Fuji Electric Co., Ltd. USER`S MANUAL Uninterruptible Power
Contents
1. 266 300 le 265 170 i 265 3 Installation 3 2 Connecting the Cable e Caution about connecting the cable Caution Electric Connect a grounding wire to a ground terminal class D shock grounding There is fear of an electric shock A commercial power ordinarily has electrodes of a grounding side and an un grounding side apart from a grounding electrode ground Be sure to confirm before connecting If connected in reverse there is fear of the malfunction by noise or the electric shock Important The permissible voltage between the input electric cable of the UPS and the ground is 230 VAC If the voltage more than 230 VAC is applied the filter circuit of the input part may be damaged The permissible input surge voltage of the UPS is 5kV peak 1 2 x 50us However if the model of the UPS is UC it is 2kVpeak 1 2 x 50us If the surge voltage more than 5kV peak UC is 2kV peak is applied the filter circuit of the input part may be damaged The input voltage of the UPS is 85 to 138 VAC When input voltage is different from the rated specification 200 VAC etc install a transformer at the outside of the UPS to convert voltage If the voltage more than the range of the input voltage is applied the UPS may be damaged Connect the UPS to an input power supply within the range of the rated input voltage of the connection device At the bypass operation the
2. INTRODUCTION Re ee es EE EEEE EE EE ee a EEE i Unpacking Opening the Packing Opening the packing Confirming the contents of the packing Overview Name and Main Function of Each Part Operation Mode of the UPS aes ieciccsccct tc icncedcesieeteteeineleiveeleos Guede itagers 4 At the normal operation At the battery operation In the event of an input power failure At the bypass operation In the event of the abnormalities inside the UPS Installation Installing the UPS ota css 6 Caution about installation Determining an installation location Determining the installation method Installation method Connecting the Cable oocoooonicccoc ninccicnnonoccconnnnnncnnnnnnnnnnnnnnnenr rana Caution about connecting the cable Preparation before connecting the cable Connecting the input and output cable INTO ACA PO Gn CN1 No voltage contact signal interface CN2 RS 232C interface Setting up the Output Voltage cccoocococccccccocccocananannnononononanananannnnnnnnnnns The setup procedures of the rated output voltage Running Turning onthe DUES ana is Confirming cable connection Turning on the UPS Turning on the connection device Turning OTF the UPS ai 20 Turning off the connection device Turning off the UPS Inspection Care and Daily Inspection How to care for the UPS Daily inspection al a 00051090 Caution and Measures for the Rolling Blackouts 24 Operation before the rolling blackouts Op
3. Warning indicates that death or serious injury may result if the UPS is not used correctly Electric shock A Caution Do not remove the cover of the UPS Since there are parts of high voltage inside the UPS there is the fear of an electric shock Caution indicates that slight or moderate injury may result or that the UPS or user s property may be damaged if the UPS is not used correctly Electric shock Injury Put neither a stick nor a finger into the cooling fan or the vent hole There is the fear of an electric shock or an injury Electric shock The maintenance other than daily inspection such as the replacement of battery or cooling fan must be performed by the specialist engineer There is the fear of an electric shock Connect a grounding wire to a ground terminal class D grounding There is the fear of an electric shock A commercial power source usually has the electrodes of a grounding side and an ungrounded side separately from a grounding electrode earthing Be sure to check before connecting If connected in reverse there is the fear of the malfunction by the noise or an electric shock When inspecting or maintaining the connection device a device getting connected to the UPS or the UPS turn off the connection device and the UPS And turn off the input breaker of the back of the UPS and cut off connection to the AC input terminal R S There is the fear of an e
4. the battery operation has continued of battery due to In the rated load the battery charge continuing operation will be completed green the battery approximately 2 minutes later operation Evacuate important connection device from the UPS If an input power supply returns the UPS will return to the normal operation No 1 automatically 13 Lighting Q Q Q b 4 Battery The battery check is performed At Slow blink at the checking the manual battery check a buzzer orange manual sounds at the start and end of the check battery check After the battery check SAL p BOS is performed for approximately 5 l seconds the UPS will return to the normal operation No 1 if there is no problem 14 Lighting Q Q Q a 1 Battery check There is possibility that the battery is Fast blink error not fully charged Perform the orange battery check manually after j operating the UPS 12 hours or more 2 E to charge the battery Since an adequate backup time cannot be assured evacuate important connection device from the UPS If the UPS becomes this state again the battery is out of order Since it is necessary to replace the battery contact an agent from which you purchased the UPS or a maintenance company 33 6 Troubleshooting 34 LED No BATTERY Warning Operational RUN ALARM OVER BYPASS CONDITION beep status Remarks green orange orange orange green orang
5. Capacity 5000VA or less Grounding Un grounding or single line grounding system Power factor 0 97 or more at the rated operation Input harmonic current Based on IEC61000 3 12 Type Small sealed lead storage battery long life battery Others gt Backup time 2 Approximately 6 minutes initial value 4000W M Nominal voltage 72V Ambient 0 to 40 C temperature Relative humidity 20 to 95 no condensation Noise 55dB A max at 1m from the front of the UPS Cooling method Forced air cooling 41 42 8 Appendix Model M UPSO50AD1C M UPSO50AD1B Outside dimension 240 x 700 x 514mm 240 x 700 x 434mm WxDxH Mass 84 without battery 48 78 without battery 42 Standard UL1778 U UC type Applicable standard VCCI CLASS A In conformity with EN62040 UC type c Input Terminal block L R N S M6 screws wo 5 3 Output Terminal block 1 U n V M6 screws E l S Ground Terminal block PE G M6 screws 1 Operation of UPS according to an input voltage Low voltage detection 77V return 82 V Overvoltage detection 148V return 142V 2 The backup time is the test result and is not a guaranteed value 8 2 Additional Description for UL Type 8 2 Additional Description for UL Type IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for UPS GX100
6. Manual bypass operation The UPS has been switched to the bypass operation manually In this state even if an input power failure occurs the battery operation cannot be performed b Slow blink Vly IN a Fast blink vr ZTS a Input error at startup Since the abnormalities have occurred at an input power supply the UPS cannot be started up Stop the UPS once and restart after confirming that an input power supply is within the range of the following conditions Input voltage 85 to 138 VAC Input frequency 47 5 to 52 5 Hz or 57 to 63 Hz Lighting O Lighting O Lighting o a Bypass operation due to an output overload during the normal operation Since the capacity of the connection device exceeded the rated value and the UPS became the overload state the UPS has switched to the bypass operation automatically Reduce the capacity of the connection device to less than the rated value of the UPS If the capacity of the connection device become below the rated value the UPS will return to the normal operation No 1 In the state of the continuation of overload even if pressing the RESET switch the warning beep does not stop Although it may become the overload temporarily by inrush current at the time of a load injection 6 2 Operation Mode List LED No BATTERY Warning Operational RUN ALARM OVER BYPASS CONDITION beep
