9000U ISOLATOR - Instrumentation and Automation Solutions
Contents
1. 10V to OV OV to 10V OV to 10V 10V to 10V and 10V to 10V Table2 Output Loading Details 6 11 Size Two Outputs 45mm x 75mm x 110mm 55mm x 75mm x 110mm Four Outputs 100mm x 75mm x 110mm 7 TROUBLE SHOOTING UNIT NOT TURNING ON The problem can be bad connection power of incorrect rating First check power on terminal of the instrument itself if it is not present then the fault is in power chord A One must take care while dealing with Power wirings because it may create electrical shock UNSTABLE READING Check for loose connections First verify that all conventional instrumentation norms have been followed for wiring Try using shielded cable for sensor input Make sure that the shield is connected to Earth ONLY at Page 6 of 9 Universal Linear Isolator 9000U Ref No m92A om 101 Issue No 10 one end This cable should not be routed along side with high tension or power cables Check for ripple on power supplies of Input section and Output sections If power supplies have ripples input voltage may be low or there is some fallure on power supply card Please note that this is an isolator and the Input and Output sections are electrically isolated from each other Therefore any power supply measurements should be done with respect to proper grounds OUTPUT NOT MATCHING WITH THE EXPECTED VALUE It is a normal tendency to doubt the instrument performance when the Output is not match
2. how to operate this product Signal before starting operation gt This manual describes the Isolator functions of this product Masibus The Signal isolator is used to provide does not guarantee the galvanic isolation from one signal application of these functions for input to another output and any particular purpose usually combines the converter Under absolutely no function circumstances may the contents of this manual in part or in whole be transcribed or copied without permission gt The contents of this manual are subject to change without prior e Isolator is normally used to Provide isolation at three levels a Between Power to Input Output b Between Input to Output c Between Output and output notice Every effort has been made to ensure that the details of this 1 3 Product Order Code manual are accurate However should any errors be found or Model 9000U important information be omitted APS No of O P amp type ES Ed ESE ml C 4 20mA U1 VAC 1 One 1 4 20mA 18 36 0 20mA U2 VDC 0 20mA please contact your nearest Masibus representative or our Sales office 1 2 Description oia aa La Four e o svoc_ 1 2 1 The need for Isolation 0 10VDC 5 en Safety isolation is important for both arn manufacturers and consumers lts purpose is to electrically separate Table1 Product Ordering Code hazardous circuits and transient sources from users and to protect products
3. The Isolator provides a good protection for sensitive system parts against voltage spikes etc 6 0 Specifications 6 1 Input Please Refer Sheet 1 attached at last of this document Note here any of these I O combinations are Page 5 of 9 Universal Linear Isolator 9000U masibus Ref No m92A om 101 Issue No 10 available with factory set They are not field settable The table below shows corresponding load according to current or voltage ratings Input I mpedance For Current I P 510 For Voltage I P 5 MQ Load OmA to 20mA and 4mA VOOL to 20mA 91002 10mA to 10mA 1mA to 1mA and OmA to 6 2 Power Supply 9O0VAC to 265VAC 45Hz to 65Hz Std 18VDC to 36VDC on request Power Consumption Less than 10VA 6 3 Output Please Refer Table 3 attached at last of this document Auxiliary Output Transmitter Power Supply 24VDC Preferred Max load 1 2KQ Max current Limit 26mA Electronic 6 4 Isolation 1 5KV AC between Input to All Output Output to Output Input to Power All Output to Power 6 5 Accuracy 0 1 of FS 6 6 Environmental Humidity 30 to 95 RH Non Condensing Ambient O to 55 C Temperature Coefficient lt 100ppm 6 7 CMRR gt 100dB 6 8 NMRR gt 70dB 6 9 Mounting DIN RAIL 35 mm Mounting 6 10 Load Resistance OV to 1V 0V to 1V 1V to OV 1V to OV 1V to 1V and 1V to 1V OV to 5V OV to 5V 5V to OV 5V to OV 5V to 5V and 5V to 5V 10V to OV
