Grid Automation Controller COM600 4.0 IEC 61850 Proxy Server
Contents
1. 05 Ba Copy Data objects RCE Report Control Block Li REA El ras Delete GOOSE b p DB DS a creating_dataset png Figure 3 4 6 1 Creating a new data set 2 Modify the data set to be sent with GOOSE n Normally GOOSE data sets are configured to the attribute level and only the value and quality are used e g Pos stVal and Pos q Use the Enable daName for GOOSE option and manually remove the unnecessary attributes from the data set dsGOOSE Dataset Editor rv dbx _ Idlnst prefix Inlnst InClass doName fe daName REX521_101 CB 120 Pos sal REX521_101 CB 120 Pos q REX521101 ESW 127 Pos stal lb REX521101 ESW 127 Pos q IM Enable dallame for GOOSE Apply Cancel modifying_dataset png Figure 3 4 6 2 Modifying the data set to be sent with GOOSE 3 Create a new GOOSE Control Block GoCB 26 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual IEC61 850_Proxy_Server_OPC_Client GG lEC61850ProxySubnetwork IEC61850ProxylED n LD LDO LD REX_521_101LD1 LN Gast INC Collapse INS INS New is Cut Communication Ds Copy Data objects RCE E Delete Goose Control Block ES RCE Rename DS REE Properties gt creating_gcb png Figure 3 4 6 3 Creating GOOSE Control Block Configure the GOOSE control block see Figure 3 4 6 4 e S
2. ml IEC 61850 Network COM600 with m i T IEC 61850 TUE ons od det Proxy Server IEC 61850 IEDs Non IEC 61850 IEDs IEC61850 Proxy Server Functional Overview PNG Figure 2 1 1 Functional overview of IEC 61850 Proxy Server IEC 61850 Proxy Server enables IEC 61850 8 1 MMS clients to access data and services of COM600 It also features a GOOSE send functionality for publishing data With these features it is possible to connect non IEC61850 IEDs to the IEC 61850 network via COM600 Also calculated data from COM600 e g from logic processor can be published to IEC61850 network using the IEC 61850 Proxy Server IEC61850 Proxy Server is configured using the Proxy Configuration tool in SAB600 The Proxy Configuration tool shows a list of IEDs and their logical devices that are configured to COM600 You can select which of them will be added to the IEC61850 Proxy Server configuration As the COM600 native data model is according to the IEC 61850 standard complicated cross reference configuration is not required You can later adjust the data set and reporting configuration The IEC 61850 Proxy Server configuration is stored into an SCL file which is loaded to the COM600 The configuration can also be exported to an SCL SCD file which can be used for the IEC 61850 client configuration When the IEC 61850 Proxy Server is started it first reads and parses the SCL configur ation It creates the IEC 61850 data model according to the SC
3. Para Value or Value range Default Description meter Addresses 29 Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual Property Para Value or Value range Default Description meter IP Address Default 127 0 0 1 Communication IP address in dotted decimal format not configurable OSI ACSE AE Default 23 ACSE protocol level configuration para Qualifier meter AE Qualifier OSI ACSE AP Title Default 1 3 9999 23 ACSE protocol level configuration para Value meter AP Title OSI Presentation Default 00000001 ACSE protocol level configuration para Selector meter Presentation selector OSI Session Default 0001 ACSE protocol level configuration para Selector meter Session selector OSI Transport Default 0001 ACSE protocol level configuration para Selector meter Transport selector 3 5 5 Configuring IEC 61850 Proxy Device properties IEC 61850 Proxy Device does not have any configurable properties 30 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 4 1 4 2 4 3 4 3 1 4 3 1 1 Operation About this section This section describes the basic operation procedures you can carry out after the IEC 61850 Proxy Server object properties have been configured After this you can for example monitor and control the condition of connections in the Proxy Subnetwork This is done
4. OK 2010 12 30 19 36 12 281 System Message OPC Data Change LON_Channel REX521_101 LD1 CBCSW1120 Pos stVal 1 2010 12 30 19 36 12 296 System Message OPC Data Change LON_Channel REX521_101 LD1 CBCSW1120 Pos stSeld FALSE 2010 12 30 19 36 59 265 System Message OPC Data Change SPA_Channel REX521_202 LD1 CBCSW1I120 Pos stVal 1 2010 12 30 19 37 32 296 System Message OPC Data Change SPA_Channel REX521_203 LD1 RREC80 AutoRecStst al 1 a Proxy_diagnostic_AE_client png Figure 4 3 1 2 1 IEC 61850 Proxy Server Diagnostic AE client 4 3 2 IEC 61850 Proxy IED 4 3 3 Online diagnostics The IEC 61850 communication activity can be monitored with the Online diagnostics function see Figure 4 3 3 1 e Inthe Status information field you can monitor the device status e Inthe Diagnostic counters field you can monitor the communication activity The available attributes can be seen in Figure 4 3 3 1 To reset Diagnostic counters click Reset counters e To take the IEC 61850 communication into use select the In use checkbox To take the communication out of use clear the checkbox e Diagnostic counters are updated every 2 seconds To update them manually click Refresh 33 Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual 34 v JA Diagnostic events enabled IED_online_diagnostics png Figure 4 3 3 1 IEC 61850 Proxy IED online diagnostics 1MRS757275 Grid Automation Cont
5. Proxy Server with Proxy Configuration Tool n Before configuring Proxy IEC 61850 Proxy Server an OPC server handling the IED communication needs to be configured to the communication structure To configure IEC 61850 Proxy Server with the Proxy Configuration Tool 1 Right click the IEC 61850 Proxy Server OPC Client object and select Proxy Config Tool Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual 3 4 3 4 1 3 4 2 3 4 2 1 2 Select the check boxes in the first column to add LDs to the IEC61850 Proxy Server OPC Client configuration 3 Click Apply to create the configuration with the selected IEDs to the communication structure 1EC61850 Proxy Server O lient Proxy Config Tool Include IED Path LDCaption LON OPC SALON ChannelkREX 521 101ALD1 REX_521_101LD1 LON_OPC_S LON_Channel REX_521_1024LD1 REK 521 102LD1 LON OPC SALON ChannelRE2 521 104ALD1 REX_521_103LD1 SPA_OPC_SASPA ChannelREX_521_2014LD1 REX 521 201LD1 SPA_OPC_SASPA ChannelREX_521_2024LD1 REX 521 202LD1 SPA_OPC_SASPA_ ChannelREX_521_2034LD1 REX_521_203LD1 Apply Cancel Proxy_config_tool png Figure 3 3 3 1 Proxy Configuration Tool The Proxy Configuration Tool includes the following columns e Include specifies if the LD is part of the Proxy configuration IED Path the OPC path of the selected LD LD Caption specifies the name of the re