7. bps 9 7 oa Serial data Data length 8 bits i output IX stop bit 1 bit 7 3 Signal ground Parity non SG Character type ASCII Refer to the graph of the previous page for contact capacity 2 3 When using the UPS monitoring function using the above contact signal preinstalled in the following OS contact your maintenance staff since the dedicated RS 232C cable for contact signal which corresponds to each OS is needed separately For more detail on the UPS monitoring function preinstalled in each OS refer to an instructions manual an on line manual etc of each OS e Windows NT 2000 XP FiFH WS9 RS 232C cable In the case of Windows 2000 and XP although the shutdown of OS can be performed during the power failure a subsequent UPS automatic shutdown cannot be performed When performing the RS 232C serial communication contact your maintenance staff since the RS 232C cable is needed separately FiFA WS9 RS 232C cable 3 4 Setting up the Output Voltage 3 4 Setting up the Output Voltage This UPS can change the rated output voltage by the switch of voltage setting on the back of the UPS A Caution Damage Confirm that the voltage set up by the switch of voltage setting is within the range of input voltage of the connection device There is fear of damaging the connection device Do not operate the switch of voltage setting during operation of the UPS There is fear of damaging the
8. connection device And even if operating the switch during operation of the UPS the output voltage cannot be changed Important Do not use 5 to 9 of the switch of voltage setting It becomes impossible for the UPS to start up normally O The setup procedures of the rated output voltage 1 Turn off the connection device 2 Press the RUN STOP switch on the front of the UPS for approximately 1 second The buzzer will sound if the switch is received 3 An output stops The RUN LED green on the front of the UPS blinks slowly in the cycles of approximately 1 6 sec 4 Turn off the input breaker on the back of the UPS 5 After confirming that all LEDs on the front of the UPS have gone out operate the switch of voltage setting on the back of the UPS The rated output voltage corresponding to a setup of the switch of voltage setting is shown below Setup of the switch of voltage setting Rated output voltage 0 100 VAC 1 105 VAC 2 110 VAC 3 115 VAC 4 120 VAC 5 9 They are not used 6 Connect the UPS to an input power supply and the connection device The RUN LED green on the front of the UPS blinks slowly in the cycles of approximately 1 6 sec 15 3 Installation 7 Press the RUN STOP switch on the front of the UPS for approximately 1 second The buzzer will sound if the switch is received 8 AC voltage set up is outputted from the output terminal block The RUN LED green on the front of
9. disturbance In this case the user may be requested to take an appropriate measure Prevention of Higher Harmonics Current Disturbance This product conforms to IEC61000 3 12 All Rights Reserved Copyright Fuji Electric Co Ltd 2011 Introduction An uninterruptible power supply is a device for supplying stable electric power to OA devices FA devices and computer devices This manual describes installation running daily management troubleshooting and maintenance of an uninterruptible power supply Use an uninterruptible power supply correctly in accordance with this manual In this manual an uninterruptible power supply this product is described as UPS for short Content and organization of this manual The organization of this manual is as follows Caution about Safety and Caution for Use The cautions about safety are described If you use the UPS be sure to read this section 1 Unpacking The cautions for taking out the UPS from a box are described 2 Overview The name of each part and the operation mode of the UPS are described 3 Installation Installation of the UPS and connection of the cable are described 4 Running The methods of run and stop of the UPS are described 5 Inspection The cautions about daily inspection and rolling blackouts are described 6 Troubleshooting Troubleshooting is described 7 Maintenance Replacement of battery and cooling fan and method of storing the UPS are describ
10. for any reason There are no user serviceable parts inside the UPS Refer servicing to qualified service personnel Ml Dont use this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly effect its safety or effectiveness M Risk of explosion if battery is replaced by an incorrect type Dispose of used batteries according to the instructions Ml Replace batteries are only the one designated by our company WE Risk of electric shock O Battery and cooling fan servicing should be performed by only authorized servicing personnel who were qualified technically Keep unauthorized personnel away from batteries and cooling fan The UPS has an internal energy source the battery The output may be energized when the unit is not connected to an AC power line Terminal marked PE G is intended for connection of the Protective Earthing Grounding conductor s This earth connection is essential before connecting supply conductors Also ensure the reliability of this connection during any servicing including connection of protective earthing grounding conductors to the output load O Capacitor stores hazardous energy Do not remove cover until 7 minutes after disconnecting all sources of supply O If this UPS installs removes or does any services be off the external input circuit breaker for disconnecting all sources of
11. input breaker on the back of the UPS confirm that the RUN LED green is blinking slowly in the cycles of approximately 1 6 sec If the breaker of the distribution board is turned off or the input breaker on the back of the UPS is turned off without turning off the UPS the internal battery will be discharged since it will be in the same state as a power failure There is fear of the battery damage or a shortening of a cycle of battery replacement 5 1 Care and Daily Inspection How to care for the UPS 1 Turn off the UPS after turning off the connection device and remove the dust adhering to the vent hole and cooling fan of the UPS with a cleaner etc 2 Wipe the surface of the UPS with a dry and soft cloth Daily inspection Confirm that the dust is not adhering to the vent hole and the cooling fan B When the dust is adhering Refer to How to care for the UPS Confirm that the surface of UPS and the electric cables are not heating unusually ES When they are heating Confirm the state and contact an agent from which you purchased the UPS or a maintenance company Confirm that a loud abnormal sound or a nasty smell is not occurring during the operation of the UPS ES When abnormalities have occurred Confirm the state and contact an agent from which you purchased the UPS or a maintenance company 23 5 Inspection 5 2 Caution and Measures for the Rolling Blackouts Important When using a g
12. is stopping Slow with an input The UPS will return to the normal blink power operation No 1 by pressing the ti supply RUN STOP switch for AT approximately 1 second 31 6 Troubleshooting 32 No LED RUN green ALARM orange Lighting O OVER LOAD orange BYPASS orange Lighting o BATTERY CONDITION green orange Warning beep a Operational status Bypass operation due to UPS failure Remarks The UPS became the failure state and switched to the bypass operation Evacuate important connection device from the UPS In this state even if an input power failure occurs the battery operation cannot be performed Confirm ambient temperature and ventilation and press the RESET switch on the front of the UPS for approximately 3 seconds after approximately 10 minutes have passed If there is no problem the UPS will return to the normal operation No 1 If the ALARM LED does not go out or lights up again even if the above operation is performed contact an agent from which you purchased the UPS or a maintenance company Lighting O Indication of the amount of battery charge green 3 Abnormality in cooling fan Abnormalities have occurred in the cooling fan If this state continues for approximately 2 minutes or the inside temperature of the UPS rises the UPS will become the failure state of No 4 b Slow blink
13. status Remarks green orange orange orange green orange 9 Q Q Lighting b Q 1 Output During the bypass operation the G Slow overload capacity of the connection device blink during the exceeds the rated value Reduce the gij bypass capacity of the connection device to AN operation less than the rated value of the UPS In this state even if pressing the bypass switch pressing the RESET switch and the BATT CHECK switch for approximately 3 seconds simultaneously the UPS will not return to the normal operation No 1 10 Lighting Q Lighting Q Indication of 1 Output During the battery operation the O 9 the amount overload capacity of the connection device of battery during the exceeds the rated value Reduce the charge battery capacity of the connection device to green operation less than the rated value of the UPS If this state continues for 100 seconds the UPS will stop Evacuate important connection device from the UPS 11 Lighting Q Q Q Indication of 2 Battery Since the abnormalities occurred at O the amount operation an input power supply the UPS of battery started to supply the electric power charge to the connection device from the green battery It is not necessary to deal with it especially If an input power supply returns the UPS will return to the normal operation No 1 automatically 12 Lighting Q Q Q Indication of 1 Battery The battery voltage dropped since O the amount voltage drop
