Home

PowerMonitor 5000 Unit, Firmware Revision 4.010

image

Contents

1. CORRECTED Default setting for Relative_Setpoint_Intvl_m was changed from 1 to 60 CORRECTED Configuration TriggerData_Log Trigger Data_Parameter_1 no longer accepts a value of 0 CORRECTED Data Log and Trigger Data Log files that are created with firmware revisions before 3 28 could not be read via CIP CORRECTED Large Data and Energy Log files were generated when 3600 was not evenly divisible by the logging interval Rockwell Automation Publication 1426 RN001D EN P September 2015 PowerMonitor 5000 Unit Firmware Revision 4 010 3 Firmware Revision 3 028 CORRECTED In the Status Alarms data table reserved elements 3 and 4 were removed The entire table shifts up by two words for example changing element 5 to element 3 This affects the data values when reading from FactoryTalk EnergyMetrix software version 2 0 or from a controller CORRECTED In the Status Alarms data table Bit 6 of Metering Status element 3 indicated that wiring diagnostics was always active CORRECTED Alarm Codes in the Alarm Log csv file sometimes incorrectly appeared as large numbers for example 4 3 E 09 CORRECTED Logic Gate input status was incorrectly reported as a large number for example 4 294967E 09 in the LoggingResults TriggerData_Header data table if the Logic Gate input was inverted CORRECTED In the Home web page the tag Upgrade Options was changed to Original Catalog Number CORRECTED Clearing a log file
2. 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1426 RN001D EN P September 2015 Supersedes Publication 1426 RN001B EN P September 2013 Copyright 2015 Rockwell Automation Inc All rights reserved Printed in the U S A
3. Changed the maximum length of the General System Configuration table from 224 bytes to 200 bytes to be compatible with the DeviceNet network maximum connection size Increased the maximum internal I O connection rate from 100 ms to 10 ms Corrected Anomalies This firmware revision includes corrected anomalies from the previous revision Firmware Revision 4 010 CORRECTED When 30 or more parameters are configured in the Data Log DataLog_Parameter_31 displays the configured parameter value and data that is associated with DataLog_Parameter_21 when read via CIP communication or FactoryTalk EnergyMetrix software CORRECTED When the Data Log interval is configured to a number that is not evenly divisible into 3600 the Data Log records are not logged at the configured interval CORRECTED The Metering Data Snapshot Parameter List for Group 2 shows L1 through L3 VA rather than kVA The parameter index range is 16834 18636 Data are correctly presented in kVA CORRECTED After executing a Restore Factory Defaults command transient waveforms are occasionally captured without a corresponding event in the Power Quality Log CORRECTED The CIP Electrical Energy Object returns data incorrectly in response to a Get_Attributes_All service request Bytes 0 5 are swapped with bytes 10 15 Firmware Revision 3 030 CORRECTED The PowerMonitor 5000 timeout and reset issue that occurred 49 days after continuous uninterrupted operation
4. Release Notes AB Allen Bradley PowerMonitor 5000 Unit Firmware Revision 4 010 Catalog Numbers 1426 M5E 1426 M5E DNT 1426 M5E CNT 1426 COMM DNT 1426 COMM CNT 1426 M6E 1426 M6E DNT 1426 M6E CNT 1426 M8E 1426 M8E DNT 1426 M8E CNT Enhancements This firmware revision includes new features Firmware Revision 4 010 Introduced support for the PowerMonitor 5000 Add on Profile AOP for use with Studio 5000 Logix Designer application IMPORTANT The PowerMonitor 5000 Add on Profile is not included in the firmware update and must be downloaded separately for installation in Logix Designer application Firmware Revision 3 030 There are currently no new enhancements in this firmware revision Firmware Revision 3 028 Introduced the PowerMonitor 5000 M8 unit with advanced power quality capabilities including the following Flicker measurement Sub cycle transient capture Harmonic magnitude and angle up to the 127th order Interharmonics harmonic and interharmonic groups up to the 50th order Firmware Revision 2 050 e Introduced optional ControNet network communication card for the MS and M6 units e Introduced the PowerMonitor 5000 M6 unit with additional capabilities including power quality measurements Rockwell Allen Bradley Rockwell Software Automation 2 PowerMonitor 5000 Unit Firmware Revision 4 010 Firmware Revision 2 045 Introduced optional DeviceNet network communication card
5. Windows Server 12 If a value of 0 is configured for the PT or CT configuration parameters incorrect metering values are displayed Occasionally when external power source outputs are turned off the MeteringResults RealTime_VIF_Power table returns small non zero values on the order of 3 39772E 10 When a PowerMonitor 5000 unit is upgraded to an M8 model Voltage and Current TID thresholds are incorrectly initialized To avoid spurious power quality events being written to the Power Quality log you have to change the values of these parameters in the Configuration Power_Quality table or web page to the correct defaults as follows IEEE1159_Voltage_TID_Limit_ 5 JEEE1159 Current TID Limit 10 Download Firmware The latest PowerMonitor 5000 firmware is found at the following website http compatibility rockwellautomation com Pages MultiProductDownload aspx From the Category pull down menu choose Energy Monitoring Additional Resources These documents contain additional information concerning related products from Rockwell Automation Resource Updating the Firmware Revision for PowerMonitor 5000 Units Installation Instructions publication 1426 IN004 Description This document provides instructions on how to update your firmware revision PowerMonitor 5000 Unit Catalog Number Upgrade Installation Instructions publication 1426 IN005 This document provides instructions on how to upgrade you
