1. not have a stop to limit turning Do not turn it too much Required equipment e Signal source standard voltage current generator with at least 10 times the accuracy of the IPSOFLA FLC e Voltmeter ammeter Adjustment procedure 1 Wait 30 minutes or more after turning the power on 2 Apply the minimum signal for the input range to the input terminals 3 Turn the ZERO potentiometer so that the output signal is at the minimum for the output range 4 Next apply the maximum signal for the input range to the input terminals 5 Turn the SPAN potentiometer so that the output signal is at the maximum for the output range e Zero adjustment Output type Rotation 4 to 20mA O to 20mA The zero point shifts upward a The zero point shifts downward O Input 100 Input 100 e Span adjustment Output type 4 to 20mA 0 to 20mA Rotation The span mA mA 20 EA 20 ez expands SPAN owa A Output Jo 4 4 y The span O n narrows 0 Input 100 0 Input 100 E Behavior for out of specifications inputs loads Excessive input If the input signal exceeds the upper limit for the range the output signal increases to 120 FS or more in approximate proportion to the input signal Insufficient input e Current output type If the input signal is below the lower limit for the range the output signal decreases to 20 FS or less in approximate proportion to the input signal Howeve
2. CP SP 1225E IP50FLA FLC INTELLPAK First order Computing Unit User s Manual Thank you for purchasing the IP50FLA FLC This manual contains information for ensuring correct use of the IP50FLA FLC It also provides necessary information for installation maintenance and troubleshooting This manual should be read by those who design and maintain devices that use the IP50FLA FLC Be sure to keep this manual nearby for handy reference RESTRICTIONS ON USE This product has been designed developed and manufactured for general purpose application in machinery and equipment Accordingly when used in applications outlined below special care should be taken to implement a fail safe and or redundant design concept as well as a periodic maintenance program e Safety devices for plant worker protection e Start stop control devices for transportation and material handling machines e Aeronautical aerospace machines e Control devices for nuclear reactors Never use this product in applications where human safety may be put at risk NOTICE Be sure that the user receives this manual before the product is used Copying or duplicating this users manual in part or in whole is forbidden The information and specifications in this manual are subject to change without notice Considerable effort has been made to ensure that this manual is free from inaccuracies and omissions If you should find an error or omission please contact Yam
3. ZERO SPAN TIME CONST oe a Voltage Er sao taa Pulse voltage A E te converter converter circuit 5 6 Power circuit AC DC DC DC 2 3 Base socket azbil Yamatake Corporation Specifications are subject to change without notice Advanced Automation Company 1 12 2 Kawana Fujisawa Kanagawa 251 8522 Japan Printed in Japan URL http www azbil com 1st Edition Issued in Mar 2007 U Printed on recycled paper 07
4. atake Corporation In no event is Yamatake Corporation liable to anyone for any indirect special or consequential damages as a result of using this product 2007 Yamatake Corporation ALL RIGHTS RESERVED SAFETY PRECAUTIONS Safety precautions are for ensuring safe and correct use of this product and for preventing injury to the operator and other people or damage to property You must observe these safety precautions Also be sure to read and understand the contents of this user s manual A WARNING Warnings are indicated when mishandling this product might result in death or serious injury to the user A CAUTION Cautions are indicated when mishandling this product might result in minor injury to the user or only physical damage to this product WARNING Before wiring removing or mounting the IP50FLA FLC be sure to turn the power OFF Otherwise touching electrically charged parts could cause electric shock CAUTION eUse the IP50FLA FLC within the operating ranges given in the specifications for temperature humidity voltage vibration shock mounting direction atmosphere etc Failure to do so could cause malfunction e Do not allow lead clippings chips or water to enter the case Doing so could cause fire or faulty operation e Firmly tighten the terminal screws at the torque listed in the specifications Insufficient tightening of terminal screws could cause electric shock or fire e Do no