14. supply Ml Donot dispose of batteries in a fire The batteries may explode Mi Do not open or mutilate batteries Released electrolyte is harmful to the skin and eyes It may be toxic 8 Appendix M A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when working on batter ies a Removewatches rings or other metal objects b Use tools with insulated handles Wear rubber gloves and boots Donot lay tools or metal parts on top of batteries Disconnect charging source prior to connecting or disconnection battery terminals Determine if battery is inadvertently grounded If inadvertently grounded remove source from ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit oan gt gt 46
15. to charge the battery For details refer to Chapter 5 3 Inspecting the Battery Battery Check Even if the UPS is not used the battery is discharged by itself inside the UPS If the UPS is left two months or more there is a possibility that the UPS get unusable since the battery becomes an over discharge state 40 8 1 Appendix Rated Specification M UPSO50AD1C M UPSO50AD1B AC output Rating capacity 5000VA 4000W Voltage 100 105 110 115 120V 2 Frequency 50 60Hz automatic changeover inside the UPS Frequency At the normal operation Depend on input frequency accuracy At the battery operation Within 0 1 Number of phase Single phase two wire with a ground terminal Load condition Linear load or rectified load with a crest factor of up to three times Voltage waveform distortion factor At the resistance load 4 or less At the rectified load 6 or less Overcurrent Effective value 100 or more protection Peak value 300 or more of rated effective value bearing the load of the crest factor of three Grounding Un grounding system Straightforward Thyristor system bypass circuit changeover time without instantaneous power interruption Changeover is impossible at the time of a power failure and overload AC input Voltage 1 85 to 138V Frequency 50 60Hz 5 Number of phase Single phase two wire with a ground terminal
16. Confirm that the voltage which was set by the voltage setup switch is within the input voltage range of the connection device There is the fear of damaging the connection device Do not operate the voltage setup switch during operation of the UPS There is the fear of damaging the connection device And even if operating the switch during operation of the UPS the output voltage cannot be changed Replace the battery periodically If continuing to use the battery that reached the end of battery life there is the fear of the leak of battery and a smoke For the replacement battery use the battery specified by our company and the new battery If using the battery other than the specified battery or using a new battery and an old battery in mixture it becomes the cause of failure and trouble When performing the rolling blackouts or when turning off the input breaker of the back of the UPS confirm that the RUN LED green is blinking slowly in the cycles of approximately 1 6 sec When the RUN LED is lighting up if turning off the breaker of distribution board or the input breaker of the back of the UPS the internal battery will be discharged because it will become the same condition as a power failure There is the fear of the battery damage or the shortening of battery replacement cycle A warning label is affixed to the UPS e Never remove the label e This warning label is directed to the UPS users vi Cau
17. FO USER S MANUAL Uninterruptible Power Supply GX 100 Series 5kVA Model M UPSO50AD1C M UPS050AD1B Fuji Electric Co Ltd For Safe Use e Handling of this manual This manual describes important information for using this product safely Please read this manual carefully before using this product Use this product after reading and understanding especially Caution about Safety and Caution for Use in this manual well Furthermore this manual should be retained for future reference High safety Uses This product is designed and manufactured for the general uses such as a general office use and a personal use and it is not designed and not manufactured for uses hereinafter called high safety uses that require a high degree of safety and are hazardous to human life and body if the required safety is not maintained such as atomic nuclear command aircraft flight control air traffic control mass transport control life supporting system and weapon control etc Do not use this product without carrying out measures to ensure the required safety for high safety uses If using this product for high safety uses consult with our sales representatives Prevention of Radio Disturbance Important This product is class A information technology equipment based on the standard of Voluntary Control Council for Interference by Information Technology Equipment VCCI Using this product in a residential area may cause radio
18. Operation Mode of the UPS e Atthe normal operation While the UPS is operating normally the UPS operates an AC power supply as an input and supplies the output of constant voltage to connection device Simultaneously the UPS charges an internal battery and prepares for the battery operation Output frequency is synchronized with input frequency UPS l DO AC AC converter Slama Boost chopper Power is fed Power is not fed Output Input power source To connection device Flow of electrici ring normal ration e Atthe battery operation In the event of an input power failure When the voltage or the frequency of an AC input power source is abnormal the UPS starts the electric discharge from the battery and continues to supply the stable electric power to the connection device In addition the changeover to the battery operation is performed without instantaneous interruption If the input power source returns the UPS will return to the above normal operation automatically UPS Power is fed DIES Power is not fed The abnorrrelities occur at an inp power source Output To connection device While the UPS is operating The abnormalities of voltage The abnormalities of frequency etc Flow of electrici rin r ration 2 2 Operation Mode of the UPS At the bypass operation In the event of the abnormalities inside the UPS When the abnormalities occur
19. Recommended environment Temperature 15 to 25 degrees C Humidity 30 to 70 no condensation 3 Installation O Determining the installation method A Caution This UPS can be installed laying down If installing laying the UPS down tilt it only to the right side seeing from the front Never tilt the UPS to the left side There is fear of a fire or the UPS failure owing to a leak of battery Ey ES This UPS can be put in a 19 inch rack using the optional rack mount attachment kit 3 1 Installing the UPS O Installation method N Caution The UPS is heavy Pay enough attention to handling the UPS Take out the UPS in a level and flat place Pay enough attention to prevent an accident such as an overturn or a drop The weight of the UPS is as follows e M UPSOSOADIC 84kg without battery 48kg e M UPSOSOADIB 78kg without battery 42kg When using the bracket standard attachment to fasten the UPS to the floor first fasten the bracket to the UPS and fasten the bracket to the floor This bracket is for preventing an overturn of the UPS M UPSOSOAD1C b e TE q el2 246 267 9 185 247 9 a a M UPS050AD1B
