Home

Mx4000 - Tann Synchronome

image

Contents

1. 3 1 5 Numeric data entry Numbers are entered by moving to the required field then typing in the required number followed by the 4 button If the number is entered incorrectly press the Ese button to restore the previous number 3 2 Recommended Programming Procedure Step 1 SET UP Define General Set up Information Phone Numbers etc Step 2 PASSWORDS Define Level 2 and Level 3 Passwords as required Step 3 AUTO LEARN Let the panel learn the devices on the loop s Step 4 VIEW DEVICES Enter Zone Numbers Location text and Change Group Assignments if required Step 5 OUTPUTS Program Output Groups as required Step 6 ZONES Enter Zone Texts as required 3 3 Level 3 Menu Functions The following table gives a list of the Level 3 Menu Functions the sub functions available within each main function and a brief description for each function Main Menu Option Sub Menus Comments 3 LOOPS View Edit View test and configure the loop devices Auto Learn Learn the Devices Present on the Loop Calibrate Calibrates devices on the loop ZONES Configure the Zones EXIT Cancel Level 3 Access and return to Level 2 Menu Options OUTPUTS Configure the Operating Characteristics of the Output Circuits TIME DATE Change the Date and Time Settings VIEW Fires View Zones and Inputs that are reporting a fire
2. Alarm Activation of an input device programmed with an Alarm action Pre Alarm A device in a pre alarm condition Fault Any device entering a fault condition Input Disabled Whenever an input device is disabled Output Disabled Whenever an output device circuit is disabled Coincidence Detection The operation of the Coincidence Detection Double Knock feature is on a per zone basis Document Reference 680 014 Author RFM4100 33 of 53 3 3 6 3 Style The way in which an output turns on in response to a particular input event can be programmed For example an output may turn on immediately it may turn on after a delay or it may pulse for a set time and then turn on This method of operation is called a Style A style may have up to three different methods of operation For example Delay gt Mode Wait Mode Wait Mode Style 00 is fixed to turn on immediately an input event occurs Style 01 defaults to pulse immediately an input event occurs Styles 02 to 20 are programmable 02 to 10 on Mx4100 Press the button to step on to the style field Change the setting using number entry to select the required output style If the style is already programmed elsewhere the relevant style parameters are automatically entered into the appropriate fields 3 3 6 3 1 Delay The delay field is the time from qualification of the input event to so
3. 20 of 53 3 Programming 3 1 Introduction 3 1 1 Access Levels The panel operation is protected from inadvertent and erroneous misuse by means of three access levels These levels are as follows Level 1 Untrained user Level 2 Authorised User Level 3 Commissioning Service and Maintenance This document covers the Level 3 functions For details on the operation and use of the panel at Levels 1 amp 2 refer to User Manual 680 015 A level 3 password is required to enter the commissioning menus For details of Passwords refer to Section 3 3 10 Level 3 Passwords If this number is lost it is not possible to enter commission mode functions e Refer to 6 1 for further formation 3 1 2 Memory Lock The configuration memory is protected against inadvertent change by means of a memory lock OPEN POSITION Before making any configuration data changes move the jumper strap to the OPEN position After all changes have been made move the jumper strap back to the CLOSE position to protect the O memory against inadvertent change CLOSED POSITION Refer to the diagram opposite for information on the Jumper settings Typical View Mx 4100 3 1 3 Navigating through menus The display will revert to status mode after 60s Press the Menu button to restore the display Commission Menu 1 LOOPS ZONES OUTPUTS TIME DATE When a
4. 6 6 1 Unprocessed Analogue information For most purposes the Value field in the View Edit menu gives the easiest to read and the most useful information from a detector as it is scaled and displayed in standard engineering units It is however possible to see the unprocessed analogue signal AN by moving to the Additional Info field Loop 1 Devices lt More gt Address Additional Info 001 0 AN 002 0 AN 003 0 AN 004 0 AN Press the V button to cycle through and display the stored Calibration Zero point ZP and the Calibration Fire point FP 6 6 2 CHQ BS Sounders Unlike standard sounders the CHQ BS sounders can be programmed to give out many different tones and be individually programmed to adjust the sound output When programmed from the panel they will default to turn on at 85dB Use one of the many tones available from the PC instead of the standard Pulse option if any special ringing is required The panel utilises the group features of the CHQ BS so that when a command is sent to turn one device on all other CHQ BS devices within the same group will turn on at virtually the same time from the same command and likewise when they are silenced Document Reference 680 014 Author RFM4100 52 of 53 6 7 Appendix 7 Mx4000 Series Loop Output Drive Capabilty The following information is applicable per loop All loops can be loaded to the maximum
5. 1000 when networked 200 1000 when Networked Number of Loops 1 1 to2 1 to4 Devices per Loop As per Detector Manufacturer s Specifications Loop Current 500mA max 500mA max per Loop 500mA max per Loop Protocols Apollo S90 XP95 Disco very Explorer amp Hochiki ESP Sounder Outputs 2 x 1A Programmable Total output current from panel not to exceed 2Amps 2x 1A Programmable 4 x 1A Programmable Relay Outputs 2 x1A 30VAC DC max 10mA 5V min Programmable 2x 1A 30V AC DC max 10mA 5V min Programmable 2 x 1A 30V AC DC max 10mA 5V min Programmable Open Collector Outputs 2 x Programmable 10mA 30V DC max 2 x Programmable 10mA 30V DC max 2 x Programmable 10mA 30V DC max Digital Outputs 6 x Programmable 6 x Programmable Auxiliary Supply Output 24V DC 300mA See notes 24V DC 300mA See notes 24V DC 300mA See notes Event Log 1000 Event amp Diagnostic 4 500 Fire Notes Aux supply tracks a maximum of 0 5V below battery terminal voltage when no mains supply available Document Reference 680 014 Author RFM4100 Standards The Mx 4100 4200 and Mx 4400 Fire Alarm Control Panels conform to the following standards BS EN54 2 1998 Control and Indicating Equipment BS ENS54 4 1998 Power Supply Equipme
6. 4 EN54 Optional Features In addition to the mandatory requirements of EN54 Part 2 the MX Control and Indicating Equipment C I E support the following optional features Fault Signals from Points The C LE is able to receive and process fault signals from points These are indicated on a per zone basis Refer to the User Manual for further information Outputs to Fire Alarm Devices The C LE has provision for connection to Fire Alarm Devices It is possible to Silence and Resound the alarms at Level 2 Refer to the User Manual for further information Delays to Outputs The C LE has provision for Output and Investigation Delays Refer to Section 3 3 6 for further information Coincidence Detection The C I E has provision for Coincidence Detection Refer to Section 3 3 6 for further information Disablement of Points The C LE has provision for enabling and disabling signals from points Refer to the User Manual for further information Test Condition The C LE has provision for testing the installation on a per zone basis Refer to the User Manual for further information Document Reference 680 014 Author RFM4100 40 of 53 5 Service and Maintenance 5 1 Maintenance Schedule It is recommended that the following maintenance schedule as per EN54 14 be adopted 5 1 1 Daily Actions The site operator user should perform the following checks and actions a T
7. This parameter determines whether the Company Logo is shown on the display during normal operation To change the setting press the Y button The status changes from to X and vice versa 3 3 13 8 Program ID The display shows the part number and version of the software installed in the panel Press the gt button to see the program checksum 8 digits 3 3 13 9 Config Data The Config Data option shows the loop protocol selected and the checksum for the configuration data A note of this number can be taken and then checked on the next service visit to see if any changes have been made to the configuration data In addition there is an option to erase the Config Data To view the Config Data Checksum press the gt button The display then shows Setup CONFIG DATA 1 NONNO To change the protocol press the Y button A pop up window is shown with the following options KEEP PROTOCOL CHANGE LOOP PROTOCOL Use the MW buttons to select the required options and press the Y button to confirm the selection Selecting CHANGE LOOP PROTOCOL will toggle to the alternative loop protocol available ie Apollo Hochiki Changing between protocols will automatically erase all loop devices from the configuration memory Perform an Auto Learn or use the PC Config Tool to re define the devices connected to the loop Document Reference 680 014 Author RFM4100 39 of 53
8. rejected and another new device is subsequently registered the display will once again show the pop up window to accept or reject this device 3 3 3 4 Procedure if the Panel finds Devices Changed When the panel finds a new type of device installed at an address previously learnt and programmed in the panel the Auto Learn process is suspended and the display shows a pop up window with options For example ACCEPT NEW DEVICE KEEP OLD DEVICE ACCEPT ALL NEW DEVICE REJECT ALL NEW DEVICE Address 002 TYPE C Document Reference 680 014 Author RFM4100 30 of 53 This situation could arise for example if a heat detector has been installed in place of an optical smoke detector If the new device type is accepted or all new device types are accepted the panel will configure the memory to register these devices All data will be configured to initial settings for sensitivity threshold changes text assignments zone assignment action etc for these devices If the new device type is rejected or all new device types are rejected the panel remembers the programming for the original devices The panel will report a fault condition until such time as the correct device types are reconnected Press the MY buttons to highlight the required menu option and then press the Y button to confirm The pop up window will disappear and the panel