5. cket first Then remove the IPSOFLA FLC from the socket 2 How to remove the IPSOFLA FLC from the socket First make sure that the IPSOFLA FLC is fully pushed onto the socket Fully press both upper and lower levers on the IPSOFLA FLC and pull it straight off the socket Pulling it off when the levers are not sufficiently pressed can damage the socket 3 How to remove the socket from the DIN rail Insert a flat head screwdriver into the slit of the DIN rail holder and pull it down Then lift the socket off the DIN rail in the direction shown by the arrow in the figure right Wire the unit as shown in the figure below Use M3 5 crimp contacts for wiring 24 Vdc or 100 110 120 Vac 200 220 240 Vac 50 60Hz utput signal depends on the number mode Connect to a power source having the rated voltage Handling Precautions e Be sure to use insulated crimp contacts for terminal connections When installing the IP50FLA FLC in a place with heavy mechanical vibration or shock use ring terminals so that they do not come loose e Make sure that nearby terminal lugs do not touch each other e Keep the input output signal line 50cm or more away from any power lines carrying over 100V Do not put them in the same conduit or duct e Before wiring double check the model No and terminal Nos on the attached label e Before turning the power on be sure that all wiring is correct e Though the IP50FLA FLC i
6. he IPSOFLA FLC in a place subject to mechanical vibration or shock attach a damping bracket like the QN718A sold separately A damping bracket cannot be attached if the IP5O0FLA FLC is mounted on a DIN rail e When installing the IP5OFLA FLC in place with much dust or metal powder mount it in a case designed to be dustproof and take measures to prevent excessive heat E Installation The IPSOFLA FLC plugs into a socket which can be attached directly to a wall or to a DIN rail Lateral installation layout When installing multiple IPSOFLA FLC units side by side use the layout shown below Unit mm Duct etc 26 min Duct etc Installation layout with damping bracket When installing the IPSOPFLA FLC with the damping bracket use the layout shown below The QN718A damping bracket is sold separately Unit mm 80 min 80 min How to attach the IP50FLA FLC to the DIN rail 1 Attach the socket first With the slider on the base of the socket facing downward hook the socket onto the DIN rail Then push in the base of the socket as shown in SS the drawing _ 2 Attach the IPSOFLA FLC Push the IPSOFLA FLC straight into the socket The label lettering should be pointing the right way Be sure to push the unit firmly into the socket E Removing 1 If the damping bracket is attached to the IPSOFLA FLC remove the damping bra
7. ing ambient humidit Storage ambient humidit Vibration resistance Shock resistance Case material Case color Terminal screw Terminal screw tightening torque Mounting Mass 200g Including the base socket Included accessories Base socket parts number QN719A Optional parts sold separately Damping bracket parts number QN718A If unit is mounted on a DIN rail these specifications do not apply E Key to model numbers ia IPS50FLC10ADTO I SSS SNS SS BS SSS Sa ee V Description Additional features IPSOFLA S T i yyy S Nonisolated first order delay computing unit IPS5OFLC CO T Isolated first order delay computing unit Selectfromtable1 Selectfromtable2 o Jo ooo A Po 100 110 120Vac 50 60Hz B I 200 220 240Vac 50 60Hz D O y y 2w 00 None TO Tropicalization DO With inspection data BO Tropicalization and inspection data YO With traceability certification Table 1 Input type input ype 0 to TOmV 0 to 100mV Dto 1V Dto 5V Tio 5V Oto 10V 0 to 50mV 0 to 6OmV Oto TOPA 010 T00uA Oto mA 0 to 10mA Oto 16mA A SSeS BE aS as SS 0 to 20mA 4 to 20mA E External dimensions Unit mm Base socket part number QN719A Terminal screw Lever 8 M3 5 DIN rail EN50022 mounting Attached view Material Cold rolled steel plate SPCC t1 Galvanizing and chromate treatment E Circuit block diagram IP50FLA IP50FLC TIME CONST
