1. CHAP 7 Diagnostic PLUS100 THR CHAPTER 7 DIAGNOSTIC DIAGNOSTIC 74 In the event of a fault the PLUS 100 THR controller warns the operator by displaying an alarm code and emitting a warning sound via the buzzer inside the control console If alarm conditions arise the display will show one of the following messages iE POSSIBLE CAUSE OPERATION TO BE PERFORMED 9 Check the room temperature sensor e fthe problem persists replace the sensor 9 Check the humidity sensor Humidity sensor fault e fthe problem persists replace the sensor Defrost sensor fault 9 Check the defrost sensor In this case eventual defrosts will last as d5 c persists replace the Eeprom alarm An error in the EEPROM memory has been e Switch system off and back on detected again all output deactivated except the alarm ones EN e Check for proper match between Software compatibility error MASTER board and console board Temperature sensor fault E Flat battery alarm Replace lithium battery CR2032 type of the Console General alarm e g overheat or max pressure switch All outputs except alarm if present are deactivated Check compressor absorption If the problem persists to contact the technical assistance service Check the connection between No connection between the Console and the the two units MASTER board If the problem persists to contact the technical assistance service Minimum or
2. 10 5 2 din 0 2 10 0 GO Rel 02 15 USE AND MAINTENANCE MANUAL pago 15 PLUS100 THR CHAP 5 Parameters programming Fans pause after defrosting minutes Enables keeping the fans still for an F5 time after dripping This time starts from the end of dripping If dripping is not 0 10 min 0 min set at the end of defrosting the fans pause occurs directly Minimum temperature alarm Enables defining a minimum temperature value to the ambient Below value Atf the alarm status will be signalled 45 M2 1 ABC with the alarm icon flashing the temperature flashes and an internal buzzer acoustically signals the existence of an anomaly The alarm is signalled after the Ald time Maximum temperature alarm Enables defining a maximum temperature value to the ambient Above value At2 the alarm status will be signalled with the alarm icon flashing the temperature flashing and an At1 1 45 C 45 C internal buzzer acoustically signals the existence of an anomaly The alarm is signalled after the Ald time The alarm does not suspend any defrosting in progress Minimum humidity alarm Enables defining a minimum humidity value to the ambient to be humidified Below the AU1 value the Eu alarm status 1 1 will be signalled with the alarm icon flashing and the buzzer active Silencing the humidity and the alarm icon remain flashing The alarm i
3. 6 o y pa 1 i 5 o 5 o p O o mn gt v gt Q gt Lc E O T 2 2 oo E O 2 O O 5 5 5 c 5 gt o x gt 9 556593 5 9 X D 5 Z T 2 y I o 3 Bec O v E G 5 Q c gt 90 E Ww d Se OO x c 3 gt 2 gt 6 BE BE LLI O T c c C 2 gt RH d 3 s I d o 9 5 5 d 2 5 E op 65 2 E HE gt 2 9 2 5 5 c 6 9 06 2 0 gt 9 o p 5 LO Cc 11 T GO E EM T 7 E 5 gt D D o O E NS 2 lt x ZO c 5 E oo 6 5 5 3 o E 6 5 CO 5 o 5 2520555590658 E O Z O0 Cc Ka qe O T E c C TON d CHAP 5 Parameters programming PLUS100 THR REGOLAZIONE UMIDITA RH 8171591 071 SA AAA On Deumidifica Set RH dUn AA E A A A A LO ooo Off Deumidifica Set RH re sid 5 J lt Z
4. Phase duration maximum 99 hours with 30 min steps For the dripping phase it is possible to exclude the humidity and the cold management The program starts by pressing the START key for a few seconds the program selection and therefore the pressing of the SET key Program start 1 press the START J key for a few seconds 2 using the UP and DOWN arrows select the wanted program 3 press the SET key to start the program The time evolution is highlighted by the advancing bars During program execution it is possible to amend the humidity and temperature setpoint directly from the keyboard without having to access programming Variations are provisional and do not alter the pre set program If a phase has 0 time it moves on to the following one The times of the phases proceed even in case of no electric power supply or control stand by Using the START key pressed briefly it is possible to see the remaining time of the phase in progress With parameter CIC it is possible to program a cycle once the program has finished automatically starts from the beginning or to hook programmes between them in order to have a greater number of phases of the 6 of the individual program A program can always be interrupted by pressing the START STOP SY key for a few seconds Page 28 USE AND MAINTENANCE MANUAL Rel 02 15 Hectrical Boards CHAP 5 Parameters programming PLUS100 THR DAY NIGHT CYCLE FOR GER