9. 500mA per loop Provision has been made to allow for a typical loading of detectors and inputs 30mA 6 7 1 Hochiki Volume Number of Loop Powered Sounder Bases 98db 29 or 95db 42 or 94db 47 or 93db 58 or 90db 72 or 88db 104 or 85db 127 6 7 2 Apollo Volume Number of Loop Powered Sounders 100db 104 Loop Powered Sounders or 92db 57 Sounder Bases or 85db 126 Sounder Bases The number of devices shown is representative for specific loop arrangements If there is a mixture of sounder types or sounder volumes on the installation or if the other devices on the loop take more than 30mA in quiescent or alarm then calculate the actual current load in alarm using the current consumption figures quoted in the device data sheets and ensure that this does not exceed the maximum output for the loop Refer to Apollo and Hochiki LoopCalculator for further information on calculating loop loading cable cross sectional area and loop distance Document Reference 680 014 Author RFM4100 53 of 53
10. 0 Disco Drift Refer to Apollo s literature for an explanation of the drift mechanism and for further information on the expected values 6 5 2 Rapid Compensation Apollo has incorporated a rapid compensation facility into the Discovery devices If a device is changed during service it can be quickly adjusted to the present ambient conditions Highlight the required Disco family device select RAPID COMPENSATION and then press the V button to confirm The panel will now instruct this device to perform a rapid compensation This will take approximately 30 seconds j This operation must only be performed with the detector in clean air No other operation should be performed on this device during this rapid compensation period Document Reference 680 014 Author RFM4100 50 of 53 6 5 3 View EEPROM The panel can read any of the extended memory locations within the Discovery devices Highlight any Disco family device select VIEW EEPROM and then press the Y button to confirm The display will prompt for entry of the required extended memory address For example Loop 1 Devices lt More gt Address Additional Info gt 0 01_0_ DI Enter the required address using the number buttons and then press the Y button to confirm The panel will now read the extended memory locations for all Discovery devices on the loop When complete the display will pre
11. 1 25 Loop Driver 0 042 1 0 0 042 1 0 Sensor Loop Current 1 25 1 25 Loop Driver 0 042 1 0 0 042 1 0 Sensor Loop Current 1 25 1 25 Loop Driver 0 042 1 0 0 042 1 0 Sensor Loop Current 1 25 1 25 Sounder Output A 1 0 Sounder Output B 1 0 Sounder Output C 1 0 Sounder Output D 1 0 Total Quiescent Load Alarm Load x 24 hr x 0 5 hr AHr cis A Total Load Quiescent Alarm x 1 2 Battery Derating factor Notes Only used on the Mx 4400 Use the detector manufacturers technical information to calculate the load on the loop for both the quiescent condition and fire alarm condition for all loop devices By default a maximum of 5 detector call point LED indicators will be turned on in a fire alarm condition This number can be changed via the PC Programming Tool The calculated loop loading must be multiplied by a factor of 1 25 to calculate the actual current draw from the batteries This is to take into account voltage conversion and conversion efficiency in generating the supply for the loop The total load calculated must be multiplied by a derating factor of 1 2 to allow for changes in battery efficiency over time Document Reference 680 014 Author RFM4100 47 of 53 6 4 Appendix 4 Cause and Effect Programming Example 6 4 1 Introduction By
12. 1 Fire System Installations The panel must be installed and configured for operation in accordance with these instructions and the applicable fire systems installation regulations appropriate to the country and location of the installation 1 2 2 Wiring Regulations The panel and system must be installed in accordance with these instructions and the applicable wiring codes and regulations appropriate to the country and location of the installation In the UK the installation must comply with the requirements of the IEE Wiring Regulations Sixteenth Edition or later Document Reference 680 014 Author RFM4100 2 Installation 2 1 Identification of Parts The following diagram shows the major parts of the panel 2 1 1 Mx 4100 Chassis Assembly Earth Lead to Cover Rear Enclosure AC Mains Battery Input Leads 2 1 2 Mx 4200 amp Mx 4400 Chassis Assembly Rear Enclosure Document Reference 680 014 Author RFM4100 2 2 Installing the Mx 4100 Enclosure The panel can weigh in excess of 15kg when the batteries are installed Use appropriate fixing hardware to secure the panel to the wall Observe
13. For example Auto Learn Loop 1 HOCHIKI Address 15 Devices found 3 When all addresses have been searched the panel displays a summary screen showing the quantity of devices found for each type of device For example Auto Learn Loop 1 HOCHIKI Address 127 Devices found 4 OPT ION MUL TMP MCP SCC I O ZMU OTHI 0 1 1 1 1 0 0 0 0 This summary provides a quick check to ensure that the panel has found all of the devices that should be connected to the loop Press the Esc button to return to the main Loops Menu Document Reference 680 014 Author RFM4100 29 of 53 3 3 3 2 Procedure if the Panel finds Devices Missing When the panel cannot communicate with a device previously programmed into the panel the Auto Learn process is suspended and the display shows a pop up window with options For example KEEP THIS DEVICE ETE THIS DEVICE EEP LL MISSING ETE L MISSING Address 002 DE E MISSING If the missing device is kept or all missing devices are kept the panel remembers the programming for these devices The panel will report a fault condition until such time as the missing devices are reconnected If the missing device is deleted or all missing devices are deleted the panel clears all previous programming for these devices This includes any sensitivity threshold changes text assignments zo
14. Reference 680 014 Author RFM4100 12 of 53 2 3 6 Installing Additional Loop Circuits in the Mx4200 amp Mx 4400 To extend the number of detector loops or to replace an existing loop driver card follow the procedure described below 711 1021REY O O Sri An example of the loop driver is shown opposite This is provided with a plastic grip handle on the top edge to ease removal of the card from the Base Card Isolate ALL sources of power before T 10 installing or removing printed circuit L ad SE 19 a e 14 E R4 TR7 TRO a ta ces BE 6 DIROT Ons E zi o mooogj a C2 s F a E 2 G w lo L11 1 L4 T56 L3 L2 153 L1 f O boards BESEE BOS He cre au PL t j sur C z A ARI 2 t EEIEIE boobtisnane BESS i Observe anti static precautions at all WIAA a f ARS VARA VARIVA DO oct 2 q times when handling printed circuit boards Loop Driver Component Side View i 3 Q rg uw a e TONT a k gt sd Open the enclosure and then open the display plate it is hinged on the right hand side and there is a magnetic catch strip on the left hand side to gain access to the Base Card A section of the Base Card identifying the locations for each loop driver is shown in the picture opposite Conapeneit side at res To install a loop driver gently guide the loop driver oop Driver Cor gp aa pr
15. above However note that the expected battery life is shortened by increase in ambient temperature The life reduces by 50 for every 10 C rise above ambient Refer to battery manufacturer for further information Manufacturer Part Numbers YUASA POWERSONIC 4AH NP4 12 5AH PS 1250 F1 7AH NP7 12 7AH PS 1270 12AH NP12 12 12AH PS 12100 F1 17AH NP18 12 18AH PS 12180 NB 24AH NP24 12B 26AH PS 12260 NB Batteries connected in parallel 48AH 2 x NP24 12B For optimum performance and charge retention Yuasa recommend that batteries are top charged prior to installation For batteries up to 6 months old from date of manufacture charge at 2 4V per cell i e 14 4V per battery for 20 hours prior to installing the batteries It is not recommended to use batteries that are older than 6 months from the date of manufacture on a new installation The panel is adequately ventilated to dissipate this hydrogen DO NOT seal the enclosure or install j It is quite normal for lead acid batteries to vent hydrogen when being charged in a sealed enclosure or cavity 5 2 1 2 Lithium Battery WARNING A lithium battery is used for data retention and for the real time clock Replace only with the same type or authorised equivalent This battery is not rechargeable Expected Shelf Life gt 10 years Replacement Schedule 10 years for panels in continuous service 10 years for spares i e when the panel board is not powered Replace
16. alarm condition Faults View Zones and Inputs that are reporting a fault condition Alarms View Zones and Inputs that are reporting an alarm condition during test Disabled View Zones Inputs and Outputs that are disabled Inputs View the current state of Zones and Inputs Outputs View the current operational condition of all output circuits Log View the Event Log Panel View the operational state voltage amp current loading of the panel I O Network View Network Diagnostics PASSWORDS Configure the Level 2 and Level 3 passwords PANEL Change the default zone assignments and output groups for all panel I O PC LINK Enable the PC Link for transfer of configuration data to and from the panel SETUP Configure General Operating Parameters Document Reference 680 014 Author RFM4100 23 of 53 3 3 1 Loops For Multi loop panels only On selecting the LOOPS option the display will prompt for the loop to be viewed programmed E g for the Mx4400 Select Loop 2nd Loop 3rd Loop 4th Loop v v x x The list of loops available will be adjusted automatically to show only those loops that have a loop driver card installed In the above example loop drivers are installed in positions 1 and 2 Press the MY buttons to scroll through the list of loops available and then pres
17. default all sounders and output devices will turn on immediately as soon as a fire is detected anywhere in the system For example Cause Effect Any Fire Anywhere gt ALL Output Devices will Turn ON Quite often an installation will require a more complex Cause and Effect solution Consider a multiple story building where phased evacuation is required when a fire occurs on a particular floor For example Cause Effect Any Fire on Floor 7 gt Sounders on Floor 6 will DELAY for 30 seconds then start From Zones 22 23 or 24 PULSING After 2 minutes turn ON Sounders on Floor 7 will Turn ON Sounders on Floor 8 will DELAY for 30 seconds then start PULSING After 2 minutes turn ON gt gt 6 4 2 Output Groups There may be several sounders on each floor These can be grouped together using the Output Groups so that a single group number can easily reference all sounders on a particular floor in the panel For example Sounders Output Group Assign All Sounders of Floor 6 gt Output Group 6 Assign All Sounders of Floor 7 gt Output Group 7 Assign All Sounders of Floor 8 gt Output Group 8 Refer to Section 3 3 2 8 for how to assign the output group to a loop output device Refer to Section 3 3 11 for how to assign the output group to an internal panel circuit 6 4 3 Styles In the example there are two ways in which the sounders should ring These two operational characteristics can be defined as Styles in the panel Fo