20. S is outputted to the connection device as the output voltage as it is If applying the voltage that exceeds the rated voltage range of the connection device the connection device may be damaged Do not apply the single line grounding at the output side It is not insulated between the input and output of the UPS Therefore do not apply the single line grounding at the output side There is the fear of causing the trouble by the noise or the failure When connecting the UPS to a three phase power supply system be sure to connect the grounding phase of the three phase power supply system to the electrode of a grounding side of the AC input of the UPS If connecting the UPS to an ungrounded power source there is the fear of causing the mal function When using a generator temporarily during the rolling blackouts use a generator satisfying the following specification If connecting a generator not satisfying the following specification to the input part of the UPS there is the fear of causing the malfunction or damage of the UPS e Voltage variation 85 to 138 VAC e Frequency variation within 5 of the rated frequency 1Hz sec e Voltage waveform distortion within 5 e Voltage zero cross condition Zero cross must not occur more than twice per cycle vii 1 1 o o 2 1 N eeen 2 2 05100100010 L EOE 001 0 002 5 1 o o viii Caution about Safety CAUTION tor Us ooo lancia E Noain Usa Nit vi Index
21. TTERY CONDITION LED orange blinks E A buzzer sounds 5 3 Inspecting the Battery Battery Check 3 Asa result of the battery check the UPS will be in the following state B Ifthe battery is fully charged LO The RUN LED green on the front of the UPS lights up and the UPS returns to the normal operation blinks The BATTERY CONDITION LED orange E If the battery is not fully charged A warning beep sounds and the BATTERY CONDITION LED orange on the front of the UPS blinks Proceed to Procedure 4 Pip pip pip pip O O continuous sound 27 5 28 Inspection O Charging the battery 4 Put out the BATTERY CONDITION LED orange by pressing the RESET switch on the front of the UPS for approximately 3 seconds and operate the UPS 12 hours or more to charge the battery A When pressing the RESET switch once the BATTERY CONDITION LED orange on the front of the UPS goes out and is switched to the indication green of the amount of battery charge Press the RESET switch Remarks In this state even if a power failure occurs the battery operation may not be performed 5 Return to Procedure 2 and perform the battery check again manually ES When the UPS will be in the state of Procedure 3 If the battery is not fully charged again The battery is out of order end of batter
22. according to the use environment replace the cooling fan early 38 7 2 Replacing the Cooling Fan The method of cooling fan replacement Caution Electric shock Put neither a stick nor a finger into the cooling fan or Injury the vent hole There is fear of an electric shock or an injury Electric shock Only maintenance personnel must perform the cooling fan replacement There is fear of an electric shock The cooling fan of this UPS can be replaced hot swap without turning off the UPS and connection device Note For details consult with an agent from which you purchased the UPS or a maintenance company Note The hot swap should be performed in a short time The UPS starts the bypass operation if the temperature inside the UPS rises out of the rated specification In the state of the bypass operation even if the abnormalities such as a power failure occur at an input power supply the battery operation cannot be performed Use the following cooling fan For the method of purchasing the cooling fan consult with an agent from which you purchased the UPS or a maintenance company Cooling fan type for replacement Fan for M UPSOSOADIB RRAF R1IX 2 RRAF GX12X 2 39 7 Maintenance 7 3 When Not Using the UPS Storage Work before storage Important Do not store the UPS in the following places In an outdoor location A place exposed to the elements An extremely humid place and a dusty place A pl
23. ace with corrosive gas or salinity A place subjected to direct sunlight A place near sparks or heating element An extremely hot or cold place or place where the temperature fluctuates greatly A place where vibration and a shock are added 1 Perform the battery check using the manual battery check function after operating the UPS 12 hours or more to charge the battery For details refer to Chapter 5 3 Inspecting the Battery Battery Check The period that can store the battery used for this UPS is approximately 2 months from the state charged fully 2 Turn off the UPS after turning off the connection device and turn off the input breaker on the back of the UPS Remove all of the connections of input and output terminal For details refer to Chapter 4 2 Turning off the UPS 3 Put the UPS in a box the box etc which was packing the UPS and store it J If a storage period exceeds two months Important If the UPS is not used for a long time charge the battery every two months Charge the battery by operating the UPS 12 hours or more every two months and after charging the battery perform the battery check If the UPS is left without operating for a long time there is a possibility that the UPS get unusable since the battery becomes an over discharge state due to self discharge Perform the battery check using the manual battery check function after operating the UPS 12 hours or more every two months
24. and the vent hole and not use the UPS in a stuffy place The cooling fan and the vent hole are equipped in order to cool the inside of the UPS There is fear that the inside and ambient temperature of the UPS get out of the rated specification Replace the cooling fan periodically If continuing to use the fan that reached the end of fan life there is fear that the inside temperature of the UPS gets out of the rated specification Do not use 5to 9 of the voltage setup switch The UPS will become unable to start up normally Caution for Use The allowable voltage between the input electric cable of the UPS and the ground is 230 VAC If applying the voltage of more than 230 VAC the filter circuit of the input part may be damaged The input surge voltage capacity of the UPS is 5kV peak 1 2 x 50us However if the model of the UPS is UC it is 2kV peak 1 2 x 50us If applying the surge voltage of more than 5kV peak 2kV peak in case of UC the filter circuit of the input part may be damaged The input voltage of the UPS is 85 to 138 VAC When input voltage is different from the rated specification 200 VAC etc install a transformer at the outside of the UPS to convert voltage If applying the voltage that exceeds the input voltage range the UPS may be damaged The input voltage of the UPS should be within the rated input voltage range of the connection device During the bypass operation the input voltage of the UP
25. bration and a shock are added Do not use the UPS in a residential area or its adjacent area This UPS is class A information technology equipment based on the standard of Voluntary Control Council for Interference by Information Technology Equipment VCCI Using this UPS in a residential area may cause radio interference In this case the user may be requested to take an appropriate measure Do not block the vent hole and cooling fan or use the UPS in a stuffy place The vent hole and cooling fan are equipped in order to cool the inside of the UPS There is a possibility that the inside and ambient temperature of the UPS may get out of the rated specification 3 1 Installing the UPS The following spaces are required for an installation location e The UPS takes in air through the vent hole on the front of the UPS and exhausts air through the cooling fan on the back of the UPS Therefore the space of 10cm or more is required in the front and rear of the UPS Front side Rear side 10cm 10cm or more or more Right side ES When performing maintenance of the UPS The space of approximately 1m is required in the front and rear of the UPS Space for Space for battery maintenance maintenance 1m or more 1m or more 0 0 3 3 no no E 3 o 0 iL oc Right side Confirm the environment of the installation location The recommended environment in consideration of the battery life etc is as follows Item
26. e 15 Lighting Q Q Q Lighting 1 End of The recommendation time of battery O orange battery life replacement has come Since it is O necessary to replace the battery contact an agent from which you purchased the UPS or a maintenance company Although the alarm indication and warning beep can be stopped by pressing the RESET switch for 3 seconds the alarm warning beep is issued again 24 hours later or at the restart When only the warning beep is stopped by pressing the RESET switch 1 second or more the alarm warning beep of the end of battery life will be issued again at the automatic battery check which is performed every two weeks 16 b a o Q Q 1 Setting error A setup of the switch of voltage Slow Fast of rated setting on the back of the UPS is blink blink output wrong Use 0 to 4 of the switch of iy Ll voltage voltage setting For details on a AN PON setup refer to Chapter 3 4 Setting up the Output Voltage 17 b Q Q Q b Waiting for a The output of the UPS has stopped Slow Slow blink restart by setup of the RS 232C blink orange communication using the connector sl si for RS 232C on the back of the UPS AN PR After a time specified at the setup SS 2S passes the UPS will be started up automatically and return to the normal operation No 1 Also the UPS can be started up with the RUN STOP switch Maintenance Replacing the Battery of the battery replaceme