5. 8858 PHASE 5 advancing Refreshment Ambient temperature value parameters Ambient relative humidity parameters value error codes Time date time parameters value running program timer Programming the controller is in programming phase Cold flashing if called for dehumidification only Hot flashing if called for dehumidification only Humidification Dehumidification Defrost Fans Light flashing if the door switch is active PLUS100 THR CHAP 5 Parameters programming 19 A Alarm 20 b Stand by 5 4 GENERAL FEATURES For safety reasons and to simplify the operators work the PLUS 100 THR has two programming levels the first level is used to modify SETPOINT parameters i e those parameters that are changed frequently The second level is for general parameter programming of the various board work modes It is not possible to access the first programming level directly from the second level you must exit the programming mode first T KEY TO SYMBOLS For practical purposes the following symbols are used e lt indicates the UP key used to increase value and to force the defrost pause e indicates the DOWN key JE used to decrease value to mute the alarm and to force the air changing 5 6 SET POINT PROGRAMMING AND DISPLAYING 1 Push the SET key to display the current SET POINT temperature and humidity alternately 2 Press the SET key and push one
6. INSTALLATION 21 IMPORTANT GENERAL INFORMATION FOR THE INSTALLER 1 Install the device in places where the protection rating is observed and try not to damage the box when drilling holes for wire pipe seats 2 Do not use multi polar cables in which there are wires connected to inductive power loads or signaling wires e g probes and digital inputs 3 Do not fit power supply wiring and signal wiring probes and digital inputs in the same raceways or ducts 4 Minimize the length of connector wires so that the wiring does not have a spiral shape 5 All wiring must be of a cross section suitable for relevant power levels 6 Place a general protection fuse upstream from the electronic controller 7 When it is necessary to extend the probes the wires must have a cross section of at least 1 mm The probes extension or shortening could alter the factory calibration then check and calibrate through an external thermometer 22 KIT FOR MOUNTING PLUS 100 THR electronic controller kit for assembling and using contains e N 2 temperature probes e N 1 fixing bracket e N 1 phone plug cable N 1 user manual Page 6 USE AND MAINTENANCE MANUAL Rel 02 15 CHAP 2 Installation PLUS100 THR PLUS 100 THR INSTALLATION 2 3 Fig 1 Position the 100N MASTER THR in the din guide and insert the four plugs to fix the box to the panel Fig 2 Disposition of console PLUS 100 THR components Fig
7. Page 24 5 15 Humidity dehumidification preservation of ambient humidity Page 25 5 16 Ventilation Page 25 5 17 Air change Page 26 5 18 Pause Page 26 5 19 Defrost Page 26 5 20 Hot gas defrost Page 27 5 21 Password function Page 27 5 22 Automatic programs Page 29 5 23 Day night cycle for germination lights OPTIONS Page 30 6 1 TeleNET monitoring supervision system CHAP 6 DIAGNOSTIC Page 31 7 1 Diagnostic MIA APPENDICES Page 32 A 1 EC declaration of conformity Page 33 A 2 PLUS 100 THR wiring diagram Pedo Rel 02 15 USE AND MAINTENANCE MANUAL Page 3 PLUS100 THR CHAP 1 Introduction CHAPTER 1 INTRODUCTION 1 1 GENERAL FEATURES DESCRIPTION The PLUS 100 THR system allows the user to control temperature and humidity in seasoning preservation rooms and industrial processes The system consists of the 100 MASTER THR unit to which all electrical connections are made and the PLUS 100 THR control console equipped with wide LCD display The system consists of the 100 MASTER THR unit to which all electrical connections are made and the PLUS 100 THR control console equipped with LCD display for fast comprehensive monitoring of conditions inside the room The system allows the user to control cold heat ventilation the room light humidification air change pauses dehumidification defrosting and alarms up to five programs of seven phases each settable and customizable APPLICATIONS Seasoning
8. dEO 0 an alarm signal Ed buzzer alarm relay is given The alarm 5 displayed even when humidity set is achieved it does not block the normal functioning and once silenced the dEt count re starts 0 alarm only 12 refreshment is performed dEO 1 a refreshment of the duration dr 5 ipd and the timer relating to the interval Pr if present is recharged eres a per il collegamento al 0 31 sistema di supervisione TeleNET Automatic cycles management or via _ the cycles via Wed TeleNET to set Aut 1 1 TeleNET management 0 seasoning cycles active Seasoning or germination selection 1 germination day night cycle active 1 5 5 0206 Rel 02 15 USE AND MAINTENANCE MANUAL Pace 19 PLUS100 THR CHAP 5 Parameters programming Total block It is possible to only see the temperature and humidity set point 1 Blocks access in 1st and 2nd level programmes Blocks access in germination P Active when PA 8 different from 0 68 amendment anc s l programmes amendment 2 Blocks access in 1st and 2nd level programmes 3 Blocks access in 2nd level programmes m uM 5 11 AUTOMATIC PROGRAMS Pr1 Pr2 Pr3 Pr4 Pr5 To access the automatic programmes parameters keep keys Ld SIART STOP and SET pressed for a few seconds the function is active only if Cg 0 1 Using key or key 7
