Home

CLD Series - American Control Electronics

image

Contents

1. CLD Series Section 5 Operation Feedback Device Selection Acceptable feedback frequency at any set speed in an application must lie within the 0 3000 Hz range Feedback frequency is directly proportional to the number of feedback pulses per revolution PPR and to the speed of the shaft RPM that the feedback transducer monitors The feedback range relates to the motor speed as follows 600 120 000 PPRminimum PPRmaximum RPMminimum RPMmaximum EXAMPLE 1 Consider an application in which the feedback source is monitoring a driven shaft and not the motor armature shaft This shaft is running at speeds as low as 1 RPM The selected feedback device must produce at least 600 PPR EXAMPLE 2 Consider an application the requires monitoring and controlling a driven shaft at speeds as high as 4000 RPM 120 000 120 000 PPRmaxi maximum APM ee 4000 The selected feedback device must produce 30 or fewer PPR The CLD100 can control armature shaft speeds within a 30 1 speed range Under no circumstances can the CLD100 be expected to control motor speed beyond this speed range CLD Series Select Switches Access the switches from the rear of the CLD100 case Using a screwdriver loosen the two screws that attach the nameplate to the case The switches are visible when the nameplate is removed Line Voltage Switch SW501 The slide switch on the left rear of the CLD100 Figure 7 is the voltage switch Set
2. Encoder Power Supply Voltage SW502 DIP Switch 1 Feedback Device Selection SW502 DIP Switches 2 amp 3 Reference Signal Selection SW502 DIP Switches 4 amp 5 Section 6 Calibration MIN and MAX Section 7 Programming Calculating Parameters Speed Scaling Factor Load Response Number Display Scaling Factor Gate Time Decimal Point Location Number Entering the Programming Mode Viewing the Programming Screens CLD Series Entering Calculated Program Parameters Save the Program Settings and Exit the Programming Mode Set the Speed Programming Examples Section 8 Leader Follower Applications Leader Follower Example Using A Leader Encoder Leader Follower Example Using Two CLD100 s Section 9 Troubleshooting Unconditional Warranty CLD Series List of Figures Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 CLD100 Dimensions Panel Cuto Inserting t Inserting t Secure the CLD100 Co SW501 Li SW502 DI SW502 DI ut he CLD1600 he Brackets CLD100 nnections ne Voltage Switch P Switch 1 Encoder Power Supply Voltage P Switches 2 and 3 Feedback Device Selection 15 SW502 DI Leader Fol Leader Fol P Switches 4 and 5 Reference Signal Selection 16 lower Connections with a Leader Encoder 34 lower Connections with Two CLD100s CLD Series Section 1 Introduction The CLD100 Seri
3. Use 18 24 AWG wire for logic wiring Use 14 16 AWG wire for AC line and motor wiring CLD Series Shielding Guidelines Under no circumstances should power and logic level leads be bundled together Induced voltage can cause unpredictable behavior in any electronic device including motor controls As a general rule American Control Electronics recommends shielding of all conductors If it is not practical to shield power conductors it is recommended to shield all logic level leads If shielding of all logic level leads is not practical the user should twist all logic leads with themselves to minimize induced noise It may be necessary to earth ground the shielded cable If noise is produced by devices other than the drive ground the shield at the drive end If noise is generated by a device on the drive ground the shield at the end away from the drive Do not ground both ends of the shield If the drive continues to pick up noise after grounding the shield it may be necessary to add AC line filtering devices or to mount the drive in a less noisy environment Logic wires from other input devices such as motion controllers and PLL velocity controllers must be separated from power lines in the same manner as the logic I O on this drive CLD Series Connections Connections to regenerative drives and ACE PWP series drives differ from connections to non regenerative drives Improper connection to regen