6. TP o JM SUPPORTED Baa ME paras Ee EE AE SU SUBEORTED Setting group control J si Saleciacmeso te o o sis seecediss me lo eo sa sescvemes te JO lo sai Conimeciscvales TP lo lo s22 cerscvaws mr lo lo s23 esscc vames mw lo Jo Reporting 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual S24 1 data change dchg S24 2 qchg change qchg S24 3 data update dupd 25 GetBRCBValues TP o SUPPORTED SUPPORTED U S26 SetBRCBValues Unbuffered report control block URCB S27 Report S27 1 data change dchg TP O SUPPORTED S27 2 qchg change qchg S27 3 data update dup S28 GetURCBValues TP TP O SUPPORTED S29 SetURCBValues SUPPORTED o Logging Logging control block S30 GetLCBValues U S31 SetLCBValues o Q TU 4 TU 32 QueryLogByTime S33 QueryLogByEntry S34 GetLogStatusValues N 4 U N o Generic substation event model GSE GOOSE CONTROL BLOCK S35 SendGOOSEMessage S36 GetReference M O Co Co SUPPORTED l U S37 GetGOOSEElementNumber TP 38 GetGoCBValues U 4 Q Q o o Q Q Q Q Q S39 SetGoCBValues GSSE CONTROL BLOCK S40 SendGSSEMessage S41 GetReference Q 00 1 M U O 1 Services AA Client Sub Server Pub Value Comments TP MC scriber lisher Buffered rep
7. True E Misc Caption tcbD ata Description Report Control Block Caption data_set_properties Figure 3 4 4 4 Data set properties GOOSE messaging The generic object oriented substation event GOOSE is used in substation automation for fast horizontal communication between IEDs It can be used to exchange for example interlocking and blocking information The information is shared from one IED to one or several IEDs using Ethernet multicast messages A message is an image of a sent MMS data set that is defined in the CID configuration IEC61850 Proxy Server supports sending of GOOSE messages The receiving of GOOSE messages is handled by the IEC 61850 OPC Server The GOOSE data is sent periodically in 802 1Q multicast frames over the local network When data changes the GOOSE frame is sent several times in a fast cycle to prevent data losses In GOOSE the sent data is based on the data set and GOOSE Control Block GoCB The data set defines what type of data is sent in the GOOSE frame GoCB links the GOOSE Control Block structure and its information to the data Table 3 4 5 1 lists the configurable GoCB object properties 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 3 4 6 Table 3 4 5 1 GoCB object properties Property Parameter Value or value range Default Description Configuration Revision Configuration Revision identi fies the version of GoCB Data Set D
8. function Terminology Term Description Alarm An abnormal state of a condition Alarms and Events AE An OPC service for providing information about alarms and events to OPC clients Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual Term Data Access DA Data Object DO Data Set Device Event Intelligent Electronic Device Logical Device LD Logical Node LN LON LON Application Guideline for substation automation LAG OPC OPC item Property Report Control Block SPA SPA device Substation Configuration Lan guage SCL Description An OPC service for providing information about process data to OPC clients Part of a logical node object representing specific information for example status or measurement From an object oriented point of view a data object is an instance of a class data object DOs are normally used as transaction objects that is they are data structures The data set is the content basis for reporting and logging The data set contains references to the data and data attribute val ues A physical device that behaves as its own communication node in the network for example protection relay Change of process data or an OPC internal value Normally an event consists of value quality and timestamp A physical IEC 61850 device that behaves as its own commu nication node in the IEC 61850 protocol Repr
9. one BRCB or URCB c7 shall declare support for at least one QueryLogB y Time or QueryLogByEntry c8 shall declare support for at least one SendGOOSEMessage or SendGSSEMessage c9 shall declare support if TP association is available c10 shall declare support for at least one SendMS V Message or SendUSV Message 5 2 SCL conformance 5 2 1 SCL conformance statement The SCL conformance statement defines several degrees of conformance for which implementations may declare support of the substation configuration language 1 Table 5 2 1 1 SCL conformance degrees SCL Conformance pas Server SCL 1 SCL File for Imple mentation Available TED offline SCL 2 SCL File available from implementation online SCL 3 SCL implementation O O O O reconfiguration sup ported online 5 3 PICS protocol conformance statement 5 3 1 Profile conformance Table 5 3 1 1 and Table 5 3 1 2 define the basic conformance statement 41 Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual 5 3 2 42 Table 5 3 1 1 PICS for A Profile support Client Server Value Comment A2 GOOSE GSE Management c2 c2 SUPPORTED A Profle CE CE EC A CE A A4 TimeSync A Profile c4 c4 cl shall be m if support for any service specified for Client S are declared within the ACSI basic conformance statement c2 shall be m if sup
10. orldent 495454 2010 12 30 19 36 11 421 System Message MMS Write REX521_101LD1 CBCSWI120 CO Pos SBOw ctINum 770 Clear 2010 12 30 19 36 11 421 System Message MMS Write REX521_101LD1 CBCSWI120 CO Pos SBOw T 17 36 11 2010 12 30 19 36 11 421 System Message MMS Write REX521_101LD1 CBCSW11 20 CO Pos SBOw T est 0 Reconnect 2010 12 30 19 36 11 421 System Message MMS Write REX521 101LD1 CBCSWIT20 CO Pos SBOW Check 3 2010 12 30 19 36 11 421 System Message OPC Write LON Channel REX521 101 LD1 CBCSWI120 Pas ctSelDf 1 OK M Active 2010 12 30 19 36 11 421 System Message OPC Data Change LON_Channel REX521_101 LD1 CBCSW1120 Pos stSeld TRUE 2010 12 30 19 36 12 281 System Message MMS Write REX521_101LD1 CBCSw1120 C0 Pos Oper ctial 0 IV Auto scroll 2010 12 30 19 36 12 281 System Message MMS Write REX521_101LD1 CBCSWI1 20 CO Pos Oper origing orCat 2 2010 12 30 19 36 12 281 System Message MMS Write REX521_101LD1 CBCSWI1 20 CO Pos 0per origingorldent 495454 Export 2010 12 30 19 36 12 281 System Message MMS Write REX521 101LD1 CBCSWI120 CO Pos Oper ciNum 2 2010 12 30 19 36 12 281 System Message MMS Write REX521_101LD1 CBCSWI120 CO Pos Oper T 17 36 12 2010 12 30 19 36 12 281 System Message MMS Write REX521_101LD1 CBCSw1120 C0 Pos Oper T est 0 2010 12 30 19 36 12 281 System Message MMS Write REX521_101LD1 CBCSWI120 CO Pos Oper Check 3 2010 12 30 19 36 12 281 System Message OPC Write LON Channel REX521_101 LD1 CBCSW1120 Pos ctlOperOff 1