6. ber call the phone number above to obtain one to your distributor to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Rockwell Automation maintains current product environmental information on its website at http www rockwellautomation com rockwellautomation about us sustainability ethics product environmental compliance page Allen Bradley Rockwell Software Rockwell Automation ControlFLASH FactoryTalk EnergyMetrix and PowerMonitor ate trademarks of Rockwell Automation Inc ControlNet and DeviceNet are trademarks of ODVA Inc Trademarks not belonging to Rockwell Automation are property of their respective companies gt ging property pP p Rockwell Otomasyon Ticaret A S Kar Plaza Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90 216 5698400 www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663
7. r catalog number PowerMonitor 5000 Unit Optional Communication Modules Installation Instructions publication 1426 IN002 This document provides instructions on how to install or replace an optional communication module on a PowerMonitor 5000 unit PowerMonitor 5000 Unit User Manual publication 1426 UM001 Provides installation instructions wiring diagrams configuration and specifications for PowerMonitor 5000 units ControlFLASH Firmware Upgrade Software User Manual publication 1756 UM105 This manual describes how to use the ControlFLASH software to upgrade device firmware Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Provides general guidelines for installing a Rockwell Automation industrial system Product Certifications website http www ab com Provides declarations of conformity certificates and other certification details You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Allen Bradley distributor or Rockwell Automation sales representative Rockwell Automation Publication 1426 RN001D EN P September 2015 PowerMonitor 5000 Unit Firmware Revision 4 010 5 Notes Rockwell Automation Publication 1426 RN001D EN P September 2015 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using i
8. ts products At http www rockwellautomation com support you can find technical and application notes sample code and links to software service packs You can also visit our Support Center at https rockwellautomation custhelp com for software updates support chats and forums technical information FAQs and to sign up for product notification updates In addition we offer multiple support programs for installation configuration and troubleshooting For more information contact your local distributor or Rockwell Automation representative or visit http www rockwellautomation com services online phone Installation Assistance Ifyou experience a problem within the first 24 hours of installation review the information that is contained in this manual You can contact Customer Support for initial help in getting your product up and running United States or Canada 1 440 646 3434 Outside United States or Canada Use the Worldwide Locator at http www rockwellautomation com rockwellautomation support overview page or contact your local Rockwell Automation representative New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures United States Contact your distributor You must provide a Customer Support case num
9. while reading it by using CIP communication caused a fatal error Now clearing a log file is not permitted until the file read is completed CORRECTED Occasional NaN values appeared in energy counter values CORRECTED Active setpoint and logic gate outputs remained active after disabling the setpoint or logic gate CORRECTED Default threshold values of user configurable sags and swells were changed to 0 for sag and 200 for swell CHANGED Changed the format of date and time parameters in the ScheduledData Input table CHANGED Added Metering Iteration to ScheduledData Input table Firmware Revision 2 050 CORRECTED When the virtual wiring correction was cleared on occasion the light did not go out until the PowerMonitor 5000 unit was power cycled CORRECTED Net Energy Counter kWh_Net is not calculated correctly when there are Forward kWh_Fwd and Reverse Energy kWh Rev values This also applies to kKVARh_Fwd kVARh_Rev and kVARh_Net CORRECTED Power Factor issue where 100 001 was recorded in the min and max value Firmware Revision 2 045 CORRECTED Demo metering mode has inconsistent behavior CORRECTED Half cycle sag swell timestamp Rockwell Automation Publication 1426 RNO01D EN P September 2015 4 PowerMonitor 5000 Unit Firmware Revision 4 010 Known Anomalies These are known anomalies in the current product revision e There are compatibility problems with the NDIS driver and Windows 8 1 and

Download Pdf Manuals

image

Related Search

Related Contents

Operating instructions Pneumatic Crimper AC 25T  MANUAL DE INSTRUCCIONES DE ARMADO Y USO  Goodman Mfg Light Commercial Self Contained Packaged Cooling and Heating Unit CPC/CPH User's Manual  MODE D`EMPLOI pdf - fims informatique  Surtido inicial de accesorios  STIRA E ASPIRA TOP M0S06167 1O08  Servidor Proxy RHN 4.0 Manual de instalación  HiModel Professional Series ESC 取扱説明書  American DJ 250 Whiteboard Accessories User Manual  