4. over the gear CLD Series Unconditional Warranty A Warranty American Control Electronics warrants that its products will be free from defects in workmanship and material for twelve 12 months or 3000 hours whichever comes first from date of manufacture thereof Within this warranty period American Control Electronics will repair or replace at its sole discretion such products that are returned to American Control Electronics 14300 De La Tour Drive South Beloit Illinois 61080 USA This warranty applies only to standard catalog products and does not apply to specials Any returns of special controls will be evaluated on a case by case basis American Control Electronics is not responsible for removal installation or any other incidental expenses incurred in shipping the product to and from the repair point B Disclaimer The provisions of Paragraph A are American Control Electronics s sole obligation and exclude all other warranties of merchantability for use expressed or implied American Control Electronics further disclaims any responsibility whatsoever to the customer or to any other person for injury to the person or damage or loss of property of value caused by any product that has been subject to misuse negligence or accident or misapplied or modified by unauthorized persons or improperly installed C Limitations of Liability In the event of any claim for breach of any of American Control Electronics s
5. less 500 000 10 50 000 however the CLD100 only uses 4 digits Thus the maximum is 5000 The display can be set to read the speed ratio actual speed in RPM or a process value such as feet per second or gallons per minute Values of 100 and 1000 have the advantage of being easily read as a ratio or percentage of the leader To select external reference set DIP switch 4 of SW502 to ON and DIP switch 5 to OFF Refer to Figure 10 on page 16 CLD Series Leader Follower Example Using A Leader Encoder In this example the CLD100 recieves a signal from an encoder on a lead motor The CLD100 then controls a follower motor at 100 of the lead motor s speed Assume the following conditions exist The lead motor s maximum speed is 1800 RPM The resolution of the encoder on the lead motor is 60 lines The magnetic pickup on the follower motor has 30 teeth NOTE For this example if the set speed is 100 the motor will follow at 100 of the lead motor s speed If the set speed is 50 the motor will follow at 50 of the lead motor s speed The CLD100 will display the follower speed in RPM Step 1 Calculate the leader frequency FR using the following formula E Maximum RPM of lead motor PPR of lead feedback 60 Thus _ 1800 60 60 1800 Hz Step 2 Calculate the follower frequency FM using the following formula _ Maximum RPM of follower motor PPR of follower feedback 60 FM Thus
6. obligations whether expressed or implied and particularly of any other claim or breach of warranty contained in Paragraph A or of any other warranties expressed or implied or claim of liability that might despite Paragraph B be decided against American Control Electronics by lawful authority American Control Electronics shall under no circumstances be liable for any consequential damages losses or expenses arising in connection with the use of or inability to use American Control Electronics s product for any purpose whatsoever An adjustment made under warranty does not void the warranty nor does it imply an extension of the original 12 month warranty period Products serviced and or parts replaced on a no charge basis during the warranty period carry the unexpired portion of the original warranty only If for any reason any of the foregoing provisions shall be ineffective American Control Electronics s liability for damages arising out of its manufacture or sale of equipment or use thereof whether such liability is based on warranty contract negligence strict liability in tort or otherwise shall not in any event exceed the full purchase price of such equipment Any action against American Control Electronics based upon any liability or obligation arising hereunder or under any law applicable to the sale of equipment or the use thereof must be commenced within one year after the cause of such action arises AMERICAN CONT
7. set DIP switch 4 to OFF and 5 to ON If an external reference signal is used set DIP switch 4 to ON and 5 to OFF The external reference is only used in Leader Follower applications INTERNAL REFERENCE SIGNAL N EXTERNAL A REFERENCE SIGNAL N pas Figure 10 SW502 DIP Switches 4 and 5 Reference Signal Selection CLD Series Section 5 Calibration Dangerous voltages exist on the CLD100 when it is powered When possible disconnect the voltage input from the CLD100 before adjusting the trim pots If the trim pots must be adjusted with power applied use insulated tools and the appropriate personal protection equipment BE ALERT High voltages can cause serious or fatal injury WARNING All adjustments increase with CW rotation and decrease with CCW rotation Use a non metallic screwdriver for calibration Each trim pot is identified on the printed circuit board Calibrate the drive for use with the CLD100 The purpose is to optimize the response on the drive to the CLD100 signal and to minimize any tendency by the drive to independently attempt to regulate motor speed The following are the drive s trim pot settings Minimum Speed CCW motor stopped Maximum Speed CW maximum voltage setting Acceleration CCW fastest acceleration Deceleration CCW fastest deceleration IR Compensation CCW minimum regulation Current Limit 150 of motor current rating CLD Series MIN and MA