11. to a third party nor used for any unauthorized purpose The software or hardware described in this document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license O Copyright 2012 ABB All rights reserved Trademarks ABB is a registered trademark of ABB Group All other brand or product names men tioned in this document may be trademarks or registered trademarks of their respective holders General This manual provides thorough information on the IEC 61850 Proxy Server and the central concepts related to it You find instructions on taking it into use The basic operation procedures are also discussed Information in this user s manual is intended for application engineers who configure the IEC 61850 Proxy Server OPC Client to establish communication to an OPC server As a prerequisite you should understand IEC 61850 protocol and the basic procedures in Station Automation Builder 600 later referred to as SAB600 This user s manual is divided into following sections Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual 1 4 Introduction This section gives an overview of the IEC 61850 Proxy Server and its features Configuration In this section you find an overview of the configuration tasks and instructions on how to create and configure IEC 61850 Proxy Server OPC Client related objects Operation This section
12. 3 5 Technical references es Si ed sed ee ds eN ae Gidse de de ee doive deed 35 5 1 ASCI conformance statement es ee ee ee ee ee ee ee ee 35 5 1 1 ACSI conformance statement uu ee ee ee Ee 35 5 1 2 ACSI basic conformance statement cce 35 5 1 3 ACSI models conformance statement 36 5 1 4 ACSI service conformance statement ee 37 5 2 SCL conformant iii dd 41 5 2 1 SCL conformance statement ee ee ee ee eens 41 5 3 PICS protocol conformance statement ee ee 41 5 3 1 Profile conformance ees ees se ee ee ee ee Re ee ee ee ee ee 41 5 3 2 MMS Conformance iii 42 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 1 1 1 2 1 3 About this manual Copyrights The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy ABB Oy assumes no responsibility for any errors that may appear in this document In no event shall ABB Oy be liable for direct indirect special incidental or consequential damages of any nature or kind arising from the use of this document nor shall ABB Oy be liable for incidental or consequential damages arising from use of any software or hardware described in this document This document and parts thereof must not be reproduced or copied without written per mission from ABB Oy and the contents thereof must not be imparted
13. 50 7 2 0 2147483647 report_control_block_properties png Figure 3 4 3 2 1 Report control block properties Table 3 4 3 2 1 Report Control Block object properties Property Parameter Value or value range Default Description Basic 19 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 1MRS757275 Property Parameter Buffer Time Buffered Configuration Revision Data Set Indexed Integrity period Report ID Option Fields Config Reference Value or value range Default Default 0 milliseconds True False Default True 0 2147483647 True False Default True 0 214748647 Default 0 True False Default False Description With this value RCB can be configured to wait for other events after the first change before sending the report Value 0 means that a new change is immediately reported to the client Configurable Controls if the RCB is buffered or unbuffered Configuration revision of the data set referenced by this RCB Every modification in the data set increases the Configur ation Revision property by one The name of the data set to be sent by the report control block Indicates if this RCB is con figured with indexed naming convention Integrity period in milliseconds If this attribute has a value gt 0 ms an integrity report with all data listed in the data set is sent periodically in
14. Class gt lt Dataset gt The data set identifies the data set to be created LNClass and DO are used to determine which LN DOs should be added to the dataset For example lt DataSet name StatNrml gt lt LNClass name GGIO gt lt DO cdc SPS name Alm gt lt LNClass gt lt LNClass name PHAR gt lt DO cdc ACD name Str gt lt LNClass gt The StatNrml data set contains all Alm named SPS typed DOs under GGIO LNClass and all str named ACD typed DOs under PHAR LNClass and so on Additional signals can be added to each data set by dragging and dropping the DO object to the Dataset Editor tool and applying changes The data sets for GOOSE have to be created manually To create data sets for GOOSE 1 Create a Dataset object to the tree under the LNO object 2 Right click the Dataset object and select Dataset Editor 3 If you are creating a GOOSE data set select the Enable daName for GOOSE checkbox 4 Drag and drop DO objects from the object tree to the Dataset Editor 5 Click Apply Data reporting About data reporting Data changes are used as a trigger for reporting This information is grouped using a data set The data set is the content basis for reporting Reporting uses information reports to transmit data The data configured in a data set is transmitted in information reports Reporting is controlled by report control blocks 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Prox
15. D DO GW HMI IEC IED LAG LAN LD LN NCC NV OLE OPC P amp C RTS SA SAB600 SCL SLD SNMP SNTP SOAP RCB URCB XML Description Alarms and Events Application Service Data Unit Buffered Report Control Block Data Access Data Message Code Definition Data Object Gateway component connecting two communication networks together Human Machine Interface International Electrotechnical Commission Intelligent Electronic Device LON Application Guideline for substation automation Local Area Network Logical Device Logical Node Network Control Center Network Variable Object Linking and Embedding OLE for Process Control Protection amp Control Request To Send Substation Automation Station Automation Builder 600 Substation Configuration Language Single Line Diagram Simple Network Management Protocol Simple Network Time Protocol Simple Object Access Protocol Report Control Block Unbuffered Report Control Block eXtended Markup Language Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 1 8 1 9 Related documents COM600 User s manual 1MRS756125 Document revisions Document version date A 30 6 2011 B 31 5 2012 Product revision History 4 0 Document revised 1MRS757275 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 2 1 Introduction Functional overview IEC 61850 MMS Client
