1. 98 GAMEWELL ZNS This manual covers the installation programming and service of the ZNS and its related modules It is a supplement to the INS 2 Installation and Programming manuals P N s 70708 05 and 70709 04 OVERVIEW Description The ZNS is a microprocessor based conventional Fire Alarm Control Panel It is designed to monitor 2 to 32 conventional initiation zones and also allows 2 circuits of addressable detection or control devices The main control panel consists of an addressable INS 2 system Addition of an ZNS Common Module provides connection to the conventional zone modules INSTALLATION AND WIRING Mechanical Two cabinet sizes are available for the ZNS the smaller is used to house a 2 to 16 zone system and the larger is used on 2 to 32 zone systems 21 W x 25 5 H x 4 D 1 to 16 zones 21 W x 31 5 H x 4 D 2 to 32 zones The ZNS Common Module p n 31014 mounts in place of the INS 2 expander module and plugs into the J5 connector It is connected to the p n 31015 Zone Mother Board modules Each mother board accepts two p n 31016 two zone Conventional Input Module Refer to drawings A M1104 D M780 and D M781 for mechanical layout Wiring Both high or low current zone should be wired in accordance with NFPA 70 article 760 Maximum loop resistance should not excede 25 ohms Refer to wiring diagram A W544 for terminations Technical Manuals Online http www tech man com ZNS Installation and Operation Manual Issue
2. that it is in Trouble Low High Current Each zone of the 31016 2 zone card can be programmed for two modes of operation Operation low current and high current The module is factory set as a high current zone Low current mode is selected by removing the following resistors Odd Zone Even Zone Resistors to remove for low current operation R1 R2 R3 R21 R22 R23 The EOL resistor high current value is 4 7K ohms and the low current value is 15K ohms NOTE Low Current zones will not function with 2 wire Smoke Detectors and should be used with contact closure devices only Addressing The 31016 zone modules must be mounted from left to right If a slot is empty the system will not detect modules beyond the first open slot Zone Programming Each 31016 2 zone card has jumpers to distinguish between Class A or Class B initiating circuits There are also jumpers to program latching and non latching zones All 31016 modules are factory set for Class B latching alarm operation See the chart below for programming options Refer to drawing A M1105 For resistor locations Technical Manuals Online http www tech man com ZNS Installation and Operation Manual Issue 4 12 4 98 Programming Programming of the 31016 modules is accomplished with the INS 2 laptop software Each zone card installed requires 2 addresses regardless of wether both zones are being used or not The 31016 requires no programming of its address It is addressed automatically v
3. 4 12 4 98 COMMON CARD Indicators The ZNS common card module has one LED When first powered it flashes the version number of the firmware on the ZNS module Thereafter it will flash whenever it is responding with zone information to an INS 2 poll Default Operation Default operation is a mode that allows alarms to be sensed and automatically routed to the Signaling Circuits if for some reason the ZNS controller fails Auxiliary Power Auxiliary power is available on the Common Card from terminals A A Resetable smoke detector power is available from terminals S S This power is removed for four seconds when the system is reset Combined total current available from both A A and S S is 0 5 amps Programming The ZNS Common Card is enabled by accessing level 4 programming area of the INS 2 main board Press the F1 key until the LED above the F1 key is illuminated Output controller location C220 must also be enabled and cannot be used by any other devices This output controller location allows the ZNS common card to reset the S S output ZONE CARD Indicators Each 2 zone module has two LED s per zone one to indicate alarm and the other to indicate trouble The standard zone module has a red and yellow the supervisory zone has two yellow LED s Alarm Disconnect Each zone of the 31016 2 zone card has a disconnect switch located next to the LEDs When this switch is activated the zone will not report an Alarm but it will show
4. 5 D W1171 A W544 APPENDIX B Drawings Ass y of ZNS 16 Zones Ass y of ZNS 32 Zones Mounting Instruction Card Guide Configuring of 2 Zone Card Wiring ZNS System Wiring ZNS 2 Zone Card Technical Manuals Online http www tech man com