8. this switch to the left position for 115 VAC input ortothe right for 230 VAC input 1 A 15 230 s0501 LINE VOLTAGE SWITCH Figure 7 SW501 Line Voltage Switch CLD Series Encoder Power Supply Voltage SW502 DIP Switch 1 DIP switch 1 selects the supply voltage for an external encoder Figure 8 Set to OFF for 5 VDC source or to ON for a 12 VDC source If using a device that does not need to be powered by the CLD100 set to OFF The power supply voltage has a maximum current of 10 mA sw CEE SUPPLY VOLTAGE n N 12 VDC ENCODER SUPPLY VOLTAGE ON Figure 8 SW502 DIP Switch 1 Encoder Power Supply Voltage CLD Series Feedback Device Selection SW502 DIP Switches 2 amp 3 DIP switches 2 and 3 are for feedback device selection Figure 9 If using an optical pickup hall sensor proximity switch or an open collector transducer set DIP switch 2 to ON and 3 to OFF If a magnetic pickup is used set DIP switch 2 to OFF and 3 to ON OPTICAL ENCODER FEEDBACK MAGNETIC PICKUP FEEDBACK Figure 9 SW502 DIP Switches 2 and 3 Feedback Device Selection CLD Series Reference Signal Selection SW502 DIP Switches 4 amp 5 DIP switches 4 and 5 are for reference signal selection Figure 10 If an internal reference signal is used normal operation
9. too high if the oscillation is rapid 2 The drive may be incorrectly calibrated Check that the acceleration deceleration and IR Comp trim pots are at their minimum settings 3 If a magnetic pickup is used extensive runout may cause an interruption in the feedback pulse train Check that the pickup s sensing tip is directly over the center of the gear teeth The gap between the sensing tip and the gear tip should be no greater than 0 010 inches 4 Electrical noise may cause the CLD100 to attempt corrections that are not justified Check the continuity and shielding of the pickup leads 5 Rapid shifts in load may be pulling the motor out of its set speed Consider using a regenerative drive with the CLD100 CLD Series The motor is running at a fixed difference below set speed 1 There may be a 60 Hz signal riding on the pickup leads Check that the pickup leads are run in their own conduit and that all connections are secure For long paths these leads must be shielded and properly grounded at the CLD100 end The motor is running at a fixed difference below set speed 1 There may be an electromechanical defect in the pickup or sensor or a break in the pickup or sensor leads Check that the pickup or sensor is working properly and that there are no breaks in the pickup or sensor leads 2 The pickup may not be properly aligned over the gear causing inaccurate feedback information Check the alignment of the pickup
10. 6 on page 11 Inhibit Terminal INH Short terminal INH to common C to inhibit the CLD100 The CLD100 output will drop to the MIN trim pot setting Remove the short to resume operation Refer to Figure 6 on page 11 Frequency Terminal Fin The CLD100 can be used as a signal source to control another CLD100 via SO502 terminals FO and FO SO502 is a two terminal cage clamp terminal block onthe printed circuit board The frequency output available from these terminals is equal to 50 fo the commanded speed Refer to page 31 for instructions on a leader follower configuration The leader CLD may only control one follower CLD If you are not using the leader follower configuration make no connections to Fin FO and FO CLD Series MODEL CLD100 1 INPUT 115 230V AC 50 60 Hz 50 mA AMERICAN CONTROL ELECTRONICS SOUTH BELOIT IL 61080 www americancontrolelectronics com G 1 L2 S1 S2 Fin IN C INH INHIBIT SWITCH OHE LILI OPEN TO RUN CLOSE TO INHIBIT Nt 115 VAC y 230 VAC EARTH GND FAC AC VOLTAGE MAGNETIC PICKUP NON POLARIZED COMMON 5 VDC or 12 VDC FROM CCW TERMINAL FROM WIPER TERMINAL NON REGENERATIVE DRIVE S1 S2 REGENERATIVE DRIVE S0 S2 PWP DRIVE s2 51 OPTICAL ENCODER Figure 6 CLD100 Connections
