Hybrid Solar Inverter TP1501 User Manual
Contents
1. Page 10 7 Monitoring system There are 2 monitor system for TP1501 one run on Microsoft Windows XP or above version for Personal Computer PC the other run on Android for smart phone The display of the PC is as below A Main Page a Aircon o i 7 Eu cs e xs Main Parameter Solar vs Grid BEE Solar Energy 6 58 WH BEE Grid Energy 238 35 WH 7V Power 29 42 W Today Money Save 7 64 Total CO2 Reduced 17 31 rid Power 538 31 W Total Money Save 18 57 Mo ey per KWH 32 1 0 2 build 50620 COM26 9600 0 8 1 2015 8 11 FF 02 35 21 Error Code 3 CRC ERROR Solar vs Grid ratio display the percentage ofthe power from solar amp grid for supplying load 2 Display the real time power of the solar amp grid supply to the load by wattage W 3 The local electricity cost S KWH User can change this value by double clicking it 4 Link the history data to Microsoft Excel or Open Office Excel Double click the button to enable it 5 Energy WH of solar vs Grid by hour Updated everyday Page 11 B Parameter Page ad Aircon Main Parameter Current Status Config Register Vin 224 00 DEVICE ID lin 0 87 95 00 3 35 IOUT MAX 110V 60Hz VAC REF B SOFT TIME 6 VIN MIN 4 36 BKP 9 DELAY 49 00 BKI 11 B SINE RATE 97 NVARY 1 NDUTY MAX 60 110V L 1100 110V H 1500 220V L 1800 220V H 2200 1 0 2 build 50620 COM26 9600 N 8 1 The com port open success In this page use
2. ARNING Connecting this unit to the electrical grid shall only be performed by qualified personnel and only after formal approval from the utility company WARNING This device contains no user serviceable parts inside Please return the unit to authorized Service Center for maintenance CAUTION This unit should be mounted on firm background and under a shading roof to avoid exposure to direct sunlight and rain CAUTION Rear heat sink of this unit may exceed 80 C 175 F Don t touch to avoid risk of burning Page 1 Table of contents 1 Introduction Installation 3 3 Wiring process 4 Operating procedure 5 Specifications 6 LED indication 7 Monitoring system 8 Trouble shooting Page 2 1 Introduction The system is a Hybrid photovoltaic inverter The 2 hybrid sources are Photovoltaic PV amp Grid power There is no expensive and bulky batteries required Hence eliminating large expenses on battery maintenance It can convert Photovoltaic DC energy via solar panel modules and invert collected energy into alternate current AC which then output to the certain home appliances that are proudly powered by solar renewable energy Once the PV energy is not good enough for the appliances the Grid power will support the rest of the energy automatically In case of the electric blackout the Grid power is no longer supporting the rest energy once the PV energy become weak The power support to the home app
3. C 600V wire for solar panel connections with the PV Inverter Power cable selection AC wire Black copper wires of 12 AWG or above should be used for alternate current input Output wire Red copper wires of 12 AWG or above should be used for alternate current output DC wire For PV input from solar panels the cross section area is dependent on the length of the wire Identifiable colored copper wires of 11 AWG section size 4 0mm2 or above Connect the most positive point from the panels to the red wire of the PV input of TP1501 amp the most negative point to the black wire of the PV input of TP1501 NEC 2008 UL 4703 approval PV wire is recommended Turn on procedure Apply the grid power first amp then after the green LED active apply the PV power amp then turn on the appliances Turn off procedure Turn off the appliances Remove the PV power amp then remove the grid power Page Recommended wiring Diagram PV Panels mi fi s ari gt 3 nl ES _ hd bee So 72 4 5 fone i 1 fil 1 I hun EI DEE DC BOX 1 ele eleje sjelejele Extension wire 4 Hybrid Inverter TP1501 110 220 50 60Hz 20A Breaker N ei fn J ame Note The AC wiring concept Disconnect the wire between the circuit AC Plug breaker amp load amp then connect the circuit breaker to the Grid input of the TP1501 amp con
