Home

KIMO Humidity / Temperature transmitter TH 200

image

Contents

1. Drill 8mm holes and mount the plate with the screws and wall plugs supplied with the transmitter Insert the transmitter on the plate see A on the drawing shown below by aligning it at 30 Rotate its housing in clockwise direction until you hear a click which confirms that the transmitter is correctly installed Then open the housing lock the clamping system of the housing on the plate with the screws as shown to remove the transmitter from the plate remember to remove the screws first 120 mm O 316 L ae stainless cle Steel plate E A oR o0 6 5mm E Maintenance Avoid aggressive solvents Protect the transmitter and probes from any cleaning product containing formol which may be used for cleaning rooms or ducts Tel 41 0 56 222 38 18 mailbox sentronic com Fax 41 0 56 222 10 12 www sentronic com Ref FT ang TH 200 16 08 11 RCS 24 P rigueux 349 282 095 Non contractual document We reserve the right to modify the characteristics of our products without prior notice
2. Electrical connections as per NFC15 100 norm This connection must bemade by a qualified technician Whilst making the connection the transmitter must not be energized Power supply connection Before making the connection you must first check the power supply which is indicated on the transmitter board see on connection drawing For 24 Vdc power supply models Power suppl terminal aie 24 Vdc power supply For 24 Vac power supply models Vac Vac erminal DIOC power supply Class Il power supply e For 115 or 230 Vac power supply models ground D neutral Power uppi terminal bloc 115 230 Vac power supply MPENTRONIC ac Produkte Support und Service Ruggh lzli 2 CH 5453 Busslingen Connection of SUB D15 RS 232 see on connection drawing Output signal selection voltage 0 10 V or current 4 20 mA The on off switch located on the left top of the transmitter see on connection drawing allows selection of the required outputs U 4 20 mA Pin Description N NC NC NC NC Output connection NC 4 20 mA current output NC 0 10V GND 4 20mA NC Output a terminal block 9 RX RS 232 10 INC Regulator displ or PLCIBMS 144 TX RS 232 passive type 12 INC 13 INC 0 10 V voltage output 14 INC 0 10V GND 4 20 mA 3 15 GND RS 232 Output termin
3. mm Remote probe 000 Length 150 or 300 mm Cable aaiae PVC 4 8 mm length 2m W Polycarbonate probes are supplied with a flow through polycarbonate protection tip with st steel filter 25 u ref EPP2 Stainless steel probe Measuring rang 0 40 to 180 C Standard probe 08 Length 100 mm Remote probe ccc Length 150 or 300 mm Cable socisiceiscscisnnicnsiesetetnvasetwesseaias silicone 4 8 mm Ig 2 m Stainless steel probes are supplied with a flow through stainless steel U protection tip with a st steel filter 25 u ref EP125 A A qhe Tip selection were EPI25 EPI100 EPFI EPFT a St steel St steel Filter material St steel St steel Filter type meshed sintered sintered Maximum particles 25u 100u Maximum air velocity 25m s 20m s Maximum temperature 180 C 120 C Maximum relative humidity 95 RH 95 RH Length 30mm Applications HVAC air conditioning system Cold storage room Industry Pharma plants u Electronics Dryer Curing Tip material 30mm Water droplets Shavings cuttings Dust Chemical products Grease 1 PC Polycarbonate 2 PTFE Teflon 3 St steel 316 L E Technical Specifications Power SUPPIY c ccceseeeeeeeeen 24 Vac Vdc 10 115 Vac or 230 Vac 10 50 60 Hz Output oo cece eseteeeeeeeeees 2 x 4 20 mA or 2 x 0 10 V 4 wires maximum load 500 Ohms 4
4. 20 mA minimum load 1 K Ohms 0 10 V Galvanic isolation inputs and outputs 115 Vac 230 Vac models Outputs 24 Vac Vde models Consumption 5 VA Relays 0 2 RCR relays 6A 230 Vac Visual alarms ccccccceeeeeeee 2 dual color LED Audible alarm cc cece buzzer Electro magnetical compatibility EN 61 326 Electrical connection 00 screw terminal block for cables 1 5 mm max RS 232 communication Digital ASCII proprietary protocol Working temperature housing 0 to 50 C Working temperature probe 20 to 120 C polycarbonate 40 to 180 C st steel Storage temperature 08 10 to 70 C Environment air and neutral gases Tel 41 0 56 222 38 18 mailbox sentronic com Fax 41 0 56 222 10 12 www sentronic com Connection Output selection 4 20 mA or 0 10 vo NS BL ae RS 232 connector Connector for standard or remote F pa humidity probe rA Analogue output 1 Analogue output 2 Analogue outputs Relay terminal blocks Power supply Ayre OL 24 Vde ac EnA a L 230 vac p i 4 E A 115 Vac r lt y A The ticked box shows maS the power supply type of the transmitter onnection fittings o o o o For 24 Vdc For 24 Vac For 230 Vac 115 Vac power supply models power supply models power supply models 0 6 0 T t phase ground neutral E