16. EE Ge crie DER EE Ee EER service contormance a dada adding IEC 61850 Proxy Server OPC Client B building objectitre ii ie Ee tacita cialis IEC 61850 Proxy Server OPC Client eie ee ee ke ee ee ee AR Ge ee RR ee ee ee ee AR ee ee Re ee ee ee configuring GOOSE ee di ie EE Aa IEC 61650 Proxy IED RR NE EE ER N RE EE OO el IEC 61850 Proxy S ubnetWork 2 38 ruine dog be dona Ge ee Ga GP Ese diet ole AE AR AR N EE OVEIVICW Es ne dd EA delete OO NE EL EE IE EE EE D data rePOrting ceed RE TAE E eg fants ter eet daa IA eel elke ie Me AE EE RO EO AE EE report control bloek idees EE Ee ee Ge Ee At ge RE eg nas de bee ge sac data set oes cos ten SE EA ES oen DS EE tance AD ea ee DE ES ER AE EE CONTIQUIIN seis tree re ee Manet nn arid de ooie ma EE RE N EE 18 Dataset EdilOF 2e ER Ee Ee SE DE EEEE Ge DR De Se EE SR Ee EE ee ee diagnostuciAE clients De ia DE te AR nent Ge eg F features si O EE a EG SE EG Ge ee GOOSE oe eg Ee GE Eg A AE GE De DUBIISHING EE ME RE EE EE ERA OER N EER ain 45 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 1MRS757275 46 IEC 61650 Proxy Server sites dant tl de features interne dl a ee IEC 61850 Proxy Server OPC Client adding is EE EE EE ME O object CONMIQUrINQ ada online diagnostics oessa riirii ee Re iin ee nn ee ee ee ke EKn P Proxy Configuration Tool ie ee ee ee RR Ee ee ee RR ee ee ee ee ee R report contro
17. IEC 61850 Proxy Server User s Manual Power and productivity for a better world 1MRS757275 Issued 30 06 2011 Version B 31 5 2012 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual Contents 1 About this manual s s KEER EKEN Ge EKKE ac 5 th Copyrights erse ME EF 5 12 TradeniarKS ss AE O E ei 5 13 Or 5 14 Document Conventions ii ER ER RR ee ee ee Re ee ee ee 6 1 5 Lise Bi symbols SEE ERGE RE Pron gh ica 7 16 o O ROA 7 1 7 Abbreviations iii ana 9 1 8 Related documents viii li 10 1 9 Document revisions ke ek ede ee 10 2 INTRODUCTION 3 sien sede Ee dee RE DE ees Ee eN oe ei de Ee de PEN ee ge daane eken 11 2 1 Functional overview ee RE eek ede ee 11 2 2 IEC 61850 Proxy Server features 12 3 Configuration messe ek Ve de ede VR AR Ee ii een r een ee te de Pe eN DA 13 3 1 About this SectiON ee ee ee RA Re RA AA Re ee aE ee 13 3 2 Overview of configuration esse ee ee ee ee ee 13 3 3 Building object te EE SR EE AE ESE ed 15 3 3 1 General about building object tree esse ee 15 3 3 2 Adding IEC 61850 Proxy Server OPC Client object 15 3 3 3 Configuring IEC 61850 Proxy Server with Proxy Configuration Tool sie SEE EER ER died 15 3 4 IEC 61850 data publishing issie eise sees see ie eu Se eye
18. L and establishes connec tions to the related COM600 OPC servers It initiates a refresh for the OPC servers to update all configured data After the data is received the IEC 61850 Proxy Server has Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual 2 2 up to date data from the underlying process and the IEC 61850 server is started The IEC 61850 Proxy Server starts normal operation During normal operation the actions for the IEC 61850 Proxy Server are initiated by IEC 61850 service request from an IEC 61850 client or by data updates from the connected OPC servers IEC 61850 Proxy Server features The IEC 61850 Proxy Server supports the following features OPC Data Access v1 0 2 0 client for process data server for diagnostics OPC Alarms and Events specifications v1 10 server for diagnostics IEC 61850 server e TEC 61850 data modeling IEC 61850 buffered and unbuffered reporting services e IEC 61850 control services IEC 61850 GOOSE send service One instance of IEC 61850 Proxy Server can be configured per COM600 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 3 1 3 2 Configuration About this section This section guides you in the configuration tasks required before you can start using the IEC 61850 Proxy Server For information on the IEC 61850 data modeling refer to COM600 User s Manual 1 Select File gt Open Manage
19. Project In the Open Manage Project dialog select the required location for the project e Projects on my computer e Projects on network 3 Select New Project on the left Enter a Project Name The Description is optional 4 Click Create 5 Click Open Project Overview of configuration Before you can start using the IEC 61850 Proxy Server you need to build and configure an object tree in SAB600 to define the communication structure Start the configuration by first configuring an OPC Server for example LON OPC Server Then continue to configure the IEC 61850 Proxy Server For information on configuring the OPC Server see the related configuration manual Figure 3 2 1 shows an example view of SAB600 including an object tree in the commu nication structure on the left and Object Properties window displaying the object properties on the right Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual n When configuring OPC servers the following characters cannot be used in object names Also avoid using a space in object names EM Local Server ProxyExample Station Automation Builder 600 ioj x DORIA Project Explorer Eile Edit View Tools Window Help Object Properties v x Comm
20. _Client y y lEC61850ProxySubnetwork F lEC61850ProxplED LO LDO LO REX_521_101LD1 LN ING Collapse INS INS Cut Communication gt se pS Ea Copy Data objects Report Control Block RCE t gl Delete GOOSE EE RCE Rename Properties creating_rcb Figure 3 4 4 2 Creating a new report control block 3 Adda Report Enabled object Add a ReportClient object for each IEC 61850 client ReportClients create the same amount of instances of the RCB each dedicated for one client DS dsData RCE rcbData RCE Report Enabled ReportClient1 ReportClient2 ReportClient3 ReportClient4 ReportClients ReportClient Figure 3 4 4 3 Adding ReportClient objects 4 Configure the report control block 5 Configure the data set of the report control block 23 Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual 3 4 5 24 Object Properties RR Ef E 010 Basic Buffer Time 100 Buffered True Configuration Revision 2 Data Set dsData indexed True Integrity period 0 Report ID E 010 Option Fields Config Reference False Data Ref False Data Set False Entry ID True Reason Code True Sequence Number True Time Stamp False E 010 Trigger Options Data Change True Data Update False Period False Quality Change