4. Hybrid Solar Inverter TP1501 User Manual IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS To reduce the risk of electrical shock and to ensure safe installation and operation of Hybrid Solar Inverter please carefully read and strictly follow all safety instructions and cautionary markings CAUTION Risk of Electric Shock Plates are live Disconnect before servicing CAUTION Risk of Electric Shock Do NOT Remove Cover No User Serviceable Parts Inside Refer Servicing To Qualified Service Personnel WARNING For Continued Protection Against Risk Of Fire Connect the Grid INPUT 2 black wires with 20A circuit breaker or fuse CAUTION To reduce the risk of electric shock and fire Do not connect the Hybrid OUTPUT 2 red wires to ground CAUTION Be sure the polarity of PV wires The RED wire is connected to the positive polarity of the PV string The BLACK wire is connected to the negative polarity of the PV string The mistake may cause the damage or fire CAUTION To reduce the risk of electrical shock disconnect both AC and DC power from the Hybrid Inverter before attempting any maintenance or cleaning or working on any circuits connected to the inverter Turning off controls will not reduce this risk Internal capacitors remain charged for 5 minutes after disconnecting all sources of power WARNING All electrical installation shall be done in accordance with local and national codes ANSI NFPA 70 W
5. ing would damage internal components and should minimize exposure to rain despite her high protection class NEMA 3R The unit should be installed in a location normally inaccessible to persons Please install this unit at eye height over 1 meter so that all information and status from LED can be read easily Mount only on firm background and with correct position as below mount straight or tilted to the back never mount tilted to front Page 4 Mounting of TP1501 Place the metal fixing plate on the designated surface of the wall and mark the holes of the screw Drill the holes and hammer in the wall anchors Place the metal fixing plate again and fasten the eight screws into their respective holes Metal fixing Metal fixing plate Mount the unit on the fixing plate Be sure that the four hooks get into their respective fixtures and settle down Page 5 Placement of TP1501 Step1 The screws will bracket fixed to the wall Step2 The TP1501 are installed on the bracket Step 2 Step3 The TP1501 is fixed on the wall 3 Wiring process PV OUTPUT GRID 60 150Vdc for 110Vac output 1500W 110Vac 90 125 AC 50 60Hz 60 300Vdc for 220Vac output 3000W 220Vac OR 190 245 AC 50 60Hz WARNING Follow local electrical codes and the National Electrical Code NEC ANSI NFPA 70 Use copper conductors only with minimum 12AWG 105 C 600V wire for power grid and minimum 12AWG 105
6. liances need to be reduced dependent on the of the PV panel installed amp the sun condition Unplug some appliances to keep some important ones in this condition This is not a Grid tied PV inverter There is no risk of the PV energy fed into the grid power Hence it is sure the TP1501 make the PV panels on the rooftop energize the home appliances under the roof possible with safety amp the lowest cost The TP1501 can operate for 110Vac 50 60Hz 220Vac 50 60Hz It can automatically synchronize the voltage amp frequency of Grid Power The TP1501 Hybrid PV inverter system can be monitored remotely via software It provides users with convenient power monitoring and recording functions without the need of additional monitoring systems AC disconnect AC plug for Aircon Refrig TV and LED The traditional Air Conditioner without Inverter inside is not recommended as the Load Page 3 2 Installation A Warning All electrical installation shall be done in accordance with local codes and national odes ANSI NFPA 70 AN Warning Connecting the TP1501 to the electrical grid shall only be lt performed by qualified personnel and only after formal approval from the utility company TP1501 can be installed indoor where sufficient air circulation is available with ambient temperature less then 50C Outdoor installation should be under controlled environment where no direct sunlight would reach as excessive heat