5. 65 housing with or without 2 line backlit display e Quick and easy mounting using the 1 4 turn system with wall mounting plate E Transmitter features Humidity Measuring range 0 to 100 RH Units of measurement 00 RH Accuracy Repeatability linearity hysteresis 1 5 RH from 3 to 98 RH and if 15 C lt T lt 25 C Temperature dependence 0 04 x T 20 RH if T lt 15 C or T gt 25 C Response time c cccccceeeeeeees lt 10 sec from 10 RH to 80 RH V 2m s Resolution 0 00 0 ccececeseeseeesseeeeneees 0 1 RH Factory calibration uncertainty 0 88 RH Type Of sensor ccccceeeeeeeeees Capacitive Type Of fluid ccc ccceeeeeeeeeees air and neutral gases high resistance to solvents Temperature Measuring range ccccccccee from 20 to 120 C polycarbonate probe from 40 to 180 C st steel probe Units of measurement 0 00 Gy F Accuracy 0 ee cccecceeeeeeeteeseeeeen 0 3 of reading 0 25 C Response time cece t 9 sec for V 1 m s Resolution ooo ce ceeecceeeeeseesersesenees 0 1 C Type Of sensor ccceeeeeeeeeee Pt 100 1 3 as per DIN IEC 751 Type Of fluid oo ee ceeeteeeeeeeen air and neutral gases Analogue output is configured by default at our factory from 0 to 50 C See Configuration part to configure analogue outputs All accuracies indicated in this tec
6. KIMO PESICEIRDEI ESA INSTRUMENTS Pressure Temperature Humidity Air Velocity e Airflow Sound level TH200 standard PC or St Steel probe WITH or WITHOUT displav E Part number To order just add the codes to complete the part number Power supply Output Probe 24 Vac Vdc 0 10 V or 4 20 mA 115 Vac 0 10 V or 4 20 mA 230 Vac 0 10 V or 4 20 mA Polycarbonate Stainless steel Probe mounting Standard Remote Display With display Without display Probe length 100 mm standard 150 mm remote 300 mm remote Example TH200 BN STH PD300 humidity transmitter type TH200 with 24Vac Vdc power supply without display with polycarbonate remote probe length 300mm SEN Ruggh lzli 2 Tel 41 0 56 222 38 18 mailbox sentronic com VSENTRONIC ac Produkte Support und Service CH 5453 Busslingen Fax 41 0 56 222 10 12 www sentronic com ew Humidity Temperature transmitter 2 a TH 200 CE e Ranges from 0 100 RH and 40 to 180 C probe dependent e Configurable intermediate ranges e Functions relative and absolute humidity dew point wet and dry temperature enthalpy e Smart Pro system interchangeable probes PC or Stainless Steel e On site calibration e Simultaneous display of 2 parameters e 2 outputs 4 20 mA or 0 10V 4 wires RS 232 2 RCR relays 6A 230 Vac e 2 visual dual color LED and audible buzzer alarms e Output diagnostics e ABS IP
7. al block A CAUTION NC gt DO NOT CONNECT Regulator display 40 or PLC BMS passive type Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 www sentronic com mailbox sentronic com F E Digital communication RS 232 communication e Via the RS 232 connection the TH200 can transmit its measurements to aKIMO Class 300 transmitter Example a CP300 can display in addition to the pressure other parameters such as humidity and temperature from a TH 200 e Via the RS 232 connection you can also configure your transmitter with the LCC 300 software The RS 232 connection cable is available in 2m 5m or 10 m maximum lengths E Configuration You can configure all the parameters of the transmitter units measuring ranges alarms outputs channels calculation formula via the different methods shown below Via keypad only on models with display A code locking system combined with keypad guarantees the security of the installation See configuration manual Via software optional on all models Simple user friendly configuration See LCC 300 user manual Configurable analogue outputs Configure the range according to your needs outputs are automatically adjusted to the new measuring range Range Range with centre zero 40 0 40 C with offset zero 30 0 70 C or standard range 0 100 C gt you can configure your own intermediate ranges according to your needs between 10 a