4. Warning Symbol The symbol calls attention to the operating procedure practice or the like which if not correctly performed or adhered to could result in personal injury or damage to or destruction of part or all of the product and system Do not proceed beyond a warning symbol until the indicated condition are fully understood and met Class 2 Type of Instrument Note Class 2 Instrument is using Line amp Neutral for Power Supply Input Under absolutely no circumstances may the contents of this manual in part or in whole be transcribed or copied without permission The contents of this manual are subject to change without prior notice Every effort has been made to ensure that the details of this manual are accurate However should any errors be found or important information be omitted please contact your nearest Masibus representative or our sales office 1 INTRODUCTION lee Purpose of The Manual 1 1 1 How to read this manual I nstaller Read Chapters 1 3 7 System Designer and New User Read All Chapters Expert User Read Chapters 4 7 1 1 2 Regarding This User s Manual Page of 9 Universal Linear Isolator 9000U masibus Ref No m92A om 101 Issue No 10 This manual should be provided to the end user Keep an extra copy or copies of the manual in a Figurel Signal Isolator Safe place Read this manual carefully to gain a thorough understanding of Input Output Process
5. and is connected to terminal plate with the help of burg Strips A Please note that some of the components on signal conditioning card are not ESD protected Direct human touch can damage semi conducting devices permanently Terminal Card All input output and supply terminals are mounted on this card The other three cards are also attached to this card using mating connections Trim pot Card This card contains Power On indication LED calibration trim pots as well as current O P indication LEDs Type Of Signal INPUTS OUTPUTS Page 7 of 9 Universal Linear Isolator 9000U Ref No m92A om 101 Issue No 10 Unidirectional Increasing Voltage Unidirectional decreasing Voltage Positive Unidirectional decreasing Voltage Negative Unidirectional decreasing Voltage Bi directional increasing Voltage Bi directional decreasing Voltage Unidirectional Increasing current Bi directional Increasing Current Bi directional decreasing Current masibus O to 10mV O to 50mV O to 100mV O to 1V O to 5V O to 10V O to 24V O to 600V O to 10mV O to 1V O to 10V O o cr O UI lt O to 50mV id O to 100mV O to 1V O to 5V O to 5V O to 10V O to 10V O to 24V 10mV to O 50mvV to 0 po te 100mMV to O TIV to 0 5V to O 5V to O 10V to O 10V to O 10mV to O 50mV to 0 ee ton 100mvV to O AV to 0 5V to O 5V to O 10V to O 10V to O 10mV to 10mV
6. OPERATOR S MANUAL 9000U ISOLATOR Masibus Automation And Instrumentation Pvt Ltd B 30 GIDC Electronics Estate Sector 25 Gandhinagar 382044 Gujarat India Ph 91 79 23287275 79 Fax 91 79 23287281 82 Email support masibus com Web www masibus com Universal Linear Isolator 9000U Ref No m92A om 101 Issue No 10 Contents 1 INTRODUCTION 1 1 Purpose of The Manual 1 2 Product Over View Description 1 3 Product Ordering Code 2 SAFETY WARNING PRECAUTIONS 2 1 Safety Precautions 2 2 Warning Precautions 01 03 3 INSTALLATION GUIDELINES 03 3 1 Mounting Details 3 2 Terminal Connections 4 OPERATION GUI DELI NE 4 1 Test Setup 4 2 Calibration Procedure 5 APPLICATION 0 Sem AADAADAADAADS RPrFWOONOVUBWNE Ro SPECI FI CATI ONS Input Power Supply Output Isolation Accuracy Environmental CMRR NMRR Mounting Load Resistance Size 7 Trouble shooting Figures amp Tables Figure 1 Signal Isolator Figure 2 DIN RAIL Mounting Figure3 Figure4 Figure5 Figure6 Figure7 Figures Table 1 Table 2 Table 3 Details Mechanical Drawing Front Sticker Details Connection Details Details For 90 265 VAC Operated Unit Details For 18 36 VDC Operated Unit Test Set up Product ordering Code Output Loading Details Input Output Range 05 05 06 06 masibus Note Information in this manual is subject to change without prior notice or permission A
7. and X Specify from tablel their surroundings Galvanic isolation is S Specify from table 3 consult factory the most popular method Transformers and opto isolators are examples of For Example galvanic isolation Transformers use Universal Linear Isolator with 4 20mA separate windings to magnetically input amp Dual output 4 20mA with 90 265 convert power from inputs to outputs VAC aux supply order code will be Opto isolators convert input signals into light and then convert it back for the 9000 C U1 2 1 output signals 2 SAFETY WARNING 1 2 2 What Is Signal I solator PRECAUTIONS Page 2 of 9 Universal Linear Isolator 9000U Ref No m92A om 101 Issue No 10 2 1 Safety Precautions Dangerous voltages capable of causing death are sometimes present in this instrument Before installation or beginning of any troubleshooting procedures the power to all equipment must be switched off and isolated Units suspected of being faulty must be disconnected and removed first and brought to a properly equipped workshop for testing and repair Component replacement and interval adjustments must be made by a company person only A 2 2 Warning Precautions gt Before wiring verify the label for correct model no and options gt Wiring must be carried out by personnel who have basic electrical knowledge and practical experience gt It is recommended that power of these units to be protected by fuses circuit breakers or externa