11. AMERICAN CONTROL 34 ELECTRONICS CLD Series USER MANUAL CLD100 1 www americancontrolelectronics com Dear Valued Consumer Congratulations on your purchase of the CLD100 Series display This User Manual was created for you to get the most out of your new device and assist with the initial setup Please visit www americancontrolelectronics com to learn more about our other drives Thank you for choosing American Control Electronics 2014 American Control Electronics All rights reserved No part of this document may be reproduced or transmitted in any form without written permission from American Control Electronics The information and technical data in this document are subject to change without notice American Control Electronics makes no warranty of any kind with respect to this material including but not limited to the implied warranties of its merchantability and fitness for a given purpose American Control Electronics assumes no responsibility for any errors that may appear in this document and makes no commitment to update or to keep current the information in this document CLD Series Safety First SAFETY WARNINGS Text in gray boxes denote important safety tips or warnings Please read these instructions carefully before performing any of the procedures contained in this manual DO NOT INSTALL REMOVE OR REWIRE THIS EQUIPMENT WITH POWER APPLIED Have a qualified electrical tech
12. CLD Series MOTOR DRIVE NO 1 MOTOR DRIVE NO 2 4 SOT 2 LINE INPUT PICK UP NI ud zis 71 11 D N Ud ZS IS TI n IAE LI LEADER FOLLOWER NO 1 RPM SET IN PERCENT DISPLAY IN RPM 1800 SET SPEED 1800 RPM 100 SET SPEED 1800 RPM SSF 100 SSF 50 DSF 100 DSF 100 FREQ FR 450 HZ FREQ FR 450 HZ FREQ M 900 HZ FREQ M 900 HZ Figure 12 Leader Follower Connections with two CLD100s CLD Series Section 9 Troubleshooting The motor will not run 1 The connections from the CLD100 ot the drive or the drive to the motor may not be wired correctly Check the connections from the CLD100 to the drive and from the drive to the motor 2 The drive may be defective Disconnect the CLD100 from the drive Connect a speed adjust potentiometer to the drive and see if the drive runs the motor properly 3 The motor may be defective Test the system with another motor The motor will not lock into speed 1 The load response number may be too low if the oscillation is gradual or
13. ROL AGA ELECTRONICS www americancontrolelectronics com 14300 DE LA TOUR DRIVE SOUTH BELOIT IL 61080 844 AMCNTRL MAN 0015 Rev 0
14. Scaling Factor 50 Display 0 0 5 0 Load Response 25 Display 0 0 2 5 Display Scaling Factor 50 Display 0 0 5 0 Decimal Point Location None Display 0 0 0 0 CLD Series Entering the Calculated Program Parameters 1 Press ENTER until the decimal point is displayed in the lower right corner e g 1234 2 Press the UP and DOWN pushbuttons until you reach the desired speed scaling factor 3 Press ENTER until their are two decimal points displayed e g 1 2 3 4 4 Press the UP and DOWN pushbuttons until you reach the desired load response number 5 Press ENTER until their are three decimal points displayed e g 1 2 3 4 6 Press the UP and DOWN pushbuttons until you reach the desired display scaling factor 7 Press ENTER until their are four decimal points displayed e g 1 2 3 4 8 Press the UP and DOWN pushbuttons until the desired decimal location is displayed 0 000 no decimal e g 1 2 3 4 0 001 tenths e g 1 2 3 4 0 002 hundredths e g 1 2 3 4 0 003 thousandths e g 1 2 3 4 Save the Program Settings and Exit the Programming Mode 1 Press and hold the ENTER pushbutton 2 Press the UP pushbutton to exit the program mode Repeat steps 1 and 2 if you are still in the programming mode If a numeral is flashing press ENTER repeatedly until all digits stop flashing CLD Series Set the Speed 1 Press ENTER once The most significant digit will blink 2 Use the UP and DO
15. WN pushbuttons to set the desired value for this digit 3 Press ENTER once The second digit from the left will blink 4 Use the UP and DOWN pushbuttons to set the desired value for this digit 5 Press ENTER once The third digit from the left will blink 6 Use the UP and DOWN pushbuttons to set the desired value for this digit 7 Press ENTER once The least significant digit will blink 8 Use the UP and DOWN pushbuttons to set the desired value for this digit 9 Press ENTER once to return to the operating mode 10 Remove power to the CLD100 11 Reconnect the drive and apply power to the CLD100 and drive simultaneously 12 The motor will accelerate to the set speed 13 To change the set speed repeat steps 1 9 CLD Series Programming Examples Example 1 An application uses a 30 tooth magnetic pickup mounted on a motor shaft The application requires that the motor speed and display be equal to the speed entry Calculate the program parameters Solution PPR 30 given in example Shaft RPM 100 arbitrarily chosen Speed Entry 100 same as Shaft RPM Speed Display 100 same as Shaft RPM _ Speed Entry 3000 _ 100 3000 _ Shaft RPM PPR 100 30 SSF Speed Display 3000 _ 100 3000 Shaft RPM PPR 100 30 DSF 100 Gate Time 2 seconds 50 50 CLD Series Example 2 An application uses a 60 tooth magnetic pickup mounted on a motor shaft The applic
