GFK-2332V IC695ETM001HU IPI

image

Contents

1. After IP Address Changed before changing its IP address Once the local IP address has changed any existing open TCP connections are unable to normally terminate This can leave SRTP connections open until their underlying TCP connections time out If quicker recovery of the SRTP connection is needed modify the wkal_idle Advanced User Parameter to reduce the TCP keep alive timer down to the desired maximum time for holding open the broken connection Refer to TCP IP Ethernet Communications for PACSystems GFK 2224 for details RX3i CPU Time Used for Changing the Ethernet interface time via the CHTIME command does not Produced EGD Timestamps affect the timestamp value within EGD exchanges produced from this Ethernet interface The EGD timestamp value reflects the current CPU time In Series 90 70 products and the Series 90 30 CPU364 EGD timestamps are taken from the Ethernet interface and do reflect CHTIME modifications ENIU Stale Data During Run In a large PPS system running 20 ENIUs when a Run mode Store is Mode Store of EGD performed that deletes the EGD exchanges for 10 of the ENIUs the other ENIUs will see the status on their exchanges indicate consumption timeouts during the RMS At the completion of the RMS the exchanges operate normally One TTL value configuration The system accepts only one TTL value If you configure a separate TTL for all EGD groups value for each EGD group the minimum TTL value is configured for all
2. Redundancy System Client Channel COMMREQs can only be initiated from the unit that owns the Redundant IP address Therefore the user application logic should use Bit 6 in the LAN Interface Status bit area Redundant IP Active as part of their enabling logic that drives a client channel COMMREQ An idle Modbus TCP connection between a Series 90 controller and the PACSystems Ethernet Interface may be prematurely terminated There is an incompatibility between the TCP Keep Alive timer values on the PACSystems Ethernet Interfaces and Series 90 Ethernet Interfaces The default value of the keep alive timer for the Series 90 modules is set to a much higher value than for the PACSystems To keep TCP connections open between a Series 90 Ethernet Interface and a PACSystems Ethernet Interface the Series 90 Interface Advanced User Parameter wkal_time should be set to the value 750 to match that of PACSystems With this change TCP connections remain open indefinitely This also applies to SRTP Client Channels that have infrequent traffic and can be resolved by using the same technique If more than the maximum 16 supported Modbus Server Connections are attempted the TCP connection may succeed but no data may be subsequently transferred RX3i Ethernet Interface Module IC695ETMO01 IPI 15 November 2015 GFK 2332V Ethernet Operational Notes SRTP Connections Remain The Ethernet Interface does not terminate all open SRTP connections Open
3. amount of data to be written exceeds the configured size of that reference memory the command will return failure status but partial data may be written into the reference memory The amount of partial data written depends upon the starting bit memory location and the data length as follows If data starts on a byte boundary location 8 e n 1 no partial data is written If data does not start on a byte boundary location 8 n 1 and data exceeds the configured reference memory by 8 or more bits partial data is written from the starting location to the next byte boundary after the starting location If data does not start on a byte boundary location 8 n 1 and data exceeds the configured reference memory by less than 8 bits partial data is written from the stating location to the end of configured reference memory For a Write PLC Memory command this can occur when writing data into the target PLC For Read PLC Memory or Read Exchange commands this can occur when writing data received from the target controller into the local CPU memory The logic application must not use any data returned to the local CPU if the EGD command status indicates failure To avoid writing partial data to the local or remote PLC be sure bit memory data transfers do not exceed the configured reference memory sizes at the appropriate PLC Do not operate with CPU in incorrect slot The operation of the Ethernet interface is