18. defines the delay from detecting an alarm to entering the alarm condition The delay time can be changed in 1 second increments 3 3 2 7 4 Alarm Apollo The Alarm Level is the level of the analogue value returned by the detector at which the panel will enter a Fire Alarm Condition The default value is 55 Setting the value higher will mean that more smoke higher temperature is required before the panel will enter the alarm condition Setting the value lower will mean that less smoke temperature is required before the panel will enter the fire alarm condition The alarm level cannot be set outside the safe operating limits defined for the particular device Apollo Discovery devices always use a value of 55 3 3 2 7 5 Alarm Hochiki The Alarm Level of the Analogue value returned by the detector at which the panel will enter a fire condition is set to Hochiki Alarm thresholds expressed as a value This is normally 3 for Multi sensor amp Optical devices Refer to Hochiki Data Sheets for further information 3 3 2 7 6 Pre Alarm The Pre Alarm Level is the level of the analogue value returned by the detector at which the panel will enter a pre alarm condition 3 3 2 7 7 Minimum Value If the detector analogue output falls below the minimum value programmed the panel will enter a fault warning condition This parameter is normally left at a value of 8 for Apollo detectors and 0 for Hochiki 3 3 2 7 8 Special Sensitivity Mode SSM Cl
19. event log press the gt button to view the additional command option as follows Setup RACE LOGGING MODE ESSMAN ECTOR BLINKING R iT OMPANY LCD LOGO O GRAM ID Press the Y button and the display will show that the event log is being erased by display the message WORKING After the event log is erased the display reverts to the Set up Options screen 3 3 13 6 Detector Blinking The Detector Blinking option determines whether the LED indicators on the devices will blink whenever the panel polls the device To change the operation press the Y button The display presents a list of options For example Use the MY buttons to scroll through the list of options and press the Y button to confirm the selection Document Reference 680 014 Author RFM4100 Page 38 of 53 The device LED indicators will not blink if NONE is chosen or will blink if ALL is chosen Note that only certain devices such as Apollo Discovery support this feature If a device such as a Discovery device is changed it may be necessary to select and reconfirm the blinking command so that the new device will blink its LED The INDIVIDUAL option should be chosen when it is required that only certain devices should blink their LED The devices that shall blink their LED can only be programmed using the PC Configuration Tool 3 3 13 7 Company LCD Logo
20. for the 7AH batteries within the panel For battery sizes greater than 7AH the batteries must be installed in a separate enclosure suitable for fire protection use with wiring connected to the panel through rigid conduit Document Reference 680 014 Author RFM4100 15 of 53 2 4 2 2 Mx 4200 amp Mx 4400 The diagrams opposite show the recommended location and orientation for the 12AH and 17AH batteries within the panel For battery sizes greater than 17AH the batteries must be installed in a separate enclosure suitable for fire protection use with wiring connected to the panel through rigid conduit For battery sizes greater than 12AH it will be necessary to remove the spade terminals fixed to the battery leads and replace these with connection fixings suitable for the installed batteries Document Reference 680 014 Author RFM4100 16 of 53 2 4 3 Detector Loop Installation Maximum of 32 Sensors Call Points between Isolators The Detection Loop Circuit should be installed as a continuous loop with isolator modules such that a short circuit condition does not remove more than 32 input devices Form the loop starting at the Loop Out and termin
21. if the battery voltage falls below 2 6 volts Manufacturer Part Number CR2032 Document Reference 680 014 Author RFM4100 42 of 53 5 2 2 Liquid Crystal Display Expected Life gt 10 years Replacement Schedule When the display becomes difficult to read The display contrast will gradually fade with time Manufacturer Part Number Replace the complete display keyboard assembly Spare part number MXS 004 Document Reference 680 014 Author RFM4100 43 of 53 6 Appendices 6 1 Appendix 1 Forgotten Level 3 Password Should the Level 3 password be forgotten contact Customer Support to obtain a temporary permit number to regain access to the panel programming functions Customer Support will require a decryption key displayed by the panel To obtain this number attempt to gain access to the Level 3 Programming Functions entering 1 when prompted for the password As soon as the Password Invalid message is shown press the 0 button and the display will show a decryption key Make a note of the first part of this number For example Level 2 Menu Please Enter Your Password 214728378 Customer Support will provide a temporary permit number that you can enter when prompted for the Level 3 password As soon as access has been regained to the Level 3 Programming Functions select the Passwords Menu Optio
22. inside the enclosure Document Reference 680 014 Author RFM4100 11 of 53 2 3 4 Remounting the Chassis Carefully replace the chassis and locate onto the upper two screws Replace the bottom two screws and tighten all four screws to hold the chassis securely to the backbox j Reconnect the chassis earth cable to the spade terminal in the rear of the enclosure 2 3 5 Recommended Cable Routing Arrangement It is recommended that the routing arrangement shown in the diagram opposite be employed Relays Sounders AUX Ad NeT A x LOOPS i Segregate the low voltage wiring Loop Circuit x ea Sounder Circuits RS485 and AUX Supply 2 from the AC Mains Wiring Segregate any wiring connected to the relay contacts Eyelets are provided in the rear of the backbox to enable the cables to be securely fastened I using tie wraps ee o Da Dice ees IR Sounders and AUX wiring should be routed behind the chassis assembly and tie wrapped to the backbox Cable screens shields should be connected to the backbox using the threaded studs provided near the knockout holes Refer to Appendix 2 Recommended Cables for further information on cable types to be used Internal arrangement showing recommended routing of cables Refer to specific sections on how to install AC Mains input and loop sounder relay and AUX outputs circuits Document
23. loops All three panels are designed for use with the Apollo Discovery Explorer XP95 and Series 90 and Hochiki ESP fire detection devices Install the panel detection loops sounder circuits etc in accordance with the instructions in Section 2 and then program the operation in accordance with the instructions detailed in Section 3 Document Reference 680 014 Author RFM4100 1 1 EN54 Functions This Fire Alarm Control Panel is compliant with the requirements of EN54 parts 2 and 4 1997 In addition to the basic requirements the following optional functions are provided and these comply with the requirements of EN54 C I E Optional Functions EN54 2 Clause Indication Fault Signals from Points Outputs Outputs to Fire Alarm Devices Controls Investigation Delays to Outputs Co incidence Detection Disablement of Points Test Condition P S E Functions EN54 4 Clause Operation from a main power supply Operation from a standby battery Monitor and Charge the Standby Battery Recognise and Notify Supply Faults This Fire Alarm Control Panel also supports additional functions that are not covered by ENS4 These are as follows Additional Function Refer to Paragraphs Programmable Cause Effect on Outputs Phased Evacuation 6 4 Auxiliary Power Supply Output 24 7 Auxiliary Relay Outputs 2 4 5 Printer Option User Manual 1 2 Installation Approvals 1 2
24. recommended lifting practices to guard e against spinal injury 2 2 1 Removing and Replacing the Enclosure Cover of the Mx 4100 The enclosure cover is fixed in place with two tamper resistant hexagon key screws These require the use of a 2 5mm Allen Key The enclosure cover must be connected to earth When replacing the cover always ensure that the earth lead spade terminal is securely seated onto the blade terminal in the backbox 2 2 2 Removing the Chassis It is recommended that the chassis be removed before fitting the panel to the wall To remove the chassis Disconnect the earth cable connecting the chassis to the spade terminal on the rear enclosure Remove the two screws holding the chassis to the back box Keep these items in a safe place for later re use Unplug the 3 way connector feeding the power supply to the Base Card Carefully remove the chassis from the rear enclosure and place in a safe place to prevent accidental damage j Do not lift the chassis by holding onto any of the printed circuit cards Hold the chassis by the metal plate only 2 2 3 Mounting the Enclosure Firstly remove the required knockouts for the installation wiring There are sufficient knockouts on the top of the enclosure for all installation wiring In addition there are knockouts at the top of the back wall if required for rear entry cabling The enclosure is provided with four fixing points 340 The diagram opposite shows the position
25. soon as possible 5 1 4 Annual Actions The service maintenance contractor should perform the following checks and actions a Perform the checks as recommended above in the daily monthly and quarterly schedules b Perform a complete Walk Test of the system to check that each call point and detector is operating to its manufacturers specification c Visually inspect all cable fittings Check that the equipment is undamaged and that the conditions of installation have not changed such that they fall outside of the equipment specifications d Inspect and test all batteries and replace as required refer to Section 5 2 for recommended replacement schedule e Record in the logbook any defects or remedial actions that must be undertaken and arrange for these to be carried out as soon as possible Document Reference 680 014 Author RFM4100 41 of 53 5 2 Replacement of Components In general all of the components parts used in the construction of the panel have been selected for long life and reliability However certain components may require to be changed on a regular service basis The details of these are as follows 5 2 1 Batteries N Respect the Environment aw Batteries must be disposed of responsibly and in accordance with any local regulations 5 2 1 1 Standby Batteries Expected Life 3 5 years at an ambient temperature of 20 C Replacement Schedule As