9. Description Installed relay Board output characteristics Notes Cold output 3 4 10A 250V AC3 2HP Relay 30A ACT 100000 cycles All outputs are free of voltage contacts Other n 9 output see connection scheme on uet 16 250V 1 Dimensional Characteristics Dimensions of 100 MASTER 11 4cm x 6 9cm x 21 4cm HxWxL Dimensions of PLUS 100 THR housing 9 8cm x 3 5cm x 18 0cm HxWxL Insulation and Mechanical Characteristics Display protection rate IP55 Box material Extinguishing ABS PEGS Rel 02 15 USE AND MAINTENANCE MANUAL Page 9 PLUS100 THR CHAP 4 Warranty conditions CHAPTER 4 WARRANTY CONDITIONS PLUS 200 EXPERT control units are covered by a 24 month warranty against all manufacturing defects as from the date indicated on the product ID code or from the date of product registration card if present In the event of a defect the product must be appropriately packaged and sent to our factory or any authorized Service Center by RMA number request Customers are entitled to have defective products repaired spare parts and labour included Transport expenses and risk shall be met entirely by the customer Repairs carried out under warranty do not prolong or renew the warranty expiration date The Warranty does not cover e Damages resulting from tampering impact or improper installation Behaviour inconsiste
10. a 00 00 23 50 day phase can start at 10 pm and end at 4 10 min steps om of the following day tt1 t1 Temperature SET start time 00 00 23 50 10 min steps 2 12 Temperature SET start time 00 00 23 50 10 min steps Temperature 1 SET 45 445 Temperature 2 SET 45 445 IGNITION OF PLUS 100 THR ELECTRONIC CONTROL 5 13 After having wired the electronic controller apply voltage 230 Vac the control will immediately and simultaneously emit a sound for a few seconds and remain fully switched on on the display COLD HOT PRESERVATION OF AMBIENT TEMPERATURE Fr The cold and hot call is managed in neutral area depending on the set temperature setpoint D key 4 and to the temperature differentials parameters dtC and The cold is activated upon exceeding of set dtF and remains active until set is achieved with dtn 0 The hot is activated below set dtC and remains active until set is achieved with dtn 0 It is possible to set a dead area with parameters dtn that deactivates hot and cold when the temperature is between SET dtn and SET dtn USE AND MAINTENANCE MANUAL Page 23 8 8 Z 3 o 9 C c D 33 5 S o I 4 goo G gt 2 o C 56 gt XU S T G Cc c 2 G 3 S O 2 gt iS v 2 2 C D x ON D eee
11. drying rooms Germination rooms with day night cycles Storage rooms with or without humidity control MAIN FEATURES Backlit LCD screen Clock and calendar Manual or automatic mode Up to 5 formula completely customazible automatic management of 7 phases for each formula dripping first phase seasoning conservation last phase simple programming and selection of set formula possibility of join together more formula for exceeding the 7 phases limit Heat and humidity can be excluded to manage storage cells with defrost activation Temperature to one decimal point Password for keypad lock Day night cycle for germination systems with double set point Dehumidification program with cold or heat call Page 4 USE AND MAINTENANCE MANUAL Rel 02 15 CHAP 1 Introduction PLUS100 THR PRODUCT IDENTIFICATION CODE 1 2 200P100THR3 Temperature and humidity control for seasoning preservation industrial processes Complete with display 100N_MASTER DIMENSIONS 13 Dimensions in mm How Moe 0 98 180 e 39 g 121 560 179 IDENTIFICATION DATA 1 4 The unit described in this manual has an ID plate on its side showing the relevant ID data e Manufacturer name Device code La e Serial number de SH Power supply POWER SUPPLY 0 5615 PLUS100 THR CHAP 2 Installation CHAPTER 2
12. for F6 0 240 sec 0 00 10 Fans speed during seasoning preservation The value of this variable is amended based on the set up made during the last phase of a performed program Refreshment period Interval between one refreshment and the subsequent one The refreshment is a work pause in which cold hot humidifies 0 Disabled and dehumidifies are disabled i dr Refreshment phase duration 1 240 min 120 min K7 Multifunction relay function choice 0 Refreshment rin clamps 15 16 1 Fans low speed Signal delay and alarm display time of Ald minimum or maximum temperature or 1 min 4 hours 240 min humidity Minimum time between switch off and subsequent ignition of the compressor It also stops the fans if they are not active for other functions Dehumidification method selection 0 cooling dEU The separate dehumidification calls hot 1 heating and cold only for temperature 2 separate dehumidification 0 disabled EnU Humidification enabling enabled Dehumidification enabling 1 1 enabled Cat Ambient probe value correction 10 10 Humidity probe value correction 20 20 EnH 1 hot enabled mohenaping EnH 0 hot disabled Hr 1 enables humidity management 0 High speed 1 Low speed only if rin 1 0 24 hours at 10 min steps 1 0 disables humidity management The humidity probe can be disconnected without error on display The evapora