4. in after a restart the functionality of the pushbutton is inverted When the pushbutton is later released an incorrect rising edge is detected which triggers an inappropriate module restart This does not occur on other PACSystems Ethernet products RX3i Ethernet Interface Module IC695ETMO01 IPI 11 November 2015 GFK 2332V Restrictions and Open Issues Subject Description COMMREQ Status Word value of 0x54A0 occasionally returned for EGD commands Occasionally a COMMREQ Status Word value of 0x54A0 is returned after COMMREQs for Ethernet Global Data commands when the previously transferred command has experienced retries in the network Executing the COMMREQ again results in successful transfer of the command Modbus TCP channel aborted during power cycle Controller response timeout errors 8 08 in Ethernet exception log under extremely heavy SRTP traffic After powering up an RX3i running Modbus TCP client channels the establish connection occasionally fails because the server rejects the open request from the client The connection will then succeed if the application retries the open when it sees a 0x9690 or OxAA90 response to an open request or to the first write request Under extremely heavy SRTP traffic conditions the Ethernet Interface may log an event in the Ethernet exception log Event 8 Entry 2 08H indicating an overload condition This error terminates the SRTP connection If this ev
5. is added or modified by a Run mode Store the exchange will not be produced until one production period of time has elapsed after the completion of the run mode store Station Manager PING commands When initiating ICMP echo requests from the PLC via the Station Manager s PING command the operation occasionally fails and an exception is logged Event eH Entry 2 6H Station Manager referr tally The EGD Station Manager referr tally may be incremented twice when an exchange timeout occurs Exchange status word reporting works correctly and is not affected wkal_idle AUP parameter should not allow zero Zero is allowed for the wkal_idle TCP keepalive timer but it is an invalid value TCP connection may timeout early if the timeout is set greater than 10 minutes If the TCP connection timeout is set higher than 10 minutes the connection may timeout before the configured value The connection timeout is derived from three AUP parameters wkal_idle wkal_cnt 1 e wkal_intvl Ethernet Operational Notes Ethernet Operational Notes Remote Station Manager access is disabled until Station manager password is changed Changing the default Station Manager password is strongly recommended User should change the station manager password to other than the default password The remote station manager access is disabled until the station manager password is changed to other than the d
6. EGD groups Protection against attack on When the FTP connection is not in use the configuration parameter FTP server Maximum FTP Server Connections should be set to 0 This protects against attack on FTP server 1 800 433 2682 1 434 978 5100 GE Intelligent Platforms www ge ip com
7. GFK 2332V November 2015 The Ethernet Interface Module IC695ETM001 connects a PACSystems RX3i controller to an Ethernet network It enables the RX3i controller to communicate with other PACSystems equipment and with Series 90 and VersaMax controllers The Ethernet Interface provides Transmission Control Protocol and Internet Protocol TCP IP communications with other control systems host computers running the Host Communications Toolkit or programmer software and computers running the TCP IP version of the programming software These communications use the Service Request Transport Protocol SRTP Modbus TCP and Ethernet Global Data EGD protocols over a four layer TCP IP Internet stack Features of the RX3i Ethernet Interface include Full programming and configuration services Firmware upgrades from the RX3i CPU using the WinLoader software utility which is supplied with updates to the Ethernet Interface software Periodic data exchange using Ethernet Global Data EGD EGD Commands to read and write controller and EGD exchange memory over the network TCP IP communication services using SRTP Support for SRTP Channels Modbus TCP Server and Modbus TCP Client Built in Station Manager for on line supervisory access to the Ethernet Interface Dedicated Station Manager port Two auto sensing 10Base T 100Base TX RJ 45 shielded twisted pair Ethernet ports for direct connection to either PACSys
8. Series 90 30 CPU should not be placed in an RX3i rack Release 3 60 of the PACSystems Ethernet Interface adds Modbus TCP Client Channels capability It supports Modbus Conformance Class 0 function codes 3 and 16 Conformance Class 1 function codes 1 2 4 5 6 and 7 and Conformance Class 2 function codes 15 22 23 and 24 PACSystems Ethernet supports 32 client connections shared between all client protocols For example if 16 client connections are used for SRTP channels there are 16 client connections available for Modbus TCP channels Any given channel can be assigned to only one protocol at a time Proficy Machine Edition Logic Developer 5 8 or later must be used to perform Run mode Store of EGD exchanges Proficy Machine Edition Logic Developer 5 7 or later must be used for Release 5 00 new features Proficy Machine Edition Logic Developer 5 5 Service Pack 2 or later must be used for Release 4 00 new features Proficy Machine Edition Logic Developer 5 0 Service Pack 3 or later must be used to program the RX3i CPU for Modbus TCP Server operation CIMPLICITY Plant Edition 6 1 Service Pack 1a with Update 040204 _s90tcp_6101 or Service Pack 2 or later must be used for Ethernet communications with PACSystems New Features and Enhancements in This Release No new features or enhancements are provided in this hardware release Problems Resolved by This Release This hardware release addresses a component obsolescence issue There
