micro800 Programmable Controller Family Selection Guide Number and Types of Inputs Outputs Number and Types of Inputs Outputs for Micro810 Micro
68. screte 16 point AC DC Relay Output Publication 2080 SG001D EN P December 2013 42 Micro800 Programmable Controller Family Selection Guide Publication 2080 SG001D EN P December 2013 Micro850 Expansion 1 0 Modules Catalog Number Type Description 2085 IF4 Analog 4 channel 14 bit isolated voltage current input 2085 IF8 Analog 8 channel 14 bit isolated voltage current input 2085 OF4 Analog 4 channel 12 bit isolated voltage current output 2085 IRT4 Specialty 4 channel 16 bit RTD and TC isolated input module 2085 ECR Terminator 2085 bus terminator 1 The 2085 ECR bus terminator should always be the last module on the system if any expansion 1 0 module is _ attached to the system 2 Refers to isolation from field side wiring to controller not channel to channel isolation Discrete Expansion I 0 2085 1016 and 2085 1032T DC Sink Source Input Modules Attribute Number of inputs 2085 1016 2085 1032T 16 sink source 32 sink source Dimensions HxWxD 44 5 x 90 x 87 mm 1 75 x 3 54 x 3 42 in Shipping weight 220 g 7 76 oz approx Bus current draw max 170 mA 5V DC 190 mA Q 5V DC Wire size 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated 75 C 167 F or greater 1 2 mm 3 64 in insulation max Wiring category 2 on signal ports Terminal screw torque 0 5 0 6 Nm max 44 5 3 Ib in 9 Input circuit type
69. t 10 point 16 point 24 point 48 point 24 point 48 point Communication ports USB 2 0 with USB 10 100 Base T USB 2 0 non isolated USB 2 0 non isolated emenden adapter Ethernet port RJ 45 RS232 RS485 non isolated combo serial RS232 RS485 RS232 RS485 non isolated combo serial RO eee 10 100 Base T Ethernet port RJ 45 Embedded digital 1 0 12 19 10 16 24 48 24 48 points Base analog I O channels Four 24V DC digital One 0 10V analog Via plug in modules Via plug in modules inputs are shared as output and expansion 0 0 10V analog T inputs DC input ad ae digital models only IMPUS can De configured as 0 10V analog inputs DC input models only and via plug in modules Number of plug in modules 0 2 2 2 3 5 3 5 Maximum digital 1 02 12 35 26 32 48 88 132 Types of accessories or e LCD display with Micro800 All plug in modules see page 51 plug ins supported backup memory Remote LCD module 2080 REMLCD e USB adapter e All plug in modules except 2080 MEMBAK RTC see page 51 Expansion 1 0 supported All expansion 1 0 modules see page 41 Power supply Embedded 120 240V Base unit has embedded 24V DC power supply optional external 120 240V AC power AC and 12 24V DC options supply available Basic instruction speed 2 5 us per basic instruction 0 30 us per basic instruction Minimum scan cycle time lt 0 25 ms lt 4ms lt 0 25 ms Software Connected Com
70. t circuit type Relay 24V DC sink transistor standard and high speed Event input interrupt support Yes 1 0 rating Input 24V DC 8 8 mA Input 24V DC 8 8 mA Output 2 A 240V AC general use Output 2 A 24V DC 1 A per point Surrounding air temperature 30 C 24V DC 0 3 A per point Surrounding air temperature 65 C Isolation voltage 250V continuous Reinforced Insulation Type Outputs to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC Inputs to Aux and Network 3250V DC Outputs to Aux and Network Inputs to Outputs 50V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC 1 0 to Aux and Network Inputs to Outputs Pilot duty rating General Specifications C300 R150 16 point controllers Attribute 2080 LC30 16AWB 2080 LC30 160WB 2080 LC30 160VB Input circuit type 120V AC 12 24V sink source standard 24V sink source high speed Output circuit type Relay 12 24V DC sink transistor standard and high speed Event input interrupt Yes support Publication 2080 SG001D EN P December 2013 22 Micro800 Programmable Controller Selection Guide General Specifications 16 point controllers Attribute 2080 LC30 16AWB 2080 LC30 160WB 2080 LC30 160VB 0 rating Input 120V AC 16 mA Input 24V DC 8 8 mA Input 24V DC 8 8 mA Output 2 A 240V AC general use Output 2 A 240V AC general use ce
71. te accuracy 0 10 Full Scale 25 C Accuracy drift with temp Voltage terminal 0 00428 96 Full Scale C Current terminal 0 00407 96 Full Scale C Calibration required Factory calibrated No customer calibration supported Overload max 30V continuous or 32 mA continuous one channel at a time Channel diagnostics Over and under range or open circuit condition by bit reporting Output Specifications 2085 OF4 Attribute 2085 OF4 Number of outputs 4 Resolution 12 bits unipolar 11 bits plus sign bipolar Voltage 2 56 mV cnt unipolar 5 13 mV cnt bipolar Current 5 13 pA cnt Data format Left justified 16 bit 2s complement Step response time up to 6396 2 ms Conversion rate max 2 ms per channel Output current terminal user 0 mA output until module is configured configurable 4 20 mA default 0 20 mA Output voltage terminal user 10V configurable 0 10V Current load on voltage output max 3 mA Absolute accuracy Voltage terminal 0 133 96 Full Scale Q 25 C or better Current terminal 0 425 96 Full Scale Q 25 C or better Accuracy drift with temp Voltage terminal 0 0045 96 Full Scale C Current terminal 0 0069 96 Full Scale C Resistive load on mA output 15 500 ohm Q 24V DC Specialty Expansion 1 0 2085 IRT4 Temperature Input Module Attribute 2085 IRT4 Number of inputs 4 Dimensions HxWxD 44 5 x 90 x 87 mm 1 75 x 3 54 x 3 42 in Shipping weight appro