21. able 5 1 3 1 ACSI models conformance statement Client Sub Server Pub Value Comments scriber lisher If Server side B1 supported are DE ES CC ne Seting soup conver fo fo CE DNE M8 5 data reference 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual Client Sub Server Pub Value Comments scriber lisher ew p p f C sesse M17 File Transfer O O c1 shall be M if support for LOGICAL DEVICE model has been declared c2 shall be M if support for LOGICAL NODE model has been declared c3 shall be M if support for DATA model has been declared c4 shall be M if support for DATA SET Substitution Report Log Control or Time model has been declared c5 shall be M if support for Report GSE or SMV models has been declared M Mandatory 5 1 4 ACSI service conformance statement The ACSI service conformance statement shall be as defined in Table 5 1 4 1 depending on the statements in Table 5 1 3 1 37 38 Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual Table 5 1 4 1 ACSI service Conformance statement Services AA Client Sub Server Pub Value Comments TP MC scriber lisher ENE EN E R J I ME TE Application association ape JM mw SUPPORTED E A gt e PAR 4 e O A CR ER palas NEE EE s5 SO e EEE s6 TOR s7 esislsisvauss
22. able attribute or updat ing the value of any other attribute An updated value may have the same value as the old value Specifies whether a report entry shall be generated on the expiration of the integrity period 21 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 1MRS757275 3 4 4 22 Property Parameter Quality Change True False Default True Value or value range Default Description Specifies whether a report entry shall be generated due to a change of the value of the quality attribute Configuring reporting n Reporting is preconfigured automatically Data sets for necessary data are created and linked to configured report control blocks To configure reporting 1 Create and configure a Data Set object IEC61 850_Proxy_Server_0 PC_Client Ee TH lEC61850ProxySubnetwork F JEC61850ProxplED LD LDO E LD REX_521_101LD1 a im INC Collapse INS INS LPL Cut SPS os Ba Copy eS REE T Delete ER REE Rename DS HAN REE Properties eo Figure 3 4 4 1 Creating a new data set 2 Create a Report Control Block object Communication gt Data Set Data objects REE Report Control Block GOOSE creating_dataset 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 1EC61850_Proxy_Server_OPC
23. ata Set Data set to be sent in GOOSE Default None GSEType Default GOOSE GSEType identifies the type of GSE Element in configuration file read only parameter APPID 0000 3FFF Application ID for the GOOSE control block hex value Default 0000 GolD Default GOOSE control block String identifier for the GOOSE path control block Max Time 0 65535 Supervision heartbeat cycle time ms Default 10000 Min Time 0 65535 Maximal sending delay ona data change ms Default 2 Multicast Address 01 0C CD 01 00 00 to 01 0C A multicast addressing scheme CD 01 01 FF is used when sending GOOSE messages A multicast address Default 01 OC CD 01 00 00 can be shared by several sending devices or it can be IED specific VLAN ID 000 FFF VLAN ID hex value Default 000 VLAN Priority 0 7 VLAN Priority Default 4 Configuring GOOSE publishing To send GOOSE data you must first define the sending data set used by the GOOSE control block and then create the control block 1 Create a new Data Set Rename it if you plan to use several different sets of data see 3 4 2 1 Dataset Editor 25 Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual B IEC61 850_Proxy_Server_OPC_Client El Gq lEC61850ProxySubnetwork E 1EC61850ProxylED HI LD LDO E LD REX_521_101LD1 ee LN EF i me Collapse INS INS lt Communication gt Lune SPS
24. by using the Online diagnostics function in SAB600 Activating COM600 with new configurations For information about activating COM600 with new configuration see COM600 User s Manual Diagnostics IEC 61850 Proxy Server OPC Client Online diagnostics To view version information on IEC 61850 Proxy Server Client or to monitor and control the state of the client right click the IEC 61850 Proxy Server OPC Client and select Online diagnostics 31 Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual 4 3 1 2 32 Proxy_online_diagnostics png Figure 4 3 1 1 1 IEC 61850 Proxy Server Online diagnostics In Online diagnostics dialog box you can e reset the IEC 61850 Proxy Server OPC Client e view the event log file clear the event log file Diagnostic AE client Diagnostic events can be monitored and controlled using the Diagnostic AE Client function see Figure 4 3 1 2 1 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 1EC61850 Proxy Server O ient Diagnostic AE client vr dpx Event count 21 Time Type Source Message Refresh 2010 12 30 19 36 11 421 System Message MMS Write REX521_101LD1 CBCSWI1 20 CO Pos SBOw ctlal 0 2010 12 30 19 36 11 421 System Message MMS Write REX521_101LD1 CBCSWI120 CO Pos SBOw origingorCat 2 Settings 2010 12 30 19 36 11 421 System Message MMS Write REXS21 101LD1 CBCSWIT20 CO Pos SBOw origin
25. covers the basic operation procedures you can carry out when transferring or activating Grid Automation Controller COM600 later referred to as COM600 with new configurations You are also given instructions on how to monitor and control the IEC 61850 Proxy Server OPC Client Technical reference This section contains a list of status codes and attributes Document conventions The following conventions are used for the presentation of material The words in names of screen elements for example the title in the title bar of a window the label for a field of a dialog box are initially capitalized e Capital letters are used for the name of a keyboard key if it is labeled on the keyboard For example press the ENTER key e Lowercase letters are used for the name of a keyboard key that is not labeled on the keyboard For example the space bar comma key and so on e Press CTRL C indicates that you must hold down the CTRL key while pressing the C key to copy a selected object in this case e Press ESC E C indicates that you press and release each key in sequence to copy a selected object in this case The names of push and toggle buttons are boldfaced For example click OK The names of menus and menu items are boldfaced For example the File menu e The following convention is used for menu operations MenuName gt Menu Item gt CascadedMenultem For example select File gt New gt Type The Start menu name alwa