9. ackplane such as IC695CHS007 CHS012 or CHS016 The ETM001 supports insertion removal while power is applied to the system hot swap This module is compatible with all RX3i CPU models 1 RX3i rack power may be off or on hot insertion 2 Holding the module firmly align the module with the correct slot and connector then swing the module down until the module s connector engages the backplane s backplane connector Visually inspect the module to be sure it is properly seated 3 Insert the two provided M3x5mm machine screws through the module s bottom bracket into threaded holes in the bottom of the backplate and screw them several turns using a 1 Phillips screwdriver Tighten to 0 7 N m 6 in Ibs Related Documents For additional information about the Ethernet Interface Module refer to the following publications GFK 2314 PACSystems RX3i System Manual GFK 2224 TCP IP Ethernet Communications for PACSystems GFK 2225 PACSystems TCP IP Communications Station Manager Manual Additional Support For support and information visit GE Intelligent Platforms website at http www ge ip com The files for this manual and other related documentation are available there Additional region and language specific websites and telephone numbers are found there as well 6 RX3i Ethernet Interface Module IC695ETMO01 IPI GFK 2332V November 2015 Important Product Information for this Release This hardware release addresses a comp
10. any previous changes made with it are no longer effective RX3i Ethernet Interface Module IC695ETMO01 IPI 13 November 2015 GFK 2332V Ethernet Operational Notes Configuration of IP Address is The Ethernet Interface cannot operate on a network until a valid IP required before using Ethernet address is configured The Ethernet addressing information must be communications configured prior to actual network operation or to recover from inadvertent changes to the Ethernet addressing data at the Ethernet Interface Use one of the following methods to initially assign an IP address Connect a serial terminal to the Interface s Station Manager port Then use the CHSOSW command to enter the desired IP address For details see PACSystems TCP IP Communications Station Manager Manual GFK 2225 Temporarily assign an IP address to the module using the SetIP tool over the Ethernet network For details see TCP IP Ethernet Communications for PACSystems GFK 2224 The Ethernet Interface automatically obtains a temporary IP Address from a BOOTP server on the network For details see TCP IP Ethernet Communications for PACSystems GFK 2224 Once a temporary IP address has been set up the Ethernet Interface can be accessed over the network by the Machine Edition programming software The programmer should then be used to configure the proper IP address for the Ethernet Interface Default IP address 0 0 0 0 The default IP address val
11. are no changes to form fit or function RX3i Ethernet Interface Module IC695ETMO01 IPI 7 November 2015 GFK 2332V Release History Release History Firmware Catalog Number Version Date Comments IC695ETMO01 HU 6 31 Nov 2015 Firmware release 6 31 IC695ETM001 HU provides a Field Upgrade Kit to address an issue identified with IC695ETM001 GT where the module can unexpectedly go into firmware update mode Ethernet OK LAN OK and Log Empty LEDs blink in unison While in firmware update mode the module is unresponsive to Ethernet traffic IC695ETMO01 HU Firmware Nov 2014 This hardware release IC695ETM001 HU addresses an 6 30 issue identified with IC695ETM001 GT where the module can unexpectedly go into firmware update mode Ethernet OK LAN OK and Log Empty LEDs blink in unison While in Boot 3 71 firmware update mode the module is unresponsive to Ethernet traffic IC695ETMO001 GT 6 30 Nov 2014 This hardware release addresses a component obsolescence issue There are no changes to form fit or function IC695ETMO01 FT 6 30 Oct 2014 Firmware version 6 30 Fixes the following issues e In very rare conditions closing Modbus or SRTP session can result in a 3 5 blink code e With unicast SNTP the ETM could lose server lock and then 1 never show any server as locked again and 2 not attempt to switch to another server In v6 30 1 Lock status can be restored when a server becomes consistent and 2 SNTP wi