27. e amount of battery charge according to the sort of lighting as follows Not lighting 0to50 The battery is not fully charged Even ifa power failure occurs the UPS may not be able to back up Vly Be as 2 AX Blinking eee 50 to 80 The battery is charged to some extent However an adequate backup time cannot be assured S Lighting 80 to 100 The battery is fully charged There is backup time at full LED No BATTERY Warning Operational RUN ALARM OVER BYPASS CONDITION beep status Remarks green orange orange orange green orange 1 Lighting Q Q Q Indication of Normal The UPS is operating normally the amount operation of battery charge green 2 Q Q Q Q Q Stopping The output of the UPS is stopping If withoutan an input power supply returns the input power UPS will become the stopping supply No 3 If the UPS does not become the stopping No 3 even if an input power supply returns check whether or not the input breaker has tripped If the breaker has tripped reset it Nevertheless if the UPS does not become the stopping No 3 contact an agent from which you purchased the UPS or a maintenance company When the UPS stopped since the input power failure had continued and electric discharge of a battery had been completed the UPS will return to the normal operation No 1 automatically if an input power supply returns 3 b Q Q Q Q Stopping The output of the UPS
28. ed 8 Appendix Rated specification and the additional description for UL type products are described Depending on the purpose to use the chapters which should be especially referred to are as follows e For installation personnel Caution about Safety Caution for Use Chapters 1 2 3 and 4 e For users Caution about Safety Caution for Use Chapters 2 4 5 and 6 e For maintenance personnel Caution about Safety Caution for Use Chapters 2 4 5 and 7 Introduction Warning indication In this manual the following warning indications are described so that user or the people around the UPS do not suffer damage to the body and property Warning Z Caution Important Warning indicates that death or serious injury may result if the UPS is not used correctly Caution indicates that slight or moderate injury may result or that the UPS or user s property may be damaged if the UPS is not used correctly Important indicates precautions for use of the UPS Symbols in this manual Symbols in this manual have the following meanings O E The state of the UPS is described Have a look if necessary How to deal with the reference place etc are described Attention e Information in this manual is subject to change without notice Caution about Safety e List of important warnings The important warnings described in this manual are as follows AN War nin g
29. eep by the following lists and deal with the trouble in accordance with the remarks in the Operation mode list e Types of blink of LED The symbols correspond to the symbols in the Operation mode list Symbol Fast blink a in the cycles of approximately 0 4 sec Blink pattern ON OFF gt Appr oxi nat el y 0 4 sec Slow blink b in the cycles of approximately 1 6 sec ON OFF 2 Approxi nat el y 1 6 sec e Types of the warning beep The symbols correspond to the symbols in the Operation mode list Warning beep Symbol a Pip pip pip pipO O 0 continuous sound ON OFF k Appr oxi matel y 0 2 sec Pip pip pip pip a stop for approximately 2 sec ON OFF 2 ESAE Bien bed 2 Pip pip pip pip gt Appr oxi natel y 0 2 sec Approxi matel y four times every k gt 3 sec approximately 3 sec Pi 3 continuance ON continuously Pi a stop for 4 approximately 4 sec Pi ON OFF ON Approxi natel y 1 sec I lt gt lt Approxi natel y 5 sec gt 6 2 Operation Mode List e Operation mode list are a SL ieee e Symbols of LED Lighting Not lighting eese Blinking e The BATTERY CONDITION LED green indicates th
30. enerator temporarily during the rolling blackouts use a generator satisfying the following specification If connecting a generator not satisfying the following specification to the input part of the UPS there is a possibility of becoming the cause of the malfunction or damage of the UPS Voltage variation 85 to 138 VAC Frequency variation within rated frequency 5 1Hz sec Voltage waveform distortion within 5 Voltage zero cross condition Zero cross must not occur twice or more in 1 cycle e Operation before the rolling blackouts Turn off the connection device and the UPS before performing the rolling blackouts Note 1 Turn off the connection device 2 Press the RUN STOP switch on the front of the UPS for approximately 1 second The buzzer will sound if the switch is received 3 An output stops The RUN LED green on the front of the UPS blinks slowly in the cycles of approximately 1 6 sec If the rolling blackouts are performed without turning off the UPS the UPS will be in the same state as an ordinary power failure Electric power is supplied to the connection device from the internal battery of the UPS until the rolling blackouts are completed Electric power is not supplied to the connection device until an input power supply returns after the electric discharge is completed Note The rolling blackouts mean the blackouts to which the date and hour such as the safety inspection of electricity i
31. eration after the rolling blackouts Inspecting the Battery Battery Check oooooncccccinnnicccinnncccccccnnacnnnnos 25 Confirming the state of the UPS Using the manual check function Charging the battery Troubleshooting 1 Ifa Warning Beep SoundS ccccconocccccnnnoccccnnnoncncnnnnnnnncnnnnnnnnnnnnnnnnnnnnnnnas 29 2 Operation Mode Listir ios i 30 e Types of blink of LED e Types of the warning beep e Operation mode list Maintenance 7 1 Replacing the Battery oooooooccccnnonicicicnnnnccccnnnnccnconnnnnnncnnnnnannrnnnnnnennnnnnas 35 e Timing of the battery replacement e The method of battery replacement e Disposal and storage of battery 2 Replacing the Cooling Fan ooooocccononnnccccnnonccccnnnnncccennnnnnncrnnnnnnennnane 38 e Timing of the cooling fan replacement The method of cooling fan replacement 3 When Not Using the UPS Storage ccoooccoconnoccccnnonoccccnnncccnnnnnnnannos 40 e Work before storage e lfastorage period exceeds two months Appendix 8 1 Rated Specification orita 41 8 2 Additional Description for UL TYp6 coooooccccconnccccnnnnocccnnnnnnnnnnnnnnnnnnnnn 43 Unpacking 1 1 Opening the Packing e Opening the packin A Caution This UPS is a heavy load Pay adequate attention to handling of the UPS Take out the UPS in the level and flat place Pay adequate attention so that an accident such as an overturn or a drop will not occur The mass of the UPS is as follows e M UPSOSOADIC 84kg with
32. he switch for performing the operation and stop of the UPS 6 RUN STOP The operation and stop are switched each time one presses the switch for approximately 1 second Press this switch when stopping the warning beep Also if 7 RESET pressing the switch for approximately 3 seconds after restoring the ro failure the ALARM LED goes out 2 It is the switch for performing the battery check manually By 8 BATT CHECK pressing the switch for approximately 2 seconds the battery check is performed If switching to the bypass operation forcibly manually while the UPS is operating normally press the switches 7 and 8 BYPASS simultaneously for approximately 3 seconds When pressing the switches simultaneously for approximately 3 seconds again the UPS returns to the normal operation 9 Vent hole It ventilates the inside of the UPS The direction of air is intake 10 Cooling fan It cools the inside of the UPS The direction of air is exhaust 11 Input terminal block Connect the UPS to an input power source 12 Input breaker It is the breaker for protecting the input circuit 13 Output terminal block Connect the UPS to an output system 14 Ground terminal Connect a grounding wire 15 Voltage setup switch Set the output voltage 16 Interface slot Mount various interface cards 17 Contact signal CN 1 It outputs a no voltage contact signal 18 RS 232C CN2 It is a RS 232C interface 2 Overview 2 2