8. r negative current is not output e Voltage output type If the input signal is below the lower limit for the range the output signal decreases to 120 FS or less in approximate proportion to the input signal Load resistance outside of specifications e Current output type If the load resistance exceeds the allowable range the voltage across the output terminals increases to about 16V in approximate proportion to the input signal Above 16V the output reaches its limit and the error becomes larger e Voltage output type For load resistance below the allowable range the output signal cannot increase proportionally and the error becomes larger 6 Specifications E Specifications nput type DC voltage and DC current see table 1 S Input impedance Output type DC voltage and DC current see table 2 Allowable load resistance Accurac Response time Zero span adjustment Power type DC Rated voltage 24Vde Operating voltage 24Vdc 10 Power consumption 2 2VA Starting current 0 11 A or less Inrash current at power on 5A or less ims Insulation resistance Between I O terminal and power terminal Between I O terminals for isolated type 100MQ or more by 500Vdc megger Dielectric strength Between I O terminal and power terminal Between I O terminals for isolated type 2000Vac 1 minute Power characteristics 0 1 FS 24Vdc 10 Temperature characteristics Operating ambient temperature Storage ambient temperature Operat
9. s operational as soon as the power is turned on wait 30 minutes or more to satisfy the accuracy levels stated in the specifications e Do not short circuit output terminals on the voltage output model Doing so could cause damage e Use an integral analog to digital converter to convert the analog output into digital output When using a high speed analog to digital converter such as successive approximation type make sure to operate by combined test beforehand 4 Input output characteristics The relation between input and output is shown in the figure below 100 Input Input Output 63 Output T Response time ae 5 Response time setup There is a potentiometer for setting response time on the front of this unit The response time is 0 5s or less when the potentiometer is turned fully counterclockwise and 20s or more when the potentiometer is turned fully clockwise Set to the desired position Elapsed time s Potentiometer m for response time setup 6 Adjustment E Zero and span adjustment The IPSOFLA FLC is calibrated before shipping Generally it is not necessary to adjust the zero or span potentiometers on the front panel When an adjustment is required in order to coordinate with associated instruments or for periodic inspection follow the procedure below Handling Precautions e The amount of adjustability for zero and span is about 10 e The potentiometer knob does
10. t use unused terminals on the IPS5OFLA FLC as relay terminals Doing so could cause electric shock fire or faulty operation e Do not block ventilation holes Doing so could cause fire or faulty operation e Do not touch electrically charged parts such as the power terminals Doing so could cause electric shock e Do not disassemble the IPSOFLA FLC Doing so could cause electric shock or faulty operation Conventions Used in This Manual The following conventions are used in this manual Handling Precautions Handling Precautions indicate items that the user should pay attention to when handling the IP5OFLA FLC Numbers within parentheses indicate steps in a sequence or parts of an explanation The IPSOFLA FLC is a thin plug in type first order delay computing unit that produces a DC signal output after a first order delay is processed for the DC signal input The response time can be set by the potentiometer on the front of the unit E Mounting locations Install the IPSOFLA FLC so as to avoid the following e High and low temperatures and humidity e Direct sunlight outdoor locations exposed to wind and rain e Splashing liquid such as water oil or chemicals e Corrosive or flammable gases e Dust and soot e Mechanical vibration and shock e Strong electric or magnetic fields e Sources of electrical noise such as high voltage ignition devices or welding machines C Handling Precautions eWhen installing t
Download Pdf Manuals
Related Search
Related Contents
User manual(English) IC-F43TR SERVICE MANUAL technical notice VERTEX ST 2 a125060F (030413) Operation Manual 03/2008 Fiberon BRDPRTF CN 20-10PK Installation Guide Sonnox Restore QuickStartGuide-1-2 Europass CV École de Sculpture Architecturale. Pilules Cuivreuses Anti Manhattan USB 2.0/HDMI Copyright © All rights reserved.