12. ay be ignored Module intermittently unresponsive after reset Intermittently when the module is restarted by using the pushbutton or Station Manager command the module will blink its OK LED for 5 minutes before completing the restart After the restart is complete the module fails to communicate with the CPU module The remedy is to power cycle the PLC A890 Commreg status after multiple Modbus open command attempts When using a Commreg to open a Modbus TCP Channel to a remote server if the initial Commreg returned an AA90 status then future Open Commands may return A890 status This indicates that local networking resources have been consumed and are not available for further connection attempts If this occurs the application must wait at least 60 seconds before making the next connection attempt This will allow networking resources to be released and made available for the next Modbus Open Command Modbus TCP request packets The Modbus TCP server expects to receive each Modbus TCP request in a separate TCP packet If multiple requests are sent in a single packet the server may or may not send a response to each request If responses are sent to the client they will be sent in separate TCP packets 12 GFK 2332V RX3i Ethernet Interface Module IC695ETMO01 IPI November 2015 Restrictions and Open Issues Subject EGD production delayed after RMS of EGD Description When a produced EGD exchange
13. disrupted if the RX3i CPU is placed in a slot other than the one in which it is configured Various Ethernet exception log events may occur such as Entry 2 Entry 2 30 or 35 or 39 or 1e or 1f or Entry 8 Entry 2 b No CPU fault logged when Ethernet interface in fatal blink code EGD I O has unexpected variability under heavy load The CPU does not log any Controller or I O Faults when the Ethernet Interface has a fatal blink code The application should monitor the LAN interface OK status bit to detect loss of module EGD I O has intermittent unexpected variability under heavy load For a Produced Exchange EGD samples may occasionally be delayed by as much as a production period or more Clear of large hardware configurations may cause log event 08 20 A Log event 08 20 may occur when very large hardware configurations are cleared and transfers are active on other Server connections This log event can be safely ignored Reset pushbutton Reset pushbutton action is different from other PACSystems Ethernet products On the RX3i Ethernet module the state of the pushbutton when the module powers up can change the behavior of the Restart pushbutton Under normal operation a pushbutton press produces a rising edge signal that triggers a module restart However if the pushbutton is pressed when power is activated either by pressing the pushbutton before turning power on or by continuing to hold the pushbutton
14. efault password The station manager password can be changed using an AUP file Refer to Appendix A Configuring Advanced User Parameters in TCP IP Ethernet Communications for PACSystems User s Manual GFK 2224K GE Intelligent Platforms strongly recommends that you change the Station Manager password to a value other than the default Before a configuration has been stored to the CPU you can change the password by using the CHPARM command to modify the Advanced User parameter AUP stpasswd For details on using this command refer to the Station Manager Manual GFK 2225 It is not recommended that you change any AUP other than stpasswd 1 Use the current password to access the Modify level of the Station Manager The default password is system Change the password Example chparm stpasswd newpass Restart the Ethernet interface or cycle power Changes made via the CHPARM command do not take effect until the Ethernet interface is restarted or power is cycled Advanced User Parameters are saved in non volatile memory Changes made by the CHPARM command are retained over restart and power cycles until changed again by the CHPARM command To permanently change the Station Manager password you must change the stpasswd parameter in the AUP file See the TCP IP Ethernet Communications for PACSystems User s Manual GFK 2224 for details After the CPU configuration has been stored into the CPU the CHPARM command is prohibited and
15. en the PING is aborted but subsequent REPP commands give the results of the last successfully terminated PING Multiple log events The Ethernet Interface sometimes generates multiple exception log events and Controller Fault Table entries when a single error condition occurs Under repetitive error conditions the exception log and or Controller Fault Table can be completely filled with repetitive error messages Intermittent SNTP loss of synchronization Under moderately heavy EGD traffic load the Ethernet Interface may occasionally lose synchronization with its SNTP time server and generate exception log event 29 entry 2 bH SRTP communication delays Average latency of communications on SRTP channels may vary considerably due to TCP retransmissions SRTP client applications should be designed to take this variance into account In particular SRTP client applications migrating from Series 90 SRTP servers to PACSystems may need to lengthen SRTP timeout parameters Spurious Ethernet Failure error On rare occasions the error Module hardware fault may be reported on the Ethernet daughterboard The corresponding fault in the exception log is Event 1 followed by text Ethernet failure This fault is a nuisance fault and may be ignored Spurious Ethernet fault In rare instances after power cycle the Ethernet Interface may log the following fault Event 28H Entry 2 000eH This fault can be safel