13. maximum humidity alarm A humidity higher or lower to that set for minimum or Check humidity management maximum humidity alarm has been reached in the The probe does not correctly ambient See variables AU1 and AU2 user detect the humidity programming level E1 E2 3 4 Et Minimum or maximum temperature alarm Check the compressor status A temperature higher or lower to that set for The probe incorrectly detects the minimum or maximum temperature alarm has been temperature or the stop start reached in the ambient See variables At1 and At2 control of the compressor does user programming level not work Check humidity management Limit Timeout for dehumidification The probe does not correctly detect the humidity Pedo Rel 02 15 USE AND MAINTENANCE MANUAL Page 31 T Temperature on display is flashing PLUS100 THR Appendices APPENDICES A 1 EC DECLARATION OF CONFORMITY COSTRUTTORE MANUFACTURER DAY PEGO S r l Via Piacentina 6 b 45030 Occhiobello RO Italy C YY Tel 39 0425 762906 Fax 39 0425 762905 DENOMINAZIONE DEL PRODOTTO NAME OF THE PRODUCT MOD PLUS100 THR IL PRODOTTO E CONFORME ALLE SEGUENTI DIRETTIVE CE THE PRODUCT IS IN CONFORMITY WITH THE REQUIREMENTS OF THE FOLLOWING EUROPEAN DIRECTIVES Direttiva Bassa Tensione LVD 2006 95 CE Low voltage directive LVD EC 2006 95 Direttiva EMC 2004 108 CE Electromagnetic compatibility EMC EC 2004 108 LA CONFORMIT
14. of or 7 keys to modify the SET POINT value Release the SET key to return to cold room temperature display modifications are saved automatically Page 14 USE AND MAINTENANCE MANUAL Rel 02 15 Electrical Boards CHAP 5 Parameters programming PLUS100 THR FIRST LEVEL PROGRAMMING User Level 5 7 To access the first programming level proceed as follows 1 Press the and keys simultaneously and keep them pressed for a few seconds until the first programming variable appears on the display Release the and 7 keys Select the variable to be modified using the or Y key When the variable has been selected it is possible e display its setting by pressing SET e modify its setting by pressing the SET key and the or 7 buttons When configuration values have been set you can exit the menu by pressing and Y simultaneously for a few seconds until the room temperature value appears 5 he modifications are saved automatically when you exit the configuration menu BON LIST OF 1 LEVEL VARIABLES User Level 5 8 HOT temperature differential with reference to main SET POINT It is expressed in absolute value and it defines the temperature hysteresis for the HOT referred to temperature SET POINT COLD temperature differential with reference to main SET POINT It is expressed in absolute value and it defines the temperature hysteresis for the COLD referred to temperature
15. only enabled 0 NO SgU 60 Dripping enabling Dripping phase evaporator fans speed 0 High speed o the value of 2nd level variable 1 Low speed ony if rin 1 tmm Phase 1 evaporator fans speed Amends n saan the value of 2nd level variable F8 only if ae 1 Phase 1 duration 0 00 99 30 30 min steps Phase 2 temperature setpoint 45 45 C 0 99 rH Phase 2 humidity setpoint 0 Disabilitata 60 NO Phase 2 refreshment 1 YES Phase 2 evaporator fans speed Amends 0 High speed Ve 1 Low speed the value of 2nd level variable F8 only if rin 1 Phase 2 duration 0 00 99 30 at 30 min steps Phase 3 temperature setpoint 45 45 0 99 rH Phase 3 humidity setpoint 0 Disabled 60 ml Pedo Rel 02 15 USE AND MAINTENANCE MANUAL Page 21 i PLUS100 THR CHAP 5 Parameters programming 0 NO Phase 3 refreshment 1 YES v3 Phase 3 evaporator fans speed Amends i ae the value of 2nd level variable F8 only if ala 1 Phase 3 duration 0 00 99 30 30 min steps Phase 4 temperature setpoint 45 45 C 0 99 rH Phase 4 humidity setpoint 0 Disabled 6096 NO Phase 4 refreshment 1 YES Phase 4 evaporator fans speed Amends 0 High speed ii 1 Low speed the value of 2nd level variable F8 E Phase 4 duration 0 00 99 20 30 min steps Phase 5 temperature setpoint 45 45 C 0 99 rH Phase 5 humidity setpoint 0 Disabled 6096 0 NO Pha
16. select the program to be amended After having selected the program press the SET key to display the parameters 2 Using key or key 7 select the parameter to be amended 3 Amend the setting by keeping the SET key pressed and by pressing one of the keys 2 or 7 4 Once configuration values have been set to exit the menu press keys and simultaneously keeping them pressed for a few seconds until the temperature value appears 5 Memorisation of the amendments made to the variables will happen automatically when exiting the configuration menu Exiting from the menu happens spontaneously after an inactivity period or by simultaneously pressing keys and 7 for a few seconds The following table represents any one of the Pr1 Pr2 Pr3 Pr4 Pr5 programmes Page 20 USE AND MAINTENANCE MANUAL Rel 02 15 PLUS100 THR CIC 0 at the end of the last program phase phase 5 it moves to manual 0 it ends the program and CIC 1 at the end of the last timed phase moves on to manual phase 5 it returns to initial phase phase CIC 0 An infinite loop of the phases is therefore created 1 loop phases CIC 2 at the end of the last program 2 calls subsequent program phase phase 5 it moves on to the subsequent program Phase 0 or dripping phase temperature 45 445 C setpoint Phase 0 or dripping phase humidity 0 99 rH setpoint 0 disabled 0 normal functioning 1 hot only enabled 2 hot cold