26. eed Ge ke 16 DAT Aboutdata SOLS ati 16 3 4 2 Configuring data Sets esse ee ee ee RR Re ee ee 16 3 4 2 1 Dataset Editor 16 34 3 Data reporting mann ii 18 3 4 3 1 About data reporting 18 3 4 3 2 Report control block o ccccccccccccccnos 19 34 4 Configuring reporting 4 444444 22 34 5 GOOSE MESSAGING es ee cited 24 3 4 6 Configuring GOOSE publishing 25 3 5 Configuring ODE EER id tre ent 28 3 5 1 General about configuring objects 28 3 5 2 Configuring IEC 61850 Proxy Server OPC Client 28 3 5 3 Configuring IEC 61850 Proxy Subnetwork 29 3 5 4 Configuring IEC 61850 Proxy IED eeen 29 3 5 5 Configuring IEC 61850 Proxy Device properties 30 RP n EE ES 31 4 1 About this section nano 31 4 2 Activating COM600 with new configurations 31 Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual 2 93 A EA DE OR AE AR EE 31 4 3 1 IEC 61850 Proxy Server OPC Client ees sees ee 31 4 3 1 1 Online diagnostics 31 4 3 1 2 Diagnostic AE client esse ee ees ooo 32 4 3 2 IEC 61850 Proxy lED SE Ge ee VR mano 33 4 3 3 Online diagnostics coco EER SEE RE SEG DE tete 3
27. elect the created data set Define APPID Application Identifier which is unique within the system It identifies the purpose of this particular dataset Define a multicast address to which the specific GOOSE data is sent The receiving IED understands which frames with a specific multicast address are the interesting ones and starts to process them Object Properties v A x IE E 010 Basic Configuration Revision 2 Data Set dsGoose GSE Type GOOSE E 080 Goose Address APPID 0000 GolD IEC61850ProxylEDREX521_101LD1 LLNO GO Goose Control Block Max Time 10000 Min Time 100 Multicast Address 01 0C CD 01 00 00 VLAN ID 000 VLAN Priority 4 El Misc Caption gcbGoose Description Goose Control Block Data Set Dataset to be sent in GOOSE GOOSE_control_block_properties Figure 3 4 6 4 GOOSE Control Block properties 27 Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual 3 5 3 5 1 3 5 2 28 Configuring objects General about configuring objects After the objects have been added configure the object properties Figure 3 5 1 1 shows an example of how to use SAB600 to configure the object properties for IEC 61850 Proxy Server OPC Client To configure an object 1 Select an object in the object tree of the communication structure The object prop erties appear in the Object Properties window The properties and their values can be viewed as shown in Fig
28. esentation of a group of functions Each function is defined as a logical node A physical device consists of one or several LDs The smallest part of a function that exchanges data An LN is an object defined by its data and methods A communication protocol developed by Echelon A proprietary method of ABB on top of the standard LON pro tocol Series of standards specifications aiming at open connectivity in industrial automation and the enterprise systems that support industry Representation of a connection to the data source within the OPC server An OPC item is identified by a string lt object path gt lt property name gt Associated with each OPC item are Value Quality and Time Stamp Named data item The report control block controls the reporting processes for event data as they occur The reporting process continues as long as the communication is available ABB proprietary communication protocol used in substation automation Protection and or Control Product supporting the SPA protocol version 2 5 or earlier XML based description language for configurations of electrical substation IEDs Defined in IEC 61850 standard 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 1 7 Abbreviations The following is a list of abbreviations associated with COM600 that you should be familiar with See also 1 6 Terminology Abbreviation AE ASDU BRCB DA DMC
29. ferenced LD in the Proxy configuration IEC 61850 data publishing About data sets A data set is an ordered group of data objects and data attributes organized as a single collection for the convenience of the client Data sets are used to define the values of data to be transmitted in case a value of a data set member changes A data set is used for reporting and GOOSE messaging Configuring data sets Dataset Editor A data set groups selected data so that a client can access it easily with a single read operation A data set is also used for event reporting data is linked to spontaneous event sending only via report control blocks RCB data set definition The client reads other data separately Data set definitions are located always under the logical device LDO and logical node LLNO 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual The data set can be modified with the Dataset Editor Open the Dataset Editor by right clicking the Dataset object and selecting Dataset Editor The Dataset object has a set of data attributes IdInst Instance of Logical Device to which the referenced data set belongs e Prefix Freely configurable part of LN caption e InInst Instance of the LN type e InClass Logical node class e doName Name of the data object from which the data set is formed daName Name of the data attribute from which the data set is formed Data attributes are co
30. l DOCK vices EER EE ad dress nantes S SGL coniermahee ad MERE Ee eh GR ged ae Ee Contact us ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA FINLAND Tel 358 10 22 11 Fax 358 10 224 1094 ABB Inc Distribution Automation 655 Century Point Lake Mary FL 32746 USA Tel 1 407 732 2000 Fax 1 407 732 2335 www abb com substationautomation Power and productivity for a better world 1MRS757275 B 31 5 2012 Copyright 2012 ABB All rights reserved AA ED ED FADED
31. llected to the data set in groups and the functional constraint defines the data attributes e fc functional constraint Functional constraint divides data attributes which have the same functional con straint to groups under the same data object For example functional constraint ST status information groups stVal q and t data attributes to the data set The caption in the object tree consists of Prefix InClass and InInst values StatUrg Dataset Editor vabx ldinst prefix Ininst InClass doName REX521_101 LLNO Mod REX521_101 LLNO Beh REX521_101 LLNO Health REX521_101 LLNO Loc REX521_101 CB CSwl Pos REX521_101 LPHD Indy REX521 101 ESw Kw BlkOpn REX521_101 ESW SW BIkCIs Enable daName for GOOSE Apply Cancel Figure 3 4 2 1 1 Dataset Editor Dataset_editor png Creating data sets If 61850 naming is used the Proxy Configuration Tool automatically creates StatNrml StatUrg and MeasFlt data sets and report control blocks for them The creation is based on proxy_dataset_defaults xml file which is located in the installation drive APCM DataBases COM600 ProxyConfigTool folder The file has the following format lt DataSet name name of dataset gt lt LNClass name LNClass of ln gt Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual 3 4 3 3 4 3 1 lt DO cdc 61850 Type of DO name Caption of DO gt lt DO gt lt LN