16. ent appears either the traffic load should be reduced or the application should use an alternate communications method to verify that critical data transfers were not lost due to the overload SRTP channel transfers may take up to 20 seconds after power cycle When SRTP communications are interrupted by a power cycle the Ethernet interface may require up to 20 seconds to reestablish TCP connection used for SRTP communications rmdir Station Manager command does not work for multi level directory path The rmdir Station Manager command does not operate properly with a multi level directory path Instead first change to the parent directory then delete the target directory without specifying a path For example the rmdir dir1 dir2 results in RMDIR Failed dir1 dir2 does not exist Instead first do cd dir and then rmdir dir2 Intermittent Ethernet log event 8H 15H after power cycle When starting after a power cycle the Ethernet Interface may intermittently log an exception entry 8H Entry 2 15H Entry 3 0000H Entry 4 0OaaH This exception is benign and may be ignored Intermittent Modbus TCP Server log events when using killms Station Manager command When using the killms Station Manager command to manually terminate an active Modbus TCP server connection the following Modbus TCP errors may occur in the Ethernet exception log Event 2fH Entry 2 209H 212H 21bH or 221H These errors m
17. ll attempt to switch to another server when the current server becomes inconsistent e The ETM clock can drift away from the locked on server s time at a several msec day rate e Removed an extraneous log event The extraneous log event would occur 1 on battery backed power up and 2 store of hardware configuration when the user configures the ETM for SNTP but does not configure the ETM for daylight savings time correction IC695ETMO01 FS 6 21 Aug 2014 Replaces the module s plastic housing with a metal case improving noise immunity reducing emissions and increasing the mechanical robustness of the product No change to the module s firmware or functionality C695ETMO001 ESt 6 21 Jan 2014 Ethernet Firmware version fixes an issue with calculating DST correction in the European Union when SNTP is enabled C695ETMO01 ER 6 20 Jul 2013 Adds support in SNTP for local time zones and daylight savings time and resolves the field issues described on page 6 C695ETMO01 EPt 6 14 Jul 2012 Resolves an issue with a spurious blink code being displayed during SRTP communications with CIMPLICITY Plant Edition software 8 RX3i Ethernet Interface Module IC695ETMO01 IPI GFK 2332V November 2015 Release History Firmware Catalog Number Version Date Comments C695ETMO01 EN 6 13 Apr 2012 Addresses a field issue and a product security issue Fo
18. nspect all shipping containers for damage If any part of the system is damaged notify the carrier immediately The damaged shipping container should be saved as evidence for inspection by the carrier As the consignee it is your responsibility to register a claim with the carrier for damage incurred during shipment GE Intelligent Platforms will fully cooperate with you however should such action be necessary After unpacking the RX3i equipment record all serial numbers Serial numbers are required if you should need to contact Customer Care during the warranty period All shipping containers and all packing material should be saved should it be necessary to transport or ship any part of the system Verify that all components of the system have been received and that they agree with your order If the system received does not agree with your order contact Customer Care Installation Location This product is intended for use with the RX3i system Its components are considered open equipment having live electrical parts that may be accessible to users and must be installed in an ultimate enclosure that is manufactured to provide safety As a minimum the enclosure shall provide a degree of protection against solid objects as small as 12mm e g fingers This equates to a NEMA UL Type 1 enclosure or an IEC60529 IP20 rating providing at least a pollution degree 2 environment For details about installing RX3i rack systems refer to GFK 2314 If