16. X 1 Set the MIN and MAX trim pots full CCW 2 Set the motor speed to zero using the following steps A Press ENTER once The most significant digit the leftmost numeral will blink B Use the UP and DOWN pushbuttons to set this digit to zero C Press ENTER once The second digit from the left will blink D Use the UP and DOWN pushbuttons to set this digit to zero E Press ENTER once The third digit from the left will blink F Use the UP and DOWN pushbuttons to set this digit to zero G Press ENTER once The least significant digit the rightmost numeral will blink H Use the UP and DOWN pushbuttons to set this digit to zero Press ENTER once to return to operating mode 3 Adjust the MIN trim pot CW until the motor shaft starts to rotate Slowly adjust the MIN trim pot CCW until the motor just stops 4 Set the CLD100 speed to 200 of maximum desired motor speed as outlined in step 2 above 5 Adjust the MAX trim pot until the motor is running at 120 of desired motor speed 6 Check that the MIN trim pot does not need to be readjusted after completing this procedure by repeatings steps 2 and 3 as necessary CLD Series Section 7 Programming Calculating Parameters Five parameters must be known before programming the CLD100 These parameters are speed scaling factor load response display scaling factor gate time and decimal point location All parameters must be programmed into the CLD100 except f
17. _ SSF Shaft RPM PPR 420 17 30 A Speed Display 3000 10 3000 _ Shaft RPM PPR 4201730 DSF 2 Gate Time 0 04 seconds 50 50 The gate time is too small You may introduce a decimal point on the display CLD Series The user could enter 100 which would appear as 10 0 miles per hour the display The speed entry and speed display numbers in the formula now become 100 Recalculating parameters Speed Entry 3000 100 3000 _ SSF 2 Shaft RPM PPR 420 17 30 23 79 24 _ Speed Display 3000 100 3000 a Shaft RPM PPR 420 17 30 DSF 23 79 24 i DSF 24 Gate Time 0 48 seconds 0 5 seconds 50 50 Adding a decimal point widens the input range the range of settings from 0 to maximum increases the gate time and decreases the rounding error to the nearest digit in the first calculation of the SSF and DSF The CLD100 has a gate time range of 0 5 3 seconds CLD Series Example 4 An application uses a 30 tooth magnetic pickup mounted on the high speed shaft of a gear motor The gear ratio is 40 1 and the high speed RPM is 1800 The user will enter the speed of the geared shaft The gear shaft RPM is what will be displayed as well Solution PPR 30 given in example Speed Entry 10 for 10 RPM arbitrarily chosen Speed Display 10 same as Speed Entry Shaft RPM Speed of high speed shaft If geared shafting is running at 10 RPMs Spe
18. _ 1800 30 60 FM 900 Hz Having derived FR and FM you can now calculate the speed scale factor CLD Series Step 3 Calculate the SSF Program the speed scale factor SSF per the following formula FR Set Speed SSF FM where FR FR calculated in step 1 FM FM calculated in step 2 Set Speed Desired leader follower speed ratio expressed as a percentage For example if you want the follower to run at half the speed of the leader the set speed is 50 For this example the set speed is 100 i e match the leader speed Thus FR SetSpeed _ 1800 100 FM E 900 SSF 200 The speed scale factor is 200 CLD Series MODEL CLD100 1 INPUT 115 230V AC 50 60 Hz 50 mA AMERICAN CONTROL ELECTRONICS SOUTH BELOIT IL 61080 www americancontrolelectronics com G Li L2 S1 S2 Fin IN C INH OPEN TO RUN 11161 CLOSE TO STOP IA FUNeSTOP swe CR A A 115 VAC or 230 VAC EARTH GND PN AC LINE VOLTAGE MAGNETIC PICKUP NON POLARIZED FOLLOWER MOTOR FROM CCW TERMINAL FROM WIPER TERMINAL 5 VDC OR 12 VDC COMMON LEADER SHAFT NON REGENERATIVE DRIVE S1 S2 0 1800 RPM REGENERATIVE DRIVE SO S2 S2 51 PWP DRIVE OPTICAL ENCODER Figure 11 Leader Follower Connections with a Leader Encoder CLD Series Leader Follower Example Using Two CLD100 s The CLD100 may drive only one follower using this method WARNING In th
19. and 3 38 inches 86 mm wide PANEL pi 3 38 86 CUTOUT AREA BOUNDED BY DASHED LINES Figure 2 Panel Cutout Step 2 Slide the CLD100 into the panel opening Figure 3 Inserting the CLD100 CLD Series Step 3 Insert the two mounting brackets into each side of the CLD100 case Figure 4 Inserting the Brackets Step 4 Secure the CLD100 to the panel using the bracket screws Figure 5 Secure the CLD100 CLD Series Do not install rewire or remove this control with input power applied Failure to heed this warning may result in fire explosion or serious injury Circuit potentials are at 115 or 230 VAC above ground To prevent the risk of injury or fatality avoid direct contact with the printed circuit board or with circuit elements Do not disconnect any of the motor leads from the drive unless power is removed or the drive is disabled Opening any one motor lead while the drive is running may destroy the drive This product does not have internal solid state motor overload protection It does not contain speed sensitive overload protection thermal memory retention or provisions to receive and act upon signal from remote devices for over temperature protection If motor over protection is needed in the end use product it needs to be provided by additional equipment in accordance with NEC standards