17. 3 Example of PLUS 100THR installation Pego Rel 02 15 USE AND MAINTENANCE MANUAL PLUS100 THR CAP 2 Installation FUNCTIONS MANAGED BY PLUS 100 THR 24 Display and adjustment of temperature and humidity settings neutral zone Stand by activation deactivation e Sensor alarms e Air change parameter adjustment e Defrost parameter adjustment Pauses parameter adjustment e Fan parameter adjustment Outputs status display e Simultaneous display of temperature and humidity e Automatic program control with automatic variation of temperature and humidity settings over time e Clock function Page 8 USE AND MAINTENANCE MANUAL Rel 02 15 Electrical Boards CHAP 3 Technical specifications PLUS100 THR CHAPTER 3 TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS 4 1 Power Supply Voltage 230 V 10 50Hz 60 2 Max power absorption only electronic control 8VA Ambient Conditions Operating temperature 5 50 C Storage temperature 10 70 Relative ambient humidity Lower than 90 Hr General Features Type of connectable probes temperature NTC 10K 1 Resolution ambient temperature 0 1 C Reading accuracy of probes ambient temperature 0 5 C Reading range 45 45 C Humidity probe Analogic input 4 20 mA Reading accuracy of humidity probe See humidity probe specifications Reading range of humidity probe 0 99 rH Output Characteristics
18. A PRESCRITTA DALLA DIRETTIVA E GARANTITA DALL ADEMPIMENTO A TUTTI GLI EFFETTI DELLE SEGUENTI NORME comprese tutte le modifiche THE CONFORMITY WITH THE REQUIREMENTS OF THIS DIRECTIVE IS TESTIFIED BY COMPLETE ADHERENCE TO THE FOLLOWING STANDARDS including all amendments Norme armonizzate EN 60730 1 EN 60730 2 9 EN 61000 6 1 EN 61000 6 3 European standards EN 60730 1 EN 60730 2 9 EN 61000 6 1 EN 61000 6 3 IL PRODOTTO E COSTITUITO PER ESSERE INCORPORATO IN UNA MACCHINA O PER ESSERE ASSEMBLATO CON ALTRI MACCHINARI PER COSTITUIRE UNA MACCHINA CONSIDERATE DALLA DIRETTIVA 2006 42 CE Direttiva Macchine THE PRODUCT HAS BEEN MANUFACTURED TO BE INCLUDED IN A MACHINE OR TO BE ASSEMBLED TOGHETER WITH OTHER MACHINERY TO COMPLETE A MACHINE ACCORDING TO DIRECTIVE EC 2006 42 Machinery Directive Paolo Pegorari Page 32 SI NANO ers Pedo Allegati PLUS100 THR PLUS 100 THR WIRING DIAGRAM A 2 a Power supply section 1 2 Power supply 230VAC 50 60 Hz Analogical inputs section 29 30 Evaporator NTC probe 31 32 Humidity probe 4 20 mA 0 100Rh 82 V 31 Y 27 28 Ambient NTC probe Digital inputs section 45 50 Stand by forcing 44 50 Disables hot forces variable EnH 0 43 50 Disables humidity forces variable Hr 0 42 50 Microdoor 41 50 Main alarm stops all outputs 35 36 12V 37 38 5485 console Rel 02 15 USE AND MAINTENANCE MANUAL JOON Mastar Outputs sec
19. MINATION LIGHTS 5 23 By setting parameter Cg Germination seasoning cycle at second programming level it is possible to choose the use of the programmes or a special program suitable for day night cycles Cg 0 default activates the automatic programmes management for seasoning Cg 1 activates the management of the germination day night cycle By means of the parameters indicated in paragraph 5 11 it is possible to determine the day start and end times and manage two differential temperature setpoint During the day phase the germination lights are switched on and the display shows the references of phase 0 switched on During the night phase the germination lights are switched off and the references of phase 4 switch on The connection of the germination lights is separate from the cell light that can be used as service light managed as usual from the microdoor and the light key The day night cycle starts by pressing the cycle start key Rel 02 15 USE AND MAINTENANCE MANUAL Page 29 PLUS100 THR CHAP 6 Options CHAPTER 6 OPTIONS TELENET MONITORING SUPERVISION SYSTEM To insert the board in a TeleNET network refer to the layout below To configure the instrument refer to the TeleNET manual IMPORTANT During configuration select PLUS 100 THR R Controller under the item Module 100N MASTER THR TeleNET 2TWRS485 USE AND MAINTENANCE MANUAL Page 30 Rel 02 15
20. PLUS100 THR 100N Master Fire GBR wj md u Lr CEA 3 4 ug m 1 r _ 1 Br _ de Co N 1 Master BEER 1 Se Use and maintenance manual ENGLISH READ AND KEEP Electrical Boards 249 REV 02 15 ELECTRICAL BOARDS FOR REFRIGERATING INSTALLATIONS Ae ENG PLUS100 THR 1 1 Page 5 1 2 Product identification code Page 5 1 3 Dimensions Page 5 1 4 Identification data INSTALLATION CHAP 2 6 2 1 Important general information for the installer Page 6 2 2 Kit for mounting Page 7 2 3 Plus 100 THR installation Page 8 2 4 Functions managed by PLUS 100 THR TECHNICAL SPECIFICATIONS CHAP 3 Page 9 3 1 Technical specifications WARRANTY CONDITIONS CHAP 4 Page 10 4 1 Warranty conditions PARAMETERS PROGRAMMING Page 11 5 1 Control panel CHAP 5 Page 11 5 2 Frontal keyboard Page 12 5 3 LED display Page 14 5 4 General features Page 14 9 0 Key to symbols Page 14 5 6 Set point programming and displaying Page 15 5 7 First level programming Page 15 5 8 List of first level variables Page 17 5 9 Second level programming Page 17 5 10 List of second level variables Page 20 5 11 Automatic programs Pri Pr2 Pr3 Pr4 Prd Page 22 5 12 Germination day night cycle Page 23 5 13 Ignition of PLUS 100 THR electronic control Page 23 5 14 Cold hot preservation of ambient temperature