19. onent obsolescence issue There are no changes to form fit or function Updates The IC695ETMO01 is field upgradeable using the firmware upgrade utility To upgrade an existing ETM001 to firmware version 6 31 you will need the upgrade kit 44A753032 G17 which can be downloaded from http www ge ip com support The hardware cannot be upgraded in the field Functional Compatibility Functional Compatibility Hot Swap requires CPU Do not remove or insert the IC695ETM001 while powered unless the CPU is firmware 2 51 running firmware release 2 51 or higher This firmware is available in upgrade kit 44A7522290 G01 SRTP and EGD performance in the Rx3i differs slightly from the Series 90 30 Each RX3i Ethernet Interface supports a greater number of SRTP connections and EGD exchanges The RX3i currently has several SRTP and EGD operational restrictions compared to the Series 90 30 When migrating Series 90 30 Ethernet applications to the RX3i please carefully read the Ethernet Operational Notes The Series 90 30 LAN Interface Module IC693CMM321 is not supported by the SRTP and EGD performance differs from Series 90 30 Series 90 30 LAN Interface module IC693CMM321 not supported by RX3i Modbus TCP support Programmer version requirements CIMPLICITY Plant Edition version requirements RX3i and should not be placed in an RX3i rack Series 90 30 CPUs with embedded LAN Interface IC693CPU364 and IC693CPU374 like any
20. property of their respective owners Copyright 2013 2015 by General Electric Company All Rights Reserved 2 RX3i Ethernet Interface Module IC695ETMO01 IPI GFK 2332V November 2015 IC695ETM001 Specifications Ethernet processor speed 200 MHz Connectors Station Manager RS 232 Port 9 pin female D connector Two 10BaseT 100BaseTX Ports 8 pin female shielded RJ 45 LAN IEEE 802 2 Logical Link Control Class IEEE 802 3 CSMA CD Medium Access Control 10 100 Mbps Number of IP addresses One Number of Ethernet Port Two both are 10BaseT 100BaseTX with auto sensing RJ 45 connection Connectors Embedded Ethernet Switch Yes Allows daisy chaining of Ethernet nodes Serial Port Station Manager Port RS 232 DCE 1200 115 200 bps Refer to the PACSystems RX3i System Manual GFK 2314 for product standards and general specifications Ethernet Interface Status Bits Note Unless LAN Interface OK Status Bit 16 is set the other status bits are invalid LAN Interface Status Bits 1 Port 1A full duplex 2 Port 1A 100Mbps 3 Port 1B full duplex 4 Port 1B 100 Mbps 5 Network Time Locked 6 Redundant IP address is active 7 8 Reserved 9 Any Channel Error error on any channel 10 12 Reserved 13 LAN OK 14 Resource problem 15 Module Overtemperature 16 LAN Interface OK Channel Status Bits Two for each channel 17 Channel 1 Status SRTP Data Transfer 18 Channel 1 Stat
21. pter 1 a heavy EGD and or SRTP load can block Station Manager operation If more than 24 SRTP Server connections are established simultaneously EGD Production may be briefly delayed for each connection after the 24th when the connections are first made after power is applied If EGD consume acceleration has been disabled then EGD Consumption is also delayed The delay only occurs once when the SRTP Server connection is established for the first time after Powerup No delay is experienced for the first 24 SRTP Server connections Very heavy EGD production and or consumption at a server device may cause EGD command timeout errors when another device attempts to send EGD commands to that server If EGD commands must preempt normal production you may set the gcmd_pri Advanced User Parameter to 2 see GFK 2224 Appendix A Note that by doing so EGD exchange production may be delayed The application timeouts within SRTP Channels also include the time needed to establish and maintain the underlying network and STRP connection Examples are establishing the TCP connection for a new channel establishing communication with the remote device and TCP retransmissions during Channel operations If the time needed for TCP connection establishment or maintenance exceeds the user specified channel application timeout values an application timeout will occur Channel application timeouts are temporary errors the channel continues to run In a
22. r details refer to GFK 2332M C695ETMO001 EM 6 12 Dec 2011 Disables several unnecessary services in the firmware that otherwise could result in disruption of system operation and or data corruption For details refer to GFK 2332L C695ETMO001 ELT 6 11 Nov 2011 Resolves an issue with missed EGD samples For details refer to GFK 2332K C695ETMO001 EK 6 10 Sep 2011 For problems resolved refer to GFK 2332J C695ETMO01 EJ 6 00 Sep 2009 Adds an SRTP inactivity timeout for better recovery from lost communication with the programmer For details and problems resolved refer to GFK 2332H C695ETM001 EH 5 51 Jan 2009 Adds new diagnostics capabilities For details and problems resolved refer to GFK 2332G Hardware version Ex updates the IC695ETM001 for RoHS compliance C695ETM001 DG 5 50 May 2008 Adds ability to modify produced and consumed EGD exchanges during run mode store For problems resolved refer to GFK 2332F C695ETM001 DF 5 01 Dec 2007 For problems resolved see GFK 2332E C695ETM001 DE 5 00 Aug 2007 Hardware changes to improve performance during hot swaps For additional new features and problems resolved refer to GFK 2332D C695ETM001 CD 3 81 May 2006 Added support for eight Ethernet interfaces in the RX3i main backplane For details and problems resolved refer to GFK 2332C C695ETMO001 CC 3 60 Nov 2005 Added support for Modbus TCP client and Ethernet plug in applications For details and problems resol