20. assume the lead motor speed is 1800 RPM The leader SSF in this example is 100 FR Thus 25 Lead Motor SpeedinRPM 25 1800 SSF of Lead CLD100 7 2 Calculate the follower motor feedback frequency FM using the following formula FM In this example assume the lead motor speed is 1800 RPM The leader SSF in this example is 100 Thus _ _ Follower Motor Speed in RPM PPR of Follower Feedback 60 As noted earlier assume the motor speed is 1800 RPM The follower feedback is 30 PPR in this example 1800 30 Thus FM a 900 Hz CLD Series 3 Calculate the speed scale factor SSF using the following formula FR Follower Speed as a of Leader Speed FM SSF Using the FR from step 1 the FM from step 2 and using a set speed of 100 for this example _ 450 100 900 The speed scale factor is 50 Enter this value as the SSF on the follower CLD100 SSF 50 4 It is recommended that you set the DSF of the follower CLD100 to 100 Although any you can set whatever DSF value you d like setting it to 100 removes the need to correlate the DSF value with system speed 5 Enter the follower speed setting as a percentage of the lead motor speed For example if you want the follower to run at the same speed as the leader the speed setting would be 100 To run the follower at half the leader speed enter 50 or 33 to run at 33 etc Refer to page 24 for instructions on entering the set speed
21. ation requires that the motor speed and display be equal to the speed entry Calculate the program parameters Solution PPR 60 given in example Shaft RPM 100 arbitrarily chosen Speed Entry 100 same as Shaft RPM Speed Display 100 same as Shaft RPM _ Speed Entry 3000 _ 100 3000 _ Shaft RPM PPR 100 60 SSF A Speed Display 3000 _ 100 3000 7 Shaft RPM PPR 100 60 DSF 50 Gate Time 1 second 50 50 The PPR in this example is larger than the PPR in Example 1 Increasing the PPR decreases the speed scaling factor display scaling factor and the game time CLD Series Example 3 An application uses a 30 tooth magnetic pickup mounted on a motor shaft that is part of an exercise treadmill The pulley is driving a belt that has a radius of 4 inches The applications requires the user to enter the speed in miles per hour and the display to read in miles per hour Calculate the program parameters Solution PPR 30 given in example Speed Entry 10 for 10 miles per hour arbitrarily chosen Speed Display 10 same as Speed Entry Shaft RPM Need to calulate by converting 10 miles per hour into RPMs NOTE Circumference of pulley 2m radius 2n 4 inches 10 miles _ 10 miles 5280 feet 12inches 1 revolution 1 hour hour 1 hour 1 mile 1 foot 2n 4 inches 60 minutes 420 17 fevolutions 420 17 RPM minute Speed Entry 3000 A 10 3000
22. ed Entry then high speed shaft is running at 400 RPMs 10 x 40 1 Gear Ratio Speed Entry 3000 10 3000 _ SSF Shaft RPM PPR 400 30 Speed Display 3000 10 3000 25 Shaft RPM PPR 400 30 i DSF 2 5 Gate Time 0 05 seconds 50 50 The gate time is not within the CLD100 s range of 0 5 3 seconds There is alos a significant error 20 in rounding 2 5 to 3 Introduce a decimal point and recalculate the program parameters Since the user will enter 10 0 for 10 RPM the speed entry is now 100 The speed display is also 100 CLD Series Recalculating the program parameters F Speed Entry 3000 100 3000 2 Shaft RPM PPR 400 30 SS 5 _ Speed Display 3000 100 3000 2 Shaft RPM PPR 400 30 DSF 5 i DSF 25 Gate Time 0 5 seconds 50 50 This is much more acceptable Note that there is no error due to rounding here because the SSF and DSF came out to be whole numbers CLD Series Section 8 Leader Follower Applications The CLD100 can be used to follow an external frequency for leader follower applications The external frequency must be a 5 VDC CMOS logic level signal or an open collector NPN transistor The external frequency must be within the range of 10 3000 Hz for correct operation The product of the external frequency and the set speed on the CLD100 must not exceed 500 kHz This will limit the speed set value to to 5000 or