26. will continue with the auto learn process If a single device is accepted rejected and another new device type is subsequently registered the display will once again show the pop up window to accept or reject this device 3 3 4 Zones The Commission Zones option lists all the zones in use by the panel and allows the zone text description to be changed Commission Zones Zone Location 0001 ASEMENT WEST 0002 ECEPTION 0015 EAST WING 0018 TOWER BLOC To change the location text assigned to the Zone press the Y button when the Zone Location Text is highlighted Refer to Section 3 1 4 for guidance on how to change text descriptions To select a different zone either use the scroll up down keys or just type in the number of the required zone followed by the V button Note that only zones in use are displayed 3 3 5 Exit To exit the Commission Mode functions and return the panel to normal operation ie level 2 select the Exit option The display will prompt for confirmation of the password For example Commission Menu 1 Please Enter Your Password Next Menu The display will then present the Level 2 Menu Functions If the password is incorrect this will be indicated or if the password is not entered within 5 seconds the display will revert to the Commission Level Menu and level 2 will not be entered After commissioning the panel must always be returned to level 2 or level 1 to gi
27. 0 5 On 24 E ANY FIRI 00 4 On Cl GI GI Output Group 8 Sounders on Floor 8 Output Group 8 3 9 Mem used ZONE GROUP CAUSE STYLE Delay gt MODE 22 8 ANY FIRI 02 30s Pulse 23 8 ANY FIRI 02 30s Pulse 24 8 ANY FIRI 02 30s Pulse E Wait MODI Eh a Ea Document Reference 680 014 Author RFM4100 49 of 53 6 5 Appendix 5 Apollo Information Special Discovery specific features are available from the Additional Info field of the Loop View Edit display It is then possible to view the internal Drift perform a rapid compensation or access any of the internal Discovery EEPROM memory locations Press the Y button and a pop up window is shown presenting a list of options For example lt More gt 004 0 Disco Press the MY buttons to highlight the required menu option and then press the Y button to confirm 6 5 1 View Drift The display then shows the Discovery devices that the panel is reading For example select the View Drift option and the display shows Loop 1 Devices lt More gt Address Additional Info gt 001 0 DRRPONE CEDERT PE 002 0 XP95 003 0 Disco Reading 004 0 Disco Reading When the reading is complete the display shows the drift within the device For example Loop 1 Devices lt More gt Address Additional Info gt 001 0 Damsxere Drift 002 0 XP95 003 0 Disco Drift 004
28. 3 13 7 Company LCD Logo Document Reference 680 014 Rev 06 Author RFM4100 3 3 13 8 Program ID 3 3 13 9 Config Data 4 EN54 Optional Features 5 Service and Maintenance 5 1 Maintenance Schedule 5 1 1 Daily Actions 5 1 2 Monthly Actions 5 1 3 Quarterly Actions 5 1 4 Annual Actions 5 2 Replacement of Components 5 2 1 Batteries 5 2 1 1 Standby Batteries 5 2 1 2 Lithium Battery 5 2 2 Liquid Crystal Display 6 Appendices 6 1 Appendix 1 Forgotten Level 3 Password 6 2 Appendix 2 Recommended Cables 6 3 Appendix 3 Battery Standby Calculation Chart 6 3 1 Mx 4100 6 3 2 Mx 4400 amp Mx 4200 6 4 Appendix 4 Cause and Effect Programming Example 6 4 1 Introduction 6 4 2 Output Groups 6 4 3 Styles 6 4 4 Output Group Programming 6 5 Appendix 5 Apollo Information 6 5 1 View Drift 6 5 2 Rapid Compensation 6 5 3 View EEPROM 6 6 Appendix 6 Hochiki Esp Information 6 6 1 Unprocessed Analogue information 6 6 2 CHQ BS Sounders 6 7 Appendix 7 Mx4000 Series Loop Output Drive Capabilty 6 7 1 Hochiki 6 7 2 Apollo Document Reference 680 014 Author RFM4100 Cautions and Warnings BEFORE INSTALLA
29. 4100 3 Programming 3 1 Introduction 3 1 1 Access Levels 3 1 2 Memory Lock 3 1 3 Navigating through menus 3 1 4 Changing Text Descriptions 3 1 5 Numeric data entry 3 2 Recommended Programming Procedure 3 3 Level 3 Menu Functions 3 3 1 Loops 3 3 2 Loops View Edit 3 3 2 1 State 3 3 2 2 Type 3 3 2 3 Value 3 3 2 4 Zone 3 3 2 5 Device Text 3 3 2 6 Action 33267 Sensitivity 3 3 2 7 1 Mode Apollo 3 3 2 7 2 Mode Hochiki 3 3 2 7 3 Delay 3 3 2 7 4 Alarm Apollo 3 3 2 7 5 Alarm Hochiki 3 3 2 7 6 Pre Alarm 3 3 2 7 7 Minimum Value 3 3 2 7 8 Special Sensitivity Mode SSM Clock 3 3 2 8 O P Group 3 3 2 9 Additional Info 3 3 2 10 Detector Testing 3 3 3 Loops Auto Learn 3 3 3 1 Normal Procedure Initial learn 3 3 3 2 Procedure if the Panel finds Devices Missing 3 3 3 3 Procedure if the Panel finds Devices Added 3 3 3 4 Procedure if the Panel finds Devices Changed 3 3 4 Zones 3 3 5 Exit 3 3 6 Outputs 3 3 6 1 Default Output Settings 3 3 6 2 Cause 3 3 6 3 Style 3 3 6 3 1 Delay 3 3 6 3 2 Mode 3 3 6 3 3 Wait 3 3 6 4 Copying Output Settings to Multiple Zones 3 3 7 Investigation Delays 3 3 7 1 Overriding Delays at Level 1 3 3 8 Time and Date 3 3 9 View Options 3 3 10 Passwords 3 3 11 Panel 3 3 12 PC Config 3 3 13 Setup 3 3 13 1 Network 3 3 13 2 Panel Zone 3 3 13 3 Service Number 3 3 13 4 Service Due Date 3 3 13 5 Trace Logging Mode 3 3 13 6 Detector Blinking 3
30. 53 2 4 2 Battery Installation The panel requires two 12V batteries Base Card Terminations for standby operation The battery leads are connected onto the base card via a two part plug and BAT socket as shown in the diagram BAT opposite AUX Refer to the Specifications for AUX 2 A A minimum and maximum battery sizes FS2 BAT FS1 Supply allowed Mx 4100 Mx 4200 amp Mx4400 Tosi Link Cable BLACK Place the batteries in the bottom of the enclosure and connect the Red lead to the positive terminal of battery 1 and the Black lead to the negative terminal of battery 2 Connect the negative of battery 1 to the positive of battery 2 using the supplied link cable Ensure that the battery terminals do not short out against any part of the enclosure circuit board or chassis plate Do not make the final battery connections until the installation wiring is completed and the system is to be powered up Always connect the AC Mains input before connecting the battery New batteries require top charging before installation Refer to Section 5 2 1 1 for a list of recommended batteries 2 4 2 1 Mx 4100 The diagram opposite shows the recommended location and orientation
31. AULT Press the button to change the sensitivity assigned to an input device When selected a new screen displays the sensitivity settings assigned For example with an Apollo Discovery ENSITIVITY ADJUST MODE ION SMOKE Alarm 3 Pre Alarm 5s Min Value SAM SSM Press the M Y gt buttons to highlight the required menu option and then press the Y button to select it Use the number buttons to enter the required value Alternatively press the Esc button to cancel the changes The alarm thresholds and delay times can be unique for every device if required Always ensure that the values chosen are suitable for the particular installation and that reliable fire coverage is maintained at all times 3 3 2 7 1 Mode Apollo This is applicable to Discovery devices only The panel fully supports the sensitivity modes within the Discovery devices Refer to the Apollo technical documentation for a detailed description and recommended use of these bands Different sensitivity modes can be chosen for both day and night periods This field can be set in the range 1 5 3 3 2 7 2 Mode Hochiki This is applicable to Multi sensor devices only e Mode 0 Default Combined optical amp heat detectors e Mode 1 Optical mode only e Mode 2 Heat mode only Document Reference 680 014 Author RFM4100 26 of 53 3 3 2 7 3 Delay The value in this field
32. TION Refer To the Ratings shown on the label inside the product and to the Specifications Chart in this document Please read this manual carefully If you are unclear on any point DO NOT proceed Contact the manufacturer or supplier for clarification and guidance Only Trained service personnel should undertake the Installation Programming and Maintenance of this equipment and the EMC Directives Failure to follow the installation instructions may compromise its This product has been designed to comply with the requirements of the Low Voltage Safety adherence to these standards This equipment is constructed with static sensitive components Observe anti static precautions at all times when handling printed circuit boards Wear an anti static earth strap connected to panel enclosure earth point Before installing or removing any printed circuit boards remove all sources of power mains and battery 1 Introduction This manual covers the installation programming and commissioning of the Mx 4100 Mx 4200 and Mx 4400 Fire Alarm Control Panels Refer to the User Manual Document No 680 015 for details of how to operate the panel The Mx 4100 is a Single Loop Analogue Addressable Fire Alarm Control Panel The Mx 4200 is a Multiple Loop Analogue Addressable Fire Alarm Control Panel with provision for up to two loops The Mx 4400 is a Multiple Loop Analogue Addressable Fire Alarm Control Panel with provision for up to four
33. Technical Data Sheet Installation amp Commissioning Manual MX4100 MX4200 amp MX4400 Fire Alarm Control Panels Document Reference 680 014 Author RFM4100 Specifications Mx 4100 Mx 4200 Mx 4400 Enclosure Steel IP40 Steel IP 40 Steel IP40 Dimensions H xWxDmm 320 x 345 x 85 475 x 450 x 115 475 x 450 x 115 Weight 5Kg 10 5Kg 10 5Kg Temperature 0 C to 45 C 0 to 45 C 0 C to 45 C Cable Entries 20mm knockouts 7 x top and 7 x top rear 18 x top 9 x top rear and 2 x bottom 18 x top 9 x top rear and 2 x bottom Mains Supply 230V 50 60Hz AC 10 15 0 4A max 90 265V 47 63 Hz AC 1 9A 90V 0 64A 265V 90 265V 47 63Hz AC 2 3A 90V 0 95A 265V Battery Capacity For 24Hr standby 24V 4Ah Internal min 24V 7Ah Internal max 24V 12Ah External max 24V 4Ah Internal minimum 24V 17Ah Internal maximum 24V 48 Ah External max 24V 4Ah Internal minimum 24V 17 Ah Internal maximum 24V 48Ah External max Charging Current 0 4A Temperature Compensated 2A Temperature Compensated 2 2A Temperature Compensated Power Supply On board 24V DC 2A High Efficiency Switched Mode Separate 24V DC 4A Universal Input Switched Mode Separate 24V DC 5A Universal Input Switched Mode Number of Fire Zones 100 250 when networked 200
34. UX Supply from the AC Mains Wiring Segregate any wiring connected to the relay contacts Eyelets are provided in the rear of the backbox to enable the cables to be securely fastened using tie wraps Refer to Appendix 2 Recommended Cables for further information on cable types to be used Refer to specific sections on how to install AC Mains input and loop sounder relay and AUX outputs circuits Internal arrangement showing recommended routing of cables Document Reference 680 014 Author RFM4100 10 of 53 2 3 Installing the Mx 4200 amp 4400 Enclosures The panel can weigh in excess of 20kg when the batteries are installed Use appropriate fixing hardware to secure the panel to the wall Observe recommended lifting practices to guard against spinal injury 2 3 1 Opening the Enclosure Cover The Mx4200 amp Mx 4400 are provided with a key lock assembly for securing the hinged door to the backbox Insert and turn the key to open the enclosure 2 3 2 Removing the Chassis It is recommended that the chassis be removed _ before fitting the panel to the wall To remove the J gJ J C chassis o o Fixing Refer to the diagram opposite Sees Disconnect the earth cable connecting the chassis to the spade terminal on the rear enclosure Remove the bottom two screws holding the chassis to the back box Keep these item