21. SET POINT Temperature NEUTRAL zone with reference to main SET POINT In neutral zone cold and hot are not activated dtF gt dtn 0 C it includes symmetrically both a superior part hot and an dtC gt dtn 0 C inferior part cold as to temperature SET POINT HUMIDIFICATION differential with reference to humidity SET POINT It is expressed in absolute value and it defines dUn 1 10 the humidification hysteresis referred to humidity SET rH POINT DEHUMIDIFICATION differential with reference to humidity SET POINT It is expressed in absolute value and it dUn 1 10 defines the dehumidification hysteresis referred to humidity rH96 SET POINT Humidity NEUTRAL zone with reference to main SET POINT In neutral zone humidification and dUU gt dUn 0 dehumidification are not activated it includes symmetrically rH both a superior part humidification and an inferior part dUd gt dUn 0 dehumidification as to humidity SET POINT rH96 Defrost interval hours d4 0 disables the defrosts 0 24 2 0 Lele 4 Maximum lenght of defrost minutes End of defrost setpoint The defrost is not executed if the temperature read from defrost probe is superior to 6 value 35 45 15 C In case of broken probe it will have a timing defrost Dripping duration minutes At the end of defrosting the compressor and the fans remain 0 2 10 min 0 min still for the set time the defrosting icon flashes dtC din 0 2
22. arameter setting by pressing the SET key To modify the parameter setting by pressing the SET key and pressing the or Y key 4 When setting has been completed you can exit the menu by pressing the lt and Y keys simultaneously and keeping them pressed until the cold room temperature reappears 5 Modifications are saved automatically when you exit the configuration menu 6 Press STAND BY to enable electronic control LIST OF 2 LEVEL VARIABLES Installer Level Microdoor input status with door closed d main alarm digital input status 9 18 1 NC 0 Fans in continuous start 1 Fans switched off if cold hot humidification and dehumidification switched off 0 Fans working during defrosting F4 Fans pause during defrosting 1 Fans not working during defrosting Fans status when cold hot humidification and dehumidification are at a stand still Evaporator fans activation for air recirculation The fans activate for a time defined by F7 if they have not started working for the F6 time If activation time coincides with the defrosting time end of defrosting is awaited The speed of the fans high low is the same as that selected for the phase in progress function not activated GO Rel 02 15 USE AND MAINTENANCE MANUAL pago 17 PLUS100 THR CHAP 5 Parameters programming Evaporator fans duration for air a recirculation Fans working time
23. c s o S D cc 2 C E Oo S 5 I 5 gt 0 o 2 Q D E gt z CU gt o T 2 0 5 5 D n Q E t OG o amp 2 O O o 2 o a c o 2 2 C e oO E w E o q c im 2 4 po o gt J fe c O D O pi ail Q o O 5 o o c o IL gt w p e as T 0 5 2 oW Sg 5 gt E Tr 2 39 fU we e Z E z Q T D DHE CU o W o OQ c Gc ME gt 2 lt o c S gc E n o o gt lt o g o O vu C 0 0 o oe B 2 E O a CO E c 0 gt d Es c so E _ 0 c gt o OD _ o p 27 O e m 5 O 2 2 9 USE 8 5 lt 5 5 o gm 2 3 3532 558252990 8 amp 2E 9 59 2 2 gt o Z X W c gt S o o E o E gt gt lt x o lt o Z
24. etent court for any controversies is acknowledged to be the Foro di Rovigo Page 10 USE AND MAINTENANCE MANUAL Rel 02 15 CHAP 5 Parameters programming PLUS100 THR CHAPTER 5 PARAMETERS PROGRAMMING CONTROL PANEL 7 hog EAE AA LOD display FRONTAL KEYBOARD PROGRAM START STOP to press 5 sec for selecting the program to run to press 5 sec for finishing a running program TIMER displays remaining time of running phase with a single key press UP MANUAL PAUSE and DEFROST activates both functions _ STAND BY system ON OFF the running program maintains the count of remaining time SET ambient temperature and humidity following pressures alternate temperature and humidity Rel 02 15 USE AND MAINTENANCE MANUAL PLUS100 THR CHAP 5 Parameters programming o E DOWN MUTE ALARM FORCING AIR CHANGE ROOM LIGHT DISPLAY LED 1111121 86886886886868888888 nnnzBBB DO e 001 01 1 we I he ee 2 O Tu 1 E PHASE 0 advancing Dripping Day germination phase i PHASE 1 advancing 3 H PHASE 2 advancing 4 E PHASE3 advancing 5 PHASE 4 advancing Night germination phase Page 12 USE AND MAINTENANCE MANUAL Rel 02 15 CHAP 5 Parameters programming PLUS100 THR 10__ 11 PRG 12 13 14 15 16 17 18