8. hnical datasheet were stated in laboratory conditions and can be guaranted for measurements carried out in the same conditions or carried out with calibration compensation As per NFX 15 113 and the Charter 2000 2001 HYGROMETERS GAL Guaranteed Accuracy Limit which has been calculated with a coverage factor value of 2 is 2 58 RH between 18 and 28 C on the measuring range from 3 to 98 RH Sensor driftis less than 1 RH year E Functions Class 200 transmitters have 2 analogue outputs which correspond to the 2 parameters displayed You can activate 1 or 2 outputs and for each output you can choose between humidity temperature and the functions below ruts tomes tots O ranges resolutions Mixing ratio 0 1 g kg Dew point 0 1 C 0 1 F C Wet temperature from 20 to 180 TCO F Enthalpy from 0 to 15 000 Kj Kg 0 1 Kj Kg The default configuration for the output 1 is 0 100 RH in hygrometry and 0 50 C in temperature for the output 2 e Easy maintenance with the new SMART PRO system digital probes Totally interchangeable they are individually adjusted and are automatically recognized by the transmitter E Housing dimensions including wall mounting plate Standard loc
9. king ring 19 mm y flow through tip Remote 150 or 300 mm locking ring 19mm nut and wt _ seal __ PVC or silicone tube HOUSING o ae ABS Fire proof classification V 0 as per UL 94 Protection ccccceeeeeeees IP 65 Display c cece alphanumeric 2 lines of 16 digits 98mm x 22mm backlit protection screen made of PMMA Connection fittings polyamide for cables 7 mm max Weight c cesses 800 g with display E Relays and Alarms Class 200 transmitters have 4 stand alone and configurable alarms 2 visual alarms dual color LED and 2 relays contacts You can set the parameter humidity temperature dew point 1or2set points high and low for each alarm the time delay 60 sec max the alarm action rising or falling the relay operation mode positive or negative security the audible alarm buzzer activation Ruggholzli 2 SENTRONIC 1c CH ees Busslingen E Probes features Polycarbonate probes Measuring rang 0 20 to 120 C Standard probe 0 Length 100
10. nd 100 of the full scale The minimum configurable range is 10 of the full scale OV 10V 4mA 20 mA E Options LCC 300 configuration software with RS 232 cable Calibration certificate EHK 500 reference portable instrument Mounting brackets Sliding fittings Connection fittings Protection tips Caps for tips Wall mounting support bracket for remote humidity probe I Optional accessories oO E E E E E E SENTRONIC c oe EN Calibration On site adjusting and calibration The EHK 500 is a reference portable instrument which enables you to adjust at one point on the TH 200 and TH 300 by correcting any offset whilst measuring in a single ambient environment housing both sensing elements You can also adjust at several points Output diagnostics With this function you can check with a multimeter or a regulator display or a PLC BMS if the transmitter outputs work properly The transmitter generates a voltage of 0 V 5 V and 10 V or a current of 4mA 12mAand 20mA Certificate e Class 300 transmitters are supplied with adjusting certificates Calibration certificates are offered as an option e The Smart Pro humidity probes are supplied with adjusting certificates and can also be supplied with calibration certificates offered as an option E Mounting To install the transmitter on a wall fix the stainless steel plate to the wall this plate is supplied with the transmitter

Download Pdf Manuals

image

Related Search

Related Contents

Aérosol Special Fourmis 400ml (voir la fiche produit)  OPERATING INSTRUCTIONS TURBOVAC  Manuel - Régulation TAC4 DL + RC - 2012.indd  EXSYS PCI-Express adapter f/ ExpressCard card, 3.5-inch Bay  LG L1950H 19" TFT  SATA Hard Drive Enclosure  INSTRUCCIONES PARA EL USO INSTRUÇÕES DE  GUIA DO USUÁRIO - Support  INSTRUCTION MANUAL M O D E D ` E M P L O I GEBRUIKSAANWIJZING  L`Assomption de Bais - Château de Sainte  