8. ing the expected value Kindly make sure that the output is really incorrect with respect to input signal before attempting any re calibration Account for measuring instrument s inaccuracies lead errors and calibration errors Care must be taken when measuring Output signal An ordinary 3 digit multimeter is used it can show reading which deviates from what the instrument is showing as the accuracy of the multimeter may not be as good as the that of the instrument So use calibrating instrument of accuracy better than 0 1 for purpose of calibration If the signal is still found to be out of tolerance calibration should be attempted as described in the next section VAGUE READING The reason can be reverse input connections INFORMATION ABOUT CARDS This unit consists of five cards a SMPS based supply card Table3 Input Output Ranges masibus b Signal conditioner card c Terminal Card d Trim pot Card SMPS based power supply card This card contains basic Switch Mode Power Supply with I P fusible resistor And two isolated supplies of 15V and Non Isolated TPS o p are generated on this card Using burg strips this card is connected to terminal card While dealing with SMPS card please take care that It is not connected to mains supply One may get high voltage shocks Signal conditioner Card This card contains signal conditioner of the input section This card contains analog Isolation circuit
9. l over current rated at the minimum value possible gt All wiring must confirm to appropriate standards of good practice and local codes and regulations Wiring must be suitable for voltage current and temperature rating of the system gt Beware not to over tighten the terminal screws gt Unused control terminals should not be used as jumper points as they may be internally connected causing damage to the unit gt Verify that the ratings of the output devices and the inputs as specified in Chapter 6 are not exceeded gt Upon receipt of the shipment remove the unit from the carton and inspect the unit for shipping damage If any damage due to transit report and claim with the carrier Write down the model number and serial number for future reference when corresponding with our Customer Support Division gt Do not use this instrument in areas such as excessive shock vibration dirt moisture corrosive gases or rain The ambient temperature of the areas should not exceed the maximum rating specified masibus gt Provide power from a single phase instrument power supply If there is a lot of noise in the power line insert an insulating transformer into the primary side of the line and use a line filter on the secondary side As counter measures against noise do not place the primary and secondary power cables close to each other 3 0 INSTALLATI ON GUI DELI NES 3 1 Mounting Details Universal Linear I
10. lV to 1V 50mV to 50mV 100mV to 100mV AV to 1V 5V to 5V 5V to 5V 10V to 10V 10V to 10V 10mV to 10mV 50mV to 50mV ERICA 100mV to 100mV TIV to 1V 5V to 5V 5V to 5V 10V to 10V 10V to 10V OmA to 1mA OmA to 20mA OmA to 20mA AMA to 20mA AmA to 20mA 1mA to 1mA 1mA to 1mA 5mA to 5mA LOMA to 10MA 10mA to 10mA 1mA to 1mA 1mA to 1mA 5mA to 5mA 10mA to 10mA 10mA to 10mA Page 8 of 9 Universal Linear Isolator 9000U masibus Ref No m92A om 101 Issue No 10 O to 10k O to 120 ohms Potentiometric O to 250 ohms 4mA to 20 mA if any one of I P terminal is open then O P will go high max 24mA Input type O to 1000 ohms O to 2000 ohms Other on demand Max Allowable voltage 200 of full scale Note Please refer one more manual page Appendix A Terminal Details for FOP Ref No m92A om 301 For FOP 100mm and TOP Please refer one more manual page Appendix B Terminal Details for DOP Ref No m92A om 201 For DOP 45mm Page 9 of 9
11. s tes Pi ee Chia 7 pee a Gh LH p EES ki 4 pS m mr Lt irat IF heal mare lt Thie i Dhe inb b H ES RH E TEP te 6000 Figure4 Front Sticker Details For DOP 55mm The ON LED will glow when power is applied to the unit Connect Output 1 and Output 2 as shown here Connect input between IN and IN symbol shown on the front label Wire Resistance Measurement Measurement 7 T T T on et 9 q g Short terminal 7 and 8 Figure5 Connection Details Connect input between TERMINAL 8 amp 9 shown on the front label for 2 Wire Resistance Measurement input type 3 Wire Resistance masibus Connect input between TERMINAL 7 OPEN 8 WIPER and 9 CLOSE Shown on the front label for 3 Wire Resistance Measurement input type input type For the potentiometric input type trim pot is provided for the input configuration 4 1 SOVACTOZSVAC 7 24 WDC TPS G W 1 2 18 wT 1 45 Hz To 65 Hz fon Pa p 2 iovocTossovoc 6 24WDC TPS 1a W 1 2 17 WI l Figure6 Details For 90 265V AC Operated Unit For DOP 55mm i 7 24WDC 7 gt 5 Gai Cay wI pe lavDc oO ENDE 7 5 24 WDC 75S Gsywi 2 C7 wi Figure7 Details For 18 36V DC Operated Unit For DOP 55mm 4 0 OPERATION GUIDELINES 4 1 Test Setup Turn on the equipment Connect the equipment as shown in figure Page 4 of 9 Universal Linear Isolator 9000U Ref No m92A om 101 Is