23. erative or PWP series drives may result in damage to the CLD100 or drive Variable speed drives manufactured by other companies may require hookup procedures that differ from those given in this manual Contact your local American Control Electronics distributor for assistance Line Voltage Terminals G L1 L2 Connect the line voltage to these terminals The CLD100 is ON when power is applied to these terminals Always provide a positive disconnect to shut down the CLD100 in case of an emergency Do NOT apply power to the CLD100 until selector switch SW501 has been properly set See page 13 for details Output Terminals S1 S2 If using a non regenerative drive connect the CLD100 S1 to drive S1 and the CLD100 S2 to drive S2 Refer to Figure 6 on page 11 If using a regenerative drive connect the CLD100 S1 to drive SO and the CLD100 82 to drive S2 Refer to Figure 6 on page 11 If using a PWP series drive connect the CLD100 S1 to drive S2 and the CLD100 S2 to drive S1 Refer to Figure 6 on page 11 CLD Series Feedback Terminals IN C If using a magnetic pickup connect the pickup signal lead to terminal IN and the signal common to terminal C If an optical encoder is used connect its positive input voltage lead to the signal lead to IN and the signal common to terminal C The voltage on the terminals is determined by DIP switch 1 Only one feedback source may be used at a time Refer to Figure
24. es control is a dual voltage digital control used with a drive motor and feedback device to regulate and display motor speed The user may enter and display the motor speed in RPM or other units such as feet per minute or inches per second The CLD100 offers the advantage of repeatable speed settings and speed stability Basic operation principles The CLD100 generates a frequency and compares this to the frequency coming from the feedback transducer attached to the motor shaft The CLD100 then generates an analog voltage to the speed control to corect for any difference between the the CLD100 reference frequency and the motor feedback frequency The CLD100 also counts the motor transducer pulses for a fixed period of time called gate time and displays this value on the front panel usually in the form of motor revolutions per minute The CLD100 generated frequency is derived from an internal 50 Hz refrence The generated frequency is equal to the 50 Hz internal reference multiplied by the set speed The product of the internal reference and set speed is then divided by the speed scale factor SSF which is entered by the user via the front pushbuttons Refer to page 19 for more information on setting the speed scale factor CLD Series Section 2 Specifications 5 5 watts nominally 5 VDC or 12 VDC NPN type encoder 5 VDC or 12 VDC NPN type proximity switch Hall effect sensor Magnetic pickup Feedback Frequency Range Exte
25. is example the follower CLD100 recieves a signal from a leader CLD100 The follower CLD100 then controls a follower motor at 100 of the lead motor s speed Leader Follower Connections Use 14 28 AWG wire to connect the leader and follower CLD100 s Connect S0502 terminal FO on the leader CLD100 to the C terminal on the follower CLD100 Connect SO502 terminal FO on the leader CLD100 to the Fin terminal on the follower CLD100 Refer to Figure 12 on page 38 If the leads are longer than 12 inches 30 cm it is recommended ot use shielded leads If shielding is not practical twist all logic leads with themselves to minimize induced noise Programming the Leader Program the leader CLD100 to reflect the following conditions Refer to page 19 for instructions on programming a CLD100 1 Set the speed scale factor SSF to 100 Although the SSF may be set to any value the frequency output via FO and FO is always the equivalent of 50 of set speed Thus setting the SSF to 100 makes it easier to monitor the signal sent to the follower CLD100 2 Set the display scale factor DSF to 100 Like the SSF the DSF may be set to any value however a setting of 100 makes it easier to monitor the system CLD Series Programming the Follower Program the follower CLD100 as follows 1 Calculate the follower reference frequency FR using the following formula 25 Lead Motor Speed in RPM SSF of Lead CLD100 In this example
26. nician install adjust and service this equipment Follow the National Electrical Code and all other applicable electrical and safety codes including the provisions of the Occupational Safety and Health Act OSHA when installing equipment Reduce the chance of an electrical fire shock or explosion by using proper grounding techniques over current protection thermal protection and enclosure Follow sound maintenance procedures It is possible for a drive to run at full speed as a result of a AN component failure American Control Electronics strongly recommends the installation of a master switch in the main power input to stop the drive in an emergency Circuit potentials are at 115 VAC or 230 VAC above earth ground Avoid direct contact with the printed circuit board or with circuit elements to prevent the risk of serious injury or fatality Use a non metallic screwdriver for adjusting the calibration trim pots Use approved personal protective equipment and insulated tools if working on this drive with power applied CLD Series Table of Contents Section 1 Introduction Section 2 Specifications Section 3 Dimensions Section 4 Installation Mounting Panel Mounting Line Voltage Terminals G L1 L2 Output Terminals S1 S2 Feedback Terminals IN C Inhibit Terminal INH Frequency Terminal Fin Section 5 Operation Feedback Device Selection Select Switches Line Voltage Switch SW501