35. ad Equipment I A x Total I A x Total Mx 4100 0 115 1 0 0 115 0 225 1 0 0 225 Auxiliary Supply Output 1 0 1 0 Sensor Loop Current 1 257 1 25 Sounder Output A 1 0 Sounder Output B 1 0 Total ZQuiescent Load Alarm Load x 24 hr x 0 5 hr carry forward Total Load Quiescent Alarm x 1 2 Battery Derating factor Use the detector manufacturers technical information to calculate the load on the loop for both the quiescent condition and fire alarm condition for all loop devices By default a maximum of 5 detector call point LED indicators will be turned on in a fire alarm condition This number can be changed via the PC Programming Tool The calculated loop loading must be multiplied by a factor of 1 25 to calculate the actual current draw from the batteries This is to take into account voltage conversion and conversion efficiency in generating the supply for the loop The total load calculated must be multiplied by a derating factor of 1 2 to allow for changes in battery efficiency over time Document Reference 680 014 Author RFM4100 46 of 53 6 3 2 Mx 4400 amp Mx 4200 Quiescent Load Fire Alarm Load Equipment I A x Total I A x Total Mx 4400 Mx4200 0 083 1 0 0 083 0 178 1 0 0 178 Auxiliary Supply Output 1 0 1 0 Loop Driver 0 042 1 0 0 042 1 0 Sensor Loop Current 1 25
36. als on the base card Route the wires around the loop connecting all devices in accordance with the manufacturers data sheet supplied with each unit Ensure that the devices are correctly installed with regard to their positive and negative terminal polarity TT especially Loop Isolator Modules QZ Q Q Connect the return wires to the Loop IN and terminals on the base card Base Card Terminations Typical The diagram opposite shows the typical arrangement of the loop connections on the base cards Refer to Section 2 3 6 for details on installing additional loop drivers on the multi loop panels the cable gland input earth stud in the panel Always ensure that all segments of the cable loop have continuity of the screen and take care to ensure that the screen is not exposed to any other e earth point e g metalwork cable trays junction boxes etc When screened cable is used it is vital to connect the screen drain wire to the chassis earth at The Loop Driver Circuit on the Base card is equipped Isolators with in built isolators to take care of short circuit conditions on the wiring between the panel and the first device on the loop It is not necessary to fit loop isolators at the panel outputs The diagram opposite shows a typical loop arrangement Maximum recommended cable loop length is 1500 to 2000 Metres Refer to Appendix 2 Recomm
37. ated whenever the input is active Pre Alarm A Pre Alarm Condition will be generated whenever the input is active Fault Signal A Fault Condition will be generated whenever the input is active Security A Security Alert Condition will be generated whenever the input is active Record A Record Entry will be stored in the Log whenever the input is active This will be hidden from the panel status display Create Alarm 1 An Alarm 1 condition will be generated whenever this input is active Create Alarm 2 An Alarm 2 condition will be generated whenever this input is active Create Alarm 3 An Alarm 3 condition will be generated whenever this input is active Key Lock Inhibits front panel controls Disable Mute Reset etc No Action is assigned to the input Control Signal Allows control of Outputs without displaying Fault or Fire or sounding buzzer Document Reference 680 014 Author RFM4100 Page 25 of 53 Fire Alarm Conditions are latched By default all other conditions are non latching The action for smoke and certain other detectors is always fire and cannot be changed 3 3 2 7 Sensitivity This parameter shows if the device sensitivity is set to it s DEFAULT or CUSTOM settings For example Loop 1 Devices lt More gt Address Sensitivity 001 0 DEFAULT 002 0 EFAULT 003 0 USTOM 004 0 EF
38. e The number displayed will vary according to the type of device fitted A H High and L Low is shown for logic inputs This parameter cannot be changed 3 3 2 4 Zone This parameter shows to which Zone the device has been assigned Use the number keys to change the zone assigned to the device 3 3 2 5 Device Text This parameter shows the 26 character location text assigned to this device For guidance on how to change the text refer to Section 3 1 4 3 3 2 6 Action This parameter shows the action that will be performed when this device indicates an active alarm condition For example Loop 1 Devices lt More gt Address Action tivity O P 001 0 FIRE SIGNAI iT 002 0 FIRE SIGNAI iT 003 0 FIRE SIGNAI iT 004 0 FIRE SIGNAI iT Press the V button to change the action assigned to this input device A pop up window is then shown on the display from which an action can be selected Select New Action FIRE SIGNAL PRE ALARM FAULT SIGNAL Press the MY buttons to scroll through the list of Actions and then press the Y button to confirm the change The display reverts to the device list showing the new action assigned to this device Alternatively press the Ese button to cancel the changes and return to the device list display The following Actions are available Additional actions are available on a PC Action Description Fire Signal A Fire Alarm Condition will be gener
39. ed On entry to the function the display shows a list of the passwords For example Password Access level User ID 15633 2 01 9988 02 13344 03 10000 04 10000 05 To change a password use the MW buttons to highlight the required password and then enter the new password using the number buttons When the password is correct press the Y button to confirm Level 3 Passwords Care should be taken when changing the Level 3 password If this new number is lost it is not possible to enter commission mode functions Refer to 6 1 for further information The factory default level 3 password is 7654 3 3 11 Panel The Panel Menu Option shows a list of the internal panel circuits and provides a means to change their default configuration settings Only use this menu if changes are to be made to the default settings for the panel s internal circuits Use the VIEW PANEL Menu Option to view the state and operating condition of each circuit The display shows for example Address State Type gt 001 0 Normal VOLTAGE 001 1 Normal VOLTAGE 002 0 Normal CURRENT 002 1 Normal CURRENT Use the NW buttons to scroll through the circuits Use the buttons to view additional information The zone and Output Group Assignments can be modified if required For further information on the View Panel Options and the information that is presented refer to the User Manual Document No 680 015 Document Refer
40. ence 680 014 Author RFM4100 36 of 53 3 3 12 PC Config The PC Link Option enables the connection of the PC Configuration Tool for retrieving configuration data from the panel and programming configuration data from a file on the PC For further information refer to the Manual supplied with the PC Configuration Tool 3 3 13 Setup The Setup Options Menu enables the configuration of panel generic operating parameters When the option is selected the display shows a list of the available parameters For example Setup HIS NETWORK NODE M T NEXT NETWORK NODE 0 P S ANEL ZONE 100 ERVICE NUMBER 01234 567890 Use the MY buttons to scroll through the list of options The following will then be shown ERVICE E DATE 1 JAN 2011 10 00 RACE LOGGING MODE STANDARD More gt ETECTOR BLINKING NONE PANY LCD LOGO Vv 3 3 13 1 Network This Network node is set to 0 for a standard non networked panel For panels in a networked application please refer to the Network document reference 680 027 3 3 13 2 Panel Zone By default all the panel inputs are assigned to the Panel Zone Alternatively the PC configuration program allows individual inputs to have different zones if required 3 3 13 3 Service Number The Service Number is the telephone number that is shown on the status display whenever a fault condition occurs To c
41. ended Cables for further information on cable types to be used Typical Loop Arrangement Take care that the voltage drop at full load is within the detector rating refer to the detector manufacturers data sheet for minimum values e To maintain signal line wiring supervision break the wiring run at each loop device Document Reference 680 014 Author RFM4100 17 of 53 2 4 4 Sounder Circuits The Mx 4100 amp Mx4200 are equipped with two supervised sounder circuits These are denoted as Circuits A and B The Mx 4400 is equipped with four supervised sounder circuits These are denoted as Circuits A B C and D Each Sounder output is rated at a maximum of 1 Ampere JOOB The terminal connections on the base card are shown in the diagram opposite Base Card Connections Typical The sounder outputs are monitored supervised for open and short circuit conditions using reverse polarity signals Sounder must be equipped with an in built blocking diode that prevents the sounder from taking power when the output is in the supervising condition An End of Line Resistor EOLR of value 10 0000 Watt must be fitted to the last sounder bell Arrangement Refer to Appendix 2 Recommended Cables for further information on cable types to be used Typical Sounder Arrangement gland input earth stud in
42. hange the number press the Y button when the option is highlighted The number is entered using the text entry facility refer to Section 3 1 4 for guidance on how to enter text Document Reference 680 014 Author RFM4100 37 of 53 3 3 13 4 Service Due Date The next service over due date can be entered into the panel memory When this date is reached the panel will enter a fault condition to alert the site operator that a service visit is overdue To change the due date press the V button when the option is highlighted The display prompts for entry of the next service date For example IPAR 24 04 02 Use the MY buttons to select between the time and date Use the number buttons to enter the required time or date As soon as a new service date is entered the panel will cancel any Service Due Fault condition 3 3 13 5 Trace Logging Mode The Trace Logging Option determines what type of information and to what level is stored in the Event Log There are three options STANDARD the normal operating mode logging fire alarm fault and warning conditions as they occur STANDARD an extended version of the standard operating mode where the removal of fault and warning conditions are also logged DIAGNOSTIC a full diagnostic trace of all conditions with greater depth to aid diagnosis of fault conditions To change the option press the Y button To erase the