12. solator is DIN rail mounting type Max ambient conditions are tested for units kept under ideal test conditions where the air around the test unit is moving and the unit is open to atmosphere from all sides In cases where multiple units are mounted close to each other both vertically and horizontally the conditions are very much different than the test conditions in terms of air movement and ability of the unit to shed out its internal heat It is therefore advised to make provision for ventilation and good air circulation inside the panel for long and reliable operation Recommended way of mounting multiple Universal Linear Isolator 9000U units is Shown below s Circulation ARH Figure2 DIN RAIL Mounting Details For DOP 55mm As air vents are provided on the top and bottom part as shown in above figure of the unit the horizontal mounting arrangement shown here allows good vertical air circulation It is also Page 3 of 9 Universal Linear Isolator 9000U Ref No m92A om 101 Issue No 10 recommended to keep adequate gap between two units Vertical mounting arrangement of multiple units is strictly not advised DA IT T3 Ded cae AE HA Figure3 Mechanical Drawing For DOP 55mm 3 2 Terminal Connection Connect rated power at appropriate terminals as marked on the front label Label of default configuration is shown below iaa mas a sm rr CI fe Corales mn Correrjerk ba a SL e
13. sue No 10 DIGITAL UNIT CALIBRATOR UNDER TEST MULTIMETER RESISTANCE LOAD PRECISION Figures Test Setup This equipment requires an external power source connect to an appropriate source The Unit gives the output according the Input feed from the appropriate source 4 2 CALIBRATION PROCEDURE Calibration for the unit should be carried out by an experienced engineer only Equipment used for the calibration Should be of high accurate 0 05 or better and good stability Isolator output has to be calibrated at two points Zero Desired O P value at minimum I P value at minimum Input value and Span Desired O P value at maximum I P value at full scale value For example I P is 1V to 1V and the desired o p is 4mA to 20mA So first at 1V I P O P must be set to 4mA using zero pot and after that at 1V I P O P must be set to 20mA using span pot In the calibration procedure the zero and span of the unit needs to be calibrated There are two zero and two span pots one zero and span pot pair is for trimming the output 1 of the unit and another zero and span pot pair is for trimming output 2 of the unit For calibration zero of output 1 set the input at zero or minimum input then using the zero pot adjust the reading on multimeter to 4 00mA after that make input at maximum max Input value and in this condition adjust the reading on multimeter to 20 00mA using span pot Check the zero again and repeat
14. the procedure until zero and span are adjusted correctly Now the zero and masibus Span adjustment of the output 1 card are calibrated Similarly calibrate output 2 of the unit Trim pots are identified by Z for zero and S for span calibration for both output separately For checking the Linearity takes reading in steps of 25 Repeat the same procedure for calibrating the other output Similarly for the potentiometric input type the output has to be calibrated at two points Zero Desired O P value at minimum I P value at minimum Input value and Span Desired O P value at maximum I P value at full scale value Variable Resistance Box can be used for calibration Note For FOP calibrate output 3 amp 4 of the unit as per above calibration procedure 5 0 APPLICATION Why Is Isolation So Important In most processes there are pieces of electronic measurement and control equipment from many different manufactures The signals from these instruments are interconnected to each other and to sensors transducers and output devices connected in the process loop In any such measurement and control system there are several problems that are likely to occur all of which can be solved by incorporating the appropriate isolation between signals APPLICATION AREA A typical application could be where the Signal has to be distributed for indication on local panel field control room main control room and DCS system