7. nect the load to the output Page 8 of TP1501 5 Specifications items Input PV voltage Charge current Maximum PV Power MPPT Grid Voltage Grid Current Output Maximum Power Output Volatge Output Current Output waveform Quput frequency Work in PV only mode Protection Maximum Grid Voltage Minimum Grid Voltage Maximum Output current Control portion Communication port System Standby power consumption Environment Water Proof Operation temperature Storage temperature altitude humidity Compliance standard EMC Mechnical W D H mm Weight unit specification Remark 60 150v crid 0y fe 60 300v Grid 2207 fs 0 15 i O O 90 125 Yac Grid L 10V Grid 1 10V Auto detected 130 245 Yac Gnd 220Y Auto detected 0 12 Ed 3000 a v according to the Grid voltage in normal mode Pure sine wave 90 60 according to the local frequency in normal mode Page 9 6 LEDs indication G N Green LED light in Hybrid mode Blink in PV only mode 7 _ Amber LED light when system failed such as grid voltage out of range or output over current system shutdown amp will try to restart again after 1 minute Yellow LED display PV status blinking when the PV panel s maximum power point tracked Status Green Amber Yellow OUTPUT Day time blink Nighi time tyes Day time without grid blink light Night time without grid ee Fe Yolatge out of range Green l lisht Fr Output Over load Green lisht o Fe
8. r can setup the voltage amp frequency during the grid power is blackout PV only mode there are 5 options no output 110V 50Hz 110V 60Hz 220V 50Hz 220V60Hz Check the local dealer if you want to change it Page 12 How to enable the Bluetooth communication Click the right button while point to the Bluetooth icon in your PC Select the Add device option Computer will find the new Bluetooth device named HC 06 Pair HCO6 with your computer by code 1234 After the Bluetooth successfully installed Right click the HC 06 amp then select the property amp select the Hardware to find which COM port that linked with HC 06 For example COM10 or COM 27 oe i a E A logs 2015 8 7 FF 05 Aircon 2015 6 2 FF 11 Aircon exe config 2015 1 24 FF O0 _ Aircon pdb 2015 6 2 PF 1L Aircon vshost 2015 6 2 FF 11 _ Aircon vshost exe contig 2015 1724 FFO _ Aircon vshost exe manitest 2010 3 17 FF L S AquaGauge dll 2013 3 23 EF 1 8 log4net dil 2011 11 3 F 0 records 2015 8 7 05 6 Open the setting INI file of the Monitoring fold in the CD enclosed with the TP1501 package Page 13 7 Replace the COM26 by the COM port that linked with Bluetooth amp then save the file om bandrate 4bll Excel Fath Device d Deyice Polling 3 Vin Max 360 Vin Ottgetoi lin Max 15 lin OTffget i Yerid Max 300 Yerid Otfset w lerid Max 2 lerid Offtsetot Yac Max 150 Vac Uffzet il lout Max 2 lout UTfse
9. t 0 DATA Tota lPyWH 2404 95280354816 Page 14 8 Double click the Aircon COM to enable the Display program I logs 2015 8 7 FF 05 2015 6 2 FF 11 __ Aircon exe config 2015 1 24 F 0 Aircon pdb 2015 6 2 F 1L E Aircon vshost 2015 6 2 FF 11L Aircon vshost exe config 2015 1 24 FF 0 x Aircon vshost exe manitest 2010 3 17 FFL amp AquaGauge dll 2013 3 23 E 1 amp log4net dll 2011 11 3 FF 0 records 2015 8 7 FF 05 setting 2015 8 7 FF 05 ron _ _T 5 a a er eu Solar vs Grid n s 50 PY Power 58 56 wW Today Money Save 0 00 Grd Power 33065 W Total Money Save 9 45 Money per KWH 3 2 102 kalt ot SSO 81 The com po CHEN HACE r aN 9 There willbe The com port open success shown on the bottom line Page 15 The Display on Android ull 60 jg 09 30 TP1501 Solar Grid 850 00 125 00 87 17 DISCOVERY DISCONNECT HC 06 FBTO6 Sat Jun 13 09 30 25 Gib 2015 lt O u How to enable APP 1 Setup your smart phone to find Bluetooth device name HC 06 amp then pair it by code 1234 2 Install the APP program apk in your CD 3 Enabling the APP named BT the above screen will appear 4 Click Discovery amp then you will find HC 06 5 Click the HC 06 6 The information shows solar power grid power amp the ration of Solar vs grid Page 16 Trouble shooting 19 No LED active amp no output It may take abou
10. t 30 seconds for the system initialized every time when the grid power first applied After that the green LED will be active If the green LED doesn t light Check the connection of the grid power No output amp the middle amber LED active a Disconnect the output load to check if the amber LED off after one minute b Check if the input voltage is not in the range 90V 125V 190V 242V 3 Solar doesn t generate power yellow LED not active in the day time In the day time if the bottom yellow LED blinking which means the solar is generating the power If the yellow LED is not active in the day time please check the connection of the PV panels Page 17