72. ue IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 65 C 4 149 F Temperature surrounding air max 65 C 149 F Temperature non operating EC 60068 2 1 Test Ab Unpackaged Nonoperating Cold EC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat EC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity EC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 non condensing Vibration EC 60068 2 6 Test Fc Operating 2 g 10 500 Hz Shock operating EC 60068 2 27 Test Ea Unpackaged Shock 25g Shock non operating EC 60068 2 27 Test Ea Unpackaged Shock DIN mount 25 g PANEL mount 35 g Emissions CISPR 11 Group 1 Class A ESD immunity IEC 61000 4 2 4 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10V m with 200 Hz 5096 Pulse 100 AM 1890 MHz 10V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV Q 5 kHz on power ports 2 kV 5 kHz on signal ports 1 kV Q 5 kHz on communication ports Surge transient immunity IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on power ports 1 kV line line DM and
73. ush current max 250 mA 120V AC Input frequency max 63 Hz Output Specifications Attribute 2080 LC50 48AWB 2080 LC50 480WB 2080 LC50 480VB 2080 LC50 480BB Relay Output Hi Speed Output Standard Output Outputs 0 through 3 Outputs 4 and higher Number of outputs 20 4 16 Output voltage min 5V DC 5V AC 10 8V DC 10V DC Output voltage max 125V DC 265V AC 26 4V DC 26 4V DC Load current min 10 mA Load current max 20A 100 mA high speed operation o 1 0 A 30 C 0 3 A 65 C standard operation 0A Q 30 0 3 A 65 C standard operation Surge current per point See Relay Contacts Ratings on page 33 4 0 A for 10 ms every 1 s 30 C every 2 s 65 api Current per common max 5A Turn on time 10 ms 2 5 us 0 1 ms Turn off time max 1 ms 1 Applies for general purpose operation only Does not apply for high speed operation Relay Contacts Ratings Maximum Volts Amperes Amperes Volt Amperes Continuous Make 120V AC 15A 1800V A 240V AC 75A 0 75 A 24N DC 1 0A 1 0A 28V A 125V DC 0 22 A For relay life chart see the Specifications section of the Micro830 and Micro850 User Manual publication 2080 UMO002 Publication 2080 SG001D EN P December 2013 38 Micro800 Programmable Controller Family Selection Guide Publication 2080 SG001D EN P December 2013 Environmental Specifications Attribute Temperature operating Val
74. utput 24V DC 1 A per point Surrounding air temperature 30 C 24 V DC 0 3 A per point Surrounding air temperature 65 C Isolation voltage 250V continuous Reinforced Insulation Type Outputs to Aux and Network 50V continuous Reinforced Inputs to Outputs Inputs to Outputs 2080 LC30 16QWB Type tested for 60 s 720V DC Inputs to Aux and Network 3250V DC Outputs to Aux and Network Inputs to Outputs Insulation Type 1 0 to Aux and Network Inputs to Outputs 2080 LC30 16AWB Type tested for 60 s 3250V DC 1 0 to Aux and Network Type tested for 60s 720V DC 1 0 to Aux and Network Inputs to Outputs Pilot duty rating C300 R150 Environmental Specifications Attribute Temperature operating Value IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 65 C 4 149 F Temperature surrounding air max 65 C 149 F Temperature non operating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 non condensing Vibration IEC 60068 2 6 Test Fc Operating 2 g 10 500 Hz Shock operating IEC 60068 2 27 Test Ea Unpackaged Shock
75. x 220 g 7 76 oz Bus current draw max 5V DC 160 mA 24V DC 50 mA Publication 2080 SG001D EN P December 2013 2085 IRT4 Temperature Input Attribute Wire size Micro800 Programmable Controller Family Selection Guide 49 Module 2085 IRT4 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated 75 C 167 F or greater 1 2 mm 3 64 in insulation max Wiring category 2 on signal ports Terminal screw torque 0 5 0 6 Nm 4 4 5 3 Ib in 2 Input type Thermocouple type B C E J K TXK XK L N R S T RTD type 00 Q Pt a 0 00385 Euro 00 Q Pt a 0 00385 Euro 00 Q Pt a 0 003916 U S 00 Q Pt a 0 003916 U S 00 Q Nickel 618 00 Q Nickel 618 20 Q Nickel 672 0 Q Copper 427 mV range 0 100 mV Ohm input 0 500 Q moP amp MN Resolution 16 bits Channel update time typical 12 500 ms per enabled channel Input impedance 10M O Accuracy 0 5 3 0 C accuracy for Thermocouple inputs 0 2 0 6 C accuracy for RTD inputs Power dissipation total 2W Enclosure type rating Meets IP20 Status indicators 1 green health indicator Isolation voltage 50V continuous Reinforced Insulation Type channel to system Type tested 720V DC for 60 s North American temp code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and G