43. he panel indicates normal operation If any faults exist these should be recorded in the logbook b Any recorded faults have received attention and have been signed off 5 1 2 Monthly Actions The site operator user should perform the following checks and actions a Any stand by generators should be started and fuel levels checked b Operate at least one call point or detector from different zones each month and check that the panel enters a fire alarm condition and that the appropriate programmed alarm or warning devices are sounded operated Where permissible this should include any links to the fire brigade or remote centre c Check that all outstanding faults have been recorded and have received attention 5 1 3 Quarterly Actions The service maintenance contractor should perform the following checks and actions a Check that all entries in the logbook have been addressed check the event log in the panel and take the necessary remedial actions b Visually inspect the panel for any moisture ingress or other deterioration check all battery connections and test check the alarm fault and other functions of the panel operation c Ascertain if any building or structural alterations have been carried out that would affect the siting of call points or detectors If so perform a visual inspection d Record in the logbook any defects or remedial actions that must be undertaken and arrange for these to be carried out as
44. inted circuit card into the guide slots of the machined end blocks and then push into place onto the connector sans ss on the Base Card mag n HT roeasseasaso LOOP 2 LOOP 3 a NETWORK I F 28 SC 00008 02 Eaaaerosse em inaaesossas naeeveoeun n Essa TO DISPLA Ensure that the pins of the connectors are correctly 1 aligned The loop driver should be inserted with the component side of the board placed on the left hand side on nr tm LE OOH The Base Card can accept up to four loop driver cards Machined End 888 it does not matter which positions are used Ensure that Block the detector loop wiring is made to the terminal block positions appropriate to the loop driver cards actually installed SS NB The Mx 4200 only has positions 1 amp 2 available Close the chassis display plate and then close up the enclosure 2 3 7 Removing a Loop Driver Card To remove a loop driver remove all power and follow the procedure above but Take a firm hold of the lever located on top of the loop driver card Gradually and carefully pull the loop driver vertically away from the base card and guide it out of the slots in the machined end blocks Document Reference 680 014 Author RFM4100 13 of 53 2 4 Wiring Installation 2 4 1 AC Mains Wiring Route the high voltage mains AC wiring into the enclosu
45. mation and Appendix 6 Hochiki Esp Information Document Reference 680 014 Author RFM4100 28 of 53 3 3 2 10 Detector Testing Individual detectors can be tested to check the chamber response and illuminate the detector LED While the address field is highlighted press the MW buttons to scroll through the list of devices to the desired detector or key in the address and then press the Y button A menu will appear to confirm that you want Test This Detector Press the Y button to confirm or press the Ese button to cancel Once selected commands are sent to the detector to turn on the detector LED and put the chamber into test The Test LED lights up and the panel display returns to the list of devices After a few seconds the analogue signal will be seen to rise If the detector is then left in the test condition the Detector State will change to a Fire Test status The test is cancelled as soon as the display is scrolled up or down or when the View Devices option is exited 3 3 3 Loops Auto Learn 3 3 3 1 Normal Procedure Initial learn The panel can automatically learn the presence or absence of devices at all addresses connected to the loop When the Auto Learn option is selected the panel starts searching each address on the loop to locate and find all of the devices connected A display is shown to indicate the progress of this procedure
46. mber and then enter the number of the output group required using the number buttons The display always shows the Output Group is shown in the top left corner Press the MW buttons to scroll through the list of zones Press the buttons to select the fields for a particular zone Press the Y button to select a particular field option to change its setting 3 3 6 1 Default Output Settings On initial installation or after clearing the configuration memory all outputs are assigned to specific Output Groups and will turn on immediately a single fire alarm occurs in any zone any fault condition for the fault relay The default assignments are as follows Output Device Output Group Cause and Effect On board Sounder A Any fire in any zone no delay On board Sounder B Any fire in any zone no delay On board Sounder C Any fire in any zone no delay On board Sounder D Any fire in any zone no delay On board Relay 1 Any fault in any zone no delay On board Relay 2 Any fire in any zone no delay On board Open Collectors Any fire in any zone no delay All Loop Output Devices Any fire in any zone no delay Mx4400 only Document Reference 680 014 Author RFM4100 32 of 53 3 3 6 2 Cause Each Output Group can be programmed to respond in a unique way to events from each individual zone An input event may be a fire ala
47. menu is displayed use the MW gt buttons to highlight the required menu option and then press the button to select it Press the Esc button from within a menu option to return to the previous menu The display can be forced back into status mode by pressing the Esc button when at the top level commissioning menu or by waiting 60s Document Reference 680 014 Author RFM4100 21 of 53 3 1 4 Changing Text Descriptions Various parameters can have a text description defined These include loop devices zones etc The zone and device text descriptions will be shown on the display in the Fire Alarm Fault and Warning Conditions etc to provide a quick and clear indication of the source of the problem To change the text description first highlight the text description within the appropriate programming option and then press the Y button The display then changes to show the text entry dialogue screen For example ESTAURANT EY IN THE The method of entering the characters is similar to the method employed on mobile telephones The number buttons provide both their appropriate number and several letters of the alphabet An example of the keypad is shown opposite For example Button 2 allows entry of the number 2 and letters A B and C When a button is pressed the number is first shown on the display at the current cursor position If the button is
48. mething happening at the output The delay time can be set in intervals of 1 second up to a maximum of 250 seconds Press the button to step on to the delay field and change the setting using number entry 3 3 6 3 2 Mode The mode field defines the method of operation of the output when it is first activated This can be ON or PULSE Press the button to step on to the delay field and change the setting using the Y button 3 3 6 3 3 Wait The wait field is the time from first activation of the output to the next operational condition mode of the output For example the output could initially be delayed for 20 seconds and turn on in a pulsing mode After a wait of a further 30 seconds it can be programmed to turn on differently such as ON The wait time can be set in intervals of 1 second up to a maximum of 250 seconds Press the button to step on to the wait field and change the setting using number entry 3 3 6 4 Copying Output Settings to Multiple Zones To save time in the entry of similar Output Group Settings for each zone it is possible to copy information programmed for a particular zone to subsequent zones Press the button to highlight the required zone number and then press the Y button The display shows a pop up window prompting for the number of the zone to which to copy the information Use the number entry to select the required zone number The Output Group programming for all of the zones from the currently selec
49. n and check change the Level 3 password Refer to Section 3 3 10 for further information Document Reference 680 014 Author RFM4100 44 of 53 6 2 Appendix 2 Recommended Cables Detector Loop amp Sounder Circuits Manufacturer Cable Type AEI Firetec Multicore Ref FIC1 AEI Firetec Multicore Ref FIC1 5 AEI Firetec Multicore Ref F1C2 5 AEI Firetec Armoured Ref F1C1 AEI Firetec Armoured Ref F1C1 5 AEI Firetec Armoured Ref F1C2 5 AEI Mineral Insulated Copper Cable AEI Mineral Insulated Copper Cable AEI Mineral Insulated Copper Cable BICC Mineral Insulated Twin Twisted CCM2T1RG BICC Mineral Insulated Twin Twisted CCM2T1 5RG CALFLEX Calflam CWZ DRAKA Firetuf OHLS FTZ DRAKA Firetuf OHLS FTZ HUBER amp SUHNER Radox FRBS M1x2x1 5 HUBER amp SUHNER Radox FRBS M1x2x2 5 PIRELLI FP200 Gold PIRELLI FP200 Gold PIRELLI FP200 Gold Document Reference 680 014 Author RFM4100 45 of 53 6 3 Appendix 3 Battery Standby Calculation Chart Use the following charts and associated notes to calculate the size of the batteries required to ensure operation of the installation in the event of AC Mains power failure 6 3 1 Mx 4100 Quiescent Load Fire Alarm Lo
50. ne assignment action etc Press the MY buttons to highlight the required menu option and then press the Y button to confirm The pop up window will disappear and the panel will continue with the auto learn process If a single device is deleted and another missing device is subsequently registered the display will once again show the pop up window to keep or delete this device 3 3 3 3 Procedure if the Panel finds Devices Added When the panel finds a device not previously learnt and programmed in the panel the Auto Learn process is suspended and the display shows a pop up window with options For example ACCEPT NEW DEVICE REJECT NEW DEVICE ACCEPT ALL NEW DEVICE REJECT ALL NEW DEVICE Address 002 NEW If the new device is accepted or all new devices are accepted the panel will configure the memory to register these devices All data will be configured to initial settings for sensitivity threshold changes text assignments zone assignment action etc for these devices If the new device is rejected or all new devices are rejected the panel clears all programming for these devices and will not attempt to communicate with the devices at these addresses Press the MY buttons to highlight the required menu option and then press the Y button to confirm The pop up window will disappear and the panel will continue with the auto learn process If a single device is accepted
51. nel RX Receive Data into the panel GND Ground Reference The RS232 I F can be used with the RS232 I F Cable Kit This kit consists of the cable and a bulkhead mounting connector thereby enabling external connection without opening the door The internal RS232 I F Cable Kit option provides connections via a standard 9 way d type connector from the outside of the enclosure To install the cable 1 Remove the cover plate in the bottom face of the back box Secure the D Type Connector in the mounting hole using the fixing hardware supplied Plug the end of the cable into the socket header on the base card Refer to the RS232 Interface Section above for details of the terminal block signals The D Type connector can be used with A PC Cable Kit to connect the panel directly to a PC A Modem and Cable Kit for remote PC connection A Printer Adapter and Cable Kits for connection to a printer Contact your supplier for the relevant part numbers and order information for option kits IJO Base Card Connections typical ESS ODO is OE RS232 Cable amp Recommended Routing Typical Internal Arrangement Mx 4 00 shown Document Reference 680 014 Author RFM4100