5. Zh Gamewell WORLDWIDE ZNS MICROPROCESSOR BASED CONVENTIONAL FIRE ALARM CONTROL PANEL 2 Installation amp Operation Manual The Gamewell Company 60 Pleasant Street Part No 71774 Ashland MA 01721 Issue 4 12 4 98 PROPRIETARY MATERIAL Technical Manuals Online http www tech man com ZNS Installation and Operation Manual Issue 4 12 4 98 The information contained in this manual is proprietary to The Gamewell Company Such information and technical drawings may not be copied or reproduced in any manner or disclosed to organizations that might be competitive to Gamewell without the express prior written consent of The Gamewell Company Technical Manuals Online http www tech man com ZNS Installation and Operation Manual Issue 4 12 4 98 GENERAL INFORMATION The Gamewell Company thanks you for choosing the ZNS Microprocessor based fire alarm control panel As with all our products we have taken great care to insure that we have provided a quality product To receive maximum benefit and many years of reliable service we would like to make the following recommendations 1 Read this manual carefully and in it s entirety before proceeding with the installation of the ZNS panel 2 Never make any connections with the power connected 3 Gamewell spends many hours testing devices that are supplied by Gamewell to be used with it s control panels to verify compatibility To maximize system performance and minimiz
6. e risk of damage to the equipment we suggest using all Gamewell Components 4 There is no substitute for proper maintenance and testing of this or any life safety product Gamewell recommends testing and maintenance of your ZNS in accordance with the guidelines set forth by the National Fire Protection Association to be done on a regular basis as a minimum 5 This manual should be stored with the ZNS panel for future reference and should not be removed providing reference to the operation and programming of the installed ZNS Thank you again for choosing Gamewell If you have any comments regarding your ZNS panel or other Gamewell products please feel free to contact us at The Gamewell Company Product Marketing Department 60 Pleasant Street Ashland MA 01721 Technical Manuals Online http www tech man com ZNS Installation and Operation Manual Issue 4 12 4 98 TABLE OF CONTENTS Overview 1 Description 1 Y INSTALLATION AND WIRING Mechanical Wiring ee Common Card Indicators Default Operation Auxiliary Power Programming t3 B2 b2 b2 P2 Zone Card Indicators Alarm Disconnect Low High Current Operation Addressing Zone Programming Programming Power Requirements WWNNNNNN Appendix A ZNS High Current Compatibility Identifier 31016 Compatible Notification Devices nab Appendix B 6 Drawings 6 Technical Manuals Online http www tech man com ZNS Installation and Operation Manual Issue 4 12 4
7. ia the ZNS by its physical location to the addresses of through 32 Additional addressable modules may be added to the addressable circuits 1 and 2 starting with address 33 JUMPER PROGRAMMING ee ees Odd Zone Even Zone Alarms Latched WIL Installed W2L Installed Alarms Not Latched WIL Removed W2L Removed Supervisory Alarms Only WIA Installed W2A Installed WIA Removed W2A Removed Zone cards are shipped with all jumpers installed Class B Alarms Latched Power Requirements The ZNS common card draws 2 mA from the 24V supply and 5 mA from the 5V supply The 31015 mother boards do not draw any power from the system Each 31016 zone card draws 0 5 mA from the 5V supply plus 6 5 mA for each trouble or alarm LED on Note that for one zone the trouble and alarm LEDs will never be on at the same time The current draw from the 24V supply for each zone on a 31016 zone card depends upon whether it is configured for hi current or low current operation lo current without detect 2 5 mA max lo current in alarm 6 mA max hi current without detectors 6 5 mA max hi current with detectors 9 1 mA max hi current in alarm 60 mA max 3 Technical Manuals Online http www tech man com ZNS Installation and Operation Manual APPENDIX A Issue 4 12 4 98 ZNS High Current Compatibility Identifier 31016 Detectors Bases Gamewell Model No Apollo Part No Qty Gamewell Model No Ap
8. ollo Part No 71033 55000 350 71036 45681 200 71034 55000 250 71086 45681 220 71035 55000 150 20 71086 LOW 45681 232 71035 160 55000 151 71086 GREEN 45681 231 71035 210 55000 152 71086 RED 45681 230 71393 45681 227 71443 55000 380 10 4 Technical Manuals Online http www tech man com ZNS Installation and Operation Manual Appendix A Cont Compatible Notification Devices Part Catalog SR 24110 HFR RSP 241575 VFR AMT 24 IS VFR SR 2475 VFR AS 2415W FR AS 2430W FR AS 2475W FR NH 12 24 R NS 2415W FR NS 2430W FR NS 2475W FR RSS 241575W FR RSSP 241575W FR RSSP 2475W FR AH 24WP R 71712 RS 2415W FR 71713 RS 241575W FR 71714 W3MT 24 VFR Part Catalog MIZ 24 R MIZ 24 W MIZ 24 LS VFR MIZ 24 IS VFR MT 24 LS VFR MT 24 MS VFR MT 24 IS VFR AS 2415 VFR AS 241575 VFR AS 24110 HFR RS 2415 VFR SR 2415 VFR RS 241575 VFR SRP 241575 VFR RSP 2430 VFR RSP 2475 VFR 71559 RS 2475 VFR 71560 RS 24110 HFR 71561 SRP 24110 HFR Technical Manuals Online http www tech man com Issue 4 12 4 98 Part Catalog RSSP 24110W FR AS 2415C FW AS 2430C FW AS 2475C FW RSS 2415C FW RSSP 2415W FR ET70 2415W FR ET70 2430W FR ET70 2475W FR ET90 24100C FW E70 241575W FR E70 2430W FR E90 2430C FW E90 24100C FW CH90 24 W CH70 241575W FR CH70 2430W FR CH70 24110W FR ZNS Installation and Operation Manual Issue 4 12 4 98 D M781 D M780 A M1104 A M110