23. tems RX3i IC695ETMO01 HU Ethernet Interface Module Module Status Indicator O ETHERNET OK LEDs ETHERNET OK LAN OK O Lanok LOG EMPTY O Loc ewpry Reset ETM001 pushbutton ETHERNET RESTART Station Manager RS 232 port D sub 9 pin female connector 000991002FE5 Pin 1 MAC Ethernet ports RJ 45 connectors 10 100 Mbps ETHERNET Bottom bracket a 10BaseT or 100BaseTX IEEE 802 3 network without an external transceiver There is only one interface to the network only one Ethernet MAC address and only one IP address Internal network switch with Auto negotiate Sense Speed and crossover detection Recessed Ethernet Restart pushbutton permits manually restarting the Ethernet firmware without power cycling the system LEDs Ethernet OK LAN OK Log Empty individual port activity and speed LEDs Configurable stand alone Redundant IP addressing which allows a single IP address to be assigned to corresponding Ethernet modules in two different controllers The Redundant IP address is configured in addition to the normal unique IP address of each Ethernet module Under application logic control only the Ethernet module in the active unit can use the Redundant IP address Time synchronization to SNTP Time Server on Ethernet network when used with Release 5 00 or later CPU module Indicates a trademark of General Electric Company and or its subsidiaries All other trademarks are the
24. ue 0 0 0 0 whether obtained from HW attempts to set IP address Configuration or backup configuration causes the Ethernet Interface to via BOOTP request a temporary IP address from a BOOTP server device on the network LAN must be tree not ring The two Ethernet network ports on the PACSystems RX3i Ethernet Interface must not be connected directly or indirectly to the same network device The hub or switch connections in an Ethernet network must form a tree and not a ring otherwise duplication of packets and network overload may result In this situation the RX3i Ethernet modules will continually reset Reporting of duplicate IP The PACSystems RX3i does not log an exception or a fault in the Controller address Fault Table when it detects a duplicate IP address on the network Multiple zero period EGD If more than one EGD produced exchange is configured for a production exchanges may not produce period of zero the exchanges may not produce similar numbers of similar numbers of samples samples Due to the way that scheduling occurs when multiple exchanges are scheduled as fast as possible some zero period exchanges may produce significantly more samples than others For more consistent EGD production configure the produced EGD exchanges with non zero production periods Changing IP address while Open SRTP Server connections established with a remote SRTP client are SRTP connection open may not terminated as expected when the R
25. us SRTP Channel Error 79 Channel 32 Status SRTP Data Transfer 80 Channel 32 Status SRTP Channel Error RX3i Ethernet Interface Module IC695ETMO01 IPI 3 November 2015 GFK 2332V Indicator Light Emitting Diodes LEDs LED State Indicates ETHERNET OK Fast Blink LAN OK O Off Performing Diagnostics LOG EMPTY O Off ETHERNET OK Slow Blink 7 l AN OK O off Waiting for Ethernet configuration j from CPU LOG EMPTY O Off ETHERNET OK Slow Blinkt P LAN OK O On Traffic Off Lay Waiting for IP Address LOG EMPTY Slow Blinkt ETHERNET OK O On LAN OK 0 On Traffic Off Operational LOG EMPTY O On Off ETHERNET OK Blink error code we pore es a ardware failure See chapter o o a z for blink code definitions ETHERNET OK E Slow Blinkt t All LEDs blink in AN OK E Slow Blinkt Hinon parem same Firmware Update g D e while awaiting or Field Wiring Station Manager rede Port Pin Daae ah ie sumei oretan Description N Data Carrier Detect n eco Data Receive Data Data Set Ready Signal Ground Data Terminal Ready Clear to Send Ready to Send Ring Indicator t Pin 1 is at the bottom right of the Station Manager port connector as viewed from the front of the module 4 RX3i Ethernet Interface Module IC695ETMO01 IPI GFK 2332V November 2015 Hardware Installation Initial Checks Upon receiving your RX3i equipment carefully i