52. nt BS EN60950 2000 Safety of information technology equipment BS EN50130 4 196 Product Family Standard Electromagnetic Compatibility Directive 89 336 EEC and the amending directive 92 23 EEC Low Voltage Directive 73 23 EEC Contents Introduction 1 1 ENS54 Functions 1 2 Installation Approvals 1 2 1 Fire System Installations 1 2 2 Wiring Regulations 2 Installation 2 1 Identification of Parts 2 1 1 Mx 4100 2 1 2 Mx 4200 amp Mx 4400 2 2 Installing the Mx 4100 Enclosure 2 2 1 Removing and Replacing the Enclosure Cover of the Mx 4100 2 2 2 Removing the Chassis 2 2 3 Mounting the Enclosure 2 2 4 Remounting the Chassis 2 2 5 Recommended Cable Routing Arrangement 2 3 Installing the Mx 4200 amp 4400 Enclosures 2 3 1 Opening the Enclosure Cover 2 3 2 Removing the Chassis 2 3 3 Mounting the Enclosure 2 3 4 Remounting the Chassis 2 3 5 Recommended Cable Routing Arrangement 2 3 6 Installing Additional Loop Circuits in the Mx4200 amp Mx 4400 2 3 7 Removing a Loop Driver Card 0 0 0 a vow 00 awaa AI O 24 Wiring Installation 2 4 1 AC Mains Wiring 2 4 1 1 Cable Gland 2 4 2 Battery Installation 2 4 2 1 Mx 4100 2 4 2 2 Mx 4200 amp Mx 4400 2 4 3 Detector Loop Installation 2 4 4 Sounder Circuits 2 4 5 Relay Circuits 2 4 6 Open Collector Outputs 2 4 7 Auxiliary Supply Output 2 4 8 RS232 Interface Document Reference 680 014 Author RFM
53. ock In addition to the SENSITIVITY ADJUST MODE a device can also run in a SPECIAL SENSITIVITY MODE SSM under time clock control The Mx4 00 supports 3 independent 7 day time clocks The Mx4200 supports 10 independent 7 day time clocks The Mx4400 supports 10 independent 7 day time clocks With the SAM SSM Option highlighted press the Y button to view the Special Sensitivity Mode settings For example SPECIAL SENSITIVITY MODE MULTI SENSOR SSM Clock 55 Mode 40 Delay 8 In the above example the panel is using special sensitivity mode 2 and time clock number 2 Enter 0 in the SSM Clock field to cancel Special Sensitivity Mode Document Reference 680 014 Author RFM4100 27 of 53 A number must be entered in the SSM Clock field to select the appropriate SSM number and time clock To view the time clock settings highlight the SSM Clock field and press the Y button For example Time Clock 2 ON gt OFF Grenier 00 00 00 00 06 30 00 00 00 00 00 00 00 00 The panel supports two independent times for each day of the week during which the SSM mode will be switched on i e during which the Special Sensitivity Mode settings are active In the above example the SSM will be active between 19 00 on Monday and 06 30 on Tuesday Press the MW gt buttons to select the appropriate time field and use the number buttons to en
54. pressed again within 4 second the first character replaces the number A further press displays the second available character and so on After pressing the button to obtain the required character wait for 1 second and the character will be entered and the cursor will move to the next character in the text description Pressing another button will immediately enter the previous character and move the cursor on to the next character Use the buttons to move backwards or forwards along the line When the text description is as required press the Y button to confirm the change If the text has been entered incorrectly press the Esc button to cancel all changes and return to the previous display The following table shows the numbers characters and symbols assigned to each button on the keypad Button 1 Press 2 Press 3 Press 4 Press 5 Press 1 1 lt lt Z O tUjH m o N e mnajulasa W N Blank oco olelulaluls w n o x Co zirz nio Alternatively press the MY buttons to scroll through a list of characters When the required character is shown press the gt button to move on to the next character The list of characters available and the order of presentation is as follows Blank amp 0123456789 lt gt ABCDEFGHIJKLMNOPQRSTUVWXYZ _ Document Reference 680 014 Rev 06 Author PS RFM4100 Page 22 of 53
55. r example The first Style is that the sounders should turn on immediately a fire is recognised in Zone 22 or in Zone 23 or in Zone 24 The panel contains a default Style Style 00 for this method of operation The second Style is that the sounders should stay silent for 30 seconds and then start pulsing After 2 minutes of pulsing they should then turn on This is a little more complex but is easy to program In the following description a new Style Style 2 will be defined for this purpose It is quite likely that Style 2 will be used extensively in the cause and effect programming for the rest of the building For example a fire on Floor 8 may also require the sounders on Floors 7 and 8 to operate in this manner Document Reference 680 014 Author RFM4100 48 of 53 6 4 4 Output Group Programming To achieve the above cause and effect requirements the three different Output Groups would be programmed and indicated on the panel as in the following display examples Output Group 6 Sounders on Floor 6 Output Group 6 3 9 Mem used ZONE GROUP CAUSE STYLE Delay gt MODE E Wait MOD 22 6 ANY FIRI 02 30s Pulse 23 6 ANY FIRI 02 30s Pulse 24 6 ANY FIRI 02 30s Pulse GI Gl FI Output Group 7 Sounders on Floor 7 Output Group 7 3 9 Mem used ZONE GROUP CAUSE STYLE Delay gt MODI 22 7 ANY FIRI 00 On 23 7 ANY FIRI 0
56. re at the upper left corner only Keep the AC wiring away from the circuit boards and all other wiring Panel Wiring Yellow The panel must be connected to the supply earth through the power cable The mains input connector is shown in the diagram opposite Note the positions of the earth neutral and live terminal connections These are clearly marked on AC Mains terminations Mx 4100 the label next to the connector The connector block contains an integral fuse holder Panel Wiring The fuses are rated as follows Brown T 1 0A H 250V for Mx 4100 T 3 15A H 250V for Mx 4200 and MX4400 Replace with correct rating and specification only Connect the Control Panel to the mains supply via a readily accessible disconnect device Isolation Switch AC Mains terminations Mx 4200 amp Mx4400 and suitable earth fault protection incorporated in the building installation wiring The Mains cable should be 0 75mm cable rated at 250V and fused via a 5A anti surge fuse 2 4 1 1 Cable Gland 20mm knockout must have a minimum flame retardant rating of 94HB j The cable gland and any cord clamp bushing s used in routing the Mains cable through the amp Suggested glands and bushings are Type Manufacturer Gland IP65 Brass M20 EExd Eexe Lappcable Gland IP68 Nylon 66 M20 Black UL94V2 Multicomp Bushing Nylon 66 M20 Black UL94V2 Multipcomp Document Reference 680 014 Author RFM4100 14 of
57. rm condition or it may be a fault disablement or other condition A combination of criteria may also be applied to each zone The Cause field determines what type of input event or a combination of input events will generate an output response for the selected input zone To inspect or change the Cause press the gt button to highlight the cause option For example tput Group 1 3 9 Mem used CAUSE STYLE Delay gt MODE Wait 00 ANY FIRI ANY FIRI ANY FIRI Press the V button to change the setting and a pop up window will appear showing the options available For example D K FIRI LARM PRE ALARM LT I P DISABLE EST CONTROL Press the MY gt buttons to highlight the required menu option and then press the to change its setting An input action type is enabled when a V is shown beneath the option It is permitted to select multiple input types in which case a combination of input events will result in an output action If there is a combination of input events the CAUSE display above shows this extended programming by adding a to the text For example Zone 2 above shows that the basic event is ANY FIRE other criteria Press the Esc button to return to the previous display The definition for each cause is as follows Fire Any single fire Double Knock D K Coincidence of 2 or more fire detectors or a single manual call point in the same zone
58. s in a safe place for later re use TRCALARH CONIROL PANEL Loosen the top two screws holding the chassis to the backbox via the keyhole slots The chassis assembly can now be removed Earth Connection Carefully remove the chassis from the rear enclosure and place in a safe place to prevent accidental damage j Do not lift the chassis by holding onto any of the printed circuit cards Hold the chassis by the metal plate only 2 3 3 Mounting the Enclosure Firstly remove the required knockouts for the installation wiring There are sufficient knockouts on the top of the enclosure for all installation wiring In addition there are knockouts at the top of the back wall if required for rear entry cabling The diagram opposite shows the positions of the four holes Use all four positions to ensure the panel is held securely to the wall Drill the required holes in the supporting wall using a en ee drill bit diameter 7 0 mm and plug with a suitable Cabl NE 40mm long expansion plug Affix the panel to the wall ocio Points x9 with M5 screws length 40mm or No 10 screws length 1 2 Ensure that there is sufficient space to allow the door to be opened when the panel is mounted In addition there should be sufficient space below the panel to allow access to the RS232 connected if fitted Finally use a brush to remove any dust or swarf from Enclosure Size and Fixing Point Dimensions
59. s of the four holes DER a 0 y Use all four positions to ensure the panel is held securely to the T 1 wall O0 00 0 O OB Te Drill the required holes in the supporting wall using a drill bit Earth diameter 7 0 mm and plug with a suitable 40mm long Ostu dela si expansion plug Affix the panel to the wall with M5 screws e ae ae ch length 40mm or No 10 screws length 1 2 Ensure that there is sufficient space to allow the cover to be esi removed replaced when the panel is mounted In addition m Cable Tie there should be sufficient space below the panel to allow Anchor Points x6 access to the RS232 connected if fitted Finally use a brush to remove any dust or swarf from inside the enclosure Enclosure Size and Fixing Point Dimensions Document Reference 680 014 Author RFM4100 2 2 4 Remounting the Chassis Carefully replace the chassis and fix into place using the two screws Reconnect the chassis earth cable to the spade terminal in the rear of the enclosure and then reconnect the supply lead from the transformer to the Base Card 2 2 5 Recommended Cable Routing Arrangement It is recommended that the routing arrangement ee di oop Tie Wrap shown in the diagram opposite be employed AC Mams ae ee Positions Segregate the low voltage wiring Loop Circuit Sounder Circuits and A