33. heck other than the automatic check Important Do not perform the battery check in succession When the battery check is performed the internal battery is actually discharged and the voltage is checked If the battery check is performed in succession there is fear of the battery damage or a shortening of a cycle of battery replacement e Confirming the state of the UPS 1 Confirm that the UPS is operating normally Confirm that the RUN LED green is lighting 0O ES When the UPS is in a stop state all LEDs on the front of the UPS are going out Turn on the UPS and proceed to Procedure 2 For details refer to Chapter 4 1 Turning on the UPS ES When the normal operation cannot be confirmed in states other than a stop Proceed to Procedure 2 after dealing with the trouble with reference to Chapter 6 Troubleshooting ey O e 2 W 2 ir o SA e dr amp Cy 25 5 Inspection 2 Using the manual check function Press the BATT CHECK switch on the front of the UPS for approximately 2 seconds Press the BATT CHECK switch for approximately 2 seconds A buzzer sounds and the BATTERY CONDITION LED orange blinks in the cycles of approximately 1 6 sec A buzzer sounds again approximately 5 seconds later and the battery check is completed 26 A buzzer sounds The BA
34. input voltage of the UPS is outputted to the connection device directly If the voltage more than the range of the rated input voltage of the connection device is applied the connection device may be damaged Do not apply single line grounding on the output side Between the input and output of the UPS is not insulated Therefore do not apply single line grounding on the output side There is a possibility of becoming the cause of the trouble by noise or the failure 10 3 2 Connecting the Cable Preparation before connecting the cable Important When connecting the UPS to a three phase power supply system be sure to connect the grounding phase of the three phase power supply system to the electrode of a grounding side of the AC input of the UPS If connecting to an un grounding power supply there is a possibility of becoming the cause of the malfunction When using a generator temporarily during the rolling blackouts use a generator satisfying the following specification If connecting a generator not satisfying the following specification to the input part of the UPS there is a possibility of becoming the cause of the malfunction or damage of the UPS Voltage variation 85 to 138 VAC Frequency variation within rated frequency 5 1Hz sec Voltage waveform distortion within 5 Voltage zero cross condition Zero cross must not occur twice or more in 1 cycle 1 Confirm the input power supply The input power
35. inside the UPS an output switching circuit switches to a bypass circuit and continues to supply electric power through the bypass circuit to the connection device In addition changeover between circuits can switch without instantaneous interruption It is also the same as when switching to the bypass operation manually with the switch on the front of the UPS At the bypass operation electric power is not supplied battery operation from the battery to the connection device Power is fed gt Power is not fed Output To connection device Input power supply The abnorrrelities inside the UPS Manual changeover to the bypass Operation Electricity flow durin ration Installation 3 1 Installing the UPS e Caution about installation A Caution Do not ride on or put an object on the UPS There is fear of an injury or an overturn Do not put an object CRT display or floppy disk etc vulnerable to magnetism around the UPS There is fear of exerting a bad influence on the object 0 Determining an installation location Important Do not install the UPS in the following places In an outdoor location A place exposed to the elements An extremely humid place and a dusty place A place with corrosive gas or salinity A place subjected to direct sunlight A place near sparks or heating element An extremely hot or cold place or place where the temperature fluctuates greatly A place where vi
36. lectric shock Caution about Safety Injury Do not ride on the UPS and not put the objects on top of the UPS There is the fear of an injury or an overturn Injury Damage This UPS is a heavy load Pay adequate attention to handling of the UPS Take out the UPS in the level and flat place Pay adequate attention so that an accident such as an overturn or a drop will not occur The mass of the UPS is as follows e M UPSOSOADIC 84kg without batteries 48kg e M UPSOSOADIB 78kg without batteries 42kg Fire Damage This UPS can be also installed transversely If installing the UPS transversely install it in the direction that took down the UPS to the right side as viewed from the front Never install it in the direction that took down the UPS to the left side There is the fear of a fire or the UPS failure by the leak of battery E Ps Caution about Safety Damage Warning label Do not use the UPS for the uses that may damage the human body or exert an important influence on the society and public e The medical equipment which has an influence on the human life directly e The equipment that may damage the human body e The socially and publicly important computer system Do not put the objects CRT display or floppy disk etc that are vulnerable to magnetism around the UPS There is the fear of having a bad influence on the objects
37. minal M6 Connecting the input and output cable Remove the terminal block cover on the back of the UPS and connect the AC output cable to the output terminal block And confirm that the ground of an input side is connected Finally connect the AC input cable to the input terminal block Connect with Input power supply and output system 3 3 Interface Port 3 3 Interface Port The interface port D sub 9 pins is mounted on the back of the UPS and can take out the following signals Use as necessary O CN1 No voltage contact signal interface D sub 9 pins male 3nmscrew Name of signal UPS failure signal Content It is the no voltage contact signal which operates when the abnormalities occur inside the UPS when the abnormalities occur in the battery or when the recommendation time of battery replacement comes Input power supply abnormal signal It is the no voltage contact signal which is outputted when the abnormalities such as the power failure occur at an input power supply In the power failure for 1 5 seconds or less it does not operate Pin Classification No of signal 1 4 Open at operation 1 6 Close at operation 2 5 Open at operation 2 7 Close at operation 3 9 Open at operation 3 8 Close at operation Battery voltage drop signal It is the no voltage contact signal which is outputted approximatel
38. nking 50 to 80 O Notlighting 0 to 50 18 4 1 Turning on the UPS 4 The battery check is performed automatically The BATTERY CONDITION LED orange on the front of the UPS blinks in the cycles of approximately 1 6 sec 5 The battery check is performed for approximately 5 seconds Then if the battery is normal the BATTERY CONDITION LED green on the front of the UPS indicates the amount of battery charge again and the UPS returns to the normal operation ES If the normal operation is not started Refer to Chapter 6 Troubleshooting e Turning on the connection device 6 Turn on the connection device if the normal operation is started 19 4 Running 20 4 2 Turning off the UPS Also when the rolling blackouts are performed be sure to perform the following operation For details refer to Chapter 5 2 Caution and Measures for the Rolling Blackouts N Caution Damage When turning off the input breaker on the back of the UPS confirm that the RUN LED green is blinking slowly in the cycles of approximately 1 6 sec If the breaker of the distribution board is turned off or the input breaker on the back of the UPS is turned off without turning off the UPS the internal battery will be discharged since it will be in the same state as a power failure There is fear of the battery damage or a shortening of a cycle of battery replacement e Turning off the connecti