32. munication structure you need to configure them see 3 5 1 General about configuring objects 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 3 3 3 3 1 3 3 2 3 3 3 Building object tree General about building object tree The object tree is built in the Communication structure of SAB600 see Figure 3 2 1 It 1s built by adding objects in a logical order starting from the OPC Server object Before the IEC 61850 Proxy Server can be taken into use you need to configure an OPC server for the process communication For more information on creating an OPC server refer to COM600 User s Manual You have two ways to add objects to the object tree in the Communication structure e You can right click the object to which you want to add a child object e You can copy the object First add the IEC 61850 Proxy Server OPC Client The following objects are created by the Proxy Configuration Tool and should not be added manually e TEC 61850 Proxy Subnetwork e IEC 61850 Proxy IED e Logical Devices e Data objects Adding IEC 61850 Proxy Server OPC Client object To add the IEC 61850 Proxy Server OPC Client object 1 Add the IEC 61850 Proxy Server OPC Client object in the Communication structure by selecting the Gateway object 2 Right click the Gateway object and select the server object for example New gt IEC61850 gt IEC61850 Proxy Server OPC Client Configuring IEC 61850
33. ort control block BRCB S24 Report TP c6 c SUPPORTED 39 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 1MRS757275 40 Services AA Client Sub TP MC scriber S42 GetGSSEElementNumber TP o TP S43 GetGsCBValues S44 SetGsCBValues U Transmission of sampled value model SVC Multicast SVC S45 SendMSVMessage S46 GetMSVCBValues S47 SetMSVCBValues Unicast SVC S48 SendUSVMessage S46 GetUSVCBValues o U U U O o ur II a ee OF 4 U S47 SetMSVCBValues 4 U Control S51 Select S52 SelectWithValue S53 Cancel S54 Operate Aly T D TP U S55 Command Termination S56 TimeActivated Operate File transfer S57 GetFile S58 SetFile S59 DeleteFile S60 GetFileAttributeValues v u T U Time T1 Time resolution of internal clock T2 Time accuracy of internal clock Server Pub Value Comments lisher c9 C c10 SUPPORTED SUPPORTED SUPPORTED SUPPORTED SUPPORTED nearest negative power of 2 in seconds o 1 a AJ oO N gt 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual Services AA Client Sub Server Pub Value Comments TP MC scriber lisher T3 supported TimeStamp resol nearest negative ution power of 2 in seconds c6 shall declare support for at least
34. port for any service specified for GOOSE GSE Management are declared within the ACSI basic conformance statement c3 shall be m if support for any service specified for GSSE A Profile are declared within the ACSI basic conformance statement c4 support for at least one other A Profile shall be declared e g in A1 A3 in order to claim conformance to IEC 61850 8 1 Table 5 3 1 2 PICS for T Profile support re pe nf CU Ja u essere Ja fx ER LS COS DS CS O cl shall be m if support for Al is declared Otherwise shall be i c2 shall be o if support for A1 is declared Otherwise shall be 1 c3 shall be m if support for A2 is declared Otherwise shall be 1 c4 shall be m if support for A3 is declared Otherwise shall be 1 MMS Conformance MMS conformance is guaranteed by MMS stack vendor 1 e Systems Integration Spe cialists Company Inc SISCO 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual All required IEC 61850 services for supporting the ACSI services stated to be supported are supported by the used MMS stack MMS EASE Light 43 44 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual Index A ACSI CONTORMANCE EE oe EE AE SE EE DE EER SEE DEE A er Ne basic cornformanEee eb EE se M AE din De Ee RE ER cade models conformaric ii Ee ER ER G
35. r OPC Alarm and Event Server not configurable DA Prog ID ABB IEC61850_Slave_OPC_DA Instance 1 ProglD for OPC Data Access Server not configurable AE Prog ID Configuring IEC 61850 Proxy Subnetwork Table 3 5 3 1 lists the configurable IEC 61850 Proxy Subnetwork object properties and the value ranges for them The actual configuration using SAB600 is performed as described in 3 2 Overview of configuration Table 3 5 3 1 IEC 61850 Proxy Subnetwork properties Property Para Value or Value range Default Description meter Communication Port Communication Port ETHO LAN port used by the IEC 61850 protocol used for GOOSE sending ETH1 Values shown here are default values Default ETHO when no connection to COM600 has been made When the first connection is made the communication port information is read from COM600 and the corresponding NIC value is written to NICInformation property IP Address Default 127 0 0 1 Communication channel IP address in dotted decimal format Communication Control TCP IP Keepalive 1 3600 TCP IP keepalive timeout in seconds Timeout Default 15 seconds Configuring IEC 61850 Proxy IED Table 3 5 3 1 lists the configurable IEC 61850 Proxy IED object properties and the value ranges for them The actual configuration using SAB600 is performed as described in 3 2 Overview of configuration Table 3 5 4 1 IEC 61850 Proxy IED properties Property
36. roller COM600 4 0 IEC 61850 Proxy Server User s Manual Technical reference ASCI conformance statement ACSI conformance statement ACSI conformance statements shall be used to provide an overview and details about a device claiming conformance with ACSI 5 1 2 ACSI basic conformance statement e 5 1 3 ACSI models conformance statement e 5 1 4 ACSI service conformance statement These statements are used to specify the communication features mapped to an SCSM The following tables provide the ACSI conformance statements for the COM600 IEC 61850 Proxy Server The tables are according to IEC 61850 7 2 ACSI basic conformance statement Table 5 1 2 1 Basic conformance statement Client Sub Server Pub Value Comments scriber lisher Server side of TWO PARTY ci APPLICATION ASSOCIATION Client side of TWO PARTY c1 APPLICATION ASSOCIATION SUPPORTED Ww B are N ERREURS EEN f f SE model GSE CES CS CA E Transmission of sampled E ia value model SVC E 87 d Publisher side SUPPORTED Og N B N N Og N do B N ES Og oO B Oo N es BK _ B4 N Subscriber side O 35 Grid Automation Controller COM600 4 0 1MRS757275 IEC 61850 Proxy Server User s Manual 5 1 3 36 cl shall be M if support for LOGICAL DEVICE model has been declared O Optional M Mandatory ACSI models conformance statement T