25. nt with Manufacturer s prescriptions and instructions Damages caused by repairs made by unauthorized persons Damages due to natural phenomena as lightings natural disasters etc In all such cases repair cost shall be charged to the Customer in full Warranty cover may be refused if the device is modified or changed PEGO S r l cannot be held liable for any loss of data and information costs of substitute goods or services damage to property people or animals lost sales or profits business interruption any direct indirect incidental assets coverage punitive special or consequential damages howsoever caused whether contractual extra contractual or due to negligence or other liability resulting from use of the product or its installation Malfunction caused by tampering shock inadequate installation automatically invalidates the warranty All instructions of this user manual and the operating conditions of the device must be respected PEGO S r l cannot be held liable for possible errors or inaccuracies written in this manual as a result of printing or transcription errors PEGO S r l reserves the right to modify its products without prior notice as it deems necessary without altering their main characteristics Every new release of a PEGO user manual replaces all the previous ones For all matters not expressly indicated the warranty is subject to the regulations contained in the Italian Civil Code art 1512 The comp
26. ona Neutra Set RH dUn r _ Off Umidifica PRA aS CC LC EA A On Umidifica CHIAMATA DEUMIDIFICAZIONE Ts AMATA UMIDIFICAZIONE T s 5 16 VENTILATION The parameters of the second level programming F4 F6 7 F8 enable setting the management of the fans in the different modes By setting parameter rin 1 it is possible to differentiate high and low speed of the fans in the various phases of a program parameters vSg v1 v2 v3 v4 v5 vSC 517 AIR CHANGE The air changes can be enabled with parameter rA Up to six daily execution times for air change can be set in parameters from rA1 up to rA6 The duration of the air change is defined by parameter drA During air change hot cold humidity and dehumidification do not activate o lt is possible at any time to force an air change with the DOWN y key Pedo Rel 02 15 USE AND MAINTENANCE MANUAL Page 25 PLUS100 THR CHAP 5 Parameters programming 5 18 PAUSE The refreshment is a phase of the pause process of the temperature and humidity management Refreshments are managed with parameters Pr and dr Pr defines the interval between one refreshment and the following one dr defines the duration of the refreshment It is possible at any time to force an air change with the UP L J key a defrosting is also
27. s signalled after the Ald time rA1 rA6 drA flashing The alarm is signalled after the Ald time AU2 99 does not signal the alarm Air change enabling in real time 0 Disabled With rA 1 it is possible to set up to 6 air changes in real time Enabled during one day through parameters rA1 rA6 _ Air change times programming lt is possible to set up to 6 times for the air changes The Maximum humidity alarm Enables defining a maximum humidity value to the ambient to be humidified Below the AU2 value the Eu alarm status will be signalled with the alarm icon flashing and the buzzer AU141 99 Rh 99 Rh active By silencing the humidity and the alarm icon remain previous value blocks the subsequent one making them 00 00 23 50 sequential Air change duration 0 10 6 Evaporator probe temperature display only NM if dE 21 nothing is displayed temperature reading Page 16 USE AND MAINTENANCE MANUAL Rel 02 15 Electrical Boards CHAP 2 Parameters programming PLUS100 THR SECOND LEVEL PROGRAMMING Installer Level 5 9 To access the second programming level press the UP and DOWN keys and the LIGHT key simultaneously for a few seconds When the first programming variable appears the system automatically goes to stand by 1 Select the variable to be modified by pressing the UP lt and DOWN keys When the parameter has been selected it is possible 2 To display the p
28. se 5 refreshment 1 YES Phase 5 evaporator fans speed Amends 0 High speed 1 Low speed the value of 2nd level variable F8 Phase 5 duration 0 00 99 30 30 min steps Seasoning preservation temperature 45 445 setpoint 0 99 rH Seasoning preservation humidity setpoint 0 Disabled 60 Seasoning preservation end timeout 0 240 days Seasoning preservation evaporator fans 0 High speed vSC speed Amends the value of 2nd level 1 Low speed variable F8 only if rin 1 GERMINATION DAY NIGHT CYCLE To access the day night cycle parameters for germination lights it is necessary to 1 Check that parameter Cg 1 Em ya 2 Keep keys y Y DOWN and EJ LIGHT pressed for a few seconds Using key or key Y select the parameter to be amended 4 Amend the setting by keeping the SET key pressed and by pressing one of the keys 2 or 7 lt 22 USE AND MAINTENANCE MANUAL Rel 02 15 Electrical Boards A Cy Y CHAP 5 Parameters programming PLUS100 THR 5 Memorisation of the amendments made to the variables will happen automatically when exiting the configuration menu Exiting from the menu happens spontaneously after an inactivity period or by simultaneously pressing keys and 7 for a few seconds Day phase start time P Germination lights active only during the 2 10 min steps day phase Day phase end time tdE can also be lt of tdS for example