27. or the gate time Speed Scaling Factor The speed scaling factor SSF correlates the digital speed set at the CLD100 with the speed in RPM desired at the feedback shaft The SSF equation is Speed Entry 3000 Shaft RPM PPR where Speed Entry speed programmed into the CLD100 This speed entry may be numerically different than the actual shaft RPM for example feet per minute gallons per minute inches per second etc Shaft RPM the speed in RPM of the shaft where the feedback device is mounted PPR the number of pulses per revolution generated by the feedback device The SSF range is 3 through 9999 and the factory setting is 50 CLD Series Load Response Number The load response number determines how fast the CLD100 responds to load changes The higher the load response number the faster the CLD100 will respond The load response number range is O through 99 The factory setting is 25 Display Scaling Factor The display scaling factor SSF correlates the speed displayed by the CLD100 with the speed at the feedback shaft The DSF equation is Speed Display 3000 SSF Shaft RPM PPR where Speed Display speed displayed by the CLD100 This speed entry may be numerically different than the actual shaft RPM for example feet per minute gallons per minute inches per second etc Shaft RPM the speed in RPM of the shaft where the feedback device is mounted PPR the number of p
28. rnal Reference Frequency 5 VDC CMOS logic level signal or open collector NPN transistor applied to IN and C terminals Signal applied to Fin and C terminals The product of the CLD leader frequency and speed setting may not exceed 500 kHz Section 3 Dimensions CLD Series jas 3 75 95 fj 7 F 0 25 6 4 53 115 0 85 22 3 38 86 ALL DIMENSIONS IN INCHES MILLIMETERS Figure 1 CLD100 Dimensions CLD Series Section 4 Installation Do not install rewire or remove this control with input power applied Failure to heed this warning may result in fire explosion or serious injury Make sure you read and understand the Safety Precautions on page i before attempting to install this product Variable speed drives manufactured by other companies may require hookup procedures that differ from those given in this manual Contact your local American Control Electronics distributor for assistance Mounting Protect the control from dirt moisture and accidental contact Provide sufficient room for access to the terminal block and calibration trim pots Mount the control away from heat sources Operate the drive within the specified ambient operating temperature range Prevent loose connections by avoiding excessive vibration of the drive CLD Series Panel Mounting Step 1 Cut a rectangular hole in the panel 1 78 inches 45 mm
29. ulses per revolution generated by the feedback device The DSF range is 3 through 9999 and the factory setting is 50 CLD Series Gate Time The display scaling factor determines the gate time the time between successive display updates The recommended gate time range is 0 5 3 seconds The gate time equation is shown below DSF Gate Time 25 Decimal Point Location The decimal point location number fixes the decimal point within the CLD100 display The CLD100 may be set for no decimal point or for a decimal point in the tenths hundredths or thousandths position The factory setting is for no decimal point CLD Series Entering the Programming Mode 1 Press and hold the ENTER pushbutton labeled E while applying AC power to the CLD100 only Do not apply power to the drive 2 Release the ENTER pushbutton after AC power is applied You have entered the programming mode when the decimal point appears on the display in the lower right hand corner If no decimal points appear or if any number is flashing remove AC power and repeat steps 1 and 2 Viewing the Programming Screens The programming screens are identified by the position of the decimal point displayed one decimal indicates speed scaling factor mode two decimals indicates load response number mode three decimals indicates display scaling factor mode and four decimals indicate decimal point location The CLD100 factory settings are Speed

Download Pdf Manuals

image

Related Search

Related Contents

Meaco 50Lm Building Dryer  Samsung GT-C3050 Benutzerhandbuch  EH10形 付属パーツ一覧訂正版131015ol  Mise en page 1  Owners Manual v2  取扱説明書 PDFダウンロード  Creda 79331S User's Manual    Sony SVD13213CXB Safety & Regulations Guide  The Deck Demon AGP6004-001THD Use and Care Manual  

Copyright © All rights reserved.
Failed to retrieve file