60. s the Y button to select the loop required The display will then show a list of programming options as follows Note On selecting the LOOPS option on the Mx4100 this display will be shown directly Loop 1 IEW EDIT AUTO LEARN CALIBRATE 3 3 2 Loops View Edit The VIEW EDIT option shows a list of the devices connected to the loop learnt by the panel For example Loop T More gt Address State Type Value 001 0 Normal CALL POINT 16 002 0 Normal MULTI SE 003 0 Normal ION SMOKE 004 0 Normal HEAT The first device on the loop is shown at the top of the list and is highlighted Press the MY buttons to scroll through the list of devices Press the buttons to view additional information The display highlights a particular parameter To change the value of this parameter if not view only press the Y button and appropriate options will be shown on the display 3 3 2 1 State This parameter shows the current operational status of the device For example this can show Normal Fire Alarm Device Missing etc This parameter cannot be changed 3 3 2 2 Type This parameter shows the type of device learnt by the panel For example this can show Call Point Multi Sensor ION Smoke Heat etc This parameter cannot be changed Document Reference 680 014 Author RFM4100 24 of 53 3 3 2 3 Value This parameter shows the analogue value returned by the devic
61. sent the information as follows Loop 1 Devices Address Additional Info gt 001 0 Damsxere EEP 1 002 0 XP95 003 0 Disco 004 0 Disco Refer to Apollo s literature for an explanation of the extended memory locations and for further information on the expected values Document Reference 680 014 Author RFM4100 51 of 53 6 6 Appendix 6 Hochiki Esp Information At power up the panel allows a couple of minutes for Hochiki Esp detectors to stabilise Any detectors that the panel knows to be present will then be calibrated The panel displays can be used normally during this time but the fire detection response will be slower until all the calibration phases are complete If devices are inspected during this period they may show their state as Reset panel has reset the device at power up resetting from a fire etc Calibrating checking ESP Zero Point and Fire Points Initialising loading detection thresholds sounder volumes etc Calibration can be manually initiated any time at access level 3 forcing all the devices on the selected loop to be calibrated Transferring new device information from a PC to the panel will also cause the effected devices to be re calibrated Periodic re calibration can be performed at levels 1 amp 2 under control of one of the 7 day timeclocks The timeclock settings are configured from PC program
62. ted zone to the zone number entered will be programmed with the same information as the currently selected zone Document Reference 680 014 Author RFM4100 34 of 53 3 3 7 Investigation Delays In addition to the Cause and Effect programming described above the panels also support an Investigation Delay Mode which allows time for a building supervisor to investigate fire signals before turning outputs on This mode can only be configured from the PC software There are two parts to this delay The first stage is set relatively short If the building supervisor does not acknowledge the fire signal within the first stage the delayed outputs will turn on The second stage gives a longer period to investigate the fire signal This delay can be cancelled at any time by pressing the EVACUATE button or any nominated input devices by default all call points cancel this mode Each input and output device can be individually programmed to use the investigation delay from the PC configuration software together with the times appropriate to each stage of the delay The user manual gives details of how the building occupier can turn the investigation delay feature on or off Delays to Outputs It must be possible to override the operation of any delays at Level 1 Refer to Section 3 3 7 1 for information on overriding delays For compliance the maximum total delay permitted is 10 minu
63. ter the required times Press the Esc button to return to the previous menu display Every type of device the device type is shown in the top right hand corner supports unique SSM settings for each SSM Clock number In the previous example the Special Sensitivity Mode settings have been defined for a Multi Sensor that is using SSM Clock number 2 If other Multi sensors on the same panel also require the same settings then you only need to set them to SSM Clock 2 If instead another Multi Sensor requires a different setting use a different SSM Clock number 3 3 2 8 O P Group The Output Group assigned to the Sounder or Relay Devices determines the manner in which the outputs will operate when a fire alarm or other programmed condition occurs For example Loop 1 Devices lt More gt Address O P Group 020 0 021 0 022 0 023 0 Use the number buttons to change the value of the O P Group setting By default all Loop Output devices are assigned to Output Group 199 For detailed information and guidance on the programming and use of Output Groups refer to Section 3 3 6 3 3 2 9 Additional Info This parameter shows additional information if available for this device For example the following display shows the Apollo detector series types Loop 1 Devices lt More gt Address Additional Info 001 0 Disco 002 0 XP95 003 0 Disco 004 0 Disco For further information on this option refer to Appendix 5 Apollo Infor
64. tes 3 3 7 1 Overriding Delays at Level 1 A facility to override any programmed delays and immediately activate the sounder circuits should be provided at Level 1 It is possible to override the delay using the panel controls see the user manual for details This can also be achieved from an input device that is programmed to turn on all outputs immediately 3 3 8 Time and Date This function allows the time and date in the panel to be changed On entry to the function the display shows the current time and date with confirmation of the day of the week on the bottom line For example E IRE 15 04 02 MON 15 APR 2002 To change the settings use the MY buttons to highlight the required option Directly enter the new time or date using the number buttons As soon as a number button is pressed the display will clear the current setting and show the new value as it is entered For example E DATE 1Y 15 04 02 MON 15 APR 2002 Document Reference 680 014 Author RFM4100 35 of 53 3 3 9 View Options The View Menu Options are identical to those available during Level 2 operation For further information on the View Options and the information that is presented refer to the User Manual Document No 680 015 3 3 10 Passwords The panel provides up to 10 User Level 2 passwords and 2 Level 3 passwords All of the passwords can be chang
65. the panel Always ensure that all segments of the cable loop have continuity of the screen and take care to ensure that the screen is not exposed to any other earth point e g metalwork cable trays junction boxes etc 9 When screened cable is used it is vital to connect the screen to the chassis earth at the cable 2 4 5 Relay Circuits Fault Output Relay 1 is arranged for failsafe operation as standard The panels are equipped with two relay outputs These are normally programmed to activate on Fault and Fire Alarm conditions respectively RELAY 2 RELAY 1 OOO Each output is unsupervised with volt free changeover Oe contacts rated at 30V AC DC 1 Ampere Optional relay cards are available if additional relays are required BILAO Base card arrangement typical Document Reference 680 014 Author RFM4100 18 of 53 2 4 6 Open Collector Outputs The Mx 4100 Mx 4200 amp Mx 4400 are equipped with two open collector type outputs that can sink up to 10mA each from the AUX Power Output These are fully programmable and can be used to control external relays The connections of the base card are shown in the diagram opposite No external back emf diodes are required The Mx 4200 amp Mx 4400 are equipped with a further six digital programmable outputs via a 10 pin connec
66. tor see opposite 24VDC and the Open Collector outputs are also available on this connector An optional 8 way relay card is available to connect to this connector 2 4 7 Auxiliary Supply Output All panels are equipped with an auxiliary 24V DC 300mA power supply output for powering external O C1 DRIVE AUX 24V AUX 24V O C2 DRIVE Base Card Connections Typical O C1 DRIVE O C2 DRIVE OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8 AUX 24V AUX 24V L Base Card Connections Mx4200 amp Mx 4400 Base Card Connections equipment such as the MX series remote terminals BAT BAT AUX GND AUX 24V AUX GND AUX 24V FS2 BAT FSI Supply Mx 4100 0000 Mx 4200 4400 Document Reference 680 014 Author RFM4100 19 of 53 2 4 8 RS232 Interface The Mx 4100 is equipped with a non isolated RS232 I F Circuit at the bottom left hand side of the base card The Mx4200 amp Mx 4400 are equipped with an isolated RS232 I F Circuit at the bottom of the base card The terminal block connections are shown opposite TX Transmit Data from the pa
67. ve normal fire coverage Document Reference 680 014 Author RFM4100 31 of 53 3 3 6 Outputs The Cause and Effect programming is a schedule of actions that will turn on one or more outputs dependant on a set of input events The Outputs Option provides the means to create simple or complex cause and effect programming within the panel Delays can be introduced to allow a phased evacuation of a building Note this is different to an Investigation Delay which is detailed in section 3 3 7 This section describes the settings and options in detail for each parameter Refer to Appendix 4 Cause and Effect Programming Example for a description of how to program a typical requirement More complex Cause and Effect programming may be undertaken using the PC Configuration tool When the OUTPUTS Option is selected the display shows the cause and effect programming for Output Group 1 For example tput Group 1 3 9 Mem used GROUP CAUSE STYLE Delay gt MODE ANY FIRE 00 1 ANY FIRE 1 ANY FIRE 1 ANY FIRE Ei e e To simplify the cause amp effect programming one or more outputs that will respond in the same way when the same set of input events occurs can be grouped together This association of outputs is called an Output Group The panel can support up to 200 of these Output Groups To select a different Output Group highlight any group nu

Download Pdf Manuals

image

Related Search

Related Contents

MaxxAir XXCRADLEEXT Instructions / Assembly  三重県立総合医療センター各種電源一部改修工事 地方独立行政法人  Swingline GBC UltraClear  Picosun Atomic Layer Deposition  Power Station PS-300  2 - Kenntnis des Fahrzeugs  Innovaphone IP0010  Untitled  Samsung WB210 Manual de utilizare  

Copyright © All rights reserved.
Failed to retrieve file