29. simultaneously activated To interrupt a refreshment position the control in stand by the times are reloaded 5 19 DEFROST Defrosting can be managed with parameters d4 d5 d6 d7 F5 that define the intervals the maximum duration the defrosting end temperature the dripping and the fans stop To manually activate defrosting it is sufficient to press the UP US key Defrosting is not activated in case the temperature set for defrosting end d6 is lower than the temperature detected by the evaporator probe Defrosting will complete upon reaching the defrosting end temperature d6 or for defrosting maximum duration d5 5 20 HOT GAS DEFROST Set parameter d1 1 for managing cycle inversion defrosting The compressor relay and the defrosting relay are activated for the entire defrosting phase For the correct management of the plant it will be the responsibility of the installer to use the defrost output that must allow the opening of the cycle inversion electrovalve and the closing of the liquid electrovalve For the capillary plants without thermostatic valve It is sufficient to control the cycle inversion electrovalve using the defrosting relay control Page 26 USE AND MAINTENANCE MANUAL Rel 02 15 Electrical Boards CHAP 5 Parameters programming PLUS100 THR PASSWORD FUNCTION 5 21 The password function activates by setting a value different from 0 for parameter PA See parameter P1 for the different pro
30. tection levels Protection is enabled automatically after approx 2 minutes of inactivity on the keyboard Numbers 000 appear on the display By keeping SET pressed the first digit flashes for amendment using up down arrow Release SET and press SET again the second amendable digit flashes Release SET and press SET again the third amendable digit flashes The operation is cyclical and therefore by pressing SET again the first digit flashes again and so on password is forgotten use universal number 100 AUTOMATIC PROGRAMS 5 22 An automatic program is a work cycle made of a maximum of 7 phases in which it is possible to automatically amend the temperature and the humidity set point when passing from one phase to the following one In each phase it is possible to choose whether to enable or not the movements managed with parameters Pr and dr and manage a different speed for the fans lt is possible to set up to 5 programmes identified with Pri Pr2 Pr4 Pr5 each of which has a different setting according to the table of paragraph 5 10 For each program the first phase is defined dripping or phase 0 5 process phases follow The last phase is the seasoning preserving phase with unlimited duration in time PLUS100 THR CHAP 5 Parameters programming Each phase and the dripping are characterised by Temperature setpoint e Humidity setpoint e Refreshments enabling disabling High or low fans speed
31. tion contacts without voltage 21 22 Alarm 23 24 Defrosting 25 26 Dehumidification 15 16 Refreshment rin 0 low speed fans rin 1 Step 1 germin lights Cg 1 13 14 Air change 11 12 Humidification 9 10 Cell light 7 8 Fans high speed if rin 1 5 6 Hot 3 4 Cold TeleNET Section 39 line A of 2TWRS485 40 line B of 2TWRS485 Page 33 PLUS100 THR NOTES Page 34 USE AND MAINTENANCE MANUAL Rel 02 15 Electrical Boards g Distributor
32. tor probe is displayed instead of humidity if dE 0 0 probe present Evaporator probe exclusion 1 probe absent Type of defrosting at cycle inversion hot d gas or resistance The compressor output is also activated with hot gas Humidity management 1 with hot gas O with resistance EM E 3 Minimum value attributable to setpoint LSt 45 HSt C 45 C of temperature Electrical Boards A EN 9 Page 18 USE AND MAINTENANCE MANUAL Rel 02 15 L CHAP 5 Parameters programming PLUS100 THR Maximum value attributable to setpoint Temperature differential referred to Setpoint for COLD BLOCK 0 20 btF It constitutes the SET btF limit below which the cold call relay 3 4 and the dehumidification 0 Disabled relay 25 26 are disabled Temperature differential referred to Setpoint for HOT BLOCK It constitutes the SET btC limit above which the hot call relay 5 6 the humidification relay 11 12 and the dehumidification relay 25 26 are disabled Limit time for DEHUMIDIFICATION the dehumidification request is not 0 min 4 hours satisfied achievement of humidity SET 1 min steps within the time dEt the variable dEO is taken into consideration for the operation 0 Disabled to be performed Counting starts at every new dehumidification request Operation to be performed in case Timeout for dehumidification dEt intervenes 0 20 C btc 0 Disabled

Download Pdf Manuals

image

Related Search

Related Contents

Téléchargement FDR - Ramsar Sites Information Service  Insignia NS-R2001 Stereo Receiver User Manual  Chamberlain 2500BC Garage Door Opener User Manual  appendix xi cdap smart card user manual  5相ステッピングモータ 取扱説明書  EPSON スキャナ用 IEEE1394 I/Fカード取扱説明書  Avocent SwitchView 1000  Laserliner SuperLine 3D  ÍNDICE  DOC-BOX 10109 Use and Care Manual  