39. nt Caution Damage Replace the battery periodically If continuing to use the UPS that the battery life ended there is fear of a leak of battery and a smoke In the following cases it is the end of battery life Replace the battery When the BATTERY CONDITION LED orange on the front of the UPS lights up and a warning beep sounds Pip pip pip pipD O O continuous sound The BATTERY CONDITION LED orange lights up When the backup time of the battery has been lowered to 3 minutes or less at the rated load Battery life is influenced greatly by ambient temperature and the conditions of connection device If using the UPS in the standard environment and conditions an ambient temperature of 25 degrees C and the rated load replace the battery in approximately 3 years g 8 oO gt 5 E 4 E 3 T a g gt 1 3 E 0 25 30 35 40 Ambient temperature of the UPS C Relation between the ambient temperatur nd the cycle of battery replacemen 35 7 Maintenance UPS model M UPS050 ADIC M UPS050 ADIB 36 The method of battery replacement N Caution Electric shock Only maintenance personnel replacement There is fear of an electric shock Damage new one If using the un specified battery or mixing an old battery and a new battery it becomes the cause of failure and trouble of the UPS Important m
40. o prevent a short circuit e This UPS uses the small sealed lead storage battery The small sealed lead storage battery uses expensive and rare resources However these precious resources are able to recycle Cooperate in recycling without disposing of the used battery If you have any questions consult with an agent from which you purchased the UPS or a maintenance company AY amp This mark is the recycle mark of small sealed lead storage battery Pb 37 7 Maintenance 7 2 Replacing the Cooling Fan 0 Timing of the cooling fan replacement Important Replace the cooling fan periodically If continuing to use the UPS that the fan life ended there is a possibility that the inside temperature of the UPS may get out of the rated specification In the following cases it is the end of cooling fan life Replace the cooling fan e When the ALARM LED orange and the BYPASS LED orange light up after a warning beep sounded for 120 seconds Pip pip pip pip0 O O continuous sound The ALARM LED orange lights up Pi continuance The BYPASS LED orange lights up e At the second battery replacement at an ambient temperature of 25 degrees C and approx 6th year in cases of the rated load It is necessary to replace the cooling fan with new one periodically since the cooling fan has a life by wear of the bearing However since the life of cooling fan may become short
41. on device 1 Turn off the connection device e Turning off the UPS 2 Press the RUN STOP switch on the front of the UPS for approximately 1 second The buzzer will sound if the switch is received Press the RUN STOP switch for approximately 1 second 4 2 Turning off the UPS 3 An output stops The RUN LED green on the front of the UPS blinks slowly in the cycles of approximately 1 6 sec ES If an output does not stop normally Refer to Chapter 6 Troubleshooting 4 Turn off the input breaker on the back of the UPS 21 22 5 1 Inspection Care and Daily Inspection In order to use the UPS safely over the long term perform the following care and daily inspection regularly ZN Warning Electric shock Do not remove the cover of the UPS Since there are some portions with high voltage in the inside of the UPS there is fear of an electric shock A Caution Electric shock When inspecting or maintaining the connection device a device getting connected to the UPS or the UPS turn off the connection device and the UPS And turn off the input breaker on the back of the UPS and cut off connection with AC input terminal R S There is fear of an electric shock Only maintenance personnel must perform the maintenance other than daily inspection such as the replacement of battery and cooling fan There is fear of an electric shock When turning off the
42. out batteries 48kg e M UPSOSOADIB 78kg without batteries 42kg 1 Open the packing box and take out the UPS e Confirming the contents of the packing 2 Confirm that there is no damage to the appearance of the UPS 3 Confirm that all accessories are contained UPS model No of pes M UPSOSOADIC User s manual this document 1 copy M UPSOSOADI1B Guarantee this document Bracket with 6 fixing screws 1 set gt Ifthe UPS got damaged or accessories are missing Contact a sales agency that you purchased the UPS 2 Overview 2 1 Name and Main Function of Each Part This chapter describes the name and main function of each part of the UPS 2 1 Name and Main Function of Each Part Name Main function It blinks green when the UPS is connected to an input power 1 RUN source It lights up green while the UPS is operating normally 2 ALARM a up orange when the abnormalities occurred inside the 3 a OVER LOAD It lights up orange when the load capacity of the connection m device exceeded the rated specification 4 BYPASS It lights up orange while the UPS is performing the bypass operation When the battery is normal it indicates the amount of battery 5 BATTERY charge according to the type lights out blinking or lighting of CONDITION lighting green When the battery is abnormal it lights up orange It is t
43. r Cloosed loop terminal is shown in Tablel and Table2 made by J apan Solderless Terminal If can not get these terminals use the similer terminal Use 75 C Copper conductors Wire size and tightening torque are shown in Tablel and Tablez Circuit diagrams are shown by figure 1 UPS must be set up with flexible conduit Table 1 Input rating wire size torque external input circuit breaker size 2POLE CIRCUIT INPUT GROUND BREAKER TIGHTENING WIRE Type of TORQUE Vin V lin A SIZE Closed loop NO m A AWG Terminal 100 105 50 47 6 110 115 45 5 43 5 R14 6 120 417 M UPSO50AD1C U M UPSO50AD1B U 43 44 8 Appendix Table 2 Output rating wire size torque external output circuit breaker size OUTPUT AN TIGHTENING WIRE Type of TORQUE Vin V lin A SIZE Closed loop NO m A AWG Terminal M UPSOSOADICU 7707135 4553435 R146 M UPSO50AD1B U 120 417 AC Input Dk Outpminal Block L R Sl O x Dual O 1 U Converter N S O x O n V PE G Boost Chopper Figure 1 Circuit diagram of Models M UPSO50AD1C U or M UPSO50AD1B U 8 2 Additional Description for UL Type Risk of electric shock Do not touch uninsulated battery terminal Risk of electric shock Do not remove the cover
44. s informed beforehand e Operation after the rolling blackouts 1 Confirm that the UPS is connected to an input power supply and the connection device The RUN LED green on the front of the UPS blinks slowly in the cycles of approximately 1 6 sec 2 Press the RUN STOP switch on the front of the UPS for approximately 1 second The buzzer will sound if the switch is received 3 AC voltage is outputted from the output terminal block and the RUN LED green on the front of the UPS lights up 4 Turn on the connection device if the normal operation is started ES For details refer to Chapter 4 1 Turning on the UPS B When a warning beep sounds Refer to Chapter 6 1 If a Warning Beep Sounds 24 5 3 Inspecting the Battery Battery Check 5 3 Inspecting the Battery Battery Check Inspection of the battery is performed using a battery check function There are two kinds of battery check functions an automatic check and a manual check The manual check is not necessary ordinarily since the automatic check is performed while the UPS is operating Automatic check is performed in the following cases e When the operation of UPS is started up e Every two weeks in an operation continuation state e When having switched to the normal operation from the bypass operation Perform manual check in the following cases e When a warning beep sounds due to the abnormalities in a battery e When performing the battery c
45. series Models that should be followed during installation and maintenance of the UPS and batteries Internal battery voltage is 72 V dc Models M UPSO50AD1 U with suffix 0 O B or C This unit intended for installation in a controlled environment and maximum ambient temperature is 25 C temperature controlled indoor area free of conductive contaminants This UPS must be fasten down the floor by L branckets or stabilizer attached UPS when vertical installation This UPS must be fasten down the floor by branckets attached this UPS This UPS is intended for use in J apan domestic Need to provide External Disconnect Overcurrent Protective Device for the AC input and the AC output for example an UL Listed branch circuit breaker with suitable ratings could provide both functions disconnect and overcurrent protection A readily accessible disconnect device shall be incorporated in the building installation wiring Circuit Breaker UL Listed Inverse time Circuit Breaker is not provided on the UPS at input side as shipped This Model must connect Circuit Breakers for use with the UPS The rated tripping current of the Circuit Breaker 2 pole type are shown in Tablel and Tablez2 Field wiring connection must be made by a UL and CSA Listed closed loop terminal connector sized for the wire gauge involved and fully insulated up to terminals Connector must be fixed using the crimp tool specified by the connector manufacture