37. this interval By default this feature is not enabled because it generates an unnecessary load to the server and network If this fea ture is used the Trigger Option Period in RCB needs to be enabled Configurable Used as identification in information reports to specify that the report is from this RCB By default report control block MMS path name is used Con figurable Defines what information is sent with the information report Configurable Config Reference 20 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual Data Ref Data Set Entry ID Reason Code Sequence Number Time Stamp Trigger Options Data change Data Update Period Property Parameter Value or value range Default Description True False Default False True False Default False True False Default True True False Default True True False Default True True False Default False True False Default True True False Default False True False Default False Data Ref Data Set Entry ID Reason Code Sequence Number Time Stamp Defines the triggering condi tions for creating reports Specifies whether a report entry shall be generated due to a change of the value of the data attribute Specifies whether a report entry shall be generated due to freezing the value of an unfreez
38. unication Substation Structure ox Al E B ProxyExample El 010 Basic Gy Gateway 4 0 x AE Prog ID ABB IEC61850_Slave_OPC_AE_ Server Ma Process Event Definitions DA Prog ID ABB IEC61850 Slave OPC DA Server Wa Communication Diagnostic Event Definitions E Misc a Common Event Settings Caption 1EC61850_Proxy_Server_OPC_Client 2 Scale Definitions Description OPC Server for IEC IEC61850 Proxy sr SPA_OPC_Server GG SPA Channel E REX 521101 H B REX 521102 ff REX 521103 C ver_OPC_Client y y lEC61850ProxySubnetwork IEC61850ProxylED LD LDO LO REX_521_101LD1 LO REX_521_102LD1 Caption LO REX_521_103LD1 Monday March 19 2012 3 58 28 PM ABB gt overview_PROXY png Figure 3 2 1 Example view of SAB600 communication structure 14 The configuration work can be divided into two separate tasks 1 building an object tree and 2 configuring object properties First you need to build an object tree This is done by adding objects to the object tree see 3 3 1 General about building object tree Figure 3 2 1 shows an example of how the object tree may look like after it has been built In the example tree you can see the IEC 61850 Proxy Server OPC Client object and its child objects such as subnetwork devices and data objects Indentation is used to indicate the parent child relationship between the objects After you have added the necessary objects to the object tree in the com
39. ure 3 5 1 1 Object Properties v AX BE 41 010 Basic AE Prog ID ABB IEC61850_Slave_OPC_AE_Server Instance 1 DA Prog ID ABB IEC61850 Slave OPC_DA_Server Instance 1 E 030 Communication Control Server Originator Category Control operation issued from an operator using a client locate Server Originator Identification ABB E Misc Caption IEC61850 Proxy Server OPC Client Description OPC Server for IEC 1EC61850 Proxy AE Prog ID Prog ID for OPC Alarm and Event Server PROXY_object_properties png Figure 3 5 1 1 Example of object properties in the Objects Properties window 2 Select the property you want to configure Depending on the property value type configuring is always done either by e selecting a predefined value from a drop down menu or e entering a text string or a numerical value in a text field The available properties for different objects are listed in the following subsections Configuring IEC 61850 Proxy Server OPC Client IEC 61850 Proxy Server OPC Client does not have any configurable properties Table 3 5 2 1 IEC 61850 Proxy Server OPC Client properties Property Parameter Value or Value range Default Description 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 3 5 3 3 5 4 Property Value or Value range Default Description Parameter ABB IEC61850_Slave_OPC_AE Serverlnstancel1 ProglD fo
40. y Server User s Manual 3 4 3 2 Report control block Report control describes the conditions for generating information reports based on parameters set by configuration or by a client Report Control Blocks control the proced ures that are required for reporting values of data from logical nodes to one client There are buffered and unbuffered report control blocks Ina Buffered Report Control Block BRCB internal events issue immediate sending of reports or buffer the events for transmission This way the values of a data object are not lost due to transport flow control constraints or loss of connection BRCB provides sequence of events functionality e Inan Unbuffered Report Control Block URCB internal events issue immediate sending of reports on a best efforts basis If no association exists or 1f the transport data flow is not fast enough to support it events may be lost Object Properties v AX Ef E 010 Basic Buffer Time 0 Buffered True Configuration Revision 0 Data Set StatUrg indexed True Integrity period 0 Report ID REX521_101LD1LLNOStatUrg BR rcbStatUrg E 010 Option Fields Config Reference False Data Ref False Data Set False Entry 1D True Reason Code True Sequence Number True Time Stamp False E 010 Trigger Options Data Change True Data Update True Period False Quality Change True E Hisc Caption rcbStatUrg Description Report Control Block Buffer Time Buffer time see IEC 618
41. ys refers to the Start menu on the Windows taskbar e System prompts messages and user responses input are shown in the Courier font For example if you enter a value out of range the following message is displayed Entered value is not valid The value must be 0 30 1MRS757275 Grid Automation Controller COM600 4 0 IEC 61850 Proxy Server User s Manual 1 5 1 6 e You can be asked to enter the string MIF349 in a field The string is shown as follows in the procedure MIF349 e Variables are shown using lowercase letters sequence name Use of symbols This publication includes warning caution and information icons that point out safety related conditions or other important information It also includes tip icons to point out useful information to the reader The corresponding icons should be interpreted as follows N The electrical warning icon indicates the presence of a hazard which could result in electrical shock A The warning icon indicates the presence of a hazard which could result in personal injury The caution icon indicates important information or warning O related to the concept discussed in the text It may indicate the presence of a hazard which could result in corruption of software or damage to equipment or property n The information icon alerts the reader to relevant facts and conditions SE The tip icon indicates advice on for example how to design your project or how to use a certain