26. ved refer to GFK 2332B C695ETM001 AB 3 00 Apr 2005 For new features and problems resolved refer to GFK 2332A C695ETM001 AA 2 51 Aug 2004 Initial release t Available only as an upgrade kit Restrictions and Open Issues Restrictions and Open Issues Subject Description Number of SRTP requests tallied may vary When running multiple SRTP client channels the number of requests as reported by the client and the server may differ between the connections SRTP connections remain open after IP address changed The Ethernet Interface does not terminate all open SRTP connections before changing its IP address If the local IP address has changed any existing open TCP connections are unable to normally terminate This can leave SRTP connections open until their underlying TCP connections time out If quicker recovery of the SRTP connection is needed modify the wkal_idle Advanced User Parameter to reduce the TCP keep alive timer to the desired maximum time for holding open the broken connection Refer to TCP IP Ethernet Communications for PACSystems GFK 2224 for details RX3i Ethernet Interface Module IC695ETMO01 IPI 9 November 2015 GFK 2332V Restrictions and Open Issues Subject Description REPP does not save results of aborted PING The Station Manager REPP command does not retain the results of a PING that is aborted due to error Results are reported wh
27. x7i s IP address is changed generate log events typically by storing a new HW Configuration to the RX7i A Series 90 SRTP client SRTP channels reports either a 9690H or 0190H status the SRTP connection may remain open until the connection is terminated as a result of a client timeout Please refer to Open Ethernet Problems Internal Problem ID Code CR 1434 for more information Series 90 30 datagram Series 90 30 format datagrams are supported but cannot access P or restrictions L memory 14 GFK 2332V changed Heavy load can block Station Manager One time delay of EGD Production and possibly Consumption if more than 24 SRTP Server connections are started simultaneously Very heavy EGD production consumption at server may cause EGD command timeouts SRTP Application Timeouts must accommodate network connection overhead Client Channels and Redundant IP Idle Modbus TCP connection between a Series 90 and a PACSystems may be prematurely terminated Attempt to open 17 or more Modbus server connections may appear successful RX3i Ethernet Interface Module IC695ETMO01 IPI November 2015 Ethernet Operational Notes Advanced User Parameter wsnd_buf should not be The Advanced User Parameter wsnd_buf should not be changed Changing this value may cause the LAN LED to go out and the Ethernet Interface to drop connection As explained in PACSystems TCP IP Station Manager Manual GFK 2225 Cha
28. y ignored Unexpected EGD COMMREQ status EGD Commands may return COMMREQ Status 9590H internal error instead of the expected B190H Can t locate remote node when unable to locate a remote device on the network Very heavy EGD production consumption at server may cause EGD command timeouts Very heavy EGD production and or consumption at a server device may cause EGD command timeout errors when another device attempts to send EGD commands to that server If EGD commands must preempt normal production you may set the gcmd_pri Advanced User Parameter to 2 see GFK 2224 Appendix A Note that by doing so EGD exchange production may be delayed SRTP server errors can cause timeouts at channel client The SRTP Server in the PACSystems Ethernet Interface can encounter various errors if a remote Series 90 client takes down an SRTP connection and then establishes a new connection This can cause unexpected channel timeout errors 0190H or 0290H at the client The SRTP server errors in the Ethernet exception log are identified as Event 2 Entry 2 may be OO1cH or 0021H 10 GFK 2332V RX3i Ethernet Interface Module IC695ETMO01 IPI November 2015 Restrictions and Open Issues Subject EGD command range failure can write partial data to controller bit memory Description When an EGD Command attempts a write operation to a bit mode reference memory range l Q T M SA SB SC where the
29. you need technical help contact Technical Support For phone numbers and email addresses see the back cover of this Guide Installation in Hazardous Areas The following information is for products bearing the UL marking for Hazardous Areas or ATEX marking for explosive atmospheres CLASS 1 DIVISION 2 GROUPS ABCD e This equipment is an open type device and is meant to be installed in an enclosure suitable for the environment that is only accessible with the use of a tool e Suitable for use in Class Division 2 Groups A B C and D Hazardous Locations or nonhazardous locations only A Warning EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS DIVISION 2 A Warning WHEN IN HAZARDOUS LOCATIONS TURN OFF POWER BEFORE REPLACING OR WIRING MODULES AND A Warning DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS A Warning EXPLOSION HAZARD USB PORT IS ONLY FOR USE IN NONHAZARDOUS LOCATIONS DO NOT USE UNLESS AREA IS KNOWN TO BE NON HAZARDOUS ATEX Zone 2 This product must be mounted in an enclosure certified in accordance with EN60079 15 for use in Zone 2 Group IIC and rated IP54 The enclosure shall only be able to be opened with the use of a tool RX3i Ethernet Interface Module IC695ETMO01 IPI 5 November 2015 GFK 2332V Module Installation The ETMO01 must be installed in the main CPU rack of an RX3i system using a Universal B