46. supply which can connect with this UPS is as follows Breaker Input Input Input Number of Ure model capacity capacity voltage frequency phase M UPS OSOADIC PAN 5kVA 85to 138 VAC ape j iia M UPS050 more SE O ote wo wire ADIB Remarks If the input voltage and the frequency are out of this range the UPS may become the following state or be damaged B When the UPS is turned on The UPS will become the input error at startup In this case the UPS cannot be started up BS While the UPS is operating Abnormalities of input voltage is detected and the battery operation is performed If the UPS is connected to an input power supply which gets out of this range frequently by repeating the charge and discharge of the battery the battery will be in an empty state or will become the cause of damage Note The input frequency is automatically chosen according to the area in which the UPS is used 11 3 12 Installation 2 The specifications of the input and output terminal block are as follows Select the crimp type terminal which is suitable for specification UPS side Input and output terminal block Specification tone Connection Figuration marking AC input L R un grounding side N S AC input grounding side 1 U AC output un grounding side n V AC output grounding side PE G Ground protective grounding 5 pole screw ter
47. the UPS lights up 9 Turn on the connection device if the normal operation is started with the rated voltage set up 16 Running 4 1 Turning on the UPS N Caution Damage Confirm that the voltage set up by the switch of voltage setting is within the range of input voltage of the connection device There is fear of damaging the connection device O Confirming cable connection 1 device Confirm that the UPS is connected to an input power supply and the connection Turn on the input breaker on the back of the UPS approximately 1 6 sec The RUN LED green on the front of the UPS blinks slowly in the cycles of gt Y ge A TO S X amp T NS eas 5 LES Ie K ee US If the UPS is not connected Refer to Chapter 3 2 Connecting the Cable 17 4 Running e Turning on the UPS 2 Press the RUN STOP switch on the front of the UPS for approximately 1 second The buzzer will sound if the switch is received Press the RUN STOP switch for approximately 1 second 3 AC voltage is outputted from the output terminal block The RUN LED green on the front of the UPS lights up The BATTERY CONDITION LED green on the front of the UPS indicates the amount of battery charge according to the sort of lighting The RUN LED green lights up The indication green of the amount of battery charge Lighting 80 to 100 ly D Bli
48. tion for Use Be careful about the following when using the UPS Important Important indicates precautions for use of the UPS Do not install and store the UPS in the following places e Inan outdoor location e A place exposed to the elements e An extremely humid place and a dusty place e A place with corrosive gas or salinity e A place subjected to direct sunlight e A place near sparks or heating element e An extremely hot or cold place or place where the temperature fluctuates greatly e A place where vibration and a shock are added Do not perform the battery check in succession When the battery check is performed the internal battery discharges actually and the voltage is checked If the battery check is performed in succession there is the fear of the battery damage or the shortening of battery replacement cycle If the UPS is not used for a long time charge the battery every two months Charge the battery by operating the UPS 12 hours or more every two months and after charging the battery perform the battery check If leaving the UPS unused for a long time the battery becomes an over discharge state due to self discharge and there is fear that the battery becomes impossible to use The disposal of used battery has legal restrictions Request the disposal to industrial waste disposal contractor or consult with a sales agency that you purchased the UPS or the maintenance agency Do not block the cooling fan
49. ust perform the battery Replace the battery with one specified by our company and a The disposal of used battery has legal restrictions Commission industrial waste disposal contractor or consult with an agent from which you purchased the UPS or a maintenance company The battery of this UPS can be replaced hot swap without turning off the UPS and connection device Note For details consult with an agent from which you purchased the UPS or a maintenance company Note The UPS performs the bypass operation during hot swapping In the state of the bypass operation even if the abnormalities such as a power failure occur at an input power supply the battery operation cannot be performed Use the battery shown in the following list For the method of purchasing the battery unit consult with an agent from which you purchased the UPS or a maintenance company Arrangement model Battery for M UPS 050AD1B Type of battery unit RRABU GX14 Number of units Note per UPS 4 units Battery unit Mass a unit Approximately 9kg Note It is necessary to replace the battery by the unit Battery capacity 12V 9Ah x 3 7 1 Replacing the Battery e Disposal and storage of battery e Pay enough attention to disposal and storage of the battery When disposing of the used battery dispose of it separately from a dry cell etc sticking the insulating tape on the terminal of battery t
50. y 2 minutes before at the rated load the end of battery discharge during the battery operation Use the contact output in the range of the voltage and current in the following graph 1 0 0 5 0 2 Contact current A 0 1 0 05 MO Contact rating Contact rating 10 30 60 Contact voltage V 120 200 13 3 14 Installation O CN2 RS 232C interface D sub 9 pins ferrele 4 40 inch screw Pin Classification Name of No of signal signal portent 2 3 Close It is the no voltage contact signal which is at operation Input power outputted when the abnormalities such as supply the power failure occur at an input power abnormal signal supply 1 In the power failure for 1 5 seconds or less it does not operate 1 3 Close Battery voltage It is the no voltage contact signal which is at operation drop signal outputted approximately 2 minutes before i at the rated load the end of battery ED discharge during the battery operation 8 7 AC output stop It is the signal which inputs into the UPS at H signal _ when stopping the AC output of the UPS reception UPS automatic E 1 The stop of the AC output is possible shutdown signal 2 only during the battery operation 2 Input this signal 5 to 25 VDC approximately 0 6 seconds or more 6 7 Serial data Communication system cala input RX Baud rate 2400
51. y life Replace the battery For details refer to Chapter 7 1 Replacing the Battery Troubleshooting 6 1 If a Warning Beep Sounds 1 Confirm the state of LED on the front of the UPS and the type of a warning beep 2 Refer to the Operation mode list and deal with it according to directions If the UPS is not connected to an input power supply connect For details refer to Chapter 3 2 Connecting the Cable ES How to stop a warning beep A warning beep can be stopped by pressing the RESET switch on the front of the UPS for approximately 1 second Note However if a warning beep does not stop even if pressing the RESET switch stop a warning beep by the following procedures For details refer to Chapter 4 2 Turning off the UPS 1 Turn off the connection device 2 Press the RUN STOP switch on the front of the UPS for approximately 1 second 3 An output stops The RUN LED green on the front of the UPS blinks slowly in the cycles of approximately 1 6 sec 4 Turn off the input breaker on the back of the UPS Note In the output overload state even if pressing the RESET switch a warning beep does not stop Reduce the capacity of the connection device to less than the rated value of the UPS 29 6 Troubleshooting 30 6 2 Operation Mode List When it seems that the abnormalities have occurred inside the UPS or the connection device has stopped confirm the LED and a warning b